Ventilation and Air-Treatment Systems for Ships

TECHNICAL SPECIFICATION

Ventilation and Air-Condition System

Shipyard: Yard type:


KEPPEL SINGMARINE MT 6012 PSV
Hull no.: Project No.: File name: Quotation no.: Orig. date: Sign:
341 08105 TS-09 Sk07.100 20.07.2007 BTN
Sales Manager: Project Manager:
Bjorn Tore Nyland Eivind Øvstedal
Revisions: Rev. date: Sign:
0 ISSUED FOR BID 20.07.2007 BTN
1 Revised after comments from Shipyard July 26 06.08.2007 BTN
2 Updated based on similar design 22.11.2007 BTN
3 Revised after meeting at Shipyard 06.12.2007 09.12.2007 BTN
4 Revised after meeting at Shipyard 10.12.2007 17.12.2007 BTN
5 Revised after comments from Shipyard 18.12.2007 18.12.2007 BTN
6 Various, C-1/C-2, C-3/C-4 29.03.2008 EØ
7 Added starter cabinet 06.05.2008 BTN
8 FC-47, S-57 10.10.2008 EØ
9 After commissioning; E-1 20.11.2009 EØ

Number of pages: 32
INDEX

BASIC OF CALCULATION ............................................................................................................................... 4


571 VENTILATION PLANT ACCOMMODATION ........................................................................................ 5
AC-1, AIR HANDLING UNIT ACCOMMODATION, WHEELHOUSE, SKY LOBBY .................................. 5
CONTROL SYSTEM .......................................................................................................................................... 5
H-1, HUMIDIFIER .............................................................................................................................................. 6
AC-2, AIR HANDLING UNIT WHEELHOUSE ................................................................................................ 6
CONTROL SYSTEM .......................................................................................................................................... 6
AH-1, DEFROSTER SYSTEM WHEELHOUSE WINDOWS ........................................................................... 7
CP-1, CONTROL PANEL ................................................................................................................................... 7
CP-2, CONTROL PANEL ................................................................................................................................... 7
CABIN UNITS..................................................................................................................................................... 8
SPIRO DUCTS, DAMPERS, SOUND TRAPS, GRILLES, EXHAUST VALVE............................................... 8
E-1, EXHAUST FAN SANITARY SPACES ...................................................................................................... 9
E-2, EXHAUST FAN WC WHEELHOUSE........................................................................................................ 9
E-3, EXHAUST FAN LOUNGE & CONF ROOM, CAPTAIN DECK ............................................................... 9
E-4, EXHAUST FAN AC-ROOM / STORE (TOP OF WHEELHOUSE) ........................................................... 9
E-5, EXHAUST FAN LAUNDRY, FORECASTLE DECK .............................................................................. 10
E-6, EXHAUST FAN DAY ROOM, MESS ROOM .......................................................................................... 10
E-7, EXHAUST FAN SMOKERS DAY ROOM ............................................................................................... 10
E-8, EXHAUST FAN HOSPITAL ..................................................................................................................... 10
E-9, EXHAUST FAN GYMNASIUM ............................................................................................................... 11
E-10, EXHAUST FAN WARDROBE ............................................................................................................... 11
E-11, EXHAUST FAN LAUNDRY, MAIN DECK........................................................................................... 11
E-12, EXHAUST FAN COFFEE SHOP, MAIN DECK .................................................................................... 11
E-13, EXHAUST FAN AC-ROOM, SHELTER DECK .................................................................................... 12
FC-14, FAN COIL ONLINE / ROV CONTROL ROOM ................................................................................... 12
FC-15, FAN COIL INSTRUMENT ROOM, CAPTAINS DECK ..................................................................... 12
FC-16, FAN COIL INSTRUMENT ROOM, FORECASTLE DECK ............................................................... 13
C-1/C-2, CHILLED WATER COOLING MACHINERY ................................................................................. 14
C-3/C-4, PROVISION COOLING PLANTS ..................................................................................................... 15
572 VENTILATION IN GALLEY .................................................................................................................... 17
S-20, SUPPLY FAN GALLEY .......................................................................................................................... 17
E-21, EXHAUST FAN GALLEY ...................................................................................................................... 17
E-22, EXHAUST FAN DRY PROVISION ROOM ........................................................................................... 18
E-23, EXHAUST FAN STORE / DRY PROVISION ROOM FWD .................................................................. 18
573 VENTILATION IN ENGINE CONTROL-/SWITCHBOARD ROOM ................................................. 19
S-30, SUPPLY FAN ENGINE CONTROL ROOM – BACK-UP ...................................................................... 19
FC-30, FAN COIL ENGINE CONTROL ROOM.............................................................................................. 19
S-31, SUPPLY FAN SWITCHBOARD ROOM ................................................................................................ 19
FC-31, FAN COIL COOLING UNIT SWITCHBOARD ROOM, PS ................................................................ 20
FC-32, FAN COIL COOLING UNIT SWITCHBOARD ROOM, SB ............................................................... 20
574 VENTILATION IN ENGINE ROOM ETC. ............................................................................................. 21
S-40, SUPPLY FAN ENGINE ROOM .............................................................................................................. 21
S-41, SUPPLY FAN ENGINE ROOM .............................................................................................................. 21
CLOSING DAMPER FOR SUPPLY FANS ENGINE ROOM .......................................................................... 21
E-42, EXHAUST FAN ENGINE ROOM WORKSHOP, TWEEN DECK ........................................................ 22
FC-40, FAN COIL ENGINE ROOM WORKSHOP, TWEEN DECK ............................................................... 22
E-43, EXHAUST FAN ENGINE STORE, TWEEN DECK............................................................................... 22
E-44, EXHAUST FAN UPPER CEMENT ROOM, TWEEN DECK ................................................................ 23
E-45, EXHAUST FAN LOWER CEMENT ROOM, TWEEN DECK ............................................................... 23
S-46, SUPPLY FAN BOW THRUSTER ROOM, TWEEN DECK ................................................................... 23

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 2
S-47, SUPPLY FAN STERN THRUSTER ROOM, TWEEN DECK ................................................................ 23
FC-41/42, FAN COIL BOW THRUSTER ROOM, TWEEN DECK ................................................................. 24
FC-43/44, FAN COIL STERN THRUSTER ROOM PS, TWEEN DECK......................................................... 24
FC-45/46, FAN COIL STERN THRUSTER ROOM SB, TWEEN DECK ........................................................ 25
S-48, SUPPLY FAN STORE ROOM PS, MAIN DECK ................................................................................... 25
S-49, SUPPLY FAN STORE ROOM SB, MAIN DECK ................................................................................... 25
E-50, EXHAUST FAN WORKSHOP, MAIN DECK ........................................................................................ 26
FC-47, FAN COIL EL- WORKSHOP, MAIN DECK........................................................................................ 26
E-51, EXHAUST FAN ROV TRANSFORMER ROOM, MAIN DECK ........................................................... 26
S-52, SUPPLY FAN INCINERATOR ROOM, MAIN DECK .......................................................................... 27
E-53, EXHAUST FAN PAINT STORE AFT PS, MAIN DECK ....................................................................... 27
E-54, EXHAUST FAN N2 GENERATOR ROOM PS, MAIN DECK ............................................................... 27
E-55, EXHAUST FAN N2 STORE ROOM SB, MAIN DECK .......................................................................... 27
E-56, EXHAUST FAN GARBAGE ROOM ...................................................................................................... 28
S-57, SUPPLY FAN EMERGENCY GENERATOR ROOM, TOP OF WH ..................................................... 28
S-58, SUPPLY FAN EMERGENCY GENERATOR ROOM, TOP OF WH ..................................................... 28
S-59, SUPPLY FAN UPPER & LOWER PUMP ROOM, TANK TOP ............................................................. 29
VENTILATION LOUVERS AND HATCHES ................................................................................................ 29
GENERAL INFORMATION ............................................................................................................................ 30
THE FOLLOWING ARE INCLUDED IN OUR DELIVERY ........................................................................... 30
THE FOLLOWING ARE NOT INCLUDED IN OUR DELIVERY .................................................................. 32

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 3
BASIC OF CALCULATION

The Plant is dimensioned on the basis of the data stated below GA, drawing no: 2141-101-100
Rev -: - and specification Rev: 1, received from Keppel Singmarine

AIR CHANGES

We have calculated with following minimum air changes:

Area Central unit Supply fans Exhaust fans

Wheelhouse 15 (AC-1/AC-2) - -
Sky Lobby 10 (AC-1/AC-2) - -
Cabins 8-14 - -
Sanitary Spaces - - 15
Mess/Day Room 10 - 10
Smokers Day Room 10 - 15
Galley - 30 40
Dry Provision - - 6
Laundry 8 - 12
Hospital 10 - 12
Wash-/Change Room 8 - -
Instrument Rooms 500 m3/h - 500 m3/h
Online/Survey Control Room 10 - -
Engine Control Eoom 15 - -

Conditions Outside Inside

Winter – 20 °C + 20 °C - 30 % RH
Summer + 45 °C - 70 % RH + 24 °C - 50 % RH

Heating medium Hot water 80/60 °C


Cooling medium R-407c / Chilled Water 5/11 °C
Fresh water + 37 °C

El. power supply 3 x 690 V – 60 Hz


3 x 440 V – 60 Hz
3 x 230 V – 60 Hz
1 x 230 V – 60 Hz

Class DNV, CLEAN, DYNPOS AUTR, Comf-V(3)


Flag SINGAPORE
Other rules SOLAS

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 4
571 VENTILATION PLANT ACCOMMODATION

AC-1, AIR HANDLING UNIT ACCOMMODATION, WHEELHOUSE, SKY LOBBY

Air treatment unit. Single duct system for air distribution

The unit consists of:


1 Mixing section with damper for fresh and return air with connections for spiro ducts
1 Filter section with filter
1 Heating section with hot water coil 80/60 °C
Capacity: 210 kW at 40 % return air
1 Empty section for steam pipes
1 Cooling section with chilled water cooling coil 5/11 °C
Capacity: 580 kW
1 Fan section with centrifugal fan and 1-speed fan motor
Motor to be suitable for frequency converter
1 Distribution section with connections for spiro ducts
1 Skid

Unit data:
Air flow : 21.000 m3/h
External pressure : 1800 Pa
Voltage : 3 x 440 V 60 Hz
Power : 21.3 kW
Current : 36.3 A

AC-1 is designed for 40 % return air

CONTROL SYSTEM

1 Frequency converter
1 Pressure transmitter
1 Pressure guard
2 3-way shunt valve
2 Valve actuator for shunt valve
1 Anti freeze thermostat
2 Taco setter valve for adjusting of max water flow to the heating and cooling coils
1 Temperature sensor and regulator
2 Thermometer

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 5
H-1, HUMIDIFIER

1 Humidifier type Compact C58


1 Room hygrostat
2 Ø-40 mm steam inlet pipe for mounting in AC-1

Unit data:
Capacity : 57 kg/h
Voltage : 3 x 440 V 60 Hz
Power : 43.5 kW
Current : 57.1 A

AC-2, AIR HANDLING UNIT WHEELHOUSE

Air treatment unit. Single duct system for air distribution.

The unit consists of:


1 Mixing section with damper for fresh and return air
1 Filter section with filter
1 Heating section with hot water coil 80/60 °C
Capacity: 25 kW
1 Cooling section with chilled water cooling coil 5/11 °C
Capacity: 45 kW
1 Fan section with centrifugal fan and 1-speed fan motor
Motor to be suitable for frequency converter
1 Distribution section with connections for spiro ducts
1 Skid

Unit data:
Air flow : 7.950 m3/h
External pressure : 1200 Pa
Voltage : 3 x 440 V 60 Hz
Power : 6.4 kW
Current : 11.23 A

The unit is designed for 100 % return air

CONTROL SYSTEM

1 Frequency converter
2 3-way shunt valve
2 Valve actuator for shunt valve
2 Taco setter valve for adjusting of max water flow to the heating and cooling coils
1 Temperature sensor and regulator
2 Thermometer

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 6
AH-1, DEFROSTER SYSTEM WHEELHOUSE WINDOWS

Supply air from AC-2

1 Heating coil for hot water mounted on AC-2.


Capacity 15 kW (20°C to 45°C)
Air flow 1.800 m3/h

2 Regulation damper w/ actuator mounted on AC-2

1 3-way shunt valve w/ actuator


1 Taco setter valve for adjusting of max water flow

40 Defroster nozzles Ø-70

CP-1, CONTROL PANEL

1 Control panel with direct start for fan with overload relay, but without main fuses.
Including, pilot voltage, transformers, switches, signal lamps pilot fuses and
supply air temp. regulator.

Starter: AC-1, H-1, E-1, E-3, E-5, E-6, E-7, E-8, E-9, E-10, E-11, E-12, E-13, S-20, E-21,
E-22 & E-23

Remote panel: S-20, E-21

CP-2, CONTROL PANEL

1 Control panel with direct start for fan with overload relay, but without main fuses.
Including, pilot voltage, transformers, switches, signal lamps pilot fuses and
supply air temp. regulator.

Starter: AC-2/AH-1, E-2, E-4

Remote panel: AC-2/AH-1

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 7
CABIN UNITS

ACU1-30/40/50 – El heating
Single pipe cabin units for mounting above ceiling panel with individual control of air flow
and electric heating coil 500/1000/1500 W.

Power supply of heating elements: 1 x 230V 60Hz


Approx. 100 kW heating elements for the accommodation.
Total quantity and heat capacity of cabin units to be finalized after ventilation drawing has been
drawn

Room thermostats for regulating heating coil in cabin units.

ACU1-30/40/50
Single pipe cabin units for mounting above ceiling panel with individual control of air flow.

Square perforated diffuser with regulation knob outside for individual regulation of air flow.

SPIRO DUCTS, DAMPERS, SOUND TRAPS, GRILLES, EXHAUST VALVE

Necessary amount of pre-insulated and un-insulated spiro ducts, fittings and flexible hoses.
Necessary amount of regulation dampers
Necessary amount of sound traps
Necessary amount of grilles for over-pressure and return air
Necessary amount of exhaust valves
Smoke dampers according to rules

Necessary amount according to AERON drawings

NOTE!
Below two items will be included but delivered by Mischling Engineering PTE LTD

1. Supply/return/exhaust spiro ducts at following decks:


• Main deck
• Shelter deck
• Boat deck
• Forecastle deck
• Captain deck
• Bridge deck
2. Round regulation dampers, sound traps, grilles and exhaust valves

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 8
E-1, EXHAUST FAN SANITARY SPACES

1 Centrifugal fan type MSV 250 B1BG w/ IRIS damper


1 2-speed el motor, direct drive
1 Suction chamber w/ connections for spiro pipes
Flexible connections and vibration dampers

Fan data:
Air flow : 2.750 m3/h
Pressure : 2.800 Pa
Voltage : 3 x 440 V 60 Hz
Power : 6,5 / 1,6 kW
Current : 11.9 / 3,0 A

E-2, EXHAUST FAN WC WHEELHOUSE

1 Duct fan type K 125 XL


1 1-speed el motor, direct drive

Fan data:
Air flow : 45 m3/h
Pressure : 310 Pa
Voltage : 1 x 230 V60 Hz
Power : 0.096 kW
Current : 0.42 A

E-3, EXHAUST FAN LOUNGE & CONF ROOM, CAPTAIN DECK

1 Duct fan type KE 50-30-4


1 1-speed el motor, direct drive

Fan data:
Air flow : 1.190 m3/h
Pressure : 350 Pa
Voltage : 1 x 230 V 60 Hz
Power : 0.829 kW
Current : 3.62 A

E-4, EXHAUST FAN AC-ROOM / STORE (TOP OF WHEELHOUSE)

1 Duct fan type K 160 XL


1 1-speed el motor, direct drive

Fan data:
Air flow : 300 m3/h
Pressure : 250 Pa
Voltage : 1 x 230 V 60 Hz
Power : 0.153 kW
Current : 0.67 A

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 9
E-5, EXHAUST FAN LAUNDRY, FORECASTLE DECK

1 Duct fan type K 200 L


1 1-speed el motor, direct drive

Fan data:
Air flow : 300 m3/h
Pressure : 340 Pa
Voltage : 1 x 230 V60 Hz
Power : 0.234 kW
Current : 1.01 A

E-6, EXHAUST FAN DAY ROOM, MESS ROOM

1 Centrifugal fan type MSV 200 B1BG w/ IRIS damper


1 2-speed el motor, direct drive
1 Suction chamber w/ connections for spiro pipes
Flexible connections and vibration dampers

Fan data:
Air flow : 2.750 m3/h
Pressure : 1.400 Pa
Voltage : 3 x 440 V 60 Hz
Power : 2.3 / 0.55 kW
Current : 4.9 / 1.1 A

E-7, EXHAUST FAN SMOKERS DAY ROOM

1 Duct fan type KE 50-30-4


1 1-speed el motor, direct drive

Fan data:
Air flow : 685 m3/h
Pressure : 350 Pa
Voltage : 1 x 230 V 60 Hz
Power : 0.829 kW
Current : 3.62 A

E-8, EXHAUST FAN HOSPITAL

1 Duct fan type K 200 L


1 1-speed el motor, direct drive

Fan data:
Air flow : 550 m3/h
Pressure : 300 Pa
Voltage : 1 x 230 V 60 Hz
Power : 0.234 kW
Current : 1.01 A

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 10
E-9, EXHAUST FAN GYMNASIUM

1 Duct fan type K 160 XL


1 1-speed el motor, direct drive

Fan data:
Air flow : 270 m3/h
Pressure : 250 Pa
Voltage : 1 x 230 V 60 Hz
Power : 0.153 kW
Current : 0.67 A

E-10, EXHAUST FAN WARDROBE

1 Duct fan type K 200 L


1 1-speed el motor, direct drive

Fan data:
Air flow : 485 m3/h
Pressure : 325 Pa
Voltage : 1 x 230 V 60 Hz
Power : 0.234 kW
Current : 1.01 A

E-11, EXHAUST FAN LAUNDRY, MAIN DECK

1 Duct fan type K 200 L


1 1-speed el motor, direct drive

Fan data:
Air flow : 550 m3/h
Pressure : 275 Pa
Voltage : 1 x 230 V 60 Hz
Power : 0.234 kW
Current : 1.01 A

E-12, EXHAUST FAN COFFEE SHOP, MAIN DECK

1 Duct fan type K 160 XL


1 1-speed el motor, direct drive

Fan data:
Air flow : 155 m3/h
Pressure : 300 Pa
Voltage : 1 x 230 V 60 Hz
Power : 0.153 kW
Current : 0.67 A

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 11
E-13, EXHAUST FAN AC-ROOM, SHELTER DECK

1 Duct fan type K 160 XL


1 1-speed el motor, direct drive

Fan data:
Air flow : 300 m3/h
Pressure : 250 Pa
Voltage : 1 x 230 V 60 Hz
Power : 0.153 kW
Current : 0.67 A

FC-14, FAN COIL ONLINE / ROV CONTROL ROOM

1 Fan coil for 100 % re-circulation of air.


The unit is complete with cooling coil and fan built together in a casing.

Unit data:
Type : QZMF-74-b-2-1
Type of refrigerant : Chilled water 5/11 °C
Cooling capacity : approx. 9 kW
Air amount : 1.400 m3/h
Voltage : 1 x 230 V - 60 Hz
Fan power : (135/170/190) W - 3-steps
Starter : Yes – Internal

1 Taco setter valve for adjusting of max water flow to coil

FC-15, FAN COIL INSTRUMENT ROOM, CAPTAINS DECK

1 Fan coil for 100 % re-circulation of air.


The unit is complete with cooling coil and fan built together in a casing.

Unit data:
Type : QZMF-74-b-2-1
Type of refrigerant : Chilled water 5/11 °C
Cooling capacity : approx. 9 kW
Air amount : 1.400 m3/h
Voltage : 1 x 230 V - 60 Hz
Fan power : (135/170/190) W - 3-steps
Starter : Yes – Internal

1 Taco setter valve for adjusting of max water flow to coil

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 12
FC-16, FAN COIL INSTRUMENT ROOM, FORECASTLE DECK

1 Fan coil for 100 % re-circulation of air.


The unit is complete with cooling coil and fan built together in a casing.

Unit data:
Type : QZMF-74-b-2-1
Type of refrigerant : Chilled water 5/11 °C
Cooling capacity : approx. 9 kW
Air amount : 1.400 m3/h
Voltage : 1 x 230 V - 60 Hz
Fan power : (135/170/190) W - 3-steps
Starter : Yes – Internal

1 Taco setter valve for adjusting of max water flow to coil

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 13
C-1/C-2, CHILLED WATER COOLING MACHINERY

1. Chill Water Units (Tag No. CH-1 & CH-2 ) Two (2) Sets
Two (2) unit of ‘JL/Dunham Bush’ packaged freshwater cooled chiller model CWCDSX470,
each having 60% capacity of total cooling capacity. The chiller shall come complete with part
winding starter and PLC controller including electrical starters for chill water pumps etc. The
Chiller Unit shall one refrigerant circuit and condenser of Copper tubes.
Data/Each.
Capacity : 470 kW or Abt. 135Rtons.
Compressors : 1 X Semi Hermetic Bitzer Screw Compressor.
EWT : 11°C
LWT : 5°C.
BHP : ~196 kW
Chill Water Flow : ~70 m3/Hr
Refrigerant : R407C
Condenser Cooling water : 150 m3/Hr
Freshwater Temp. : 37°C.
The packaged chiller shall be delivered fully assembled on a common skid.

2. Closed Loop Chill Water Expansion Tank. One (1) Set


One (1) set of closed loop chill water expansion tank for replenishment of chill water for the
system.

3. Start Up & Commissioning One (1) Lot


One (1) Engineer for the starting up and commissioning of Air Conditioning Chiller Units and
Provision System. Test Protocol shall be furnished by AERON.

4. Refrigerant Recovery System One (1) Set


One (1) set of ‘Unitor’ refrigerant recovery system for the recovery of refrigerant from system
Complete with two (2) Recovery Cylinders and weighting scale etc.

5. Refrigerant Monitoring System One (1) Set


One (1) set of ‘Unitor’ refrigerant leak monitoring system (For Fixed Installation) for the
refrigerant leak monitoring with six (6) sensors and alarm panel (Buzzer & Visual ) including
potential free signals for remote indication

6. Chill Water Pumps (Tag No. CWP-1 & CWP-2) Two (2) Sets.
Two (2) units Allen Gwynnes or equivalent (Malaysia) each of 60% capacity chill water pump
complete with base skid and suction and discharge pressure gauge complete with stop valves.
Data.
Capacity : 75m3/hr
Head : 30m
Power : 12.7 kW
Voltage : 440V/3Ph/60Hz.

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 14
C-3/C-4, PROVISION COOLING PLANTS

Our Scope Of Work And Supply


1. Provision Plant Condensing Units (Tag No. Prov-CU-1/CU-2) Two (2) Sets
Two (2) units of ‘Bitzer’ or equivalent refrigeration condensing units factory assembled with 1X
100% capacity compressor and freshwater cooled condensers. One compressor shall be able to
maintain all rooms temperature and one compressor unit shall act as standby.

Each condensing unit comprises of :

1.1 1 Unit of ‘Bitzer’ Semi-Sealed Type reciprocating compressor.


Data
Model : Bitzer / 4TC-8.2Y
Cooling Capacity : 6kW
ET : -34°C
CT : 46 °C
Refrigerant : R404A
Motor : Built-In Type.
Power : 5.8 kW

1.2 1 Unit of freshwater cooled condensers inclusive of storage space acting as receiver, safety
valve and purge valves.
Data
Capacity : 15 kW.
Water Flow Rate. : 6 m3/Hr
Type : Freshwater cooled Shell And Tube Type.

1.3 1 set of gauge panel comprises of :


a. 1pc ‘Danfoss’ Oil pressure switch.
b. 1pc ‘Danfoss’ High pressure switches
c. 1pc ‘Danfoss’ Low pressure switch.
d. 3pcs of oil filled pressure gauges for suction, discharge and oil pressure respectively
complete with stop valves.

1.4 1 Pc Oil Separator.

1.5 1 set of filter drier complete with stop valves.

1.6 1 set base foundation and piping material and insulation for the inter-piping connections.
The condensing units shall be delivered filly assembled on the sturdy base skid.

2. Provision Plant Electrical Control Panel (Tag No. : Prov-EC) One (1) Set
One (1) unit of Electric Control Panel which consist of all electric components and starters for
start//stop of compressors, automatic and manual operations, necessary interlock with water flow
switch, overloading of compressor, high pressure safety cut out and defrosting timer for the
automatic defrosting of the Freezer coils. The start/stop push buttons, indicating lamps on
solenoid valves activation, fault lamps and Auto/Manual selector switch shall be displayed on the

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 15
external of the panel.

3. Fan Coil Units (Tag No. FCU-1 & FCU-2) Two (2) Sets
Two (2) in nos. of ‘Roller’ or equivalent induced draft Fan Coil Cooler Units, R404A direct
expansion type for Freezer & Chiller Rooms respectively. The Freezer Rooms shall come
complete with Electric Defrosting Heaters For Coil, Pan and Drain Pipes.

4. Suction Trap One (1) Set


One (1) unit of Suction Trap/Liquid Separator supply loose for site installation.

5. Digital Type Thermometer & Thermostat Panel One (1) Set.


The digital thermometer/thermostat Panel consist of 2pcs Digital Thermometer/Thermostat,
mounted onto a common panel.

6. Dial Thermometer Two (2) Sets


2Pcs Dial Thermometer supply loose for installation near to Cold Room.
The thermometer shall come complete with sensor of length 4.5m

7. Control Valves Panels Two (2) Set


Two (2) Sets of Control Valve Panel each consist of :
1 PC of liquid line stop valves and by-pass valves.
1 PC of ‘Danfoss’ Thermostatic Expansion Valves.
1 PC of ‘Danfoss’ Solenoid valves.
1 PC of ‘Danfoss’ Back Pressure Regulator. (For FCU-2 Only)

8. Man Trap In Alarm One (1) Set


One (1) unit of man trap in alarm complete with Buzzer and Visual Flash.
One (1) Activation Button for each room.

Aeron's delivery does not include:

Standard spare parts


Delivery of electric cables
Doors or accessories to provision doors
Foundations with necessary mounting, irons and bolts etc.
Drilling and cutting through bulkheads and decks
Water pumps w/starters
Water piping and manifolds for condenser
Drainage from evaporators
Fasteners for pipelines
Supply and fittings of pipes from safety valves
Protection of machinery of pipelines if necessary
Painting of any parts for the plant after despatch
Pressure air, nitrogen and water, light etc. that are necessary during
Installation and testing of the plant
Unloading and transportation of the goods from railway, truck or ship
Bringing onboard of materials
Any item not specially mentioned in the technical specification

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 16
572 VENTILATION IN GALLEY

S-20, SUPPLY FAN GALLEY

1 Duct fan type KT 50-30-4


1 1-speed el motor, direct drive

Fan data:
Air flow : 1.405 m3/h
Pressure : 310 Pa
Voltage : 3 x 440 V 60 Hz
Power : 0,8 kW
Current : 1,7 A

1 Frequency converter
1 Fire Damper

1 Cooling coil, TTC capacity: 30 kW (chilled water)


1 Taco setter valve for adjusting of max water flow to coil
1 3-way on/off valve w/ actuator
1 Thermostat

E-21, EXHAUST FAN GALLEY

1 Centrifugal fan type SKV 300 B(F)1OG


1 1-speed el motor, direct drive
Suitable for frequency converter
1 Damper type LSS-300. Manually operated

Fan data:
Air flow : 1.875 m3/h
Pressure : 400 Pa.
Voltage : 3 x 440 V 60 Hz
Power : 1.3 kW
Current : 2.8 A

1 Frequency converter
1 Grease filter
1 Fire Damper

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 17
E-22, EXHAUST FAN DRY PROVISION ROOM

1 Duct fan type K 160 XL


1 1-speed el motor, direct drive

Fan data:
Air flow : 235 m3/h
Pressure : 350 Pa
Voltage : 1 x 230 V60 Hz
Power : 0.153 kW
Current : 0.67 A

E-23, EXHAUST FAN STORE / DRY PROVISION ROOM FWD

1 Duct fan type K 160 XL


1 1-speed el motor, direct drive

Fan data:
Air flow : 200 m3/h
Pressure : 360 Pa
Voltage : 1 x 230 V60 Hz
Power : 0.153 kW
Current : 0.67 A

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 18
573 VENTILATION IN ENGINE CONTROL-/SWITCHBOARD ROOM

S-30, SUPPLY FAN ENGINE CONTROL ROOM – BACK-UP

1 Duct fan type K 160 XL


1 1-speed el motor, direct drive
1 Motor protection switch, MPS-1

Fan data:
Air flow : 250 m3/h
Pressure : 275 Pa
Voltage : 1 x 230 V 60 Hz
Power : 0.153 kW
Current : 0.67 A

FC-30, FAN COIL ENGINE CONTROL ROOM

1 Fan coil for 100 % re-circulation of air.


The unit is complete with cooling coil and fan built together in a casing.

Unit data:
Type : QZMF-74-b-2-1
Type of refrigerant : Chilled water 5/11 °C
Cooling capacity : approx. 9 kW
Air amount : 1.400 m3/h
Voltage : 1 x 230 V - 60 Hz
Fan power : (135/170/190) W - 3-steps
Starter : Yes – Internal

1 Taco setter valve for adjusting of max water flow to coil

S-31, SUPPLY FAN SWITCHBOARD ROOM

1 Duct fan type K 160 XL


1 1-speed el motor, direct drive
1 Motor protection switch, MPS-2

Fan data:
Air flow : 250 m3/h
Pressure : 275 Pa
Voltage : 1 x 230 V 60 Hz
Power : 0.153 kW
Current : 0.67 A

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 19
FC-31, FAN COIL COOLING UNIT SWITCHBOARD ROOM, PS

Unit data:
1 Fan coil for 100 % re-circulation of air
The unit is complete with filter, cooling coil and fan built together in a casing.

Unit data:
Make : AERON
Type of refrigerant : Chilled water 5/11 °C
Cooling capacity : 30 kW
Air amount : approx. 5.500 m3/h
Pressure : approx.300 Pa
Voltage : 3 x 440 V - 60 Hz
Fan power : 1.8 kW
Current : 3.5 A
Plenum chamber : No
Starter : Yes
Weight : kg

1 3-way on/off valve w/ actuator


1 Taco setter valve for adjusting of max water flow to coil
1 Thermostat

FC-32, FAN COIL COOLING UNIT SWITCHBOARD ROOM, SB

Unit data:
1 Fan coil for 100 % re-circulation of air
The unit is complete with filter, cooling coil and fan built together in a casing.

Unit data:
Make : AERON
Type of refrigerant : Chilled water 5/11 °C
Cooling capacity : 30 kW
Air amount : approx. 5.500 m3/h
Pressure : approx.300 Pa
Voltage : 3 x 440 V - 60 Hz
Fan power : 1.8 kW
Current : 3.5 A
Plenum chamber : No
Starter : Yes
Weight : kg

1 3-way on/off valve w/ actuator


1 Taco setter valve for adjusting of max water flow to coil
1 Thermostat

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 20
574 VENTILATION IN ENGINE ROOM ETC.

S-40, SUPPLY FAN ENGINE ROOM

1 Axial fan type 1120 A1K


1 1-speed el motor, direct drive. Suitable for frequency converter
To be reversible
1 Flexible connection set
1 Counter flange

Fan data:
Air flow : 85.000 m3/h
Pressure : 800 Pa
Voltage : 3 x 690 V 60 Hz
Power : 34.5 kW
Current : 36.0 A

1 Frequency converter (MASTER), Remote panel for ECR


1 Pressure transmitter
1 Thermostat
1 Sound trap R-1120 mm, L=2000 mm with cone and grating on top

S-41, SUPPLY FAN ENGINE ROOM

1 Axial fan type 1120 A1K


1 1-speed el motor, direct drive. Suitable for frequency converter
1 Flexible connection set
1 Counter flange

Fan data:
Air flow : 85.000 m3/h
Pressure : 800 Pa
Voltage : 3 x 440 V 60 Hz
Power : 34.5 kW
Current : 57.5 A

1 Frequency converter. (SLAVE), Remote panel for ECR


1 Sound trap R-1120 mm, L=2000 mm with cone and grating on top

CLOSING DAMPER FOR SUPPLY FANS ENGINE ROOM

2 Damper type SS-Vent – Ø-1120 w/ actuator


Dimension : 1370 x 1370 x 200 mm
Voltage : 1 x 230 V 60 Hz
Power : 25 W

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 21
E-42, EXHAUST FAN ENGINE ROOM WORKSHOP, TWEEN DECK

1 Centrifugal fan type MSV 125 B1BG


1 2-speeds el motor, direct drive
1 Set flexible connections and vibration dampers
1 Starter cabinet, CP-3

Fan data:
Air flow : 800 m3/h
Pressure : 800 Pa
Voltage : 3 x 440 V 60 Hz
Power : 0.7 / 0.17 kW
Current : 1.2 / 0,86 A

FC-40, FAN COIL ENGINE ROOM WORKSHOP, TWEEN DECK

1 Fan coil for 100 % re-circulation of air.


The unit is complete with cooling coil and fan built together in a casing.

Unit data:
Type : QZMF-74-b-2-1
Type of refrigerant : Chilled water 5/11 °C
Cooling capacity : approx. 9 kW
Air amount : 1.400 m3/h
Voltage : 1 x 230 V - 60 Hz
Fan power : (135/170/190) W - 3-steps
Starter : Yes – Internal

1 Taco setter valve for adjusting of max water flow to coil

E-43, EXHAUST FAN ENGINE STORE, TWEEN DECK

1 Duct fan type K 160 XL


1 1-speed el motor, direct drive
1 Motor protection switch, MPS-3

Fan data:
Air flow : 200 m3/h
Pressure : 300 Pa.
Voltage : 1 x 230 V 60 Hz
Power : 0.153 kW
Current : 0.67 A

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 22
E-44, EXHAUST FAN UPPER CEMENT ROOM, TWEEN DECK

1 Axial fan type 400 A1K


1 2-speeds el motor, direct drive
1 Counter flange
1 Starter cabinet, CP-4
Fan data:
Air flow : 5.000 m3/h
Pressure : 650 Pa
Voltage : 3 x 440 V 60 Hz
Power : 2.3 / 0.55 kW
Current : 4.9 / 1.1 A

E-45, EXHAUST FAN LOWER CEMENT ROOM, TWEEN DECK

1 Axial fan type 400 A1K


1 2-speeds el motor, direct drive
1 Counter flange
1 Starter cabinet, CP-5
Fan data:
Air flow : 5.000 m3/h
Pressure : 650 Pa
Voltage : 3 x 440 V 60 Hz
Power : 2.3 / 0.55 kW
Current : 4.9 / 1.1 A

S-46, SUPPLY FAN BOW THRUSTER ROOM, TWEEN DECK

1 Duct fan type K 200 L


1 1-speed el motor, direct drive
1 Motor protection switch, MPS-4
Fan data:
Air flow : 500 m3/h
Pressure : 300 Pa.
Voltage : 1 x 230 V 60 Hz
Power : 0.234 kW
Current : 1.01 A

S-47, SUPPLY FAN STERN THRUSTER ROOM, TWEEN DECK

1 Duct fan type K 200 L


1 1-speed el motor, direct drive
1 Motor protection switch, MPS-5
Fan data:
Air flow : 500 m3/h
Pressure : 300 Pa.
Voltage : 1 x 230 V 60 Hz
Power : 0.234 kW
Current : 1.01 A

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 23
FC-41/42, FAN COIL BOW THRUSTER ROOM, TWEEN DECK

2 Fan coil type TTC for chilled water 5/11 ºC

Coil data:
Capacity 25 kW

2 Axial fan type 400 A1B


2 1-speed el motor, direct drive
2 Starter cabinet, CP-6 & CP-7

Fan data:
Air flow : 3.000 m3/h
Pressure : 175 Pa
Voltage : 3 x 440 V60 Hz
Power : 0.43 kW
Current : 1.07 A

2 3-way on/off valve w/ actuator


2 Taco setter valve for adjusting of max water flow to coil
2 Thermostat

One unit for continuous operation and one for 100 % back-up

FC-43/44, FAN COIL STERN THRUSTER ROOM PS, TWEEN DECK

2 Fan coil type TTC for chilled water 5/11 ºC

Coil data:
Capacity 25 kW

2 Axial fan type 400 A1B


2 1-speed el motor, direct drive
2 Starter cabinet, CP-8 & CP-9

Fan data:
Air flow : 3.000 m3/h
Pressure : 175 Pa
Voltage : 3 x 440 V60 Hz
Power : 0.43 kW
Current : 1.07 A

2 3-way on/off valve w/ actuator


2 Taco setter valve for adjusting of max water flow to coil
2 Thermostat

One unit for continuous operation and one for 100 % back-up

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 24
FC-45/46, FAN COIL STERN THRUSTER ROOM SB, TWEEN DECK

2 Fan coil type TTC for chilled water 5/11 ºC

Coil data:
Capacity 25 kW

2 Axial fan type 400 A1B


2 1-speed el motor, direct drive
2 Starter cabinet, CP-10 & CP11

Fan data:
Air flow : 3.000 m3/h
Pressure : 175 Pa
Voltage : 3 x 440 V60 Hz
Power : 0.43 kW
Current : 1.07 A

2 3-way on/off valve w/ actuator


2 Taco setter valve for adjusting of max water flow to coil
2 Thermostat

One unit for continious operation and one for 100 % back-up

S-48, SUPPLY FAN STORE ROOM PS, MAIN DECK

1 Duct fan type K 200 L


1 1-speed el motor, direct drive
1 Motor protection switch, MPS-6

Fan data:
Air flow : 500 m3/h
Pressure : 300 Pa.
Voltage : 1 x 230 V 60 Hz
Power : 0.234 kW
Current : 1.01 A

S-49, SUPPLY FAN STORE ROOM SB, MAIN DECK

1 Duct fan type K 200 L


1 1-speed el motor, direct drive
1 Motor protection switch, MPS-7

Fan data:
Air flow : 500 m3/h
Pressure : 300 Pa.
Voltage : 1 x 230 V 60 Hz
Power : 0.234 kW
Current : 1.01 A

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 25
E-50, EXHAUST FAN WORKSHOP, MAIN DECK

1 Duct fan type K 160 XL


1 1-speed el motor, direct drive
1 Motor protection switch, MPS-8

Fan data:
Air flow : 220 m3/h
Pressure : 350 Pa
Voltage : 1 x 230 V60 Hz
Power : 0.153 kW
Current : 0.67 A

FC-47, FAN COIL EL- WORKSHOP, MAIN DECK

1 Fan coil for 100 % re-circulation of air.


The unit is complete with cooling coil and fan built together in a casing.

Unit data:
Type : QZMF 54-2-2-1
Type of refrigerant : Chilled water 5/11 °C
Cooling capacity : approx. 5 kW
Air amount : 1.000 m3/h
Voltage : 1 x 230 V - 60 Hz
Fan power : (135/170/190) W - 3-steps
Starter : Yes – Internal

1 Taco setter valve for adjusting of max water flow to coil

E-51, EXHAUST FAN ROV TRANSFORMER ROOM, MAIN DECK

1 Duct fan type K 200 L


1 1-speed el motor, direct drive
1 Motor protection switch, MPS-9

Fan data:
Air flow : 600 m3/h
Pressure : 200 Pa
Voltage : 1 x 230 V 60 Hz
Power : 0.234 kW
Current : 1.01 A

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 26
S-52, SUPPLY FAN INCINERATOR ROOM, MAIN DECK

1 Duct fan type K 200 L


1 1-speed el motor, direct drive
1 Motor protection switch, MPS-10
Fan data:
Air flow : 500 m3/h
Pressure : 300 Pa
Voltage : 1 x 230 V 60 Hz
Power : 0.234 kW
Current : 1.01 A

E-53, EXHAUST FAN PAINT STORE AFT PS, MAIN DECK

1 Duct fan type EX 140-4C


1 1-speed EX el motor, direct drive
1 Motor protection switch, MPS-11

Fan data:
Air flow : 300 m3/h
Pressure : 150 Pa.
Voltage : 1 x 230 V60 Hz
Power : 0.147 kW
Current : 0.65 A

E-54, EXHAUST FAN N2 GENERATOR ROOM PS, MAIN DECK

1 Duct fan type K 200 L


1 1-speed el motor, direct drive
1 Motor protection switch, MPS-12
Fan data:
Air flow : 400 m3/h
Pressure : 400 Pa
Voltage : 1 x 230 V 60 Hz
Power : 0.234 kW
Current : 1.01 A

E-55, EXHAUST FAN N2 STORE ROOM SB, MAIN DECK

1 Duct fan type K 200 L


1 1-speed el motor, direct drive
1 Motor protection switch, MPS-13
Fan data:
Air flow : 400 m3/h
Pressure : 400 Pa
Voltage : 1 x 230 V 60 Hz
Power : 0.234 kW
Current : 1.01 A

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 27
E-56, EXHAUST FAN GARBAGE ROOM

1 Duct fan type K 200 L


1 1-speed el motor, direct drive
1 Motor protection switch, MPS-14
Fan data:
Air flow : 400 m3/h
Pressure : 400 Pa
Voltage : 1 x 230 V 60 Hz
Power : 0.234 kW
Current : 1.01 A

S-57, SUPPLY FAN EMERGENCY GENERATOR ROOM, TOP OF WH

1 Axial fan type 450 A1K


1 1-speed el motor, direct drive
1 Counter flange
1 Starter cabinet, CP-12
* The fan in use when the generator is running

Fan data:
Air flow : 12.000 m3/h
Pressure : 400 Pa
Voltage : 3 x 690 V 60 Hz
Power : 4,6 kW
Current : 5,5 A

S-58, SUPPLY FAN EMERGENCY GENERATOR ROOM, TOP OF WH

1 Duct fan type K 200 L


1 1-speed el motor, direct drive
1 Motor protection switch, MPS-15
* The fan in use when the generator is not running

Fan data:
Air flow : 500 m3/h
Pressure : 300 Pa
Voltage : 1 x 230 V 60 Hz
Power : 0.234 kW
Current : 1.01 A

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 28
S-59, SUPPLY FAN UPPER & LOWER PUMP ROOM, TANK TOP

1 Axial fan type 400 A1K


1 2-speeds el motor, direct drive
1 Counter flange
1 Starter cabinet, CP-13
Fan data:
Air flow : 5.000 m3/h
Pressure : 650 Pa
Voltage : 3 x 440 V 60 Hz
Power : 2.3 / 0.55 kW
Current : 4.9 / 1.1 A

VENTILATION LOUVERS AND HATCHES


Sys. no: Pos. System Airflow Qty Type Cut out Remarks Hinged
no: m3/h (W x H) ¤ side
*AC-1 - Inlet Accommodation 12 500 1 DRSL-F 680 x 1600 w/ hatch Right
S-40 - Inlet Engine Room 85 000 1 DRS-F 1480 x 3050 - 2 parts
S-41 - Inlet Engine Room 85 000 1 DRS-F 1480 x 3050 - 2 parts
w/
- - Outlet Engine Room 3 x 34 000 3 SS-Vent-FS 900 x 2070 -
damper

• Louver of AC-1 is designed for 60% fresh air


• Inlet Engine Rooms are supplied in two parts and fixed together with bolts

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 29
GENERAL INFORMATION

THE FOLLOWING ARE INCLUDED IN OUR DELIVERY

1 4 SETS OF INSTALLATION AND ENGINEERING MANUAL CONTAINING:


General information.
Complete technical specification
Measuring drawings of all components
Engineering of heating and air-conditioning inside accommodation
Engineering of air amount in each room inside accommodation
Data sheets for evaporator and heating battery
Principal drawings with dimensions for all ventilation in accommodation
Up to 1 revisions of drawings is included. Additional revisions according to separate prices
Electric data for all equipment «Technical data»
Cable and survey diagram for Control systems
Current circuit diagrams for control panels
Technical data sheets for electric components
Piping diagram for refrigerating machinery
All text to be in English language
Necessary approval drawings for ventilation and air-conditioning in accommodation
including refrigerating machinery

2 RESPONSIBILITY
AERON to be responsible for ventilation and air-condition inside accommodation
The drawings and scope of supply to be in accordance with the technical specification, the
classification society rules, and the national rules etc.
AERON is not responsible for design and calculating of air amount etc. outside
accommodation, but deliver fans according to technical specification.

3 4 SETS OF OPERATING AND MAINTENANCE INSTRUCTION BOOKS FOR


THE VENTILATION AND AIR-CONDITION SYSTEMS - CONTAINING:
The same as for Engineering Manual, but with «as built» drawings as far as practicable.
Description of the plant
Measuring reports from start up and trial run for all fans we deliver.
Measuring report from start up and trial run with register of air-mass in every room inside
the accommodation.
Maintenance and Operating instructions for AERON-air-handling units
Maintenance and Operating instructions for auxiliary components
Maintenance and operating instructions for fans
Recommended list of spare parts
Type Test certificate for all electric motors

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 30
4 4 SETS OF OPERATING AND MAINTENANCE INSTRUCTION BOOKS
FOR REFRIGERATING MACHINERY - CONTAINING:
Description of the plant
Operating instructions of refrigerating machinery, compressors etc.
Technical specification of refrigerating machinery
Operating instruction of compressors
Operating instructions for auxiliary components
Maintenance and Description of condensers
Measuring drawings, current circuit diagrams and piping diagrams of refrigerating
machinery
Start up / instruction manual
General seeking for defects
Supplementary information

5 START UP AND TRIAL RUN


A Pre-start up procedure to be sent to yard describes what have to be finished before we
arrive to shipyard. A Start up procedure to be sent to yard describing what we shall do at the
yard.

1 person for start up and trial run of ventilation and air-conditioning systems
1 person for start up and trial run of refrigerating machinery

Based on one trip with necessary assistance for 5 working days with 10 hours day time
work each day. Waiting time caused by the yard will be charged SGD 1450

THE FOLLOWING REPORTS WILL BE DELIVERED:


Measuring of air-amount in all rooms in accommodation
Measuring of air-amount of all fans outside accommodation
Measuring of ampere of all electric motors
All equipment to be checked.

Refrigerating machinery to be started up, checked and handed over.


Pre-commissioning and commissioning report to be delivered.

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 31
THE FOLLOWING ARE NOT INCLUDED IN OUR DELIVERY

1 Innstallation of equipment not mentioned in this technical specification


2 All grills in doors.
3 Delivery and mounting of piping and closing valves, which is not specified.
4 Natural ventilation's
5 Foundations with necessary irons, bolts etc
6 Insulation and insulation work.
7 Painting of any parts for the plant after dispatch
8 Drilling and cutting through bulkheads and decks.
9 All kind of shipwork, like welding etc.
10 Bringing onboard of materials or transportation at the yard.
11 All kinds of square formed ducts.
12 All kind of spiro pipes etc outside accommodation
13 Delivery of electric cables
14 Automatic water valves for refrigerant machinery
15 Water pumps with starters for supply to refrigerant machinery (OPTION)
16 -
17 Drainage from evaporators
18 Fasteners for pipelines (refrigerant system)
19 Vibration dampers and flexible hoses except where it is described
20 Pressure air, nitrogen, Water, light, electric power, etc. which is necessary during adjusting and delivery.
21 Any classification costs for the installation onboard ship
22 Unloading and transportation of the goods at the shipyard
23 Screws, tools etc. necessary for installation of the plant
24 Any item not specially mentioned in this technical specification

Client: Project: Yard no.: Rev.: 9 Date:


KEPPEL SINGMARINE MT 6012 PSV H341 08105 20.11.09
Aeron AS * Nulandsvika 8 * N-4400 Flekkefjord * Norway * Phone: +47 38 32 78 00 * web : www.aeron.no Page 32