TECHNICAL SPECIFICATION
Number of pages: 32
INDEX
The Plant is dimensioned on the basis of the data stated below GA, drawing no: 2141-101-100
Rev -: - and specification Rev: 1, received from Keppel Singmarine
AIR CHANGES
Wheelhouse 15 (AC-1/AC-2) - -
Sky Lobby 10 (AC-1/AC-2) - -
Cabins 8-14 - -
Sanitary Spaces - - 15
Mess/Day Room 10 - 10
Smokers Day Room 10 - 15
Galley - 30 40
Dry Provision - - 6
Laundry 8 - 12
Hospital 10 - 12
Wash-/Change Room 8 - -
Instrument Rooms 500 m3/h - 500 m3/h
Online/Survey Control Room 10 - -
Engine Control Eoom 15 - -
Winter – 20 °C + 20 °C - 30 % RH
Summer + 45 °C - 70 % RH + 24 °C - 50 % RH
Unit data:
Air flow : 21.000 m3/h
External pressure : 1800 Pa
Voltage : 3 x 440 V 60 Hz
Power : 21.3 kW
Current : 36.3 A
CONTROL SYSTEM
1 Frequency converter
1 Pressure transmitter
1 Pressure guard
2 3-way shunt valve
2 Valve actuator for shunt valve
1 Anti freeze thermostat
2 Taco setter valve for adjusting of max water flow to the heating and cooling coils
1 Temperature sensor and regulator
2 Thermometer
Unit data:
Capacity : 57 kg/h
Voltage : 3 x 440 V 60 Hz
Power : 43.5 kW
Current : 57.1 A
Unit data:
Air flow : 7.950 m3/h
External pressure : 1200 Pa
Voltage : 3 x 440 V 60 Hz
Power : 6.4 kW
Current : 11.23 A
CONTROL SYSTEM
1 Frequency converter
2 3-way shunt valve
2 Valve actuator for shunt valve
2 Taco setter valve for adjusting of max water flow to the heating and cooling coils
1 Temperature sensor and regulator
2 Thermometer
1 Control panel with direct start for fan with overload relay, but without main fuses.
Including, pilot voltage, transformers, switches, signal lamps pilot fuses and
supply air temp. regulator.
Starter: AC-1, H-1, E-1, E-3, E-5, E-6, E-7, E-8, E-9, E-10, E-11, E-12, E-13, S-20, E-21,
E-22 & E-23
1 Control panel with direct start for fan with overload relay, but without main fuses.
Including, pilot voltage, transformers, switches, signal lamps pilot fuses and
supply air temp. regulator.
ACU1-30/40/50 – El heating
Single pipe cabin units for mounting above ceiling panel with individual control of air flow
and electric heating coil 500/1000/1500 W.
ACU1-30/40/50
Single pipe cabin units for mounting above ceiling panel with individual control of air flow.
Square perforated diffuser with regulation knob outside for individual regulation of air flow.
Necessary amount of pre-insulated and un-insulated spiro ducts, fittings and flexible hoses.
Necessary amount of regulation dampers
Necessary amount of sound traps
Necessary amount of grilles for over-pressure and return air
Necessary amount of exhaust valves
Smoke dampers according to rules
NOTE!
Below two items will be included but delivered by Mischling Engineering PTE LTD
Fan data:
Air flow : 2.750 m3/h
Pressure : 2.800 Pa
Voltage : 3 x 440 V 60 Hz
Power : 6,5 / 1,6 kW
Current : 11.9 / 3,0 A
Fan data:
Air flow : 45 m3/h
Pressure : 310 Pa
Voltage : 1 x 230 V60 Hz
Power : 0.096 kW
Current : 0.42 A
Fan data:
Air flow : 1.190 m3/h
Pressure : 350 Pa
Voltage : 1 x 230 V 60 Hz
Power : 0.829 kW
Current : 3.62 A
Fan data:
Air flow : 300 m3/h
Pressure : 250 Pa
Voltage : 1 x 230 V 60 Hz
Power : 0.153 kW
Current : 0.67 A
Fan data:
Air flow : 300 m3/h
Pressure : 340 Pa
Voltage : 1 x 230 V60 Hz
Power : 0.234 kW
Current : 1.01 A
Fan data:
Air flow : 2.750 m3/h
Pressure : 1.400 Pa
Voltage : 3 x 440 V 60 Hz
Power : 2.3 / 0.55 kW
Current : 4.9 / 1.1 A
Fan data:
Air flow : 685 m3/h
Pressure : 350 Pa
Voltage : 1 x 230 V 60 Hz
Power : 0.829 kW
Current : 3.62 A
Fan data:
Air flow : 550 m3/h
Pressure : 300 Pa
Voltage : 1 x 230 V 60 Hz
Power : 0.234 kW
Current : 1.01 A
Fan data:
Air flow : 270 m3/h
Pressure : 250 Pa
Voltage : 1 x 230 V 60 Hz
Power : 0.153 kW
Current : 0.67 A
Fan data:
Air flow : 485 m3/h
Pressure : 325 Pa
Voltage : 1 x 230 V 60 Hz
Power : 0.234 kW
Current : 1.01 A
Fan data:
Air flow : 550 m3/h
Pressure : 275 Pa
Voltage : 1 x 230 V 60 Hz
Power : 0.234 kW
Current : 1.01 A
Fan data:
Air flow : 155 m3/h
Pressure : 300 Pa
Voltage : 1 x 230 V 60 Hz
Power : 0.153 kW
Current : 0.67 A
Fan data:
Air flow : 300 m3/h
Pressure : 250 Pa
Voltage : 1 x 230 V 60 Hz
Power : 0.153 kW
Current : 0.67 A
Unit data:
Type : QZMF-74-b-2-1
Type of refrigerant : Chilled water 5/11 °C
Cooling capacity : approx. 9 kW
Air amount : 1.400 m3/h
Voltage : 1 x 230 V - 60 Hz
Fan power : (135/170/190) W - 3-steps
Starter : Yes – Internal
Unit data:
Type : QZMF-74-b-2-1
Type of refrigerant : Chilled water 5/11 °C
Cooling capacity : approx. 9 kW
Air amount : 1.400 m3/h
Voltage : 1 x 230 V - 60 Hz
Fan power : (135/170/190) W - 3-steps
Starter : Yes – Internal
Unit data:
Type : QZMF-74-b-2-1
Type of refrigerant : Chilled water 5/11 °C
Cooling capacity : approx. 9 kW
Air amount : 1.400 m3/h
Voltage : 1 x 230 V - 60 Hz
Fan power : (135/170/190) W - 3-steps
Starter : Yes – Internal
1. Chill Water Units (Tag No. CH-1 & CH-2 ) Two (2) Sets
Two (2) unit of ‘JL/Dunham Bush’ packaged freshwater cooled chiller model CWCDSX470,
each having 60% capacity of total cooling capacity. The chiller shall come complete with part
winding starter and PLC controller including electrical starters for chill water pumps etc. The
Chiller Unit shall one refrigerant circuit and condenser of Copper tubes.
Data/Each.
Capacity : 470 kW or Abt. 135Rtons.
Compressors : 1 X Semi Hermetic Bitzer Screw Compressor.
EWT : 11°C
LWT : 5°C.
BHP : ~196 kW
Chill Water Flow : ~70 m3/Hr
Refrigerant : R407C
Condenser Cooling water : 150 m3/Hr
Freshwater Temp. : 37°C.
The packaged chiller shall be delivered fully assembled on a common skid.
6. Chill Water Pumps (Tag No. CWP-1 & CWP-2) Two (2) Sets.
Two (2) units Allen Gwynnes or equivalent (Malaysia) each of 60% capacity chill water pump
complete with base skid and suction and discharge pressure gauge complete with stop valves.
Data.
Capacity : 75m3/hr
Head : 30m
Power : 12.7 kW
Voltage : 440V/3Ph/60Hz.
1.2 1 Unit of freshwater cooled condensers inclusive of storage space acting as receiver, safety
valve and purge valves.
Data
Capacity : 15 kW.
Water Flow Rate. : 6 m3/Hr
Type : Freshwater cooled Shell And Tube Type.
1.6 1 set base foundation and piping material and insulation for the inter-piping connections.
The condensing units shall be delivered filly assembled on the sturdy base skid.
2. Provision Plant Electrical Control Panel (Tag No. : Prov-EC) One (1) Set
One (1) unit of Electric Control Panel which consist of all electric components and starters for
start//stop of compressors, automatic and manual operations, necessary interlock with water flow
switch, overloading of compressor, high pressure safety cut out and defrosting timer for the
automatic defrosting of the Freezer coils. The start/stop push buttons, indicating lamps on
solenoid valves activation, fault lamps and Auto/Manual selector switch shall be displayed on the
3. Fan Coil Units (Tag No. FCU-1 & FCU-2) Two (2) Sets
Two (2) in nos. of ‘Roller’ or equivalent induced draft Fan Coil Cooler Units, R404A direct
expansion type for Freezer & Chiller Rooms respectively. The Freezer Rooms shall come
complete with Electric Defrosting Heaters For Coil, Pan and Drain Pipes.
Fan data:
Air flow : 1.405 m3/h
Pressure : 310 Pa
Voltage : 3 x 440 V 60 Hz
Power : 0,8 kW
Current : 1,7 A
1 Frequency converter
1 Fire Damper
Fan data:
Air flow : 1.875 m3/h
Pressure : 400 Pa.
Voltage : 3 x 440 V 60 Hz
Power : 1.3 kW
Current : 2.8 A
1 Frequency converter
1 Grease filter
1 Fire Damper
Fan data:
Air flow : 235 m3/h
Pressure : 350 Pa
Voltage : 1 x 230 V60 Hz
Power : 0.153 kW
Current : 0.67 A
Fan data:
Air flow : 200 m3/h
Pressure : 360 Pa
Voltage : 1 x 230 V60 Hz
Power : 0.153 kW
Current : 0.67 A
Fan data:
Air flow : 250 m3/h
Pressure : 275 Pa
Voltage : 1 x 230 V 60 Hz
Power : 0.153 kW
Current : 0.67 A
Unit data:
Type : QZMF-74-b-2-1
Type of refrigerant : Chilled water 5/11 °C
Cooling capacity : approx. 9 kW
Air amount : 1.400 m3/h
Voltage : 1 x 230 V - 60 Hz
Fan power : (135/170/190) W - 3-steps
Starter : Yes – Internal
Fan data:
Air flow : 250 m3/h
Pressure : 275 Pa
Voltage : 1 x 230 V 60 Hz
Power : 0.153 kW
Current : 0.67 A
Unit data:
1 Fan coil for 100 % re-circulation of air
The unit is complete with filter, cooling coil and fan built together in a casing.
Unit data:
Make : AERON
Type of refrigerant : Chilled water 5/11 °C
Cooling capacity : 30 kW
Air amount : approx. 5.500 m3/h
Pressure : approx.300 Pa
Voltage : 3 x 440 V - 60 Hz
Fan power : 1.8 kW
Current : 3.5 A
Plenum chamber : No
Starter : Yes
Weight : kg
Unit data:
1 Fan coil for 100 % re-circulation of air
The unit is complete with filter, cooling coil and fan built together in a casing.
Unit data:
Make : AERON
Type of refrigerant : Chilled water 5/11 °C
Cooling capacity : 30 kW
Air amount : approx. 5.500 m3/h
Pressure : approx.300 Pa
Voltage : 3 x 440 V - 60 Hz
Fan power : 1.8 kW
Current : 3.5 A
Plenum chamber : No
Starter : Yes
Weight : kg
Fan data:
Air flow : 85.000 m3/h
Pressure : 800 Pa
Voltage : 3 x 690 V 60 Hz
Power : 34.5 kW
Current : 36.0 A
Fan data:
Air flow : 85.000 m3/h
Pressure : 800 Pa
Voltage : 3 x 440 V 60 Hz
Power : 34.5 kW
Current : 57.5 A
Fan data:
Air flow : 800 m3/h
Pressure : 800 Pa
Voltage : 3 x 440 V 60 Hz
Power : 0.7 / 0.17 kW
Current : 1.2 / 0,86 A
Unit data:
Type : QZMF-74-b-2-1
Type of refrigerant : Chilled water 5/11 °C
Cooling capacity : approx. 9 kW
Air amount : 1.400 m3/h
Voltage : 1 x 230 V - 60 Hz
Fan power : (135/170/190) W - 3-steps
Starter : Yes – Internal
Fan data:
Air flow : 200 m3/h
Pressure : 300 Pa.
Voltage : 1 x 230 V 60 Hz
Power : 0.153 kW
Current : 0.67 A
Coil data:
Capacity 25 kW
Fan data:
Air flow : 3.000 m3/h
Pressure : 175 Pa
Voltage : 3 x 440 V60 Hz
Power : 0.43 kW
Current : 1.07 A
One unit for continuous operation and one for 100 % back-up
Coil data:
Capacity 25 kW
Fan data:
Air flow : 3.000 m3/h
Pressure : 175 Pa
Voltage : 3 x 440 V60 Hz
Power : 0.43 kW
Current : 1.07 A
One unit for continuous operation and one for 100 % back-up
Coil data:
Capacity 25 kW
Fan data:
Air flow : 3.000 m3/h
Pressure : 175 Pa
Voltage : 3 x 440 V60 Hz
Power : 0.43 kW
Current : 1.07 A
One unit for continious operation and one for 100 % back-up
Fan data:
Air flow : 500 m3/h
Pressure : 300 Pa.
Voltage : 1 x 230 V 60 Hz
Power : 0.234 kW
Current : 1.01 A
Fan data:
Air flow : 500 m3/h
Pressure : 300 Pa.
Voltage : 1 x 230 V 60 Hz
Power : 0.234 kW
Current : 1.01 A
Fan data:
Air flow : 220 m3/h
Pressure : 350 Pa
Voltage : 1 x 230 V60 Hz
Power : 0.153 kW
Current : 0.67 A
Unit data:
Type : QZMF 54-2-2-1
Type of refrigerant : Chilled water 5/11 °C
Cooling capacity : approx. 5 kW
Air amount : 1.000 m3/h
Voltage : 1 x 230 V - 60 Hz
Fan power : (135/170/190) W - 3-steps
Starter : Yes – Internal
Fan data:
Air flow : 600 m3/h
Pressure : 200 Pa
Voltage : 1 x 230 V 60 Hz
Power : 0.234 kW
Current : 1.01 A
Fan data:
Air flow : 300 m3/h
Pressure : 150 Pa.
Voltage : 1 x 230 V60 Hz
Power : 0.147 kW
Current : 0.65 A
Fan data:
Air flow : 12.000 m3/h
Pressure : 400 Pa
Voltage : 3 x 690 V 60 Hz
Power : 4,6 kW
Current : 5,5 A
Fan data:
Air flow : 500 m3/h
Pressure : 300 Pa
Voltage : 1 x 230 V 60 Hz
Power : 0.234 kW
Current : 1.01 A
2 RESPONSIBILITY
AERON to be responsible for ventilation and air-condition inside accommodation
The drawings and scope of supply to be in accordance with the technical specification, the
classification society rules, and the national rules etc.
AERON is not responsible for design and calculating of air amount etc. outside
accommodation, but deliver fans according to technical specification.
1 person for start up and trial run of ventilation and air-conditioning systems
1 person for start up and trial run of refrigerating machinery
Based on one trip with necessary assistance for 5 working days with 10 hours day time
work each day. Waiting time caused by the yard will be charged SGD 1450