You are on page 1of 29

AEP611S ADVANCED

ELECTRICAL PRINCIPLES 215


SYMMETRICAL
COMPONENTS
APPLICATIONS OF
SYMMETRICAL COMPONENTS

LECTURE 2
SEQUENCE NETWORKS OF
SYNCHRONOUS GENERATORS
2014 Symmetrical Components - Compiled by K. Kanyimba (kk)
3. APPLICATIONS OF
SYMMETRICAL COMPONENTS

• The method of symmetrical components may be applied to


the solution of all kinds of unbalanced 3-phase network
problems such as the unbalanced four-wire star-connected
load, the unbalanced delta-connected load and the
unbalanced three-wire star-connected load.
• However, when the source impedance is assumed to be
negligible, the methods of solution adopted then (see
Lectures on Three-phase Systems) are easier than the
application of the method of symmetrical components.
• Where the source impedance is taken into account, the
method of symmetrical components must be applied if the
source is a synchronous generator, or a transformer supplied
by a synchronous generator. This is because the impedance
of a synchronous generator to positive-sequence currents
is different from its impedance to negative phase-sequence
currents and to zero phase-sequence currents.
2014 2 Symmetrical Components - Compiled by K. Kanyimba (kk)
APPLICATIONS OF
SYMMETRICAL COMPONENTS (CONT.)

• The source impedance is likely to be of significance under


fault conditions in 3-phase networks. Indeed, for a fault at
the generator terminals the generator impedance is the
only impedance present.
• The main field of application of symmetrical components,
therefore, is the analysis of 3-phase networks under
asymmetrical (unsymmetrical) fault conditions.
• It also follows that most of the faults that occur on power
systems are unsymmetrical in nature.
• These faults may consist of
(i) Solid unsymmetrical short-circuits.
(ii) Unsymmetrical faults through impedances and
(iii) Open conductors.

2014 3 Symmetrical Components - Compiled by K. Kanyimba (kk)


APPLICATIONS OF
SYMMETRICAL COMPONENTS (CONT.)

• Unsymmetrical short-circuits occur as:


(i) Single line-to-ground (S-L-G) faults,
(ii) Line-to-line (L-L)/Double-line (D-L) faults and
(iii) Line-to-line-to-ground (L-L-G)/Double line-to-ground
(D-L-G) faults.
• The path of the fault from line-to-line or line-to-ground may
or may not contain impedance.
Open-conductor Faults:
• One or two open conductors result in unsymmetrical faults,
either through the breaking of one or two conductors or
through the action of fuses and other devices that may not
open the three phases simultaneously.

2014 4 Symmetrical Components - Compiled by K. Kanyimba (kk)


APPLICATIONS OF
SYMMETRICAL COMPONENTS (CONT.)

• Some Fault Statistics:

Fault Type Percentage of


Total Faults
(i) Three-phase Balanced Faults < 5%
(ii) Unbalanced Faults
- Single-line-to-ground 60 – 75 %
- Double-line-to-ground 15 – 25 %
- Line-to-line 5 – 15 %

2014 5 Symmetrical Components - Compiled by K. Kanyimba (kk)


APPLICATIONS OF
SYMMETRICAL COMPONENTS (CONT.)

3.1. SEQUENCE NETWORKS


• In any part of a circuit, the voltage drop caused by current of a
certain sequence depends on the impedance of that part of
the circuit to current of that sequence.
• The impedance of any section of a balanced network to
current of one sequence may be different from the impedance
to current of another sequence.
• The impedance of a circuit when positive-sequence currents
alone are flowing is called the impedance to positive-
sequence current or simply positive-sequence impedance.
• Similarly, when only negative-sequence or zero-sequence
currents are present the impedances are called impedance to
negative-sequence current or negative-sequence
impedance) and impedance to zero-sequence current (or
zero-sequence impedance), respectively.

2014 6 Symmetrical Components - Compiled by K. Kanyimba (kk)


SEQUENCE NETWORKS (CONT.)

• The single-phase equivalent circuit composed of the


impedances to the current of any one sequence only is
called the sequence network for that particular sequence,
i.e.
– positive-sequence network,
– negative-sequence network
and
– zero-sequence network.
• In order to calculate the effect of an asymmetrical
condition by the method of symmetrical components, it is
essential to
(i) to determine the sequence impedances
and
(i) to combine them to form the sequence networks.
2014 7 Symmetrical Components - Compiled by K. Kanyimba (kk)
APPLICATIONS OF
SYMMETRICAL COMPONENTS (CONT.)

3.2. A SYNCHRONOUS GENERATOR SUPPLYING AN


UNBALANCED LOAD
3.2.1. THE SEQUENCE NETWORKS OF UNLOADED
SYNCHRONOUS GENERATORS
• Three-phase generators are specifically designed so that
the phase e.m.f.s form a balanced 3-phase system.
• It is assumed, therefore, that the e.m.f. of the synchronous
generator shown in Figure 3.1 is of positive phase-
sequence only.
• Then, the generator e.m.f.s are
– Ean
– Ebn (= a2Ean)
– Ecn (= aEan)

2014 8 Symmetrical Components - Compiled by K. Kanyimba (kk)


THE SEQUENCE NETWORKS OF UNLOADED
SYNCHRONOUS GENERATORS (CONT.)

Figure 3.1. A synchronous generator


supplying an unbalanced load.
2014 9 Symmetrical Components - Compiled by K. Kanyimba (kk)
THE SEQUENCE NETWORKS OF UNLOADED
SYNCHRONOUS GENERATORS (CONT.)

2014 10 Symmetrical Components - Compiled by K. Kanyimba (kk)


THE SEQUENCE NETWORKS OF UNLOADED
SYNCHRONOUS GENERATORS (CONT.)

2014 11 Symmetrical Components - Compiled by K. Kanyimba (kk)


THE SEQUENCE NETWORKS OF UNLOADED
SYNCHRONOUS GENERATORS (CONT.)

2014 12 Symmetrical Components - Compiled by K. Kanyimba (kk)


THE SEQUENCE NETWORKS OF UNLOADED
SYNCHRONOUS GENERATORS (CONT.)

2014 13 Symmetrical Components - Compiled by K. Kanyimba (kk)


THE SEQUENCE NETWORKS OF UNLOADED
SYNCHRONOUS GENERATORS (CONT.)

2014 14 Symmetrical Components - Compiled by K. Kanyimba (kk)


THE SEQUENCE NETWORKS OF UNLOADED
SYNCHRONOUS GENERATORS (CONT.)

2014 15 Symmetrical Components - Compiled by K. Kanyimba (kk)


THE SEQUENCE NETWORKS OF UNLOADED
SYNCHRONOUS GENERATORS (CONT.)

2014 16 Symmetrical Components - Compiled by K. Kanyimba (kk)


THE SEQUENCE NETWORKS OF UNLOADED
SYNCHRONOUS GENERATORS (CONT.)

• An examination of equations 3.4, 3.6 and 3.9 reveals that,


when an unbalanced load is imposed on a system, the
positive, negative and zero phase-sequence components
may be considered separately if the impedance of each
phase of the network is balanced (symmetric).
• Under these conditions the positive, negative and zero
phase-sequence networks, which are interpretations of
equations 3.4, 3.6 and 3.9, may be drawn, as in Figures
3.2, 3.3, 3.4 and 3.5.

2014 17 Symmetrical Components - Compiled by K. Kanyimba (kk)


THE SEQUENCE NETWORKS OF UNLOADED
SYNCHRONOUS GENERATORS (CONT.)

In Summary:
• The generated voltages are of positive-sequence only,
since the generator is designed to supply balanced three-
phase voltages.
• Therefore, the positive-sequence network is composed
of an e.m.f. in series with the positive-sequence
impedance of the generator.
• The negative- and zero-sequence networks contain no
e.m.f.s but include the impedances of the generator to
negative-sequence currents and zero-sequence
currents, respectively.
• Figures 3.2, 3.3, 3.4, 3.5 and 3.6 show the sequence
networks of the generator.

2014 18 Symmetrical Components - Compiled by K. Kanyimba (kk)


THE SEQUENCE NETWORKS OF UNLOADED
SYNCHRONOUS GENERATORS (CONT.)

(a) Positive-sequence current paths. (b) Positive-sequence


network.
Figure 3.2. Paths for positive-sequence currents in a generator and in
the positive-sequence network.
2014 19 Symmetrical Components - Compiled by K. Kanyimba (kk)
THE SEQUENCE NETWORKS OF UNLOADED
SYNCHRONOUS GENERATORS (CONT.)

(a) Negative-sequence (b) Negative-sequence


current paths. Network.
Figure 3.3. Negative-sequence current paths in a generator and in
the negative-sequence network.

2014 20 Symmetrical Components - Compiled by K. Kanyimba (kk)


THE SEQUENCE NETWORKS OF UNLOADED
SYNCHRONOUS GENERATORS (CONT.)

(a) Zero-sequence (b) Zero-sequence


current paths. network.
Figure 3.4. Zero-sequence current paths in a solidly-grounded
generator and in the zero-sequence network.

2014 21 Symmetrical Components - Compiled by K. Kanyimba (kk)


THE SEQUENCE NETWORKS OF UNLOADED
SYNCHRONOUS GENERATORS (CONT.)

Figure 3.5. A synchronous generator supplying an unbalanced


load with the star-point grounded through an impedance, Zn.
2014 22 Symmetrical Components - Compiled by K. Kanyimba (kk)
THE SEQUENCE NETWORKS OF UNLOADED
SYNCHRONOUS GENERATORS (CONT.)

(a) Zero-sequence (b) Zero-sequence


current paths network
Figure 3.6. Zero-sequence current paths in a generator grounded
through an impedance (Zn) and in the zero-sequence network.

2014 23 Symmetrical Components - Compiled by K. Kanyimba (kk)


THE SEQUENCE NETWORKS OF UNLOADED
SYNCHRONOUS GENERATORS (CONT.)
NB:
• The current flowing in the impedance Zn between the neutral
and the ground, in Figure 3.6(a), is 3Ia0.
• The voltage drop is therefore, 3ZnIa0 or (3Zn)Ia0. For the sake
of convenience, the current is assumed to be Ia0, but flowing
through and equivalent impedance given by, 3Zn.
• By referring to Figure 3.6(b), it can be seen that the voltage
drop of zero-sequence from point ‘a’ to ground is -3Ia0Zn –
Ia0Zg0, where Zg0 is the zero-sequence impedance per phase
of the generator.
• The zero-sequence network which is a single-phase circuit
assumed to carry only the zero-sequence current of one
phase, must therefore have an impedance of 3Zn + Zg0, as
shown.
• The total zero-sequence impedance through which Ia0 flows is
Z0 = 3Zn + Zg0. … eqn. 3.10.
2014 24 Symmetrical Components - Compiled by K. Kanyimba (kk)
THE SEQUENCE NETWORKS OF UNLOADED
SYNCHRONOUS GENERATORS (CONT.)

Figure 3.7. The positive phase-sequence network, the negative phase-


sequence network and the zero phase-sequence network of a
synchronous generator supplying an unbalanced load.
• The sequence networks shown in Figure 3.7 are single-
phase equivalent circuits of the balanced three-phase
circuits (of Figures 3.2(a), 3.3(a) and 3.4(a)) through which
the symmetrical components of the unbalanced currents are
considered to flow. to flow.
2014 25 Symmetrical Components - Compiled by K. Kanyimba (kk)
THE SEQUENCE NETWORKS OF UNLOADED
SYNCHRONOUS GENERATORS (CONT.)

• The generated e.m.f. in the positive-sequence network is the


no-load terminal voltage to neutral, which is also equal to
the transient and sub-transient internal voltages since the
generator is not loaded.
• The reactance is the sub-transient, transient, or
synchronous reactance, depending on the condition of
interest.
• The reference bus for the positive-sequence network and the
negative-sequence network is the neutral of the generator.
• As far as the positive-sequence and the negative-sequence
components are concerned, the neutral of the generator is at
ground potential even if there is a connection between
neutral and ground having a finite or zero impedance since
the connection will carry no positive-sequence or negative-
sequence current.
2014 26 Symmetrical Components - Compiled by K. Kanyimba (kk)
THE SEQUENCE NETWORKS OF UNLOADED
SYNCHRONOUS GENERATORS (CONT.)

2014 27 Symmetrical Components - Compiled by K. Kanyimba (kk)


THE SEQUENCE NETWORKS OF UNLOADED
SYNCHRONOUS GENERATORS (CONT.)

2014 28 Symmetrical Components - Compiled by K. Kanyimba (kk)


THE SEQUENCE NETWORKS OF UNLOADED
SYNCHRONOUS GENERATORS (CONT.)

Typical Values of Sequence Impedances for Common


Generators:
(i) Positive-sequence values are the same as Xd, Xd’ and Xd”.
(ii) Negative-sequence values are affected by the rotation of
the rotor, however, X2 ≈ Xd”.
(iii) The zero-sequence reactance is approximated to the
leakage reactance, i.e., X0 ≈ XL.

2014 29 Symmetrical Components - Compiled by K. Kanyimba (kk)

You might also like