Our Recommendations for Various Testing and Processes

Sr. No Testing Annually Bi Annually

01 Oil Testing as per IS 1866 √

02 DGA test of Oil √

03 Transformer Oil Furan Analysis test X √

04 Sweep Frequency Response Analysis Test X √

05 EHV Bushing Test on Bushings i.e. Testing of X √


Capacitance Measurement & TAN DELTA
Test up to 10/12 KV for your Transformer
Bushings
06 Testing of Capacitance Measurement & TAN X √
DELTA Test Up to 10/12 KV for your
Transformer.
07 IR & PI Value test of transformer. √

08 Testing of Voltage Ratio test of transformer √

09 Testing of Magnetic Balance Test for √


transformer.
10 Testing of Winding Resistance Measurement √
test for Transformer.
11 Low voltage Open circuit and Short circuit √
test of your Transformer
12 All Protection Circuit & stimulation √

Sr.No Maintenance Processes Annually Bi Annually

01 OLTC Overhauling √

02 Oil Filtration √

03 preventive maintenance of transformer as √


per OEM guidelines
04 Overhauling of transformer 7 to 10 Years as per IS 10028 Part II for Power
Transformer

Yours truly,

For Voltamp Transformers Ltd,

Yogesh Shah
In Charge – Services
M.No: 93775 69496
Regd. Office & Works Branches
Makarpura, Vadodara Ahmedabad, Bangalore, Bhubaneshwar
Gujarat, India – 390 014 Chandigarh, Chennai, Delhi, Jaipur,Kolkatta,
www.voltamptransformers.com Mumbai, Pune, Raipur, Secunderabad,
Coimbatore
C:\Documents and Settings\SATYESH-SAS\Desktop\Maintainance Schedule.doc

You might also like