0.3L2
1.FOOTINGS : 50 mm
2.COLUMN : 40 mm
L2
0.25L2
0.15L2
3.BEAMS : 25 mm
4.SLABS : 20 mm
5.STAIRCASE : 20 mm
0.15L1
0.25L1
5
0.3L1
NOTE: Refer Relavant
Architectural Drawing
4
B1
L1
3
C4 C6
Client Name:Mr.Nirikshit
Project Type:Residential Building
S1 Date:11-Feb-2024
2
B2
1
0.1L1
0.15L1
C8 C7
MUMTY LEVEL SLAB LAYOUT
DESIGN:
Terrace Slab Detailing
AREA STATEMENT:
Plot Area : 1,353 SQ.FT.
D SOIL BEARING CAPACITY
A B C E F G
Foundations have been designed
According to given site soil condition.
Soil Bearing Capacity (SBC) - 200 KN/m.sq.
STEEL REINFORCEMENT
Steel Reinforcement confirming to IS 1786-1985 code,
FE - 500 grade should be used.
M7.5 = 1:4:8 ( USED AS P.C.C. )
M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
CLEAR COVER TO MAIN
B1 B2 REINFORCEMENT:
6 C2 1.FOOTINGS : 50 mm
C1 2.COLUMN : 40 mm
3.BEAMS : 25 mm
0.3L2
4.SLABS : 20 mm
L2
5.STAIRCASE : 20 mm
S1
0.25L2
0.15L2
S2
B3 B4
0.15L1
0.25L1
5 C9 C10
C3
0.3L1
S3 S4
NOTE: Refer Relavant
Architectural Drawing
B5
4 S5
C5
B6 B7 B8
3 C13 C12 Client Name:Mr.Nirikshit
L1
C4 C6
Project Type:Residential Building
Date:11-Feb-2024
S7 S8
2
B12
B9 B10 B11
1 C14 C15
C8 C7
0.1L1
0.15L1
TERRACE SLAB LAYOUT
DESIGN:
First Floor Slab Detailing
AREA STATEMENT:
Plot Area : 1,353 SQ.FT.
SOIL BEARING CAPACITY
D Foundations have been designed
A B C E F G According to given site soil condition.
Soil Bearing Capacity (SBC) - 200 KN/m.sq.
STEEL REINFORCEMENT
Steel Reinforcement confirming to IS 1786-1985 code,
FE - 500 grade should be used.
M7.5 = 1:4:8 ( USED AS P.C.C. )
M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
CLEAR COVER TO MAIN
B1 B2 REINFORCEMENT:
6 C2
1.FOOTINGS : 50 mm
C1 2.COLUMN : 40 mm
3.BEAMS : 25 mm
4.SLABS : 20 mm
5.STAIRCASE : 20 mm
0.3L2
S1
L2
0.25L2
0.15L2
S2
B3 B4
5 C9 C10
0.15L1
C3
0.25L1
NOTE: Refer Relavant
0.3L1
S3 S4 Architectural Drawing
B5
4 S5
C5
B6 B7 B8
3 S6 C13 C12 Client Name:Mr.Nirikshit
C4 C6
Project Type:Residential Building
L1
Date:11-Feb-2024
B9 S8
2
S9
B11
B10 B12 B13
1 C14 C15
C8 C7
0.1L1
0.15L1
FIRST FLOOR SLAB LAYOUT
DESIGN:
Ground Floor Slab Detailing
AREA STATEMENT:
Plot Area : 1,353 SQ.FT.
D SOIL BEARING CAPACITY
A B C E F G Foundations have been designed
According to given site soil condition.
Soil Bearing Capacity (SBC) - 200 KN/m.sq.
STEEL REINFORCEMENT
Steel Reinforcement confirming to IS 1786-1985 code,
FE - 500 grade should be used.
M7.5 = 1:4:8 ( USED AS P.C.C. )
M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
B1 B2 CLEAR COVER TO MAIN
6 C2 C11
REINFORCEMENT:
C1 1.FOOTINGS : 50 mm
2.COLUMN : 40 mm
3.BEAMS : 25 mm
4.SLABS : 20 mm
S1
0.3L2
5.STAIRCASE : 20 mm
L2
0.25L2
0.15L2
(150THK)
B3 B4
5 C9 C10
C3
0.15L1
0.25L1
S3 S4
0.3L1
NOTE: Refer Relavant
Architectural Drawing
B5
4 S5 (150THK) (150THK)
C5
B6(150THK) B7 B8
3 S6 C13 C12
C4 C6
Client Name:Mr.Nirikshit
Project Type:Residential Building
L1
B9
(150THK) S8 Date:11-Feb-2024
2
S9
(150THK)
(150THK) (150 SUNK)
B11
B10 B12 B13
1 C14 C15
C8 C7
0.1L1
0.15L1
GROUND FLOOR SLAB LAYOUT
DESIGN:
BEAM SCHEDULE (M20:Fe500) (LEVEL: MUMTY) Mumty Level Beam Layout & Schedule
SIZE BOTTOM REINFORCEMENT TOP REINFORCEMENT
AREA STATEMENT:
BEAM SHEAR STIRRUPS SFR REMARKS Plot Area : 1,353 SQ.FT.
NUMBERS B D STRAIGHT CURTAILED EXTRA EXTRA STRAIGHT EXTRA EXTRA
SOIL BEARING CAPACITY
LEFT RIGHT LEFT SUPP RIGHT SUPP Foundations have been designed
B1 9" 15" 2-T12 - - - 2-T12 - - 2L-T8@150 C/C - - According to given site soil condition.
Soil Bearing Capacity (SBC) - 200 KN/m.sq.
B2 9" 15" 2-T12 - - - 2-T12 - - 2L-T8@150 C/C - -
STEEL REINFORCEMENT
B3 9" 15" 2-T12 - - - 2-T12 - - 2L-T8@150 C/C - - Steel Reinforcement confirming to IS 1786-1985 code,
B4 9" 15" 2-T12 - - - 2-T12 - - 2L-T8@150 C/C - - FE - 500 grade should be used.
M7.5 = 1:4:8 ( USED AS P.C.C. )
M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
CLEAR COVER TO MAIN
REINFORCEMENT:
D
1.FOOTINGS : 50 mm
A B C E F G
2.COLUMN : 40 mm
3.BEAMS : 25 mm
4.SLABS : 20 mm
5.STAIRCASE : 20 mm
6
NOTE: Refer Relavant
Architectural Drawing
5
4
Client Name:Mr.Nirikshit
Project Type:Residential Building
B1 Date:11-Feb-2024
3
C4 C6
2
B3
B4
B2
1
C8 C7
MUMTY LEVEL BEAM LAYOUT & SCHEDULE
DESIGN:
Mumty Level Beam Elevation
AREA STATEMENT:
Plot Area : 1,353 SQ.FT.
SOIL BEARING CAPACITY
2-T12 2-T12 Foundations have been designed
According to given site soil condition.
Soil Bearing Capacity (SBC) - 200 KN/m.sq.
STEEL REINFORCEMENT
Steel Reinforcement confirming to IS 1786-1985 code,
FE - 500 grade should be used.
2-T12 2-T12 M7.5 = 1:4:8 ( USED AS P.C.C. )
M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
20-2L-T8 20-2L-T8 CLEAR COVER TO MAIN
REINFORCEMENT:
@6"C/C @6" C/C 1.FOOTINGS : 50 mm
2.COLUMN : 40 mm
3.BEAMS : 25 mm
4.SLABS : 20 mm
C4 C6 C8 B2: 9"x15" C7 5.STAIRCASE : 20 mm
B1: 9"x15"
NOTE: Refer Relavant
Architectural Drawing
2-T12 2-T12
Client Name:Mr.Nirikshit
Project Type:Residential Building
Date:11-Feb-2024
2-T12 2-T12
24-2L-T8 24-2L-T8
@6" C/C @6" C/C
C8 B3: 9"x15" C4 C7 B4: 9"x15" C6
MUMTY LEVEL BEAM ELEVATION
DESIGN:
Terrace Level Beam Layout
AREA STATEMENT:
D Plot Area : 1,353 SQ.FT.
A B C E F G SOIL BEARING CAPACITY
Foundations have been designed
According to given site soil condition.
Soil Bearing Capacity (SBC) - 200 KN/m.sq.
STEEL REINFORCEMENT
Steel Reinforcement confirming to IS 1786-1985 code,
FE - 500 grade should be used.
M7.5 = 1:4:8 ( USED AS P.C.C. )
M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
B1 B2 CLEAR COVER TO MAIN
6 C2 REINFORCEMENT:
C1 1.FOOTINGS : 50 mm
2.COLUMN : 40 mm
3.BEAMS : 25 mm
4.SLABS : 20 mm
5.STAIRCASE : 20 mm
B3 B4
5 C9 C10
C3
NOTE: Refer Relavant
Architectural Drawing
B5
4
C5
B6 B7 B8
3 C13 C12
C4 C6 Client Name:Mr.Nirikshit
Project Type:Residential Building
Date:11-Feb-2024
2
B9 B10 B11
1 C14 C15
C8 C7
TERRACE LEVEL BEAM LAYOUT
DESIGN:
Terrace Level Beam Elevation
AREA STATEMENT:
Plot Area : 1,353 SQ.FT.
SOIL BEARING CAPACITY
2-T16
Foundations have been designed
According to given site soil condition.
2-T16
Soil Bearing Capacity (SBC) - 200 KN/m.sq.
22-2L-T8 7-2L-T8 10-2L-T8 2-T16 STEEL REINFORCEMENT
@5" C/C @5" C/C @5" C/C 2-T16 2-T16
Steel Reinforcement confirming to IS 1786-1985 code,
760
C1
B1:9"X15" C2
B2:9"X15" FE - 500 grade should be used.
2-T16
2-T16 2-T16 M7.5 = 1:4:8 ( USED AS P.C.C. )
2-T16 24-2L-T8 9-2L-T8 43-2L-T8 M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
@5" C/C @5" C/C @5" C/C CLEAR COVER TO MAIN
C8 B13:9"X15" C4 B14:9"X15" C5 B15:9"X18" C1
REINFORCEMENT:
2-T16
9-2L-T8 8-2L-T8
13-2L-T8 8-2L-T8 1.FOOTINGS : 50 mm
@5" C/C @5"
@5"
C/C
C/C @5" C/C 2.COLUMN : 40 mm
C3
B3:9"X15" C9
B4:9"X15" C10
2-T16 3.BEAMS : 25 mm
4.SLABS : 20 mm
2-T16 2-T16 5.STAIRCASE : 20 mm
8-2L-T8
12-2L-T8 8-2L-T8
@5"
@5"C/C
C/C @5" C/C
2-T16
34-2L-T8 C7
B16:9"X15" C6
@5" C/C B17
B5:9"X15"
C5
2-T16 3-T16 2-T16
2-T16
2-T16 3-T16 2-T16
2-T16 20-2L-T8 7-2L-T8 29-2L-T8 6-2L-T8
15-2L-T8 7-2L-T8
18-2L-T8 8-2L-T8
13-2L-T8 8-2L-T8 B7
@5" C/C @5" C/C @5" C/C @5" C/C
@5" C/C @5" C/C
@5" C/C @5"
@5"
C/CC/C @5" C/C
B17:9"X15" C3 B18:9"X15" C2
B6:9"X15" B7:9"X15" B8:9"X15"
C4 C6 C13 C12
NOTE: Refer Relavant
2-T16 3-T16 2-T16 Architectural Drawing
2-T16 2-T16
8-2L-T8
14-2L-T8 8-2L-T8 26-2L-T8 30-2L-T8
@5"
@5"
C/CC/C @5" C/C @5" C/C @5" C/C B2
2-T16
20-2L-T8 13-2L-T8 7-2L-T8 20-2L-T8 7-2L-T8 B19:9"X15" B20:9"X15" B21:9"X15"
C14 C13 C9
@5" C/C @5" C/C @5" C/C @5" C/C @5" C/C
B9:9"X15" B10:9"X15" B11:9"X15"
C8 C7 C14 C15 Client Name:Mr.Nirikshit
2-T16 Project Type:Residential Building
Date:11-Feb-2024
2-T16 2-T16
26-2L-T8 8-2L-T8
20-2L-T8
2-T16
@5" C/C @5" C/C
@5" C/C
8-2L-T8 8-2L-T8
8-2L-T8 B22:9"X15" B23:9"X15"
C15 C12 C10
@5" C/C @5" C/C
@5" C/C
C8
B12:9"X15" C7
TERRACE LEVEL BEAM ELEVATION
DESIGN:
BEAM SCHEDULE (M20:Fe500) (LEVEL: TERRACE) Terrace Level Beam Schedule
AREA STATEMENT:
SIZE BOTTOM REINFORCEMENT TOP REINFORCEMENT
Plot Area : 1,353 SQ.FT.
BEAM SHEAR STIRRUPS SFR REMARKS
NUMBERS B D STRAIGHT CURTAILED EXTRA EXTRA STRAIGHT EXTRA EXTRA SOIL BEARING CAPACITY
LEFT RIGHT LEFT SUPP RIGHT SUPP Foundations have been designed
According to given site soil condition.
B1 9" 15" 2-T16 - - - 2-T16 - - 28-2L-T8@5",5",5" C/C - -
Soil Bearing Capacity (SBC) - 200 KN/m.sq.
B2 9" 15" 2-T16 - - - 2-T16 - - 6-2L-T8@5" C/C - CANTILEVERED STEEL REINFORCEMENT
B3 9" 15" 2-T16 - - - 2-T16 - - 5-2L-T8@5" C/C - - Steel Reinforcement confirming to IS 1786-1985 code,
FE - 500 grade should be used.
B4 9" 15" 2-T16 - - - 2-T16 - - 27-2L-T8@5",5",5" C/C - -
M7.5 = 1:4:8 ( USED AS P.C.C. )
B5 9" 15" 2-T16 - - - 2-T16 - - 8-2L-T8@5" C/C - -
M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
B6 9" 15" 2-T16 - - - 2-T16 - - 21-2L-T8@5",5",5" C/C - -
CLEAR COVER TO MAIN
B7 9" 15" 2-T16 - - - 2-T16 - - 7-2L-T8@5" C/C - - REINFORCEMENT:
B8 9" 15" 2-T16 - - - 2-T16 - - 27-2L-T8@5",5",5" C/C - - 1.FOOTINGS : 50 mm
B9 9" 15" 2-T16 - - - 2-T16 - - 7-2L-T8@5" C/C - - 2.COLUMN : 40 mm
B10 9" 15" 2-T16 - - - 2-T16 - - 19-2L-T8@5",5",5" C/C - - 3.BEAMS : 25 mm
B11 9" 15" 2-T16 - - - 2-T16 - - 26-2L-T8@5",5",5" C/C - -
4.SLABS : 20 mm
5.STAIRCASE : 20 mm
B12 9" 15" 2-T16 - - - 2-T16 - - 22-2L-T8@5",5",5" C/C - -
B13 9" 15" 2-T16 - - - 2-T16 - - 7-2L-T8@5" C/C - -
B14 9" 15" 2-T16 - - - 2-T16 - - 5-2L-T8@5" C/C - -
2-T16
B15 9" 18" 2-T16 - - - 2-T16 - - 7-2L-T8@5" C/C - -
2-T16 2-T16 2-T16
B16 9" 15" 2-T16 - - - 2-T16 - - 26-2L-T8@5",5",5" C/C - -
B17 9" 15" 2-T16 1-T16 - - 2-T16 - 1-T16 26-2L-T8@5",5",5" C/C - -
B18 9" 15" 2-T16 - - - 2-T16 1-T16 - 34-2L-T8@5",5",5" C/C - -
B19 9" 15" 2-T16 - - - 2-T16 - - 28-2L-T8@5",5",5" C/C - -
B20 9" 15" 2-T16 - - - 2-T16 - 1-T16 7-2L-T8@5" C/C - -
B21 9" 15" 2-T16 - - - 2-T16 1-T16 - 7-2L-T8@5" C/C - -
B22 9" 15" 2-T16 - - - 2-T16 - - 7-2L-T8@5" C/C - -
B23 9" 15" 2-T16 - - - 2-T16 - - 27-2L-T8@5",5",5" C/C - -
TERRACE LEVEL BEAM SCHEDULE
Client Name:Mr.Nirikshit
Project Type:Residential Building
Date:11-Feb-2024
DESIGN:
D First Floor Level Beam Layout
AREA STATEMENT:
A B C E F G Plot Area : 1,353 SQ.FT.
SOIL BEARING CAPACITY
Foundations have been designed
According to given site soil condition.
Soil Bearing Capacity (SBC) - 200 KN/m.sq.
STEEL REINFORCEMENT
Steel Reinforcement confirming to IS 1786-1985 code,
FE - 500 grade should be used.
B1 B2 M7.5 = 1:4:8 ( USED AS P.C.C. )
6 C2 M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
C1 CLEAR COVER TO MAIN
REINFORCEMENT:
1.FOOTINGS : 50 mm
2.COLUMN : 40 mm
3.BEAMS : 25 mm
4.SLABS : 20 mm
5.STAIRCASE : 20 mm
B3 B4
5 C9 C10
C3
B5 NOTE: Refer Relavant
4 Architectural Drawing
C5
B6 B7 B8
3 C13 C12
C4 C6
Client Name:Mr.Nirikshit
B9
Project Type:Residential Building
2 Date:11-Feb-2024
B10 B12 B13
1 C14 C15
C8 C7
B11
STAIRS MID LANDING BEAM
FIRST FLOOR LEVEL BEAM LAYOUT
DESIGN:
First Floor Beam Elevation
2-T16 3-T16 2-T16
2-T16
2-T16 2-T16
AREA STATEMENT:
Plot Area : 1,353 SQ.FT.
2-T16
SOIL BEARING CAPACITY
2-T16
27-2L-T8 10-2L-T8 2-T16
2-T16
Foundations have been designed
@5"C/C @5"C/C
24-2L-T8 9-2L-T8 According to given site soil condition.
B1:9"X15" B2:9"X15" @5"C/C @5" C/C 43-2L-T8
@5"C/C Soil Bearing Capacity (SBC) - 200 KN/m.sq.
C1 C2 C8 C4 C5 C1
B14:9"X15" B15:9"X15" B16:9"X24" STEEL REINFORCEMENT
Steel Reinforcement confirming to IS 1786-1985 code,
FE - 500 grade should be used.
2-T16
M7.5 = 1:4:8 ( USED AS P.C.C. )
M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
2-T16
3-T16 2-T16 CLEAR COVER TO MAIN
9-2L-T8 25-2L-T8
@5"C/C @5"C/C REINFORCEMENT:
B3:9"X15" B4:9"X15" 2-T16 3-T16 2-T16 1.FOOTINGS : 50 mm
C3 C9 C10
24-2L-T8 2.COLUMN : 40 mm
@5"C/C 3.BEAMS : 25 mm
B17:9"X15"
C7 C6 4.SLABS : 20 mm
2-T16
5.STAIRCASE : 20 mm
2-T16 2-T16
2-T16
2-T16
28-2L-T8 2-T16 2-T16 + 2-T16 2-T16
@5"C/C B18
B5:9"X15"
2-T16+2T16 1-T16 2-T16
C5
30-2L-T8 35-2L-T8
B7 @5" C/C @5" C/C
B18:9"x15" B19:9"x15"
C3 C2
2-T16 3-T16 2-T16 3-T16
2-T16 3-T16 2-T16 3-T16 2-T16
20-2L-T8 18-2L-T8 25-2L-T8 NOTE: Refer Relavant
@5"C/C @5"C/C @5"C/C 2-T16
B6:9"X15" B7:9"X15" B8:9"X15"
2-T16 2-T16 2-T16
Architectural Drawing
C4 C6 C13 C12
2-T16
2-T16
2-T16 21-2L-T8 7-2L-T8 26-2L-T8 30-2L-T8 B2
@5"C/C @5" C/C @5"C/C @5"C/C
C14 C13 C9
2-T16 3-T16 2-T16 B20:9"X15" B21:9"X15" B22:9"X15"
19-2L-T8
B17 @5"C/C B20
Client Name:Mr.Nirikshit
B9:9"X15"
Project Type:Residential Building
Date:11-Feb-2024
2-T16
2-T16 3-T16 2-T16
2-T16
8-2L-T8 8-2L-T8
@5" C/C @5" C/C 2-T16
B10:9"X15" 26-2L-T8 26-2L-T8
C8 C7 @5"C/C @5"C/C
B23:9"X15" B24:9"X15"
C15 C12 C10
2-T16
2-T16
20-2L-T8 21-2L-T8 25-2L-T8
@5"C/C @5" C/C @5"C/C
B11:9"X15" B12:9"X15" B13:9"X15"
C8 C7 C14 C15
FIRST FLOOR LEVEL BEAM ELEVATION
DESIGN:
First Floor Level Beam Schedule
AREA STATEMENT:
BEAM SCHEDULE (M20:Fe500) (LEVEL: FF) Plot Area : 1,353 SQ.FT.
SOIL BEARING CAPACITY
SIZE BOTTOM REINFORCEMENT TOP REINFORCEMENT
BEAM SHEAR STIRRUPS SFR REMARKS Foundations have been designed
NUMBERS B D STRAIGHT CURTAILED EXTRA EXTRA STRAIGHT EXTRA EXTRA According to given site soil condition.
LEFT RIGHT LEFT SUPP RIGHT SUPP Soil Bearing Capacity (SBC) - 200 KN/m.sq.
B1 9" 15" 2-T16 - - - 2-T16 - 1-T16 7-2L-T8@5" C/C - -
STEEL REINFORCEMENT
Steel Reinforcement confirming to IS 1786-1985 code,
B2 9" 15" 2-T16 - - - 2-T16 1-T16 - 6-2L-T8@5" C/C - CANTILEVERED
FE - 500 grade should be used.
B3 9" 15" 2-T16 - - - 2-T16 - - 5-2L-T8@5" C/C - - M7.5 = 1:4:8 ( USED AS P.C.C. )
B4 9" 15" 2-T16 - - - 2-T16 - - 7-2L-T8@5" C/C - - M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
B5 9" 15"
+
2-T16 - - - 2-T16 - - 7-2L-T8@5" C/C - - CLEAR COVER TO MAIN
2-T16 2-T16 2-T16
REINFORCEMENT:
B6 9" 15" 2-T16 - - - 2-T16 - - 7-2L-T8@5" C/C - -
1.FOOTINGS : 50 mm
B7 9" 15" 2-T16 1-T16 - - 2-T16 - 1-T16 7-2L-T8@5" C/C - -
2.COLUMN : 40 mm
B8 9" 15" 2-T16 1-T16 - - 2-T16 1-T16 1-T16 7-2L-T8@5" C/C - -
3.BEAMS : 25 mm
B9 9" 15" 2-T16 1-T16 - - 2-T16 - - 7-2L-T8@5" C/C - - 4.SLABS : 20 mm
B10 9" 15" 2-T16 - - - 2-T16 - - 22-2L-T8@5",5",5" C/C - - 5.STAIRCASE : 20 mm
B11 9" 15" 2-T16 - - - 2-T16 - - 7-2L-T8@5" C/C - -
B12 9" 15" 2-T16 - - - 2-T16 - - 8-2L-T8@5" C/C - -
B13 9" 15" 2-T16 - - - 2-T16 - - 7-2L-T8@5" C/C - -
B14 9" 15" 2-T16 - - - 2-T16 - - 7-2L-T8@5" C/C - -
B15 9" 15" 2-T16 - - - 2-T16 - - 5-2L-T8@5" C/C - -
2-T16
B16 9" 24" 2-T16 - - - 2-T16 - 9-2L-T8@5" C/C - -
2-T16 2-T16 2-T16
B17 9" 15" 2-T16 1-T16 - - 2-T16 1-T16 - 7-2L-T8@5" C/C - -
B18 9" 15" 2-T16 2-T16 2-T16 - 2-T16 7-2L-T8@5" C/C
B19 9" 15" 2-T16 1-T16 2-T16 2-T16 7-2L-T8@5" C/C
B20 9" 15" 2-T16 - - - 2-T16 - - 27-2L-T8@5",5",5" C/C - -
2-T16 2-T16 2-T16
B21 9" 15" 2-T16 - - - 2-T16 - - 7-2L-T8@5" C/C - -
2-T16 2-T16
B22 9" 15" 2-T16 - - - 2-T16 - - 7-2L-T8@5" C/C - -
2-T16
B23 9" 15" 2-T16 - - - 2-T16 - 1-T16 7-2L-T8@5" C/C - -
B24 9" 15" 2-T16 - - - 2-T16 1-T16 - 7-2L-T8@5" C/C - -
Client Name:Mr.Nirikshit
Project Type:Residential Building
FIRST FLOOR LEVEL BEAM SCHEDULE Date:11-Feb-2024
DESIGN:
Ground Floor Level Beam Layout
D AREA STATEMENT:
A B C E F G Plot Area : 1,353 SQ.FT.
SOIL BEARING CAPACITY
Foundations have been designed
According to given site soil condition.
Soil Bearing Capacity (SBC) - 200 KN/m.sq.
STEEL REINFORCEMENT
Steel Reinforcement confirming to IS 1786-1985 code,
FE - 500 grade should be used.
M7.5 = 1:4:8 ( USED AS P.C.C. )
B1 B2
6 C2 C11
M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
CLEAR COVER TO MAIN
C1
REINFORCEMENT:
1.FOOTINGS : 50 mm
2.COLUMN : 40 mm
3.BEAMS : 25 mm
4.SLABS : 20 mm
5.STAIRCASE : 20 mm
B3 B4
5 C9 C10
C3
B5 NOTE: Refer Relavant
4 Architectural Drawing
C5
B6 B7 B8
3 C13 C12
C4 C6
Client Name:Mr.Nirikshit
B9 Project Type:Residential Building
2 Date:11-Feb-2024
B11 B12 B13
1 C14 C15
C8 C7
B10
GROUND FLOOR LEVEL BEAM LAYOUT
DESIGN:
Ground Floor Level Beam Elevation
AREA STATEMENT:
Plot Area : 1,353 SQ.FT.
2-T16
2-T16 2-T16
2-T16 SOIL BEARING CAPACITY
2-T16 2-T16
Foundations have been designed
According to given site soil condition.
2-T16
2-T16 2-T16 2-T16
2-T16 Soil Bearing Capacity (SBC) - 200 KN/m.sq.
STEEL REINFORCEMENT
32-2L-T8 42-2L-T8 29-2L-T8 9-2L-T8 52-2L-T8
@5" C/C @5" C/C @5" C/C @5" C/C @5" C/C Steel Reinforcement confirming to IS 1786-1985 code,
C1 B1:9"X15" C2 B2:9"X15" C11 C8 B14:9"X15" C4 B15:9"X15" C5 B16:9"X18" C1
FE - 500 grade should be used.
M7.5 = 1:4:8 ( USED AS P.C.C. )
M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
CLEAR COVER TO MAIN
2-T16 3-T16 2-T16 3-T16 REINFORCEMENT:
3-T16 2-T16 3-T16
1.FOOTINGS : 50 mm
2-T16 3-T16 2-T16 2.COLUMN : 40 mm
2-T16 3-T16 2-T16
11-2L-T8 30-2L-T8 3.BEAMS : 25 mm
@5" C/C @5" C/C 29-2L-T8 4.SLABS : 20 mm
B3:9"X15" B4:9"X15" @5" C/C
C3 C9 C10 5.STAIRCASE : 20 mm
B17:9"X15"
C7 C6
2-T16
2-T16
2-T16 2-T16
2-T16
34-2L-T8 2-T16 3-T16 2-T16 3-T16 2-T16
@5" C/C B18
B5:9"X15" 30-2L-T8 35-2L-T8
B7 @5" C/C @5" C/C
C5
B18:9"X15" B19:9"X15"
C3 C2
2-T16 3-T16 2-T16 3-T16
NOTE: Refer Relavant
2-T16 3-T16 2-T16
2-T16 Architectural Drawing
2-T16 2-T16
23-2L-T8 21-2L-T8 30-2L-T8
@5" C/C @5" C/C @5" C/C
B6:9"X15" B7:9"X15" B8:9"X15" 2-T16
C4 C6 C13 C12 2-T16
31-2L-T8 31-2L-T8
@5" C/C @5" C/C
2-T16
C14 B20:9"X15" C13 B21:9"X15" C9
2-T16 3-T16 2-T16 Client Name:Mr.Nirikshit
22-2L-T8 Project Type:Residential Building
B17 @5" C/C B20
B9:9"X15"
Date:11-Feb-2024
2-T16
2-T16 3-T16 2-T16 3-T16 2-T16
2-T16
2-T16 3-T16 2-T16
23-2L-T8
@5" C/C 31-2L-T8 31-2L-T8 36-2L-T8
B10:9"X15" @5" C/C @5" C/C @5" C/C
C8 C7 B22:9"X15" B23:9"X15" B24:9"X15"
C15 C12 C10 C11
2-T16
2-T16
23-2L-T8 21-2L-T8 30-2L-T8
@5" C/C @5" C/C @5" C/C
B11:9"X15" B12:9"X15" B13:9"X15"
C8 C7 C14 C15
GROUND FLOOR LEVEL BEAM ELEVATION
DESIGN:
Ground Floor Level Beam Schedule
BEAM SCHEDULE (M20:Fe500) (LEVEL: GF) AREA STATEMENT:
Plot Area : 1,353 SQ.FT.
SIZE BOTTOM REINFORCEMENT TOP REINFORCEMENT
BEAM SHEAR STIRRUPS SFR REMARKS SOIL BEARING CAPACITY
NUMBERS B D STRAIGHT CURTAILED EXTRA EXTRA STRAIGHT EXTRA EXTRA Foundations have been designed
LEFT RIGHT LEFT SUPP RIGHT SUPP According to given site soil condition.
Soil Bearing Capacity (SBC) - 200 KN/m.sq.
B1 230 380 2-T16 - - - 2-T16 - - 8-2L-T8@125 C/C - -
STEEL REINFORCEMENT
2-T16
Steel Reinforcement confirming to IS 1786-1985 code,
B2 230 380 2-T16 - - - 2-T16 - - 8-2L-T8@125 C/C - - FE - 500 grade should be used.
2-T16 2-T16 2-T16
M7.5 = 1:4:8 ( USED AS P.C.C. )
B3 230 380 2-T16 - - - 2-T16 - 1-T16 6-2L-T8@125 C/C - -
M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
B4 230 380 2-T16 1-T16 - - 2-T16 1-T16 1-T16 8-2L-T8@125 C/C - - CLEAR COVER TO MAIN
B5 230 380 2-T16 - - - 2-T16 - - 8-2L-T8@125 C/C - - REINFORCEMENT:
B6 230 380 2-T16 - - - 2-T16 - - 8-2L-T8@125 C/C - - 1.FOOTINGS : 50 mm
B7 230 380 2-T16 - - - 2-T16 - 1-T16 8-2L-T8@125 C/C - - 2.COLUMN : 40 mm
B8 230 380 2-T16 1-T16 - - 2-T16 1-T16 1-T16 8-2L-T8@125 C/C - -
3.BEAMS : 25 mm
4.SLABS : 20 mm
B9 230 380 2-T16 1-T16 - - 2-T16 - - 8-2L-T8@125 C/C - -
5.STAIRCASE : 20 mm
B10 230 380 2-T16 - - - 2-T16 - - 8-2L-T8@125 C/C - -
B11 230 380 2-T16 - - - 2-T16 - - 8-2L-T8@125 C/C - -
B12 230 380 2-T16 - - - 2-T16 - - 8-2L-T8@125 C/C - -
B13 230 380 2-T16 - - - 2-T16 - - 8-2L-T8@125 C/C - -
B14 230 380 2-T16 - - - 2-T16 - - 8-2L-T8@125 C/C - -
B15 230 380 2-T16 - - - 2-T16 - - 5-2L-T8@125 C/C - -
2-T16
B16 230 450 2-T16 - - - 2-T16 - - 9-2L-T8@125 C/C - -
2-T16 2-T16 2-T16
B17 230 380 2-T16 1-T16 - - 2-T16 1-T16 1-T16 8-2L-T8@125 C/C - -
B18 230 380 2-T16 1-T16 - - 2-T16 - - 8-2L-T8@125 C/C - -
2-T16
B19 230 380 2-T16 1-T16 - - 2-T16 - - 8-2L-T8@125 C/C - -
2-T16 2-T16
B20 230 380 2-T16 - - - 2-T16 - - 8-2L-T8@125 C/C - -
2-T16 2-T16 2-T16
B21 230 380 2-T16 - - - 2-T16 - - 8-2L-T8@125 C/C - -
2-T16
B22 230 380 2-T16 - - - 2-T16 - 1-T16 8-2L-T8@125 C/C - -
B23 230 380 2-T16 - - - 2-T16 1-T16 1-T16 8-2L-T8@125 C/C - -
B24 230 380 2-T16 1-T16 - - 2-T16 1-T16 - 8-2L-T8@125 C/C - - Client Name:Mr.Nirikshit
Project Type:Residential Building
Date:11-Feb-2024
GROUND FLOOR LEVEL BEAM SCHEDULE
DESIGN:
Column Centerline Plan
D AREA STATEMENT:
A B C E F G Plot Area : 1,353 SQ.FT.
SOIL BEARING CAPACITY
Foundations have been designed
According to given site soil condition.
Soil Bearing Capacity (SBC) - 200 KN/m.sq.
STEEL REINFORCEMENT
Steel Reinforcement confirming to IS 1786-1985 code,
FE - 500 grade should be used.
B1 B2 M7.5 = 1:4:8 ( USED AS P.C.C. )
6 C2 C11
M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
C1 CLEAR COVER TO MAIN
REINFORCEMENT:
1.FOOTINGS : 50 mm
2.COLUMN : 40 mm
3.BEAMS : 25 mm
4.SLABS : 20 mm
5.STAIRCASE : 20 mm
B3 B4
5 C9 C10
C3
NOTE: Refer Relavant
Architectural Drawing
4
C5
B5 B6 B7
3 C13 C12
C4 C6
Client Name:Mr.Nirikshit
B8 Project Type:Residential Building
2 Date:11-Feb-2024
B9 B10 B11
1 C14 C15
C8 C7
PLINTH BEAM LAYOUT
DESIGN:
Column Centerline Plan
AREA STATEMENT:
Plot Area : 1,353 SQ.FT.
SOIL BEARING CAPACITY
Foundations have been designed
According to given site soil condition.
Soil Bearing Capacity (SBC) - 200 KN/m.sq.
STEEL REINFORCEMENT
2-T16
2-T16 2-T16 Steel Reinforcement confirming to IS 1786-1985 code,
2-T16 3-T16 2-T16 3-T16
FE - 500 grade should be used.
2-T16 M7.5 = 1:4:8 ( USED AS P.C.C. )
2-T16
2-T16
M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
32-2L-T8 42-2L-T8 29-2L-T8 9-2L-T8 52-2L-T8
@5" C/C @5" C/C @5" C/C @5" C/C @5" C/C CLEAR COVER TO MAIN
B1:9"X15" B2:9"X15" C8 B12:9"X15" C4 B13:9"X15" C5 B14:9"X15" C1
REINFORCEMENT:
C1 C2 C11 1.FOOTINGS : 50 mm
2.COLUMN : 40 mm
3.BEAMS : 25 mm
2-T16 4.SLABS : 20 mm
5.STAIRCASE : 20 mm
2-T16 3-T16 2-T16
2-T16
29-2L-T8
@5" C/C
2-T16
B15:9"X15"
C7 C6
11-2L-T8 30-2L-T8
@5" C/C @5" C/C
B3:9"X15" B4:9"X15"
2-T16
C3 C9 C10
2-T16
35-2L-T8
@5" C/C
B16:9"X15"
C3 C2
2-T16 2-T16 NOTE: Refer Relavant
Architectural Drawing
2-T16 2-T16
23-2L-T8 21-2L-T8 30-2L-T8 19-2L-T8
@5" C/C @5" C/C @5" C/C @5" C/C
B10 B8
B5:9"X15" B6:9"X15" B7:9"X15" B17:9"X15"
C4 C6 C13 C12
2-T16
3-T16 2-T16 3-T16 2-T16
Client Name:Mr.Nirikshit
Project Type:Residential Building
2-T16 3-T16 2-T16
2-T16 3-T16 2-T16
Date:11-Feb-2024
31-2L-T8 31-2L-T8
22-2L-T8 @5" C/C @5" C/C
B15 @5" C/C B18
B18:9"X15" B19:9"X15"
B8:9"X15" C14 C13 C9
2-T16
2-T16
2-T16
2-T16
31-2L-T8 31-2L-T8 36-2L-T8
23-2L-T8 21-2L-T8 30-2L-T8 @5" C/C @5" C/C @5" C/C
@5" C/C @5" C/C @5" C/C
B20:9"X15" B21:9"X15" B22:9"X15"
B9:9"X15" B10:9"X15" B11:9"X15"
C15 C12 C10 C11
C8 C7 C14 C15
PLINTH BEAM ELEVATION
DESIGN:
BEAM SCHEDULE (M20:Fe500) (LEVEL: PB) Column Centerline Plan
AREA STATEMENT:
SIZE BOTTOM REINFORCEMENT TOP REINFORCEMENT
BEAM SHEAR STIRRUPS SFR REMARKS
Plot Area : 1,353 SQ.FT.
NUMBERS B D STRAIGHT CURTAILED EXTRA EXTRA STRAIGHT EXTRA EXTRA SOIL BEARING CAPACITY
LEFT RIGHT LEFT SUPP RIGHT SUPP Foundations have been designed
According to given site soil condition.
B1 9" 15" 2-T16 - - - 2-T16 - 1-T16 8-2L-T8@5" C/C - -
Soil Bearing Capacity (SBC) - 200 KN/m.sq.
B2 9" 15" 2-T16 - - - 2-T16 1-T16 1-T16 8-2L-T8@5" C/C - - STEEL REINFORCEMENT
B3 9" 15" 2-T16 - - - 2-T16 - - 6-2L-T8@5" C/C - - Steel Reinforcement confirming to IS 1786-1985 code,
FE - 500 grade should be used.
B4 9" 15" 2-T16 - - - 2-T16 - - 8-2L-T8@5" C/C - -
M7.5 = 1:4:8 ( USED AS P.C.C. )
B5 9" 15" 2-T16 - - - 2-T16 - - 8-2L-T8@5" C/C - -
M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
B6 9" 15" 2-T16 - - - 2-T16 - - 8-2L-T8@5" C/C - -
CLEAR COVER TO MAIN
B7 9" 15" 2-T16 - - - 2-T16 - - 8-2L-T8@5" C/C - - REINFORCEMENT:
B8 9" 15" 2-T16 1-T16 - - 2-T16 - - 8-2L-T8@5" C/C - - 1.FOOTINGS : 50 mm
B9 9" 15" 2-T16 - - - 2-T16 - - 8-2L-T8@5" C/C - - 2.COLUMN : 40 mm
B10 9" 15" 2-T16 - - - 2-T16 - - 8-2L-T8@5" C/C - -
3.BEAMS : 25 mm
4.SLABS : 20 mm
B11 9" 15" 2-T16 - - - 2-T16 - - 8-2L-T8@5" C/C - -
5.STAIRCASE : 20 mm
B12 9" 15" 2-T16 - - - 2-T16 - - 8-2L-T8@5" C/C - -
B13 9" 15" 2-T16 - - - 2-T16 - - 5-2L-T8@5" C/C - -
2-T16
B14 9" 15" 2-T16 - - - 2-T16 - - 8-2L-T8@5" C/C - -
2-T16 2-T16 2-T16
B15 9" 15" 2-T16 1-T16 - - 2-T16 - - 8-2L-T8@5" C/C - -
B16 9" 15" 2-T16 - - - 2-T16 - - 8-2L-T8@5" C/C - -
B17 9" 15" 2-T16 - - - 2-T16 - - 8-2L-T8@5" C/C - -
B18 9" 15" 2-T16 1-T16 - - 2-T16 1-T16 1-T16 8-2L-T8@5" C/C - -
B19 9" 15" 2-T16 - - - 2-T16 1-T16 - 8-2L-T8@5" C/C - -
B20 9" 15" 2-T16 - - - 2-T16 - - 8-2L-T8@5" C/C - -
B21 9" 15" 2-T16 - - - 2-T16 - - 8-2L-T8@5" C/C - -
B22 9" 15" 2-T16 - - - 2-T16 - - 8-2L-T8@5" C/C - -
PLINTH BEAM SCHEDULE
Client Name:Mr.Nirikshit
Project Type:Residential Building
Date:11-Feb-2024
DESIGN:
Column Schedule 01
AREA STATEMENT:
TERRACE Plot Area : 1,353 SQ.FT.
SOIL BEARING CAPACITY
Foundations have been designed
According to given site soil condition.
TO
Soil Bearing Capacity (SBC) - 200 KN/m.sq.
STEEL REINFORCEMENT
MUMTY Steel Reinforcement confirming to IS 1786-1985 code,
FE - 500 grade should be used.
M7.5 = 1:4:8 ( USED AS P.C.C. )
M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM CLEAR COVER TO MAIN
REINFORCEMENT:
FF
1.FOOTINGS : 50 mm
2.COLUMN : 40 mm
3.BEAMS : 25 mm
LINKS LINKS LINKS LINKS
TO
T8 @ 6"
4.SLABS : 20 mm
T8 @ 6" T8 @ 6" T8 @ 6"
5.STAIRCASE : 20 mm
TERRACE
9"
9"
9"
9"
T16 T16 T16 T16
24"
T12
24" 18" 18"
12-T16 12-T16 8-T16 4-T16+4-T12
M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM
GF
LINKS LINKS LINKS LINKS
TO
T8 @ 6" T8 @ 6" T8 @ 6" T8 @ 6"
FF
NOTE: Refer Relavant
9"
9"
9"
9"
9"
9"
9"
9"
T16 T16 T16 T16 T16
24" 24" 18" 18" T12
18"
12-T16 12-T16 8-T16 8-T16 4-T16+4-T12
M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM
BASE
LINKS LINKS LINKS LINKS LINKS
TO
T8 @ 6" T8 @ 6" T8 @ 6" T8 @ 6" T8 @ 6"
PB
9"
9"
9"
9"
9"
T16 T16 T16 T16 T16
T12
24" 24" 18" 18" 18"
12-T16 12-T16 8-T16 8-T16 4-T16+4-T12
COLUMN MARKED C1 C2 C11 C3 C9
COLUMN SCHEDULE 01
DESIGN:
M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM Column Schedule 02
AREA STATEMENT:
TERRACE
Plot Area : 1,353 SQ.FT.
SOIL BEARING CAPACITY
Foundations have been designed
LINKS LINKS
TO According to given site soil condition.
T8 @ 6" T8 @ 6"
Soil Bearing Capacity (SBC) - 200 KN/m.sq.
MUMTY STEEL REINFORCEMENT
9"
T16 T16
T12 FE - 500 grade should be used.
18" 18"
4-T16+4-T12 8-T16
M7.5 = 1:4:8 ( USED AS P.C.C. )
M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM M20= 1:1.5:3 ( USED AS MIN. GRADE IN BUILDING )
CLEAR COVER TO MAIN
FF REINFORCEMENT:
1.FOOTINGS : 50 mm
2.COLUMN : 40 mm
LINKS LINKS LINKS LINKS LINKS
TO 3.BEAMS : 25 mm
T8 @ 6" T8 @ 6" T8 @ 6" T8 @ 6" T8 @ 6"
4.SLABS : 20 mm
TERRACE 5.STAIRCASE : 20 mm
9"
9"
9"
9"
9"
T16 T16 T16 T16 T16
T12 T12
18" 24" 18" 18" 18"
4-T16+4-T12 12-T16 4-T16+4-T12 8-T16 8-T16
M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM
GF
LINKS LINKS LINKS LINKS LINKS
TO
T8 @ 6" T8 @ 6" T8 @ 6" T8 @ 6" T8 @ 6"
FF
9"
9"
9"
9"
9"
T16 T16 T16 T16 T16
T12 T12
18" 24" 18" 18" 18"
NOTE: Refer Relavant
4-T16+4-T12 12-T16 4-T16+4-T12 8-T16 8-T16 Architectural Drawing
M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM
PB
LINKS LINKS LINKS LINKS LINKS
TO
T8 @ 6" T8 @ 6" T8 @ 6" T8 @ 6" T8 @ 6"
GF
Client Name:Mr.Nirikshit
Project Type:Residential Building
9"
9"
9"
9"
9"
T16 T16 T16 T16 T16
18"
T12 24" 18"
T12 18" 18"
Date:11-Feb-2024
4-T16+4-T12 12-T16 4-T16+4-T12 8-T16 8-T16
M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM
BASE
LINKS LINKS LINKS LINKS LINKS
TO
T8 @ 6" T8 @ 6" T8 @ 6" T8 @ 6" T8 @ 6"
PB
9"
9"
9"
9"
9"
T16 T16 T16 T16 T16
T12 T12 18"
18" 24" 18" 18"
4-T16+4-T12 12-T16 4-T16+4-T12 8-T16 8-T16
COLUMN MARKED C10 C5 C4 C6 C13
COLUMN SCHEDULE 02
DESIGN:
Column Schedule 03
AREA STATEMENT:
M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM Plot Area : 1,353 SQ.FT.
TERRACE
SOIL BEARING CAPACITY
Foundations have been designed
According to given site soil condition.
LINKS
Soil Bearing Capacity (SBC) - 200 KN/m.sq.
LINKS
TO STEEL REINFORCEMENT
T8 @ 6" T8 @ 6"
Steel Reinforcement confirming to IS 1786-1985 code,
FE - 500 grade should be used.
MUMTY
9"
9"
9"
9"
9"
9"
T16 T16 T16 T16 T16
T12 T12
18" 18" 18" 18" 18"
8-T16 4-T16+4-T12 4-T16+4-T12 8-T16 8-T16
M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM
GF
LINKS LINKS LINKS LINKS LINKS
TO
T8 @ 6" T8 @ 6" T8 @ 6" T8 @ 6" T8 @ 6"
FF
NOTE: Refer Relavant
9"
9"
9"
9"
9"
T16 T16 T16 T16 T16
T12 T12
18" 18" 18" 18" 18" Architectural Drawing
8-T16 4-T16+4-T12 4-T16+4-T12 8-T16 8-T16
M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM
PB
LINKS LINKS LINKS LINKS LINKS
TO
T8 @ 6" T8 @ 6" T8 @ 6" T8 @ 6" T8 @ 6"
Client Name:Mr.Nirikshit
GF Project Type:Residential Building
9"
9"
9"
9"
9"
T16 T16 T16 T16 T16
18" 18"
T12 18"
T12 18" 18"
Date:11-Feb-2024
8-T16 4-T16+4-T12 4-T16+4-T12 8-T16 8-T16
M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM M20 : Fe500 , COVER = 40MM
BASE
LINKS LINKS LINKS LINKS LINKS
TO
T8 @ 6" T8 @ 6" T8 @ 6" T8 @ 6" T8 @ 6"
PB
9"
9"
9"
9"
9"
T16 T16 T16 T16 T16
T12 T12
18" 18" 18" 18" 18"
8-T16 4-T16+4-T12 4-T16+4-T12 8-T16 8-T16
COLUMN MARKED C12 C8 C7 C14 C15
COLUMN SCHEDULE 03