1 OBJECTIVE
© Metso Outotec. Metso Outotec reserves all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly
This Technical Specification establishes the basic characteristics and minimum requirements for the
supply of LV Dry Transformers to be used on Metso equipment.
The design, manufacture and installation of equipment must comply with the relevant government
acts, by-laws, and regulations, at both state and national levels.
Design and installation must comply with the rules and provisions of the latest editions and
amendments of the relevant international standards. Standards may be adopted with the following
precedence:
o International (IEC and ISO)
o IEEE
forbidden.
o British (BS)
o German (DIN)
DATA
DATE 31/07/2020
SETOR
DEPARTMENT MNGCM B Revision 02/07/21 MHS VGQ
NOME
NAME MHS A Initial Emission 31/07/20 MHS VGQ
PROJETO ALTERAÇÃO/EMISSÃO DATA PROJETO / DESIGN
DESIGN
REV. MODIFICATION/ / EM SSION DATE
EXEC.
APROVAÇÃO / APPROVED
ESPECIFICAÇÃO PURCHASING Nº
DE COMPRA SPECIFICATION 400100026-ETP
DENOMINAÇÃO / DESCRIPTION REV. FOLHA/SHEET
o American (NEMA)
© Metso Outotec. Metso Outotec reserves all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly
o Other
In the absence of any specified standard, the original Supplier’s recommendations must prevail
subject to the Purchaser’s approval.
The latest revisions of the most used standards for Transformers listed in table below must be applied
full as a minimum.
DATA
DATE 31/07/2020
SETOR
DEPARTMENT MNGCM B Revision 02/07/21 MHS VGQ
NOME
NAME MHS A Initial Emission 31/07/20 MHS VGQ
PROJETO ALTERAÇÃO/EMISSÃO DATA PROJETO / DESIGN
DESIGN
REV. MODIFICATION/ / EM SSION DATE
EXEC.
APROVAÇÃO / APPROVED
ESPECIFICAÇÃO PURCHASING Nº
DE COMPRA SPECIFICATION 400100026-ETP
DENOMINAÇÃO / DESCRIPTION REV. FOLHA/SHEET
SUPPRESSION DEVICES
IEEE Standard for General Requirements for Dry-Type
© Metso Outotec. Metso Outotec reserves all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly
IEEE C57.12.01
Distribution and Power Transformers
IEEE Standard for Requirements, Terminology, and Test
IEEE C57.32
Procedures for Neutral Grounding Devices
ABNT 6856 Transformador de Corrente – Especificação e ensaios
4 SCOPE OF SUPPLY
This specification establishes the minimum requirements necessary for the correct provision of
engineering, labour, tools, materials, equipment, components and all accessories necessary for the correct
design, manufacture, inspection, testing, packaging, transportation and delivery of Dry Transformers up to and
including 36kV, grounding resistance and associated components indicated in this document, the attached
files and the reference documents to be used in SMPG System installations.
to -25°C.
DATA
DATE 31/07/2020
SETOR
DEPARTMENT MNGCM B Revision 02/07/21 MHS VGQ
NOME
NAME MHS A Initial Emission 31/07/20 MHS VGQ
PROJETO ALTERAÇÃO/EMISSÃO DATA PROJETO / DESIGN
DESIGN
REV. MODIFICATION/ / EM SSION DATE
EXEC.
APROVAÇÃO / APPROVED
ESPECIFICAÇÃO PURCHASING Nº
DE COMPRA SPECIFICATION 400100026-ETP
DENOMINAÇÃO / DESCRIPTION REV. FOLHA/SHEET
NOTE: If required a transformer designed for operation at an altitude greater than 1000m (if needed, it
© Metso Outotec. Metso Outotec reserves all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly
will be explicitly written in section 1.1) at normal altitudes, the limits of temperature rise given in Table 1 shall
be reduced by the following amounts for each 500m which the intended working altitude exceeds 1000m:
- natural-air-cooled transformers: 2.5%
- forced-air-cooled-transformers: 5%
Also, in this situation, if the operation altitudes are between 1000m and 3000m above sea-level, but
tested at normal altitude, the rated short duration separate source AC withstand voltage shall be increased by
1% for each 100m above 1000m. Above 3000m, the insulation level shall be defined by agreement between
supplier and purchaser.
The transformer insulation system temperature should be 155 °C (F), with Average winding-
temperature rise limits at rated current 100 K. Temperature rise measured in accordance with clause 23 of
IEC 60076-11:2004
NOTE: If service conditions outside normal conditions are identified, the supplier must inform and
provide a solution for Metso. These solutions must be sent to us for previous approval.
forbidden.
DATA
DATE 31/07/2020
SETOR
DEPARTMENT MNGCM B Revision 02/07/21 MHS VGQ
NOME
NAME MHS A Initial Emission 31/07/20 MHS VGQ
PROJETO ALTERAÇÃO/EMISSÃO DATA PROJETO / DESIGN
DESIGN
REV. MODIFICATION/ / EM SSION DATE
EXEC.
APROVAÇÃO / APPROVED
ESPECIFICAÇÃO PURCHASING Nº
DE COMPRA SPECIFICATION 400100026-ETP
DENOMINAÇÃO / DESCRIPTION REV. FOLHA/SHEET
6 RATED POWER
© Metso Outotec. Metso Outotec reserves all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly
The transformer shall be capable of carrying, in continuous service, the rated power (for a multi-
winding transformer: the specified combination(s) of winding rated powers) under conditions specified and
without exceeding the temperature-rise limitations specified in IEC 60076-2.
7 TAPPINGS
8 CONNECTIONS
Unless otherwise specified in item 1.1, transformer connections shall be Dyn11. The neutral
connection shall be capable of carrying full phase rated current.
9 GROUNDING
A transformer shall be capable of service without damage under conditions of over fluxing where the
ratio of voltage over frequency exceeds the corresponding ratio at rated voltage and rated frequency by no
more than 5 %.
Each transformer shall be provided with a rating plate of weatherproof material, fitted in a visible
forbidden.
position, showing the items indicated below. The entries on the plate shall be indelibly marked (that is, by
etching, engraving, stamping or by a photo-chemical process).
DATA
DATE 31/07/2020
SETOR
DEPARTMENT MNGCM B Revision 02/07/21 MHS VGQ
NOME
NAME MHS A Initial Emission 31/07/20 MHS VGQ
PROJETO ALTERAÇÃO/EMISSÃO DATA PROJETO / DESIGN
DESIGN
REV. MODIFICATION/ / EM SSION DATE
EXEC.
APROVAÇÃO / APPROVED
ESPECIFICAÇÃO PURCHASING Nº
DE COMPRA SPECIFICATION 400100026-ETP
DENOMINAÇÃO / DESCRIPTION REV. FOLHA/SHEET
Transformers shall be identified according to the cooling method employed. Letter symbols for use in
connection with each cooling method shall be as given in Table 1.
Table 1 - Letter Symbols
Symbol
forbidden.
DATA
DATE 31/07/2020
SETOR
DEPARTMENT MNGCM B Revision 02/07/21 MHS VGQ
NOME
NAME MHS A Initial Emission 31/07/20 MHS VGQ
PROJETO ALTERAÇÃO/EMISSÃO DATA PROJETO / DESIGN
DESIGN
REV. MODIFICATION/ / EM SSION DATE
EXEC.
APROVAÇÃO / APPROVED
ESPECIFICAÇÃO PURCHASING Nº
DE COMPRA SPECIFICATION 400100026-ETP
DENOMINAÇÃO / DESCRIPTION REV. FOLHA/SHEET
Forced F
© Metso Outotec. Metso Outotec reserves all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly
The temperature rises of each winding of the transformer, designed for operation at normal service
conditions, shall not exceed the corresponding limit specified in this document when tested in accordance with
Temperature-rise test (type test) of IEC 60076-11.
The maximum temperature occurring in any part of the winding insulation system is called the hot-spot
temperature. The hot spot temperature shall not exceed the rated value of the hot-spot winding temperature
specified in IEC 60905. This temperature could be measured, however an approximate value for practical
purposes can be calculated by using equation 1 in 4.2.4 of IEC 60905 with the values for Z and q given in 7.2
of IEC 60905.
Components used as insulating material may be used separately or in combination providing that their
temperature according insulation system temperature that is defined.
The temperature of the core, metallic parts and adjacent materials shall not reach a value that will cause
damage to any part of the transformer.
15 INSULATION LEVEL
Highest voltage for equipment Um Rated short duration separate Rated lightning impulse withstand
(r.m.s) kV source AC withstand voltage (r.m.s) voltage (peak value) kV
kV List 1 List 2
≤ 1,1 3 - -
16 EARTHING TERMINAL
Transformers shall be fitted with an earth terminal for the connection of a protective conductor. All
exposed metallic conductive non-live parts shall be connected to the earth terminal by construction or
forbidden.
otherwise.
DATA
DATE 31/07/2020
SETOR
DEPARTMENT MNGCM B Revision 02/07/21 MHS VGQ
NOME
NAME MHS A Initial Emission 31/07/20 MHS VGQ
PROJETO ALTERAÇÃO/EMISSÃO DATA PROJETO / DESIGN
DESIGN
REV. MODIFICATION/ / EM SSION DATE
EXEC.
APROVAÇÃO / APPROVED
ESPECIFICAÇÃO PURCHASING Nº
DE COMPRA SPECIFICATION 400100026-ETP
DENOMINAÇÃO / DESCRIPTION REV. FOLHA/SHEET
17 ROUTINE TESTS
© Metso Outotec. Metso Outotec reserves all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly
Must follow the most recent international standards. See NBR 7036 for reference.
19 VISUAL INSPECTION
The transformer must undergo a visual inspection covering the following items:
Check the characteristics of the nameplate with the purchase order.
Check the absence of cracks or chips in the bushings and external damage to the tank or
accessories.
Check the correct level of the insulating liquid (if applicable).
Check the accuracy of the instruments, through readings (if applicable).
Examine for signs of corrosion.
Examine the correct marking of the terminals.
Observe if there are leaks through the bushings, plugs, and sides.
Check the external components of the switching system.
Check the condition of the packaging, if any.
DATA
DATE 31/07/2020
SETOR
DEPARTMENT MNGCM B Revision 02/07/21 MHS VGQ
NOME
NAME MHS A Initial Emission 31/07/20 MHS VGQ
PROJETO ALTERAÇÃO/EMISSÃO DATA PROJETO / DESIGN
DESIGN
REV. MODIFICATION/ / EM SSION DATE
EXEC.
APROVAÇÃO / APPROVED
ESPECIFICAÇÃO PURCHASING Nº
DE COMPRA SPECIFICATION 400100026-ETP
DENOMINAÇÃO / DESCRIPTION REV. FOLHA/SHEET
21 ATTACHMENTS
© Metso Outotec. Metso Outotec reserves all rights in this document and in the information contained herein. Reproduction, use or disclosure to third parties without express authority is strictly
The Contractor must have, know, and consider all the requirements described in the Client’s
specifications/documents listed below.
Document
Crusher 54-75 Crusher 60-89 Crusher 60-110
description
Single Line Diagram 900109017-NID 900109010-NID 900109024-NID
Design Criteria –
400100147-ETP
Electrical and Energy
Design Criteria –
Control, Automation, 400100146-ETP
and Instrumentation
Painting Instructions 400100022-ETP
22 DATASHEETS
The Supplier shall fill all fields in the attached Data Sheets.
If such requested information is not available or not applicable, it must be explicitly indicated or
alternative actions to follow.
TAG: Quantity:
Service: LOW VOLTAGE DRY TRANSFORMERS
DATA
DATE 31/07/2020
SETOR
DEPARTMENT MNGCM B Revision 02/07/21 MHS VGQ
NOME
NAME MHS A Initial Emission 31/07/20 MHS VGQ
PROJETO ALTERAÇÃO/EMISSÃO DATA PROJETO / DESIGN
DESIGN
REV. MODIFICATION/ / EM SSION DATE
EXEC.
APROVAÇÃO / APPROVED
ESPECIFICAÇÃO PURCHASING Nº
DE COMPRA SPECIFICATION 400100026-ETP
DENOMINAÇÃO / DESCRIPTION REV. FOLHA/SHEET
GENERAL DATA
Manufacturer Inform
Country of manufacture Inform
Type Inform
Model Inform
Standards Inform
Specification Inform
DATA
DATE 31/07/2020
SETOR
DEPARTMENT MNGCM B Revision 02/07/21 MHS VGQ
NOME
NAME MHS A Initial Emission 31/07/20 MHS VGQ
PROJETO ALTERAÇÃO/EMISSÃO DATA PROJETO / DESIGN
DESIGN
REV. MODIFICATION/ / EM SSION DATE
EXEC.
APROVAÇÃO / APPROVED
ESPECIFICAÇÃO PURCHASING Nº
DE COMPRA SPECIFICATION 400100026-ETP
DENOMINAÇÃO / DESCRIPTION REV. FOLHA/SHEET
DATA
DATE 31/07/2020
SETOR
DEPARTMENT MNGCM B Revision 02/07/21 MHS VGQ
NOME
NAME MHS A Initial Emission 31/07/20 MHS VGQ
PROJETO ALTERAÇÃO/EMISSÃO DATA PROJETO / DESIGN
DESIGN
REV. MODIFICATION/ / EM SSION DATE
EXEC.
APROVAÇÃO / APPROVED