Professional Documents
Culture Documents
Fire-Design Manual - by Mahboob Shaikh
Fire-Design Manual - by Mahboob Shaikh
DESIGN MANUAL
FOR
FIRE PROTECTION AND
DETECTION SYSTEMS
Sprinkler System
Standpipe System
Foam System
NFPA 13
(Standard for Installation of Sprinkler System/2013)
(Chapter 23)
COMPLETE GUIDE ON
PLANS
&
CALCULATIONS
Basics of Hydraulics
Hydraulic Calculation- PRILIMINARY CONCEPTS
Hydraulic Calculation –EXAMPLE CALCULATION (MANUAL+
SOFTWARE)
Hydraulic Calculation Considerations for Storage Sprinklers
– CMDA/CMSA/ESFR Sprinklers
– In Rack Sprinklers
Plan Review Checklists
CONTENT
BASICS OF HYDRAULICS
PRESSURE FLOW
2
62.4 lbs/ft 2
0.433 lbs/in
1 ft 1 ft
A cubic foot of water results in a static pressure at its base of 62.4 lbs/ft2
Converted to square inches a column of water 1-foot high exerts a
pressure of 0.433 lbs/in2
15 ft
5 ft
Example : 02
What is the pressure at the hydrant?
Pressure (psi) = 0.433 x Elevation (ft)
P 0.433 x 200 ft
P 90.93psi
P 91 psi
0.001123Q2
Pv 4
di
• When velocities are high in a closed system the pressure needs to
be accounted for in the calculations.
• It can reduce the flows and pressures needed in a system 5-10
percent.
• In most sprinkler systems velocities are low and their pressures
create a minor effect, therefore velocity pressures can be ignored.
• It should be used at points where large flows take a 90-degree turn
in the piping.
FLOW :
Q=AxV
Q = Flow in ft3/sec
A = Cross sectional area of pipe in ft2
V = Water velocity in ft/sec
Q is a constant for any given closed system.
Q = A1 x V 1 = A2 x V 2
A 1 x V 1 = A2 x V 2
If water is flowing at 5.7 ft/sec in 6-inch pipe, how fast is it flowing when
the pipe size is reduced to 3-inch?
Solution :
𝐴1 X 𝑉1
V2 =
𝐴2
2 2 2
A = r = (3 in) = 28.3 in
1
2 2 2
A = r = (1.5 in) = 7.1 in
2
(28.3in2 )(5.7ft/sec)
V2 22.7ft/sec
7.1in2
V2 = 22.7 ft/sec
Q 29.83 di Pv CD
2
Note : This is used when testing water supplies to determine the amount
of flow
Q k P
Where:
Q is flow (gpm)
k is k-factor determined in the sprinkler listing (gpm/psi½)
P is the pressure (psi)
• The diameter of the opening and discharge coefficient are
incorporated into the empirical determination of k-factor.
Solution :
Q k P
Q 5.6 20 psi
Q 25.0 gpm
Example : 05
What is the pressure for a sprinkler that has a k-factor of 17.6 and the
expected flow is 83 gpm?
Solution :
2
Q
P
k
2
83 gpm
P
17.6
Solution :
Q
k
P
65 gpm
k
30 psi
65
k 11.86
5.48
Hydraulic Calculation
(PRILIMINARY CONCEPTS)
Hazen-Williams formula
– Fire sprinkler systems
– Water-spray systems
Darcy-Weisbach formula
(The Darcy-Weisbach equation more accurately accounts for the
effects of turbulence, temperature, and viscosity )
– Anti-freeze systems
– Water mist systems
– Foam-water systems
Fanning formula
4.52Q1.85
PL 1.85 4.87
C di
Where:
PL = friction loss (psi/ft)
Q = flow (gpm)
C = roughness coefficient (based on pipe material)
di = interior pipe diameter (inches)
40 ?
Solution :
4.52Q1.85 4.52(110gpm)1.85
PL 1.85 4.87
C di (120)1.85(2.067in)4.87
PL = 0.112 psi/ft
Friction Loss = 0.112 psi/ft x 32 ft = 3.6 psi
4.87
Actual inside diameter
Factor
Schedule 40 Steel Pipe inside diameter
What is the equivalent pipe length of Type K copper tube which used for
a 3-inch standard turn 90-degree elbow?
Solution:
– Type K Copper
– Interior diameter
4.87
4.87
Actual i.d. 2.907
Factor 0.77
Schedule 40 Steel Pipe i.d. 3.068
Hydraulic Calculation
STEP BY STEP PROCEDURE
MANUAL + ELITE SOFTWARE
9. Hydraulic Calculations
9.1 Identify hazard category
9.2 Determine sprinkler spacing
9.3 Determine piping arrangement
9.4 Calculate amount of water needed per sprinkler
9.5 Calculate number and location of open sprinklers in
the hydraulically most demanding area
9.6 Start at most remote sprinkler and work towards the
water supply calculating flows and pressures
9.7 Compare demand with supply
10. Notes and Details for Plans
11. As-Built Drawings
Plan view
200 FT.
Elevation view
18 FT.
200 FT.
info@mitionline.com Design|Inspection|Training Mehboob Shaikh | +919146861270
MECHSOFT ENGINEERING DESIGN AND CONSULTANCY
z
100 FT.
200 FT.
Mains and branches are Sch 40
pipes
15 FT.
Isometric View
1
2
5 Area of operation have
3 1-inch been reduced in
1 ½-inch accordance with cl.
1 ¼-inch 6 11.2.3.2.3
4
1 ¼-inch 7
1 ½-inch 8
BL1
3-inch
Riser
- 3x
y 55
2
3(18)
y 55
2
54
y 55 28%
2
Area of Coverage = S x L
Area of Coverage = 10 x 12.5
Area of Coverage = 125 Sq. ft.
𝐷𝑒𝑠𝑖𝑔𝑛 𝐴𝑟𝑒𝑎
No. of Sprinklers in the design area =
𝐴𝑟𝑒𝑎 𝑜𝑓 𝐶𝑜𝑣𝑒𝑟𝑎𝑔𝑒
1080
No. of Sprinklers in the design area =
125
No. of Sprinklers in the design are = 9 Sprinklers
Data Summary :
Main Path :
1 2 3 4 BL1 BL2
BL3 TOR
Auxillary Paths-1 :
5 6 7 8 BL2
Auxillary Paths-2 :
6 BL3
18.8 gpm @
11.3 psi
19.95 gpm
@ 12.69 psi
84..36 gpm
@ 27.28 psi
28.33 gpm
21.3 gpm @
@ 27.71psi
14.4 psi
84.36 gpm
@ 24.38 psi
N 197.07 gpm
@ 41.41 psi
System Demand
197 gpm @ 41.40 psi
Flow (gpm)
ELITE SOFTWARE
CALCULATION
Print Report
Therefore,
Design area = Allowable area per sprinkler x no. of sprinkler in the design
area
Design Area = 100 x 15
Design Area = 1500 SF
Depends on,
In accordance, 17.1.5.6
In accordance, 18.5.3
Depends on,
– Type of sprinklers at the ceiling ( CMSA/ESFR)
Min. Q = 30 GPM
Hence for k = 5.6 , P = 28.7 psi
for k = 8.0 , P = 14.1 psi
for k = 11.2 , P = 7.2 psi
• 18.5.4
– 30 psi
– 30.7 gpm for k‐5.6 sprinkler
– 43.8 gpm for k‐8.0 sprinkler
– 61.3 gpm for k‐11.2 sprinkler
Example- 11 :
1
2
B 3
4
5
6
7
8
9
10
A
10
Ceiling
– 665 GPM @ 84 PSI
In Rack
– 247 at 75 PSI
– Calculate the two demands separately from the most remote point
to the node where they connect
– Apply the k‐factor to the higher pressure to get the new flow:
Step 01 :
– Calculate the two demands separately from the most remote point
to the node where they connect
Step 02 :
– Get the k‐factor for the lower pressure situation
𝑄
K=
𝑆𝑞.𝑟𝑡 𝑃
247
K=
𝑆𝑞.𝑟𝑡 75
K = 28.52
Step 03 :
Apply the K‐factor to the higher pressure,
Q = K X Sq. rt (P)
Q = 261.4 GPM
Step 04:
Add the flows together
– In‐Racks: 262 gpm at 84 psi
– Ceiling: 665 gpm at 84 psi To In Ceiling Level Sprinklers
To In Rack Sprinklers
Project address:
______________________________________________________________________
Owner’s name:
______________________________________________________________________
Contractor address:
______________________________________________________________________
______________________________________________________________________
• Type of system being installed: Wet___ Dry ___ Preaction ___ Deluge_____________
•Building description:
Square footage of the project: ________________________
Use of building: __________________________ Building height: __________________
Total area of building: _____________________ Area per floor: ___________________
Total number for floors above grade: __________ below grade: ___________________
– Class I
– Class II
– Class III
– Class IV
– Group A
– Group B
– Group C
YES NO
– __ Name of owner or occupant
– __ Location, including street address
– __ Point of compass
– __ Full height cross section
– __ Ceiling/roof heights and slopes not shown in the full height cross section
– __ Location of partitions
– __ Location of fire walls
– __ Occupancy class of each area or room
– __ Location and size of concealed spaces, closets, attics, and bathrooms
– __ Small enclosures in which no sprinklers are to be installed
– __ Scale the plans were drawn to
_____Capacity is verified at _______ gpm (L/min) for a duration of ______ hours for a
total capacity of ______ gal (L)
YES NO
_ _ Location and elevation of static and residual hydrants in relationship to the riser
location
_ _ Date and time of flow test (must be within one year of design)
_ _ Static, residual, and flow from test
_ _ Name of person who conducted or source of water supply information
Fire Pump
– Electric
– Diesel
– Steam
– N/A
Rated Capacity: ____________________
Water Tank
– Steel
– Wood
– Concrete
– Wet
– Dry
– Preaction
– Deluge
• Classification of occupancy:
– Light hazard
– Ordinary: Group 1 _ Group 2 _
– Extra hazard: Group 1 _ Group 2 _
– Class I
– Group A plastic
– Class II
– Group B plastic
– Class III
– Group C plastic
– Class IV
– Mixed commodity
Reinforced _
Unreinforced _
STEP 6: DESIGN
The following information has been clearly indicated on plans / specifications / hydraulic
calculations:
– Type of system:
– Hydraulically calculated
– Pipe schedule
– Density/area method
– Area of operation and density noted?
– Area of operation reduced for:
– Quick-response sprinklers
– High-temperature sprinklers
– Area of operation increased for: Sloped ceilings
– Dry pipe/double-interlock preaction systems _
– Multiple adjustments needed?
STEP 8: ALARMS
f. Date.
g. Time.
h. Test conducted by or information supplied by.
INDIVIDUAL PLANS
Plot or Site Plan
Description Yes No NA
Mains
Description Yes No NA
Size of FDC indicated and per code, both inlets and outlets.
END OF DOCUMENT
250 GPM C
250 GPM @ 100 psi A
250 GPM B
45’ of 4” pipe
10’
750 GPM
D 500 GPM
Building with250’
Five Standpipes
200’ of 4” Sch 40 pipe of 4” Sch 40
pipe
T
Transition point between AG and UG Piping Cement line Di pipe D = 6” & L = 75’
To Water Supply U
Node A
Node O ( outlet of
Right angle valve)
1’ of 2.5” pipe
B
Flow @ Node O = 250 GPM
Step 03 Step 04
Factor = 1.08
Pt 109.48
Pt 114.01
Pt 150.34
Pt 185.90
Class II standpipe systems are much easier to calculation than Class I (or Class III) systems.
Example :
Assume, piping between the water supply and the most remote hose station has
following details
Diameter = 1.5 “
Length = 200’ ( Including Eq. Fittings)
Friction loss per ft of pipe flowing 100 GPM = 0.317 psi ( refer below graph)
Pressure Required at the water supply source = Pressure demand @ remote hose
station + Pressure loss along length of pipe
FOAM SYSTEM
Hydraulic Calculations :
Q = k x (P)^(1/2)
K = Q/(P)^1/2
K = 13/(30)^(1/2) = 2.3
Therefore ;
P = (Q /k)^2
P = (16/3)^2
P = 28.44 < Min. Operating Pressure ( Refused)
10 = 0.4085 x 16.4/d^2
d = 0.8 inch say 1 Inch.
10 = 0.4085 x 32.4/d^2
d = 1.15 inch say 1.5 Inch.
10 = 0.4085 x 65.6/d^2
d = 1.63 inch say 2 Inch.
10 = 0.4085 x 98.4/d^2
d = 2.004 inch say 2 inch
32.6 GPM
16.4 GPM 16.4 GPM
65.6 GPM
16.4 GPM 16.4 GPM
1 inch 1 inch
1.5 inch
1 inch 1 inch
2 inch
1 inch 1 inch
2 inch
DV 2 inch
1
2
5 4
DV
6
MITI Consultancy Design|Inspection|Training info@mitionline.com
Pressure Loss Calculation Sheet
1. Installation Identification
2. Hazard Classification and Description
3. Liquid Identification
4. Type of Protection
5. Surface Area of Liquid to be protected
6. Foam agent Selected
7. Description, Number & Placement of Foam
application devices
8. Foam solution application Rate
9. Foam Concentrate Supply Rate
10. Water Supply Rate
11. Duration of Discharge
12. Total Quantity of Water required
13. Pipe Size Determination
14. Valve Selection and Location
15. Foam Propotioner Selection
16. Pump Consideration
17. Hydraulic Calculation
17.1 – Starting point
17.2 – Determination of Supply Riser Size
17.3 – Determination of Friction losses.
17.4 - Summary
Example Project
= ∏/4 (d)^2
= 11310 SF
Q=AxV
V = 0.4085 x Q (gpm) / d^2(inches)
10 = 0.4085 x 566/d^2
FL = 0.0420 psi/ft
Q=AxV
10 = 0.4085 x 1132/d^2
Foam Propotioner
5 1132 GPM @ 94.26 psi
psi
SUBJECT : Fixed foam System for flammable liquid atmospheric storage tank
HAZARD : 120-ft-diameter outdoor cone roof flammable liquid storage tank
Flammable or combustible liquid identification: Gasoline—SG 0.72
Foam agent selected: Fluoroprotein—3%
Duration of discharge: 55 min
Foam
Make Added Total Pipe & Eq. Propotioner Required
Pipe size Friction Static Psi
type and GPM GPM fitting Length Psi Press, GPM
location
Psi/ft Total Psi
Ref: NFPA 13, FL =
Table 4.52*Q^1.85/C^1.85*
23.4.3.1.1 d^4.87
1 566 566 50
Pump Capacity = Required Pressure(Considering Frictional,elevation Losses)- Available Pressure from city supply(if any)
Plan view
8 Meter
2.5 mtr
Elevation view
8 Mtr.
V=lxbxh
V = 8 x 4.25 x 2.5
V(Gross)= 85 Cubic Meter.
Volume of Any Impermiable Member such as Fixed Solid objects etc.
V1 = 0 Cubic Meter ( assuming there is no such member in the room)
V(net) = V – V1 = 85 – 0 = 85 Cubic Meter.
Altitude : 1500 Mtr.
𝑉 𝐶
Agent Quantity (w) = 𝑆 (100−𝐶 )
85 8.4
Agent Quantity (w) = 0.1362 (100−8.4)
W = 57.23 kg
W = 48 kg.
W = 48 kg
𝒘 𝒙𝒔
( )
𝑪 = 𝟏𝟎𝟎 𝒘 𝒙𝒔𝑽
( )+𝟏
𝑽
Where;
Q = Agent quantity supplied from the system [kg]
V = hazard volume [m³]
s = specific vapor volume [m³/kg] = k1+k2*T
T = Min./Max. hazard temperature [°C]
S = k1+k2xT
S = k1+k2x20
S = 0.1268+ 0.0005133 x 20
S = 0.1362 for min. Temp.
S = k1+k2xT
S = k1+k2x30
S = 0.1268+ 0.0005133 x 30
S = 0.1423 for Max. Temp.
(𝟎. 𝟎𝟖𝟒𝟐𝟒)
𝑪 = 𝟏𝟎𝟎
(𝟎. 𝟎𝟖𝟒𝟐𝟒) + 𝟏
𝑪 = 𝟕. 𝟕 % @ 20 C Min. Temp.
𝟓𝟒𝒙𝟎. 𝟏𝟒𝟐𝟑
( )
𝑪 = 𝟏𝟎𝟎 𝟖𝟓
𝟓𝟒 𝒙𝟎. 𝟏𝟒𝟐𝟑
( )+𝟏
𝟖𝟓
(𝟎. 𝟎𝟗𝟎𝟒𝟎)
𝑪 = 𝟏𝟎𝟎
(𝟎. 𝟎𝟗𝟎𝟒𝟎) + 𝟏
𝑪 = 𝟖. 𝟐𝟗 % @ 30 C Max. Temp
Note :Unless a hydraulic flow calculation is done, approximate 80% of the max. filling
should be used to determine a container size (Recommanded practices from
Manufacturers)
Discharge Nozzles
Discharge Ports
4.53 Mtr.
2.25 Mtr.
4.5 Mtr.
4 Mtr.
5.9 Mtr.
4 Mtr.
8 Meter
𝑽𝒐𝒍𝒖𝒎𝒆 𝒐𝒇 𝑯𝒂𝒛𝒂𝒓𝒅
Number of Nozzles =
𝑪𝒐𝒗𝒆𝒓𝒂𝒈𝒆 𝑨𝒓𝒆𝒂 𝒐𝒇 𝑬𝒂𝒄𝒉 𝑵𝒐𝒛𝒛𝒐𝒍𝒆
𝟖𝟓
Number of Nozzles(360° or 180°) =
𝟗𝟓.𝟑
Piping arrangment :
5 2
1
4 1
E1N1
1
3
Connection Details 1
between container 1
outlet and pipe
Plan view
20 Mtr.
Min. Temp = 20 C
Max. Temp. = 54 C
False Ceiling
HVAC Duct = 5% of total volume
Elevation
3 Mtr.
Computer Room
Battery Room
1 Mtr.
Elevation
1 Mtr.
Elevation
10 ft..
7 ft..
20 ft..
10 ft.
Room Wall-2
3 Mtr.
Skid is away by 1
Mtr. From each wall
Distance from
Distance of equipment equipment to virtual
from wall boundary
Therefore, Design Rate of CO2 = Protected Volume x Flow rate (from above graph)
= 97.5 cubic Mtr x 10 kg/ Cubic Mtr x Min.
Therefore,
The number of 45.4 kg high pressure CO2 Cylinder = 649/45.4 = 14.3 say 15
Number of Cylinder = 15
Dimensions
Length = 2.13 m
Width = 2.44 m ( open Front)
Height = 1.83 m
L = 1.52 m
W = 1.22 m
H = 1.22
Solution:
𝑄 1000
= = 234 lb/min.in2
𝐷^2 4.28
𝐿 500
= = 201 lb/min.in2
𝐷^1.25 2.48
𝑄 500
= = 193 lb/min.in2
𝐷^2 2.592
𝐿 200
= = 110 lb/min.in2
𝐷^1.25 1.813
500
Equivalent Orifice area = = 0.5482 Sq. Inch( Diameter will be 0.83 inch.)
912
Initial Considerations :
Pressure Required at the top of the structure = 100 psi (NFPA 14)
Height of the building ( 212’ x 0.433) = +92 psi
Friction loss in the piping = +10 psi
1. Total Pressure required for System = 202 psi
Residual pressure at street = 35 psi
Backflow Losses = -7 psi
Water Meter = -3 psi
Elevation Changes = 0 psi
Friction Loss in Suction Piping = -3 psi
2. Available Suction Pressure at Pump = 22 psi
200
150
140
65
50
Overload Point
Size Selection normally varies from 90% to 140% of rated capacity & Pressure
Standpipe Outlet
75 feet
Pump
Rated Pressure for 750 GPM (as per the Manufacturer Curve)
= 115 psi
Step- 05 : Add the suction flow (at the demand flow) to get the
discharge pressure (at demand flow
Shut off Pressure ( Churn Pressure) = 149 psi @ 0 GPM
Net Pressure @ 750 GPM = 115 psi
Net Pressure @ 1000 GPM = 92 psi (@ demand flow)
Net Pressure @ 1125 GPM = 80 psi (@ 150% of demand flow)
Rated Pressure for 1000 GPM (as per the Manufacturer Curve)
= 115 psi
Solution :
System Demand = 1400 GPM
Required pump capacity = 1400/150% = 933 GPM say 1000 GPM
1400 GPM would be 140% of rated capacity. (refer Manufacturer
curve for exact value)
Hence, Pump Rating should not be less than 1000 GPM @ 125
psi.
Type of Systems
1. Class 1 Manual Wet type
2. Wet Pipe Sprinkler System
3. Dry Pipe Sprinkler System
A detailed Hydraulic calculation shall be performed on a software in order to determine flow and pressure
requirement in multiple Hazard area based on above given table.
Therefore;
New area of operation = 1500 x 1.3 =1950 SF
Density = 0.15 gpm /sf
10 Times Rule :
Flat Side Up
Discharge Pipe
250 3½ 3 2 2½ 3½ 1-2 ½ 3
500 5 5 3 5 5 2-2 ½ 4
750 6 6 4 6 5 3- 2½ 6
1000 8 6 4 8 6 4-2 ½ 6
1250 8 8 6 8 6 6-2 ½ 8
1500 8 8 6 8 8 6-2 ½ 8
JP
Antivortex Plate
EP DP
MITI Consultancy Design|Inspection|Training info@mitionline.com
MITI Consultancy Design|Inspection|Training info@mitionline.com
Fire Alarm System Secondary Battery -Set Calculation Worksheet
TOTAL STANDBY
STANDBY CURRENT ALARM CURRENT TOTAL ALARM
ITEM DESCRIPTION QTY CURRENT PER QTY
PER UNIT(AMPS) PER UNIT(AMPS) CURRENT ITEM
ITEM
FACP Fire alarm Control Panel 0.2500 X 1 0.2500 0.5000 X 1 0.5000
ANN Annunciator 0.1250 X 1 0.1250 0.2500 X 1 0.2500
SMOKE Smoke detector 0.0001 X 100 0.0100 0.0010 X 100 0.1000
HEAT Heat Detector - X 10 - 0.0010 X 10 0.0100
PULL Pull Station - X 14 - 0.0010 X 14 0.0140
BELL FDC Bell - X 3 - 0.0500 X 3 0.1500
HORN Horn - X 20 - 0.0500 X 20 1.0000
STROBE Strobe - X 40 - 0.1000 X 40 4.0000
H/S Horn/Strobe - X 20 - 0.1500 X 20 3.0000
0 0 - X 0 - - X 0 -
0 0 - X 0 - - X 0 -
0 0 - X 0 - - X 0 -
0 0 - X 0 - - X 0 -
Total System Standby Current(Amps) 0.3850 Total System Alarm Current(Amps) 9.0240
Step No. 01 :
1.1. Calculate length of wire from fire alarm control panel to the end of fire alarm
circuit.
1.2. Calculate Wire Size and resitance using NEC(NFPA 70-2017); Ch.09; Table 8
Step No. 02 :
Calculate Total Resistance for NAC
Step No. 03 :
Calculate Total Amperage for alarm notification devices
Step No. 04 :
Calculate Total Volatage Drop for branch circuit.
Step No. 05 :
Determine if enough voltage is available to operate fire Alarm notification devices
Example
Step 01 :
Wire length from control panel to end of Circuit = 500 ft. x 2(Postive+ Negative)
= 1000 ft.
Wire Guage = 12 AWG / 1.98 ohms per 1000 ft. ( NEC Ch. 9, Table 8)
Step 02 :
Resistance per foot of wire = 1.98/1000 = 0.00198 ohms/ ft.
Therefore; Circuit Resistance = Total wire length ( from step 1) x Ohms/ft.
= 1000 x 0.00198
Circuit Resistance = 1.98 Ohms
Step 03 :
Total alarm notification device amperage and devices may be rated in milliamps
Step 04 :
Total voltage drop for the branch circuit.
V = IR
V = Total Current from Step (3) x Total Resistance from Step (2)
= 0.5 x 1.98
Step 05 :
As per UL 864 & NFPA 72, It must be 85% of Battery Capacity i.e; 20.4 VDC, due to
internal Voltage drop it will always be less than 20.4VDC
Value of Voltage at Last Device Must be Greater than 16 VDC to circuit to work
Since Allowable voltage drop is 20.4 V (FACU) - 16 VDC (NOV) = 4.4 V ( Panel cut off
voltage is generally taken as 19.1 V)
Total Voltage Drop = 20.4 – 0.99 = 19.41 V (shall not be less than 16V. Hence, OK)
But may not be the case always as mentioned above Because The “worst case”
could be (for instance) the third longest circuit with the third greatest device load
connected. So, better to provide multiple circuit calculation.
In Accordance with NFPA 101 LSC 2018, IBC 2018 & ICC A117.1 2009
The occupant load factor of the mall is based on the gross leasable
area, which is the floor area dedicated for tenant use only. The gross
leasable area does not include the anchor buildings. Tenant spaces that
have their own means of egress independent of the mall are not
required to be included in the gross leasable area
Follow same step considering separate OLF for every use in tenant and anchor space in accordance
with table 7.3.1.2 of NFPA 101 LSC or Table 1004.1.2 of IBC 2018
Therefore;
Number of Pews = 28
210,000
Occupant Load = 100
Office Space
OL = 169
14
Number and Width of Exits: Example - 6
For Space-A
15
Number and Width of Exits: Example - 6
For Space-A
16
Number and Width of Exits: Example - 6
For Staircase & Corridor width
Since there are two exit stairs, each stair has to serve A B
only one‐half of the total occupant load for the floor.
Therefore, the corridor width can be reduced as well. Office Space Retail
OL = 125 OL = 30
Width of Corridor = 162 x 0.2 = 32.4 say 33 inch
That means that the doors entering the exit stairs can
each be the minimum 36‐inch (914‐mm) width.
However, most codes specify a 44‐inch (1118‐mm)
minimum for the corridor C
Office Space
Considering ICC A117.1-2009 for disabilities
OL = 169
60 Inch. Corridor is required.
18
Width of Exits : Example - 7
A multi‐story building. It indicates the occupant load for L-8 OL = 450 & 2 Exits
each floor and the number of exits based on these
occupant loads (using the table shown in Figure 4.16 ). L-7 OL = 825 & 3 Exits
The fourth floor has the largest occupant load, with a total
of 1020, and therefore requires the largest number of L-6 OL = 495 & 2 Exits
exits.
L-5 OL = 800 & 3 Exits
OL = 982 & 3 Exits Highest Occupant load is on Level 4 which requires 4 Exit as
4 Exits per NFPA 101,Ch.7,Cl. 7.4
Minimum As a result, Every floor below it must also have four exits, even
OL = 905 & 3 Exits though their occupant loads specify fewer exits. Four separate
exit stairs that are continuous from the fourth to the first floor
would meet the requirement.
OL = 400 & 2 Exits
2 Exits
OL = 51 & 2 Exits
Minimum
CFI-1 Exam Preparation- Mehboob Shaikh(CFPS, CFI, AMIE) 20
DETERMINATION OF REQUIRED FIRE
RESISTANCE RATINGS & TYPE OF
CONSTRUCTION
Therefore,
Area Modification (IBC section 506)
𝐴𝑡 𝑥 𝐼𝑓 𝐴𝑡 𝑥 𝐼𝑠
Aa = At + +
100 100
where
Aa = Allowable area per floor (ft2).
At = Tabular area per floor in accordance with Table 503 (ft2 ).
If = Area increase due to frontage (percent) as calculated in accordance
with Section 506.2.
Is = Area increase due to sprinkler protection (percent) as calculated in
accordance with Section 506.3
where
If = Area increase due to frontage (percent).
F = Building perimeter which fronts on a public way or open space
having 20 ft (6.1 m) minimum width.
P = Perimeter of building.
W = Minimum width of public way or open space.
𝐹 𝑊
If = 100 x − 0.25 x
𝑃 30
If = 20%
Is = 200%
% Increase
Base Area 100
Frontage Increase 20
Sprinkler Increase 200
Total Increase 320 %
Therefore;
(A) Allowable Area for Assembly Occupancy :
Therefore;
(B) Allowable Area for Business Occupancy :
Therefore;
(C) Allowable Area for Day Care Occupancy :
Therefore;
(D) Allowable Area for Mercantile Occupancy :
complied
Second Floor Mercantile 15,000 80,625 0.18
Business 60,000 140,625 0.42
First Floor Mercantile 15,000 80,625 0.18
Mercantile 25,000 80,625 0.31
Business 15,000 140,625 0.10
Assembly 14,000 58,125 0.24
Day Care 6000 99,375 0.06
CFI-1 Exam Preparation- Mehboob Shaikh(CFPS, CFI, AMIE) 22
Procedure for Determining the Code
Requirements for a building or structure
&
Understanding Building Height & Area
3 Determine the occupant load. Refer to Cl.7.3 & Occupancy chapter 12 through 42
9 Where two or more occupancy chapters apply, such as in a mixed use building, the most
stringent requirements apply.
10 Operating feature requirements CFI-1 Exam Preparation- Mehboob Shaikh(CFPS, CFI, AMIE) 2
Refer Clause “ Operating Features” of Applicable
Comparison of Occupancy Classifications
Occupancy ICC NFPA
Classification International Building Code Life Safety Code and NFPA 5000
ASSEMBLY A-1 Assembly, Theaters (Fixed Seats) A - Assembly (variations noted by occupant
A-2 Assembly, Food and/or Drink Consumption load)
A-3 Assembly, Worship, Recreation, Amusement
A-4 Assembly, Indoor Sporting Events
A-5 Assembly, Outdoor Activities
BUSINESS B- Business B –Business
AHC- Ambulatory Health Care
EDUCATIONAL E- Educational (includes some day care) E- Educational
Determine,
1. If the Hotel use can be located in the building…?
2. Building has area required by the code for that use..?
CFI-1 Exam Preparation- Mehboob Shaikh(CFPS, CFI, AMIE) 9
Solution
• Occupancy Classification : R-1 occupancy classification
• Floor area required for 100 People = Load Factor x Occupant Load
= 200 x 100
= 20,000 Sq. Ft. < 24,000 Sq. ft.(Available)
Total Floor area (20,000 Sq. ft) > Total Allowed Area (14,000 Sq. ft.) Allowable area Per floor
Hence, with this construction type this occupancy can’t be allowed in Total allowed area for two
this building floors = 14,000 Sq. Ft.
CFI-1 Exam Preparation- Mehboob Shaikh(CFPS, CFI, AMIE)
11
Solution
Lets Check if the occupancy is allowed in this construction type :
Maximum allowable number of
stories.
Fire Hazardous
Walls