Professional Documents
Culture Documents
ZX2
Gas-insulated
medium voltage switchgear
Contents
Page
1 Introduction 5
2 Applications 6
3 Characteristics 7
4 Your benefit 8
5 Technical data 9
5.1 Technical data of the panel 9
5.2 Technical data of the circuit-breaker 12
5.3 Technical data of the disconnector and three position disconnector 13
6 Fundamental structure of the panels 14
7 Components 21
7.1 Vacuum circuit-breaker 22
7.2 Three position disconnector 26
7.3 Disconnector 29
7.4 Optional view ports 31
7.5 Busbar 32
7.6 Inner cone termination system 34
7.6.1 Connection of cables 34
7.6.2 Connection of fully insulated bars 35
7.6.3 Connection of surge arresters 35
7.7 Outer cone termination system 36
7.7.1 Outer cone connectors ABB type CSE-A 37
7.7.2 Selection of cable connectors (Panel width 600 mm) 38
7.7.3 Selection of cable connectors (Double feeder panel - panel width 2 x 400 mm) 50
7.8 Main earthing bar 54
7.9 Test sockets 54
7.10 Capacitive voltage indicator systems 50
7.11 Current and voltage detection devices 58
7.11.1 Ring core current transformers 59
7.11.2 Block-type transformers and block-type sensors 60
7.11.3 Current transformers 61
7.11.4 Earth fault transformers 61
7.11.5 Dimensioning of current transformers 62
7.11.6 Voltage transformers 63
7.12 Protection and control units 64
7.13 Sulphur hexafluoride 65
7.14 Gas system in the panels 65
7.15 SF6 density sensor 66
7.16 Pressure relief systems 67
7.17 Surface treatment 67
Switchgear systems and their components rank among the most important facilities for electrical power transmission and distribution.
Their versatile functions and the opportunities they provide contribute on the one hand to safety in general, and on the other hand they
secure the availability of electrical energy.
Flexible combination, reliability, availability and economy are the attributes that make it easy for our clients in industry and utilities to
decide in favor of products from the ZX series. Together with complete conventional solutions, the use of digital protection and control
technology, sensor systems and plug-in connections makes ZX systems unrestrictedly fit for the future, and the primary function of reli-
able power distribution is fulfilled with no ifs and buts. This is ensured by ABB’s uncompromising approach to quality, which leaves no
customer’s wishes unfulfilled. Aligned to each need, the panel types of the ZX family offer a solution for each requirement. In over 70
countries the customers rely on gas-insulated switchgears from ABB.
The ZX series leave our works as tested panels and, as SF6 switchgear, are exemplary in terms of safety, economy and availability. Their
compact design permits installation in even the most constricted spaces. The hermetically sealed enclosures make the systems shock-
proof and protect the high voltage components from all environmental influences.
ABB AG’s Calor Emag Medium Voltage Products division develops, manufactures and installs switchgear systems and components for
electrical power distribution in the medium voltage range. Based in Ratingen, Germany, we have the know-how, global project experi-
ence and local partners for the supply of panels and turnkey medium voltage switchgear systems.
– – SF6 gas-insulated with hermetically – – Inner cone cable connection system to EN 50181 and
sealed pressure system DIN 47637, in sizes 2 and 3
–– Rated voltages up to 36 kV (42 kV) – – Outer cone cable connection system to EN 50181, type C
–– Up to 2500 A and 40 kA – – Connection facility for surge arresters
–– Single and double busbar design
–– Up to 4000 A in single busbar design Current and voltage metering
–– Stainless steel encapsulation, manufactured
from laser cut sheet material –– Instrument transformers and sensors
–– Modular structure
–– Switchgear with a leakage rate of less than Protection and control
0.1 % per annum
–– Integrated leakage testing of the panels –– Combined protection and control devices
–– Indoor installation –– Discrete protection devices with conventional control
–– Suitable for site altitudes over 1000 m above sea level
Protection against maloperation
Panel variants
–– Electrical switch interlocks
–– Incoming and outgoing feeder panels –– Optional: additional mechanical interlocks
–– Cable termination panels
–– Termination panels for fully insulated bars Pressure relief
–– Sectionaliser
–– Riser – – Via pressure relief ducts into the switchroom, or
–– Metering panels – – Via pressure relief ducts to the outside
–– Double feeder panels
–– Customised panel versions Installation
Circuit-breaker, disconnector and three position discon- – – Panels joined together by plug-in connectors
nector
– – Vacuum circuit-breaker
–– Disconnector with functions for
–– Busbar connection
–– Disconnection
– – Disconnector/earthing switch (three position disconnector)
with functions for
–– Busbar connection
–– Disconnection
–– Earthing
–– As the high voltage compartments are independent of ex- –– No gas work is required as a rule at site. There is thus no
ternal influences (degree of protection IP65), the probability need to evacuate and fill the high voltage compartments,
of a fault during operation is extremely low. test them for leakage and measure the dewpoint of the
insulating gas at site.
–– As evidenced by arc fault testing, our switchgear systems
are notable for maximum operator safety. Maximum availability
–– A further increase in operator safety can be achieved by –– The plug-in busbar technology without screw couplings
providing pressure relief to outside the switchgear room. permits simple and therefore safe assembly.
Minimum overall costs –– In spite of the extremely low failure probability of the ZX
switchgear systems, replacement of components in the gas
–– The compact design of the panels reduces the space re- compartments and therefore a rapid return to service after
quired and therefore the size of the station. The result is a repairs is possible.
lower investment requirement.
–– In gas-insulated switchgear, earthing of switchgear sec-
–– Freedom from maintenance is achieved by constant condi- tions is performed by a high quality vacuum circuit-breaker.
tions in the high voltage compartments in conjunction with The circuit-breaker can close onto a short-circuit signifi-
the selection of suitable materials. The injurious influences cantly more frequently and reliably than a positively making
of dust, vermin, moisture, oxidation and contaminated air in earthing switch.
the high voltage compartments are precluded, as the gas-
tight compartments are filled with inert gas.
As a rule, therefore, isolation of the switchgear to perform
maintenance work is not required.
1)
Rated current for 60 Hz on request
2)
60 Hz see section “Non standard operating conditions”
3)
Insulating gas: SF6 (sulphur hexafluoride)
4)
All pressures stated are absolute pressures at 20 °C
5)
100 kPa = 1 bar
6)
Higher degrees of protection on request
7)
Higher ambient air temperature on request
8)
Higher site altitude see section “Non standard operating conditions”
The panels are arc fault tested in accordance with IEC 62271-200.
Table 5.1.2: Internal arc classification of the switchgear in accordance with IEC 62271-200
Panels with inner cone cable connection system and all other panel variants without Classification IAC AFLR
cable connection Internal arc 40 kA 1 s
Classification IAC AFLR
up to 12 kV
Panels with outer cone cable connection system, Internal arc 40 kA 1 s
panel width 600 mm Classification IAC AFLR
> 12 kV
Internal arc 31.5 kA 1 s
Double feeder panel with outer cone cable connection system, Classification IAC AFLR
panel width 2 x 400 mm Internal arc 25 kA 1 s
With pressure relief into the switchgear room, the IAC qualification
requires a switchgear installation consisting of at least four panels.
If a pressure relief duct leading to the outside is used, at least two
panels are required for the IAC qualification.
Table 5.1.3: Loss of Service Continuity of the switchgear in accordance with IEC 62271-200
LSC2B
Loss of Service Continuity
Other panels and all cable compartments may
remain energized.
The partition class to IEC 62271-200 defines the nature of the par-
tition between live parts and an opened, accessible compartment.
Partition class PM
1)
Higher levels to international standards on request
2)
Rated current for 60 Hz on request
3)
Higher operating currents on request
4)
Different operating sequences on request
5)
Times for >36 kV, 40 kA circuit-breakers on request
6)
Different auxiliary voltages on request
7)
Dependent on the vacuum circuit-breaker
Table 5.3.1: Technical data of the disconnector and the three position disconnector
IEC ratings Special ratings
Rated voltage Ur kV 12 24 36
Maximum rated voltage kV 12 24 36 42
Rated power frequency withstand voltage across the isolating distance kV 32 60 80 1)
Rated lightning impulse withstand voltage across the isolating distance kV 85 145 195 1)
1)
On request
2)
Higher operating currents on request
3)
Different auxiliary voltages on request
4)
At rated auxiliary voltage
Modular structure
Each feeder panel consists of the circuit-breaker compartment the low voltage compartment (F). The circuit-breaker compartment
(A), one or two busbar compartments (B), the cable termination and the busbar compartments are filled with gas. There are no
compartment (C), the pressure relief duct for the circuit breaker gas connections between the two or three compartments or to
compartment and for the cable termination compartment (D), one gas compartments in adjacent panels.
or two pressure relief ducts for the busbar compartments (E) and
Fig. 6.1: Outgoing cable panel 1250 A with block-type transformer/sensor, single busbar at front
D A
Fig. 6.2: Outgoing cable panel 2000 A with current and voltage Fig. 6.3: Outgoing cable panel 2000 A with sensor and voltage transformer,
transformer, single busbar at rear double busbar
E E E
B F
B F B
D
A D
C
C
The cable (1.3) and test plug sockets (1.4) and the circuit-breaker The pressure relief disk (1.13) of the circuit-breaker compartment
poles (1.1) are located in the circuit-breaker compartment . is located in the rear wall of the enclosure. The circuit-breaker
operating mechanism (1.2), the gas leakage sensor (1.10) and the
The current-carrying connection between the circuit-breaker and filling valve (1.11) are located on the mounting plate of the circuit-
the three position disconnector respectively the disconnector in breaker (1.14) which is bolted to the front wall of the enclosure.
the busbar compartment is effected via single pole cast resin
bushings (1.12). The seals of the components are o-ring seals which are not ex-
posed to any UV radiation.
There are three basic versions of circuit-breaker compartments
available: The circuit-breaker compartments in systems consisting of several
panels have no gas connections to the neighbouring panels, nor
–– Current detection by blocktype transformers or sensors is there any gas connection to the busbar compartments located
(fig. 6.4) with max. two cable sockets per phase above the circuit-breaker compartments.
– – Current detection by current transformer (fig. 6.5)
– – Current detection by sensors or combination of sensor/cur-
rent transformers (fig. 6.6).
1.12
1.0
1.10
1.11
1.1
1.13 1.2
1.14
1.9
1.3
1.4
1.0 Circuit-breaker compartment (enclosure) 1.10 Gas density sensor for circuit-breaker
1.1 Circuit-breaker pole compartment
1.2 Circuit-breaker mechanism 1.11 Filling valve for circuit-breaker compartment
1.3 Cable socket 1.12 Cast resin bushing to busbar
1.4 Test socket (also for use with other 1.13 Pressure relief disk
plug-in devices) 1.14 Mounting plate
1.9 Block-type transformer
█ Insulating gas SF6
1.12
1.0
1.10
1.11
1.15 1.1
1.13 1.2
1.14
1.3
1.4 1.16
1.12
1.0
1.10
1.11
1.1
1.13 1.2
1.17 1.14
1.3
1.4
1.0 Circuit-breaker compartment (enclosure) 1.11 Filling valve for circuit-breaker compartment
1.1 Circuit-breaker pole 1.12 Cast resin bushing to busbar
1.2 Circuit-breaker mechanism 1.13 Pressure relief disk
1.3 Cable socket 1.14 Mounting plate
1.4 Test socket (also for use with other plug-in devices) 1.17 Combination sensor
1.10 Gas density sensor for circuit-breaker compartment
█ Insulating gas SF6
The pressure relief disk (1.13) of the busbar compartment is lo- As with the circuit-breaker compartment, the seals on the compo-
cated in the roof of the enclosure. nents are o-ring seals which are not exposed to any UV radiation.
Front busbar compartment The busbar connection to the adjacent panels is effected by plug-
in connectors (2.2) located at either side of the enclosure. The
The operating mechanism (2.5) of the three position disconnector busbar compartments in switchgears consisting of several panels
(2.3), the gas leakage sensor (2.7) and the filling valve (2.8) are have no gas connections with the neighbouring panels, nor is
located on the front wall of the enclosure. there any gas connection to the circuit-breaker compartment lo-
cated below the busbar compartments.
Rear busbar compartment
1.13
2.1
2.2
2.0
2.10
2.9
2.8
2.3
2.5
2.7
1.12
1.12 Cast resin bushing 2.7 Gas density sensor for busbar compartment
1.13 Pressure relief disk 2.8 Filling valve for busbar compartment
2.0 Busbar compartment (enclosure) 2.9 Earthing contact
2.1 Busbar system 2.10 Flat conductor
2.2 Plug-in busbar connector
2.3 Three position disconnector █ Insulating gas SF6
2.5 Three position disconnector operating mechanism
1.13
2.1
2.2
2.0
2.10
2.6 2.4
2.7
2.8
1.12
The cable termination compartment contains the main earthing bar In the unlikely event of an arc fault in the cable termination or cir-
(3.5), the high voltage cables (3.2) with fitted cable plugs (3.1), and cuit-breaker compartments, pressure is relieved through the rear
cable fasteners (3.3) and, where appropriate, surge arresters or pressure relief duct (4.0).
voltage transformers.
Fig. 6.9: Cable termination compartment (C) and rear pressure relief duct (D)
4.0
(D)
3.1
3.5
1.8
3.0
3.3
(C)
3.2
3.6
The low voltage compartment (F) The entry for external secondary cables (6.5) is located in the base
plate of the low voltage compartment.
The operating mechanism for the circuit-breaker (1.2), the mecha-
nism for the three position disconnector (2.5), sensors for gas
density monitoring in the gas compartments (1.10 and 2.7), pro-
tection devices and further secondary devices and their wiring
6.6
6.4
6.4
2.5
2.7 6.2
2.8
6.0
6.4
1.10
1.11
1.2
1.2 Operating mechanism for the circuit-breaker
1.10 Sensors for gas density monitoring for
1.14
Circuit-breaker compartment
1.11 Filling valve for circuit-breaker compartment
1.14 Mounting plate for circuit-breaker
2.5 Three position disconnector mechanism
6.4 2.7 Gas density sensor for front busbar compartment
6.3 2.8 Filling valve for front busbar compartment
6.0 Low voltage compartment
6.1 Central unit of a combined protection and control device
6.2 Human-machine interface of a combined protection
and control device
6.1 6.3 Opening for loop lines
6.4 Wiring section
6.5 Secondary cable entry
6.6 Low voltage compartment door
6.5
1.13
4.1 1.0 Circuit-breaker compartment
2.0 2.1 1.1 Circuit-breaker pole
6.0 1.2 Circuit-breaker operating mechanism
1.3 Cable socket
1.4 Test socket (also for use with other
2.3 2.5 plug-in devices)
6.2 1.5 Capacitive voltage indicator system
1.5 1.8 Voltage transformer
1.12
1.9 Block-type transformer or sensor
1.0
1.12 Bushing, circuit-breaker/busbar compartment
1.1
4.0 1.13 Pressure relief disk
1.13 1.15 Current transformer
1.9 1.2
2.0 Busbar compartment
1.4 1.3
2.1 Busbar system
3.5 3.1
2.3 Three position disconnector
3.0 6.1 2.4 Disconnector
3.2 2.5 Three position disconnector mechanism
3.3 2.6 Disconnector mechanism
3.0 Cable termination compartment
3.1 Cable plug
3.2 High voltage cable
3.3 Cable fastener
3.5 Main earthing bar
Fig. 7.2: Feeder Panel 2000 A, Double busbar 4.0 Pressure relief duct, rear
4.1 (for circuit-breaker compartment and cable
2.1 termination compartment)
1.13
4.1 Pressure relief duct, top
2.0 6.0
(for busbar compartment)
2.3
2.5 6.0 Low voltage compartment
2.4 6.2 6.1 Central unit of a combined protection and
2.6
1.12 control device
1.5
6.2 Human-machine interface of a combined
1.0 protection and control device
1.15 1.1
4.0
1.13 1.2 █ Insulating gas SF6
1.3
1.4
3.5 3.1
1.8 6.1
3.2
3.0 3.3
The fixed mounted vacuum circuit-breakers (fig. 7.1.1) are three Vacuum interrupter
phase switching devices and fundamentally consist of the operat-
ing mechanism and the three pole parts. The pole parts contain The outer casing of the vacuum interrupter (fig. 7.1.2) consists of
the switching elements proper, the vacuum interrupters. ceramic insulators (1), whose ends are sealed off by stainless
steel lids (2). The contacts (4 and 5) surrounded by the potential-
The pole parts are installed on a common mounting plate. The free centre screen (3) are made of copper/chromium composite.
operating mechanism is on the opposite side from the mounting As a consequence of the extremely low static pressure of less
plate. In this way, the pole parts, mounting plate and operating than 10-4 to 10-8 hPa inside the interrupter chamber, only a rela-
mechanism form a single assembly. The mounting plate for this tively small contact gap is required to achieve a high dielectric
assembly is screwed to the front wall of the circuit-breaker com- strength. The switching motion is transmitted into the enclosed
partment in a gas-tight manner at the works. system of the vacuum interrupter via a metal bellows (6). An anti-
rotation element (7) is fitted to protect the metal bellows from
The pole parts are located in the circuit-breaker compartment torsion and to guide the conductor leading to the moving con-
which is filled with SF6, and are therefore protected from external tact. The connection to the operating mechanism is effected by a
influences. The operating mechanism is located in the low voltage threaded pin (8) fastened in the feed conductor.
compartment and is therefore easily accessible
If contacts through which current is flowing are opened in a
Functions of the vacuum circuit-breaker vacuum, a metal vapour arc arises under short-circuit conditions.
This arc creates the charge carriers required to conduct the cur-
–– Switching operating current on and off rent inside the vacuum interrupter. The arc is extinguished at the
–– Short-circuit breaking operations first natural zero of the alternating current after switch-off, i.e. after
–– Earthing function in conjunction separation of the contacts. With the rapid reestablishment of the
with the three position disconnector contact gap in the vacuum, the current flow is then securely inter-
rupted.
For earthing, the three position disconnector prepares the con-
nection to earth while in the de-energized condition. Earthing
proper is performed by the circuit-breaker. A circuit-breaker func-
tioning as an earthing switch is of higher quality than any other
earthing switch.
2 1 4 2 7
3 5 6 8
The interrupter (9) inside the pole part is embedded in cast resin
or located in a cast resin pole tube (10). With the breaker closed,
the current flows from breaker terminal (11) to the fixed contact in
the vacuum interrupter, and from there via the moving contact to
breaker terminal (12). The operating motions are effected by insu-
lated actuating rods (8).
11 9 10 12 8 14 13
2
4
6
3
Table 7.1.1: Secondary equipment for the circuit-breaker mechanism in feeder panels
VDE designation
IEC designation
Equipment
Standard
Option
-MAS -M0 Charging motor for spring mechanism ●
-BGS -S1 Auxiliary switch “Spring charged” ●
-MBO1 -Y2 Shunt release OFF ●
-MBC -Y3 Shunt release ON ●
-BGB1 -S3 Auxiliary switch “CB ON/OFF” ●
-BGB2 -S4 Auxiliary switch “CB ON/OFF” ●
-BGB3 -S5 Auxiliary switch “CB ON/OFF” ●
-KFN -K0 Anti-pumping device ●
-RLE1 -Y1 Blocking magnet “CB ON” ●
-BGL1 -S2 Auxiliary switch for blocking magnet ●
-BGB4 -S7 Auxiliary switch for fault signal (impulse time 35 ms) ●
-MBU -Y4 1)
Undervoltage release ●
-MBO3 -Y7 1)
Indirect overcurrent release ●
-MBO2 -Y9 2 nd shunt release OFF ●
1)
Combination of -MBU with -MBO3 is not possible
disconnector The operating mechanism block for the three position disconnec-
tor consists of the following functional groups (figs. 7.2.4 to 7.2.6):
The three position disconnectors are combined disconnectors –– Drive motor (1)
and earthing switches. The three switch positions, connecting, –– Position detection with micro switches (2)
disconnecting and earthing, are clearly defined by the mechanical –– Additional auxiliary switches as an option (3)
structure of the switch. Simultaneous connection and earthing is –– Mechanical position indicator (4)
therefore impossible. –– Hand crank receptacle for emergency manual operation (5)
–– Optional mechanical access interlock for emergency
The three position disconnectors are motor-operated rod-type manual operation (6)
switches whose live switching components are located in the
busbar compartment filled with SF6, while the mechanism block is The various options for secondary equipment in the mechanism
easily accessible in the low voltage compartment. variants can be found in table 7.2.1.
The switch (fig. 7.2.1) has its disconnected position in the central
position. In the disconnector ON and earthing switch ON limit
positions, the moving contact (sliding part) (2) driven by an insulat-
ing spindle (1) reaches the fixed contacts (disconnector contact
(3) or earthing contact (4)) which are fitted with one or two spiral
contacts.
Fig. 7.2.1: Three position disconnector in disconnector ON position Fig. 7.2.2: Partial view of the three position disconnector in the central posi-
tion
3 2 1 4
Fig. 7.2.3: Partial view of the three position disconnector in the earthing
switch ON position (reed contact switched on by permanent magnet)
Cover
1
6
3
Fig. 7.2.5: (Detail A in fig. 7.2.4 – without cover) Micro switches for switch
position detection (2) and mechanical access interlock (closed) for emergency
manual operation (6)
Fig. 7.2.6: Mechanical access interlock (open) for emergency manual opera-
tion, hand crank receptacle for emergency manual operation (5)
Table 7.2.1 shows the secondary equipment for the three position
disconnector operating mechanism in an outgoing feeder panel.
The “Standard” column indicates the equipment necessary for
control of the panel. Over and above this, the use of further de-
vices such as additional auxiliary switches is possible as an option
to meet your specific requirements.
Table 7.2.1: Secondary equipment for the three position disconnector mechanism in feeder panels
VDE designation
IEC designation
Equipment
Standard
Option
-MAD -M1 Drive motor ●
-BGI11 -S15 Microswitch to detect switch position “Disconnector OFF” ●
-BGI12 -S16 Microswitch to detect switch position “Disconnector ON” ●
-BGE57 -S57 Microswitch to detect switch position “Earthing switch OFF” ●
-BGE58 -S58 Microswitch to detect switch position “Earthing switch ON” ●
-BGI11 -S11 Microswitch to detect switch position “Disconnector OFF” ●
-BGI12 -S12 Microswitch to detect switch position “Disconnector ON” ●
-BGE51 -S51 Microswitch to detect switch position “Earthing switch OFF” ●
-BGE52 -S52 Microswitch to detect switch position “Earthing switch ON” ●
-BGE3.1 -B5E1
-BGE3.2 -B5E2 Reed contacts to detect the “Earthing switch ON” switch position ●
-BGE3.3 -B5E3
-BGL1 -S151
Microswitch for (optional) access blocking of hand crank receptacle for emergency manual operation ●
-BGL2 -S152
Except for the lack of an earthing contact the design of the dis- The two-part operating mechanism of the disconnector consists of
connector is the same as that of the three position disconnector. the following functional groups (figs. 7.3.2 to 7.3.5):
Accordingly the two switch positions are “connect” and “discon-
nect”. –– Drive motor (1)
–– Position detection with micro switches (2)
–– Additional auxiliary switches as an option
Fig. 7.3.1: Disconnector in ON position –– Mechanical position indicator (4)
–– Hand crank receptacle for emergency manual operation (5)
–– Optional mechanical access interlock for emergency
manual operation (6)
Fig. 7.3.2: Rear part of the disconnector operating mechanism with motor Fig. 7.3.3: Front part of the disconnector operating mechanism in the low
(1) on the back of the panel voltage compartment. The operating mechanism of the three position dis-
connector is located above the disconnector operating mechanism.
Fig. 7.3.4: (Detail A in fig. 7.3.3) Inductive proximity switches (2) for switch Fig. 7.3.5: Mechanical access interlock for emergency
position detection (Optional with auxiliary switches) and access interlock manual operation (5)
(6) for emergency manual operation
3
5 4
2
Table 7.3.1: Secondary equipment for the disconnector mechanism in feeder panels
VDE designation
IEC designation
Equipment
Standard
Option
-MAD -M1 Drive motor ●
-BGI11 -S15 Microswitch to detect switch position “Disconnector OFF” ●
-BGI12 -S16 Microswitch to detect switch position “Disconnector ON” ●
-BGI11 -S11 Auxiliary switch “Disconnector OFF” ●
-BGI12 -S12 Auxiliary switch “Disconnector ON” ●
-BGL1 -S151
Microswitch for (optional) access blocking of hand crank receptacle for emergency manual operation ●
-BGL2 -S152
The view ports for the front busbar compartment are located in the
low voltage compartment, and those for the rear busbar compart-
ment are located in the cover of the busbar compartment at the
rear of the panel (fig. 7.4.1).
View A
A A
View ports
The busbars, located in the gas compartment of the panels, are compensation for expansion in the busbars running through a
connected together by plug-in busbar connectors (figs. 7.5.1 to switchgear system is necessary.
7.5.3). The busbar connection consists of the cast resin busbar
socket (1) mounted in the busbar compartment from the inside, The circuit-breaker and busbar compartments are separate cham-
the silicone insulating part (2), the contact tube (3) and the spiral bers in the gas system. Busbar operation therefore continues to
contacts (4). be possible in the event of a fault in the circuit-breaker compart-
ment of an outgoing feeder panel. The gas systems of adjacent
The electrically conductive connection from the embedded part of busbar compartments are also not connected to each other (ex-
the cast resin busbar socket to the contact tube is established by ception: double feeder panels).
one or two spiral contacts, depending on the rated busbar cur-
rent. The silicone insulating part isolates the high voltage potential The plug connector system on the one hand facilitates the delivery
from earth potential. The surfaces of all electrically conductive of panels tested at the works for leakage and dielectric strength,
components (embedded part, spiral contact and contact tube) are and on the other hand no gas work is required during installation
silver plated. As the contact tubes are axially movable, no further at site (with the exception of installation of heat sinks on busbar
compartments at site).
Fig. 7.5.1: Busbar socket (1) with insulating part (2), contact tube (3) and
spiral contacts (4)
Fig. 7.5.2: Busbar connection, plugged in at one end Fig. 7.5.3: Busbar connection between the panels
Removal of intermediate panels Fully insulated bars can be connected with special busbar sockets
in an end panel (fig. 7.5.5).
The busbar connection with busbar socket, insulating part and
contact tube can be dismantled when the busbar is earthed, the
SF6 properly pumped out and the busbar compartment opened.
Fig. 7.5.4: Busbar enclosures with busbar end insulators (1) and busbar sockets (2)
1 2
The inner cone termination system is above all notable for its total
insulation and the associated protection against accidental con-
tact.
An overview of the cross-sections of the cables to be connected Table 7.6.1.1: Assignment of cable cross-sections
is presented in table 7.6.1.1. As the assignment of plug sizes to
the actual cable used can depend on further cable data, these are Rated voltage Cable cross-section
Plug size
to be discussed with the plug supplier. [kV] [mm 2]
2 25-300
Up to four cables per phase can be used, depending on the panel 12
3 120-800
design. 2 25-300
24
3 50-800
The current carrying capacity of the panels as stated is achieved 2 35-240
when all the sockets in the panel are evenly fitted with cables. 36
3 50-800
Fig. 7.6.1: View into the gas-insulated circuit-breaker compartment with Fig. 7.6.1.1: View into the cable termination compartment
inner cone sockets in air with cable plugs and cables
Fig. 7.6.2.1: Connection of a fully insulated bar using plug size 3 Fig. 7.6.3.1: Connection of surge arresters (1)
Outer cones are used in double feeder panels (width 2 x 400 mm) Shockproof cable connector systems are always to be used. A
and in panels as shown in fig. 8.1.1.2.1 (width 600 mm). selection of connector systems which can be used within the
space available is shown in tables 7.7.2.1 to 7.7.3.2. When mak-
Outer cone device termination components to EN 50181, fitted ing your selection, please take account of the current and short-
gas-tight in the wall between the panel module and the cable ter- circuit capacities of the cables and connector systems. Please
mination compartment, facilitate connection of cables and surge consult the latest catalogues from the manufacturers for precise
arresters (figs. 7.7.1 to 7.7.2). When the shutter on the cable ter- ordering details and information on any coupling units required.
mination compartment has been removed, the cables are acces-
sible from the rear of the system.
Fig. 7.7.1: View into the cable termination area with outer cones in air Fig. 7.7.2: View into the cable termination compartment in air with shock-
proof cable connectors (ABB type CSE-A) and cables
In the form of the product CSE-A, ABB offers outercone connec- All connector sleeves are routinely tested with regards to partial
tors for polymeric cables of all current cable cross-sections and discharge and AC, to ensure that supplied accessories are of
cable diameters. highest quality.
The connectors are made of rubber and they are cold mountable. The kits are supplied with adaptor, cable lug and connector hood
The outer conductive layer of the conductor ensures a touch proof with pre-installed earth conductor. Extra material such as earthing
system is approximate 2 mm thick and vulcanized together in one kits, crutch seals for 3-core cables and screen potential mate-
process with the insulation and inner deflector. This method gives rial for cable armouring is also within the ABB range of products.
a robust product with highest mechanical withstand. Kindly contact ABB Sales Representative for more information.
Fig. 7.7.1.1: Connector ABB type CSE-A-36630-01 Fig. 7.7.1.2: Connector ABB type Kabeldon CSE-A-36630-02
Table 7.7.1.1: Technical data of the connector ABB Kabeldon type CSE-A
Table 7.7.2.1 a: Selection of cable connectors, panel width 600 mm, 12 kV, max. 630 A
Cables fitted Cable connector manufacturer / connector type
Cable cross-section
Maximum operating
max. current
Südkabel GmbH
Three cables +
ABB Kabeldon
voltage
surge arrester
surge arrester
surge arrester
Two cables +
Three cables
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
● CSE-A 12630-01
CSE-A 12630-01
●
CSEP-A 12630-01
CSE-A 12630-01
25 - 70 ●
CSAP-A 12xx
CSE-A 12630-01
● CSEP-A 12630-01
CSAP-A 12xx
● 430TB CB12-630 RSTI-58xx
● ● 400TB/G
CB12-630 RSTI-58xx
● 430TBM-P2
CC12-630 RSTI-CC-58xx
CB12-630
● 430TBM-P3
2xCC12-630
430TB CB12-630 RSTI-58xx
●
300SA CSA12-... RSTI-CC-58SA
12 630 25 - 300
400TB/G
● ●
400PB
CB12-630 RSTI-58xx
430TBM-P2
● CC12-630 RSTI-CC-58xx
300SA
CSA12-... RSTI-CC-58SA
CB12-630
● 2 x CC12-630
CSA12-...
● SET12
SET12
●
SEHDK13.1
SET12
50- 300 ●
MUT13
SET12
● SEHDK13.1
MUT13
Cable cross-section
Maximum operating
max. current
Südkabel GmbH
Three cables +
ABB Kabeldon
voltage
surge arrester
surge arrester
surge arrester
Two cables +
Three cables
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
● 484TB/G
● 484TB/M-P2
● 484TB/M-P3
70 - 630 484TB/G
●
800SA
484TB/M-P2
●
800SA
● CSE-A 12630-02
CSE-A 12630-02
●
CSEP-A 12630-02
CSE-A 12630-02
95 - 300 ●
CSAP-A 12xx
CSE-A 12630-02
12 630 ● CSEP-A 12630-02
CSAP-A 12xx
● SEHDT13
300 - 500 SEHDT13
●
MUT33
400 ● CB36-630(1250)
500 CB36-630(1250)
●
630 CSA12-..
● CSE-A 12630-03 440TB/G
● 440TB/G-P2
CSE-A 12630-03 440TB/G
400 - 630 ●
CSAP-A 12xx 400PB
440TB/G-P2
●
400PB
Cable cross-section
Maximum operating
max. current
Südkabel GmbH
Three cables +
ABB Kabeldon
voltage
surge arrester
surge arrester
surge arrester
Two cables +
Three cables
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
● 400TB/G
CB12-630 RSTI-58xx
● 430TBM-P2
CC12-630 RSTI-CC-58xx
CB12-630 RSTI-58xx
● 430TBM-P3
2 x CC12-630 2 x RSTI-CC-58xx
CB12-630 RSTI-58xx
400TB/G
25 - 300 ● CC12-630 RSTI-CC-58xx
400PB
CSA12... RSTI-CC-58SA
430TBM-P2
●
300SA
CB12-630 RSTI-58xx
● 2 x CC12-630 2 x RSTI-CC-58xx
CSA12... RSTI-CC-58SA
● 484TB/M-P2
● 484TB/M-P3
484TB/M-P2
70 - 630 ●
800SA
484TB/M-P3
●
800SA
CSE-A 12630-02
12 1250 ●
CSEP-A 12630-02
CSE-A 12630-02
●
2 x CSEP-A 12630-02
CSE-A 12630-02
95 - 300
● CSEP-A 12630-02
CSAP-A 12..
CSE-A 12630-02
● 2 x CSEP-A 12630-02
CSAP-A 12..
300 - 500 ● SEHDT13
CB36-630(1250)
●
CC36-630(1250)
CB36-630(1250)
●
2 x CC36-630(1250)
400
CB36-630(1250)
500
● CC36-630(1250)
630
CSA12-...
CB36-630(1250)
● 2 x CC36-630(1250)
CSA12-...
Cable cross-section
Maximum operating
max. current
Südkabel GmbH
Three cables +
ABB Kabeldon
voltage
surge arrester
surge arrester
surge arrester
Two cables +
Three cables
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
CSE-A 12630-03
●
CSEP-A 12630-03
CSE-A 12630-03
●
2 x CSEP-A 12630-03
CSE-A 12630-03
● CSEP-A 12630-03
400 - 630 CSAP-A 12..
CSE-A 12630-03
● 2 x CSEP-A 12630-03
CSAP-A 12..
● 440TB/G-P2
440TB/G-P2
●
400PB
12 1250
● RSTI-x95x
RSTI-x95x
●
RSTI-CC-x95x
RSTI-x95x
●
2 x RSTI-CC-x95x
RSTI-x95x
●
400 - 800 RSTI-CC-68SA
RSTI-x95x
● RSTI-CC-x95x
RSTI-CC-68SA
RSTI-x95x
● 2 x RSTI-CC-x95x
RSTI-CC-68SA
Cable cross-section
Maximum operating
max. current
Südkabel GmbH
Three cables +
ABB Kabeldon
voltage
surge arrester
surge arrester
surge arrester
Two cables +
Three cables
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
● CSE-A 24630-01
CSE-A 24630-01
●
CSEP-A 24630-01
CSE-A 24630-01
25 - 70 ●
CSAP-A 24xx
CSE-A 24630-01
● CSEP-A 24630-01
CSAP-A 24xx
● SET24
SET24
●
SEHDK23.1
SET24
25- 240 ●
MUT23
SET24
● SEHDK23.1
MUT23
● CB24-630 RSTI-58xx
CB24-630 RSTI-58xx
●
CC24-630 RSTI-CC-58xx
24 630 CB24-630
●
2xCC24-630
CB24-630 RSTI-58xx
●
25 - 300 CSA24-... RSTI-CC-58SA
CB24-630 RSTI-58xx
● CC24-630 RSTI-CC-58xx
CSA24-... RSTI-CC-58SA
CB24-630
● 2 x CC24-630
CSA24-...
● K430TB
● ● K400TB/G
● K430TBM-P2
● K430TBM-P3
K430TB
35 - 300 ●
300SA
K400TB/G
● ●
400PB
K430TBM-P2
●
300SA
Cable cross-section
Maximum operating
max. current
Südkabel GmbH
Three cables +
ABB Kabeldon
voltage
surge arrester
surge arrester
surge arrester
Two cables +
Three cables
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
● K484TB/G
● K484TB/M-P2
● K484TB/M-P3
70 - 630 K484TB/G
●
800SA
K484TB/M-P2
●
800SA
● CSE-A 24630-02
CSE-A 24630-02
●
CSEP-A 24630-02
CSE-A 24630-02
95 - 300 ●
CSAP-A 24xx
CSE-A 24630-02
24 630 ● CSEP-A 24630-02
CSAP-A 24xx
● SEHDT23
300 - 500 SEHDT23
●
MUT33
400 ● CB36-630(1250)
500 CB36-630(1250)
●
630 CSA24-..
● CSE-A 24630-03 K440TB/G
● K440TB/G-P2
CSE-A 24630-03 K440TB/G
400 - 630 ●
CSEP-A 24630-03 400PB
K440TB/G-P2
●
400PB
Cable cross-section
Maximum operating
max. current
Südkabel GmbH
Three cables +
ABB Kabeldon
voltage
surge arrester
surge arrester
surge arrester
Two cables +
Three cables
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
CB24-630 RSTI-58xx
●
CC24-630 RSTI-CC-58xx
CB24-630 RSTI-58xx
●
2 x CC24-630 2 x RSTI-CC-58xx
CB24-630 RSTI-58xx
25-300
● CC24-630 RSTI-CC-58xx
CSA24... RSTI-CC-58SA
CB24-630 RSTI-58xx
● 2 x CC24-630 2 x RSTI-CC-58xx
CSA24... RSTI-CC-58SA
● K400TB/G
● K430TBM-P2
● K430TBM-P3
35 - 300 K400TB/G
●
400PB
K430TBM-P2
●
300SA
● K484TB/M-P2
● K484TB/M-P3
K484TB/M-P2
70 - 630 ●
800SA
K484TB/M-P3
24 1250 ●
800SA
CSE-A 24630-02
●
CSEP-A 24630-02
CSE-A 24630-02
●
2 x CSEP-A 24630-02
CSE-A 24630-02
95 - 300
● CSEP-A 24630-02
CSAP-A 24..
CSE-A 24630-02
● 2 x CSEP-A 24630-02
CSAP-A 24..
300 - 500 ● SEHDT13
CB36-630(1250)
●
CC36-630(1250)
CB36-630(1250)
●
2 x CC36-630(1250)
400
CB36-630(1250)
500
● CC36-630(1250)
630
CSA12-...
CB36-630(1250)
● 2 x CC36-630(1250)
CSA12-...
Cable cross-section
Maximum operating
max. current
Südkabel GmbH
Three cables +
ABB Kabeldon
voltage
surge arrester
surge arrester
surge arrester
Two cables +
Three cables
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
CSE-A 24630-03
●
CSEP-A 24630-03
CSE-A 24630-03
●
2 x CSEP-A 24630-03
CSE-A 24630-03
● CSEP-A 24630-03
400 - 630 CSAP-A 24..
CSE-A 24630-03
● 2 x CSEP-A 24630-03
CSAP-A 24..
● K440TB/G-P2
K440TB/G-P2
●
400PB
24 1250
● RSTI-x95x
RSTI-x95x
●
RSTI-CC-x95x
RSTI-x95x
●
2 x RSTI-CC-x95x
RSTI-x95x
●
400 - 800 RSTI-CC-68SA
RSTI-x95x
● RSTI-CC-x95x
RSTI-CC-68SA
RSTI-x95x
● 2 x RSTI-CC-x95x
RSTI-CC-68SA
Cable cross-section
Maximum operating
max. current
Südkabel GmbH
Three cables +
ABB Kabeldon
voltage
surge arrester
surge arrester
surge arrester
Two cables +
Three cables
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
● CB36-630
CB36-630
●
CC36-630
CB36-630
25 - 300 ●
CSA36-...
CB36-630
● CC36-630
CSA36-...
● M484TB/G
● M484TB/M-P2
● M484TB/M-P3
M484TB/G
●
35 - 630 800SA
M484TB/M-P2
●
800SA
36 630
M484TB/M-P3
●
800SA
● CSE-A 36630-01
50 - 70 CSE-A 36630-01
●
CSEP-A 36630-01
● M430TB
● M400TB/G
● M400TB/G-P2
● M430TBM-P2
M430TB
50 - 240 ●
300SA
M400TB/G
● ●
400PBxx
M430TBM-P2
●
300SA
Cable cross-section
Maximum operating
max. current
Südkabel GmbH
Three cables +
ABB Kabeldon
voltage
surge arrester
surge arrester
surge arrester
Two cables +
Three cables
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
● RSTI-68xx
RSTI-68xx
●
RSTI-CC-68xx
RSTI-68xx
50 - 300 ●
RSTI-CC-68SAxx
RSTI-68xx
● RSTI-CC-68xx
RSTI-CC-68SAxx
● SET36
70 - 300 SET36
●
MUT33
● CSE-A 36630-02
95 - 300 CSE-A 36630-02
●
CSEP-A 36630-02
36 630 ● SEHDT33
300 - 500 SEHDT33
●
MUT33
400 ● CB36-630(1250)
500 CB36-630(1250)
●
630 CSA36-..
● M440TB/G
● M440TB/G-P2
M440TB/G
300 - 630 ●
400PBxx
M440TB/G-P2
●
400PBxx
● CSE-A 36630-03
400 - 630 CSE-A 36630-03
●
CSEP-A 36630-03
Cable cross-section
Maximum operating
max. current
Südkabel GmbH
Three cables +
ABB Kabeldon
voltage
surge arrester
surge arrester
surge arrester
Two cables +
Three cables
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
CB36-630
●
CC36-630
CB36-630
●
2 x CC36-630
CB36-630
25 - 300
● CC36-630
CSA36-...
CB36-630
● 2 x CC36-630
CSA36-...
● M484TB/M-P2
35 - 630 M484TB/M-P2
●
800SA
● M400TB/G-P2
● M430TBM-P2
M400TB/G
50 - 240 ●
+400PBxx
M430TBM-P2
●
+300SA
RSTI-68xx
●
RSTI-CC-68xx
RSTI-68xx
●
36 1250 2 x RSTI-CC-68xx
RSTI-68xx
50 - 300
● 2 x RSTI-CC-68xx
RSTI-CC-68SA
RSTI-68xx
● 2 x RSTI-CC-68xx
RSTI-CC-68SA
CSE-A 36630-02
95 - 300 ●
CSEP-A 36630-02
300 - 500 ● SEHDT33
● M440TB/G-P2
300 - 630 M440TB/G-P2
●
400PBxx
CB36-630(1250)
●
CC36-630(1250)
CB36-630(1250)
●
2 x CC36-630(1250)
400
CB36-630(1250)
500
● CC36-630(1250)
630
CSA36-..
CB36-630(1250)
● 2 x CC36-630(1250)
CSA36-..
Cable cross-section
Maximum operating
max. current
Südkabel GmbH
Three cables +
ABB Kabeldon
voltage
surge arrester
surge arrester
surge arrester
Two cables +
Three cables
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
CSE-A 36630-03
400 - 630 ●
CSEP-A 36630-03
● RSTI-x95x
RSTI-x95x
●
RSTI-CC-x95x
RSTI-x95x
36 1250 ●
2 x RSTI-CC-x95x
400 - 800
RSTI-x95x
●
RSTI-CC-68SAxx
RSTI-x95x
● RSTI-CC-x95x
RSTI-CC-68SAxx
max. current
Südkabel GmbH
ABB Kabeldon
voltage
surge arrester
surge arrester
Two cables +
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
● CSE-A 12630-01
CSE-A 12630-01
●
CSEP-A 12630-01
CSE-A 12630-01
25 - 70 ●
CSAP-A 12xx
CSE-A 12630-01
● CSEP-A 12630-01
CSAP-A 12xx
● 430TB CB12-630 RSTI-58xx
● 400TB/G
CB12-630 RSTI-58xx
● 430TBM-P2
CC12-630 RSTI-CC-58xx
430TB CB12-630 RSTI-58xx
●
12 630 25 - 300 300SA CSA12-... RSTI-CC-58SA
400TB/G
●
400PB
CB12-630 RSTI-58xx
430TBM-P2
● CC12-630 RSTI-CC-58xx
300SA
CSA12-... RSTI-CC-58SA
● SET12
SET12
●
SEHDK13.1
SET12
50- 300 ●
MUT13
SET12
● SEHDK13.1
MUT13
Cable cross-section
Maximum operating
max. current
Südkabel GmbH
ABB Kabeldon
voltage
surge arrester
surge arrester
Two cables +
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
● 484TB/G
● 484TB/M-P2
484TB/G
70 - 630 ●
800SA
484TB/M-P2
●
800SA
● CSE-A 12630-02
CSE-A 12630-02
●
CSEP-A 12630-02
CSE-A 12630-02
95 - 300 ●
CSAP-A 12xx
12 630 CSE-A 12630-02
● CSEP-A 12630-02
CSAP-A 12xx
● SEHDT13
300 - 500 SEHDT13
●
MUT33
400 ● CB36-630(1250)
500 CB36-630(1250)
●
630 CSA12-..
● CSE-A 12630-03 440TB/G
400 - 630 CSE-A 12630-03 440TB/G
●
CSAP-A 12xx 400PB
Cable cross-section
Maximum operating
max. current
Südkabel GmbH
ABB Kabeldon
voltage
surge arrester
surge arrester
Two cables +
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
● CSE-A 24630-01
CSE-A 24630-01
●
CSEP-A 24630-01
CSE-A 24630-01
25 - 70 ●
CSAP-A 24xx
CSE-A 24630-01
● CSEP-A 24630-01
CSAP-A 24xx
● SET24
SET24
●
SEHDK23.1
SET24
25 - 240 ●
MUT23
SET24
● SEHDK23.1
MUT23
24 630 ● CB24-630 RSTI-58xx
CB24-630 RSTI-58xx
●
CC24-630 RSTI-CC-58xx
CB24-630 RSTI-58xx
25 - 300 ●
CSA24-... RSTI-CC-58SA
CB24-630 RSTI-58xx
● CC24-630 RSTI-CC-58xx
CSA24-... RSTI-CC-58SA
● K430TB
● K400TB/G
● K430TBM-P2
K430TB
●
35 - 300 300SA
K400TB/G
●
400PB
K430TBM-P2
●
300SA
Cable cross-section
Maximum operating
max. current
Südkabel GmbH
ABB Kabeldon
voltage
surge arrester
surge arrester
Two cables +
EUROMOLD
One cable +
Two cables
One cable
Tyco
[kV] [A] [mm2]
● K484TB/G
● K484TB/M-P2
K484TB/G
70 - 630 ●
800SA
K484TB/M-P2
●
800SA
● CSE-A 24630-02
CSE-A 24630-02
●
CSEP-A 24630-02
CSE-A 24630-02
95 - 300 ●
CSAP-A 24xx
24 630 CSE-A 24630-02
● CSEP-A 24630-02
CSAP-A 24xx
● SEHDT23
300 - 500 SEHDT23
●
MUT33
400 ● CB36-630(1250)
500 CB36-630(1250)
●
630 CSA24-..
● CSE-A 24630-03 K440TB/G
400 - 630 CSE-A 24630-03 K440TB/G
●
CSAP-A 24xx 400PB
The main earthing bar of the switchgear system runs through the cessible in the cable termination compartment, and are used to
cable termination compartments of the panels. The earthing bars accommodate surge arresters (fig. 7.9.6), for cable tests, for insu-
in the individual panels are connected together during installa- lation testing of the panels, for testing of the protection systems
tion at site. The cross-section of the main earth bar is 400 mm2 by primary current injection and for maintenance earthing of the
(ECuF30 40 mm x 10 mm) (Exception: The cross-section of main relevant outgoing feeder panel. Suitable testing and earthing sets
earth bars in double feeder panels is 30 mm x 8 mm). are available for these purposes (figs. 7.9.3 to 7.9.5).
Details on earthing the switchgear can be found in section 11.7. When sensors are used, these sensors contain the test sockets.
The test sockets must be closed off with blanking plugs of high
dielectric strength during normal operation of the panel.
7.9 Test sockets
Outgoing cable panels and cable termination panels are equipped
with test sockets (figs. 7.9.1 and 7.9.2). The test sockets are ac-
Fig. 7.9.2: View from the rear into the cable termination compartment: Test
sockets (1) – access blocked by insulating blanking plugs; main earth-
ing bar (transport condition) (2); cable blanking plug (3) for unused cable
Fig. 7.9.1: View into the circuit-breaker compartment: test sockets sockets, and wiring for capacitive indicator unit (4).
2 3 1 4
Fig. 7.9.3: Current test plug Fig. 7.9.4: Voltage test plug
Various capacitive, low impedance voltage indicator systems are CAVIN-System (Abb. 7.10.4)
available for checking of the off-circuit condition of a feeder. The
coupling electrode is integrated in the test sockets or in the sen- As the KVDS-system, but:
sors and – when an additional capacitive voltage indicator system
is fitted in the panel door – in the cable sockets. The capacitive – – Two integrated relay contacts for signals/interlocks
voltage indicator system is located at the rear of the panel. A – – LED display of relay status:
further system in the low voltage compartment door can also be –– No Error: Relay 1 closed (All three conductors have the
used. same voltage state and auxiliary voltage is available.
–– Error: Relay 1 open (The three conductors are carrying
All systems used are voltage detection systems (VDS) according different voltages, or the auxiliary voltage has failed.)
to IEC 61243-5. –– HV OFF:
Relay 2 closed (UL1 = UL2 = UL3 < phase to earth voltage
All the systems used permit phase comparison with the aid of an when the response voltage is reached.)
addition, compatible phase comparator. –– HV ON:
Relay 2 open (In at least one phase, U / √3 > phase to
LRM-system (Fig. 7.10.1) earth voltage when the response voltage is reached, or
auxiliary voltage has failed.)
– – Additional indicator unit (fig. 7.10.2) required –– Auxiliary voltage required for the relays
–– Repeat testing necessary
–– LC-display
–– Three phase
–– No additional indicator unit required
–– Maintenance-free with integrated self-test:
– – No symbol visible: De-energized
– – Half lightning arrow displayed: Voltage applied
– – Full lightning arrow displayed:
Voltage applied and self-test passed
Additional indicator
Integrated self-test
Installation point:
Auxiliary voltage
unit required
panel door
LC-display
panel rear
System
istics
The areas of application for current and voltage detection devices the secondary circuit is proportional to the change in time of the
are primary current. The current sensor signal therefore has a phase
shift of 90°, which has to be compensated for by integration in the
–– Protection applications, subsequent processing.
– – Measurement,
– – Billing metering. Voltage transformers
Inductive voltage transformers are low capacity transformers in
Conventional current and voltage transformers and/or current and which the primary and secondary voltage is proportional and in
voltage sensors may optionally be used. phase. The primary and secondary windings are electrically iso-
lated from each other.
Current transformers
Voltage sensors
The inductive transmission principle of a current transformer is
based on the use of a ferromagnetic core. Irrespective of its The voltage sensor functions on the principle of a potentiometer-
structure as a bushing or block-type transformer, bar-primary or type resistor. The output signal from the voltage sensor is propor-
wound-primary transformer, a current transformer is in principle tional to the primary voltage and linear throughout the working
subject to hysteresis and saturation. In the rated current range, range.
the primary and secondary currents are proportional and in phase
.
Current sensors
– – Device A: Ring core current transformer for fitting to the – – Device E: Current sensor in the circuit-breaker compart-
outer cone bushing ment
– – Device B: Block-type transformer, block-type sensor or – – Device F: Optional bushing-type current transformer be-
combined block-type transformer/sensor in the circuit- tween the three position disconnector and circuit-breaker
breaker compartment in a sectionaliser and riser panel
– – Device C: Current transformer in the circuit breaker com- – – Device G: Voltage transformer (outside the gas compart-
partment ment only, plug-in type)
B
A
G
Panels with only one cable per phase can also be fitted on
request with ring core current transformers in the form of
straight-through transformers for cables.
Fig. 7.11.1.1: Ring core current transformer (device A) Fig. 7.11.1.2: Ring core current transformer up to 1250 A
Table 7.11.1.1: Technical data of the ring core current transformers (primary data)
Type og current transformer 1 2
Rated voltage Ur kV 0,72
Rated short duration power-frequency withstand voltage Ud kV 3
Rated frequency fr Hz 50 / 60
Rated thermal short-time current Itherm kA 25 31,5
Rated impulse current Ip kA 62,5 100
Capacity 1)
VA 2,5 to 15 ...20
Measuring cores
Class 1)
0,2 / 0,5 / 1
Capacity 1)
VA 2,5 to 15 ...20
Protection cores Class 1)
5P to 10P 5P
Overcurrent factor 1)
10 to 20 20
1)
Depending on rated primary current
The block-type instrument transformer (fig. 7.11.2.1 and 7.11.2.2) one tap. The measurement accuracy is better than 1%.
or block-type sensor is used in outgoing feeder panels with inner
cone cable connection system for rated currents up to 1250 A 1) Voltage sensor
and in various bus tie panels for rated currents up to 2500 A.
The voltage sensor for operating voltages up to 6 kV has a ratio of
The block-type transformer or block-type sensor consists of cast 5000 : 1, for up to 24 kV a ratio of 10000 : 1, and for 36 kV a ratio
resin in which the corresponding components are embedded. It is of 20000 : 1. The measurement accuracy is better than 1%.
located in the gas compartment, and is therefore protected from
external influences. The terminal board is easily accessible from Current transformer
the outside and lead-sealable. The cross-section of the connect-
ing wires is 2.5 mm² (larger cross-sections on request). When only current transformers are used, the device can contain
At low primary currents, the block-type transformer provides the up to 3 current transformer cores in a 600 mm wide panel and up
opportunity to lay the primary conductor around the iron core in to 5 current transformer cores in an 800 mm wide panel.
several windings (wound-primary transformer). This can signifi-
cantly increase the performance of the transformer. The possible
technical data can be found in table 7.11.5.1.
Current sensor
Fig. 7.11.2.1: Block-type transformer or block-type sensor, device B Fig. 7.11.2.2: Circuit diagram of the block-type transformer/sensor
(example)
P1
Current-sensor
Current-transformer
Voltage-sensor
P2
Outgoing feeder panels for currents > 1250 A are fitted with cur-
rent transformers as shown in fig. 7.11.3.1. These transformers
are located in the gas compartment and can accommodate up to
5 cores.
The secondary wiring of the current transformer is routed out of
the gas compartment into the low voltage compartment via sec-
ondary bushings below the circuit-breaker. The cross-section of
the connecting wires is 2.5 mm² (larger cross-sections on request).
The technical data can be found in table 7.11.5.1.
The direct path to the right current transformers is via Further information for different protection systems
the technical documentation of the selected protection
device. The current transformer requirements of the relay If the current transformers to be used in the network concerned
can be found there. (e.g. on the opposite side of the network) have already been
specified, early coordination of the switchgear configuration is ad-
visable. This requires, but is not limited to, the provision of data on
the ratio, rated capacity, accuracy class, and the resistance of the
secondary winding and secondary wiring. Further configurations
for the particular application can then be requested.
Table 7.11.5.1: Technical data of the current transformers (primary data), device B and C
Rated voltage Ur kV ...24 ...36
Max. operating voltage kV 24 40.5
Rated short duration power-frequency withstand voltage Ud kV 50 70 (85)
Rated lightning impulse withstand voltage Up kV 125 170 (185)
Rated frequency fr Hz 50 / 60
100 / 250 x I r,
Rated thermal short-time current Itherm
max. 40 kA - 3 s
Rated impulse current Ip kA 100
1)
Depending on rated primary current
The voltage transformers are always located outside the gas com-
partments. They are of the plug-in type (plug size 2 to EN 50181
and DIN 47637). The voltage transformers can be dismantled for
test purposes.
Feeder automation
Bay control and
Metering panel
measurement
Transformer
Generator
protection
protection
protection
regulation
Incomer
Voltage
Feeder
tection
Motor
tion
SPAM 150 C ●
Basic SPAJ 160 C ●
REU 610 ● ●
Range REM 610 ●
REF 610 ● ● ●
REF 615 ● ● ● 1)
●
Middle RED 615 ● 1)
●
RET 615 ● 1)
●
Range REM 615 ● 1)
●
REU 615 ● ● ● 1)
●
Motor ●
REM 543
Generator ●
Motor ●
REM 545
Generator ● ●
RET 541 Control ●
RET 543 Basic ● ●
RET 545 Multi ● ●
REF 541 Control ●
High REF 543 Basic ● ● ● ● ● ● ●
REF 545 Multi ● ● ● ● ● ● ●
Range Basic low ● ● ● ●
Basic ● ● ● ●
Multi low ● ● ● ●
REF 542plus
Multi ● ● ● ● ● ●
Differential ● ●
Distance ● ● ● ● ● ● ● ●
REF 630 ● ● ● ●
RET 630 ●
REM 630 ●
1)
Control of a circuit-breaker is possible
Sulphur hexafluoride (chemical symbol SF6) is non-toxic, non- Each panel has gas filling connectors (fig 7.14.1 - see also section
combustible, chemically inactive gas with a high dielectric strength. 6), through which the gas compartments can be filled with gas, for
instance in the case of repairs.
Its ununique electrical and thermal properties have made the de-
sign of new, more efficient switchgear possible. The change from The service pressure in the individual gas compartments is moni-
conventional insulation to the non-flammable, chemically inactive tored by separate density sensors (temperature-compensated
and non-toxic heavy gas sulphur hexafluoride has led to significant pressure sensors, fig 7.14.1). A shortfall below the insulation
savings in space and materials, and to greater safety of the instal- warning level (120 kPa) in a gas compartment is indicated on the
lations. Switchgear systems insulated with sulphur hexafluoride protection and control unit or by a signal lamp. Temporary opera-
have become highly successful especially in applications where tion of the panel at atmospheric pressure ( > 100 kPa) is in princi-
space is constricted and compact design is required. On account ple possible if the SF6 content of the insulating gas is at least 95 %
of their insensitivity to air-pollution, enclosed SF6 systems are also (exceptions: 120 kPa required for rated voltage > 36 kV, and
used in the chemicals industry, in desert areas and at coastal lo- 110 kPa for operation of a double feeder panel with rated voltage
cations. > 17.5 kV).
SF6 has been used in HV-switchgear since 1960. As an option, the thermal effects of an internal arc fault can be lim-
ited by an Ith protection function. For this purpose, the signal from
an additional switching contact for all the gas density sensors
7.14 Gas system (threshold 190 kPa) is logically linked to an overcurrent excitation
system and used to trip defined circuit-breakers. The logic opera-
in the panels tion is performed by the combined protection and control unit RE_,
and reduces the breaking time to only approx. 100 ms.
The gas compartments are designed as hermetically sealed pres- The leakage rate of the gas compartments is determined by inte-
sure systems. As they are filled with SF6, constant ambient condi- gral leakage testing:
tions are permanently ensured for the entire high voltage area of The panel is placed in a test chamber. The panel and the test
the panel. It is not necessary to top up the insulating gas during chamber are evacuated. The gas compartments in the panel are
the expected service life of the system. Under normal operating filled with helium. In this condition, the leakage rate is determined
conditions, no checks on the insulating gas are necessary. The by measurement of the helium content in the test chamber. The
insulating gas is maintenance-free. helium is recovered after measurement, and the gas compart-
ments in the panel simultaneously evacuated. They are then filled
The circuit-breaker compartment and the busbar compartment with SF6 at the rated filling pressure for insulation (130 kPa at
in each panel are separate gas compartments with their own 20 °C). This means that systems are only filled with SF6 when they
gas filling connectors (fig. 7.14.1). The gas compartments of the have successfully passed the leakage test.
individual panels in a row are not connected together (exception:
double feeder panels).
Fig. 7.14.1: Gas filling connector (1) and density sensor (2)
1 2
Fig. 7.15.1 shows the function of the SF6 density sensor. Between Gas losses
the measuring chamber and a reference chamber there is a mov-
ing mounting plate which operates electrical contacts. A loss of gas in the monitored gas compartment results in a drop
in pressure in the measuring volume and thus a movement of the
Temperature compensation mounting plate (to the left in fig. 7.15.1). The contact for the pres-
sure loss signal is operated.
The pressure in the monitored gas compartment rises with in-
creasing temperature. As, however, the temperature in the refer- Two versions of SF 6 density sensors
ence chamber and thus the pressure of the reference volume
increases to the same extent, this does not lead to any movement Two versions of the density sensors (figs. 7.15.2 and 7.15.3) are
of the mounting plate. used.
1 2 4 6
5 3
1 Monitored gas compartment
2 Measuring volume
3 Enclosed volume for temperature compensation (reference volume)
4 Mounting plate moved by interaction of forces (pressure of measuring volume
against pressure of reference volume)
5 Contact for self-supervision (p > 150 kPa)
6 Contact for gas loss (p < 120 kPa)
Fig. 7.15.2: Version 1 of the SF6 density sensor Fig. 7.15.3: Version 2 of the SF6 density sensor
In the unlikely event of an internal arc fault in a gas compartment, The gas-tight enclosures of the panels consist of stainless steel
the relevant pressure relief disk opens. sheets. The cable termination compartments, the low voltage
compartments, the covered pressure relief ducts at the rear and
There is an opportunity to discharge pressure via pressure relief the pressure relief ducts on the busbar compartments are manu-
ducts and an absorber into the switchgear room or to the outside. factured from galvanised sheet steel, and therefore surface treat-
ment is not required in these cases.
Pressure relief via pressure relief ducts and absorbers The covers at the rear of the panels and the end covers at the
into the switchroom (fig. 7.16.1) sides of the switchgear system can be supplied galvanised or
optionally coated with a powder stove enamel in RAL 7035 (light
Discharge of pressure from the circuit-breaker compartments and grey).
cable termination compartments is effected via the rear pressure
relief duct, and then through a pressure relief duct designed as a Other colours for the painted components are available on re-
broad end cover at the side of the switchgear block into the up- quest.
per duct. Discharge of pressure from the busbar compartments is
directed into the upper pressure relief duct. The pressure surge is
cooled in the (plasma) absorber located above the upper duct and
released into the switchgear room.
8 Range of panels
Pressure relief to the outside via pressure relief ducts and
absorbers (fig. 7.16.2)
The following panel variants are available in single and double bus-
Discharge of the pressure takes place in principle in the same way bar versions:
as pressure relief via absorbers. The pressure is discharged into
the open air by means of a customised pressure relief duct exten- –– Incoming and outgoing feeder panels
sion leading to an opening in the outside wall of the switchroom –– Cable termination panels
–– Sectionaliser panels
The building wall through which the pressure relief duct is led –– Metering panels
to the outside must not contain any combustible materials. The –– Double feeder panels
area outside below the pressure relief discharge opening is to be –– Customised panel versions
fenced off and marked with warning signs. There must not be any
accessible areas such as stairs or walkways above the pressure
relief opening. Storage of combustible materials in the areas men-
tioned is prohibited. The dimensions of these safety areas are to
be clarified for the individual system supplied.
Fig. 7.16.1: Pressure relief duct (discharging into the switchroom) Fig. 7.16.2: Pressure relief duct (discharging to the outside)
2785 1)
2600 1)
2300
1)
Without taking account of voltage transformers or heat sinks on busbar compartments
2300
1760 1760
Fig. 8.1.1.1.3: Feeder panel 2000 A with current and voltage transformer Fig. 8.1.1.1.4: Feeder panel 2500 A with current and voltage transformer
and three cables per phase and four cables per phase, cooling by heat sinks
2300
2870
1760
2090
Fig. 8.1.1.1.5: Feeder panel 2500 A with current sensor, voltage transform-
er and three cables (630 mm2) per phase, cooling by fan
2500
1760
Voltage sensor Inner cone socket 2nd coupling electrode Current transformer
1..3 x Size 2 or for capacitive voltage Current sensor
1..4 x Size 3 indicator in the door
Surge arrester
Current sensor
Voltage sensor
up to 1250 A
Current sensor
Voltage sensor
Current transformer
up to 1250 A
Table 8.1.1.1.1: Overview of variants of incoming and outgoing feeder panels with inner cone termination system
U r: ... 36 kV
I r: ... 800 A (1 x size 2)
Panel width 600 mm: I r: ... 1250 A (2 ... 3 x size 2 and 1 ... 2 x size 3) 1)
I p: ... 31.5 kA ( Ur ≤ 36 kV )
I p: ... 40 kA ( Ur ≤ 17.5 kV )
U r: ... 36 kV
I r: ... 800 A (1 x size 2)
Panel width 800 mm: I r: ... 1250 A (2 x size 2 and 1 ... 3 x size 3) 1)
I r: ... 2500 A (3 ... 4 x size 3)
I p: ... 40 kA
1)
Three sockets per phase only in conjunction with current transformers to fig. 7.11.3.1
Fig. 8.1.1.2.1: Feeder panel with outer cone, 1250 A Fig. 8.1.1.2.2: Double feeder panel 24 kV, 630 A
2300
2300
1760 1760
Voltage
transformer,
isolatable and
plugged
Table 8.1.1.2.1: Overview of variants of feeder panels with outer cone termination system
U r: ... 36 kV
I r: ... 1250 A
Panel width 600 mm:
I p: ... 31.5 kA ( Ur ≤ 36 kV )
I p: ... 40 kA ( Ur ≤ 17.5 kV )
U r: ... 24 kV
Double feeder panel
I r: ... 630 A
Panel width 2 x 400 mm:
I r: ... 25 kA
The structure of the double feeder panel deviates from that of a –– Only the outer cone plug system (one or two cables per
conventional outgoing feeder panel as described below. phase) to DIN 47636 is used.
–– The double panel facilitates even more compact station –– Only ring core current transformers or ring core sensors are
planning for systems up to 24 kV. used.
–– The width (= transport width) of a double feeder panel –– Two separate low voltage compartment doors (width 400
is 800 mm, with two outgoing feeders of 400 mm width mm) are fitted.
grouped together in the double panel.
–– Technical data which deviate from the conventional panel
–– The busbar compartment for the two feeders in a double (compare section 4):
feeder panel is a continuous gas compartment extending
over the panel width of 800 mm. Ur: ...24 kV
–– Ik: ...25 kA
–– The two circuit-breaker compartments in a double feeder Ir (feeder): ...630 A
panel are two independent units. Ir (busbar): ...2500 A
Fig. 8.1.1.2.3: Double feeder panel: version with busbar at the front, two cables per phase and surge arresters
400 mm
800 mm
Incoming feeder panels ( Ir up to 4000 A, fig. 8.1.1.3.1) Outgoing feeder panels within a block with parallel bus-
bars ( I r up to 2500 A, fig. 8.1.1.3.2)
In this version, the busbars of two double busbar panels of
800 mm width each are connected in parallel by the disconnec- The feeder current coming from the two parallel busbars is fed via
tors. These two panels thus perform the function of a single bus- the two disconnectors and the circuit-breaker to the cable sock-
bar panel for currents up to 4000 A. ets. This double busbar panel thus performs the function of a sin-
gle busbar panel with one busbar for currents up to 4000 A.
The operating current coming from the cable sockets is fed via the
two circuit-breakers and the four disconnectors in the two panels Display of the switch positions and control of the switching de-
to the two parallel busbars. vices are effected by the human-machine interface of the protec-
tion and control unit. The function of the panel as a single busbar
Display of the switch positions and control of the switching de- panel is shown on the display of this human-machine interface.
vices are effected at the master control unit (only one of the two
human-machine interfaces is used for display and control). The On earthing, the earthing switch is operated while the pure dis-
function of the two panels as a single busbar panel is shown on connector remains in the OFF position.
the display of this human-machine interface.
The variants for this panel version can be found in section 8.2.1.
On earthing, the two earthing switches are operated while the
pure disconnectors remain in the OFF position.
2090
1760
Fig. 8.1.1.4.1: Cable termination panel 2000 A Fig. 8.1.1.4.2: Cable termination panel 1250 A with voltage transformer at
the cable
2300
2300
1760 1760
U r: ... 36 kV
Panel width 800 mm: I r: ... 2500 A (3 or 4 x size 3)
I p: ... 40 kA
The sectionaliser panel contains the circuit-breaker, two three In addition, sectionalisers can be fitted with current transformers
position disconnectors and a block-type current transformer or between the circuit-breaker and the three position disconnectors.
current sensor. In the sectionaliser panel, the position of the busbar changes from
front to rear or vice versa.
Fig. 8.1.2.1.1: Sectionaliser panel 1250 A with block-type CT or sensor Fig. 8.1.2.1.2: Sectionaliser panel 2000 A with current transformers
2300
2300
1760 1760
Bushing-type CT
only in panel width
800 mm
Block-type CT or
sensor
4 variants:
U r: ... 36 kV - without transformers
Panel width 800 mm: I r: ... 1250 A or ...2500 A - Block-type CT or sensor
I p: ... 40 kA - Bushing-type CT
- Block-type CT or sensor + Bushing-type CT
2300
1760 1760
Sockets for plug-in voltage transformers are provided above the –– For 800 mm wide panels including double feeder panels.
busbar compartment in outgoing feeder panels with integrated –– For panels without cooling systems.
measurement. The following limitations to the use of integrated –– Not for sectionaliser panels.
measurement must be taken into account at the planning stage: –– The distance from the end of the system with pressure
relief duct must be three panel widths.
–– For 800 mm wide panels including double feeder panels. – – The ceiling height must be at least 3500 mm
–– For panels without cooling systems. – – The transport unit height is 2330 mm
–– Not for sectionaliser panels. – – Gas work at site is necessary.
–– The distance from the end of the system with pressure
relief duct must be three panel widths.
– – The ceiling height must be at least 3000 mm
– – The transport unit height is 2300 mm
2585
2300
1760 1760
Fig. 8.1.3.2: Integrated busbar metering system with plugged-in and isolat-
able voltage transformers (example for measurement of the front busbar)
3130
1760
Fig. 8.2.1.1.1: Feeder panel 800 A with block-type transformer or sensor Fig. 8.2.1.1.2: Feeder panel 1250 A with block-type transformer or sensor
and one cable per phase and two cables per phase
2300
2300
1760
1760
Fig. 8.2.1.1.3: Feeder panel 2000 A with current and voltage transformer Fig. 8.2.1.1.4: Feeder panel 2500 A with current and voltage transformer
and three cables per phase and four cables per phase, cooling by heat sink
2300
2870
1760
Fig. 8.2.1.1.5: Feeder panel 2500 A with current sensor and voltage trans- 2090
former and three cables (630 mm2) per phase, cooling by fan
2500
1760
Voltage sensor Inner cone socket 2nd coupling electrode Current transformer
1..3 x size 2 or for capacitive voltage Current sensor
1..4 x size 3 indicator in the door
Surge arrester
Current sensor
Voltage sensor
up to 1250 A
Current sensor
Voltage sensor
Current transformer
up to 1250 A
Table 8.2.1.1.1: Overview of variants of incoming and outgoing feeder panels with inner cone termination system
U r: ... 36 kV
I r: ... 800 A (1 x size 2)
Panel width 600 mm: I r: ... 1250 A (2 ... 3 x size 2 and 1 ... 2 x size 3) 1)
I p: ... 31.5 kA ( Ur ≤ 36 kV )
I p: ... 40 kA ( Ur ≤ 17.5 kV )
U r: ... 36 kV
I r: ... 800 A (1 x size 2)
Panel width 800 mm: I r: ... 1250 A (2 x size 2 und 1 ... 3 x size 3) 1)
I r: ... 2500 A (3 ... 4 x size 3)
I p: ... 40 kA
1) Three sockets per phase only in conjunction with current transformers to fig. 7.11.3.1
2300
2300
1760 1760
Voltage
transformer,
isolatable and
plugged
Table 8.2.1.2.1: Overview of variants of feeder panels with outer cone termination system
U r: ... 36 kV
I r: ... 1250 A
Panel width 600 mm:
I p: ... 31.5 kA ( Ur ≤ 36 kV )
I p: ... 40 kA ( Ur ≤ 17.5 kV )
U r: ... 24 kV
Double feeder panel
I r: ... 630 A
Panel width 2 x 400 mm:
I r: ... 25 kA
The structure of the double feeder panel deviates from that of a –– Only the outer cone plug system (one or two cables per
conventional outgoing feeder panel as described below. phase) to DIN 47636 is used.
–– The double panel facilitates even more compact station –– Only ring core current transformers or ring core sensors are
planning for systems up to 24 kV. used.
–– The width (= transport width) of a double feeder panel –– Two separate low voltage compartment doors (width
is 800 mm, with two outgoing feeders of 400 mm width 400 mm) are fitted.
grouped together in the double panel.
–– Technical data which deviate from the conventional panel
–– The busbar compartment for the two feeders in a double (compare section 4).
feeder panel is a continuous gas compartment extending
over the panel width of 800 mm. Ur: ...24 kV
Ik: ...25 kA
–– The two circuit-breaker compartments in a double feeder Ir (feeder): ...630 A
panel are two independent units. Ir (busbar): ...2500 A
Fig. 8.2.1.2.3: Double feeder panel: version with two cables per phase and surge arresters
Busbar at rear
Busbar at front
400 mm
800 mm
Fig. 8.2.1.3.1: Cable termination panel 1250 A (Example with continuous Fig. 8.2.1.3.2: Cable termination panel 2000 A (Example with continuous
busbar at the front) busbar at the rear and voltage transformer on the outgoing feeder)
2300
2300
1760 1760
or
U r: ... 36 kV
Panel width 800 mm: I r: ... 2500 A (3 or 4 x size 3)
I p: ... 40 kA
Fig. 8.2.2.1.1: Sectionaliser panel for the front busbar, 2000 A Fig. 8.2.2.1.2: Riser panel for the front busbar, 2000 A
2300
2300
1760 1760
Bushing-type CT
(only in panel width 800 mm)
Block-type CT
or sensor
1760 1760
Fig. 8.2.2.3.1: Bus coupler, 1250 A with block-type CTs or sensors Fig. 8.2.2.3.2: Bus coupler, 2000 A, with sensors or CTs between the
circuit-breaker and the three position disconnectors
2300
2300
1760 1760
Bushing-type CT
(only in panel depth 800 mm)
Block-type CT
or sensor
Section A-A
A
2300
1760
Table 8.2.3.1: Overview of variants for the bus coupler panels without circuit-breaker
U r: ...36 kV
I r: ...2000 A or
Panel width 800 mm:
I r: ...2500 A (cooling only with heat sinks)
I p: ...40 kA
The following methods of busbar metering are available: The integrated busbar metering system with plugged-in and iso-
latable voltage transformers
The metering panel
Above the busbar compartment of an outgoing feeder panel with
The metering panel with a width of 600 mm contains isolatable integrated busbar metering, there are sockets for plug-in voltage
voltage transformers. Operation of the isolating system is per- transformers and a series isolating device. As a snap-action oper-
formed at the low voltage compartment. ating mechanism is used, operation of the isolating device is even
possible when the busbar is live. The following limitations must
Integrated metering with plugged-in voltage transformers be taken into account in the planning when an integrated busbar
metering system with isolatable voltage transformers is used:
Sockets for plug-in voltage transformers are provided above the
busbar compartment in outgoing feeder panels with integrated –– For 800 mm wide panels including double feeder panels.
measurement. The following limitations to the use of integrated –– For panels without cooling systems.
measurement must be taken into account at the planning stage: –– Not for sectionaliser panels.
–– The distance from the end of the system must be three
–– For 800 mm wide panels including double feeder panels. panel widths to the side pressure relief duct.
–– For panels without cooling systems. – – The ceiling height must be at least 3500 mm
–– Not for sectionaliser panels. – – The transport unit height is 2330 mm
–– The distance from the end of the system with pressure – – Gas work at site is necessary.
relief duct must be three panel widths.
– – The ceiling height must be at least 3000 mm
– – The transport unit height is 2300 mm
2585
2300
1760 1760
Fig. 8.2.4.3: Integrated busbar metering system with plugged-in and isolat-
able voltage transformers (example for measurement of the front busbar)
3130
1760
The panel variants presented in sections 8.1 to 8.2 are standard IAC qualification according to IEC 62271-200 of special panels
panels. Should you require panel variants which are not listed may not be possible in all cases.
there when planning your switchgear, please contact the ABB
office responsible for your area. Our design team will be pleased
to submit and implement technical proposals to fulfil your require-
ments.
1760 1760
Fig. 8.3.2: Panel for capacitor switching (36 kV, 40 kA, 800 A) Fig. 8.3.3: Panel with additional three-position disconnector and cable
earthing switch (36 kV, 40 kA, 1250 A)
2300
2300
1760
1760
At a maximum ambient air temperature of 40 °C, a maximum 24 h The positions of the relevant fans and heat sinks are shown in the
average ambient air temperature of 35 °C and a rated frequency illustrations below.
of 50 Hz (standard operating conditions), no cooling facilities are
required for a rated current of up to 2000 A. A: Radial flow fan
B, C: Heat sink on the busbar compartment
For standard operating conditions and rated currents > 2000 A D: Heat sink on the circuit-breaker compartment
(max. 2500 A), two cooling methods are available as alternatives:
The cooling of the sectionaliser panel with-out circuit breaker (sec-
–– Forced ventilation by fans, combined with heat sinks if tion 8.2.3.1) for rated currents > 2000 A is effected only with heat
necessary. sinks.
A A A
D D D
Double busbar Single busbar at the front Single busbar at the rear
C B B C
D D D
Double busbar Single busbar at the front Single busbar at the rear
may deviate from the cooling methods stated above. Such special
cases can be investigated on request.
– – Panels with fans can be positioned as the first, second, With the outgoing feeder earthed, the test sockets can be fitted
and anywhere from the fourth panel at the absorber end. with an earthing set (fig. 7.9.5) connected to the main earthing bar.
Earthing of the busbar is effected via the closed feeder disconnec-
– – A panel with heat sink B and/or C (section 8.4) must have tor and subsequently closed circuit-breaker (see fig. 10.1.1).
at least one free side (with-out heat sink or busbar meas-
urement).
Earthing set
Pressure stress on the switchroom Heaters are to be fitted in the low voltage compartments to pre-
clude condensation phenomena (outside the gas-tight enclosures)
With pressure relief inside the switchroom, a pressure rise in the resulting from major rapid temperature fluctuations and corre-
room can be expected in the – highly unlikely – event of an inter- sponding humidity. The specified temperature conditions accord-
nal arc fault. This is to be taken into account when planning the ing to IEC 62271-1 (> -5 °C) are also to be ensured by means of
building. The pressure rise can be calculated by ABB on request. room heating.
Pressure relief openings in the switchroom may be necessary.
Planning of the space required for the switchgear must take account of the escape routes,
− − the possibility of inserting panels into an existing row,
− − the boundary conditions for IAC qualification, and
–– space required for dismantling and assembly of voltage transformers.
Fig. 11.2.1: Example of a single row installation (Top view, dimensions in mm)
50 1) 250 2)
> 800 5)
1760 6)
3)
Fig. 11.2.2: Example of a double row installation (Top view, dimensions in mm)
50 1) 250 2)
> 800 5)
1760 7)
3)
1760 7)
> 800 5)
1)
End cover
2)
Lateral pressure relief duct
3)
Door height: > 2300 mm (with integrated measurement: > 2500 mm, with heat sinks mounted on a busbar compartment: 3200 mm)
4)
Recommended dimension taking account of the insertion of panels into an existing row (can possibly be reduced as stated in section 11.3)
5)
Recommended dimension; can be reduced under certain circumstances as stated in section 11.3
6)
Observe the notes on escape routes in section 11.3.
7)
With heat sinks at the circuit-breaker compartment: 2090 mm; the data on panel depth apply to low voltage compartments of 400 mm depth.
The aisle width in front of the switchgear is to be planned with at- into the escape routes. ... Exits shall be arranged so that the
tention to the need to remove panels from or insert panels into ex- length of the escape route within the room ... does not exceed
isting rows, and to the requirements of the relevant standards (see … 20 m. ... If an operating aisle does not exceed 10 m, one exit
IEC 61936 and IEC 62271-200). The minimum and recommended is enough. An exit or emergency possibilities shall be provided at
minimum aisle widths can be found in tables below. both ends of the escape route if its length exceeds 10 m. ... The
minimum height of an emergency door [possibly the 2nd door] shall
“Aisles shall be at least 800 mm wide. ... Space for evacuation be 2 000 mm [clear height] and the minimum clear opening 750
shall always be at least 500 mm, even when removable parts or mm.” 1)
open doors, which are blocked in the direction of escape, intrude
Table 11.3.1: Restrictive conditions on minimizing the aisle widths in front of the switchgear
Minimum aisle width Recommended aisle width Aisle width required for
(Doors close in the direction taking no account of remov- removal and insertion of
of the escape route) al or insertion of panels panels
Minimum aisle width Recommended aisle width Aisle width required for
taking no account of remov- removal and insertion of
al or insertion of panels panels
1)
Take the depth of low voltage compartment (400 mm or 500 mm) into account.
2)
Tiefe des Geräteschrankes (400 mm oder 500 mm) beachten
Table 11.3.2: IAC qualification on reduction of the wall distance behind the switchgear and the side wall distance
Wall distance behind Wall distance to the side of the IAC qualification when a pressure IAC qualification when a pressure
the switchgear switchgear (at one or both ends relief duct discharging into relief duct discharging to
of the switchgear) the switchgear room is used the outside is used
[mm] [mm]
> 800 > 800 AFLR
> 600 1)
> 800 AFL
AFLR
> 800 > 500 AFR
> 600 1)
> 500 AF
1)
Reduzierung auf minimal 500 mm auf Anfrage
2)
According to IEC 62271-200: IAC - qualification AFLR
Fig. 11.5.1: Feeder Panel with block-type CT or sensor, Fig. 11.5.2: Feeder Panel with block-type CT or sensor,
panel width 600 mm panel width 800 mm
300 400
150 150 210 210
Outlines of the
panel
1760
Primary cables
350
350
185
185
558
Fig. 11.5.3: Double feeder panel, panel width 2 x 400 mm Fig. 11.5.4: Feeder panel with CT or sensor, Panel width 800 mm
35 730 400
70 130 130 140 130130 210
210
190
530
625
1320 ± 12
730
85 630
400 400
85 630 800
800
400 300
210 210 190 190
Cable axes as per
number and type of
plug connectors
530
350
155
1760
1760
625
730
1145
875
165 190
85 630 75 450
600
800
Fig. 11.5.6: Opening for control cables, panel width 600 mm Fig. 11.5.7: Opening for control cables, panel width 800 mm
190
190
165
165
85 430 85 630
600 800
Fig. 11.5.8: Opening for control cables, panel width 600 mm, depth of Fig. 11.5.9: Opening for control cables, panel width 800 mm, depth of
low voltage compartment: 500 mm low voltage compartment: 500 mm
190
190
265
265
85 430 85 630
600
800
1)
Within in switchgear block
The optional foundation frames consist of aluminium sections. When installing the foundation frame at site, observe the form and
They are supplied pre-assembled for one panel each. Founda- position tolerances stated in the order documents.
tion frames of 600 mm or 800 mm in width are used, depending
on the panel width. 800 mm wide frames are available for double When the 500 mm deep low voltage compartment (optional) is
panels of 400 mm width. used, the panel depth is increased by 100 mm at the front (see
figs. 11.6.1 and 11.6.2).
The foundation frames are fastened to the concrete floor and em-
bedded in the floor topping.
Fig. 11.6.1: Foundation frame, panel with a LV compartment depth of Fig. 10.6.2: Foundation frame, panel with a LV compartment depth of
400 mm (standard), panel width 800 mm 500 mm (option), panel width 800 mm
Outlines of the
panel
420
Additional section,
420
required when volt-
age transformers
are fitted in the
cable termination
compartment and
the floor plate is not
supported, e.g. by
1633
1633
1860
concrete.
625
625
1760
190 130
107
265
87
207
187
85 630
800 85 630
800
The floor plates of the panels have L13 x 14 slots for fastening the
panels to the frame sections. Provide M 8 threads or bore holes for
screws M 8 in the frame sections at the positions of the slots.
Fig. 11.7.1: Example of a false floor in the area of a five-panel ZX2 switch-
gear system as an aid to planning. Plan view. Dimensions in mm.
1633
1593
850
323
A
107
400 100 600
Detail A
14
13
re r
le
bo 8 o
ho
M
11.8.1 Design of earthing Limitation of the interference level within the switchgear system is
systems with regard supported by suitable measures as listed below.
to touch voltage and –– Separate laying of power, signal and control cables.
thermal stress –– Suitable screening and earthing of the equipment.
We recommend that the switchgear be earthed as shown in fig- earthing bar in the low voltage compartments are to be connected
ures 11.8.3.1 and 11.8.3.2. at multiple points to the ring located beneath the switchgear.
A ring consisting of 80 mm x 5 mm copper strip is to be located Details on the use of materials and the number of connections
beneath the switchgear and connected at several points with a can be found in figure 11.8.3.1 and 11.8.3.2. When planning the
maximum spacing of 5 m to the earthing system of the building. switchgear earthing, please observe the notes in sections 11.8.1
The foundation frame, the main earthing bar in the panels and the and 11.8.2.
Fig. 11.8.3.1: Earthing recommendation, shown schematically as a sectional elevation of the lower part of a panel including the concrete floor
3
5
Cable compartment
11
10
8 4
A A
1 1
2 2
Fig. 11.8.3.2: Earthing recommendation, plan view (section A-A of figure 11.8.3.1)
11
Section A-A
6
3
9 10
2
2
5 4
7
8
Non-standard operating conditions may require special action. A Site altitudes > 1000 m above sea level
number of non-standard requirements and the measures which
may be necessary are listed below. Over and above this, our de- The panels are suitable for site altitudes > 1000 m above
sign team will be pleased to make a technical proposal to meet sea level with the following exceptions.
your specific requirements.
–– All panels with test voltages > 70/170kV
Rated frequency 60 Hz –– Double panels with test voltages > 28/75kV
–– Outer cone panels with voltage transformer isolating
In principle, at an operating frequency of 60 Hz, a reduction factor device and test voltages > 50/125kV
of 0.97 is to be applied to the permissible current to determine a –– C-panels with a load current > 800 A
thermal equivalent to a 50 Hz load current. –– C-panels with an ambient temperature > 25° C
In individual cases, an evaluation of the type test can indicate that
no reduction is necessary. –– At site altitudes > 1000 m, a reduction of the permis-
sible operating current and/or the ambient tempera-
Seismic withstand capability ture may be necessary. The correction factors for the
permissible operating current can be found in table
The panels are tested to IEEE Std. 693 Draft 6; 1997. 1) 12.1.
Table 12.1: Correction factors for permissible operating current at site altitudes > 1000 m
Ambient air temperature / ° C 20 30 35 40
Frequency / Hz 50 60 50 60 50 60 50 60
1)
Additional measures required (on request)
3500
3000
2500
2000
1500
Panels with Ir = 2500 A at 40 °C
Panels with Ir = 2000 A at 40 °C
1000 Panels with Ir = 1250 A at 40 °C
Panels with Ir = 800 A at 40 °C
500
-5 0 5 10 15 20 25 30 35 40 45 50 55