You are on page 1of 16

DRAWING PAGE REVISION DRAWING

N:o N:o

K101.2828 - 1100 1 / 15 a/17-04-02 ANALOG INPUTS


1100 2 / 15 a/17-04-02 ANALOG INPUTS
1100 3 / 15 a/17-04-02 ANALOG INPUTS
1100 4 / 15 a/17-04-02 24 VDC RELAY OUTPUT CONNECTIONS
1100 5 / 15 a/17-04-02 24 VDC RELAY OUTPUT CONNECTIONS
1100 6 / 15 a/17-04-02 24 VDC RELAY OUTPUT CONNECTIONS
1100 7 / 15 a/17-04-02 24 VDC RELAY OUTPUT CONNECTIONS
1100 8 / 15 a/17-04-02 ON/OFF 24 VDC INPUT CONNECTIONS
1100 9 / 15 a/17-04-02 ON/OFF 24 VDC INPUT CONNECTIONS
1100 10 / 15 a/17-04-02 ON/OFF 24 VDC INPUT CONNECTIONS
1100 11 / 15 a/17-04-02 ON/OFF 24 VDC INPUT CONNECTIONS
1100 12 / 15 a/17-04-02 ON/OFF 24 VDC INPUT CONNECTIONS
1100 13 / 15 a/17-04-02 ON/OFF 24 VDC INPUT CONNECTIONS
1100 14 / 15 a/17-04-02 ON/OFF 24 VDC INPUT CONNECTIONS
1100 15 / 15 a/17-04-02 ON/OFF 24 VDC INPUT CONNECTIONS

UNITY POWER PLANT I/O LIST OF COMMON CFA901


MADE 27-05-02 Jan Rönnholm SUDAN LIST OF DRAWINGS SHEET 1 OF SHEETS 1
CHKD. JÅ PROJECT No. / DRAWING No. REV
APPR. BK DIESEL POWER STATION K101.2828 - 1100 -
Department: AD Unity power plant CFA901 Code: 18V32
Drawn: MN Sudan I/O List Drawn: 10.01.2002 / MN
Checked: Revision: a'/'17.04.2002 / MN'
Approved: Diesel power station Drawing: K101.2828-1100

Sensor / Range Scaling Alarm / IO Memory WOIS


Ch. Text Switch Start End Unit Start End trip limit Tag name address address address Notes
Siemens S7-400/300
SM-331
Rack 1 slot 04
Analog inputs
0 MV-switchgear busbar A voltage 4-20mA 8,8 13,2 kV 8800 13200 BAM901UU12PV IW100 DB131.DBD0 Indication
BAM901UU12SF M 1.0 Sensor fault
M 15.0 Alarm
M 15.1 Alarm
1 MV-switchgear busbar A frequency 4-20mA 45 55 Hz 4500 5500 BAM901UF12PV IW102 DB131.DBD4 Indication
BAM901UF12SF M 1.1 Sensor fault
M 15.2 Alarm
M 15.3 Alarm
2 MV-switchgear busbar B voltage 4-20mA 8,8 13,2 kV 8800 13200 BAM902UU12PV IW104 DB131.DBD8 Indication
BAM902UU12SF M 1.2 Sensor fault
M 15.4 Alarm
M 15.5 Alarm
3 MV-switchgear busbar B frequency 4-20mA 45 55 Hz 4500 5500 BAM902UF12PV IW106 DB131.DBD12 Indication
BAM902UF12SF M 1.3 Sensor fault
M 15.6 Alarm
M 15.7 Alarm
4 4-20mA 0 15 Bar 0 150 IW108 DB131.DBD16 Indication
M 1.4 Sensor fault
M 16.0 Alarm
M 16.1 Alarm
5 Spare 4-20mA 0 50 cSt 0 500 IW110 DB131.DBD20 Indication
M 1.5 Sensor fault
M 16.2 Alarm
M 16.3 Alarm
6 Outdoor temp PT-100 -50 100 ºC NGA901T001PV IW112 DB131.DBD24 Indication
NGA901T001SF M 1.6 Sensor fault
M 16.4 Alarm
M 16.5 Alarm
7 (Reserved by PT-100 channel 6) IW114 DB131.DBD28 Indication
M 1.7 Sensor fault
M 16.6 Alarm
M 16.7 Alarm

Page 1/15
Department: AD Unity power plant CFA901 Code: 18V32
Drawn: MN Sudan I/O List Drawn: 10.01.2002 / MN
Checked: Revision: a'/'17.04.2002 / MN'
Approved: Diesel power station Drawing: K101.2828-1100

Sensor / Range Scaling Alarm / IO Memory WOIS


Ch. Text Switch Start End Unit Start End trip limit Tag name address address address Notes
Siemens S7-400/300
SM-331
Rack 1 slot 05
Analog inputs
0 LV-switchgear busbar A voltage 4-20 mA 300 460 V BFA901U001PV IW116 DB131.DBD32 Indication
BFA901U001SF M 2.0 Sensor fault
M 17.0 Alarm
M 17.1 Alarm
1 LV-switchgear busbar B voltage 4-20 mA 300 460 V BFA902U001PV IW118 DB131.DBD36 Indication
BFA902U001SF M 2.1 Sensor fault
M 17.2 Alarm
M 17.3 Alarm
2 DC-system 1 voltage 4-20mA 83 138 V BEY901U001PV IW120 DB131.DBD40 Indication
BEY901U001SF M 2.2 Sensor fault
M 17.4 Alarm
M 17.5 Alarm
3 DC-system 2 voltage 4-20mA 83 138 V BEY921U001PV IW122 DB131.DBD44 Indication
BEY902U001SF M 2.3 Sensor fault
M 17.6 Alarm
M 17.7 Alarm
4 Spare 4-20mA 0 100 ºC IW124 DB131.DBD48 Indication
M 2.4 Sensor fault
M 18.0 Alarm
M 18.1 Alarm
5 Spare 4-20mA 0 100 ºC IW126 DB131.DBD52 Indication
M 2.5 Sensor fault
M 18.2 Alarm
M 18.3 Alarm
6 Spare 4-20mA 0 100 ºC IW128 DB131.DBD56 Indication
M 2.6 Sensor fault
M 18.4 Alarm
M 18.5 Alarm
7 Spare 4-20mA 0 100 ºC IW130 DB131.DBD60 Indication
M 2.7 Sensor fault
M 18.6 Alarm
M 18.7 Alarm

Page 2/15
Department: AD Unity power plant CFA901 Code: 18V32
Drawn: MN Sudan I/O List Drawn: 10.01.2002 / MN
Checked: Revision: a'/'17.04.2002 / MN'
Approved: Diesel power station Drawing: K101.2828-1100

Sensor / Range Scaling Alarm / IO Memory WOIS


Ch. Text Switch Start End Unit Start End trip limit Tag name address address address Notes
Siemens S7-400/300
SM-331
Rack 1 slot 06
Analog inputs
0 4-20 mA 0 100 % IW132 DB131.DBD64 Indication
M 3.0 Sensor fault
M 19.0 Alarm
M 19.1 Alarm
1 4-20 mA 0 120 ºC IW134 DB131.DBD68 Indication
M 3.1 Sensor fault
M 19.2 Alarm
M 19.3 Alarm
2 Exhaust gas boiler 1 steam pressure 4-20mA 0 16 Bar RCA901P001PV IW136 DB131.DBD72 Indication
RCA901P001SF M 3.2 Sensor fault
M 19.4 Alarm
M 19.5 Alarm
3 Exhaust gas boiler 2 steam pressure 4-20mA 0 16 Bar RCA901P002PV IW138 DB131.DBD76 Indication
RCA901P002SF M 3.3 Sensor fault
M 19.6 Alarm
M 19.7 Alarm
4 Exhaust gas boiler 3 steam pressure 4-20mA 0 16 Bar RCA901P003PV IW140 DB131.DBD80 Indication
RCA901P003SF M 3.4 Sensor fault
M 20.0 Alarm
M 20.1 Alarm
5 Spare 4-20mA 0 100 % IW142 DB131.DBD84 Indication
M 3.5 Sensor fault
M 20.2 Alarm
M 20.3 Alarm
6 Spare 4-20mA 0 100 IW144 DB131.DBD88 Indication
M 3.6 Sensor fault
M 20.4 Alarm
M 20.5 Alarm
7 Spare 4-20mA 0 100 IW146 DB131.DBD92 Indication
M 3.7 Sensor fault
M 20.6 Alarm
M 20.7 Alarm

Page 3/15
Department: AD Unity power plant CFA901 Code: 18V32
Drawn: MN Sudan I/O List Drawn: 10.01.2002 / MN
Checked: Revision: a'/'17.04.2002 / MN'
Approved: Diesel power station Drawing: K101.2828-1100

Sensor / Range Scaling Alarm / IO Memory WOIS


Ch. Text Switch Start End Unit Start End trip limit Tag name address address address Notes
Siemens S7-400/300
SM-322
Rack 1 slot 07
24 VDC Relay output
0 Common alarm DO CFA901D035ALI Q 0.0 M 150.0 - Control

1 Common plc fault DO CFA901D036ALI Q 0.1 M 150.1 - Control

2 Synch. permission/ stop DO CFA901K103 Q 0.2 M 150.2 - Control

3 MV-switchgear busbar A parallel with grid DO CFA901K104 Q 0.3 M 150.3 - Control

4 MV-switchgear busbar B parallel with grid DO CFA901K105 Q 0.4 M 150.4 - Control

5 Bustie breaker synch. permission DO CFA901K106 Q 0.5 M 150.5 - Control

6 Spare DO CFA901K107 Q 0.6 M 150.6 Control

7 Booster unit V001 control DO PCA901V001SO Q 0.7 M 150.7 - Control

8 Booster pump 1 central start/stop DO PCA901M001STA Q 1.0 M 151.0 - Control

9 DO Q 1.1 M 151.1 - Control

10 Automatic filter control DO PCA901M003STA Q 1.2 M 151.2 - Control

11 Starting air unit compressor 1 control DO TSA901M001STA Q 1.3 M 151.3 - Control

12 Starting air unit compressor 2 control DO TSA901M002STA Q 1.4 M 151.4 - Control

13 Spare DO CFA901K114 Q 1.5 M 151.5 - Control

14 Spare DO CFA901K115 Q 1.6 M 151.6 - Control

15 Audible alarm remote reset DO CFA901K116 Q 1.7 M 151.7 - Control

Page 4/15
Department: AD Unity power plant CFA901 Code: 18V32
Drawn: MN Sudan I/O List Drawn: 10.01.2002 / MN
Checked: Revision: a'/'17.04.2002 / MN'
Approved: Diesel power station Drawing: K101.2828-1100

Sensor / Range Scaling Alarm / IO Memory WOIS


Ch. Text Switch Start End Unit Start End trip limit Tag name address address address Notes
Siemens S7-400/300
SM-322
Rack 1 slot 07
24 VDC Relay output
16 Heglig east feeder breaker synch. (BAO905) DO BAO905Q000SYN Q 2.0 M 152.0 - Control

17 Heglig west feeder breaker synch. (BAO906) DO BAO906Q000SYN Q 2.1 M 152.1 - Control

18 Bustie breaker synch. (BAB901) DO BAB901Q000SYN Q 2.2 M 152.2 - Control

19 Black start breaker Q4 synch. (BFA901) DO BFA901Q004SYN Q 2.3 M 152.3 - Control

20 Heglig east feeder breaker close control (BAO905) DO BAO905Q000CLC Q 2.4 M 152.4 - Control

21 Heglig west feeder breaker close control (BAO906) DO BAO906Q000CLC Q 2.5 M 152.5 - Control

22 Bustie breaker close control (BAB901) DO BAB901Q000CLC Q 2.6 M 152.6 Control

23 Black start breaker Q4 close control (BFA901) DO BFA901Q004CLC Q 2.7 M 152.7 - Control

24 Black start breaker Q4 open control (BFA901) DO BFA901Q004OPC Q 3.0 M 153.0 - Control

25 LV-swg. main breaker Q1 synch. (BFA901) DO BFA901Q001SYN Q 3.1 M 153.1 - Control

26 LV-swg. main breaker Q2 synch. (BFA901) DO BFA901Q002SYN Q 3.2 M 153.2 - Control

27 LV-swg. busbar breaker Q3 synch. (BFA901) DO BFA901Q003SYN Q 3.3 M 153.3 - Control

28 LV-swg. main breaker Q1 close control (BFA901) DO BFA901Q001OPC Q 3.4 M 153.4 - Control

29 LV-swg. main breaker Q2 close control (BFA901) DO BFA901Q002OPC Q 3.5 M 153.5 - Control

30 LV-swg. busbar breaker Q3 close control (BFA901) DO BFA901Q003OPC Q 3.6 M 153.6 - Control

31 Spare DO CFA901K132 Q 3.7 M 153.7 - Control

Page 5/15
Department: AD Unity power plant CFA901 Code: 18V32
Drawn: MN Sudan I/O List Drawn: 10.01.2002 / MN
Checked: Revision: a'/'17.04.2002 / MN'
Approved: Diesel power station Drawing: K101.2828-1100

Sensor / Range Scaling Alarm / IO Memory WOIS


Ch. Text Switch Start End Unit Start End trip limit Tag name address address address Notes
Siemens S7-400/300
SM-322
Rack 1 slot 08
24 VDC Relay output
0 Munga 1 feeder breaker open control (BAO901) DO BAO901Q000OPC Q 4.0 M 154.0 - Control

1 Munga 1 feeder breaker close control (BAO901) DO BAO901Q000CLC Q 4.1 M 154.1 - Control

2 Unity FSF north feeder breaker open control (BAO903) DO BAO903Q000OPC Q 4.2 M 154.2 - Control

3 Unity FSF north feeder breaker close control (BAO903) DO BAO903Q000CLC Q 4.3 M 154.3 - Control

4 Heglig east feeder breaker open control (BAO905) DO BAO905Q000OPC Q 4.4 M 154.4 - Control

5 Unity FPF 1 feeder breaker open control (BAO907) DO BAO907Q000OPC Q 4.5 M 154.5 - Control

6 Unity FPF 1 feeder breaker close control (BAO907) DO BAO907Q000CLC Q 4.6 M 154.6 Control

7 Unity FPF 2 feeder breaker open control (BAO908) DO BAO908Q000OPC Q 4.7 M 154.7 - Control

8 Unity FPF 2 feeder breaker close control (BAO908) DO BAO908Q000CLC Q 5.0 M 155.0 - Control

9 Heglig west feeder breaker open control (BAO906) DO BAO906Q000OPC Q 5.1 M 155.1 - Control

10 Unity FSF west feeder breaker open control (BAO904) DO BAO904Q000OPC Q 5.2 M 155.2 - Control

11 Unity FSF west feeder breaker close control (BAO904) DO BAO904Q000CLC Q 5.3 M 155.3 - Control

12 Munga 2 feeder breaker open control (BAO902) DO BAO902Q000OPC Q 5.4 M 155.4 - Control

13 Munga 2 feeder breaker close control (BAO902) DO BAO902Q000CLC Q 5.5 M 155.5 - Control

14 Unity FSF south feeder breaker open control (BAO909) DO BAO909Q000OPC Q 5.6 M 155.6 - Control

15 Unity FSF south feeder breaker close control (BAO909) DO BAO909Q000CLC Q 5.7 M 155.7 - Control

Page 6/15
Department: AD Unity power plant CFA901 Code: 18V32
Drawn: MN Sudan I/O List Drawn: 10.01.2002 / MN
Checked: Revision: a'/'17.04.2002 / MN'
Approved: Diesel power station Drawing: K101.2828-1100

Sensor / Range Scaling Alarm / IO Memory WOIS


Ch. Text Switch Start End Unit Start End trip limit Tag name address address address Notes
Siemens S7-400/300
SM-322
Rack 1 slot 08
24 VDC Relay output
16 Grounding trafo breaker 1 open control (BAU901) DO BAU901Q000OPC Q 6.0 M 156.0 - Control

17 Grounding trafo breaker 1 close control (BAU901) DO BAU901Q000CLC Q 6.1 M 156.1 - Control

18 Aux. trafo breaker 1 open control (BAA901) DO BAA901Q000OPC Q 6.2 M 156.2 - Control

19 Aux. trafo breaker 1 close control (BAA901) DO BAA901Q000CLC Q 6.3 M 156.3 - Control

20 Bustie breaker open control (BAB901) DO BAB901Q000OPC Q 6.4 M 156.4 - Control

21 Aux. trafo breaker 2 open control (BAA902) DO BAA902Q000OPC Q 6.5 M 156.5 - Control

22 Aux. trafo breaker 2 close control (BAA902) DO BAA902Q000CLC Q 6.6 M 156.6 Control

23 Grounding trafo breaker 2 open control (BAU902) DO BAU902Q000OPC Q 6.7 M 156.7 - Control

24 Grounding trafo breaker 2 close control (BAU902) DO BAU902Q000CLC Q 7.0 M 157.0 - Control

25 LV-swg. main breaker Q1 open control (BFA901) DO BFA901Q001OPC Q 7.1 M 157.1 - Control

26 LV-swg. main breaker Q2 open control (BFA901) DO BFA901Q002OPC Q 7.2 M 157.2 - Control

27 LV-swg. busbar breaker Q3 open control (BFA901) DO BFA901Q003OPC Q 7.3 M 157.3 - Control

28 Spare DO CFA901K161 Q 7.4 M 157.4 - Control

29 Spare DO CFA901K162 Q 7.5 M 157.5 - Control

30 Spare DO CFA901K163 Q 7.6 M 157.6 - Control

31 Spare DO CFA901K164 Q 7.7 M 157.7 - Control

Page 7/15
Department: AD Unity power plant CFA901 Code: 18V32
Drawn: MN Sudan I/O List Drawn: 10.01.2002 / MN
Checked: Revision: a'/'17.04.2002 / MN'
Approved: Diesel power station Drawing: K101.2828-1100

Sensor / Range Scaling Alarm / IO Memory WOIS


Ch. Text Switch Start End Unit Start End trip limit Tag name address address address Notes
Siemens S7-400/300
SM-321
Rack 1 slot 09
24 VDC Inputs
0 Spare DI NO I 0.0 M 45.0

1 CRO booster unit V001 in remote control mode DI NO BJM901S001CEN I 0.1 M 45.1 Control

2 CRO booster unit crude oil mode DI NO PCA901V001CRO I 0.2 M 45.2 Indication

3 CRO booster unit LFO mode DI NO PCA901V001LFO I 0.3 M 45.3 Indication

4 CRO booster unit booster pump 1 running DI NO PCA901M001ACK I 0.4 M 45.4 Indication

5 CRO booster unit booster pumps central mode DI NO PCA901M001CEN I 0.5 M 45.5 Control

6 CRO booster unit booster pump 2 running DI NO PCA901M002ACK I 0.6 M 45.6 Indication

7 DI NO I 0.7 M 45.7 Control

8 CRO booster unit automatic filter diff. press/ ctrl voltage DI NC PCA901B014HL I 1.0 M 46.0 Alarm

9 CRO booster unit common alarm DI NC BJM901S035ALI I 1.1 M 46.1 Alarm

10 CRO booster unit automatic filter flush by diff press DI NC I 1.2 M 46.2 Alarm

11 Spare DI NO I 1.3 M 46.3

12 Return fuel unit pump running DI NO PDA901M001ACK I 1.4 M 46.4 Indication

13 Return fuel unit common alarm DI NC BJI901S035ALI I 1.5 M 46.5 Alarm

14 Sludge transfer panel drain pump running DI NO DDC901M001ACK I 1.6 M 46.6 Indication

15 Sludge transfer panel common alarm DI NC BJQ901S035ALI I 1.7 M 46.7 Alarm

Page 8/15
Department: AD Unity power plant CFA901 Code: 18V32
Drawn: MN Sudan I/O List Drawn: 10.01.2002 / MN
Checked: Revision: a'/'17.04.2002 / MN'
Approved: Diesel power station Drawing: K101.2828-1100

Sensor / Range Scaling Alarm / IO Memory WOIS


Ch. Text Switch Start End Unit Start End trip limit Tag name address address address Notes
Siemens S7-400/300
SM-321
Rack 1 slot 10
24 VDC Inputs
0 Sludge loading pump running DI NO BJV901M001ACK I 2.0 M 47.0 Indication

1 Sludge loading pump unit common alarm DI NC BJV901S035ALI I 2.1 M 47.1 Alarm

2 Oily water transfer unit pump running DI NO BJU901M001ACK I 2.2 M 47.2 Indication

3 Oily water transfer unit common alarm DI NC BJU901S035ALI I 2.3 M 47.3 Alarm

4 Spare DI NO I 2.4 M 47.4

5 Siclock common alarm DI NC I 2.5 M 47.5

6 ESM common alarm (Wois 1) DI NC I 2.6 M 47.6

7 ESM common alarm (Wois 2) DI NC I 2.7 M 47.7

8 Busbar B voltage supervision DI NO BAM902S014ACK I 3.0 M 48.0 Control

9 MCB open in CFA901 DI NC CFA901F000MCB I 3.1 M 48.1 Alarm

10 Busbar A voltage supervision DI NO BAM901S014ACK I 3.2 M 48.2 Control

11 Synchronizer in auto position DI NO CFA901S006AUI I 3.3 M 48.3 Control

12 Synchronizing on DI NO CFA901S006ACK I 3.4 M 48.4 Control

13 Saco unit IRF DI NC CFA901S022ALI I 3.5 M 48.5 Alarm

14 Alarm acknowledge DI NC CFA901S018ALI I 3.6 M 48.6 Control

15 ESM common alarm (Panel) DI NC I 3.7 M 48.7

Page 9/15
Department: AD Unity power plant CFA901 Code: 18V32
Drawn: MN Sudan I/O List Drawn: 10.01.2002 / MN
Checked: Revision: a'/'17.04.2002 / MN'
Approved: Diesel power station Drawing: K101.2828-1100

Sensor / Range Scaling Alarm / IO Memory WOIS


Ch. Text Switch Start End Unit Start End trip limit Tag name address address address Notes
Siemens S7-400/300
SM-321
Rack 1 slot 11
24 VDC Inputs
0 Starting air unit compressor 1 running DI NO TSA901M001ACK I 4.0 M 49.0 Indication

1 Starting air unit compressor 2 running DI NO TSA901M002ACK I 4.1 M 49.1 Indication

2 Starting air unit manual mode DI NO BLA901S001MAI I 4.2 M 49.2 Control

3 Starting air unit common alarm DI NC BLA901S035ALI I 4.3 M 49.3 Alarm

4 Control & working air unit compressor running DI NO TCA901M001ACK I 4.4 M 49.4 Indication

5 Control & working air unit common alarm DI NC BLB901S035ALI I 4.5 M 49.5 Alarm

6 Control & working air unit low pressure alarm DI NO bar 4 I 4.6 M 49.6 Alarm

7 Spare DI NO I 4.7 M 49.7

8 Black start unit common alarm DI NC BLM901S035ALI I 5.0 M 50.0 Alarm

9 Black start unit generator running DI NO SAB901S007ACK I 5.1 M 50.1 Indication

10 LV-swg main breaker Q1 open (BFA901) DI NO BFA901Q001OPN I 5.2 M 50.2 Indication


BFA901Q001ALI M 124.0 Alarm
11 LV-swg main breaker Q1 closed (BFA901) DI NO BFA901Q001CLO I 5.3 M 50.3 Indication

12 LV-swg main breaker Q1 fault (BFA901) DI NC BFA901Q001ALM I 5.4 M 50.4 Alarm

13 LV-swg main breaker Q2 open (BFA901) DI NO BFA901Q002OPN I 5.5 M 50.5 Indication


BFA901Q002ALI M 124.1 Alarm
14 LV-swg main breaker Q2 closed (BFA901) DI NO BFA901Q002CLO I 5.6 M 50.6 Indication

15 LV-swg main breaker Q2 fault (BFA901) DI NC BFA901Q002ALM I 5.7 M 50.7 Alarm

Page 10/15
Department: AD Unity power plant CFA901 Code: 18V32
Drawn: MN Sudan I/O List Drawn: 10.01.2002 / MN
Checked: Revision: a'/'17.04.2002 / MN'
Approved: Diesel power station Drawing: K101.2828-1100

Sensor / Range Scaling Alarm / IO Memory WOIS


Ch. Text Switch Start End Unit Start End trip limit Tag name address address address Notes
Siemens S7-400/300
SM-321
Rack 2 slot 04
24 VDC Inputs
0 LV-swg busbar breaker Q3 open (BFA901) DI NO BFA901Q003OPN I 6.0 M 51.0 Indication
BFA901Q003ALI M124.2
1 LV-swg busbar breaker Q3 closed (BFA901) DI NO BFA901Q003CLO I 6.1 M 51.1 Indication

2 LV-swg busbar breaker Q3 fault (BFA901) DI NC BFA901Q003ALM I 6.2 M 51.2 Alarm

3 LV-swg black start generator breaker Q4 open (BFA901) DI NO BFA901Q004OPN I 6.3 M 51.3 Indication
BFA901Q004ALI M 124.3
4 LV-swg black start generator breaker Q4 closed (BFA901) DI NO BFA901Q004CLO I 6.4 M 51.4 Indication

5 LV-swg black start generator breaker Q4 fault (BFA901) DI NC BFA901Q004ALM I 6.5 M 51.5 Alarm

6 LV-swg common alarm DI NC BFA901S035ALI I 6.6 M 51.6 Alarm

7 Spare DI NO I 6.7 M 51.7

8 Spare DI NO I 7.0 M 52.0

9 MV-swg busbar A parallel with grid DI NO CFA901K037ACK I 7.1 M 52.1 Control

10 LV-swg Black start breaker Q4 synchronizing on DI NO CFA901K062ACK I 7.2 M 52.2 Control

11 MV-swg bustie breaker BAB901 synchronizing on DI NO CFA901K057ACK I 7.3 M 52.3 Control

12 MV-swg breaker BAO905 synchronizing on DI NO CFA901K052ACK I 7.4 M 52.4 Control

13 MV-swg breaker BAO906 synchronizing on DI NO CFA901K055ACK I 7.5 M 52.5 Control

14 Power plant shutdown DI NC CFA901S020EST I 7.6 M 52.6 Shutdown

15 MV-swg busbar B parallel with grid DI NO BFA902S035ALI I 7.7 M 52.7 Alarm

Page 11/15
Department: AD Unity power plant CFA901 Code: 18V32
Drawn: MN Sudan I/O List Drawn: 10.01.2002 / MN
Checked: Revision: a'/'17.04.2002 / MN'
Approved: Diesel power station Drawing: K101.2828-1100

Sensor / Range Scaling Alarm / IO Memory WOIS


Ch. Text Switch Start End Unit Start End trip limit Tag name address address address Notes
Siemens S7-400/300
SM-321
Rack 2 slot 05
24 VDC Inputs
0 110 VDC system BEY901 common alarm DI NC BEY901S035ALI I 8.0 M 53.0 Alarm

1 110 VDC system BEY902 common alarm DI NC BEY902S035ALI I 8.1 M 53.1 Alarm

2 Spare DI NO I 8.2 M 53.2

3 Heglig east (BAO905) voltage supervision DI NO BAO905U001ACK I 8.3 M 53.3

4 Heglig west (BAO906) voltage supervision DI NO BAO906U001ACK I 8.4 M 53.4

5 LV-swg main breaker Q1 synchronizing on DI NO CFA901K203ACK I 8.5 M 53.5 Control

6 LV-swg main breaker Q2 synchronizing on DI NO CFA901K206ACK I 8.6 M 53.6 Control

7 LV-swg busbar breaker Q3 synchronizing on DI NO CFA901K0209ACK I 8.7 M 53.7 Control

8 Fire alarm, common alarm (XA-101) DI NO I 9.0 M 54.0 Alarm

9 Fire alarm, common fault (XA-102) DI NO I 9.1 M 54.1 Alarm

10 Fire alarm, engine hall (XA-103) DI NO I 9.2 M 54.2 Alarm

11 Fire alarm, control room (XA-104) DI NO I 9.3 M 54.3 Alarm

12 Fire alarm, work shop (XA-105) DI NO I 9.4 M 54.4 Alarm

13 Fire alarm, MV house (XA-106) DI NO I 9.5 M 54.5 Alarm

14 Fire alarm, booster/ fuel oil unit (XA-107) DI NO I 9.6 M 54.6 Alarm

15 Fire alarm, fuel treatment house (XA-108) DI NO I 9.7 M 54.7 Alarm

Page 12/15
Department: AD Unity power plant CFA901 Code: 18V32
Drawn: MN Sudan I/O List Drawn: 10.01.2002 / MN
Checked: Revision: a'/'17.04.2002 / MN'
Approved: Diesel power station Drawing: K101.2828-1100

Sensor / Range Scaling Alarm / IO Memory WOIS


Ch. Text Switch Start End Unit Start End trip limit Tag name address address address Notes
Siemens S7-400/300
SM-321
Rack 2 slot 06
24 VDC Inputs
0 Synch selected in HV switchyard/ interlock DI NO I 10.0 M 55.0 Control

1 Spare DI NO I 10.1 M 55.1

2 Spare DI NO I 10.2 M 55.2

3 Spare DI NO I 10.3 M 55.3

4 Spare DI NO I 10.4 M 55.4

5 Spare DI NO I 10.5 M 55.5

6 Spare DI NO I 10.6 M 55.6

7 Spare DI NO I 10.7 M 55.7

8 Spare DI NO I 11.0 M 56.0

9 Spare DI NO I 11.1 M 56.1

10 Spare DI NO I 11.2 M 56.2

11 Spare DI NO I 11.3 M 56.3

12 Spare DI NO I 11.4 M 56.4

13 Spare DI NO I 11.5 M 56.5

14 Spare DI NO I 11.6 M 56.6

15 Spare DI NO I 11.7 M 56.7

Page 13/15
Department: AD Unity power plant CFA901 Code: 18V32
Drawn: MN Sudan I/O List Drawn: 10.01.2002 / MN
Checked: Revision: a'/'17.04.2002 / MN'
Approved: Diesel power station Drawing: K101.2828-1100

Sensor / Range Scaling Alarm / IO Memory WOIS


Ch. Text Switch Start End Unit Start End trip limit Tag name address address address Notes
Siemens S7-400/300
SM-321
Rack 2 slot 07
24 VDC Inputs
0 Exhaust gas boiler 1 water level high DI NC RCC901L001LAH I 12.0 M 57.0 Alarm

1 Exhaust gas boiler 1 water level low DI NC RCC901L001LAL I 12.1 M 57.1 Alarm

2 Exhaust gas boiler 1 pressure high DI NC RCC901P002PAH I 12.2 M 57.2 Alarm

3 Exhaust gas boiler 2 water level high DI NC RCC902L001LAH I 12.3 M 57.3 Alarm

4 Exhaust gas boiler 2 water level low DI NC RCC902L001LAL I 12.4 M 57.4 Alarm

5 Exhaust gas boiler 2 pressure high DI NC RCC902P002PAH I 12.5 M 57.5 Alarm

6 Exhaust gas boiler 3 water level high DI NC RCC903L001LAH I 12.6 M 57.6 Alarm

7 Exhaust gas boiler 3 water level low DI NC RCC903L001LAL I 12.7 M 57.7 Alarm

8 Exhaust gas boiler 3 pressure high DI NC RCC903P002PAH I 13.0 M 58.0 Alarm

9 Exhaust gas boiler feed water tank low level DI NC RBA901L001LAL I 13.1 M 58.1 Alarm

10 Exhaust gas boiler feed water tank low low level DI NC RBA901L003LALL I 13.2 M 58.2 Alarm

11 Exhaust gas boiler feed water pump 1 running DI NO RBB901M001ACK I 13.3 M 58.3 Indication

12 Exhaust gas boiler feed water pump 1 fault DI NC RBB901M001MCF I 13.4 M 58.4 Alarm

13 Exhaust gas boiler feed water pump 2 running DI NO RBB901M002ACK I 13.5 M 58.5 Indication

14 Exhaust gas boiler feed water pump 2 fault DI NC RBB901M002MCF I 13.6 M 58.6 Alarm

15 Exhaust gas boiler container cooling fan running DI NO RHC901M001ACK I 13.7 M 58.7 Indication

Page 14/15
Department: AD Unity power plant CFA901 Code: 18V32
Drawn: MN Sudan I/O List Drawn: 10.01.2002 / MN
Checked: Revision: a'/'17.04.2002 / MN'
Approved: Diesel power station Drawing: K101.2828-1100

Sensor / Range Scaling Alarm / IO Memory WOIS


Ch. Text Switch Start End Unit Start End trip limit Tag name address address address Notes
Siemens S7-400/300
SM-321
Rack 2 slot 08
24 VDC Inputs
0 Exhaust gas boiler container cooling fan fault DI NC RHC901M001MCF I 14.0 M 59.0 Alarm

1 Exhaust gas boiler oily water alarm DI NC RDD901Q001CAH I 14.1 M 59.1 Alarm

2 DI NO I 14.2 M 59.2 Indication

3 DI NC I 14.3 M 59.3 Alarm

4 Aux. boiler level high DI NC RCE901L001LAH I 14.4 M 59.4 Alarm

5 Aux. boiler level low DI NC RCE901L001LAL I 14.5 M 59.5 Alarm

6 Aux. boiler level low low DI NC RCE901L001LALL I 14.6 M 59.6 Alarm

7 Aux. boiler pressure high DI NC RCE901P001PAH I 14.7 M 59.7 Alarm

8 Aux. boiler oil burner running DI NO RCE901M001ACK I 15.0 M 60.0 Indication

9 Aux. boiler oil burner fault DI NC RCE901M001ALI I 15.1 M 60.1 Alarm

10 Day tank level low DI NC PBD901 I 15.2 M 60.2 Alarm

11 Spare DI NO I 15.3 M 60.3

12 Spare DI NC I 15.4 M 60.4

13 Spare DI NO I 15.5 M 60.5

14 Spare DI NC I 15.6 M 60.6

15 Spare DI NO I 15.7 M 60.7

Page 15/15