[ 10 -kVA, Distribution Transformer (11/ 0.

415-kV)]

P.O No &
2676(GEPCO) Date: 28/9/2023 Inspection Date:
Addl PO No.:
Inspection
H/TR/6553 Date: 9/1/2024 Offered Quantity: 40 Nos.
Call No.:
WAPDA
DDS-84: 2020 Sr. Nos. HA- 3874 to HA- 3913 Tested Quantity: 13 Nos.
Specification:

Power Power
Induced Over-
Frequency Frequency Bird
Victor Group Voltage Tank Gass Paint Turn Ratio Visual
Voltage Voltage Protection
Test Withstand Pressure Thickness Test Test Inspection
Withstand Withstand Test
Transformer Sr. Test
Sr. No. Test Test
No.

34-kV for 1-Min 3-kV for 1-Min on 830-Volts at 100-


(Dyn11) on HT Side. LT Side.
8-kV for 1-Min.
Hz for 1-Min.
15 psi 120 Micron (Min.) Results attached As per Spec.

Withstood the Withstood the Withstood the Withstood the Qualified the Qualified the
1 HA- 3875 Dyn11 test test test test test 131 test
Qualified

Withstood the Withstood the Withstood the Withstood the Qualified the Qualified the
2 HA- 3878 Dyn11 test test test test test 130 test
Qualified

Withstood the Withstood the Withstood the Withstood the Qualified the Qualified the
3 HA- 3881 Dyn11 test test test test test 128 test
Qualified

Withstood the Withstood the Withstood the Withstood the Qualified the Qualified the
4 HA- 3884 Dyn11 test test test test test 133 test
Qualified

Withstood the Withstood the Withstood the Withstood the Qualified the Qualified the
5 HA- 3887 Dyn11 test test test test test 129 test
Qualified

Withstood the Withstood the Withstood the Withstood the Qualified the Qualified the
6 HA- 3890 Dyn11 test test test test test 129 test
Qualified

Withstood the Withstood the Withstood the Withstood the Qualified the Qualified the
7 HA- 3893 Dyn11 test test test test test 125 test
Qualified

Withstood the Withstood the Withstood the Withstood the Qualified the Qualified the
8 HA- 3896 Dyn11 test test test test test 124 test
Qualified

Withstood the Withstood the Withstood the Withstood the Qualified the Qualified the
9 HA- 3899 Dyn11 test test test test test 125 test
Qualified

Withstood the Withstood the Withstood the Withstood the Qualified the Qualified the
10 HA- 3902 Dyn11 test test test test test 129 test
Qualified

Withstood the Withstood the Withstood the Withstood the Qualified the Qualified the
11 HA- 3905 Dyn11 test test test test test 131 test
Qualified

Withstood the Withstood the Withstood the Withstood the Qualified the Qualified the
12 HA- 3908 Dyn11 test test test test test 134 test
Qualified

Withstood the Withstood the Withstood the Withstood the Qualified the Qualified the
13 HA- 3911 Dyn11 test test test test test 125 test
Qualified
Mr. Shahid Nadeem Engr. Boota Goraya Engr. Farhan Younis
Lab Incharge Superintending Engineer GEPCO Asst.Manager (MI) PPMC
RATIO TEST REPORT
[ 10 -kVA, Distribution Transformer (11/ 0.415-kV)]

P.O No & Addl PO No.: 2676(GEPCO) Date: 28/9/2023 Inspection Date:

Inspection Call No.: H/TR/6553 Date: 9/1/2024 Offered Quantity: 40 Nos.

WAPDA Specification: DDS-84: 2020 Sr. Nos.: HA- 3874 to HA- 3913 Tested Quantity: 13 Nos.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Step Specifie
Tolerances HA- 3875 HA- 3878 HA- 3881 HA- 3884 HA- 3887 HA- 3890 HA- 3893 HA- 3896 HA- 3899 HA- 3902 HA- 3905 HA- 3908 HA- 3911
Nos. d Values

AB/an Max. Min.

2 45.91 46.14 45.68 45.91 46.04 45.98 45.91 45.92 46.02 46.05 45.88 45.96 45.95 45.95 46.06 45.96

3 44.76 44.98 44.54 44.70 44.83 44.77 44.70 44.71 44.81 44.84 44.67 44.75 44.74 44.74 44.85 44.75

4 43.61 43.83 43.39 43.49 43.62 43.56 43.49 43.50 43.60 43.63 43.46 43.54 43.53 43.53 43.64 43.54

BC/bn

2 45.91 46.14 45.68 46.01 46.05 45.85 46.06 45.84 45.85 45.84 45.99 46.07 45.90 46.07 45.86 46.02

3 44.76 44.98 44.54 44.80 44.84 44.64 44.85 44.63 44.64 44.63 44.78 44.86 44.69 44.86 44.65 44.81

4 43.61 43.83 43.39 43.59 43.63 43.43 43.64 43.42 43.43 43.42 43.57 43.65 43.48 43.65 43.44 43.60

CA/cn

2 45.91 46.14 45.68 46.04 45.95 46.02 46.06 45.86 45.98 46.00 45.93 45.93 45.88 46.02 46.03 45.85

3 44.76 44.98 44.54 44.83 44.74 44.81 44.85 44.65 44.77 44.79 44.72 44.72 44.67 44.81 44.82 44.64

4 43.61 43.83 43.39 43.62 43.53 43.60 43.64 43.44 43.56 43.58 43.51 43.51 43.46 43.60 43.61 43.43

Mr. Shahid Nadeem Engr. Boota Goraya Engr. Farhan Younis


Lab Incharge Superintending Engineer GEPCO Asst.Manager (MI) PPMC
RESISTANCE TEST REPORT
[ 10 -kVA, Distribution Transformer (11/ 0.415-kV)]

P.O No & Addl PO


2676(GEPCO) Date: 28/9/2023 Inspection Date:
No.:
Inspection Call No.: H/TR/6553 Date: 9/1/2024 Offered Quantity: 40 Nos.

WAPDA Specification: DDS-84: 2020 Sr. Nos. HA- 3874 to HA- 3913 Tested Quantity: 13 Nos.

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Sr. No. HA- 3875 HA- 3878 HA- 3881 HA- 3884 HA- 3887 HA- 3890 HA- 3893 HA- 3896 HA- 3899 HA- 3902 HA- 3905 HA- 3908 HA- 3911

RY 255.67 254.16 254.61 255.38 253.96 255.58 255.78 254.94 253.97 255.11 255.19 255.99 254.31
Resistance at

14 °C YB 255.56 254.90 255.67 254.93 255.01 254.75 255.85 254.09 255.36 255.63 254.45 255.44 254.86

(Ohm)

BR 255.12 254.71 255.37 255.55 254.79 254.81 254.82 254.04 255.79 254.01 254.40 254.28 254.78

ry 284.79 285.07 284.62 282.06 284.06 283.80 285.98 283.63 283.58 282.58 283.95 285.70 284.07
Resistance at

14 °C yb 284.17 285.49 282.35 284.63 282.52 284.32 285.61 284.41 282.65 283.23 285.20 282.78 284.90

(Milli Ohm)

br 283.66 285.44 283.96 283.63 282.65 282.61 285.98 282.42 282.31 284.30 285.62 283.29 285.84

Mr. Shahid Nadeem Engr. Boota Goraya Engr. Farhan Younis


Lab Incharge Superintending Engineer GEPCO Asst.Manager (MI) PPMC
10-KVA Pole Mounted Distribution Transformers
P.O No. : 2676(GEPCO) P.O Date : 28/9/2023
Inspection Call No. : H/TR/6553 Inspection Call Date : 9/1/2024
P.O Qty : 300 Qty Already Accepted : 99
Offered Qty : 40 Balance Qty: 201
Specified Iron Losses (W) : 52 Specified Cu Losses (W) : 256

Test Date :

STATEMENT SHOWING LOSSES OF 10-KVA DISTRIBUTION TRANSFORMERS


NO-LOAD LOSSES DATA FULL-LOAD LOSSES DATA

Full Load
Applied Voltage No Load Applied Current Copper
No-Load Current (A) Impedance Voltage (V) Losses at 14 Total Losses
(V) Losses (A) Losses Percentage
°C (312 W)
Impedance (%
Z)
Sr. T/F Sr. No. Mean Value R Y B Mean R Y B Mean Mean Value
Value W (Total) Value W (Total) at 75 °C

1 HA- 3874 240.9 0.38 0.29 0.37 0.35 40 230.0 230.0 230.0 230.0 0.528 195 243 3.90% 283

2 HA- 3875 240.3 0.39 0.30 0.42 0.37 40 234.0 234.0 234.0 234.0 0.526 191 238 3.95% 278

3 HA- 3876 241.4 0.55 0.34 0.46 0.45 41 233.0 233.0 233.0 233.0 0.526 195 243 3.94% 284

4 HA- 3877 240.4 0.43 0.33 0.46 0.41 41 235.0 235.0 235.0 235.0 0.525 195 243 3.97% 284

5 HA- 3878 241.9 0.43 0.29 0.41 0.38 40 232.0 232.0 232.0 232.0 0.528 196 244 3.93% 284

6 HA- 3879 240.3 0.40 0.29 0.42 0.37 41 235.0 235.0 235.0 235.0 0.529 191 238 3.96% 279

7 HA- 3880 240.1 0.32 0.27 0.34 0.31 39 229.0 229.0 229.0 229.0 0.528 194 242 3.88% 281

8 HA- 3881 241 0.45 0.32 0.44 0.40 41 236.0 236.0 236.0 236.0 0.527 193 240 3.98% 281

9 HA- 3882 240.5 0.39 0.28 0.37 0.35 40 235.0 235.0 235.0 235.0 0.527 193 240 3.97% 280

10 HA- 3883 240.2 0.44 0.33 0.45 0.41 40 227.0 227.0 227.0 227.0 0.528 191 238 3.84% 278

11 HA- 3884 240.1 0.42 0.39 0.41 0.41 41 231.0 231.0 231.0 231.0 0.528 191 238 3.90% 279

12 HA- 3885 240.8 0.39 0.31 0.37 0.36 40 229.0 229.0 229.0 229.0 0.529 193 240 3.88% 280

13 HA- 3886 240 0.47 0.35 0.50 0.44 42 229.0 229.0 229.0 229.0 0.529 193 240 3.88% 282

14 HA- 3887 240.1 0.43 0.32 0.41 0.39 41 221.0 221.0 221.0 221.0 0.528 189 235 3.75% 276

15 HA- 3888 240 0.43 0.49 0.41 0.44 42 233.0 233.0 233.0 233.0 0.526 190 237 3.93% 279

16 HA- 3889 240.3 0.38 0.29 0.38 0.35 40 233.0 233.0 233.0 233.0 0.524 192 239 3.94% 279

17 HA- 3890 240 0.34 0.29 0.36 0.33 39 239.0 239.0 239.0 239.0 0.525 192 239 4.02% 278

18 HA- 3891 240.2 0.37 0.32 0.35 0.35 40 232.0 232.0 232.0 232.0 0.528 190 237 3.92% 277

19 HA- 3892 240.3 0.39 0.31 0.39 0.36 41 238.0 238.0 238.0 238.0 0.529 193 240 4.01% 281

20 HA- 3893 240.7 0.50 0.32 0.48 0.43 41 230.0 230.0 230.0 230.0 0.529 195 243 3.90% 284

21 HA- 3894 240.2 0.71 0.49 0.39 0.53 43 233.0 233.0 233.0 233.0 0.529 193 240 3.94% 283

22 HA- 3895 240.1 0.45 0.33 0.44 0.41 39 235.0 235.0 235.0 235.0 0.529 192 239 3.96% 278

23 HA- 3896 240.1 0.39 0.29 0.41 0.36 40 230.0 230.0 230.0 247.8 0.525 195 243 4.16% 283

24 HA- 3897 240.5 0.36 0.35 0.41 0.37 42 229.0 229.0 229.0 229.0 0.029 194 242 3.88% 284

25 HA- 3898 240.3 0.40 0.33 0.36 0.36 41 231.0 231.0 231.0 231.0 0.527 195 243 3.91% 284

26 HA- 3899 240.1 0.34 0.29 0.36 0.33 40 233.0 233.0 233.0 233.0 0.529 190 237 3.93% 277

27 HA- 3900 240.5 0.34 0.27 0.35 0.32 40 231.0 231.0 231.0 231.0 0.528 191 238 3.90% 278

28 HA- 3901 241.1 0.37 0.33 0.40 0.37 41 232.0 232.0 232.0 232.0 0.525 192 239 3.92% 280

29 HA- 3902 240.1 0.34 0.28 0.38 0.33 40 234.0 234.0 234.0 234.0 0.524 191 238 3.95% 278

30 HA- 3903 240.6 0.47 0.33 0.37 0.39 40 244.0 244.0 244.0 244.0 0.527 190 237 4.09% 277

_____________ _____________ _____________


Mr. Shahid Nadeem Engr. Boota Goraya Engr. Farhan Younis
10-KVA Pole Mounted Distribution Transformers
P.O No. : 2676(GEPCO) P.O Date : 28/9/2023
Inspection Call No. : H/TR/6553 Inspection Call Date : 9/1/2024
P.O Qty : 300 Qty Already Accepted : 99
Offered Qty : 40 Balance Qty: 201
Specified Iron Losses (W) : 52 Specified Cu Losses (W) : 256

Test Date :

STATEMENT SHOWING LOSSES OF 10-KVA DISTRIBUTION TRANSFORMERS


NO-LOAD LOSSES DATA FULL-LOAD LOSSES DATA

Full Load
Applied Voltage No Load Applied Current Copper
No-Load Current (A) Impedance Voltage (V) Losses at 14 Total Losses
(V) Losses (A) Losses Percentage
°C (312 W)
Impedance (%
Z)
Sr. T/F Sr. No. Mean Value R Y B Mean R Y B Mean Mean Value
Value W (Total) Value W (Total) at 75 °C

31 HA- 3904 241 0.41 0.37 0.45 0.41 41 242.0 242.0 242.0 242.0 0.525 194 242 4.07% 283

32 HA- 3905 241.4 0.37 0.41 0.43 0.40 41 231.0 231.0 231.0 231.0 0.526 191 238 3.90% 279

33 HA- 3906 241.9 0.36 0.39 0.33 0.36 41 236.0 236.0 236.0 236.0 0.525 186 232 3.96% 273

34 HA- 3907 241.3 0.48 0.35 0.45 0.43 42 236.0 236.0 236.0 236.0 0.527 193 240 3.98% 282

35 HA- 3908 240.3 0.35 0.41 0.39 0.38 41 237.0 237.0 237.0 237.0 0.529 195 243 4.00% 284

36 HA- 3909 241.2 0.43 0.31 0.45 0.40 41 231.0 231.0 231.0 231.0 0.527 194 242 3.91% 283

37 HA- 3910 240.4 0.40 0.48 0.49 0.46 41 235.0 235.0 235.0 235.0 0.525 196 244 3.98% 285

38 HA- 3911 240.9 0.34 0.30 0.36 0.33 41 236.0 236.0 236.0 236.0 0.528 202 251 4.01% 292

39 HA- 3912 240.4 0.37 0.40 0.41 0.39 40 233.0 233.0 233.0 233.0 0.529 197 245 3.95% 285

40 HA- 3913 241.1 0.39 0.46 0.43 0.43 42 231.0 231.0 231.0 231.0 0.528 199 248 3.93% 290

Average : 41 240 281


Minimum : 39 232 273
Maximum : 43 251 292

Specified : 52 256 308

_____________ _____________ _____________


Mr. Shahid Nadeem Engr. Boota Goraya Engr. Farhan Younis