You are on page 1of 464

MO KSA

TECHNICAL REPORT
King Abdullah International Gardens

Date: 2/29/2024 Document Number: SA-13082-SF


Revision: Rev00 Status: IFR
Author: Keskin, Can Berk Author email: Canberk.keskin@hilti.com

Revision Status Description Date Author Checked Approved


Rev00 IFR CHW Piping Supports 2/29/2024 Keskin, Can Altaibayev, Korompli,
Berk Nauryzbay Paraskevi
Technical report

KSA

TABLE OF CONTENTS
1. Introduction ................................................................................................................................................. 2
1.1. Project: King Abdullah International Gardens ................................................................................... 2
1.2. Customer ........................................................................................................................................... 2
1.3. Basic assumptions ............................................................................................................................. 3
2. Standards, reports, and design criteria ...................................................................................................... 4
2.1. States of design ................................................................................................................................. 4
2.2. Reference codes and standards ........................................................................................................ 4
2.3. General notes about calculations ...................................................................................................... 4
2.4. Units ................................................................................................................................................... 4
2.5. Software ............................................................................................................................................. 5
3. Product information .................................................................................................................................... 6
3.1. Used Hilti portfolio.............................................................................................................................. 6
3.2. Installation products ........................................................................................................................... 6
3.3. Anchors .............................................................................................................................................. 6
3.4. Product assumptions ......................................................................................................................... 6
4. Design input from the customer ................................................................................................................. 7
4.1. Input documents from the customer .................................................................................................. 7
4.2. Assumptions from Hilti ....................................................................................................................... 7
4.3. Loads ................................................................................................................................................. 7
4.3.1. Seismic Loads ............................................................................................................................... 8
4.3.2. Wind/Snow/Sand Loads ................................................................................................................ 8
4.3.3. Load cases .................................................................................................................................... 8
5. Summary of calculations ............................................................................................................................ 9
6. Design solutions and verifications ............................................................................................................ 10
7. Special Terms and Conditions of HILTI (“Hilti”) for Technical advice ..................................................... 14
8. Appendices ............................................................................................................................................... 16
8.1. Appendix 01 – Engineering Input Checklist/ Client Input ................................................................ 16
8.2. Appendix 02 – PROFIS Design reports ........................................................................................... 19

Keskin, Can Berk - 2/29/2024 - Canberk.keskin@hilti.com

The company receiving this design package is solely responsible for confirming, reviewing and approving the adequacy and accuracy of all
information contained herein; and for verifying that the proposed solution is suitable for the intended applications.
Technical report

KSA

1. Introduction
The Scope of this document is to provide proof of the structural integrity of designed supports according to the
Agreed Framework. It is important to notice that not all individual supports are calculated, but calculations are
done according to a common agreement.

This document was done according to the relevant regulations and approvals stated later in the document.

Chapter 7. “Appendices” forms an integral part of this documentation as amended from time to time as
indicated by the revision status in this document.

1.1. Project:
Systems under the scope of Hilti design is piping supports including fixpoints for the green clouded lines
below.

1.2. Customer
Name: Zaid Al Hussain Group

Keskin, Can Berk - 2/29/2024 - Canberk.keskin@hilti.com

The company receiving this design package is solely responsible for confirming, reviewing and approving the adequacy and accuracy of all
information contained herein; and for verifying that the proposed solution is suitable for the intended applications.
Technical report

KSA

1.3. Basic assumptions


Provided inputs and additional information provided in the Engineering Input Checklist (Appendix 01) and its
appendices define fundamental design boundaries and are assumed to be correct at the time of current
revision of this document. All basic loadings and design considerations were derived from clients` information
issued.

Hilti provides technical advice on their products, but load inputs and calculations should be verified and
checked by the customer project designer. It is also assumed that guidance in Instruction For Use is kept for
all products mentioned in present document and there is no need for capacity reduction from abnormal use of
products.

Keskin, Can Berk - 2/29/2024 - Canberk.keskin@hilti.com

The company receiving this design package is solely responsible for confirming, reviewing and approving the adequacy and accuracy of all
information contained herein; and for verifying that the proposed solution is suitable for the intended applications.
Technical report

KSA

2. Standards, reports, and design criteria

2.1. States of design


Following states of design will be considered:
• Ultimate limit state (ULS) – load bearing capacity
• Serviceability limit state (SLS) – deflection

2.2. Reference codes and standards


Attached design reports and calculated design resistance of Hilti products are in accordance with the
following standards:

Document No Document Title


EN 1990 Eurocode 0: Basis of Structural Design
EN 1991 Eurocode 1: Actions on structures
EN 1993 Eurocode 3: Design of steel structures
EN 1998 Eurocode 8: Design of structures for earthquake resistance
Fig 1: Standards

2.3. General notes about calculations


Where possible channel design computation is carried out by the Hilti design software ‘PROFIS’ (“Software”)
which uses the calculation engine from the RSTAB framework software by Dlubal, analogous to the elastic-
elastic method in conformance with EC3 for Europe. The connector design method is based on a combination
of several calculation models following the principles of EC3 for Europe and tests carried out by an independent
institute (HTL Rankweil, Austria).
Local Stress and deformation of members at places where the load is manually entered are not considered.
All connectors and strut connection interfaces provided by Hilti are developed considering local stress and
deformation in accordance with the Eurocode.

2.4. Units
The S.I (system international) metric system was used. The following table shows the unit associated with the
items of major interest for structural analysis purposes.

Item Unit
Length mm
Angles o (degree)
Forces kN
Moments kNm
Distributed Load kN/m
Masses kg
Member stress N/mm2 (MPa)

Keskin, Can Berk - 2/29/2024 - Canberk.keskin@hilti.com

The company receiving this design package is solely responsible for confirming, reviewing and approving the adequacy and accuracy of all
information contained herein; and for verifying that the proposed solution is suitable for the intended applications.
Technical report

KSA

Pressure Pa
Fig 2: Units

Conversion between 1kg = 9.81N


2.5. Software
The following software has been used in structural design.
Software Version
PROFIS Modular Supports Engineering 3057
PROFIS Engineering 3.0.91
Fig 3: Software

Keskin, Can Berk - 2/29/2024 - Canberk.keskin@hilti.com

The company receiving this design package is solely responsible for confirming, reviewing and approving the adequacy and accuracy of all
information contained herein; and for verifying that the proposed solution is suitable for the intended applications.
Technical report

KSA

3. Product information
The values used in these calculations are based on the following documentation provided by Hilti.

3.1. Used Hilti portfolio


In this project following Hilti product portfolios were used:
• MT Systems
• Anchors

3.2. Installation products


Products used in this calculation report are either approved via 3rd party approvals stated below or according
to Hilti technical data which has been made by 3rd party structural analysis companies for products where no
general regulation offered.

Hilti has developed Internal Guidelines for definition essential characteristics and evaluation of the
performance of its Installation Products. Technical data has been provided from testing, analytical calculations
or finite element analysis or combination of these.

All used products are manufactured under a qualified Quality Management System in according with the
requirements of ISO 9001 and ISO 14001 standard. Hilti is taking full responsibility for its product quality from
development to end of the lifecycle.

3.3. Anchors
For all those anchors holding a European Technical Assessment (ETA) the technical data used in this report
is based and in accordance with the information given in the respective ETA. Additional Hilti technical data,
supplementing the ETA technical data, may be available, in which case, it will be clearly noted in calculation
reports.

For all those anchors not holding an ETA, the technical data used in this report is based on numerous tests
and evaluation criteria according to the current state-of-the-art and/or the relevant European applicable
regulations for the assessment of fasteners, which is the basis for obtaining an ETA.

3.4. Product assumptions


In calculations, it is assumed that all used products are assembled according to valid and up to date IFU
(Instruction For Use). It is also assumed that products are unaltered and undamaged to achieve specified
loading capacities.

Keskin, Can Berk - 2/29/2024 - Canberk.keskin@hilti.com

The company receiving this design package is solely responsible for confirming, reviewing and approving the adequacy and accuracy of all
information contained herein; and for verifying that the proposed solution is suitable for the intended applications.
Technical report

KSA

4. Design input from the customer


4.1. Input documents from the customer
Following documents has been agreed with the customer as a starting point for the calculations:

• Seismic load is %2.2 of dead load at X and Y-Dir.


• Safety Factor is 2.00
• 1.5m spacing for Pvc pipe supports.
• 3.0m spacing for Steel pipe supports.
• Valve weight is 4kg/m.
• HDG/OC materials to use.
• Base material is concrete.
• Design code: Eurocode
• Sch40 standards to follow for steel and pvc pipes.
• Pipeclamps and U-Bolts will be selected to cover insulation thickness.
• Thermal expansion forces to consider.

4.2. Assumptions from Hilti


• Default values for deflections used are L/200 for beams and L/150 for cantilevers.
• Wind pressure is 81kn/m2.
• Insulation density is 64kg/m3.
• Friction Factor is 0.20
• Risers and Mechanical equipments are not considered in design.
• Rubber inlay should be provided by coustomer.
• For some of the provided solutions, pipes may need to be slightly adjusted.
• Seismic design is not considered for the pipes smaller than DN65.
• The design shown in this report is a preliminary design which needs to verified against exact site
conditions
• Only for fixpoint types D and F, galvanized materials which needs to be confirmed by
customer were proposed.
• Assumed compensator properties are shown in fixpoint summary table in 6.2
• A physical stopper must be applied to the pipe in order to properly transfer the fixed-point
force from the pipe to the fixed-point. A physical stopper can appear in different forms
dependent on the material, diameter, thickness, and finish of pipe. The design, calculation
and installation of the physical stopper is in the responsibility of the customer.
• It is important to highlight the fact that all the design of the supports for chilled water
pipes is based on assumptions for the horizontal and vertical loads. Also, the fixed point
loads and locations are based on assumptions, customer needs to verify and confirm
these assumptions.
• Hilti strongly advises customer to provide a pipe stress analysis report to ensure that all
expansion loads are being captured.

4.3. Loads
Load actions are classified in EC1990 by their variation in time as permanent actions (G), variable actions (Q)
and accidental actions (A). For simplicity, we refer to all variable loads as Live loads and permanent loads as
Dead loads. For live loads, we use a partial safety factor of 1,5 for ULS. For dead loads, we use a partial safety
factor 1,35. For SLS safety factor is 1,0 for both load cases.
Pipes and ducts represent elements for which variations in time are considered as negligible by EN1990
definitions. Based on that, loads from pipes and ducts are assumed to be dead loads.
Technical report

KSA

4.3.1. Seismic Loads


Seismic load is %2.2 of dead load at 2-Dir.

4.3.2. Wind/Snow/Sand Loads


Wind pressure is 81kn/m2.

4.3.3. Load cases


For design, load cases and load combinations are presented in appendix02 Profis design reports.

Keskin, Can Berk - 2/29/2024 - Canberk.keskin@hilti.com

The company receiving this design package is solely responsible for confirming, reviewing and approving the adequacy and accuracy of all
information contained herein; and for verifying that the proposed solution is suitable for the intended applications.
Technical report

KSA

5. Summary of calculations

The structural integrity for each one of the support solutions listed in Fig 4 has been checked. Calculations
have been done in PROFIS Installation, unless specified otherwise.
The calculations show that these solutions meet all requirements as specified by the customer, as well as the
relevant standards and regulations. Therefore, it can be stated that these solutions are safe for use.

Design Status Comments


Case-1 OK Profis design reports appendix02
Case-2 OK Profis design reports appendix02
Case-3 OK Profis design reports appendix02
Case-4 OK Profis design reports appendix02
Case-5-7-10 OK Profis design reports appendix02
Case-6 OK Profis design reports appendix02
Case-8 OK Profis design reports appendix02
Case-9 OK Profis design reports appendix02
Case-11 OK Profis design reports appendix02
Case-12 OK Profis design reports appendix02
Case-13 OK Profis design reports appendix02
Case-14 OK Profis design reports appendix02
Case-15 OK Profis design reports appendix02
Case-16 OK Profis design reports appendix02
Fixpoint Type A OK Profis design reports appendix02
Fixpoint Type B NOT OK Design Table at section 6.2
Fixpoint Type C OK Design Table at section 6.2
Fixpoint Type D OK Design Table at section 6.2
Fixpoint Type E OK Profis design reports appendix02
Fixpoint Type F OK Design Table at section 6.2
Fixpoint Type G OK Profis design reports appendix02
Fig 4: Executive summary

Keskin, Can Berk - 2/29/2024 - Canberk.keskin@hilti.com

The company receiving this design package is solely responsible for confirming, reviewing and approving the adequacy and accuracy of all
information contained herein; and for verifying that the proposed solution is suitable for the intended applications.
Technical report

KSA

6. Design solutions and verifications


6.1. Typical Proposed solutions

Support Types
Ref. Examples of Typical Solutions
Goal Post
Support
Types

Goal Post
Support
Types

Goal Post
Support
Types

Keskin, Can Berk - 2/29/2024 - Canberk.keskin@hilti.com

The company receiving this design package is solely responsible for confirming, reviewing and approving the adequacy and accuracy of all
information contained herein; and for verifying that the proposed solution is suitable for the intended applications.
Technical report

KSA

FixPoint
Support
Types

FixPoint
Support
Types

FixPoint
Support
Types

FixPoint
Support
Types

Keskin, Can Berk - 2/29/2024 - Canberk.keskin@hilti.com

The company receiving this design package is solely responsible for confirming, reviewing and approving the adequacy and accuracy of all
information contained herein; and for verifying that the proposed solution is suitable for the intended applications.
6.2. Detailed structural calculations/ Technical results verifications
Tables below indicates applied loads and cases for support design on project

CASE SUMMARY TABLE

Fixpoint
Wind Load Distance to Support Total Support Fixpoint
Case No Inside Trench B.O.P. F.F.L. Pipes Design
Existment Base Spc Length Quantity Quantity
Type

(m) (m) (m) (m) (m)


1 No Yes 869.85 869.35 0.50 x2 DN100 3.00 13.00 6 2x3 A
875.00 5.65 x2 DN100 2x2 B
2 869.35 3.00 6
No Yes 875.30 5.95 x2 DN50 13.00 -
3 875.30 869.35 5.95 x2 DN50 1.50 6 -
869.50 0.15 x2 DN100 2x2 C
4 869.35 3.00 9
Yes No 869.80 0.45 x2 DN50 19.00 -
5 869.80 869.35 0.45 x2 DN50 1.50 9 -
869.50 0.15 x2 DN200 2x3 D
6 869.35 3.00 22
Yes No 869.80 0.45 x2 DN50 55.00 -
7 869.80 869.35 0.45 x2 DN50 1.50 22 -
8 No Yes 870.60 869.35 1.25 x2 DN100 3.00 20.00 9 2x2x3 E
869.50 0.15 x2 DN150 -
9 869.35 3.00 6
Yes No 869.80 0.45 x1 DN50 12.00 -
10 869.80 869.35 0.45 x1 DN50 1.50 6 -
11 Yes No 869.50 869.35 0.15 x2 DN150 3.00 11.00 6 1x2 F
12 Yes No 870.65 869.35 1.30 x2 DN150 3.00 6.00 4 -
13 No Yes 870.40 869.35 1.05 x2 DN150 3.00 36.00 15 2x2 G
14 No Yes 870.80 869.35 1.45 x1 DN150 3.00 5.00 3 -
15 No Yes 871.50 869.35 2.15 x2 DN150 3.00 5.50 4 -
16 No Yes 869.70 869.35 0.35 x2 DN100 3.00 5.50 4 -
Technical report

KSA

LOAD SUMMARY TABLE


Weight of Pipering / U-Bolt
Weight of Axial
Weight of Additional Insulated Seismic Wind Load
Pipe Insulation Pipe Friction Support Design Friction
Pipe Size O.D. Insulation Valve Pipe Dead Load Load in X & (0.81kn/m2 Design
Material Thickness Filled with Factor Spc Load (SF=2) Load in X & Total Dia Type Utilization
(64kg/m3) Weight Filled with Y Dir(%2.2) pressure) Capacity
Water Y Dir
Water
DN (mm) (mm) (kg/m) (kg/m) (kg/m) (kg/m) (m) (kn) (kn) (kn) (kn) (kn) (mm) (kn) (%)
MP-PI 135-
Sch40 Pvc 50.00 60.30 38.00 3.00 0.75 - 3.75 - 1.50 0.06 0.11 - 0.17 - 136.30 143 M8/M10 1.50 8%
HDG
MP-UB 219
Sch40 Steel 100.00 114.30 51.00 24.20 1.69 4.00 29.89 0.20 3.00 0.90 1.79 0.02 0.53 0.18 216.30 7.42 24%
8" M12 OC

MP-UB 273
Sch40 Steel 150.00 168.30 51.00 46.80 2.25 4.00 53.05 0.20 3.00 1.59 3.18 0.04 0.66 0.32 270.30 7.42 43%
10" M12 OC

MP-UB 324
Sch40 Steel 200.00 219.10 51.00 74.60 2.77 4.00 81.37 0.20 3.00 2.44 4.88 0.05 0.78 0.49 321.10 7.42 66%
12" M12 OC

NOTE : FOR FIXPOINT DESIGN TYPE B; PIPES NEED TO BE ADJUSTED TO A REASONABLE HEIGHT OR ADDITIONAL STRUCTURAL MEMBERS NEED TO BE
PROVIDED FOR FIXPOINT CONNECTIONS SINCE THE DISTANCE IS TOO HEIGHT FOR A FIXPOINT DESIGN.

Keskin, Can Berk - 2/29/2024 - Canberk.keskin@hilti.com

The company receiving this design package is solely responsible for confirming, reviewing and approving the adequacy and accuracy of all
information contained herein; and for verifying that the proposed solution is suitable for the intended applications.
7. Special Terms and Conditions of HILTI (“Hilti”) for Technical advice
1. These terms and conditions apply to the technical advice provided by Hilti to its customers
("Customer"), when Customers seek for certain Hilti's products. These terms and conditions also apply to
future instances of technical advice provided by Hilti to Customer, without the Customer having to be inform
about these terms and conditions in each individual case. Customer's general terms and conditions shall not
apply, even when Hilti has not expressly objected them.

2. Hilti generally provides the technical advice based on technical and legal provisions applicable at Hilti’s
place of establishment.

3. It is the Customer's responsibility to inform Hilti of all project or object related marginal conditions
relevant for Hilti's technical advice, and to check that the technical assumptions by Hilti are correct and
complete and immediately inform Hilti of any misalignments in text form. Hilti is not obliged to verify or check
the project and/or object related framework conditions reported by the Customer (e.g. to ensure compliance
with the actual on-site conditions, legal requirements or plausibility). This also applies when Hilti has inspected
or had access to an object, design documents, or similar technical information on the project or object. Object
or project related framework conditions shall be deemed to be the basis for Hilti's technical advice only when
Hilti has expressly confirmed this; for example, through the reproduction of, or reference to, documents
provided by Hilti in the technical consultation or separate written confirmation. It is the Customer's responsibility
to arrange and pay for the technical advice provided by Hilti.

4. The output is prepared based on the technical information that the Customer provides to Hilti, for Hilti
to provide a non-binding suggestion over the product to be used by the Customer in its project. Insofar as
Hilti's technical advice is based on object or project related framework conditions, it is the Customer's sole
responsibility to ensure and verify this advice is under the actual circumstances and correspond to the specific
application intended by the Customer. Even slight deviations in design or slight differences between the actual
conditions and those specified by the Customer to Hilti, which Hilti has used for providing the technical advice,
will require a technical re-evaluation and re-calculation, which shall be the Customer's sole responsibility to
arrange with Hilti.

5. Designs and calculations are carried out with the relevant Hilti Profis calculation software or R-stab
software, details about the software, its limitations and underlying measurement methods can be obtained
from Hilti. Hilti designs and calculations are based on codes, general design standards, and Hilti-published
data current as of their creation date. For Hilti component and connection design see published technical data,
including material and cross-section properties, allowable load values, factors of safety, methods of
calculation, and limiting factors.

6. When providing designs and calculations, Hilti does not consider the following technical requirements:

• Supports considering thermal expansion/contraction;


• Seismic resistant design;
• Fire resistant design;
• Dynamic loading;
• Pipe insulation / avoid condensation;
• Specific approvals;
• Calculation of third party products.

If any of the above technical requirements need to be considered, Customer must specifically inquire with Hilti
whether this is possible. Hilti must agree in writing (typically mentioned in Technical report) to provide a solution
taking the above technical requirements into account, otherwise they are not considered.
Technical report

KSA

7. If the bill of materials contains Hilti anchors, Profis MSE and/or Profis Engineering software is utilized
for the calculation. Load values of the anchors are published in the current Technical Manual.

Technical advice of direct fastening (DX) connections is based on FTM Hilti Fastening technology Manual.

8. In case of modification or additional object or project related framework conditions which require
additional technical advice from Hilti, Hilti may accept to do so at an additional charge to be agreed with the
Customer.

9. The technical advice refers exclusively to products sold by Hilti and it is not transferable to products
from other manufacturers. All technical solutions communicated as part of the technical advice are always
object or project specific and non-transferable. It is therefore the Customers' sole liability to decide whether
to acquire or not the product suggested by Hilti; the Product shall be sold on the sole basis of Hilti’s standard
product warranty.

10. Unless expressly stated or agreed otherwise, performance deadlines and dates in the technical advice
are always non-binding.

11. Technical recommendations made by Hilti to Customers are deemed to be non-binding and for the
only purpose to provide the Customer with an initial indication of technical feasibility of Hilti's products and a
provisional estimation of material costs. The Technical recommendations constitute a conceptual or detailed
design, and must be reviewed and approved by the appropriate and responsible person from the Customer’s
side. In particular regarding conformity with the data in the technical data sheets, technical manuals, operating
instructions and approvals of the respective Hilti products, the applicable laws and regulations, the recognized
engineering standards and the on-site conditions. The technical data sheets, technical manuals, operating
instructions and approvals for Hilti products can be viewed at https://www.hilti.sa/
or ordered from Hilti.

12. Hilti's liability is limited to direct damage caused by intent and gross negligence, so HILTI is not liable
for consequential damages, loss of business, damages or any other variation that impacts the assets of the
Customer or any third party.

13. Personal data, sensitive personal data, databases, and other information that may be considered
protected will be treated in accordance with Hilti data protection policy and in accordance with current
regulations.

14. Additionally, the Customer declares to know and accept the Hilti Terms and Conditions of Sale that
can be consulted in https://www.hilti.sa/content/hilti/META/SA/en/support/legal/index/terms.html

which are understood to be an integral part of this document. In case of contradiction between the Terms and
Conditions of Sale of Hilti and this document, the latter will always prevail.

Keskin, Can Berk - 2/29/2024 - Canberk.keskin@hilti.com

The company receiving this design package is solely responsible for confirming, reviewing and approving the adequacy and accuracy of all
information contained herein; and for verifying that the proposed solution is suitable for the intended applications.
Technical report

KSA

8. Appendices
8.1. Appendix 01 – Engineering Input Checklist/ Client Input

Keskin, Can Berk - 2/29/2024 - Canberk.keskin@hilti.com

The company receiving this design package is solely responsible for confirming, reviewing and approving the adequacy and accuracy of all
information contained herein; and for verifying that the proposed solution is suitable for the intended applications.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
LEGEND/SYMBOLS Legends: SYMBOLS AND LEGEND: LEGENDS KEY PLAN

FIRE PIPE (FP) VD/VCD VOLUME CONTROL DAMPER


FRESH AIR DUCT
DISTANCE BETWEEN TWO FIRE HYDRANTS
L/s LITRE PER SECOND
EL OR EAL EXHAUST LOUVRE
CROSS SECTION REFERENCE FCU FAN COIL UNIT RETURN AIR DUCT
FD FIRE DAMPER
A L
FGL
LENGTH OF PIPE
FINISHED GROUND LEVEL L/L LOW LEVEL SUPPLY AIR DUCT A
TOC TOP OF CULVERT H/L HIGH LEVEL
SC
IL INVERT LEVEL F/A FROM ABOVE EXHAUST AIR DUCT
EGL EXISTING GROUND LEVEL T/A TO ABOVE sketch-Layout2-Layout1 (3)1.jpg
U DATA F/B FROM BELOW AHU RETURN OPENING
MATCHLINE
T/B TO BELOW
FP FLOW DIRECTION SAD SUPPLY AIR DUCT
RAD RETURN AIR DUCT JET NOZZLE DIFFUSER
FAD FRESH AIR DUCT
FIRE HOSE REEL CABINET EAD EXHAUST AIR DUCT
SD SUPPLY DIFFUSER DRUM JET DIFFUSER
SG SUPPLY GRILLE
LSD LINEAR SUPPLY DIFFUSER
INTERFACE PIT AIR VALVE CHAMBER
ED EXHAUST DIFFUSER
EG EXHAUST GRILLE FLOOR LINEAR GRILLE
LRD LINEAR RETURN DIFFUSER NOTE/LEGEND :
B VALVE PIT WASHOUT CHAMBER ATT
FLEX
SOUND ATTENUATOR
FLEXIBLE CONNECTION
FLOOR GRILLE IN
LANDSCAPE AREA B
BOD BOTTOM OF DUCT General Notes:
ISOLATION PIT THRUST BLOCK BOU BOTTOM OF UNIT FIRE DAMPER 1. THIS DRAWING IS ISSUED FOR INFORMATION ONLY. THE FINAL COMPOSITE SHOP DRAWING WILL
BOP BOTTOM OF PIPE FOLLOW THE APPROVAL ON THE SEPARATE TRADES.
FFL FINISH FLOOR LEVEL 2. ALL DIMENSIONS ARE IN mm UNLESS NOTED OTHERWISE NOTED.
VOLUME DAMPER 3. THIS DRAWING SHALL BE READ IN CONJUNCTION WITH ALL RELATED ARCHITECTURAL,
LANDSCAPE, STRUCTURAL AND SERVICES DRAWINGS & SPECIFICATIONS.
SOUND ATTENUATOR 4. ALL WORK SHALL BE CARRIED OUT IN ACCORDANCE WITH THE SPECIFICATIONS
5. ALL MANHOLES, DRAW PITS AND ACCESS CHAMBERS SHALL BE CONSTRUCTED TO HAVE THE
CHAMBER COVER LEVEL FLUSH WITH THE SURROUNDING SITE TOPOGRAPHY
6. UNLESS OTHERWISE INDICATED, ALL DRAW PITS AND ACCESS CHAMBERS SHALL HAVE FRAME
AIR HANDLING UNIT AND COVER SUROUNDS CONSTRUCTED FROM 150mm PRE-CAST CONCRETE OR 150mm MORTAR
JOINTED DENSE CONCRETE BLOCKS, MINIMUM GRADE C20
7. FOR PITS USED TO ACCESS CABLED SERVICES, END DUCTS ARE TO BE IN LINE TO ALLOW
₂ ₂
CABLES TO BE PULLED STRAIGHT THROUGH WHERE REQUIRED. WHERE POSSIBLE DUCTS ARE
DUCT WALL OPENING TO BE POSITIONED EQUIDISTANT FROM SIDE WALLS OR A MINIMUM OF 85mm DISTANT FROM THE
₂ ₂ INSIDE FACE OF SIDE WALLS
8. THE FINAL DESIGN OF ANY THRUST BLOCKS REQUIRED FOR PIPED UTILITY SERVICES CARRYING

C 9.
FLUIDS IS TO BE DEFINED BY THE CONTRACTOR IN ACCORDANCE WITH THE LATERAL BEARING
CAPACITY OF SURROUNDING SUB-GRADE AT EACH RELEVANT LOCATION
THE ORIENTATION OF WASHOUT CHAMBERS SHOULD BE TO SUIT SITE CONDITIONS
C
10. WHERE REQUIRED THE CONTRACTOR SHALL INSTALL A DRAIN FROM HYDRANT CHAMBERS TO A
SOAKAWAY. SOAKAWAY SIZES TO BE DETERMINED BY ENGINEER ON SITE
11. DRAW PITS FOR DUCTED ELECTRICAL POWER AND TELECOMMUNICATIONS SERVICES TO BE
PROVIDED TO ASSIST CABLE PULLING WHERE LENGTHS OF DUCTING BETWEEN JUNCTIONS
EXCEED 200m IN LENGTH
12. UTILITIES INFRASTRUCTURE CONTAINMENT SERVING CRESCENTS, ANCILLARY BUILDINGS AND
GARDENS SHALL TERMINATE IN ACCESS PITS AND/OR BURIED ACCESS CHAMBERS IN THE
VICINITY OF THE APPROPRIATE PLANTROOMS. FINAL CONNECTIONS INTO INDIVIDUAL
PLANTROOMS FROM THE RELEVANT UTILITY TERMINATION PITS ARE SHOWN ON THE RELEVANT
MEP PLANTROOM DRAWINGS
13. FINAL CO-ORDINATION OF CONNECTIONS TO SECURITY BOLLARDS, CESSPOOLS, PUMPING
STATIONS, BULK WATER STORAGE TANKS, AND LPG GAS COMPOUNDS IS TO BE IN ACCORDANCE
WITH MANUFACTURER/SPECIALIST SUB-CONTRACTOR DETAILS
14. ALL MEP SERVICES SHOULD BE READ FROM (F.F.L) FINISH FLOOR LEVEL

D CHWP AREA (1)


D

TOH +874.00
+TR 874.50BOH+870.75
TOH +874.00 +BOH 870.75
BOH+870.75
+TR 874.50
TOH +874.00
BOH+869.00 +TR 874.50
+BOH 870.75 E
+BOH 869.00
TOH +874.00 +TM 874.45
+TR 874.50 BOH+869.00 +TM 874.45
+BOH 869.00
+TR 874.50 +TW 874.80
+TM 869.34
F +TR 874.50
+BOH 869.00 +TM 872.45
+TR 874.50 +TR 874.50
+BOH 869.00 +BR 869.75
+BR 869.20
TSE 869.36
TP 869.26 N KEYPLAN
TOH +872.00
+TR 872.50 BOH+868.75
+TM 869.373
TOH +874.00 +BOH 868.75 +TM 869.335
+TM 869.38 TP 869.255
BOH+869.00
+TD 867.15
+TR 869.60
HR Makka
TSE 869.355
TP 869.293
+WL 869.00 TP 869.255 TSE 869.36
TP 869.30
+BL 867.25

TSE 869.40
TSE 869.393
0.4
5%
0.45%
0.4
5% TP 869.255
+TM 869.34
F
+TR 874.50 TSE 869.37
+TM 869.38 +TR 869.40 TP 869.26 TP 869.20
+BR 869.30 TR 869.50 TP 869.27
5%
+TR 869.50 TR 869.40 0.4
TOH +874.00 869.20m

BOH+869.00 +BL 867.25 TM +869.35


G TW 874.50 +
+TR 874.50 +TR 869.40
TP 869.235
TM+869.48

0.15%
+BOH 869.00 +TR 874.50
+TR 874.50 +BL 868.00 +BOH 869.00
TOH +874.00
+BOH 870.00 BOH+869.00
TOH +874.00
BOH+870.00
TOH +874.00 +TR 874.50
+BOH 869.00
+TM 874.45 REFERENCE DRAWINGS

0.45%
BOH+869.00
TOH +874.00 KAIG3-SD-CG-L-HP-1002-01 CENOZOIC GARDEN LEVELS AND GRADING PLAN
BOH+869.00 CENOZOIC GARDEN HDCC CUBES LAYOUT PLAN (SHEET 1
KAIG3-SD-CG-C-GA-1520-00 OF 2)
+TM 869.38 +TR 874.50
+BOH 869.00
CRESCENT 1 CENOZOIC GARDEN UNDERGROUND FIRE
G
TM+869.48 KAIG3-SD-CG-M-FF-1001-00
FIGHTING LAYOUT SHEET 1 OF 2
TP 869.215 TM
+TR 874.50 TR 869.50 + TM TSE 869.195
TSE 869.32 +869.30
TOH +873.10
CRESCENT 1 CENOZOIC GARDEN CHILLD WATER
+BR 869.30 +869.30 TP 869.295 KAIG3-SD-CG-M-HP-1000-01
TSE 869.32 TP 869.22 BOH+869.10 PIPEWORK LAYOUT MASTER PLAN
TR 873.60 +

ENTR
+TM 874.45 +TR 874.50
H BL +868.80
TP 869.22
TR 869.50 0.
+BOH 869.00
15%
+BOH 869.10
KAIG3-SD-CG-M-HV-1000-01
CRESCENT 1 CENOZOIC GARDEN VENTILATION LAYOUT
MASTER PLAN
45 0.

ANCE
TP 869.215 % TM CRESCENT 1 CENOZOIC GARDEN UNDERGROUND
TP 869.191 +TM 869.275 KAIG3-SD-CG-M-DP-1001-01
TSE 869.315 +869.267 DRAINAGE LAYOUT SHEET 1 OF 2
+TW 874.50 TSE 869.291 CRESCENT 1 CENOZOIC GARDEN WATER FEATURE WET
KAIG3-SD-CG-M-DP-7001-00
TM WELL DETAILS
TP 869.187
+869.295 CRESCENT 1 CENOZOIC GARDEN WATER FEATURE PIPE
TSE 869.287 KAIG3-SD-CG-M-DP-1003-00
ROUTING PLAN LAYOUT SHEET 1 OF 2
BL +867.78 MH CENOZOIC GARDEN POWER CONTAINMENT LAYOUT
TM TSE 869.287
+869.20
KAIG3-SD-CG-E-CR-1003-00
SHEET 2 H
+869.266 CENOZOIC GARDEN LOW CURRENT CONTAINMENT
TSE 869.286 TP 869.187 F.F.L. KAIG3-SD-CG-LC-CR-1003-00
+TM 869.267 LAYOUT SHEET 2
TP 869.186 TP 869.179
+TD 867.15
TR 869.40 KAIG3-SD-CG-L-IR-1001-00 CENOZOIC GARDEN IRRIGATION SYSTEM
+TM 874.45 TOH +874.00 +WL 869.00
I BOH+869.00 TM+869.38 TP 869.184

0.45%
+TR 874.50 POOL 1 BL +867.35 TSE 869.284 TP 869.20

TM TP
+869.264 869.195 TP 869.20
+TR 869.40 +TM 869.275 TSE
869.295
01 07.09.23 ISSUED FOR APPROVAL ZHBG
+TM 869.223 TP 869.19 00 16.02.23 ISSUED FOR APPROVAL ZHBG
55 %
CHWP AREA (2) TSE
TSE
869.25
0. REVISION
NO.
DATE PURPOSE & REMARKS ZHBG I
TD 869.15
TM
869.25
+869.23
TR 869.60 TP 869.15 TP 869.15 TSE 869.30 Trade ARCHITECTURE LANDSCAPE STRUCTURAL MECHANICAL ELECTRICAL
TR 869.40
TM+869.58 Date:
TP
J 869.20

0.15
TM+869.48 +TM 869.28
Sign:
TOH +874.00 TP 869.276

%
TM +869.347

0.45 %
BOH+869.00 TSE 869.376 +TR 873.00
+TR 874.50 +TR 874.50 +BR 869.10
TSE 869.367 BL +867.78
+BOH 869.00 +BR 869.20 TM TR 869.30
TP 869.267 TSE 869.276 +TM 869.256 KINGDOM OF SAUDI ARABIA
+869.371
TP 869.171 TP 869.176
TR 869.50 PROJECT TITLE:
TP 869.262 BL +868.80
+TM 869.251 TSE 869.271
TSE 869.370 TP 869.20
0.
TP 869.270
TP 869.267 55
TSE 869.367 %
+TR 873.00
+BOH 869.25
+TR 873.00
+BOH 869.25 KING ABDULLAH INTERNATIONAL GARDENS
.\1A_03_02.jpg
J
TP 869.265 STAGE 3

0.45 %
TOH +872.50
TP 869.270 BOH+869.25
TSE 869.370 +TM 869.313
TP 869.242
+TR 874.50 OWNER:
0.35

+TR 874.50
+BR 869.20 TR 869.40
K TP 869.237 0.55%
TP 869.233 TSE 869.333
%

+TR 873.50 TP 869.242 TP 869.182


TP 869.228 TM +872.95
+BOH 869.00
TP 869.260 TOH +873.00 TM 0.55%
+TM 874.45
TP 869.255 BOH+869.00
+869.322 TSE 869.321
+TR 869.260 TSE 869.342 .\AL RIYADH MUNICIPALITY.jpg

TP 869.221

0.45
+TW 874.50 TP 869.233 MINISTRY OF MUNICIPAL AND RURAL AFFAIRS
TSE 869.360
TM+869.335 AL RIYADH MUNICIPALITY .\55.png

%
TOH +874.00
TOH +874.00 +TR 874.50 BOH+869.00 TM +869.301
BOH+869.00 +BOH 869.00
+TR 874.50
+BOH 870.00 TM
TOH +874.00
BOH+870.00
+869.278
TSE 869.298
TOH +872.50
+ TW 874.80 DESIGNER: K
TP 869.20
0.35 %

TP 869.198 BOH+869.25

TOH +874.00
.\DSIGNER.jpg
+TM 874.45 BOH+869.00
L TP 869.243 TP 869.238
TM+869.323 TOH +874.00
BOH+869.00
TSE 869.343
+TR 874.50
TSE 869.343 +TR 873.00 +869.20 CONSULTANT :
+TR 874.50
+BOH 869.00 +BR 869.20 TP 869.333 +TR 874.50 +BOH 869.25 T.S.L.
TM+ 869.323 +TM 874.45 TP 869.193
+BOH 869.00
+TR 869.40 TSE 869.293

TM .\dar cad.jpg
0.

TOH +874.00
35

BOH+869.00 +869.273
%

TSE 869.372
TP 869.272 TOH +872.50
0.45

+TR 874.50
BOH+869.25 MAIN CONTRACTOR: L
%

TP 869.222 +TM 872.45


TM+869.293 +BOH 869.00
TOH +874.00
TM+869.352 BOH+869.00
TSE 869.372 TSE 869.362
HR
M
CHWP AREA (3) +TD 867.15
TP 869.272
TR 869.50 TP 869.262

0.35 %
TP 869.25
TSE 869.35
TP 869.20
TP 869.238

TP 869.188
0.35 %
TP 869.165
TM+869.24
TOH
+TR +872.50
873.00
BOH+869.25
+BR 869.35 +TR 872.50
+BOH 868.75
.\ZDHBG.PNG M
+TWS 869.00 TSE 869.26
0.

TP 869.262 TR 869.40 TOH +872.00


45

TP 869.25 DISCIPLINE:
TSE 869.362 TSE 869.338 TP 869.16 BOH+868.75
ELECTROMECHANICAL
%

TSE 869.35
TM+869.342

TM+869.33 TM+869.318 DRAWING TITLE :


TP TD 869.15
BL +867.40
869.155 CRESCENT 1 - CENOZOIC GARDEN
0.30 %
TM+869.250
TP 869.15 +TR 872.50
+BOH 868.75 +TM 872.45 MEP COMPOSITE LAYOUT
TP 869.171
+BL 868.50 TSE869.270
SHEET - 1 OF 2
TOH +872.00 DRAWING NO:
870.07m BOH+868.75 TP 869.170 TOH +872.00
N N
5%

TR 869.40 BOH+868.75
+BL 868.40 KAIG3-SD-CG-G-MS-4001-01
0.5

+TR 872.50 BL +867.78


+BOH 868.75 +TR 871.50
+TM 872.45 +BOH 868.75

0.3
+TR 874.50 Date: Drawn By: In Charge: Checked By:

0%
BL +867.35 +TR 871.50 TP 869.20
+BOH 869.00
+BOH 868.75
TR 869.40 07.09.23 GK SK SAN
5%
0.3
FOR CONTINUATION REFER TO DRG. NO. KAIG3-SD-CG-G-MS-4002-01 Scale: 1:100 Size: A0

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
KEY PLAN
LEGEND/SYMBOLS Legends: SYMBOLS AND LEGEND: LEGENDS

FIRE PIPE (FP) VD/VCD VOLUME CONTROL DAMPER


FRESH AIR DUCT
DISTANCE BETWEEN TWO FIRE HYDRANTS
L/s LITRE PER SECOND
EL OR EAL EXHAUST LOUVRE
CROSS SECTION REFERENCE FCU FAN COIL UNIT RETURN AIR DUCT

A L
FGL
LENGTH OF PIPE
FINISHED GROUND LEVEL
FD
L/L
FIRE DAMPER
LOW LEVEL SUPPLY AIR DUCT A
TOC TOP OF CULVERT H/L HIGH LEVEL
SC
IL INVERT LEVEL F/A
T/A
FROM ABOVE
TO ABOVE
EXHAUST AIR DUCT
sketch-Layout2-Layout1 (3)1.jpg
EGL EXISTING GROUND LEVEL
U DATA F/B FROM BELOW
MATCHLINE AHU RETURN OPENING
T/B TO BELOW
FP
FLOW DIRECTION SAD SUPPLY AIR DUCT
RAD RETURN AIR DUCT JET NOZZLE DIFFUSER
FAD FRESH AIR DUCT
FIRE HOSE REEL CABINET EAD EXHAUST AIR DUCT
SD SUPPLY DIFFUSER DRUM JET DIFFUSER
SG SUPPLY GRILLE
LSD LINEAR SUPPLY DIFFUSER
INTERFACE PIT AIR VALVE CHAMBER
ED EXHAUST DIFFUSER
EG EXHAUST GRILLE FLOOR LINEAR GRILLE
LRD LINEAR RETURN DIFFUSER NOTE/LEGEND :
B VALVE PIT WASHOUT CHAMBER ATT
FLEX
SOUND ATTENUATOR
FLEXIBLE CONNECTION
FLOOR GRILLE IN B
LANDSCAPE AREA General Notes:
BOD BOTTOM OF DUCT
ISOLATION PIT BOU BOTTOM OF UNIT 1. THIS DRAWING IS ISSUED FOR INFORMATION ONLY. THE FINAL COMPOSITE SHOP DRAWING WILL
THRUST BLOCK FIRE DAMPER
BOP BOTTOM OF PIPE FOLLOW THE APPROVAL ON THE SEPARATE TRADES.
2. ALL DIMENSIONS ARE IN mm UNLESS NOTED OTHERWISE NOTED.
FFL FINISH FLOOR LEVEL
VOLUME DAMPER 3. THIS DRAWING SHALL BE READ IN CONJUNCTION WITH ALL RELATED ARCHITECTURAL,
LANDSCAPE, STRUCTURAL AND SERVICES DRAWINGS & SPECIFICATIONS.
4. ALL WORK SHALL BE CARRIED OUT IN ACCORDANCE WITH THE SPECIFICATIONS
SOUND ATTENUATOR 5. ALL MANHOLES, DRAW PITS AND ACCESS CHAMBERS SHALL BE CONSTRUCTED TO HAVE THE
CHAMBER COVER LEVEL FLUSH WITH THE SURROUNDING SITE TOPOGRAPHY
6. UNLESS OTHERWISE INDICATED, ALL DRAW PITS AND ACCESS CHAMBERS SHALL HAVE FRAME
AND COVER SUROUNDS CONSTRUCTED FROM 150mm PRE-CAST CONCRETE OR 150mm MORTAR
AIR HANDLING UNIT JOINTED DENSE CONCRETE BLOCKS, MINIMUM GRADE C20
7. FOR PITS USED TO ACCESS CABLED SERVICES, END DUCTS ARE TO BE IN LINE TO ALLOW
₂ ₂ CABLES TO BE PULLED STRAIGHT THROUGH WHERE REQUIRED. WHERE POSSIBLE DUCTS ARE
TO BE POSITIONED EQUIDISTANT FROM SIDE WALLS OR A MINIMUM OF 85mm DISTANT FROM THE
DUCT WALL OPENING INSIDE FACE OF SIDE WALLS
₂ ₂
8. THE FINAL DESIGN OF ANY THRUST BLOCKS REQUIRED FOR PIPED UTILITY SERVICES CARRYING

C 9.
FLUIDS IS TO BE DEFINED BY THE CONTRACTOR IN ACCORDANCE WITH THE LATERAL BEARING
CAPACITY OF SURROUNDING SUB-GRADE AT EACH RELEVANT LOCATION
THE ORIENTATION OF WASHOUT CHAMBERS SHOULD BE TO SUIT SITE CONDITIONS
C
10. WHERE REQUIRED THE CONTRACTOR SHALL INSTALL A DRAIN FROM HYDRANT CHAMBERS TO A
SOAKAWAY. SOAKAWAY SIZES TO BE DETERMINED BY ENGINEER ON SITE
11. DRAW PITS FOR DUCTED ELECTRICAL POWER AND TELECOMMUNICATIONS SERVICES TO BE
PROVIDED TO ASSIST CABLE PULLING WHERE LENGTHS OF DUCTING BETWEEN JUNCTIONS
EXCEED 200m IN LENGTH
12. UTILITIES INFRASTRUCTURE CONTAINMENT SERVING CRESCENTS, ANCILLARY BUILDINGS AND
GARDENS SHALL TERMINATE IN ACCESS PITS AND/OR BURIED ACCESS CHAMBERS IN THE
VICINITY OF THE APPROPRIATE PLANTROOMS. FINAL CONNECTIONS INTO INDIVIDUAL
PLANTROOMS FROM THE RELEVANT UTILITY TERMINATION PITS ARE SHOWN ON THE RELEVANT
MEP PLANTROOM DRAWINGS
13. FINAL CO-ORDINATION OF CONNECTIONS TO SECURITY BOLLARDS, CESSPOOLS, PUMPING
STATIONS, BULK WATER STORAGE TANKS, AND LPG GAS COMPOUNDS IS TO BE IN ACCORDANCE
WITH MANUFACTURER/SPECIALIST SUB-CONTRACTOR DETAILS
14. ALL MEP SERVICES SHOULD BE READ FROM (F.F.L) FINISH FLOOR LEVEL
15. MAXIMUM DISTANCES BETWEEN SUPPORTS IS 1500mm UNLESS OTHERWISE INDICATED.
16. PVC COATED RIGID STEEL CONDUIT/ CABLE TRAY AND FITTINGS (FOR OUTDOOR, WET AREAS
AND ROOMS).
D 17. INSTALL AN APPROPRIATE EXPANTION FITTING WHEREVER THE CONDUIT/ CABLE TRAY RUN
CRSSES AN EXPANSION JOINT. D

F
N KEYPLAN
2" 2"

4" 4"

Makka

F
869.20m

REFERENCE DRAWINGS

SSL +869.35

+TP 870.10
+TP 868.500
H
6" 6"
+TP 869.35

SECTION - A SECTION - B 02 09.12.23 ISSUED FOR APPROVAL ZHBG


Scale: 1:50 Scale: 1:50 01 30.10.23 ISSUED FOR APPROVAL ZHBG
00 07.09.23 ISSUED FOR APPROVAL ZHBG
REVISION
NO.
DATE PURPOSE & REMARKS ZHBG I
Trade ARCHITECTURE LANDSCAPE STRUCTURAL MECHANICAL ELECTRICAL
Date:
J Sign:

KINGDOM OF SAUDI ARABIA


PROJECT TITLE:

KING ABDULLAH INTERNATIONAL GARDENS


.\1A_03_02.jpg
J
STAGE 3

OWNER:
K
.\AL RIYADH MUNICIPALITY.jpg

MINISTRY OF MUNICIPAL AND RURAL AFFAIRS


AL RIYADH MUNICIPALITY .\55.png

DESIGNER: K
.\DSIGNER.jpg
L
CONSULTANT :

.\dar cad.jpg
MAIN CONTRACTOR: L
+TP 869.182
+TP 869.15

M .\ZDHBG.PNG M
+TP 868.000 +TP 868.000
∅160 HDPE IL: 868.450
DISCIPLINE:
ELECTROMECHANICAL
110∅ UPVC DRAWING TITLE :
IL: 867.730 CRESCENT 1 - CENOZOIC GARDEN
MEP COMPOSITE LAYOUT
SECTIONS
DRAWING NO:
N SECTION - C SECTION - D
KAIG3-SD-CG-G-MS-2001-02 N
Scale: 1:50 Scale: 1:50

Date: Drawn By: In Charge: Checked By:


09.12.23 SK SAN OB
Scale: 1:50 Size: A0

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Technical report

KSA

8.2. Appendix 02 – PROFIS Design reports

Keskin, Can Berk - 2/29/2024 - Canberk.keskin@hilti.com

The company receiving this design package is solely responsible for confirming, reviewing and approving the adequacy and accuracy of all
information contained herein; and for verifying that the proposed solution is suitable for the intended applications.
Case-1

Project: SA-13082-SF

Submitted by:

Hilti contact information


Contact name:
Contact e-mail:
Contact phone:
Contact company:

Customer contact information


Customer name:
Customer e-mail:
Customer phone:
Customer company:

Date: 28/02/2024

This submittal is auto-generated based on user-selected inputs.


Therefore, Hilti no representation as to the suitability of these systems for their intended use. 1 / 26
Version: 1.13.1

Solution: Case-1 Date: 28/02/2024

Table of content

1 Geometry and Application


1.1 Supports
1.2 Nodes
1.3 Members
1.4 Connections
1.5 Release Conditions
1.6 Media Interface Channel
1.7 Gliders
2 Part list
2.1 Members
2.2 Base Connectors
2.3 System Connectors
2.4 Other
3 Load Types
3.1 Loading objects
3.2 Point Loads
3.3 Distributed loads
3.4 Area loads
4 Load Combinations
4.1 Ultimate Limit State
4.2 Serviceability Limit State
5 Results
5.1 Calculation summary
5.2 Members
5.3 System Connectors
5.4 Base Connectors
6 Remarks, Your Cooperation Duties

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 2 / 26
Version: 1.13.1

Solution: Case-1 Date: 28/02/2024

1 Geometry and Application

Support Details
Modular Support Spacing [mm] Undefined

Intermediate Supports required?

Pipe Fasteners with Glider and Presetting used? (See


subchapter 'Gliders' in chapter 'Geometry and
Application')

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 3 / 26
Version: 1.13.1

Solution: Case-1 Date: 28/02/2024

1.1 Supports - Concrete

Concrete

Thickness Drilling Depth


Node No. No. Orientation Concrete grade
[mm] [mm]
1 1 Horizontal C20/25 200.00 150
4 2 Horizontal C20/25 200.00 150
6 3 Horizontal C20/25 200.00 150
8 4 Horizontal C20/25 200.00 150

1.2 Nodes

X Y Z
No. No. Connector name Connector variant
[mm] [mm] [mm]
1 1 -215.00 0.00 -500.00 MT-B-O2 MT-B-O2 (C)
2 - -215.00 0.00 -72.25 MT-C-LL1 MT-C-LL1 (C)
3 - 733.50 0.00 -72.25 MT-C-LL1 MT-C-LL1 (C)
4 2 733.50 0.00 -500.00 MT-B-O2 MT-B-O2 (C)
5 - 733.50 0.00 -235.46 MT-AB-LL2 45 MT-AB-LL2 45 (E)
6 3 733.50 264.54 -500.00 MT-AB A MT-AB A (C)
7 - -215.00 0.00 -235.46 MT-AB-LL2 45 MT-AB-LL2 45 (E)
8 4 -215.00 264.54 -500.00 MT-AB A MT-AB A (C)

1.3 Members

Member Releases Rotation


No. Node start Node end Member Name
Start End [°]
1 1 2 - 1 MT-40 180.00
2 2 3 1 2 MT-40 0.00
3 3 4 2 - MT-40 180.00
4 5 6 3 4 MT-40 0.00
5 7 8 5 6 MT-40 0.00

1.4 Connections

Cross- Cross- Cross- Cross-


Section/Rotation Section/Rotation Section/Rotation Section/Rotation
Node No. Description Variant
Arm1 Arm2 Arm3 Arm4
[-/°] [-/°] [-/°] [-/°]
1 MT-B-O2 MT-B-O2 (C) MT-40/180 - - -
2 MT-C-LL1 MT-C-LL1 (C) MT-40/180 MT-40/0 - -
3 MT-C-LL1 MT-C-LL1 (C) MT-40/0 MT-40/180 - -
4 MT-B-O2 MT-B-O2 (C) MT-40/180 - - -
5 MT-AB-LL2 45 MT-AB-LL2 45 (E) MT-40/180 MT-40/0 - -
6 MT-AB A MT-AB A (C) MT-40/0 - - -
7 MT-AB-LL2 45 MT-AB-LL2 45 (E) MT-40/180 MT-40/0 - -
8 MT-AB A MT-AB A (C) MT-40/0 - - -

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 4 / 26
Version: 1.13.1

Solution: Case-1 Date: 28/02/2024

1.5 Release Conditions

Spring Constants
Releases
Member Translational Rotational
No. Cu,x Cu,y Cu,z Cφx Cφy Cφz
Ux Uy Uz φx φy φz
[kN/m] [kN/m] [kN/m] [kNm/Rad] [kNm/Rad] [kNm/Rad]
2 no no no no yes yes - - - - 0.001 0.001
2 no no no no yes yes - - - - 0.001 0.001
4 no no no no yes yes - - - - 0.000 0.000
4 no no no no yes yes - - - - 0.000 0.000
5 no no no no yes yes - - - - 0.000 0.000
5 no no no no yes yes - - - - 0.000 0.000

1.6 Media Interface Channel

Start Position Length


No. Member No. Media Interface Z-Position Y-Position
[mm] [mm]

1.7 Gliders

Position Start Travel


No. Member No. Glider Custom Load
[mm] [mm] [mm]

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 5 / 26
Version: 1.13.1

Solution: Case-1 Date: 28/02/2024

2 Part list

2.1 Members

Quantity Weight Length


Position Item Number Description Cutting type
[-] [kg] [mm]
1 2268506 I.-Channel MT-40 2 2.05 501.90 N - None
2 2268506 I.-Channel MT-40 1 1.85 906.00 N - None
3 2268506 I.-Channel MT-40 1 0.66 324.09 N - None
4 2268506 I.-Channel MT-40 1 0.66 323.63 N - None

2.2 Base Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
5 2272094 2-hole Baseplate MT-B-O2 2 2.05
11 2346395 Angle brace MT-AB A set adjustable 2 0.88

2.3 System Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
9 2272047 Angle connector MT-C-LL1 2 0.67
10 2272115 Angle brace MT-AB-LL2 45 2 1.11

2.4 Other

Quantity Weight
Position Item Number Description
[-] [kg]
6 2273254 Hexagon bolt MT-TLB 16 0.40
7 2272080 Twist-Lock MT-TL M10 16 0.56
8 2105719 Stud anchor HST3 M12x115 40/20 8 0.80

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 6 / 26
Version: 1.13.1

Solution: Case-1 Date: 28/02/2024

3 Load Types

3. Loads

Custom loads

Load No. Load Distribution Load Case Load Type Comments


1 Point load LC 7: Design Permanent -
2 Point load LC 7: Design Permanent -
3 Point load LC 8: Wind (+x) Variable -
4 Point load LC 9: Wind (-x) Variable -
5 Point load LC 13: Seismic (+x) Seismic -
6 Point load LC 14: Seismic (-x) Seismic -
7 Point load LC 14: Seismic (-x) Seismic -
8 Point load LC 13: Seismic (+x) Seismic -
9 Point load LC 2: Pipe Permanent -
10 Point load LC 2: Pipe Permanent -
11 Point load LC 2: Pipe Permanent -
12 Point load LC 2: Pipe Permanent -

3.2 Point Loads

Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
1 Design 2 275.00 0.00 0.00 -1.79 0.00 0.00 0.00
2 Design 2 673.50 0.00 0.00 -1.79 0.00 0.00 0.00
3 Wind (+x) 2 474.25 0.53 -0.00 -0.00 -0.00 -0.00 -0.00
4 Wind (-x) 2 474.25 -0.53 -0.00 -0.00 -0.00 -0.00 -0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 7 / 26
Version: 1.13.1

Solution: Case-1 Date: 28/02/2024


Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
5 Seismic (+x) 2 275.00 0.02 -0.00 -0.00 -0.00 -0.00 -0.00
6 Seismic (-x) 2 275.00 -0.02 -0.00 -0.00 -0.00 -0.00 -0.00
7 Seismic (-x) 2 673.50 0.02 -0.00 -0.00 -0.00 -0.00 -0.00
8 Seismic (+x) 2 673.50 -0.02 -0.00 -0.00 -0.00 -0.00 -0.00
9 Pipe 2 673.50 0.00 0.18 0.00 0.00 0.00 0.00
10 Pipe 2 275.00 0.00 0.18 0.00 0.00 0.00 0.00
11 Pipe 2 275.00 0.18 0.00 0.00 0.00 0.00 0.00
12 Pipe 2 673.50 0.18 0.00 0.00 0.00 0.00 0.00
13 Self Weight Support 1 0.00 0.00 0.00 -0.01 0.00 0.00 0.00
14 Self Weight Support 1 427.75 0.00 0.00 -0.00 0.00 0.00 0.00
15 Self Weight Support 2 948.50 0.00 0.00 -0.00 0.00 0.00 0.00
16 Self Weight Support 3 427.75 0.00 0.00 -0.01 0.00 0.00 0.00
17 Self Weight Support 3 163.21 0.00 0.00 -0.01 0.00 0.00 0.00
18 Self Weight Support 4 374.12 0.00 0.00 -0.00 0.00 0.00 0.00
19 Self Weight Support 1 264.54 0.00 0.00 -0.01 0.00 0.00 0.00
20 Self Weight Support 5 374.12 0.00 0.00 -0.00 0.00 0.00 0.00

3.3 Distributed loads

Start End
Fx Fy Fz Mx My Mz
Load No. Load Type Members Position Position
[kN/m] [kN/m] [kN/m] [kNm/m] [kNm/m] [kNm/m]
[mm] [mm]
21 Self Weight Support 1 0.00 427.75 0.00 0.00 -0.02 0.00 0.00 0.00
22 Self Weight Support 2 0.00 948.50 0.00 0.00 -0.02 0.00 0.00 0.00
23 Self Weight Support 3 0.00 427.75 0.00 0.00 -0.02 0.00 0.00 0.00
24 Self Weight Support 4 0.00 374.12 0.00 0.00 -0.02 0.00 0.00 0.00
25 Self Weight Support 5 0.00 374.12 0.00 0.00 -0.02 0.00 0.00 0.00

3.4 Area loads

3.4.1 User input

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 8 / 26
Version: 1.13.1

Solution: Case-1 Date: 28/02/2024

4 Load Combinations

Design base EN 1993

Load combination design base EN 1990

4.1 Ultimate Limit State

Design base Load combination and safety factors


ULS - 001a-ULS: SW_inf (Support Only) 1.00 * LC1
ULS - 001b-ULS: SW_sup (Support Only) 1.35 * LC1
ULS - 002a-ULS: SW_inf Support + Media 1.00 * LC1 + 1.00 * LC2
ULS - 002b-ULS: SW_sup Support + Media 1.35 * LC1 + 1.35 * LC2
ULS - 004a-ULS: SW_inf + Design Loads 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC7
ULS - 004b-ULS: SW_sup + Design Loads 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
ULS - 006a-ULS: SW_inf + Wind (+x) 1.00 * LC1 + 1.00 * LC2 + 1.50 * LC8
ULS - 006b-ULS: SW_sup + Wind (+x) 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8
ULS - 007a-ULS: SW_inf + Wind (-x) 1.00 * LC1 + 1.00 * LC2 + 1.50 * LC9
ULS - 007b-ULS: SW_sup + Wind (-x) 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC9
ULS - 015a-ULS: SW_inf + Live + Snow + Wind (+x) 1.00 * LC1 + 1.00 * LC2 + 1.50 * 0.60 * LC8
ULS - 015b-ULS: SW_sup + Live + Snow + Wind (+x) 1.35 * LC1 + 1.35 * LC2 + 1.50 * 0.60 * LC8
ULS - 016a-ULS: SW_inf + Live + Snow + Wind (-x) 1.00 * LC1 + 1.00 * LC2 + 1.50 * 0.60 * LC9
ULS - 016b-ULS: SW_sup + Live + Snow + Wind (-x) 1.35 * LC1 + 1.35 * LC2 + 1.50 * 0.60 * LC9
ULS - 027a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC13
z) + Live + Snow
ULS - 027b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC14
+ Live + Snow
ULS - 029a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC13
z) + Live + Snow
ULS - 030a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC14
+ Live + Snow
ULS - 027a-ULS_Base : SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 027b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 029a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 030a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 031a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC13 + 1.00 * 0.74 * LC7
z) + Design
ULS - 031b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC14 + 1.00 * 0.74 * LC7
+ Design
ULS - 033a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC13 + 1.00 * 0.74 * LC7
z) + Design
ULS - 034a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC14 + 1.00 * 0.74 * LC7
+ Design
ULS - 032a-ULS_Base: SW + Seismic (+x) + Seismic (-y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC13 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 031b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC14 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 033a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC13 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 034a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC14 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 037-ULS: SW_inf + Impact + Live + Snow 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.20 * LC8
ULS - 038-ULS: SW_inf + Impact + Live + Snow 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.20 * LC9

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 9 / 26
Version: 1.13.1

Solution: Case-1 Date: 28/02/2024

4.2 Serviceability Limit State

Load Case Load combination and safety factors


SLS - 001-SLS: SW (Support Only) 1.00 * LC1
SLS - 002-SLS: SW Support + Media Objects 1.00 * LC1 + 1.00 * LC2
SLS - 004-SLS: SW + Design Loads 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7
SLS - 006-SLS: SW + Wind (+x) 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC8
SLS - 007-SLS: SW + Wind (-x) 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC9
SLS - 015-SLS: SW + Live + Snow + Wind (+x) 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC8
SLS - 016-SLS: SW + Live + Snow + Wind (-x) 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC9

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 10 / 26
Version: 1.13.1

Solution: Case-1 Date: 28/02/2024

5 Results

5.1 Calculation summary

5.1.3 Members

Governing load ULS SLS


No Member Status
combination number* [%] [%]
1 MT-40 006b-ULS 37.56 - OK
2 MT-40 004-SLS 84.70 61.10 OK
3 MT-40 006b-ULS 39.84 - OK
4 MT-40 004b-ULS 2.20 - OK
5 MT-40 004b-ULS 2.20 - OK

5.1.2 Base Connectors

Governing load ULS SLS


No Base connector Status
combination number* [%] [%]
1 MT-B-O2 006b-ULS 67.84 - OK
4 MT-B-O2 006b-ULS 67.84 - OK
6 MT-AB A 001b-ULS 7.00 - OK
8 MT-AB A 001b-ULS 7.00 - OK

5.1.3 System Connectors

Governing load ULS SLS


No Connector Status
combination number* [%] [%]
2 MT-C-LL1 004b-ULS 44.89 - OK
3 MT-C-LL1 004b-ULS 44.93 - OK
5 MT-AB-LL2 45 004b-ULS 6.03 - OK
7 MT-AB-LL2 45 004b-ULS 6.03 - OK
*006b-ULS: SW_sup + Wind (+x) . Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8
*004-SLS: SW + Design Loads . Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7
*004b-ULS: SW_sup + Design Loads . Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
*001b-ULS: SW_sup (Support Only) . Respective Combination Equation: 1.35 * LC1

Overall Status: Calculation OK, design criteria met!

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 11 / 26
Version: 1.13.1

Solution: Case-1 Date: 28/02/2024

5.2 Members

5.2.1 Member Properties


5.2.1.1 MT-40 Members: 1, 2, 3, 4, 5
5.2.1.1.1 Section properties
t A Iy Iz It
[mm] [mm²] [mm⁴] [mm⁴] [mm⁴]
2.00 285.00 57717.48 65876.44 259.85

Iω M Wy Wz Wy
[mm⁶] [kg/m] [mm³] [mm³] [mm³]
38410000.00 4.08 -2652.65 -3099.95 -2652.65

5.2.1.1.2 Material properties


E G Fu Fy Fy.cold
Steel grade
[N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²]
Steel S 280 GD 210000.00 80769.00 360.00 280.00 305.00

5.2.2 Member Design

5.2.2.1 Overview

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 12 / 26
Version: 1.13.1

Solution: Case-1 Date: 28/02/2024

5.2.2.2 Stress Analysis

5.2.2.2.1 Table of Results

Load Combination σ τ σeqv σlimit τlimit Utilization


No. Member
number* [N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²] [%]
1 I.-Channel MT-40 006b-ULS -102.04 -10.53 102.18 277.27 160.08 36.85
2 I.-Channel MT-40 004b-ULS -205.16 18.60 205.46 277.27 160.08 74.10
3 I.-Channel MT-40 006b-ULS 105.38 10.53 105.52 277.27 160.08 38.06
4 I.-Channel MT-40 006b-ULS 0.00 0.97 3.21 0.00 160.08 1.16
5 I.-Channel MT-40 006b-ULS 0.00 0.96 3.20 0.00 160.08 1.16

*006b-ULS: SW_sup + Wind (+x). Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8

*004b-ULS: SW_sup + Design Loads. Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7

5.2.2.2 Governing Member Loading

Beam No. 1

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40 0.00 006b-ULS 0.36 0.16 0.64 0.00 -0.27 0.00
MT-40 85.55 006b-ULS 0.36 0.16 0.64 0.00 -0.22 -0.01
MT-40 171.10 006b-ULS 0.36 0.16 0.64 0.00 -0.16 -0.03
MT-40 256.65 006b-ULS 0.36 0.16 0.64 0.00 -0.11 -0.04
MT-40 264.54(-) 006b-ULS 0.36 0.16 0.64 0.00 -0.10 -0.04
MT-40 264.54(+) 006b-ULS -0.02 -0.24 0.64 0.00 -0.10 -0.04
MT-40 342.20 006b-ULS -0.02 -0.24 0.64 0.00 -0.05 -0.02
MT-40 427.75 006b-ULS -0.02 -0.24 0.64 0.00 0.00 0.00

Beam No. 2

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40 0.00 004b-ULS 0.24 0.24 -1.80 0.00 0.00 0.00
MT-40 189.70 004b-ULS 0.24 0.24 -1.80 0.00 -0.34 -0.05
MT-40 275.00(-) 004b-ULS 0.24 0.24 -1.80 0.00 -0.49 -0.07
MT-40 275.00(+) 004b-ULS -0.00 -0.00 -0.01 0.00 -0.49 -0.07
MT-40 379.40 004b-ULS -0.00 -0.00 -0.00 0.00 -0.50 -0.07
MT-40 569.10 004b-ULS -0.00 -0.00 0.00 0.00 -0.50 -0.07
MT-40 673.50(-) 004b-ULS -0.00 -0.00 0.01 0.00 -0.49 -0.07
MT-40 673.50(+) 004b-ULS -0.24 -0.24 1.80 0.00 -0.49 -0.07
MT-40 758.80 004b-ULS -0.24 -0.24 1.80 0.00 -0.34 -0.05
MT-40 948.50 004b-ULS -0.24 -0.24 1.80 0.00 0.00 0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 13 / 26
Version: 1.13.1

Solution: Case-1 Date: 28/02/2024

Beam No. 3

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40 0.00 006b-ULS -0.02 0.24 0.64 -0.00 -0.00 -0.00
MT-40 85.55 006b-ULS -0.02 0.24 0.64 -0.00 0.05 -0.02
MT-40 163.21(-) 006b-ULS -0.02 0.24 0.64 -0.00 0.10 -0.04
MT-40 163.21(+) 006b-ULS 0.36 -0.16 0.64 0.00 0.10 -0.04
MT-40 171.10 006b-ULS 0.36 -0.16 0.64 0.00 0.11 -0.04
MT-40 256.65 006b-ULS 0.36 -0.16 0.64 0.00 0.16 -0.03
MT-40 342.20 006b-ULS 0.36 -0.16 0.64 0.00 0.22 -0.01
MT-40 427.75 006b-ULS 0.36 -0.16 0.64 0.00 0.27 0.00

Beam No. 4

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40 0.00 004b-ULS -0.59 0.00 -0.00 -0.00 0.00 -0.00
MT-40 74.82 004b-ULS -0.59 0.00 -0.00 -0.00 -0.00 -0.00
MT-40 149.65 004b-ULS -0.59 0.00 -0.00 -0.00 -0.00 -0.00
MT-40 224.47 004b-ULS -0.59 0.00 0.00 -0.00 -0.00 -0.00
MT-40 299.29 004b-ULS -0.59 0.00 0.00 -0.00 -0.00 -0.00
MT-40 374.12 004b-ULS -0.59 0.00 0.00 -0.00 -0.00 -0.00

Beam No. 5

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40 0.00 004b-ULS -0.59 0.00 -0.00 -0.00 0.00 -0.00
MT-40 74.82 004b-ULS -0.59 0.00 -0.00 -0.00 -0.00 -0.00
MT-40 149.65 004b-ULS -0.59 0.00 -0.00 -0.00 -0.00 -0.00
MT-40 224.47 004b-ULS -0.59 0.00 0.00 -0.00 -0.00 -0.00
MT-40 299.29 004b-ULS -0.59 0.00 0.00 -0.00 -0.00 -0.00
MT-40 374.12 004b-ULS -0.59 0.00 0.00 -0.00 -0.00 -0.00

*006b-ULS: SW_sup + Wind (+x). Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8

*004b-ULS: SW_sup + Design Loads. Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 14 / 26
Version: 1.13.1

Solution: Case-1 Date: 28/02/2024

Normal load

Shear load in Y direction

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 15 / 26
Version: 1.13.1

Solution: Case-1 Date: 28/02/2024

Shear load in Z direction

Torsion around X

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 16 / 26
Version: 1.13.1

Solution: Case-1 Date: 28/02/2024

Moment around Y

Moment around Z

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 17 / 26
Version: 1.13.1

Solution: Case-1 Date: 28/02/2024

5.2.3 Stability Analysis

Buckling ratio

Buckling Max. lateral torsional Max. buckling under Max.


Member Length
Length Buckling ratio buckling under bending compression interaction
No. [mm]
[mm] [%] [%] [%]
1 427.75 855.50 2.00 37.56 0.00 37.56
2 948.50 948.50 1.00 77.83 1.18 84.70
3 427.75 855.50 2.00 39.84 0.00 39.84
4 374.12 748.23 2.00 0.00 2.20 2.20
5 374.12 748.23 2.00 0.00 2.20 2.20

5.2.4 Deflection Analysis

Criteria
☑Maximum Allowable Deflection (Beam) L/200
☑Maximum Allowable Deflection (Cantilever)L/150
- Maximum Deflection (Absolute) -
☑No Deflection checks calculated for 1.50mm

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 18 / 26
Version: 1.13.1

Solution: Case-1 Date: 28/02/2024

Overview

Results
Reference
Member Max deflection Utilization
Load Combination number* Governing criteria Length Limit
No. [mm] [%]
[mm]
1 016-SLS Relative (Beam) 427.75 L/200 -0.08 0.00
2 004-SLS Relative (Beam) 948.50 L/200 -2.90 61.10
3 016-SLS Relative (Beam) 427.75 L/200 0.00 0.00
4 016-SLS Relative (Beam) 374.12 L/200 0.00 0.00
5 016-SLS Relative (Beam) 374.12 L/200 0.00 0.00

*016-SLS: SW + Live + Snow + Wind (-x). Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC9

*004-SLS: SW + Design Loads. Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 19 / 26
Version: 1.13.1

Solution: Case-1 Date: 28/02/2024

Deflection 1.00 * LC1

Deflection 1.00 * LC1 + 1.00 * LC2

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 20 / 26
Version: 1.13.1

Solution: Case-1 Date: 28/02/2024

Deflection 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7

Deflection 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC8

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 21 / 26
Version: 1.13.1

Solution: Case-1 Date: 28/02/2024

Deflection 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC9

Deflection 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC8

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 22 / 26
Version: 1.13.1

Solution: Case-1 Date: 28/02/2024

Deflection 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC9

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 23 / 26
Version: 1.13.1

Solution: Case-1 Date: 28/02/2024

5.3 System Connectors

5.3 Connectors

5.3.1 Overview

Connector: MT-C-LL1
Fx Fy Fz Mx My Mz
Connector variant: MT-C-LL1 (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 3
Local Forces: -0.24 -0.24 -1.80 0.00 0.00 -0.00
Resistance: 8.20 1.24 8.06 0.03 0.19 0.03
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 44.93 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
Combination
Connector: MT-AB-LL2 45
Fx Fy Fz Mx My Mz
Connector variant: MT-AB-LL2 45 (E)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 5
Local Forces: -0.59 0.00 -0.00 -0.00 0.00 0.00
Resistance: 9.72 0.10 0.10 0.10 0.00 0.00
abs(Fx.ed/Fx.rd);abs(Fy.ed/Fy.rd);abs(Fz.ed/Fz.rd);abs(Mx.ed/Mx.rd);abs(My
Equation:
.ed/My.rd);abs(Mz.ed/Mz.rd)
Utilization: 6.03 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 24 / 26
Version: 1.13.1

Solution: Case-1 Date: 28/02/2024

5.4 Base Connectors

5.4 Bases

5.4.1 Overview

Base connector: MT-B-O2


Fx Fy Fz Mx My Mz
Connector variant: MT-B-O2 (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 1
Local Forces: 0.34 0.16 0.64 0.00 -0.27 0.00
Resistance: 12.60 2.43 7.34 0.06 0.55 0.23
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 67.84 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8
Combination
Base connector: MT-AB A
Fx Fy Fz Mx My Mz
Connector variant: MT-AB A (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 6
Local Forces: -0.57 0.00 0.01 -0.00 0.00 0.00
Resistance: 13.86 0.10 0.10 0.10 0.00 0.00
abs(Fx.ed/Fx.rd);abs(Fy.ed/Fy.rd);abs(Fz.ed/Fz.rd);abs(Mx.ed/Mx.rd);abs(My
Equation:
.ed/My.rd);abs(Mz.ed/Mz.rd)
Utilization: 7.00 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.50 * 0.60 * LC9
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 25 / 26
Version: 1.13.1

Solution: Case-1 Date: 28/02/2024

6 Remarks, Your Cooperation Duties

Any and all information and data contained in the Software concern solely the use of Hilti products and based on the principles, formulas and security
regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly complied with by
the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the relevant Hilti product.
The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole
responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole responsibility for
having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior
to using them for your specific facility. The Software servers only as an aid to interpret norms and permits without any guarantee as to the absence of
errors, the correctness and relevance ot the results or suitability for a specific application.

You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular
backup of programs and, if applicable, carry out the updates of that you are using the current and thus up-to-date version of the Software in each case
by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or
programs, arising from a culpable breach of duty by you.

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 26 / 26
Case-2

Project: SA-13082-SF

Submitted by:

Hilti contact information


Contact name:
Contact e-mail:
Contact phone:
Contact company:

Customer contact information


Customer name:
Customer e-mail:
Customer phone:
Customer company:

Date: 28/02/2024

This submittal is auto-generated based on user-selected inputs.


Therefore, Hilti no representation as to the suitability of these systems for their intended use. 1 / 26
Version: 1.13.1

Solution: Case-2 Date: 28/02/2024

Table of content

1 Geometry and Application


1.1 Supports
1.2 Nodes
1.3 Members
1.4 Connections
1.5 Release Conditions
1.6 Media Interface Channel
1.7 Gliders
2 Part list
2.1 Members
2.2 Base Connectors
2.3 System Connectors
2.4 Other
3 Load Types
3.1 Loading objects
3.2 Point Loads
3.3 Distributed loads
3.4 Area loads
4 Load Combinations
4.1 Ultimate Limit State
4.2 Serviceability Limit State
5 Results
5.1 Calculation summary
5.2 Members
5.3 System Connectors
5.4 Base Connectors
6 Remarks, Your Cooperation Duties

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 2 / 26
Version: 1.13.1

Solution: Case-2 Date: 28/02/2024

1 Geometry and Application

Support Details
Modular Support Spacing [mm] Undefined

Intermediate Supports required?

Pipe Fasteners with Glider and Presetting used? (See


subchapter 'Gliders' in chapter 'Geometry and
Application')

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 3 / 26
Version: 1.13.1

Solution: Case-2 Date: 28/02/2024

1.1 Supports - Concrete

Concrete

Thickness Drilling Depth


Node No. No. Orientation Concrete grade
[mm] [mm]
3 1 Horizontal C20/25 200.00 150
4 2 Horizontal C20/25 200.00 150

1.2 Nodes

X Y Z
No. No. Connector name Connector variant
[mm] [mm] [mm]
1 - -190.75 0.00 5482.95 MT-C-GS A OC MT-C-GS A OC (C_D_CS)
2 - 709.25 0.00 5482.95 MT-C-GS A OC MT-C-GS A OC (C_D_CS)
3 1 -190.75 0.00 -500.00 MT-B-GL O4C OC MT-B-GL O4C OC (C)
4 2 709.25 0.00 -500.00 MT-B-GL O4C OC MT-B-GL O4C OC (C)
5 - -190.75 0.00 5122.95 MT-C-GS A OC MT-C-GS A OC (C_D_CS)
6 - 709.25 0.00 5122.95 MT-C-GS A OC MT-C-GS A OC (C_D_CS)

1.3 Members

Member Releases Rotation


No. Node start Node end Member Name
Start End [°]
1 1 2 - - MT-70 90.00
2 1 3 - - MT-90 90.00
3 2 4 - - MT-90 90.00
4 5 6 - - MT-70 90.00

1.4 Connections

Cross- Cross- Cross- Cross-


Section/Rotation Section/Rotation Section/Rotation Section/Rotation
Node No. Description Variant
Arm1 Arm2 Arm3 Arm4
[-/°] [-/°] [-/°] [-/°]
MT-C-GS A OC
1 MT-C-GS A OC MT-70/90 MT-90/90 - -
(C_D_CS)
MT-C-GS A OC
2 MT-C-GS A OC MT-70/90 MT-90/90 - -
(C_D_CS)
3 MT-B-GL O4C OC MT-B-GL O4C OC (C) MT-90/90 - - -
4 MT-B-GL O4C OC MT-B-GL O4C OC (C) MT-90/90 - - -
MT-C-GS A OC
5 MT-C-GS A OC MT-90/90 MT-70/90 - -
(C_D_CS)
MT-C-GS A OC
6 MT-C-GS A OC MT-90/90 MT-70/90 - -
(C_D_CS)

1.5 Release Conditions

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 4 / 26
Version: 1.13.1

Solution: Case-2 Date: 28/02/2024


Spring Constants
Releases
Member Translational Rotational
No. Cu,x Cu,y Cu,z Cφx Cφy Cφz
Ux Uy Uz φx φy φz
[kN/m] [kN/m] [kN/m] [kNm/Rad] [kNm/Rad] [kNm/Rad]

1.6 Media Interface Channel

Start Position Length


No. Member No. Media Interface Z-Position Y-Position
[mm] [mm]

1.7 Gliders

Position Start Travel


No. Member No. Glider Custom Load
[mm] [mm] [mm]

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 5 / 26
Version: 1.13.1

Solution: Case-2 Date: 28/02/2024

2 Part list

2.1 Members

Quantity Weight Length


Position Item Number Description Cutting type
[-] [kg] [mm]
1 2268365 I.-Girder MT-70 OC 2 6.25 800.00 N - None
2 2268369 I.-Girder MT-90 OC 2 109.80 6118.45 N - None

2.2 Base Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
5 2343282 Baseplate MT-B-GL O4C OC 2 13.04

2.3 System Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
3 2272068 Angle connector MT-C-GS A OC adjustable 8 3.12

2.4 Other

Quantity Weight
Position Item Number Description
[-] [kg]
4 2272084 Thread forming bolt MT-TFB OC 44 1.25
6 2105870 Stud anchor HST3-R M12x115 40/20 8 0.81

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 6 / 26
Version: 1.13.1

Solution: Case-2 Date: 28/02/2024

3 Load Types

3. Loads

Custom loads

Load No. Load Distribution Load Case Load Type Comments


1 Point load LC 7: Design Permanent -
2 Point load LC 7: Design Permanent -
3 Point load LC 13: Seismic (+x) Seismic -
4 Point load LC 14: Seismic (-x) Seismic -
5 Point load LC 13: Seismic (+x) Seismic -
6 Point load LC 14: Seismic (-x) Seismic -
7 Point load LC 2: Pipe Permanent -
8 Point load LC 2: Pipe Permanent -
9 Point load LC 8: Wind (+x) Variable -
10 Point load LC 9: Wind (-x) Variable -
11 Point load LC 7: Design Permanent -
12 Point load LC 7: Design Permanent -
13 Point load LC 8: Wind (+x) Variable -
14 Point load LC 9: Wind (-x) Variable -

3.2 Point Loads

Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
1 Design 4 250.00 0.00 0.00 -1.79 0.00 0.00 0.00
2 Design 4 650.00 0.00 0.00 -1.79 0.00 0.00 0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 7 / 26
Version: 1.13.1

Solution: Case-2 Date: 28/02/2024


Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
3 Seismic (+x) 4 250.00 0.02 0.00 0.00 0.00 0.00 0.00
4 Seismic (-x) 4 250.00 -0.02 -0.00 -0.00 -0.00 -0.00 -0.00
5 Seismic (+x) 4 650.00 0.02 0.00 0.00 0.00 0.00 0.00
6 Seismic (-x) 4 650.00 -0.02 -0.00 -0.00 -0.00 -0.00 -0.00
9 Pipe 4 250.00 0.18 0.18 0.00 0.00 0.00 0.00
10 Pipe 4 650.00 0.18 0.18 0.00 0.00 0.00 0.00
11 Wind (+x) 4 450.00 0.53 0.00 0.00 0.00 0.00 0.00
12 Wind (-x) 4 450.00 -0.53 -0.00 -0.00 -0.00 -0.00 -0.00
13 Design 1 250.00 0.00 0.00 -0.11 0.00 0.00 0.00
14 Design 1 650.00 0.00 0.00 -0.11 0.00 0.00 0.00
15 Wind (+x) 1 450.00 0.17 0.00 0.00 0.00 0.00 0.00
16 Wind (-x) 1 450.00 -0.17 -0.00 -0.00 -0.00 -0.00 -0.00
17 Self Weight Support 1 0.00 0.00 0.00 -0.01 0.00 0.00 0.00
18 Self Weight Support 1 900.00 0.00 0.00 -0.01 0.00 0.00 0.00
19 Self Weight Support 2 5982.95 0.00 0.00 -0.07 0.00 0.00 0.00
20 Self Weight Support 3 5982.95 0.00 0.00 -0.07 0.00 0.00 0.00
21 Self Weight Support 2 360.00 0.00 0.00 -0.01 0.00 0.00 0.00
22 Self Weight Support 3 360.00 0.00 0.00 -0.01 0.00 0.00 0.00

3.3 Distributed loads

Start End
Fx Fy Fz Mx My Mz
Load No. Load Type Members Position Position
[kN/m] [kN/m] [kN/m] [kNm/m] [kNm/m] [kNm/m]
[mm] [mm]
23 Self Weight Support 1 0.00 900.00 0.00 0.00 -0.04 0.00 0.00 0.00
24 Self Weight Support 2 0.00 5982.95 0.00 0.00 -0.09 0.00 0.00 0.00
25 Self Weight Support 3 0.00 5982.95 0.00 0.00 -0.09 0.00 0.00 0.00
26 Self Weight Support 4 0.00 900.00 0.00 0.00 -0.04 0.00 0.00 0.00

3.4 Area loads

3.4.1 User input

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 8 / 26
Version: 1.13.1

Solution: Case-2 Date: 28/02/2024

4 Load Combinations

Design base EN 1993

Load combination design base EN 1990

4.1 Ultimate Limit State

Design base Load combination and safety factors


ULS - 001a-ULS: SW_inf (Support Only) 1.00 * LC1
ULS - 001b-ULS: SW_sup (Support Only) 1.35 * LC1
ULS - 002a-ULS: SW_inf Support + Media 1.00 * LC1 + 1.00 * LC2
ULS - 002b-ULS: SW_sup Support + Media 1.35 * LC1 + 1.35 * LC2
ULS - 004a-ULS: SW_inf + Design Loads 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC7
ULS - 004b-ULS: SW_sup + Design Loads 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
ULS - 006a-ULS: SW_inf + Wind (+x) 1.00 * LC1 + 1.00 * LC2 + 1.50 * LC8
ULS - 006b-ULS: SW_sup + Wind (+x) 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8
ULS - 007a-ULS: SW_inf + Wind (-x) 1.00 * LC1 + 1.00 * LC2 + 1.50 * LC9
ULS - 007b-ULS: SW_sup + Wind (-x) 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC9
ULS - 015a-ULS: SW_inf + Live + Snow + Wind (+x) 1.00 * LC1 + 1.00 * LC2 + 1.50 * 0.60 * LC8
ULS - 015b-ULS: SW_sup + Live + Snow + Wind (+x) 1.35 * LC1 + 1.35 * LC2 + 1.50 * 0.60 * LC8
ULS - 016a-ULS: SW_inf + Live + Snow + Wind (-x) 1.00 * LC1 + 1.00 * LC2 + 1.50 * 0.60 * LC9
ULS - 016b-ULS: SW_sup + Live + Snow + Wind (-x) 1.35 * LC1 + 1.35 * LC2 + 1.50 * 0.60 * LC9
ULS - 027a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC13
z) + Live + Snow
ULS - 027b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC14
+ Live + Snow
ULS - 029a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC13
z) + Live + Snow
ULS - 030a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC14
+ Live + Snow
ULS - 027a-ULS_Base : SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 027b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 029a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 030a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 031a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC13 + 1.00 * 0.74 * LC7
z) + Design
ULS - 031b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC14 + 1.00 * 0.74 * LC7
+ Design
ULS - 033a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC13 + 1.00 * 0.74 * LC7
z) + Design
ULS - 034a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC14 + 1.00 * 0.74 * LC7
+ Design
ULS - 032a-ULS_Base: SW + Seismic (+x) + Seismic (-y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC13 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 031b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC14 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 033a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC13 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 034a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC14 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 037-ULS: SW_inf + Impact + Live + Snow 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.20 * LC8
ULS - 038-ULS: SW_inf + Impact + Live + Snow 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.20 * LC9

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 9 / 26
Version: 1.13.1

Solution: Case-2 Date: 28/02/2024

4.2 Serviceability Limit State

Load Case Load combination and safety factors


SLS - 001-SLS: SW (Support Only) 1.00 * LC1
SLS - 002-SLS: SW Support + Media Objects 1.00 * LC1 + 1.00 * LC2
SLS - 004-SLS: SW + Design Loads 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7
SLS - 006-SLS: SW + Wind (+x) 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC8
SLS - 007-SLS: SW + Wind (-x) 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC9
SLS - 015-SLS: SW + Live + Snow + Wind (+x) 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC8
SLS - 016-SLS: SW + Live + Snow + Wind (-x) 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC9

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 10 / 26
Version: 1.13.1

Solution: Case-2 Date: 28/02/2024

5 Results

5.1 Calculation summary

5.1.3 Members

Governing load ULS SLS


No Member Status
combination number* [%] [%]
2 MT-70 006b-ULS 43.27 - OK
13 MT-90 002-SLS 39.49 92.61 OK
15 MT-90 002-SLS 40.00 92.61 OK
16 MT-70 006b-ULS 54.04 - OK

5.1.2 Base Connectors

Governing load ULS SLS


No Base connector Status
combination number* [%] [%]
3 MT-B-GL O4C OC 006b-ULS 90.67 - OK
4 MT-B-GL O4C OC 006b-ULS 92.72 - OK

5.1.3 System Connectors

Governing load ULS SLS


No Connector Status
combination number* [%] [%]
1 MT-C-GS A OC 006b-ULS 47.43 - OK
2 MT-C-GS A OC 006b-ULS 47.70 - OK
5 MT-C-GS A OC 006b-ULS 64.27 - OK
6 MT-C-GS A OC 006b-ULS 63.26 - OK
*006b-ULS: SW_sup + Wind (+x) . Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8
*002-SLS: SW Support + Media Objects . Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2

Overall Status: Calculation OK, design criteria met!

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 11 / 26
Version: 1.13.1

Solution: Case-2 Date: 28/02/2024

5.2 Members

5.2.1 Member Properties


5.2.1.1 MT-70 Members: 1, 4
5.2.1.1.1 Section properties
t A Iy Iz It
[mm] [mm²] [mm⁴] [mm⁴] [mm⁴]
2.75 428.78 158700.00 158700.00 297500.00

Iω M Wy Wz Wy
[mm⁶] [kg/m] [mm³] [mm³] [mm³]
2039000.00 7.82 -6349.48 -6349.48 -6349.48

5.2.1.1.2 Material properties


E G Fu Fy Fy.cold
Steel grade
[N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²]
S350GD 1.0529 210000.00 80769.00 420.00 350.00 350.00

5.2.1.2 MT-90 Members: 2, 3


5.2.1.2.1 Section properties
t A Iy Iz It
[mm] [mm²] [mm⁴] [mm⁴] [mm⁴]
3.00 976.08 1508000.00 1508000.00 2047000.00

Iω M Wy Wz Wy
[mm⁶] [kg/m] [mm³] [mm³] [mm³]
15470000.00 17.95 -30169.60 -30169.60 -30169.60

5.2.1.2.2 Material properties


E G Fu Fy Fy.cold
Steel grade
[N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²]
S350GD 1.0529 210000.00 80769.00 420.00 350.00 350.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 12 / 26
Version: 1.13.1

Solution: Case-2 Date: 28/02/2024

5.2.2 Member Design

5.2.2.1 Overview

5.2.2.2 Stress Analysis

5.2.2.2.1 Table of Results

Load Combination σ τ σeqv σlimit τlimit Utilization


No. Member
number* [N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²] [%]
1 I.-Girder MT-70 OC 006b-ULS -137.46 12.41 137.69 318.18 183.70 43.27
2 I.-Girder MT-90 OC 006b-ULS 125.63 -2.66 125.64 318.18 183.70 39.49
3 I.-Girder MT-90 OC 006b-ULS -127.27 2.66 127.28 318.18 183.70 40.00
4 I.-Girder MT-70 OC 006b-ULS -171.74 0.00 171.95 318.18 0.00 54.04

*006b-ULS: SW_sup + Wind (+x). Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8

5.2.2.2 Governing Member Loading

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 13 / 26
Version: 1.13.1

Solution: Case-2 Date: 28/02/2024

Beam No. 1

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-70 0.00 006b-ULS 0.11 1.87 0.00 0.00 -0.02 0.85
MT-70 180.00 006b-ULS 0.11 1.88 0.00 0.00 -0.02 0.51
MT-70 360.00 006b-ULS 0.11 1.89 0.00 0.00 -0.02 0.17
MT-70 450.00(-) 006b-ULS 0.11 1.90 0.00 0.00 -0.02 0.00
MT-70 450.00(+) 006b-ULS -0.15 1.90 0.00 0.00 -0.02 0.00
MT-70 540.00 006b-ULS -0.15 1.90 0.00 0.00 -0.02 -0.17
MT-70 720.00 006b-ULS -0.15 1.91 0.00 0.00 -0.02 -0.51
MT-70 900.00 006b-ULS -0.15 1.92 0.00 0.00 -0.02 -0.86

Beam No. 2

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-90 0.00 006b-ULS 1.86 -0.11 0.00 -0.02 0.00 -0.85
MT-90 360.00(-) 006b-ULS 1.82 -0.11 0.00 -0.02 0.00 -0.81
MT-90 360.00(+) 006b-ULS 4.11 -0.77 0.24 0.01 0.00 -1.87
MT-90 1196.59 006b-ULS 4.03 -0.77 0.24 0.01 0.20 -1.22
MT-90 2393.18 006b-ULS 3.89 -0.77 0.24 0.01 0.49 -0.31
MT-90 3589.77 006b-ULS 3.75 -0.77 0.24 0.01 0.78 0.61
MT-90 4786.36 006b-ULS 3.60 -0.77 0.24 0.01 1.08 1.53
MT-90 5982.95 006b-ULS 3.46 -0.77 0.24 0.01 1.37 2.45

Beam No. 3

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-90 0.00 006b-ULS -1.93 -0.15 0.00 0.02 0.00 -0.86
MT-90 360.00(-) 006b-ULS -1.98 -0.15 0.00 0.02 0.00 -0.81
MT-90 360.00(+) 006b-ULS -4.39 -0.77 0.24 -0.01 0.00 -1.87
MT-90 1196.59 006b-ULS -4.48 -0.77 0.24 -0.01 0.20 -1.22
MT-90 2393.18 006b-ULS -4.61 -0.77 0.24 -0.01 0.49 -0.31
MT-90 3589.77 006b-ULS -4.75 -0.77 0.24 -0.01 0.78 0.61
MT-90 4786.36 006b-ULS -4.90 -0.77 0.24 -0.01 1.08 1.53
MT-90 5982.95 006b-ULS -5.04 -0.77 0.24 -0.01 1.37 2.45

Beam No. 4

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-70 0.00 006b-ULS 0.66 2.33 -0.24 0.00 0.02 1.06
MT-70 180.00 006b-ULS 0.66 2.34 -0.24 0.00 -0.02 0.64
MT-70 250.00(-) 006b-ULS 0.66 2.34 -0.24 0.00 -0.04 0.47
MT-70 250.00(+) 006b-ULS 0.42 2.34 0.00 0.00 -0.04 0.47
MT-70 360.00 006b-ULS 0.42 2.35 0.00 0.00 -0.04 0.21
MT-70 450.00(-) 006b-ULS 0.42 2.35 0.00 0.00 -0.04 0.00
MT-70 450.00(+) 006b-ULS -0.38 2.35 0.00 0.00 -0.04 0.00
MT-70 540.00 006b-ULS -0.38 2.36 0.00 0.00 -0.04 -0.21
MT-70 650.00(-) 006b-ULS -0.38 2.36 0.00 0.00 -0.04 -0.47
MT-70 650.00(+) 006b-ULS -0.62 2.36 0.24 0.00 -0.04 -0.47
MT-70 720.00 006b-ULS -0.62 2.37 0.24 0.00 -0.02 -0.64
MT-70 900.00 006b-ULS -0.62 2.38 0.24 0.00 0.02 -1.06

*006b-ULS: SW_sup + Wind (+x). Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 14 / 26
Version: 1.13.1

Solution: Case-2 Date: 28/02/2024

Normal load

Shear load in Y direction

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 15 / 26
Version: 1.13.1

Solution: Case-2 Date: 28/02/2024

Shear load in Z direction

Torsion around X

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 16 / 26
Version: 1.13.1

Solution: Case-2 Date: 28/02/2024

Moment around Y

Moment around Z

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 17 / 26
Version: 1.13.1

Solution: Case-2 Date: 28/02/2024

5.2.3 Stability Analysis

Buckling ratio

Buckling Max. lateral torsional Max. buckling under Max.


Member Length
Length Buckling ratio buckling under bending compression interaction
No. [mm]
[mm] [%] [%] [%]
1 900.00 900.00 1.00 0.00 0.85 0.85
2 5982.95 5982.95 1.00 0.00 4.16 4.16
3 5982.95 5982.95 1.00 0.00 8.24 8.24
4 900.00 900.00 1.00 0.00 0.63 0.63

5.2.4 Deflection Analysis

Criteria
☑Maximum Allowable Deflection (Beam) L/200
☑Maximum Allowable Deflection (Cantilever)L/150
- Maximum Deflection (Absolute) -
☑No Deflection checks calculated for 1.50mm

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 18 / 26
Version: 1.13.1

Solution: Case-2 Date: 28/02/2024

Overview

Results
Reference
Member Max deflection Utilization
Load Combination number* Governing criteria Length Limit
No. [mm] [%]
[mm]
1 016-SLS Relative (Beam) 900.00 L/200 -0.04 0.00
2 016-SLS Relative(Cantilever) 5982.95 L/150 36.94 92.61
3 016-SLS Relative(Cantilever) 5982.95 L/150 36.94 92.61
4 016-SLS Relative (Beam) 900.00 L/200 -0.01 0.00

*016-SLS: SW + Live + Snow + Wind (-x). Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC9

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 19 / 26
Version: 1.13.1

Solution: Case-2 Date: 28/02/2024

Deflection 1.00 * LC1

Deflection 1.00 * LC1 + 1.00 * LC2

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 20 / 26
Version: 1.13.1

Solution: Case-2 Date: 28/02/2024

Deflection 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7

Deflection 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC8

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 21 / 26
Version: 1.13.1

Solution: Case-2 Date: 28/02/2024

Deflection 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC9

Deflection 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC8

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 22 / 26
Version: 1.13.1

Solution: Case-2 Date: 28/02/2024

Deflection 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC9

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 23 / 26
Version: 1.13.1

Solution: Case-2 Date: 28/02/2024

5.3 System Connectors

5.3 Connectors

5.3.1 Overview

Connector: MT-C-GS A OC
Fx Fy Fz Mx My Mz
Connector variant: MT-C-GS A OC (C_D_CS)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 5
Local Forces: 0.66 0.24 2.33 0.00 -1.06 0.02
Resistance: 25.24 10.59 41.34 1.06 2.21 0.40
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 64.27 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 24 / 26
Version: 1.13.1

Solution: Case-2 Date: 28/02/2024

5.4 Base Connectors

5.4 Bases

5.4.1 Overview

Base connector: MT-B-GL O4C OC


Fx Fy Fz Mx My Mz
Connector variant: MT-B-GL O4C OC (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 4
Local Forces: -5.13 0.24 -0.77 -0.01 2.45 1.37
Resistance: 72.17 15.19 21.71 2.33 4.74 4.80
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 92.72 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 25 / 26
Version: 1.13.1

Solution: Case-2 Date: 28/02/2024

6 Remarks, Your Cooperation Duties

Any and all information and data contained in the Software concern solely the use of Hilti products and based on the principles, formulas and security
regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly complied with by
the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the relevant Hilti product.
The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole
responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole responsibility for
having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior
to using them for your specific facility. The Software servers only as an aid to interpret norms and permits without any guarantee as to the absence of
errors, the correctness and relevance ot the results or suitability for a specific application.

You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular
backup of programs and, if applicable, carry out the updates of that you are using the current and thus up-to-date version of the Software in each case
by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or
programs, arising from a culpable breach of duty by you.

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 26 / 26
Case-3

Project: SA-13082-SF

Submitted by:

Hilti contact information


Contact name:
Contact e-mail:
Contact phone:
Contact company:

Customer contact information


Customer name:
Customer e-mail:
Customer phone:
Customer company:

Date: 28/02/2024

This submittal is auto-generated based on user-selected inputs.


Therefore, Hilti no representation as to the suitability of these systems for their intended use. 1 / 25
Version: 1.13.1

Solution: Case-3 Date: 28/02/2024

Table of content

1 Geometry and Application


1.1 Supports
1.2 Nodes
1.3 Members
1.4 Connections
1.5 Release Conditions
1.6 Media Interface Channel
1.7 Gliders
2 Part list
2.1 Members
2.2 Base Connectors
2.3 System Connectors
2.4 Other
3 Load Types
3.1 Loading objects
3.2 Point Loads
3.3 Distributed loads
3.4 Area loads
4 Load Combinations
4.1 Ultimate Limit State
4.2 Serviceability Limit State
5 Results
5.1 Calculation summary
5.2 Members
5.3 System Connectors
5.4 Base Connectors
6 Remarks, Your Cooperation Duties

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 2 / 25
Version: 1.13.1

Solution: Case-3 Date: 28/02/2024

1 Geometry and Application

Support Details
Modular Support Spacing [mm] Undefined

Intermediate Supports required?

Pipe Fasteners with Glider and Presetting used? (See


subchapter 'Gliders' in chapter 'Geometry and
Application')

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 3 / 25
Version: 1.13.1

Solution: Case-3 Date: 28/02/2024

1.1 Supports - Concrete

Concrete

Thickness Drilling Depth


Node No. No. Orientation Concrete grade
[mm] [mm]
3 1 Horizontal C20/25 200.00 150

1.2 Nodes

X Y Z
No. No. Connector name Connector variant
[mm] [mm] [mm]
1 - -190.75 0.00 5482.95 MT-C-GS A OC MT-C-GS A OC (C_CS)
3 1 -190.75 0.00 -500.00 MT-C-GL OC MT-C-GL OC (C_2)
4 - 528.78 0.00 5482.95 MT-AB-G T OC MT-AB-G T OC (C_D)
5 - -190.75 0.00 4831.22 MT-B-GS AB OC MT-B-GS AB OC (C)

1.3 Members

Member Releases Rotation


No. Node start Node end Member Name
Start End [°]
1 1 2 - - MT-70 90.00
2 1 3 - - MT-90 0.00
3 4 5 1 2 MT-70 0.00

1.4 Connections

Cross- Cross- Cross- Cross-


Section/Rotation Section/Rotation Section/Rotation Section/Rotation
Node No. Description Variant
Arm1 Arm2 Arm3 Arm4
[-/°] [-/°] [-/°] [-/°]
MT-C-GS A OC
1 MT-C-GS A OC MT-70/90 MT-90/0 - -
(C_CS)
3 MT-C-GL OC MT-C-GL OC (C_2) MT-90/0 - - -
4 MT-AB-G T OC MT-AB-G T OC (C_D) MT-70/90 MT-70/0 - -
5 MT-B-GS AB OC MT-B-GS AB OC (C) MT-90/0 MT-70/0 - -

1.5 Release Conditions

Spring Constants
Releases
Member Translational Rotational
No. Cu,x Cu,y Cu,z Cφx Cφy Cφz
Ux Uy Uz φx φy φz
[kN/m] [kN/m] [kN/m] [kNm/Rad] [kNm/Rad] [kNm/Rad]
3 no no no no yes yes - - - - 0.000 0.000
3 no no no no yes yes - - - - 0.000 0.000

1.6 Media Interface Channel

Start Position Length


No. Member No. Media Interface Z-Position Y-Position
[mm] [mm]
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 4 / 25
Version: 1.13.1

Solution: Case-3 Date: 28/02/2024

1.7 Gliders

Position Start Travel


No. Member No. Glider Custom Load
[mm] [mm] [mm]

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 5 / 25
Version: 1.13.1

Solution: Case-3 Date: 28/02/2024

2 Part list

2.1 Members

Quantity Weight Length


Position Item Number Description Cutting type
[-] [kg] [mm]
1 2268365 I.-Girder MT-70 OC 1 3.32 850.00 N - None
2 2268365 I.-Girder MT-70 OC 1 2.87 735.03 N - None
3 2268369 I.-Girder MT-90 OC 1 53.91 6007.95 N - None

2.2 Base Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
6 2272066 Angle connector MT-C-GL OC 2 2.32

2.3 System Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
4 2272068 Angle connector MT-C-GS A OC adjustable 1 0.39
8 2272116 Angle brace MT-AB-G T OC adjustable 2 0.70
9 2332787 Baseplate MT-B-GS AB OC 1 1.65

2.4 Other

Quantity Weight
Position Item Number Description
[-] [kg]
5 2272084 Thread forming bolt MT-TFB OC 24 0.68
7 2105870 Stud anchor HST3-R M12x115 40/20 4 0.41

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 6 / 25
Version: 1.13.1

Solution: Case-3 Date: 28/02/2024

3 Load Types

3. Loads

Custom loads

Load No. Load Distribution Load Case Load Type Comments


1 Point load LC 7: Design Permanent -
2 Point load LC 7: Design Permanent -
3 Point load LC 8: Wind (+x) Variable -
4 Point load LC 9: Wind (-x) Variable -

3.2 Point Loads

Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
13 Design 1 250.00 0.00 0.00 -0.11 0.00 0.00 0.00
14 Design 1 650.00 0.00 0.00 -0.11 0.00 0.00 0.00
15 Wind (+x) 1 450.00 0.17 0.00 0.00 0.00 0.00 0.00
16 Wind (-x) 1 450.00 -0.17 -0.00 -0.00 -0.00 -0.00 -0.00
17 Self Weight Support 1 0.00 0.00 0.00 -0.00 0.00 0.00 0.00
18 Self Weight Support 2 5982.95 0.00 0.00 -0.02 0.00 0.00 0.00
19 Self Weight Support 1 719.53 0.00 0.00 -0.01 0.00 0.00 0.00
20 Self Weight Support 2 651.73 0.00 0.00 -0.02 0.00 0.00 0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 7 / 25
Version: 1.13.1

Solution: Case-3 Date: 28/02/2024

3.3 Distributed loads

Start End
Fx Fy Fz Mx My Mz
Load No. Load Type Members Position Position
[kN/m] [kN/m] [kN/m] [kNm/m] [kNm/m] [kNm/m]
[mm] [mm]
21 Self Weight Support 1 0.00 900.00 0.00 0.00 -0.04 0.00 0.00 0.00
22 Self Weight Support 2 0.00 5982.95 0.00 0.00 -0.09 0.00 0.00 0.00
23 Self Weight Support 3 0.00 970.81 0.00 0.00 -0.04 0.00 0.00 0.00

3.4 Area loads

3.4.1 User input

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 8 / 25
Version: 1.13.1

Solution: Case-3 Date: 28/02/2024

4 Load Combinations

Design base EN 1993

Load combination design base EN 1990

4.1 Ultimate Limit State

Design base Load combination and safety factors


ULS - 001a-ULS: SW_inf (Support Only) 1.00 * LC1
ULS - 001b-ULS: SW_sup (Support Only) 1.35 * LC1
ULS - 004a-ULS: SW_inf + Design Loads 1.00 * LC1 + 1.00 * LC7
ULS - 004b-ULS: SW_sup + Design Loads 1.35 * LC1 + 1.00 * LC7
ULS - 006a-ULS: SW_inf + Wind (+x) 1.00 * LC1 + 1.50 * LC8
ULS - 006b-ULS: SW_sup + Wind (+x) 1.35 * LC1 + 1.50 * LC8
ULS - 007a-ULS: SW_inf + Wind (-x) 1.00 * LC1 + 1.50 * LC9
ULS - 007b-ULS: SW_sup + Wind (-x) 1.35 * LC1 + 1.50 * LC9
ULS - 015a-ULS: SW_inf + Live + Snow + Wind (+x) 1.00 * LC1 + 1.50 * 0.60 * LC8
ULS - 015b-ULS: SW_sup + Live + Snow + Wind (+x) 1.35 * LC1 + 1.50 * 0.60 * LC8
ULS - 016a-ULS: SW_inf + Live + Snow + Wind (-x) 1.00 * LC1 + 1.50 * 0.60 * LC9
ULS - 016b-ULS: SW_sup + Live + Snow + Wind (-x) 1.35 * LC1 + 1.50 * 0.60 * LC9
ULS - 031a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * 0.74 * LC7
z) + Design
ULS - 037-ULS: SW_inf + Impact + Live + Snow 1.00 * LC1 + 1.00 * 0.20 * LC8
ULS - 038-ULS: SW_inf + Impact + Live + Snow 1.00 * LC1 + 1.00 * 0.20 * LC9

4.2 Serviceability Limit State

Load Case Load combination and safety factors


SLS - 001-SLS: SW (Support Only) 1.00 * LC1
SLS - 004-SLS: SW + Design Loads 1.00 * LC1 + 0.70 * LC7
SLS - 006-SLS: SW + Wind (+x) 1.00 * LC1 + 1.00 * LC8
SLS - 007-SLS: SW + Wind (-x) 1.00 * LC1 + 1.00 * LC9
SLS - 015-SLS: SW + Live + Snow + Wind (+x) 1.00 * LC1 + 1.00 * 0.60 * LC8
SLS - 016-SLS: SW + Live + Snow + Wind (-x) 1.00 * LC1 + 1.00 * 0.60 * LC9

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 9 / 25
Version: 1.13.1

Solution: Case-3 Date: 28/02/2024

5 Results

5.1 Calculation summary

5.1.3 Members

Governing load ULS SLS


No Member Status
combination number* [%] [%]
2 MT-70 006-SLS 0.90 76.32 OK
13 MT-90 006-SLS 16.66 50.50 OK
18 MT-70 006-SLS 0.43 76.35 OK

5.1.2 Base Connectors

Governing load ULS SLS


No Base connector Status
combination number* [%] [%]
3 MT-C-GL OC 006b-ULS 33.31 - OK

5.1.3 System Connectors

Governing load ULS SLS


No Connector Status
combination number* [%] [%]
1 MT-C-GS A OC 004b-ULS 6.72 - OK
4 MT-AB-G T OC 004b-ULS 0.77 - OK
5 MT-B-GS AB OC 004b-ULS 1.08 - OK
*006-SLS: SW + Wind (+x) . Respective Combination Equation: 1.00 * LC1 + 1.00 * LC8
*006b-ULS: SW_sup + Wind (+x) . Respective Combination Equation: 1.35 * LC1 + 1.50 * LC8
*004b-ULS: SW_sup + Design Loads . Respective Combination Equation: 1.35 * LC1 + 1.00 * LC7

Overall Status: Calculation OK, design criteria met!

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 10 / 25
Version: 1.13.1

Solution: Case-3 Date: 28/02/2024

5.2 Members

5.2.1 Member Properties


5.2.1.1 MT-70 Members: 1, 3
5.2.1.1.1 Section properties
t A Iy Iz It
[mm] [mm²] [mm⁴] [mm⁴] [mm⁴]
2.75 428.78 158700.00 158700.00 297500.00

Iω M Wy Wz Wy
[mm⁶] [kg/m] [mm³] [mm³] [mm³]
2039000.00 3.91 -6349.48 -6349.48 -6349.48

5.2.1.1.2 Material properties


E G Fu Fy Fy.cold
Steel grade
[N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²]
S350GD 1.0529 210000.00 80769.00 420.00 350.00 350.00

5.2.1.2 MT-90 Members: 2


5.2.1.2.1 Section properties
t A Iy Iz It
[mm] [mm²] [mm⁴] [mm⁴] [mm⁴]
3.00 976.08 1508000.00 1508000.00 2047000.00

Iω M Wy Wz Wy
[mm⁶] [kg/m] [mm³] [mm³] [mm³]
15470000.00 8.97 -30169.60 -30169.60 -30169.60

5.2.1.2.2 Material properties


E G Fu Fy Fy.cold
Steel grade
[N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²]
S350GD 1.0529 210000.00 80769.00 420.00 350.00 350.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 11 / 25
Version: 1.13.1

Solution: Case-3 Date: 28/02/2024

5.2.2 Member Design

5.2.2.1 Overview

5.2.2.2 Stress Analysis

5.2.2.2.1 Table of Results

Load Combination σ τ σeqv σlimit τlimit Utilization


No. Member
number* [N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²] [%]
1 I.-Girder MT-70 OC 004b-ULS 2.83 0.88 2.87 318.18 183.70 0.90
2 I.-Girder MT-90 OC 006b-ULS -52.99 0.00 53.00 318.18 0.00 16.66
3 I.-Girder MT-70 OC 004b-ULS -1.36 0.00 1.36 318.18 0.00 0.43

*004b-ULS: SW_sup + Design Loads. Respective Combination Equation: 1.35 * LC1 + 1.00 * LC7

*006b-ULS: SW_sup + Wind (+x). Respective Combination Equation: 1.35 * LC1 + 1.50 * LC8

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 12 / 25
Version: 1.13.1

Solution: Case-3 Date: 28/02/2024

5.2.2.2 Governing Member Loading

Beam No. 1

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-70 0.00 004b-ULS 0.20 -0.12 0.00 0.00 0.00 -0.01
MT-70 180.00 004b-ULS 0.20 -0.11 0.00 0.00 0.00 0.01
MT-70 250.00(-) 004b-ULS 0.20 -0.11 0.00 0.00 0.00 0.01
MT-70 250.00(+) 004b-ULS 0.20 0.00 0.00 0.00 0.00 0.01
MT-70 360.00 004b-ULS 0.20 0.01 0.00 0.00 0.00 0.01
MT-70 540.00 004b-ULS 0.20 0.02 0.00 0.00 0.00 0.01
MT-70 650.00(-) 004b-ULS 0.20 0.02 0.00 0.00 0.00 0.01
MT-70 650.00(+) 004b-ULS 0.20 0.13 0.00 0.00 0.00 0.01
MT-70 720.00 004b-ULS 0.00 -0.01 0.00 0.00 0.00 -0.00
MT-70 900.00 004b-ULS 0.00 0.00 0.00 0.00 0.00 -0.00

Beam No. 2

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-90 0.00 006b-ULS -0.02 0.00 -0.33 0.00 0.00 -0.00
MT-90 651.73(-) 006b-ULS -0.10 0.00 -0.33 0.00 -0.21 -0.00
MT-90 651.73(+) 006b-ULS -0.26 0.00 -0.26 0.00 -0.21 -0.00
MT-90 1196.59 006b-ULS -0.30 0.00 -0.26 0.00 -0.35 -0.00
MT-90 2393.18 006b-ULS -0.43 0.00 -0.25 0.00 -0.66 -0.00
MT-90 3589.77 006b-ULS -0.57 0.00 -0.26 0.00 -0.96 -0.00
MT-90 4786.36 006b-ULS -0.72 0.00 -0.25 0.00 -1.27 -0.00
MT-90 5982.95 006b-ULS -0.86 0.00 -0.26 0.00 -1.57 -0.00

Beam No. 3

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-70 0.00 004b-ULS -0.25 0.00 -0.02 0.00 0.00 -0.00
MT-70 194.16 004b-ULS -0.26 0.00 -0.01 0.00 -0.00 -0.00
MT-70 388.32 004b-ULS -0.27 0.00 -0.00 0.00 -0.00 -0.00
MT-70 582.49 004b-ULS -0.27 0.00 0.00 0.00 -0.00 -0.00
MT-70 776.65 004b-ULS -0.28 0.00 0.01 0.00 -0.00 -0.00
MT-70 970.81 004b-ULS -0.29 0.00 0.02 0.00 0.00 -0.00

*004b-ULS: SW_sup + Design Loads. Respective Combination Equation: 1.35 * LC1 + 1.00 * LC7

*006b-ULS: SW_sup + Wind (+x). Respective Combination Equation: 1.35 * LC1 + 1.50 * LC8

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 13 / 25
Version: 1.13.1

Solution: Case-3 Date: 28/02/2024

Normal load

Shear load in Y direction

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 14 / 25
Version: 1.13.1

Solution: Case-3 Date: 28/02/2024

Shear load in Z direction

Torsion around X

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 15 / 25
Version: 1.13.1

Solution: Case-3 Date: 28/02/2024

Moment around Y

Moment around Z

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 16 / 25
Version: 1.13.1

Solution: Case-3 Date: 28/02/2024

5.2.3 Stability Analysis

Buckling ratio

Buckling Max. lateral torsional Max. buckling under Max.


Member Length
Length Buckling ratio buckling under bending compression interaction
No. [mm]
[mm] [%] [%] [%]
1 900.00 1800.00 2.00 0.00 0.38 0.38
2 5982.95 5982.95 1.00 0.00 1.76 1.76
3 970.81 970.81 1.00 0.00 0.30 0.30

5.2.4 Deflection Analysis

Criteria
☑Maximum Allowable Deflection (Beam) L/150
☑Maximum Allowable Deflection (Cantilever)L/75
- Maximum Deflection (Absolute) -
☑No Deflection checks calculated for 1.50mm

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 17 / 25
Version: 1.13.1

Solution: Case-3 Date: 28/02/2024

Overview

Results
Reference
Member Max deflection Utilization
Load Combination number* Governing criteria Length Limit
No. [mm] [%]
[mm]
1 006-SLS Relative(Cantilever) 900.00 L/75 -9.16 76.32
2 006-SLS Relative(Cantilever) 5982.95 L/75 -40.28 50.50
3 006-SLS Relative(Cantilever) 970.81 L/75 9.88 76.35

*006-SLS: SW + Wind (+x). Respective Combination Equation: 1.00 * LC1 + 1.00 * LC8

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 18 / 25
Version: 1.13.1

Solution: Case-3 Date: 28/02/2024

Deflection 1.00 * LC1

Deflection 1.00 * LC1 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 19 / 25
Version: 1.13.1

Solution: Case-3 Date: 28/02/2024

Deflection 1.00 * LC1 + 1.00 * LC8

Deflection 1.00 * LC1 + 1.00 * LC9

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 20 / 25
Version: 1.13.1

Solution: Case-3 Date: 28/02/2024

Deflection 1.00 * LC1 + 1.00 * 0.60 * LC8

Deflection 1.00 * LC1 + 1.00 * 0.60 * LC9

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 21 / 25
Version: 1.13.1

Solution: Case-3 Date: 28/02/2024

5.3 System Connectors

5.3 Connectors

5.3.1 Overview

Connector: MT-C-GS A OC
Fx Fy Fz Mx My Mz
Connector variant: MT-C-GS A OC (C_CS)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 1
Local Forces: 0.20 0.00 0.12 0.00 -0.01 0.00
Resistance: 9.47 3.64 16.71 0.16 0.36 0.13
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 6.72 % OK
Governing Load
1.35 * LC1 + 1.00 * LC7
Combination
Connector: MT-AB-G T OC
Fx Fy Fz Mx My Mz
Connector variant: MT-AB-G T OC (C_D)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 4
Local Forces: -0.25 0.02 0.00 0.00 0.00 0.00
Resistance: 32.99 6.44 1.83
Equation: (( Fx.ed^2 + Fy.ed^2 )^0.5)/Fx.rd + Fz.ed / Fz.rd+Mx.ed/Mx.rd
Utilization: 0.77 % OK

Governing Load
1.35 * LC1 + 1.00 * LC7
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 22 / 25
Version: 1.13.1

Solution: Case-3 Date: 28/02/2024


Connector: MT-B-GS AB OC
Fx Fy Fz Mx My Mz
Connector variant: MT-B-GS AB OC (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 5
Local Forces: -0.29 -0.02 -0.00 0.00 0.00 -0.00
Resistance: 29.00 19.90 4.60 0.73
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 1.08 % OK
Governing Load
1.35 * LC1 + 1.00 * LC7
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 23 / 25
Version: 1.13.1

Solution: Case-3 Date: 28/02/2024

5.4 Base Connectors

5.4 Bases

5.4.1 Overview

Base connector: MT-C-GL OC


Fx Fy Fz Mx My Mz
Connector variant: MT-C-GL OC (C_2)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 3
Local Forces: -0.89 0.00 0.26 -0.00 -1.57 0.00
Resistance: 119.61 37.57 37.53 2.73 4.93 1.65
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 33.31 % OK
Governing Load
1.35 * LC1 + 1.50 * LC8
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 24 / 25
Version: 1.13.1

Solution: Case-3 Date: 28/02/2024

6 Remarks, Your Cooperation Duties

Any and all information and data contained in the Software concern solely the use of Hilti products and based on the principles, formulas and security
regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly complied with by
the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the relevant Hilti product.
The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole
responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole responsibility for
having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior
to using them for your specific facility. The Software servers only as an aid to interpret norms and permits without any guarantee as to the absence of
errors, the correctness and relevance ot the results or suitability for a specific application.

You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular
backup of programs and, if applicable, carry out the updates of that you are using the current and thus up-to-date version of the Software in each case
by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or
programs, arising from a culpable breach of duty by you.

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 25 / 25
Case-4

Project: SA-13082-SF

Submitted by:

Hilti contact information


Contact name:
Contact e-mail:
Contact phone:
Contact company:

Customer contact information


Customer name:
Customer e-mail:
Customer phone:
Customer company:

Date: 28/02/2024

This submittal is auto-generated based on user-selected inputs.


Therefore, Hilti no representation as to the suitability of these systems for their intended use. 1 / 23
Version: 1.13.1

Solution: Case-4 Date: 28/02/2024

Table of content

1 Geometry and Application


1.1 Supports
1.2 Nodes
1.3 Members
1.4 Connections
1.5 Release Conditions
1.6 Media Interface Channel
1.7 Gliders
2 Part list
2.1 Members
2.2 Base Connectors
2.3 System Connectors
2.4 Other
3 Load Types
3.1 Loading objects
3.2 Point Loads
3.3 Distributed loads
3.4 Area loads
4 Load Combinations
4.1 Ultimate Limit State
4.2 Serviceability Limit State
5 Results
5.1 Calculation summary
5.2 Members
5.3 System Connectors
5.4 Base Connectors
6 Remarks, Your Cooperation Duties

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 2 / 23
Version: 1.13.1

Solution: Case-4 Date: 28/02/2024

1 Geometry and Application

Support Details
Modular Support Spacing [mm] Undefined

Intermediate Supports required?

Pipe Fasteners with Glider and Presetting used? (See


subchapter 'Gliders' in chapter 'Geometry and
Application')

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 3 / 23
Version: 1.13.1

Solution: Case-4 Date: 28/02/2024

1.1 Supports - Concrete

Concrete

Thickness Drilling Depth


Node No. No. Orientation Concrete grade
[mm] [mm]
1 1 Horizontal C20/25 200.00 150
5 2 Horizontal C20/25 200.00 150

1.2 Nodes

X Y Z
No. No. Connector name Connector variant
[mm] [mm] [mm]
1 1 -190.75 0.00 -500.00 MT-B-O2 OC MT-B-O2 OC (C)
2 - -190.75 0.00 -162.05 MT-C-L2 OC MT-C-L2 OC (C)
3 - 709.25 0.00 -162.05 MT-C-L2 OC MT-C-L2 OC (C)
5 2 709.25 0.00 -500.00 MT-B-O2 OC MT-B-O2 OC (C)

1.3 Members

Member Releases Rotation


No. Node start Node end Member Name
Start End [°]
1 2 3 1 2 MT-40 180.00
2 1 4 - - MT-40 180.00
3 5 6 - - MT-40 0.00

1.4 Connections

Cross- Cross- Cross- Cross-


Section/Rotation Section/Rotation Section/Rotation Section/Rotation
Node No. Description Variant
Arm1 Arm2 Arm3 Arm4
[-/°] [-/°] [-/°] [-/°]
1 MT-B-O2 OC MT-B-O2 OC (C) MT-40/180 - - -
2 MT-C-L2 OC MT-C-L2 OC (C) MT-40/180 MT-40/180 - -
3 MT-C-L2 OC MT-C-L2 OC (C) MT-40/180 MT-40/0 - -
5 MT-B-O2 OC MT-B-O2 OC (C) MT-40/0 - - -

1.5 Release Conditions

Spring Constants
Releases
Member Translational Rotational
No. Cu,x Cu,y Cu,z Cφx Cφy Cφz
Ux Uy Uz φx φy φz
[kN/m] [kN/m] [kN/m] [kNm/Rad] [kNm/Rad] [kNm/Rad]
1 no no no no yes yes - - - - 0.001 0.001
1 no no no no yes yes - - - - 0.001 0.001

1.6 Media Interface Channel

Start Position Length


No. Member No. Media Interface Z-Position Y-Position
[mm] [mm]
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 4 / 23
Version: 1.13.1

Solution: Case-4 Date: 28/02/2024

1.7 Gliders

Position Start Travel


No. Member No. Glider Custom Load
[mm] [mm] [mm]

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 5 / 23
Version: 1.13.1

Solution: Case-4 Date: 28/02/2024

2 Part list

2.1 Members

Quantity Weight Length


Position Item Number Description Cutting type
[-] [kg] [mm]
1 2268508 I.-Channel MT-40 OC 1 1.75 857.50 N - None
2 2268508 I.-Channel MT-40 OC 2 2.61 641.00 N - None

2.2 Base Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
3 2272096 2-hole Baseplate MT-B-O2 OC 2 2.05

2.3 System Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
7 2271519 Angle connector MT-C-L2 OC 2 0.52

2.4 Other

Quantity Weight
Position Item Number Description
[-] [kg]
4 2273256 Hexagon bolt MT-TLB OC 10 0.25
5 2272082 Twist-Lock MT-TL M10 OC 10 0.35
6 2105870 Stud anchor HST3-R M12x115 40/20 4 0.41

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 6 / 23
Version: 1.13.1

Solution: Case-4 Date: 28/02/2024

3 Load Types

3. Loads

Custom loads

Load No. Load Distribution Load Case Load Type Comments


1 Point load LC 7: Design Permanent -
2 Point load LC 7: Design Permanent -
3 Point load LC 13: Seismic (+x) Seismic -
4 Point load LC 14: Seismic (-x) Seismic -
5 Point load LC 13: Seismic (+x) Seismic -
6 Point load LC 14: Seismic (-x) Seismic -
7 Point load LC 2: Pipe Permanent -
8 Point load LC 2: Pipe Permanent -
9 Point load LC 7: Design Permanent -
10 Point load LC 7: Design Permanent -

3.2 Point Loads

Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
1 Design 1 250.00 0.00 0.00 -1.79 0.00 0.00 0.00
2 Design 1 650.00 0.00 0.00 -1.79 0.00 0.00 0.00
3 Seismic (+x) 1 250.00 0.02 0.00 0.00 0.00 0.00 0.00
4 Seismic (-x) 1 250.00 -0.02 -0.00 -0.00 -0.00 -0.00 -0.00
5 Seismic (+x) 1 650.00 0.02 0.00 0.00 0.00 0.00 0.00
6 Seismic (-x) 1 650.00 -0.02 -0.00 -0.00 -0.00 -0.00 -0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 7 / 23
Version: 1.13.1

Solution: Case-4 Date: 28/02/2024


Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
9 Pipe 1 250.00 0.18 0.18 0.00 0.00 0.00 0.00
10 Pipe 1 650.00 0.18 0.18 0.00 0.00 0.00 0.00
13 Design 2 535.00 0.00 0.00 -0.11 0.00 0.03 0.00
14 Design 3 535.00 0.00 0.00 -0.11 0.00 -0.03 0.00
15 Self Weight Support 2 0.00 0.00 0.00 -0.01 0.00 0.00 0.00
16 Self Weight Support 1 0.00 0.00 0.00 -0.00 0.00 0.00 0.00
17 Self Weight Support 1 900.00 0.00 0.00 -0.00 0.00 0.00 0.00
18 Self Weight Support 3 0.00 0.00 0.00 -0.01 0.00 0.00 0.00

3.3 Distributed loads

Start End
Fx Fy Fz Mx My Mz
Load No. Load Type Members Position Position
[kN/m] [kN/m] [kN/m] [kNm/m] [kNm/m] [kNm/m]
[mm] [mm]
19 Self Weight Support 1 0.00 900.00 0.00 0.00 -0.02 0.00 0.00 0.00
20 Self Weight Support 2 0.00 650.00 0.00 0.00 -0.02 0.00 0.00 0.00
21 Self Weight Support 3 0.00 650.00 0.00 0.00 -0.02 0.00 0.00 0.00

3.4 Area loads

3.4.1 User input

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 8 / 23
Version: 1.13.1

Solution: Case-4 Date: 28/02/2024

4 Load Combinations

Design base EN 1993

Load combination design base EN 1990

4.1 Ultimate Limit State

Design base Load combination and safety factors


ULS - 001a-ULS: SW_inf (Support Only) 1.00 * LC1
ULS - 001b-ULS: SW_sup (Support Only) 1.35 * LC1
ULS - 002a-ULS: SW_inf Support + Media 1.00 * LC1 + 1.00 * LC2
ULS - 002b-ULS: SW_sup Support + Media 1.35 * LC1 + 1.35 * LC2
ULS - 004a-ULS: SW_inf + Design Loads 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC7
ULS - 004b-ULS: SW_sup + Design Loads 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
ULS - 027a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC13
z) + Live + Snow
ULS - 027b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC14
+ Live + Snow
ULS - 029a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC13
z) + Live + Snow
ULS - 030a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC14
+ Live + Snow
ULS - 027a-ULS_Base : SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 027b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 029a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 030a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 031a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC13 + 1.00 * 0.74 * LC7
z) + Design
ULS - 031b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC14 + 1.00 * 0.74 * LC7
+ Design
ULS - 033a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC13 + 1.00 * 0.74 * LC7
z) + Design
ULS - 034a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC14 + 1.00 * 0.74 * LC7
+ Design
ULS - 032a-ULS_Base: SW + Seismic (+x) + Seismic (-y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC13 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 031b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC14 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 033a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC13 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 034a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC14 + 1.00 * 0.74 * LC7
Seismic (-z) + Design

4.2 Serviceability Limit State

Load Case Load combination and safety factors


SLS - 001-SLS: SW (Support Only) 1.00 * LC1
SLS - 002-SLS: SW Support + Media Objects 1.00 * LC1 + 1.00 * LC2
SLS - 004-SLS: SW + Design Loads 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 9 / 23
Version: 1.13.1

Solution: Case-4 Date: 28/02/2024

5 Results

5.1 Calculation summary

5.1.3 Members

Governing load ULS SLS


No Member Status
combination number* [%] [%]
2 MT-40 004-SLS 80.07 53.34 OK
11 MT-40 004b-ULS 50.35 - OK
12 MT-40 004b-ULS 54.19 - OK

5.1.2 Base Connectors

Governing load ULS SLS


No Base connector Status
combination number* [%] [%]
1 MT-B-O2 OC 004b-ULS 73.02 - OK
5 MT-B-O2 OC 004b-ULS 81.43 - OK

5.1.3 System Connectors

Governing load ULS SLS


No Connector Status
combination number* [%] [%]
2 MT-C-L2 OC 004b-ULS 32.94 - OK
3 MT-C-L2 OC 004b-ULS 36.42 - OK
*004-SLS: SW + Design Loads . Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7
*004b-ULS: SW_sup + Design Loads . Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7

Overall Status: Calculation OK, design criteria met!

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 10 / 23
Version: 1.13.1

Solution: Case-4 Date: 28/02/2024

5.2 Members

5.2.1 Member Properties


5.2.1.1 MT-40 Members: 1, 2, 3
5.2.1.1.1 Section properties
t A Iy Iz It
[mm] [mm²] [mm⁴] [mm⁴] [mm⁴]
2.00 285.00 57717.48 65876.44 259.85

Iω M Wy Wz Wy
[mm⁶] [kg/m] [mm³] [mm³] [mm³]
38410000.00 2.04 -2652.65 -3099.95 -2652.65

5.2.1.1.2 Material properties


E G Fu Fy Fy.cold
Steel grade
[N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²]
Steel S 280 GD 210000.00 80769.00 360.00 280.00 305.00

5.2.2 Member Design

5.2.2.1 Overview

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 11 / 23
Version: 1.13.1

Solution: Case-4 Date: 28/02/2024

5.2.2.2 Stress Analysis

5.2.2.2.1 Table of Results

Load Combination σ τ σeqv σlimit τlimit Utilization


No. Member
number* [N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²] [%]
I.-Channel MT-40
1 004b-ULS 185.98 -18.60 186.31 277.27 160.08 67.20
OC
I.-Channel MT-40
2 004b-ULS -58.59 0.00 58.62 277.27 0.00 21.14
OC
I.-Channel MT-40
3 004b-ULS -66.45 -14.15 66.48 277.27 160.08 23.98
OC

*004b-ULS: SW_sup + Design Loads. Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 12 / 23
Version: 1.13.1

Solution: Case-4 Date: 28/02/2024

5.2.2.2 Governing Member Loading

Beam No. 1

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40 0.00 004b-ULS 0.11 -0.24 1.80 0.00 -0.00 -0.00
MT-40 180.00 004b-ULS 0.11 -0.24 1.80 0.00 0.32 0.04
MT-40 250.00(-) 004b-ULS 0.11 -0.24 1.80 0.00 0.45 0.06
MT-40 250.00(+) 004b-ULS -0.13 0.00 0.01 0.00 0.45 0.06
MT-40 360.00 004b-ULS -0.13 0.00 0.00 0.00 0.45 0.06
MT-40 540.00 004b-ULS -0.13 0.00 -0.00 0.00 0.45 0.06
MT-40 650.00(-) 004b-ULS -0.13 0.00 -0.01 0.00 0.45 0.06
MT-40 650.00(+) 004b-ULS -0.37 0.24 -1.80 0.00 0.45 0.06
MT-40 720.00 004b-ULS -0.37 0.24 -1.80 0.00 0.32 0.04
MT-40 900.00 004b-ULS -0.37 0.24 -1.80 0.00 -0.00 -0.00

Beam No. 2

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40 0.00 004b-ULS -1.93 -0.24 0.11 0.00 -0.07 -0.08
MT-40 130.00 004b-ULS -1.93 -0.24 0.11 0.00 -0.05 -0.05
MT-40 260.00 004b-ULS -1.93 -0.24 0.11 0.00 -0.04 -0.02
MT-40 337.95(-) 004b-ULS -1.92 -0.24 0.11 0.00 -0.03 -0.00
MT-40 337.95(+) 004b-ULS -0.12 0.00 0.00 0.00 -0.03 -0.00
MT-40 390.00 004b-ULS -0.12 0.00 0.00 0.00 -0.03 -0.00
MT-40 520.00 004b-ULS -0.11 0.00 0.00 0.00 -0.03 -0.00
MT-40 535.00(-) 004b-ULS -0.11 0.00 0.00 0.00 -0.03 -0.00
MT-40 535.00(+) 004b-ULS -0.00 0.00 0.00 0.00 0.00 -0.00
MT-40 650.00 004b-ULS -0.00 0.00 0.00 0.00 0.00 -0.00

Beam No. 3

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40 0.00 004b-ULS -1.93 0.24 -0.37 -0.00 0.10 0.08
MT-40 130.00 004b-ULS -1.93 0.24 -0.37 -0.00 0.05 0.05
MT-40 260.00 004b-ULS -1.93 0.24 -0.37 -0.00 -0.00 0.02
MT-40 337.95(-) 004b-ULS -1.92 0.24 -0.37 -0.00 -0.03 0.00
MT-40 337.95(+) 004b-ULS -0.12 0.00 0.00 0.00 -0.03 -0.00
MT-40 390.00 004b-ULS -0.12 0.00 0.00 0.00 -0.03 -0.00
MT-40 520.00 004b-ULS -0.11 0.00 0.00 0.00 -0.03 -0.00
MT-40 535.00(-) 004b-ULS -0.11 0.00 0.00 0.00 -0.03 -0.00
MT-40 535.00(+) 004b-ULS -0.00 0.00 0.00 0.00 0.00 -0.00
MT-40 650.00 004b-ULS -0.00 0.00 0.00 0.00 0.00 -0.00

*004b-ULS: SW_sup + Design Loads. Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 13 / 23
Version: 1.13.1

Solution: Case-4 Date: 28/02/2024

Normal load

Shear load in Y direction

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 14 / 23
Version: 1.13.1

Solution: Case-4 Date: 28/02/2024

Shear load in Z direction

Torsion around X

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 15 / 23
Version: 1.13.1

Solution: Case-4 Date: 28/02/2024

Moment around Y

Moment around Z

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 16 / 23
Version: 1.13.1

Solution: Case-4 Date: 28/02/2024

5.2.3 Stability Analysis

Buckling ratio

Buckling Max. lateral torsional Max. buckling under Max.


Member Length
Length Buckling ratio buckling under bending compression interaction
No. [mm]
[mm] [%] [%] [%]
1 900.00 900.00 1.00 71.25 1.69 80.07
2 650.00 1300.00 2.00 21.98 13.87 50.35
3 650.00 1300.00 2.00 25.58 13.87 54.19

5.2.4 Deflection Analysis

Criteria
☑Maximum Allowable Deflection (Beam) L/200
☑Maximum Allowable Deflection (Cantilever)L/150
- Maximum Deflection (Absolute) -
☑No Deflection checks calculated for 1.50mm

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 17 / 23
Version: 1.13.1

Solution: Case-4 Date: 28/02/2024

Overview

Results
Reference
Member Max deflection Utilization
Load Combination number* Governing criteria Length Limit
No. [mm] [%]
[mm]
1 004-SLS Relative (Beam) 900.00 L/200 2.40 53.34
2 004-SLS Relative (Beam) 650.00 L/200 -0.03 0.00
3 004-SLS Relative (Beam) 650.00 L/200 -0.04 0.00

*004-SLS: SW + Design Loads. Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 18 / 23
Version: 1.13.1

Solution: Case-4 Date: 28/02/2024

Deflection 1.00 * LC1

Deflection 1.00 * LC1 + 1.00 * LC2

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 19 / 23
Version: 1.13.1

Solution: Case-4 Date: 28/02/2024

Deflection 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 20 / 23
Version: 1.13.1

Solution: Case-4 Date: 28/02/2024

5.3 System Connectors

5.3 Connectors

5.3.1 Overview

Connector: MT-C-L2 OC
Fx Fy Fz Mx My Mz
Connector variant: MT-C-L2 OC (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 3
Local Forces: -0.37 0.24 1.80 0.00 -0.00 0.00
Resistance: 5.84 1.56 12.38 0.06
Equation: abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)
Utilization: 36.42 % OK

Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 21 / 23
Version: 1.13.1

Solution: Case-4 Date: 28/02/2024

5.4 Base Connectors

5.4 Bases

5.4.1 Overview

Base connector: MT-B-O2 OC


Fx Fy Fz Mx My Mz
Connector variant: MT-B-O2 OC (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 5
Local Forces: -1.95 0.24 -0.37 -0.00 0.10 0.08
Resistance: 14.00 2.43 7.34 0.06 0.55 0.23
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 81.43 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 22 / 23
Version: 1.13.1

Solution: Case-4 Date: 28/02/2024

6 Remarks, Your Cooperation Duties

Any and all information and data contained in the Software concern solely the use of Hilti products and based on the principles, formulas and security
regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly complied with by
the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the relevant Hilti product.
The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole
responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole responsibility for
having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior
to using them for your specific facility. The Software servers only as an aid to interpret norms and permits without any guarantee as to the absence of
errors, the correctness and relevance ot the results or suitability for a specific application.

You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular
backup of programs and, if applicable, carry out the updates of that you are using the current and thus up-to-date version of the Software in each case
by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or
programs, arising from a culpable breach of duty by you.

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 23 / 23
Case-5-7-10

Project: SA-13082-SF

Submitted by:

Hilti contact information


Contact name:
Contact e-mail:
Contact phone:
Contact company:

Customer contact information


Customer name:
Customer e-mail:
Customer phone:
Customer company:

Date: 28/02/2024

This submittal is auto-generated based on user-selected inputs.


Therefore, Hilti no representation as to the suitability of these systems for their intended use. 1 / 19
Version: 1.13.1

Solution: Case-5-7-10 Date: 28/02/2024

Table of content

1 Geometry and Application


1.1 Supports
1.2 Nodes
1.3 Members
1.4 Connections
1.5 Release Conditions
1.6 Media Interface Channel
1.7 Gliders
2 Part list
2.1 Members
2.2 Base Connectors
2.3 System Connectors
2.4 Other
3 Load Types
3.1 Loading objects
3.2 Point Loads
3.3 Distributed loads
3.4 Area loads
4 Load Combinations
4.1 Ultimate Limit State
4.2 Serviceability Limit State
5 Results
5.1 Calculation summary
5.2 Members
5.3 System Connectors
5.4 Base Connectors
6 Remarks, Your Cooperation Duties

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 2 / 19
Version: 1.13.1

Solution: Case-5-7-10 Date: 28/02/2024

1 Geometry and Application

Support Details
Modular Support Spacing [mm] Undefined

Intermediate Supports required?

Pipe Fasteners with Glider and Presetting used? (See


subchapter 'Gliders' in chapter 'Geometry and
Application')

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 3 / 19
Version: 1.13.1

Solution: Case-5-7-10 Date: 28/02/2024

1.1 Supports - Concrete

Concrete

Thickness Drilling Depth


Node No. No. Orientation Concrete grade
[mm] [mm]
1 1 Horizontal C20/25 200.00 150

1.2 Nodes

X Y Z
No. No. Connector name Connector variant
[mm] [mm] [mm]
1 1 -190.75 0.00 -500.00 MT-B-T OC MT-B-T OC (E)

1.3 Members

Member Releases Rotation


No. Node start Node end Member Name
Start End [°]
1 1 2 - - MT-30 0.00

1.4 Connections

Cross- Cross- Cross- Cross-


Section/Rotation Section/Rotation Section/Rotation Section/Rotation
Node No. Description Variant
Arm1 Arm2 Arm3 Arm4
[-/°] [-/°] [-/°] [-/°]
1 MT-B-T OC MT-B-T OC (E) MT-30/0 - - -

1.5 Release Conditions

Spring Constants
Releases
Member Translational Rotational
No. Cu,x Cu,y Cu,z Cφx Cφy Cφz
Ux Uy Uz φx φy φz
[kN/m] [kN/m] [kN/m] [kNm/Rad] [kNm/Rad] [kNm/Rad]

1.6 Media Interface Channel

Start Position Length


No. Member No. Media Interface Z-Position Y-Position
[mm] [mm]

1.7 Gliders

Position Start Travel


No. Member No. Glider Custom Load
[mm] [mm] [mm]

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 4 / 19
Version: 1.13.1

Solution: Case-5-7-10 Date: 28/02/2024

2 Part list

2.1 Members

Quantity Weight Length


Position Item Number Description Cutting type
[-] [kg] [mm]
1 2268500 I.-Channel MT-30 OC 1 0.97 650.00 N - None

2.2 Base Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
2 2272092 2-hole Baseplate MT-B-T OC 1 0.56

2.3 System Connectors

Quantity Weight
Position Item Number Description
[-] [kg]

2.4 Other

Quantity Weight
Position Item Number Description
[-] [kg]
3 2272082 Twist-Lock MT-TL M10 OC 2 0.07
4 2273256 Hexagon bolt MT-TLB OC 2 0.05
5 2105870 Stud anchor HST3-R M12x115 40/20 2 0.20

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 5 / 19
Version: 1.13.1

Solution: Case-5-7-10 Date: 28/02/2024

3 Load Types

3. Loads

Custom loads

Load No. Load Distribution Load Case Load Type Comments


1 Point load LC 7: Design Permanent -

3.2 Point Loads

Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
13 Design 1 535.00 0.00 0.00 -0.11 0.00 -0.03 0.00
14 Self Weight Support 1 0.00 0.00 0.00 -0.01 0.00 0.00 0.00

3.3 Distributed loads

Start End
Fx Fy Fz Mx My Mz
Load No. Load Type Members Position Position
[kN/m] [kN/m] [kN/m] [kNm/m] [kNm/m] [kNm/m]
[mm] [mm]
15 Self Weight Support 1 0.00 650.00 0.00 0.00 -0.01 0.00 0.00 0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 6 / 19
Version: 1.13.1

Solution: Case-5-7-10 Date: 28/02/2024

3.4 Area loads

3.4.1 User input

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 7 / 19
Version: 1.13.1

Solution: Case-5-7-10 Date: 28/02/2024

4 Load Combinations

Design base EN 1993

Load combination design base EN 1990

4.1 Ultimate Limit State

Design base Load combination and safety factors


ULS - 001a-ULS: SW_inf (Support Only) 1.00 * LC1
ULS - 001b-ULS: SW_sup (Support Only) 1.35 * LC1
ULS - 004a-ULS: SW_inf + Design Loads 1.00 * LC1 + 1.00 * LC7
ULS - 004b-ULS: SW_sup + Design Loads 1.35 * LC1 + 1.00 * LC7
ULS - 031a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * 0.74 * LC7
z) + Design

4.2 Serviceability Limit State

Load Case Load combination and safety factors


SLS - 001-SLS: SW (Support Only) 1.00 * LC1
SLS - 004-SLS: SW + Design Loads 1.00 * LC1 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 8 / 19
Version: 1.13.1

Solution: Case-5-7-10 Date: 28/02/2024

5 Results

5.1 Calculation summary

5.1.3 Members

Governing load ULS SLS


No Member Status
combination number* [%] [%]
11 MT-30 004-SLS 10.60 39.03 OK

5.1.2 Base Connectors

Governing load ULS SLS


No Base connector Status
combination number* [%] [%]
1 MT-B-T OC 004b-ULS 34.48 - OK
*004-SLS: SW + Design Loads . Respective Combination Equation: 1.00 * LC1 + 0.70 * LC7
*004b-ULS: SW_sup + Design Loads . Respective Combination Equation: 1.35 * LC1 + 1.00 * LC7

Overall Status: Calculation OK, design criteria met!

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 9 / 19
Version: 1.13.1

Solution: Case-5-7-10 Date: 28/02/2024

5.2 Members

5.2.1 Member Properties


5.2.1.1 MT-30 Members: 1
5.2.1.1.1 Section properties
t A Iy Iz It
[mm] [mm²] [mm⁴] [mm⁴] [mm⁴]
2.00 180.00 12099.30 51923.40 162.57

Iω M Wy Wz Wy
[mm⁶] [kg/m] [mm³] [mm³] [mm³]
8522000.00 1.49 -1004.46 -2443.24 -1004.46

5.2.1.1.2 Material properties


E G Fu Fy Fy.cold
Steel grade
[N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²]
Steel S 280 GD 210000.00 80769.00 360.00 280.00 317.00

5.2.2 Member Design

5.2.2.1 Overview

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 10 / 19
Version: 1.13.1

Solution: Case-5-7-10 Date: 28/02/2024

5.2.2.2 Stress Analysis

5.2.2.2.1 Table of Results

Load Combination σ τ σeqv σlimit τlimit Utilization


No. Member
number* [N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²] [%]
I.-Channel MT-30
1 004b-ULS -30.55 0.00 30.55 288.18 0.00 10.60
OC

*004b-ULS: SW_sup + Design Loads. Respective Combination Equation: 1.35 * LC1 + 1.00 * LC7

5.2.2.2 Governing Member Loading

Beam No. 1

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-30 0.00 004b-ULS -0.12 0.00 0.00 0.00 -0.03 -0.00
MT-30 130.00 004b-ULS -0.12 0.00 0.00 0.00 -0.03 -0.00
MT-30 260.00 004b-ULS -0.12 0.00 0.00 0.00 -0.03 -0.00
MT-30 390.00 004b-ULS -0.12 0.00 0.00 0.00 -0.03 -0.00
MT-30 520.00 004b-ULS -0.11 0.00 0.00 0.00 -0.03 -0.00
MT-30 535.00(-) 004b-ULS -0.11 0.00 0.00 0.00 -0.03 -0.00
MT-30 535.00(+) 004b-ULS -0.00 0.00 0.00 0.00 0.00 -0.00
MT-30 650.00 004b-ULS 0.00 0.00 0.00 0.00 0.00 -0.00

*004b-ULS: SW_sup + Design Loads. Respective Combination Equation: 1.35 * LC1 + 1.00 * LC7

Normal load

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 11 / 19
Version: 1.13.1

Solution: Case-5-7-10 Date: 28/02/2024

Shear load in Y direction

Shear load in Z direction

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 12 / 19
Version: 1.13.1

Solution: Case-5-7-10 Date: 28/02/2024

Torsion around X

Moment around Y

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 13 / 19
Version: 1.13.1

Solution: Case-5-7-10 Date: 28/02/2024

Moment around Z

5.2.3 Stability Analysis

Buckling ratio

Buckling Max. lateral torsional Max. buckling under Max.


Member Length
Length Buckling ratio buckling under bending compression interaction
No. [mm]
[mm] [%] [%] [%]
1 650.00 1300.00 2.00 0.00 1.19 1.19

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 14 / 19
Version: 1.13.1

Solution: Case-5-7-10 Date: 28/02/2024

5.2.4 Deflection Analysis

Criteria
☑Maximum Allowable Deflection (Beam) L/200
☑Maximum Allowable Deflection (Cantilever)L/150
- Maximum Deflection (Absolute) -
☑No Deflection checks calculated for 1.50mm

Overview

Results
Reference
Member Max deflection Utilization
Load Combination number* Governing criteria Length Limit
No. [mm] [%]
[mm]
1 004-SLS Relative(Cantilever) 650.00 L/150 1.69 39.03

*004-SLS: SW + Design Loads. Respective Combination Equation: 1.00 * LC1 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 15 / 19
Version: 1.13.1

Solution: Case-5-7-10 Date: 28/02/2024

Deflection 1.00 * LC1

Deflection 1.00 * LC1 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 16 / 19
Version: 1.13.1

Solution: Case-5-7-10 Date: 28/02/2024

5.3 System Connectors

5.3 Connectors

5.3.1 Overview

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 17 / 19
Version: 1.13.1

Solution: Case-5-7-10 Date: 28/02/2024

5.4 Base Connectors

5.4 Bases

5.4.1 Overview

Base connector: MT-B-T OC


Fx Fy Fz Mx My Mz
Connector variant: MT-B-T OC (E)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 1
Local Forces: -0.13 0.00 0.00 0.00 -0.03 0.00
Resistance: 12.60 1.61 8.57 0.08 0.09 0.05
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 34.48 % OK
Governing Load
1.35 * LC1 + 1.00 * LC7
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 18 / 19
Version: 1.13.1

Solution: Case-5-7-10 Date: 28/02/2024

6 Remarks, Your Cooperation Duties

Any and all information and data contained in the Software concern solely the use of Hilti products and based on the principles, formulas and security
regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly complied with by
the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the relevant Hilti product.
The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole
responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole responsibility for
having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior
to using them for your specific facility. The Software servers only as an aid to interpret norms and permits without any guarantee as to the absence of
errors, the correctness and relevance ot the results or suitability for a specific application.

You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular
backup of programs and, if applicable, carry out the updates of that you are using the current and thus up-to-date version of the Software in each case
by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or
programs, arising from a culpable breach of duty by you.

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 19 / 19
Case-6

Project: SA-13082-SF

Submitted by:

Hilti contact information


Contact name:
Contact e-mail:
Contact phone:
Contact company:

Customer contact information


Customer name:
Customer e-mail:
Customer phone:
Customer company:

Date: 28/02/2024

This submittal is auto-generated based on user-selected inputs.


Therefore, Hilti no representation as to the suitability of these systems for their intended use. 1 / 23
Version: 1.13.1

Solution: Case-6 Date: 28/02/2024

Table of content

1 Geometry and Application


1.1 Supports
1.2 Nodes
1.3 Members
1.4 Connections
1.5 Release Conditions
1.6 Media Interface Channel
1.7 Gliders
2 Part list
2.1 Members
2.2 Base Connectors
2.3 System Connectors
2.4 Other
3 Load Types
3.1 Loading objects
3.2 Point Loads
3.3 Distributed loads
3.4 Area loads
4 Load Combinations
4.1 Ultimate Limit State
4.2 Serviceability Limit State
5 Results
5.1 Calculation summary
5.2 Members
5.3 System Connectors
5.4 Base Connectors
6 Remarks, Your Cooperation Duties

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 2 / 23
Version: 1.13.1

Solution: Case-6 Date: 28/02/2024

1 Geometry and Application

Support Details
Modular Support Spacing [mm] Undefined

Intermediate Supports required?

Pipe Fasteners with Glider and Presetting used? (See


subchapter 'Gliders' in chapter 'Geometry and
Application')

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 3 / 23
Version: 1.13.1

Solution: Case-6 Date: 28/02/2024

1.1 Supports - Concrete

Concrete

Thickness Drilling Depth


Node No. No. Orientation Concrete grade
[mm] [mm]
1 1 Horizontal C20/25 200.00 150
5 2 Horizontal C20/25 200.00 150

1.2 Nodes

X Y Z
No. No. Connector name Connector variant
[mm] [mm] [mm]
1 1 -190.75 0.00 -500.00 MT-B-GS T OC MT-B-GS T OC (C_MT-70)
2 - -190.75 0.00 -43.10 MT-C-GS A OC MT-C-GS A OC (C_CS)
3 - 709.25 0.00 -43.10 MT-C-GS A OC MT-C-GS A OC (C_CS)
5 2 709.25 0.00 -500.00 MT-B-GS T OC MT-B-GS T OC (C_MT-70)

1.3 Members

Member Releases Rotation


No. Node start Node end Member Name
Start End [°]
1 2 3 1 2 MT-70 180.00
2 1 4 - - MT-70 0.00
3 5 6 - - MT-70 0.00

1.4 Connections

Cross- Cross- Cross- Cross-


Section/Rotation Section/Rotation Section/Rotation Section/Rotation
Node No. Description Variant
Arm1 Arm2 Arm3 Arm4
[-/°] [-/°] [-/°] [-/°]
MT-B-GS T OC
1 MT-B-GS T OC MT-70/0 - - -
(C_MT-70)
MT-C-GS A OC
2 MT-C-GS A OC MT-70/180 MT-70/0 - -
(C_CS)
MT-C-GS A OC
3 MT-C-GS A OC MT-70/180 MT-70/0 - -
(C_CS)
MT-B-GS T OC
5 MT-B-GS T OC MT-70/0 - - -
(C_MT-70)

1.5 Release Conditions

Spring Constants
Releases
Member Translational Rotational
No. Cu,x Cu,y Cu,z Cφx Cφy Cφz
Ux Uy Uz φx φy φz
[kN/m] [kN/m] [kN/m] [kNm/Rad] [kNm/Rad] [kNm/Rad]
1 no no no no yes yes - - - - 0.001 0.001
1 no no no no yes yes - - - - 0.001 0.001

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 4 / 23
Version: 1.13.1

Solution: Case-6 Date: 28/02/2024

1.6 Media Interface Channel

Start Position Length


No. Member No. Media Interface Z-Position Y-Position
[mm] [mm]

1.7 Gliders

Position Start Travel


No. Member No. Glider Custom Load
[mm] [mm] [mm]

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 5 / 23
Version: 1.13.1

Solution: Case-6 Date: 28/02/2024

2 Part list

2.1 Members

Quantity Weight Length


Position Item Number Description Cutting type
[-] [kg] [mm]
1 2268365 I.-Girder MT-70 OC 1 3.32 850.00 N - None
2 2268365 I.-Girder MT-70 OC 2 5.41 691.92 N - None

2.2 Base Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
3 2272100 Baseplate MT-B-GS T OC 2 4.33

2.3 System Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
6 2272068 Angle connector MT-C-GS A OC adjustable 2 0.78

2.4 Other

Quantity Weight
Position Item Number Description
[-] [kg]
4 2272084 Thread forming bolt MT-TFB OC 20 0.57
5 2105870 Stud anchor HST3-R M12x115 40/20 4 0.41

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 6 / 23
Version: 1.13.1

Solution: Case-6 Date: 28/02/2024

3 Load Types

3. Loads

Custom loads

Load No. Load Distribution Load Case Load Type Comments


1 Point load LC 7: Design Permanent -
2 Point load LC 7: Design Permanent -
3 Point load LC 13: Seismic (+x) Seismic -
4 Point load LC 14: Seismic (-x) Seismic -
5 Point load LC 13: Seismic (+x) Seismic -
6 Point load LC 14: Seismic (-x) Seismic -
7 Point load LC 2: Pipe Permanent -
8 Point load LC 2: Pipe Permanent -
9 Point load LC 7: Design Permanent -
10 Point load LC 7: Design Permanent -

3.2 Point Loads

Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
1 Design 1 250.00 0.00 0.00 -4.88 0.00 0.00 0.00
2 Design 1 650.00 0.00 0.00 -4.88 0.00 0.00 0.00
3 Seismic (+x) 1 250.00 0.05 0.00 0.00 0.00 0.00 0.00
4 Seismic (-x) 1 250.00 -0.05 -0.00 -0.00 -0.00 -0.00 -0.00
5 Seismic (+x) 1 650.00 0.05 0.00 0.00 0.00 0.00 0.00
6 Seismic (-x) 1 650.00 -0.05 -0.00 -0.00 -0.00 -0.00 -0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 7 / 23
Version: 1.13.1

Solution: Case-6 Date: 28/02/2024


Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
9 Pipe 1 250.00 0.49 0.49 0.00 0.00 0.00 0.00
10 Pipe 1 650.00 0.49 0.49 0.00 0.00 0.00 0.00
13 Design 2 585.00 0.00 0.00 -0.11 0.00 0.03 0.00
14 Design 3 585.00 0.00 0.00 -0.11 0.00 -0.03 0.00
15 Self Weight Support 2 0.00 0.00 0.00 -0.02 0.00 0.00 0.00
16 Self Weight Support 1 0.00 0.00 0.00 -0.00 0.00 0.00 0.00
17 Self Weight Support 1 900.00 0.00 0.00 -0.00 0.00 0.00 0.00
18 Self Weight Support 3 0.00 0.00 0.00 -0.02 0.00 0.00 0.00

3.3 Distributed loads

Start End
Fx Fy Fz Mx My Mz
Load No. Load Type Members Position Position
[kN/m] [kN/m] [kN/m] [kNm/m] [kNm/m] [kNm/m]
[mm] [mm]
19 Self Weight Support 1 0.00 900.00 0.00 0.00 -0.04 0.00 0.00 0.00
20 Self Weight Support 2 0.00 700.00 0.00 0.00 -0.04 0.00 0.00 0.00
21 Self Weight Support 3 0.00 700.00 0.00 0.00 -0.04 0.00 0.00 0.00

3.4 Area loads

3.4.1 User input

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 8 / 23
Version: 1.13.1

Solution: Case-6 Date: 28/02/2024

4 Load Combinations

Design base EN 1993

Load combination design base EN 1990

4.1 Ultimate Limit State

Design base Load combination and safety factors


ULS - 001a-ULS: SW_inf (Support Only) 1.00 * LC1
ULS - 001b-ULS: SW_sup (Support Only) 1.35 * LC1
ULS - 002a-ULS: SW_inf Support + Media 1.00 * LC1 + 1.00 * LC2
ULS - 002b-ULS: SW_sup Support + Media 1.35 * LC1 + 1.35 * LC2
ULS - 004a-ULS: SW_inf + Design Loads 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC7
ULS - 004b-ULS: SW_sup + Design Loads 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
ULS - 027a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC13
z) + Live + Snow
ULS - 027b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC14
+ Live + Snow
ULS - 029a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC13
z) + Live + Snow
ULS - 030a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC14
+ Live + Snow
ULS - 027a-ULS_Base : SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 027b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 029a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 030a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 031a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC13 + 1.00 * 0.74 * LC7
z) + Design
ULS - 031b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC14 + 1.00 * 0.74 * LC7
+ Design
ULS - 033a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC13 + 1.00 * 0.74 * LC7
z) + Design
ULS - 034a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC14 + 1.00 * 0.74 * LC7
+ Design
ULS - 032a-ULS_Base: SW + Seismic (+x) + Seismic (-y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC13 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 031b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC14 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 033a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC13 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 034a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC14 + 1.00 * 0.74 * LC7
Seismic (-z) + Design

4.2 Serviceability Limit State

Load Case Load combination and safety factors


SLS - 001-SLS: SW (Support Only) 1.00 * LC1
SLS - 002-SLS: SW Support + Media Objects 1.00 * LC1 + 1.00 * LC2
SLS - 004-SLS: SW + Design Loads 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 9 / 23
Version: 1.13.1

Solution: Case-6 Date: 28/02/2024

5 Results

5.1 Calculation summary

5.1.3 Members

Governing load ULS SLS


No Member Status
combination number* [%] [%]
2 MT-70 004-SLS 67.73 53.66 OK
11 MT-70 004b-ULS 31.08 - OK
13 MT-70 004b-ULS 32.32 - OK

5.1.2 Base Connectors

Governing load ULS SLS


No Base connector Status
combination number* [%] [%]
1 MT-B-GS T OC 004b-ULS 52.74 - OK
5 MT-B-GS T OC 004b-ULS 52.94 - OK

5.1.3 System Connectors

Governing load ULS SLS


No Connector Status
combination number* [%] [%]
2 MT-C-GS A OC 004b-ULS 53.48 - OK
3 MT-C-GS A OC 004b-ULS 57.86 - OK
*004-SLS: SW + Design Loads . Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7
*004b-ULS: SW_sup + Design Loads . Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7

Overall Status: Calculation OK, design criteria met!

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 10 / 23
Version: 1.13.1

Solution: Case-6 Date: 28/02/2024

5.2 Members

5.2.1 Member Properties


5.2.1.1 MT-70 Members: 1, 2, 3
5.2.1.1.1 Section properties
t A Iy Iz It
[mm] [mm²] [mm⁴] [mm⁴] [mm⁴]
2.75 428.78 158700.00 158700.00 297500.00

Iω M Wy Wz Wy
[mm⁶] [kg/m] [mm³] [mm³] [mm³]
2039000.00 3.91 -6349.48 -6349.48 -6349.48

5.2.1.1.2 Material properties


E G Fu Fy Fy.cold
Steel grade
[N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²]
S350GD 1.0529 210000.00 80769.00 420.00 350.00 350.00

5.2.2 Member Design

5.2.2.1 Overview

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 11 / 23
Version: 1.13.1

Solution: Case-6 Date: 28/02/2024

5.2.2.2 Stress Analysis

5.2.2.2.1 Table of Results

Load Combination σ τ σeqv σlimit τlimit Utilization


No. Member
number* [N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²] [%]
1 I.-Girder MT-70 OC 004b-ULS -214.89 31.66 215.52 318.18 183.70 67.73
2 I.-Girder MT-70 OC 004b-ULS -98.89 0.00 98.89 318.18 0.00 31.08
3 I.-Girder MT-70 OC 004b-ULS -102.82 5.06 102.82 318.18 183.70 32.32

*004b-ULS: SW_sup + Design Loads. Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 12 / 23
Version: 1.13.1

Solution: Case-6 Date: 28/02/2024

5.2.2.2 Governing Member Loading

Beam No. 1

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-70 0.00 004b-ULS 0.57 -0.66 4.90 0.00 -0.00 -0.00
MT-70 180.00 004b-ULS 0.57 -0.66 4.89 0.00 0.88 0.12
MT-70 250.00(-) 004b-ULS 0.57 -0.66 4.89 0.00 1.22 0.17
MT-70 250.00(+) 004b-ULS -0.09 0.00 0.01 0.00 1.22 0.17
MT-70 360.00 004b-ULS -0.09 0.00 0.00 0.00 1.23 0.17
MT-70 540.00 004b-ULS -0.09 0.00 -0.00 0.00 1.23 0.17
MT-70 650.00(-) 004b-ULS -0.09 0.00 -0.01 0.00 1.22 0.17
MT-70 650.00(+) 004b-ULS -0.76 0.66 -4.89 0.00 1.22 0.17
MT-70 720.00 004b-ULS -0.76 0.66 -4.89 0.00 0.88 0.12
MT-70 900.00 004b-ULS -0.76 0.66 -4.90 0.00 -0.00 -0.00

Beam No. 2

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-70 0.00 004b-ULS -5.06 0.66 -0.57 0.00 0.29 0.30
MT-70 140.00 004b-ULS -5.05 0.66 -0.57 0.00 0.21 0.21
MT-70 280.00 004b-ULS -5.04 0.66 -0.57 0.00 0.13 0.12
MT-70 420.00 004b-ULS -5.03 0.66 -0.57 0.00 0.05 0.02
MT-70 456.90(-) 004b-ULS -5.03 0.66 -0.57 0.00 0.03 0.00
MT-70 456.90(+) 004b-ULS -0.12 0.00 0.00 0.00 0.03 -0.00
MT-70 560.00 004b-ULS -0.12 0.00 0.00 0.00 0.03 -0.00
MT-70 585.00(-) 004b-ULS -0.12 0.00 0.00 0.00 0.03 -0.00
MT-70 585.00(+) 004b-ULS -0.01 0.00 0.00 0.00 0.00 -0.00
MT-70 700.00 004b-ULS -0.00 0.00 0.00 0.00 0.00 -0.00

Beam No. 3

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-70 0.00 004b-ULS -5.06 0.66 -0.76 -0.00 0.32 0.30
MT-70 140.00 004b-ULS -5.05 0.66 -0.76 -0.00 0.21 0.21
MT-70 280.00 004b-ULS -5.04 0.66 -0.76 -0.00 0.10 0.12
MT-70 420.00 004b-ULS -5.03 0.66 -0.76 -0.00 -0.00 0.02
MT-70 456.90(-) 004b-ULS -5.03 0.66 -0.76 -0.00 -0.03 0.00
MT-70 456.90(+) 004b-ULS -0.12 0.00 0.00 0.00 -0.03 -0.00
MT-70 560.00 004b-ULS -0.12 0.00 0.00 0.00 -0.03 -0.00
MT-70 585.00(-) 004b-ULS -0.12 0.00 0.00 0.00 -0.03 -0.00
MT-70 585.00(+) 004b-ULS -0.01 0.00 0.00 0.00 0.00 -0.00
MT-70 700.00 004b-ULS -0.00 0.00 0.00 0.00 0.00 -0.00

*004b-ULS: SW_sup + Design Loads. Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 13 / 23
Version: 1.13.1

Solution: Case-6 Date: 28/02/2024

Normal load

Shear load in Y direction

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 14 / 23
Version: 1.13.1

Solution: Case-6 Date: 28/02/2024

Shear load in Z direction

Torsion around X

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 15 / 23
Version: 1.13.1

Solution: Case-6 Date: 28/02/2024

Moment around Y

Moment around Z

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 16 / 23
Version: 1.13.1

Solution: Case-6 Date: 28/02/2024

5.2.3 Stability Analysis

Buckling ratio

Buckling Max. lateral torsional Max. buckling under Max.


Member Length
Length Buckling ratio buckling under bending compression interaction
No. [mm]
[mm] [%] [%] [%]
1 900.00 900.00 1.00 0.00 0.76 0.76
2 700.00 1400.00 2.00 0.00 6.81 6.81
3 700.00 1400.00 2.00 0.00 6.81 6.81

5.2.4 Deflection Analysis

Criteria
☑Maximum Allowable Deflection (Beam) L/200
☑Maximum Allowable Deflection (Cantilever)L/150
- Maximum Deflection (Absolute) -
☑No Deflection checks calculated for 1.50mm

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 17 / 23
Version: 1.13.1

Solution: Case-6 Date: 28/02/2024

Overview

Results
Reference
Member Max deflection Utilization
Load Combination number* Governing criteria Length Limit
No. [mm] [%]
[mm]
1 004-SLS Relative (Beam) 900.00 L/200 2.41 53.66
2 004-SLS Relative (Beam) 700.00 L/200 -0.09 0.00
3 004-SLS Relative (Beam) 700.00 L/200 -0.02 0.00

*004-SLS: SW + Design Loads. Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 18 / 23
Version: 1.13.1

Solution: Case-6 Date: 28/02/2024

Deflection 1.00 * LC1

Deflection 1.00 * LC1 + 1.00 * LC2

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 19 / 23
Version: 1.13.1

Solution: Case-6 Date: 28/02/2024

Deflection 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 20 / 23
Version: 1.13.1

Solution: Case-6 Date: 28/02/2024

5.3 System Connectors

5.3 Connectors

5.3.1 Overview

Connector: MT-C-GS A OC
Fx Fy Fz Mx My Mz
Connector variant: MT-C-GS A OC (C_CS)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 3
Local Forces: -0.76 0.66 4.90 0.00 -0.00 0.00
Resistance: 7.30 3.64 16.71 0.16 0.43 0.13
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 57.86 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 21 / 23
Version: 1.13.1

Solution: Case-6 Date: 28/02/2024

5.4 Base Connectors

5.4 Bases

5.4.1 Overview

Base connector: MT-B-GS T OC


Fx Fy Fz Mx My Mz
Connector variant: MT-B-GS T OC (C_MT-70)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 5
Local Forces: -5.08 -0.66 0.76 -0.00 -0.32 -0.30
Resistance: 67.64 18.22 24.39 0.84 1.93 1.35
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 52.94 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 22 / 23
Version: 1.13.1

Solution: Case-6 Date: 28/02/2024

6 Remarks, Your Cooperation Duties

Any and all information and data contained in the Software concern solely the use of Hilti products and based on the principles, formulas and security
regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly complied with by
the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the relevant Hilti product.
The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole
responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole responsibility for
having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior
to using them for your specific facility. The Software servers only as an aid to interpret norms and permits without any guarantee as to the absence of
errors, the correctness and relevance ot the results or suitability for a specific application.

You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular
backup of programs and, if applicable, carry out the updates of that you are using the current and thus up-to-date version of the Software in each case
by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or
programs, arising from a culpable breach of duty by you.

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 23 / 23
Case-8

Project: SA-13082-SF

Submitted by:

Hilti contact information


Contact name:
Contact e-mail:
Contact phone:
Contact company:

Customer contact information


Customer name:
Customer e-mail:
Customer phone:
Customer company:

Date: 28/02/2024

This submittal is auto-generated based on user-selected inputs.


Therefore, Hilti no representation as to the suitability of these systems for their intended use. 1 / 26
Version: 1.13.1

Solution: Case-8 Date: 28/02/2024

Table of content

1 Geometry and Application


1.1 Supports
1.2 Nodes
1.3 Members
1.4 Connections
1.5 Release Conditions
1.6 Media Interface Channel
1.7 Gliders
2 Part list
2.1 Members
2.2 Base Connectors
2.3 System Connectors
2.4 Other
3 Load Types
3.1 Loading objects
3.2 Point Loads
3.3 Distributed loads
3.4 Area loads
4 Load Combinations
4.1 Ultimate Limit State
4.2 Serviceability Limit State
5 Results
5.1 Calculation summary
5.2 Members
5.3 System Connectors
5.4 Base Connectors
6 Remarks, Your Cooperation Duties

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 2 / 26
Version: 1.13.1

Solution: Case-8 Date: 28/02/2024

1 Geometry and Application

Support Details
Modular Support Spacing [mm] Undefined

Intermediate Supports required?

Pipe Fasteners with Glider and Presetting used? (See


subchapter 'Gliders' in chapter 'Geometry and
Application')

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 3 / 26
Version: 1.13.1

Solution: Case-8 Date: 28/02/2024

1.1 Supports - Concrete

Concrete

Thickness Drilling Depth


Node No. No. Orientation Concrete grade
[mm] [mm]
1 1 Horizontal C20/25 200.00 150
4 2 Horizontal C20/25 200.00 150
6 3 Horizontal C20/25 200.00 150
8 4 Horizontal C20/25 200.00 150

1.2 Nodes

X Y Z
No. No. Connector name Connector variant
[mm] [mm] [mm]
1 1 -190.75 0.00 -500.00 MT-B-O2B MT-B-O2B (C)
2 - -190.75 0.00 677.75 MT-C-LL1 MT-C-LL1 (C)
3 - 709.25 0.00 677.75 MT-C-LL1 MT-C-LL1 (C)
4 2 709.25 0.00 -500.00 MT-B-O2B MT-B-O2B (C)
5 - 709.25 0.00 88.87 MT-AB-LL2 45 MT-AB-LL2 45 (E)
6 3 709.25 588.87 -500.00 MT-AB A MT-AB A (C)
7 - -190.75 0.00 88.87 MT-AB-LL2 45 MT-AB-LL2 45 (E)
8 4 -190.75 588.87 -500.00 MT-AB A MT-AB A (C)

1.3 Members

Member Releases Rotation


No. Node start Node end Member Name
Start End [°]
1 1 2 - 1 MT-40D 180.00
2 2 3 1 2 MT-40 0.00
3 3 4 2 - MT-40D 180.00
4 5 6 3 4 MT-40 0.00
5 7 8 5 6 MT-40 0.00

1.4 Connections

Cross- Cross- Cross- Cross-


Section/Rotation Section/Rotation Section/Rotation Section/Rotation
Node No. Description Variant
Arm1 Arm2 Arm3 Arm4
[-/°] [-/°] [-/°] [-/°]
1 MT-B-O2B MT-B-O2B (C) MT-40D/180 - - -
2 MT-C-LL1 MT-C-LL1 (C) MT-40D/180 MT-40/0 - -
3 MT-C-LL1 MT-C-LL1 (C) MT-40/0 MT-40D/180 - -
4 MT-B-O2B MT-B-O2B (C) MT-40D/180 - - -
5 MT-AB-LL2 45 MT-AB-LL2 45 (E) MT-40D/180 MT-40/0 - -
6 MT-AB A MT-AB A (C) MT-40/0 - - -
7 MT-AB-LL2 45 MT-AB-LL2 45 (E) MT-40D/180 MT-40/0 - -
8 MT-AB A MT-AB A (C) MT-40/0 - - -

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 4 / 26
Version: 1.13.1

Solution: Case-8 Date: 28/02/2024

1.5 Release Conditions

Spring Constants
Releases
Member Translational Rotational
No. Cu,x Cu,y Cu,z Cφx Cφy Cφz
Ux Uy Uz φx φy φz
[kN/m] [kN/m] [kN/m] [kNm/Rad] [kNm/Rad] [kNm/Rad]
2 no no no no yes yes - - - - 0.001 0.001
2 no no no no yes yes - - - - 0.001 0.001
4 no no no no yes yes - - - - 0.000 0.000
4 no no no no yes yes - - - - 0.000 0.000
5 no no no no yes yes - - - - 0.000 0.000
5 no no no no yes yes - - - - 0.000 0.000

1.6 Media Interface Channel

Start Position Length


No. Member No. Media Interface Z-Position Y-Position
[mm] [mm]

1.7 Gliders

Position Start Travel


No. Member No. Glider Custom Load
[mm] [mm] [mm]

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 5 / 26
Version: 1.13.1

Solution: Case-8 Date: 28/02/2024

2 Part list

2.1 Members

Quantity Weight Length


Position Item Number Description Cutting type
[-] [kg] [mm]
1 2268518 I.-Channel MT-40D 2 10.52 1253.00 N - None
2 2268506 I.-Channel MT-40 1 1.66 815.00 N - None
3 2268506 I.-Channel MT-40 1 1.60 782.76 N - None
4 2268506 I.-Channel MT-40 1 1.60 782.30 N - None

2.2 Base Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
5 2282212 2-hole Baseplate MT-B-O2B 2 4.14
11 2346395 Angle brace MT-AB A set adjustable 2 0.88

2.3 System Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
9 2272047 Angle connector MT-C-LL1 2 0.67
10 2272115 Angle brace MT-AB-LL2 45 2 1.11

2.4 Other

Quantity Weight
Position Item Number Description
[-] [kg]
6 2273254 Hexagon bolt MT-TLB 20 0.50
7 2272080 Twist-Lock MT-TL M10 20 0.70
8 2105719 Stud anchor HST3 M12x115 40/20 8 0.80

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 6 / 26
Version: 1.13.1

Solution: Case-8 Date: 28/02/2024

3 Load Types

3. Loads

Custom loads

Load No. Load Distribution Load Case Load Type Comments


1 Point load LC 7: Design Permanent -
2 Point load LC 7: Design Permanent -
3 Point load LC 8: Wind (+x) Variable -
4 Point load LC 9: Wind (-x) Variable -
5 Point load LC 13: Seismic (+x) Seismic -
6 Point load LC 14: Seismic (-x) Seismic -
7 Point load LC 14: Seismic (-x) Seismic -
8 Point load LC 13: Seismic (+x) Seismic -
9 Point load LC 2: Pipe Permanent -
10 Point load LC 2: Pipe Permanent -
11 Point load LC 2: Pipe Permanent -
12 Point load LC 2: Pipe Permanent -

3.2 Point Loads

Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
1 Design 2 275.00 0.00 0.00 -1.79 0.00 0.00 0.00
2 Design 2 673.50 0.00 0.00 -1.79 0.00 0.00 0.00
3 Wind (+x) 2 474.25 0.53 -0.00 -0.00 -0.00 -0.00 -0.00
4 Wind (-x) 2 474.25 -0.53 -0.00 -0.00 -0.00 -0.00 -0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 7 / 26
Version: 1.13.1

Solution: Case-8 Date: 28/02/2024


Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
5 Seismic (+x) 2 275.00 0.02 -0.00 -0.00 -0.00 -0.00 -0.00
6 Seismic (-x) 2 275.00 -0.02 -0.00 -0.00 -0.00 -0.00 -0.00
7 Seismic (-x) 2 673.50 0.02 -0.00 -0.00 -0.00 -0.00 -0.00
8 Seismic (+x) 2 673.50 -0.02 -0.00 -0.00 -0.00 -0.00 -0.00
9 Pipe 2 673.50 0.00 0.18 0.00 0.00 0.00 0.00
10 Pipe 2 275.00 0.00 0.18 0.00 0.00 0.00 0.00
11 Pipe 2 275.00 0.18 0.00 0.00 0.00 0.00 0.00
12 Pipe 2 673.50 0.18 0.00 0.00 0.00 0.00 0.00
13 Self Weight Support 1 0.00 0.00 0.00 -0.02 0.00 0.00 0.00
14 Self Weight Support 1 1177.75 0.00 0.00 -0.00 0.00 0.00 0.00
15 Self Weight Support 2 900.00 0.00 0.00 -0.00 0.00 0.00 0.00
16 Self Weight Support 3 1177.75 0.00 0.00 -0.02 0.00 0.00 0.00
17 Self Weight Support 3 588.88 0.00 0.00 -0.01 0.00 0.00 0.00
18 Self Weight Support 4 832.79 0.00 0.00 -0.00 0.00 0.00 0.00
19 Self Weight Support 1 588.87 0.00 0.00 -0.01 0.00 0.00 0.00
20 Self Weight Support 5 832.79 0.00 0.00 -0.00 0.00 0.00 0.00

3.3 Distributed loads

Start End
Fx Fy Fz Mx My Mz
Load No. Load Type Members Position Position
[kN/m] [kN/m] [kN/m] [kNm/m] [kNm/m] [kNm/m]
[mm] [mm]
21 Self Weight Support 1 0.00 1177.75 0.00 0.00 -0.04 0.00 0.00 0.00
22 Self Weight Support 2 0.00 900.00 0.00 0.00 -0.02 0.00 0.00 0.00
23 Self Weight Support 3 0.00 1177.75 0.00 0.00 -0.04 0.00 0.00 0.00
24 Self Weight Support 4 0.00 832.79 0.00 0.00 -0.02 0.00 0.00 0.00
25 Self Weight Support 5 0.00 832.79 0.00 0.00 -0.02 0.00 0.00 0.00

3.4 Area loads

3.4.1 User input

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 8 / 26
Version: 1.13.1

Solution: Case-8 Date: 28/02/2024

4 Load Combinations

Design base EN 1993

Load combination design base EN 1990

4.1 Ultimate Limit State

Design base Load combination and safety factors


ULS - 001a-ULS: SW_inf (Support Only) 1.00 * LC1
ULS - 001b-ULS: SW_sup (Support Only) 1.35 * LC1
ULS - 002a-ULS: SW_inf Support + Media 1.00 * LC1 + 1.00 * LC2
ULS - 002b-ULS: SW_sup Support + Media 1.35 * LC1 + 1.35 * LC2
ULS - 004a-ULS: SW_inf + Design Loads 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC7
ULS - 004b-ULS: SW_sup + Design Loads 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
ULS - 006a-ULS: SW_inf + Wind (+x) 1.00 * LC1 + 1.00 * LC2 + 1.50 * LC8
ULS - 006b-ULS: SW_sup + Wind (+x) 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8
ULS - 007a-ULS: SW_inf + Wind (-x) 1.00 * LC1 + 1.00 * LC2 + 1.50 * LC9
ULS - 007b-ULS: SW_sup + Wind (-x) 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC9
ULS - 015a-ULS: SW_inf + Live + Snow + Wind (+x) 1.00 * LC1 + 1.00 * LC2 + 1.50 * 0.60 * LC8
ULS - 015b-ULS: SW_sup + Live + Snow + Wind (+x) 1.35 * LC1 + 1.35 * LC2 + 1.50 * 0.60 * LC8
ULS - 016a-ULS: SW_inf + Live + Snow + Wind (-x) 1.00 * LC1 + 1.00 * LC2 + 1.50 * 0.60 * LC9
ULS - 016b-ULS: SW_sup + Live + Snow + Wind (-x) 1.35 * LC1 + 1.35 * LC2 + 1.50 * 0.60 * LC9
ULS - 027a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC13
z) + Live + Snow
ULS - 027b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC14
+ Live + Snow
ULS - 029a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC13
z) + Live + Snow
ULS - 030a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC14
+ Live + Snow
ULS - 027a-ULS_Base : SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 027b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 029a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 030a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 031a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC13 + 1.00 * 0.74 * LC7
z) + Design
ULS - 031b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC14 + 1.00 * 0.74 * LC7
+ Design
ULS - 033a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC13 + 1.00 * 0.74 * LC7
z) + Design
ULS - 034a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC14 + 1.00 * 0.74 * LC7
+ Design
ULS - 032a-ULS_Base: SW + Seismic (+x) + Seismic (-y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC13 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 031b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC14 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 033a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC13 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 034a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC14 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 037-ULS: SW_inf + Impact + Live + Snow 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.20 * LC8
ULS - 038-ULS: SW_inf + Impact + Live + Snow 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.20 * LC9

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 9 / 26
Version: 1.13.1

Solution: Case-8 Date: 28/02/2024

4.2 Serviceability Limit State

Load Case Load combination and safety factors


SLS - 001-SLS: SW (Support Only) 1.00 * LC1
SLS - 002-SLS: SW Support + Media Objects 1.00 * LC1 + 1.00 * LC2
SLS - 004-SLS: SW + Design Loads 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7
SLS - 006-SLS: SW + Wind (+x) 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC8
SLS - 007-SLS: SW + Wind (-x) 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC9
SLS - 015-SLS: SW + Live + Snow + Wind (+x) 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC8
SLS - 016-SLS: SW + Live + Snow + Wind (-x) 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC9

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 10 / 26
Version: 1.13.1

Solution: Case-8 Date: 28/02/2024

5 Results

5.1 Calculation summary

5.1.3 Members

Governing load ULS SLS


No Member Status
combination number* [%] [%]
1 MT-40D 006-SLS 42.52 49.76 OK
2 MT-40 004-SLS 80.65 53.38 OK
3 MT-40D 006-SLS 42.90 49.77 OK
6 MT-40 004b-ULS 8.47 - OK
9 MT-40 004b-ULS 7.62 - OK

5.1.2 Base Connectors

Governing load ULS SLS


No Base connector Status
combination number* [%] [%]
1 MT-B-O2B 006b-ULS 74.49 - OK
4 MT-B-O2B 006b-ULS 77.07 - OK
6 MT-AB A 001b-ULS 12.00 - OK
8 MT-AB A 001b-ULS 12.00 - OK

5.1.3 System Connectors

Governing load ULS SLS


No Connector Status
combination number* [%] [%]
2 MT-C-LL1 004b-ULS 42.62 - OK
3 MT-C-LL1 004b-ULS 47.16 - OK
5 MT-AB-LL2 45 004b-ULS 8.82 - OK
7 MT-AB-LL2 45 001b-ULS 8.00 - OK
*006-SLS: SW + Wind (+x) . Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC8
*004-SLS: SW + Design Loads . Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7
*004b-ULS: SW_sup + Design Loads . Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
*006b-ULS: SW_sup + Wind (+x) . Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8
*001b-ULS: SW_sup (Support Only) . Respective Combination Equation: 1.35 * LC1

Overall Status: Calculation OK, design criteria met!

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 11 / 26
Version: 1.13.1

Solution: Case-8 Date: 28/02/2024

5.2 Members

5.2.1 Member Properties


5.2.1.1 MT-40D Members: 1, 3
5.2.1.1.1 Section properties
t A Iy Iz It
[mm] [mm²] [mm⁴] [mm⁴] [mm⁴]
2.00 429.52 299600.00 131800.00 520.41

Iω M Wy Wz Wy
[mm⁶] [kg/m] [mm³] [mm³] [mm³]
154300000.00 8.40 -7048.65 -6199.90 -7048.65

5.2.1.1.2 Material properties


E G Fu Fy Fy.cold
Steel grade
[N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²]
Steel S 280 GD 210000.00 80769.00 360.00 280.00 305.00

5.2.1.2 MT-40 Members: 2, 4, 5


5.2.1.2.1 Section properties
t A Iy Iz It
[mm] [mm²] [mm⁴] [mm⁴] [mm⁴]
2.00 285.00 57717.48 65876.44 259.85

Iω M Wy Wz Wy
[mm⁶] [kg/m] [mm³] [mm³] [mm³]
38410000.00 2.04 -2652.65 -3099.95 -2652.65

5.2.1.2.2 Material properties


E G Fu Fy Fy.cold
Steel grade
[N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²]
Steel S 280 GD 210000.00 80769.00 360.00 280.00 305.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 12 / 26
Version: 1.13.1

Solution: Case-8 Date: 28/02/2024

5.2.2 Member Design

5.2.2.1 Overview

5.2.2.2 Stress Analysis

5.2.2.2.1 Table of Results

Load Combination σ τ σeqv σlimit τlimit Utilization


No. Member
number* [N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²] [%]
1 I.-Channel MT-40D 006b-ULS 114.65 17.91 114.67 277.27 160.08 41.36
2 I.-Channel MT-40 004b-ULS -193.01 19.61 193.01 277.27 160.08 69.61
3 I.-Channel MT-40D 006b-ULS 115.56 -18.88 115.58 277.27 160.08 41.69
4 I.-Channel MT-40 006b-ULS 0.00 0.68 4.77 0.00 160.08 1.72
5 I.-Channel MT-40 006b-ULS 0.00 0.68 4.37 0.00 160.08 1.58

*006b-ULS: SW_sup + Wind (+x). Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8

*004b-ULS: SW_sup + Design Loads. Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7

5.2.2.2 Governing Member Loading

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 13 / 26
Version: 1.13.1

Solution: Case-8 Date: 28/02/2024

Beam No. 1

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40D 0.00 006b-ULS 0.44 0.32 0.64 0.00 -0.75 0.05
MT-40D 235.55 006b-ULS 0.46 0.32 0.64 0.00 -0.60 -0.02
MT-40D 471.10 006b-ULS 0.47 0.32 0.64 0.00 -0.45 -0.10
MT-40D 588.87(-) 006b-ULS 0.48 0.32 0.64 0.00 -0.38 -0.14
MT-40D 588.87(+) 006b-ULS -0.05 -0.23 0.64 0.00 -0.38 -0.14
MT-40D 706.65 006b-ULS -0.04 -0.23 0.64 0.00 -0.30 -0.11
MT-40D 942.20 006b-ULS -0.03 -0.23 0.64 0.00 -0.15 -0.05
MT-40D 1177.75 006b-ULS -0.02 -0.23 0.64 0.00 0.00 -0.00

Beam No. 2

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40 0.00 004b-ULS 0.24 0.23 -1.71 -0.00 0.00 0.00
MT-40 180.00 004b-ULS 0.24 0.23 -1.70 -0.00 -0.31 -0.04
MT-40 275.00(-) 004b-ULS 0.24 0.23 -1.70 -0.00 -0.47 -0.06
MT-40 275.00(+) 004b-ULS -0.00 -0.01 0.09 -0.00 -0.47 -0.06
MT-40 360.00 004b-ULS -0.00 -0.01 0.09 -0.00 -0.46 -0.06
MT-40 540.00 004b-ULS -0.00 -0.01 0.10 -0.00 -0.44 -0.06
MT-40 673.50(-) 004b-ULS -0.00 -0.01 0.10 -0.00 -0.43 -0.06
MT-40 673.50(+) 004b-ULS -0.24 -0.26 1.89 -0.00 -0.43 -0.06
MT-40 720.00 004b-ULS -0.24 -0.26 1.89 -0.00 -0.34 -0.05
MT-40 900.00 004b-ULS -0.24 -0.26 1.90 -0.00 0.00 0.00

Beam No. 3

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40D 0.00 006b-ULS -0.02 0.26 0.64 -0.00 -0.00 0.00
MT-40D 235.55 006b-ULS -0.03 0.26 0.64 -0.00 0.15 -0.06
MT-40D 471.10 006b-ULS -0.04 0.26 0.64 -0.00 0.30 -0.12
MT-40D 588.88(-) 006b-ULS -0.05 0.26 0.64 -0.00 0.38 -0.15
MT-40D 588.88(+) 006b-ULS 0.54 -0.35 0.64 0.00 0.38 -0.15
MT-40D 706.65 006b-ULS 0.53 -0.35 0.64 0.00 0.45 -0.11
MT-40D 942.20 006b-ULS 0.52 -0.35 0.64 0.00 0.60 -0.03
MT-40D 1177.75 006b-ULS 0.51 -0.35 0.64 0.00 0.75 0.06

Beam No. 4

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40 0.00 004b-ULS -0.86 0.00 -0.01 -0.00 0.00 -0.00
MT-40 166.56 004b-ULS -0.86 0.00 -0.00 -0.00 -0.00 -0.00
MT-40 333.12 004b-ULS -0.86 0.00 -0.00 -0.00 -0.00 -0.00
MT-40 499.67 004b-ULS -0.87 0.00 0.00 -0.00 -0.00 -0.00
MT-40 666.23 004b-ULS -0.87 0.00 0.00 -0.00 -0.00 -0.00
MT-40 832.79 004b-ULS -0.87 0.00 0.01 -0.00 0.00 -0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 14 / 26
Version: 1.13.1

Solution: Case-8 Date: 28/02/2024

Beam No. 5

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40 0.00 004b-ULS -0.77 0.00 -0.01 -0.00 0.00 -0.00
MT-40 166.56 004b-ULS -0.77 0.00 -0.00 -0.00 -0.00 -0.00
MT-40 333.12 004b-ULS -0.78 0.00 -0.00 -0.00 -0.00 -0.00
MT-40 499.67 004b-ULS -0.78 0.00 0.00 -0.00 -0.00 -0.00
MT-40 666.23 004b-ULS -0.78 0.00 0.00 -0.00 -0.00 -0.00
MT-40 832.79 004b-ULS -0.79 0.00 0.01 -0.00 0.00 -0.00

*006b-ULS: SW_sup + Wind (+x). Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8

*004b-ULS: SW_sup + Design Loads. Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7

Normal load

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 15 / 26
Version: 1.13.1

Solution: Case-8 Date: 28/02/2024

Shear load in Y direction

Shear load in Z direction

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 16 / 26
Version: 1.13.1

Solution: Case-8 Date: 28/02/2024

Torsion around X

Moment around Y

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 17 / 26
Version: 1.13.1

Solution: Case-8 Date: 28/02/2024

Moment around Z

5.2.2.3 Shear Limits

Fy,Ed Fy,Rd Fz,Ed Fz,Rd Utilization


No. Type Load Combination number*
[kN] [kN] [kN] [kN] [%]
1 MT-40D 006b-ULS - - 0.64 4.25 15.07
3 MT-40D 006b-ULS - - 0.64 4.25 15.07

5.2.3 Stability Analysis

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 18 / 26
Version: 1.13.1

Solution: Case-8 Date: 28/02/2024

Buckling ratio

Buckling Max. lateral torsional Max. buckling under Max.


Member Length
Length Buckling ratio buckling under bending compression interaction
No. [mm]
[mm] [%] [%] [%]
1 1177.75 1177.75 1.00 42.52 0.00 42.52
2 900.00 900.00 1.00 73.21 1.11 80.65
3 1177.75 1177.75 1.00 42.90 0.00 42.90
4 832.79 1665.58 2.00 0.00 8.47 8.47
5 832.79 1665.58 2.00 0.00 7.62 7.62

5.2.4 Deflection Analysis

Criteria
☑Maximum Allowable Deflection (Beam) L/200
☑Maximum Allowable Deflection (Cantilever)L/150
- Maximum Deflection (Absolute) -
☑No Deflection checks calculated for 1.50mm

Overview

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 19 / 26
Version: 1.13.1

Solution: Case-8 Date: 28/02/2024

Results
Reference
Member Max deflection Utilization
Load Combination number* Governing criteria Length Limit
No. [mm] [%]
[mm]
1 006-SLS Relative(Cantilever) 1177.75 L/150 3.91 49.76
2 004-SLS Relative (Beam) 900.00 L/200 -2.40 53.38
3 006-SLS Relative(Cantilever) 1177.75 L/150 3.91 49.77
4 016-SLS Relative (Beam) 832.79 L/200 0.00 0.00
5 016-SLS Relative (Beam) 832.79 L/200 0.00 0.00

*006-SLS: SW + Wind (+x). Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC8

*004-SLS: SW + Design Loads. Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7

*016-SLS: SW + Live + Snow + Wind (-x). Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC9

Deflection 1.00 * LC1

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 20 / 26
Version: 1.13.1

Solution: Case-8 Date: 28/02/2024

Deflection 1.00 * LC1 + 1.00 * LC2

Deflection 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 21 / 26
Version: 1.13.1

Solution: Case-8 Date: 28/02/2024

Deflection 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC8

Deflection 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC9

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 22 / 26
Version: 1.13.1

Solution: Case-8 Date: 28/02/2024

Deflection 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC8

Deflection 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC9

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 23 / 26
Version: 1.13.1

Solution: Case-8 Date: 28/02/2024

5.3 System Connectors

5.3 Connectors

5.3.1 Overview

Connector: MT-C-LL1
Fx Fy Fz Mx My Mz
Connector variant: MT-C-LL1 (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 3
Local Forces: -0.24 -0.26 -1.90 -0.00 0.00 -0.00
Resistance: 8.20 1.24 8.06 0.03 0.19 0.03
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 47.16 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
Combination
Connector: MT-AB-LL2 45
Fx Fy Fz Mx My Mz
Connector variant: MT-AB-LL2 45 (E)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 5
Local Forces: -0.86 0.00 -0.01 -0.00 0.00 0.00
Resistance: 9.72 0.10 0.10 0.10 0.00 0.00
abs(Fx.ed/Fx.rd);abs(Fy.ed/Fy.rd);abs(Fz.ed/Fz.rd);abs(Mx.ed/Mx.rd);abs(My
Equation:
.ed/My.rd);abs(Mz.ed/Mz.rd)
Utilization: 8.82 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 24 / 26
Version: 1.13.1

Solution: Case-8 Date: 28/02/2024

5.4 Base Connectors

5.4 Bases

5.4.1 Overview

Base connector: MT-B-O2B


Fx Fy Fz Mx My Mz
Connector variant: MT-B-O2B (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 4
Local Forces: 0.48 -0.35 -0.64 0.00 0.75 -0.06
Resistance: 17.64 6.50 26.92 3.00 1.48 0.36
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 77.07 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8
Combination
Base connector: MT-AB A
Fx Fy Fz Mx My Mz
Connector variant: MT-AB A (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 6
Local Forces: -0.87 0.00 0.01 -0.00 0.00 0.00
Resistance: 13.86 0.10 0.10 0.10 0.00 0.00
abs(Fx.ed/Fx.rd);abs(Fy.ed/Fy.rd);abs(Fz.ed/Fz.rd);abs(Mx.ed/Mx.rd);abs(My
Equation:
.ed/My.rd);abs(Mz.ed/Mz.rd)
Utilization: 12.00 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.50 * 0.60 * LC9
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 25 / 26
Version: 1.13.1

Solution: Case-8 Date: 28/02/2024

6 Remarks, Your Cooperation Duties

Any and all information and data contained in the Software concern solely the use of Hilti products and based on the principles, formulas and security
regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly complied with by
the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the relevant Hilti product.
The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole
responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole responsibility for
having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior
to using them for your specific facility. The Software servers only as an aid to interpret norms and permits without any guarantee as to the absence of
errors, the correctness and relevance ot the results or suitability for a specific application.

You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular
backup of programs and, if applicable, carry out the updates of that you are using the current and thus up-to-date version of the Software in each case
by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or
programs, arising from a culpable breach of duty by you.

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 26 / 26
Case-9

Project: SA-13082-SF

Submitted by:

Hilti contact information


Contact name:
Contact e-mail:
Contact phone:
Contact company:

Customer contact information


Customer name:
Customer e-mail:
Customer phone:
Customer company:

Date: 28/02/2024

This submittal is auto-generated based on user-selected inputs.


Therefore, Hilti no representation as to the suitability of these systems for their intended use. 1 / 23
Version: 1.13.1

Solution: Case-9 Date: 28/02/2024

Table of content

1 Geometry and Application


1.1 Supports
1.2 Nodes
1.3 Members
1.4 Connections
1.5 Release Conditions
1.6 Media Interface Channel
1.7 Gliders
2 Part list
2.1 Members
2.2 Base Connectors
2.3 System Connectors
2.4 Other
3 Load Types
3.1 Loading objects
3.2 Point Loads
3.3 Distributed loads
3.4 Area loads
4 Load Combinations
4.1 Ultimate Limit State
4.2 Serviceability Limit State
5 Results
5.1 Calculation summary
5.2 Members
5.3 System Connectors
5.4 Base Connectors
6 Remarks, Your Cooperation Duties

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 2 / 23
Version: 1.13.1

Solution: Case-9 Date: 28/02/2024

1 Geometry and Application

Support Details
Modular Support Spacing [mm] Undefined

Intermediate Supports required?

Pipe Fasteners with Glider and Presetting used? (See


subchapter 'Gliders' in chapter 'Geometry and
Application')

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 3 / 23
Version: 1.13.1

Solution: Case-9 Date: 28/02/2024

1.1 Supports - Concrete

Concrete

Thickness Drilling Depth


Node No. No. Orientation Concrete grade
[mm] [mm]
1 1 Horizontal C20/25 200.00 150
4 2 Horizontal C20/25 200.00 150
6 3 Horizontal C20/25 200.00 150
8 4 Horizontal C20/25 200.00 150

1.2 Nodes

X Y Z
No. No. Connector name Connector variant
[mm] [mm] [mm]
1 1 -190.75 0.00 -500.00 MT-B-O2 OC MT-B-O2 OC (C)
2 - -190.75 0.00 -93.10 MT-C-L2 OC MT-C-L2 OC (C)
3 - 709.25 0.00 -93.10 MT-C-L2 OC MT-C-L2 OC (C)
4 2 709.25 0.00 -500.00 MT-B-O2 OC MT-B-O2 OC (C)
5 - 709.25 0.00 -258.66 MT-AB-LL2 45 OC MT-AB-LL2 45 OC (E)
6 3 709.25 241.34 -500.00 MT-AB A OC MT-AB A OC (C)
7 - -190.75 0.00 -258.66 MT-AB-LL2 45 OC MT-AB-LL2 45 OC (E)
8 4 -190.75 241.34 -500.00 MT-AB A OC MT-AB A OC (C)

1.3 Members

Member Releases Rotation


No. Node start Node end Member Name
Start End [°]
1 2 3 1 2 MT-60 180.00
2 3 4 2 - MT-40D 180.00
3 5 6 3 4 MT-40 0.00
4 7 8 5 6 MT-40 0.00
5 1 9 - - MT-40D 0.00

1.4 Connections

Cross- Cross- Cross- Cross-


Section/Rotation Section/Rotation Section/Rotation Section/Rotation
Node No. Description Variant
Arm1 Arm2 Arm3 Arm4
[-/°] [-/°] [-/°] [-/°]
1 MT-B-O2 OC MT-B-O2 OC (C) MT-40D/0 - - -
2 MT-C-L2 OC MT-C-L2 OC (C) MT-60/180 MT-40D/0 - -
3 MT-C-L2 OC MT-C-L2 OC (C) MT-60/180 MT-40D/180 - -
4 MT-B-O2 OC MT-B-O2 OC (C) MT-40D/180 - - -
5 MT-AB-LL2 45 OC MT-AB-LL2 45 OC (E) MT-40D/180 MT-40/0 - -
6 MT-AB A OC MT-AB A OC (C) MT-40/0 - - -
7 MT-AB-LL2 45 OC MT-AB-LL2 45 OC (E) MT-40/0 MT-40D/0 - -
8 MT-AB A OC MT-AB A OC (C) MT-40/0 - - -

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 4 / 23
Version: 1.13.1

Solution: Case-9 Date: 28/02/2024

1.5 Release Conditions

Spring Constants
Releases
Member Translational Rotational
No. Cu,x Cu,y Cu,z Cφx Cφy Cφz
Ux Uy Uz φx φy φz
[kN/m] [kN/m] [kN/m] [kNm/Rad] [kNm/Rad] [kNm/Rad]
1 no no no no yes yes - - - - 0.001 0.001
1 no no no no yes yes - - - - 0.001 0.001
3 no no no no yes yes - - - - 0.000 0.000
3 no no no no yes yes - - - - 0.000 0.000
4 no no no no yes yes - - - - 0.000 0.000
4 no no no no yes yes - - - - 0.000 0.000

1.6 Media Interface Channel

Start Position Length


No. Member No. Media Interface Z-Position Y-Position
[mm] [mm]

1.7 Gliders

Position Start Travel


No. Member No. Glider Custom Load
[mm] [mm] [mm]

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 5 / 23
Version: 1.13.1

Solution: Case-9 Date: 28/02/2024

2 Part list

2.1 Members

Quantity Weight Length


Position Item Number Description Cutting type
[-] [kg] [mm]
1 2268516 I.-Channel MT-60 OC 1 3.14 815.00 N - None
2 2268520 I.-Channel MT-40D OC 1 1.82 433.90 N - None
3 2268520 I.-Channel MT-40D OC 1 2.69 641.00 N - None
4 2268508 I.-Channel MT-40 OC 1 0.61 300.82 N - None
5 2268508 I.-Channel MT-40 OC 1 0.61 301.28 N - None

2.2 Base Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
6 2272096 2-hole Baseplate MT-B-O2 OC 2 2.05
12 2346396 Angle brace MT-AB A OC set adjustable 2 0.88

2.3 System Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
10 2271519 Angle connector MT-C-L2 OC 2 0.52
11 2273585 Angle brace MT-AB-LL2 45 OC 2 1.11

2.4 Other

Quantity Weight
Position Item Number Description
[-] [kg]
7 2273256 Hexagon bolt MT-TLB OC 18 0.45
8 2272082 Twist-Lock MT-TL M10 OC 18 0.63
9 2105870 Stud anchor HST3-R M12x115 40/20 8 0.81

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 6 / 23
Version: 1.13.1

Solution: Case-9 Date: 28/02/2024

3 Load Types

3. Loads

Custom loads

Load No. Load Distribution Load Case Load Type Comments


1 Point load LC 7: Design Permanent -
2 Point load LC 7: Design Permanent -
3 Point load LC 13: Seismic (+x) Seismic -
4 Point load LC 14: Seismic (-x) Seismic -
5 Point load LC 13: Seismic (+x) Seismic -
6 Point load LC 14: Seismic (-x) Seismic -
7 Point load LC 2: Pipe Permanent -
8 Point load LC 2: Pipe Permanent -
9 Point load LC 7: Design Permanent -

3.2 Point Loads

Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
1 Design 1 250.00 0.00 0.00 -3.18 0.00 0.00 0.00
2 Design 1 650.00 0.00 0.00 -3.18 0.00 0.00 0.00
3 Seismic (+x) 1 250.00 0.04 0.00 0.00 0.00 0.00 0.00
4 Seismic (-x) 1 250.00 -0.04 -0.00 -0.00 -0.00 -0.00 -0.00
5 Seismic (+x) 1 650.00 0.04 0.00 0.00 0.00 0.00 0.00
6 Seismic (-x) 1 650.00 -0.04 -0.00 -0.00 -0.00 -0.00 -0.00
9 Pipe 1 250.00 0.32 0.32 0.00 0.00 0.00 0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 7 / 23
Version: 1.13.1

Solution: Case-9 Date: 28/02/2024


Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
10 Pipe 1 650.00 0.32 0.32 0.00 0.00 0.00 0.00
13 Design 5 535.00 0.00 0.00 -0.11 0.00 0.00 0.00
14 Self Weight Support 5 0.00 0.00 0.00 -0.01 0.00 0.00 0.00
15 Self Weight Support 1 0.00 0.00 0.00 -0.00 0.00 0.00 0.00
16 Self Weight Support 1 900.00 0.00 0.00 -0.00 0.00 0.00 0.00
17 Self Weight Support 2 406.90 0.00 0.00 -0.01 0.00 0.00 0.00
18 Self Weight Support 2 165.56 0.00 0.00 -0.01 0.00 0.00 0.00
19 Self Weight Support 3 341.31 0.00 0.00 -0.00 0.00 0.00 0.00
20 Self Weight Support 4 0.00 0.00 0.00 -0.01 0.00 0.00 0.00
21 Self Weight Support 4 341.31 0.00 0.00 -0.00 0.00 0.00 0.00

3.3 Distributed loads

Start End
Fx Fy Fz Mx My Mz
Load No. Load Type Members Position Position
[kN/m] [kN/m] [kN/m] [kNm/m] [kNm/m] [kNm/m]
[mm] [mm]
22 Self Weight Support 1 0.00 900.00 0.00 0.00 -0.04 0.00 0.00 0.00
23 Self Weight Support 2 0.00 406.90 0.00 0.00 -0.04 0.00 0.00 0.00
24 Self Weight Support 3 0.00 341.31 0.00 0.00 -0.02 0.00 0.00 0.00
25 Self Weight Support 4 0.00 341.31 0.00 0.00 -0.02 0.00 0.00 0.00
26 Self Weight Support 5 0.00 650.00 0.00 0.00 -0.04 0.00 0.00 0.00

3.4 Area loads

3.4.1 User input

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 8 / 23
Version: 1.13.1

Solution: Case-9 Date: 28/02/2024

4 Load Combinations

Design base EN 1993

Load combination design base EN 1990

4.1 Ultimate Limit State

Design base Load combination and safety factors


ULS - 001a-ULS: SW_inf (Support Only) 1.00 * LC1
ULS - 001b-ULS: SW_sup (Support Only) 1.35 * LC1
ULS - 002a-ULS: SW_inf Support + Media 1.00 * LC1 + 1.00 * LC2
ULS - 002b-ULS: SW_sup Support + Media 1.35 * LC1 + 1.35 * LC2
ULS - 004a-ULS: SW_inf + Design Loads 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC7
ULS - 004b-ULS: SW_sup + Design Loads 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
ULS - 027a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC13
z) + Live + Snow
ULS - 027b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC14
+ Live + Snow
ULS - 029a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC13
z) + Live + Snow
ULS - 030a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC14
+ Live + Snow
ULS - 027a-ULS_Base : SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 027b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 029a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 030a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 031a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC13 + 1.00 * 0.74 * LC7
z) + Design
ULS - 031b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC14 + 1.00 * 0.74 * LC7
+ Design
ULS - 033a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC13 + 1.00 * 0.74 * LC7
z) + Design
ULS - 034a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC14 + 1.00 * 0.74 * LC7
+ Design
ULS - 032a-ULS_Base: SW + Seismic (+x) + Seismic (-y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC13 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 031b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC14 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 033a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC13 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 034a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC14 + 1.00 * 0.74 * LC7
Seismic (-z) + Design

4.2 Serviceability Limit State

Load Case Load combination and safety factors


SLS - 001-SLS: SW (Support Only) 1.00 * LC1
SLS - 002-SLS: SW Support + Media Objects 1.00 * LC1 + 1.00 * LC2
SLS - 004-SLS: SW + Design Loads 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 9 / 23
Version: 1.13.1

Solution: Case-9 Date: 28/02/2024

5 Results

5.1 Calculation summary

5.1.3 Members

Governing load ULS SLS


No Member Status
combination number* [%] [%]
2 MT-60 004b-ULS 52.65 - OK
3 MT-40D 004b-ULS 24.57 - OK
8 MT-40 004b-ULS 3.53 - OK
10 MT-40 004b-ULS 3.54 - OK
11 MT-40D 004b-ULS 26.55 - OK

5.1.2 Base Connectors

Governing load ULS SLS


No Base connector Status
combination number* [%] [%]
1 MT-B-O2 OC 004b-ULS 69.91 - OK
4 MT-B-O2 OC 004b-ULS 68.58 - OK
6 MT-AB A OC 004b-ULS 7.57 - OK
8 MT-AB A OC 004b-ULS 7.58 - OK

5.1.3 System Connectors

Governing load ULS SLS


No Connector Status
combination number* [%] [%]
2 MT-C-L2 OC 004b-ULS 64.36 - OK
3 MT-C-L2 OC 004b-ULS 60.96 - OK
5 MT-AB-LL2 45 OC 004b-ULS 10.68 - OK
7 MT-AB-LL2 45 OC 004b-ULS 10.70 - OK
*004b-ULS: SW_sup + Design Loads . Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7

Overall Status: Calculation OK, design criteria met!

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 10 / 23
Version: 1.13.1

Solution: Case-9 Date: 28/02/2024

5.2 Members

5.2.1 Member Properties


5.2.1.1 MT-60 Members: 1
5.2.1.1.1 Section properties
t A Iy Iz It
[mm] [mm²] [mm⁴] [mm⁴] [mm⁴]
2.75 498.77 285700.00 170800.00 999.88

Iω M Wy Wz Wy
[mm⁶] [kg/m] [mm³] [mm³] [mm³]
158106000.00 3.85 -7804.06 -8037.37 -7804.06

5.2.1.1.2 Material properties


E G Fu Fy Fy.cold
Steel grade
[N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²]
Steel S 280 GD 210000.00 80769.00 360.00 280.00 311.60

5.2.1.2 MT-40D Members: 2, 5


5.2.1.2.1 Section properties
t A Iy Iz It
[mm] [mm²] [mm⁴] [mm⁴] [mm⁴]
2.00 429.52 299600.00 131800.00 520.41

Iω M Wy Wz Wy
[mm⁶] [kg/m] [mm³] [mm³] [mm³]
154300000.00 4.20 -7048.65 -6199.90 -7048.65

5.2.1.2.2 Material properties


E G Fu Fy Fy.cold
Steel grade
[N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²]
Steel S 280 GD 210000.00 80769.00 360.00 280.00 305.00

5.2.1.3 MT-40 Members: 3, 4


5.2.1.3.1 Section properties
t A Iy Iz It
[mm] [mm²] [mm⁴] [mm⁴] [mm⁴]
2.00 285.00 57717.48 65876.44 259.85

Iω M Wy Wz Wy
[mm⁶] [kg/m] [mm³] [mm³] [mm³]
38410000.00 2.04 -2652.65 -3099.95 -2652.65

5.2.1.3.2 Material properties


E G Fu Fy Fy.cold
Steel grade
[N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²]
Steel S 280 GD 210000.00 80769.00 360.00 280.00 305.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 11 / 23
Version: 1.13.1

Solution: Case-9 Date: 28/02/2024

5.2.2 Member Design

5.2.2.1 Overview

5.2.2.2 Stress Analysis

5.2.2.2.1 Table of Results

Load Combination σ τ σeqv σlimit τlimit Utilization


No. Member
number* [N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²] [%]
I.-Channel MT-60
1 004b-ULS 113.56 19.73 113.70 283.27 163.55 40.14
OC
I.-Channel MT-40D
2 004b-ULS -28.25 17.97 33.38 277.27 160.08 12.04
OC
I.-Channel MT-40
3 004b-ULS -4.97 0.00 4.98 277.27 0.00 1.80
OC
I.-Channel MT-40
4 004b-ULS -4.98 0.00 4.99 277.27 0.00 1.80
OC
I.-Channel MT-40D
5 004b-ULS -28.54 0.00 33.49 277.27 0.00 12.08
OC

*004b-ULS: SW_sup + Design Loads. Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7

5.2.2.2 Governing Member Loading

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 12 / 23
Version: 1.13.1

Solution: Case-9 Date: 28/02/2024

Beam No. 1

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-60 0.00 004b-ULS 0.43 -0.43 3.20 -0.00 -0.00 -0.00
MT-60 180.00 004b-ULS 0.43 -0.43 3.19 -0.00 0.58 0.08
MT-60 250.00(-) 004b-ULS 0.43 -0.43 3.19 -0.00 0.80 0.11
MT-60 250.00(+) 004b-ULS -0.00 0.00 0.01 -0.00 0.80 0.11
MT-60 360.00 004b-ULS -0.00 0.00 0.00 -0.00 0.80 0.11
MT-60 540.00 004b-ULS -0.00 0.00 -0.00 -0.00 0.80 0.11
MT-60 650.00(-) 004b-ULS -0.00 0.00 -0.01 -0.00 0.80 0.11
MT-60 650.00(+) 004b-ULS -0.43 0.43 -3.19 -0.00 0.80 0.11
MT-60 720.00 004b-ULS -0.43 0.43 -3.19 -0.00 0.58 0.08
MT-60 900.00 004b-ULS -0.43 0.43 -3.20 -0.00 -0.00 -0.00

Beam No. 2

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40D 0.00 004b-ULS -3.21 0.43 0.43 -0.00 -0.00 0.00
MT-40D 81.38 004b-ULS -3.21 0.43 0.43 -0.00 0.04 -0.04
MT-40D 162.76 004b-ULS -3.22 0.43 0.43 -0.00 0.07 -0.07
MT-40D 165.56(-) 004b-ULS -3.22 0.43 0.43 -0.00 0.07 -0.07
MT-40D 165.56(+) 004b-ULS -2.49 -0.30 0.43 0.00 0.07 -0.07
MT-40D 244.14 004b-ULS -2.50 -0.30 0.43 0.00 0.11 -0.05
MT-40D 325.52 004b-ULS -2.50 -0.30 0.43 0.00 0.14 -0.02
MT-40D 406.90 004b-ULS -2.51 -0.30 0.43 0.00 0.18 0.00

Beam No. 3

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40 0.00 004b-ULS -1.04 0.00 -0.00 -0.00 0.00 -0.00
MT-40 68.26 004b-ULS -1.04 0.00 -0.00 -0.00 -0.00 -0.00
MT-40 136.52 004b-ULS -1.04 0.00 -0.00 -0.00 -0.00 -0.00
MT-40 204.78 004b-ULS -1.04 0.00 0.00 -0.00 -0.00 -0.00
MT-40 273.05 004b-ULS -1.04 0.00 0.00 -0.00 -0.00 -0.00
MT-40 341.31 004b-ULS -1.04 0.00 0.00 -0.00 0.00 -0.00

Beam No. 4

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40 0.00 004b-ULS -1.04 0.00 -0.00 -0.00 0.00 -0.00
MT-40 68.26 004b-ULS -1.04 0.00 -0.00 -0.00 -0.00 -0.00
MT-40 136.52 004b-ULS -1.04 0.00 -0.00 -0.00 -0.00 -0.00
MT-40 204.78 004b-ULS -1.04 0.00 0.00 -0.00 -0.00 -0.00
MT-40 273.05 004b-ULS -1.05 0.00 0.00 -0.00 -0.00 -0.00
MT-40 341.31 004b-ULS -1.05 0.00 0.00 -0.00 0.00 -0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 13 / 23
Version: 1.13.1

Solution: Case-9 Date: 28/02/2024

Beam No. 5

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40D 0.00 004b-ULS -2.63 -0.31 -0.43 0.00 0.18 -0.00
MT-40D 130.00 004b-ULS -2.62 -0.31 -0.43 0.00 0.12 0.04
MT-40D 241.34(-) 004b-ULS -2.61 -0.31 -0.43 0.00 0.07 0.07
MT-40D 241.34(+) 004b-ULS -3.34 0.43 -0.43 0.00 0.07 0.07
MT-40D 260.00 004b-ULS -3.34 0.43 -0.43 0.00 0.06 0.06
MT-40D 390.00 004b-ULS -3.33 0.43 -0.43 0.00 0.01 0.01
MT-40D 406.90(-) 004b-ULS -3.33 0.43 -0.43 0.00 0.00 0.00
MT-40D 406.90(+) 004b-ULS -0.12 0.00 0.00 0.00 0.00 -0.00
MT-40D 520.00 004b-ULS -0.12 0.00 0.00 0.00 0.00 -0.00
MT-40D 535.00(-) 004b-ULS -0.12 0.00 0.00 0.00 0.00 -0.00
MT-40D 535.00(+) 004b-ULS -0.01 0.00 0.00 0.00 0.00 -0.00
MT-40D 650.00 004b-ULS -0.00 0.00 0.00 0.00 0.00 -0.00

*004b-ULS: SW_sup + Design Loads. Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7

Normal load

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 14 / 23
Version: 1.13.1

Solution: Case-9 Date: 28/02/2024

Shear load in Y direction

Shear load in Z direction

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 15 / 23
Version: 1.13.1

Solution: Case-9 Date: 28/02/2024

Torsion around X

Moment around Y

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 16 / 23
Version: 1.13.1

Solution: Case-9 Date: 28/02/2024

Moment around Z

5.2.2.3 Shear Limits

Fy,Ed Fy,Rd Fz,Ed Fz,Rd Utilization


No. Type Load Combination number*
[kN] [kN] [kN] [kN] [%]
2 MT-40D 004b-ULS - - 0.43 4.25 10.17
5 MT-40D 002b-ULS - - -0.43 4.25 10.16

5.2.3 Stability Analysis

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 17 / 23
Version: 1.13.1

Solution: Case-9 Date: 28/02/2024

Buckling ratio

Buckling Max. lateral torsional Max. buckling under Max.


Member Length
Length Buckling ratio buckling under bending compression interaction
No. [mm]
[mm] [%] [%] [%]
1 900.00 900.00 1.00 42.18 1.00 52.65
2 406.90 813.80 2.00 11.36 3.61 24.57
3 341.31 682.61 2.00 0.00 3.53 3.53
4 341.31 682.61 2.00 0.00 3.54 3.54
5 650.00 1300.00 2.00 11.36 4.93 26.55

5.2.4 Deflection Analysis

Criteria
☑Maximum Allowable Deflection (Beam) L/200
☑Maximum Allowable Deflection (Cantilever)L/150
- Maximum Deflection (Absolute) -
☑No Deflection checks calculated for 1.50mm

Overview

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 18 / 23
Version: 1.13.1

Solution: Case-9 Date: 28/02/2024

Results
Reference
Member Max deflection Utilization
Load Combination number* Governing criteria Length Limit
No. [mm] [%]
[mm]
1 004-SLS Relative (Beam) 900.00 L/200 0.01 0.00
2 004-SLS Relative (Beam) 406.90 L/200 0.00 0.00
3 004-SLS Relative (Beam) 341.31 L/200 0.00 0.00
4 004-SLS Relative (Beam) 341.31 L/200 0.00 0.00
5 004-SLS Relative (Beam) 650.00 L/200 -0.03 0.00

*004-SLS: SW + Design Loads. Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7

Deflection 1.00 * LC1

Deflection 1.00 * LC1 + 1.00 * LC2

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 19 / 23
Version: 1.13.1

Solution: Case-9 Date: 28/02/2024

Deflection 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 20 / 23
Version: 1.13.1

Solution: Case-9 Date: 28/02/2024

5.3 System Connectors

5.3 Connectors

5.3.1 Overview

Connector: MT-C-L2 OC
Fx Fy Fz Mx My Mz
Connector variant: MT-C-L2 OC (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 2
Local Forces: 0.43 -0.43 3.20 -0.00 -0.00 -0.00
Resistance: 3.97 1.56 12.38 0.06
Equation: abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)
Utilization: 64.36 % OK

Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
Combination

Connector: MT-AB-LL2 45 OC
Fx Fy Fz Mx My Mz
Connector variant: MT-AB-LL2 45 OC (E)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 7
Local Forces: -1.04 0.00 -0.00 -0.00 0.00 0.00
Resistance: 9.72 0.10 0.10 0.10 0.00 0.00
abs(Fx.ed/Fx.rd);abs(Fy.ed/Fy.rd);abs(Fz.ed/Fz.rd);abs(Mx.ed/Mx.rd);abs(My
Equation:
.ed/My.rd);abs(Mz.ed/Mz.rd)
Utilization: 10.70 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 21 / 23
Version: 1.13.1

Solution: Case-9 Date: 28/02/2024

5.4 Base Connectors

5.4 Bases

5.4.1 Overview

Base connector: MT-B-O2 OC


Fx Fy Fz Mx My Mz
Connector variant: MT-B-O2 OC (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 1
Local Forces: -2.64 -0.30 -0.43 0.00 0.18 -0.00
Resistance: 14.00 2.43 7.34 0.06 0.55 0.23
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 69.91 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
Combination
Base connector: MT-AB A OC
Fx Fy Fz Mx My Mz
Connector variant: MT-AB A OC (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 8
Local Forces: -1.05 0.00 0.01 -0.00 0.00 0.00
Resistance: 13.86 0.10 0.10 0.10 0.00 0.00
abs(Fx.ed/Fx.rd);abs(Fy.ed/Fy.rd);abs(Fz.ed/Fz.rd);abs(Mx.ed/Mx.rd);abs(My
Equation:
.ed/My.rd);abs(Mz.ed/Mz.rd)
Utilization: 7.58 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 22 / 23
Version: 1.13.1

Solution: Case-9 Date: 28/02/2024

6 Remarks, Your Cooperation Duties

Any and all information and data contained in the Software concern solely the use of Hilti products and based on the principles, formulas and security
regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly complied with by
the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the relevant Hilti product.
The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole
responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole responsibility for
having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior
to using them for your specific facility. The Software servers only as an aid to interpret norms and permits without any guarantee as to the absence of
errors, the correctness and relevance ot the results or suitability for a specific application.

You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular
backup of programs and, if applicable, carry out the updates of that you are using the current and thus up-to-date version of the Software in each case
by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or
programs, arising from a culpable breach of duty by you.

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 23 / 23
Case-11

Project: SA-13082-SF

Submitted by:

Hilti contact information


Contact name:
Contact e-mail:
Contact phone:
Contact company:

Customer contact information


Customer name:
Customer e-mail:
Customer phone:
Customer company:

Date: 28/02/2024

This submittal is auto-generated based on user-selected inputs.


Therefore, Hilti no representation as to the suitability of these systems for their intended use. 1 / 23
Version: 1.13.1

Solution: Case-11 Date: 28/02/2024

Table of content

1 Geometry and Application


1.1 Supports
1.2 Nodes
1.3 Members
1.4 Connections
1.5 Release Conditions
1.6 Media Interface Channel
1.7 Gliders
2 Part list
2.1 Members
2.2 Base Connectors
2.3 System Connectors
2.4 Other
3 Load Types
3.1 Loading objects
3.2 Point Loads
3.3 Distributed loads
3.4 Area loads
4 Load Combinations
4.1 Ultimate Limit State
4.2 Serviceability Limit State
5 Results
5.1 Calculation summary
5.2 Members
5.3 System Connectors
5.4 Base Connectors
6 Remarks, Your Cooperation Duties

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 2 / 23
Version: 1.13.1

Solution: Case-11 Date: 28/02/2024

1 Geometry and Application

Support Details
Modular Support Spacing [mm] Undefined

Intermediate Supports required?

Pipe Fasteners with Glider and Presetting used? (See


subchapter 'Gliders' in chapter 'Geometry and
Application')

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 3 / 23
Version: 1.13.1

Solution: Case-11 Date: 28/02/2024

1.1 Supports - Concrete

Concrete

Thickness Drilling Depth


Node No. No. Orientation Concrete grade
[mm] [mm]
1 1 Horizontal C20/25 200.00 150
4 2 Horizontal C20/25 200.00 150
6 3 Horizontal C20/25 200.00 150
8 4 Horizontal C20/25 200.00 150

1.2 Nodes

X Y Z
No. No. Connector name Connector variant
[mm] [mm] [mm]
1 1 -190.75 0.00 -500.00 MT-B-O2 OC MT-B-O2 OC (C)
2 - -190.75 0.00 -93.10 MT-C-L2 OC MT-C-L2 OC (C)
3 - 709.25 0.00 -93.10 MT-C-L2 OC MT-C-L2 OC (C)
4 2 709.25 0.00 -500.00 MT-B-O2 OC MT-B-O2 OC (C)
5 - 709.25 0.00 -258.66 MT-AB-LL2 45 OC MT-AB-LL2 45 OC (E)
6 3 709.25 241.34 -500.00 MT-AB A OC MT-AB A OC (C)
7 - -190.75 0.00 -258.66 MT-AB-LL2 45 OC MT-AB-LL2 45 OC (E)
8 4 -190.75 241.34 -500.00 MT-AB A OC MT-AB A OC (C)

1.3 Members

Member Releases Rotation


No. Node start Node end Member Name
Start End [°]
1 1 2 - 1 MT-40D 180.00
2 2 3 1 2 MT-60 180.00
3 3 4 2 - MT-40D 180.00
4 5 6 3 4 MT-40 0.00
5 7 8 5 6 MT-40 0.00

1.4 Connections

Cross- Cross- Cross- Cross-


Section/Rotation Section/Rotation Section/Rotation Section/Rotation
Node No. Description Variant
Arm1 Arm2 Arm3 Arm4
[-/°] [-/°] [-/°] [-/°]
1 MT-B-O2 OC MT-B-O2 OC (C) MT-40D/180 - - -
2 MT-C-L2 OC MT-C-L2 OC (C) MT-40D/180 MT-60/180 - -
3 MT-C-L2 OC MT-C-L2 OC (C) MT-60/180 MT-40D/180 - -
4 MT-B-O2 OC MT-B-O2 OC (C) MT-40D/180 - - -
5 MT-AB-LL2 45 OC MT-AB-LL2 45 OC (E) MT-40D/180 MT-40/0 - -
6 MT-AB A OC MT-AB A OC (C) MT-40/0 - - -
7 MT-AB-LL2 45 OC MT-AB-LL2 45 OC (E) MT-40D/180 MT-40/0 - -
8 MT-AB A OC MT-AB A OC (C) MT-40/0 - - -

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 4 / 23
Version: 1.13.1

Solution: Case-11 Date: 28/02/2024

1.5 Release Conditions

Spring Constants
Releases
Member Translational Rotational
No. Cu,x Cu,y Cu,z Cφx Cφy Cφz
Ux Uy Uz φx φy φz
[kN/m] [kN/m] [kN/m] [kNm/Rad] [kNm/Rad] [kNm/Rad]
2 no no no no yes yes - - - - 0.001 0.001
2 no no no no yes yes - - - - 0.001 0.001
4 no no no no yes yes - - - - 0.000 0.000
4 no no no no yes yes - - - - 0.000 0.000
5 no no no no yes yes - - - - 0.000 0.000
5 no no no no yes yes - - - - 0.000 0.000

1.6 Media Interface Channel

Start Position Length


No. Member No. Media Interface Z-Position Y-Position
[mm] [mm]

1.7 Gliders

Position Start Travel


No. Member No. Glider Custom Load
[mm] [mm] [mm]

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 5 / 23
Version: 1.13.1

Solution: Case-11 Date: 28/02/2024

2 Part list

2.1 Members

Quantity Weight Length


Position Item Number Description Cutting type
[-] [kg] [mm]
1 2268520 I.-Channel MT-40D OC 2 3.64 433.90 N - None
2 2268516 I.-Channel MT-60 OC 1 3.14 815.00 N - None
3 2268508 I.-Channel MT-40 OC 1 0.61 300.82 N - None
4 2268508 I.-Channel MT-40 OC 1 0.61 301.28 N - None

2.2 Base Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
5 2272096 2-hole Baseplate MT-B-O2 OC 2 2.05
11 2346396 Angle brace MT-AB A OC set adjustable 2 0.88

2.3 System Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
9 2271519 Angle connector MT-C-L2 OC 2 0.52
10 2273585 Angle brace MT-AB-LL2 45 OC 2 1.11

2.4 Other

Quantity Weight
Position Item Number Description
[-] [kg]
6 2273256 Hexagon bolt MT-TLB OC 18 0.45
7 2272082 Twist-Lock MT-TL M10 OC 18 0.63
8 2105870 Stud anchor HST3-R M12x115 40/20 8 0.81

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 6 / 23
Version: 1.13.1

Solution: Case-11 Date: 28/02/2024

3 Load Types

3. Loads

Custom loads

Load No. Load Distribution Load Case Load Type Comments


1 Point load LC 7: Design Permanent -
2 Point load LC 7: Design Permanent -
3 Point load LC 13: Seismic (+x) Seismic -
4 Point load LC 14: Seismic (-x) Seismic -
5 Point load LC 13: Seismic (+x) Seismic -
6 Point load LC 14: Seismic (-x) Seismic -
7 Point load LC 2: Pipe Permanent -
8 Point load LC 2: Pipe Permanent -

3.2 Point Loads

Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
1 Design 2 250.00 0.00 0.00 -3.18 0.00 0.00 0.00
2 Design 2 650.00 0.00 0.00 -3.18 0.00 0.00 0.00
3 Seismic (+x) 2 250.00 0.04 0.00 0.00 0.00 0.00 0.00
4 Seismic (-x) 2 250.00 -0.04 -0.00 -0.00 -0.00 -0.00 -0.00
5 Seismic (+x) 2 650.00 0.04 0.00 0.00 0.00 0.00 0.00
6 Seismic (-x) 2 650.00 -0.04 -0.00 -0.00 -0.00 -0.00 -0.00
9 Pipe 2 250.00 0.32 0.32 0.00 0.00 0.00 0.00
10 Pipe 2 650.00 0.32 0.32 0.00 0.00 0.00 0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 7 / 23
Version: 1.13.1

Solution: Case-11 Date: 28/02/2024


Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
11 Self Weight Support 1 0.00 0.00 0.00 -0.01 0.00 0.00 0.00
12 Self Weight Support 1 406.90 0.00 0.00 -0.00 0.00 0.00 0.00
13 Self Weight Support 2 900.00 0.00 0.00 -0.00 0.00 0.00 0.00
14 Self Weight Support 3 406.90 0.00 0.00 -0.01 0.00 0.00 0.00
15 Self Weight Support 3 165.56 0.00 0.00 -0.01 0.00 0.00 0.00
16 Self Weight Support 4 341.31 0.00 0.00 -0.00 0.00 0.00 0.00
17 Self Weight Support 1 241.34 0.00 0.00 -0.01 0.00 0.00 0.00
18 Self Weight Support 5 341.31 0.00 0.00 -0.00 0.00 0.00 0.00

3.3 Distributed loads

Start End
Fx Fy Fz Mx My Mz
Load No. Load Type Members Position Position
[kN/m] [kN/m] [kN/m] [kNm/m] [kNm/m] [kNm/m]
[mm] [mm]
19 Self Weight Support 1 0.00 406.90 0.00 0.00 -0.04 0.00 0.00 0.00
20 Self Weight Support 2 0.00 900.00 0.00 0.00 -0.04 0.00 0.00 0.00
21 Self Weight Support 3 0.00 406.90 0.00 0.00 -0.04 0.00 0.00 0.00
22 Self Weight Support 4 0.00 341.31 0.00 0.00 -0.02 0.00 0.00 0.00
23 Self Weight Support 5 0.00 341.31 0.00 0.00 -0.02 0.00 0.00 0.00

3.4 Area loads

3.4.1 User input

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 8 / 23
Version: 1.13.1

Solution: Case-11 Date: 28/02/2024

4 Load Combinations

Design base EN 1993

Load combination design base EN 1990

4.1 Ultimate Limit State

Design base Load combination and safety factors


ULS - 001a-ULS: SW_inf (Support Only) 1.00 * LC1
ULS - 001b-ULS: SW_sup (Support Only) 1.35 * LC1
ULS - 002a-ULS: SW_inf Support + Media 1.00 * LC1 + 1.00 * LC2
ULS - 002b-ULS: SW_sup Support + Media 1.35 * LC1 + 1.35 * LC2
ULS - 004a-ULS: SW_inf + Design Loads 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC7
ULS - 004b-ULS: SW_sup + Design Loads 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
ULS - 027a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC13
z) + Live + Snow
ULS - 027b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC14
+ Live + Snow
ULS - 029a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC13
z) + Live + Snow
ULS - 030a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC14
+ Live + Snow
ULS - 027a-ULS_Base : SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 027b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 029a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 030a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 031a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC13 + 1.00 * 0.74 * LC7
z) + Design
ULS - 031b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC14 + 1.00 * 0.74 * LC7
+ Design
ULS - 033a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC13 + 1.00 * 0.74 * LC7
z) + Design
ULS - 034a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC14 + 1.00 * 0.74 * LC7
+ Design
ULS - 032a-ULS_Base: SW + Seismic (+x) + Seismic (-y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC13 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 031b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC14 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 033a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC13 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 034a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC14 + 1.00 * 0.74 * LC7
Seismic (-z) + Design

4.2 Serviceability Limit State

Load Case Load combination and safety factors


SLS - 001-SLS: SW (Support Only) 1.00 * LC1
SLS - 002-SLS: SW Support + Media Objects 1.00 * LC1 + 1.00 * LC2
SLS - 004-SLS: SW + Design Loads 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 9 / 23
Version: 1.13.1

Solution: Case-11 Date: 28/02/2024

5 Results

5.1 Calculation summary

5.1.3 Members

Governing load ULS SLS


No Member Status
combination number* [%] [%]
1 MT-40D 004b-ULS 24.57 - OK
2 MT-60 004b-ULS 52.65 - OK
3 MT-40D 004b-ULS 24.57 - OK
8 MT-40 004b-ULS 3.53 - OK
10 MT-40 004b-ULS 3.53 - OK

5.1.2 Base Connectors

Governing load ULS SLS


No Base connector Status
combination number* [%] [%]
1 MT-B-O2 OC 004b-ULS 68.57 - OK
4 MT-B-O2 OC 004b-ULS 68.58 - OK
6 MT-AB A OC 004b-ULS 7.57 - OK
8 MT-AB A OC 004b-ULS 7.57 - OK

5.1.3 System Connectors

Governing load ULS SLS


No Connector Status
combination number* [%] [%]
2 MT-C-L2 OC 004b-ULS 64.36 - OK
3 MT-C-L2 OC 004b-ULS 60.96 - OK
5 MT-AB-LL2 45 OC 004b-ULS 10.68 - OK
7 MT-AB-LL2 45 OC 004b-ULS 10.68 - OK
*004b-ULS: SW_sup + Design Loads . Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7

Overall Status: Calculation OK, design criteria met!

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 10 / 23
Version: 1.13.1

Solution: Case-11 Date: 28/02/2024

5.2 Members

5.2.1 Member Properties


5.2.1.1 MT-40D Members: 1, 3
5.2.1.1.1 Section properties
t A Iy Iz It
[mm] [mm²] [mm⁴] [mm⁴] [mm⁴]
2.00 429.52 299600.00 131800.00 520.41

Iω M Wy Wz Wy
[mm⁶] [kg/m] [mm³] [mm³] [mm³]
154300000.00 8.40 -7048.65 -6199.90 -7048.65

5.2.1.1.2 Material properties


E G Fu Fy Fy.cold
Steel grade
[N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²]
Steel S 280 GD 210000.00 80769.00 360.00 280.00 305.00

5.2.1.2 MT-60 Members: 2


5.2.1.2.1 Section properties
t A Iy Iz It
[mm] [mm²] [mm⁴] [mm⁴] [mm⁴]
2.75 498.77 285700.00 170800.00 999.88

Iω M Wy Wz Wy
[mm⁶] [kg/m] [mm³] [mm³] [mm³]
158106000.00 3.85 -7804.06 -8037.37 -7804.06

5.2.1.2.2 Material properties


E G Fu Fy Fy.cold
Steel grade
[N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²]
Steel S 280 GD 210000.00 80769.00 360.00 280.00 311.60

5.2.1.3 MT-40 Members: 4, 5


5.2.1.3.1 Section properties
t A Iy Iz It
[mm] [mm²] [mm⁴] [mm⁴] [mm⁴]
2.00 285.00 57717.48 65876.44 259.85

Iω M Wy Wz Wy
[mm⁶] [kg/m] [mm³] [mm³] [mm³]
38410000.00 2.04 -2652.65 -3099.95 -2652.65

5.2.1.3.2 Material properties


E G Fu Fy Fy.cold
Steel grade
[N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²]
Steel S 280 GD 210000.00 80769.00 360.00 280.00 305.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 11 / 23
Version: 1.13.1

Solution: Case-11 Date: 28/02/2024

5.2.2 Member Design

5.2.2.1 Overview

5.2.2.2 Stress Analysis

5.2.2.2.1 Table of Results

Load Combination σ τ σeqv σlimit τlimit Utilization


No. Member
number* [N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²] [%]
I.-Channel MT-40D
1 004b-ULS -28.25 0.00 33.38 277.27 0.00 12.04
OC
I.-Channel MT-60
2 004b-ULS 113.56 -19.73 113.70 283.27 163.55 40.14
OC
I.-Channel MT-40D
3 004b-ULS -28.25 17.97 33.38 277.27 160.08 12.04
OC
I.-Channel MT-40
4 004b-ULS -4.97 0.00 4.98 277.27 0.00 1.80
OC
I.-Channel MT-40
5 004b-ULS -4.97 0.16 4.98 277.27 160.08 1.80
OC

*004b-ULS: SW_sup + Design Loads. Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7

5.2.2.2 Governing Member Loading

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 12 / 23
Version: 1.13.1

Solution: Case-11 Date: 28/02/2024

Beam No. 1

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40D 0.00 004b-ULS -2.51 0.30 0.43 0.00 -0.18 0.00
MT-40D 81.38 004b-ULS -2.50 0.30 0.43 0.00 -0.14 -0.02
MT-40D 162.76 004b-ULS -2.50 0.30 0.43 0.00 -0.11 -0.05
MT-40D 241.34(-) 004b-ULS -2.49 0.30 0.43 0.00 -0.07 -0.07
MT-40D 241.34(+) 004b-ULS -3.22 -0.43 0.43 0.00 -0.07 -0.07
MT-40D 244.14 004b-ULS -3.22 -0.43 0.43 0.00 -0.07 -0.07
MT-40D 325.52 004b-ULS -3.21 -0.43 0.43 0.00 -0.04 -0.04
MT-40D 406.90 004b-ULS -3.21 -0.43 0.43 0.00 -0.00 -0.00

Beam No. 2

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-60 0.00 004b-ULS 0.43 -0.43 3.20 0.00 -0.00 -0.00
MT-60 180.00 004b-ULS 0.43 -0.43 3.19 0.00 0.58 0.08
MT-60 250.00(-) 004b-ULS 0.43 -0.43 3.19 0.00 0.80 0.11
MT-60 250.00(+) 004b-ULS -0.00 0.00 0.01 0.00 0.80 0.11
MT-60 360.00 004b-ULS -0.00 0.00 0.00 0.00 0.80 0.11
MT-60 540.00 004b-ULS -0.00 0.00 -0.00 0.00 0.80 0.11
MT-60 650.00(-) 004b-ULS -0.00 0.00 -0.01 0.00 0.80 0.11
MT-60 650.00(+) 004b-ULS -0.43 0.43 -3.19 0.00 0.80 0.11
MT-60 720.00 004b-ULS -0.43 0.43 -3.19 0.00 0.58 0.08
MT-60 900.00 004b-ULS -0.43 0.43 -3.20 0.00 -0.00 -0.00

Beam No. 3

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40D 0.00 004b-ULS -3.21 0.43 0.43 -0.00 -0.00 -0.00
MT-40D 81.38 004b-ULS -3.21 0.43 0.43 -0.00 0.04 -0.04
MT-40D 162.76 004b-ULS -3.22 0.43 0.43 -0.00 0.07 -0.07
MT-40D 165.56(-) 004b-ULS -3.22 0.43 0.43 -0.00 0.07 -0.07
MT-40D 165.56(+) 004b-ULS -2.49 -0.30 0.43 0.00 0.07 -0.07
MT-40D 244.14 004b-ULS -2.50 -0.30 0.43 0.00 0.11 -0.05
MT-40D 325.52 004b-ULS -2.50 -0.30 0.43 0.00 0.14 -0.02
MT-40D 406.90 004b-ULS -2.51 -0.30 0.43 0.00 0.18 0.00

Beam No. 4

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40 0.00 004b-ULS -1.04 0.00 -0.00 -0.00 0.00 -0.00
MT-40 68.26 004b-ULS -1.04 0.00 -0.00 -0.00 -0.00 -0.00
MT-40 136.52 004b-ULS -1.04 0.00 -0.00 -0.00 -0.00 -0.00
MT-40 204.78 004b-ULS -1.04 0.00 0.00 -0.00 -0.00 -0.00
MT-40 273.05 004b-ULS -1.04 0.00 0.00 -0.00 -0.00 -0.00
MT-40 341.31 004b-ULS -1.04 0.00 0.00 -0.00 0.00 -0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 13 / 23
Version: 1.13.1

Solution: Case-11 Date: 28/02/2024

Beam No. 5

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40 0.00 004b-ULS -1.04 0.00 -0.00 -0.00 0.00 -0.00
MT-40 68.26 004b-ULS -1.04 0.00 -0.00 -0.00 -0.00 -0.00
MT-40 136.52 004b-ULS -1.04 0.00 -0.00 -0.00 -0.00 -0.00
MT-40 204.78 004b-ULS -1.04 0.00 0.00 -0.00 -0.00 -0.00
MT-40 273.05 004b-ULS -1.04 0.00 0.00 -0.00 -0.00 -0.00
MT-40 341.31 004b-ULS -1.04 0.00 0.00 -0.00 0.00 -0.00

*004b-ULS: SW_sup + Design Loads. Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7

Normal load

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 14 / 23
Version: 1.13.1

Solution: Case-11 Date: 28/02/2024

Shear load in Y direction

Shear load in Z direction

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 15 / 23
Version: 1.13.1

Solution: Case-11 Date: 28/02/2024

Torsion around X

Moment around Y

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 16 / 23
Version: 1.13.1

Solution: Case-11 Date: 28/02/2024

Moment around Z

5.2.2.3 Shear Limits

Fy,Ed Fy,Rd Fz,Ed Fz,Rd Utilization


No. Type Load Combination number*
[kN] [kN] [kN] [kN] [%]
1 MT-40D 002b-ULS - - 0.43 4.25 10.16
3 MT-40D 004b-ULS - - 0.43 4.25 10.17

5.2.3 Stability Analysis

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 17 / 23
Version: 1.13.1

Solution: Case-11 Date: 28/02/2024

Buckling ratio

Buckling Max. lateral torsional Max. buckling under Max.


Member Length
Length Buckling ratio buckling under bending compression interaction
No. [mm]
[mm] [%] [%] [%]
1 406.90 813.80 2.00 11.36 3.61 24.57
2 900.00 900.00 1.00 42.18 1.00 52.65
3 406.90 813.80 2.00 11.36 3.61 24.57
4 341.31 682.61 2.00 0.00 3.53 3.53
5 341.31 682.61 2.00 0.00 3.53 3.53

5.2.4 Deflection Analysis

Criteria
☑Maximum Allowable Deflection (Beam) L/200
☑Maximum Allowable Deflection (Cantilever)L/150
- Maximum Deflection (Absolute) -
☑No Deflection checks calculated for 1.50mm

Overview

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 18 / 23
Version: 1.13.1

Solution: Case-11 Date: 28/02/2024

Results
Reference
Member Max deflection Utilization
Load Combination number* Governing criteria Length Limit
No. [mm] [%]
[mm]
1 004-SLS Relative (Beam) 406.90 L/200 -0.07 0.00
2 004-SLS Relative (Beam) 900.00 L/200 0.01 0.00
3 004-SLS Relative (Beam) 406.90 L/200 0.00 0.00
4 004-SLS Relative (Beam) 341.31 L/200 0.00 0.00
5 004-SLS Relative (Beam) 341.31 L/200 0.00 0.00

*004-SLS: SW + Design Loads. Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7

Deflection 1.00 * LC1

Deflection 1.00 * LC1 + 1.00 * LC2

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 19 / 23
Version: 1.13.1

Solution: Case-11 Date: 28/02/2024

Deflection 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 20 / 23
Version: 1.13.1

Solution: Case-11 Date: 28/02/2024

5.3 System Connectors

5.3 Connectors

5.3.1 Overview

Connector: MT-C-L2 OC
Fx Fy Fz Mx My Mz
Connector variant: MT-C-L2 OC (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 2
Local Forces: 0.43 -0.43 3.20 0.00 -0.00 -0.00
Resistance: 3.97 1.56 12.38 0.06
Equation: abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)
Utilization: 64.36 % OK

Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
Combination

Connector: MT-AB-LL2 45 OC
Fx Fy Fz Mx My Mz
Connector variant: MT-AB-LL2 45 OC (E)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 5
Local Forces: -1.04 0.00 0.00 -0.00 0.00 0.00
Resistance: 9.72 0.10 0.10 0.10 0.00 0.00
abs(Fx.ed/Fx.rd);abs(Fy.ed/Fy.rd);abs(Fz.ed/Fz.rd);abs(Mx.ed/Mx.rd);abs(My
Equation:
.ed/My.rd);abs(Mz.ed/Mz.rd)
Utilization: 10.68 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 21 / 23
Version: 1.13.1

Solution: Case-11 Date: 28/02/2024

5.4 Base Connectors

5.4 Bases

5.4.1 Overview

Base connector: MT-B-O2 OC


Fx Fy Fz Mx My Mz
Connector variant: MT-B-O2 OC (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 4
Local Forces: -2.52 0.30 0.43 0.00 -0.18 0.00
Resistance: 14.00 2.43 7.34 0.06 0.55 0.23
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 68.58 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
Combination
Base connector: MT-AB A OC
Fx Fy Fz Mx My Mz
Connector variant: MT-AB A OC (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 6
Local Forces: -1.05 0.00 0.01 -0.00 0.00 0.00
Resistance: 13.86 0.10 0.10 0.10 0.00 0.00
abs(Fx.ed/Fx.rd);abs(Fy.ed/Fy.rd);abs(Fz.ed/Fz.rd);abs(Mx.ed/Mx.rd);abs(My
Equation:
.ed/My.rd);abs(Mz.ed/Mz.rd)
Utilization: 7.57 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 22 / 23
Version: 1.13.1

Solution: Case-11 Date: 28/02/2024

6 Remarks, Your Cooperation Duties

Any and all information and data contained in the Software concern solely the use of Hilti products and based on the principles, formulas and security
regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly complied with by
the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the relevant Hilti product.
The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole
responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole responsibility for
having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior
to using them for your specific facility. The Software servers only as an aid to interpret norms and permits without any guarantee as to the absence of
errors, the correctness and relevance ot the results or suitability for a specific application.

You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular
backup of programs and, if applicable, carry out the updates of that you are using the current and thus up-to-date version of the Software in each case
by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or
programs, arising from a culpable breach of duty by you.

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 23 / 23
Case-12

Project: SA-13082-SF

Submitted by:

Hilti contact information


Contact name:
Contact e-mail:
Contact phone:
Contact company:

Customer contact information


Customer name:
Customer e-mail:
Customer phone:
Customer company:

Date: 28/02/2024

This submittal is auto-generated based on user-selected inputs.


Therefore, Hilti no representation as to the suitability of these systems for their intended use. 1 / 23
Version: 1.13.1

Solution: Case-12 Date: 28/02/2024

Table of content

1 Geometry and Application


1.1 Supports
1.2 Nodes
1.3 Members
1.4 Connections
1.5 Release Conditions
1.6 Media Interface Channel
1.7 Gliders
2 Part list
2.1 Members
2.2 Base Connectors
2.3 System Connectors
2.4 Other
3 Load Types
3.1 Loading objects
3.2 Point Loads
3.3 Distributed loads
3.4 Area loads
4 Load Combinations
4.1 Ultimate Limit State
4.2 Serviceability Limit State
5 Results
5.1 Calculation summary
5.2 Members
5.3 System Connectors
5.4 Base Connectors
6 Remarks, Your Cooperation Duties

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 2 / 23
Version: 1.13.1

Solution: Case-12 Date: 28/02/2024

1 Geometry and Application

Support Details
Modular Support Spacing [mm] Undefined

Intermediate Supports required?

Pipe Fasteners with Glider and Presetting used? (See


subchapter 'Gliders' in chapter 'Geometry and
Application')

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 3 / 23
Version: 1.13.1

Solution: Case-12 Date: 28/02/2024

1.1 Supports - Concrete

Concrete

Thickness Drilling Depth


Node No. No. Orientation Concrete grade
[mm] [mm]
1 1 Horizontal C20/25 200.00 150
4 2 Horizontal C20/25 200.00 150
6 3 Horizontal C20/25 200.00 150
8 4 Horizontal C20/25 200.00 150

1.2 Nodes

X Y Z
No. No. Connector name Connector variant
[mm] [mm] [mm]
1 1 -190.75 0.00 -500.00 MT-B-O2B OC MT-B-O2B OC (C)
2 - -190.75 0.00 711.90 MT-C-L2 OC MT-C-L2 OC (C)
3 - 709.25 0.00 711.90 MT-C-L2 OC MT-C-L2 OC (C)
4 2 709.25 0.00 -500.00 MT-B-O2B OC MT-B-O2B OC (C)
5 - 709.25 0.00 278.45 MT-AB-LL2 45 OC MT-AB-LL2 45 OC (E)
6 3 709.25 766.68 -488.23 MT-AB A OC MT-AB A OC (C)
7 - -190.75 0.00 278.45 MT-AB-LL2 45 OC MT-AB-LL2 45 OC (E)
8 4 -190.75 766.68 -488.23 MT-AB A OC MT-AB A OC (C)

1.3 Members

Member Releases Rotation


No. Node start Node end Member Name
Start End [°]
1 1 2 - 1 MT-40D 180.00
2 2 3 1 2 MT-60 0.00
3 3 4 2 - MT-40D 180.00
4 5 6 3 4 MT-40 0.00
5 7 8 5 6 MT-40 0.00

1.4 Connections

Cross- Cross- Cross- Cross-


Section/Rotation Section/Rotation Section/Rotation Section/Rotation
Node No. Description Variant
Arm1 Arm2 Arm3 Arm4
[-/°] [-/°] [-/°] [-/°]
1 MT-B-O2B OC MT-B-O2B OC (C) MT-40D/180 - - -
2 MT-C-L2 OC MT-C-L2 OC (C) MT-40D/180 MT-60/0 - -
3 MT-C-L2 OC MT-C-L2 OC (C) MT-60/0 MT-40D/180 - -
4 MT-B-O2B OC MT-B-O2B OC (C) MT-40D/180 - - -
5 MT-AB-LL2 45 OC MT-AB-LL2 45 OC (E) MT-40D/180 MT-40/0 - -
6 MT-AB A OC MT-AB A OC (C) MT-40/0 - - -
7 MT-AB-LL2 45 OC MT-AB-LL2 45 OC (E) MT-40D/180 MT-40/0 - -
8 MT-AB A OC MT-AB A OC (C) MT-40/0 - - -

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 4 / 23
Version: 1.13.1

Solution: Case-12 Date: 28/02/2024

1.5 Release Conditions

Spring Constants
Releases
Member Translational Rotational
No. Cu,x Cu,y Cu,z Cφx Cφy Cφz
Ux Uy Uz φx φy φz
[kN/m] [kN/m] [kN/m] [kNm/Rad] [kNm/Rad] [kNm/Rad]
2 no no no no yes yes - - - - 0.001 0.001
2 no no no no yes yes - - - - 0.001 0.001
4 no no no no yes yes - - - - 0.000 0.000
4 no no no no yes yes - - - - 0.000 0.000
5 no no no no yes yes - - - - 0.000 0.000
5 no no no no yes yes - - - - 0.000 0.000

1.6 Media Interface Channel

Start Position Length


No. Member No. Media Interface Z-Position Y-Position
[mm] [mm]

1.7 Gliders

Position Start Travel


No. Member No. Glider Custom Load
[mm] [mm] [mm]

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 5 / 23
Version: 1.13.1

Solution: Case-12 Date: 28/02/2024

2 Part list

2.1 Members

Quantity Weight Length


Position Item Number Description Cutting type
[-] [kg] [mm]
1 2268520 I.-Channel MT-40D OC 2 11.29 1344.88 N - None
2 2268516 I.-Channel MT-60 OC 1 3.14 815.00 N - None
3 2268508 I.-Channel MT-40 OC 1 2.13 1043.77 N - None
4 2268508 I.-Channel MT-40 OC 1 2.13 1044.22 N - None

2.2 Base Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
5 2282213 2-hole Baseplate MT-B-O2B OC 2 4.14
11 2346396 Angle brace MT-AB A OC set adjustable 2 0.88

2.3 System Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
9 2271519 Angle connector MT-C-L2 OC 2 0.52
10 2273585 Angle brace MT-AB-LL2 45 OC 2 1.11

2.4 Other

Quantity Weight
Position Item Number Description
[-] [kg]
6 2273256 Hexagon bolt MT-TLB OC 22 0.55
7 2272082 Twist-Lock MT-TL M10 OC 22 0.77
8 2105870 Stud anchor HST3-R M12x115 40/20 8 0.81

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 6 / 23
Version: 1.13.1

Solution: Case-12 Date: 28/02/2024

3 Load Types

3. Loads

Custom loads

Load No. Load Distribution Load Case Load Type Comments


1 Point load LC 7: Design Permanent -
2 Point load LC 7: Design Permanent -
3 Point load LC 13: Seismic (+x) Seismic -
4 Point load LC 14: Seismic (-x) Seismic -
5 Point load LC 13: Seismic (+x) Seismic -
6 Point load LC 14: Seismic (-x) Seismic -
7 Point load LC 2: Pipe Permanent -
8 Point load LC 2: Pipe Permanent -

3.2 Point Loads

Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
1 Design 2 250.00 0.00 0.00 -3.18 0.00 0.00 0.00
2 Design 2 650.00 0.00 0.00 -3.18 0.00 0.00 0.00
3 Seismic (+x) 2 250.00 0.04 0.00 0.00 0.00 0.00 0.00
4 Seismic (-x) 2 250.00 -0.04 -0.00 -0.00 -0.00 -0.00 -0.00
5 Seismic (+x) 2 650.00 0.04 0.00 0.00 0.00 0.00 0.00
6 Seismic (-x) 2 650.00 -0.04 -0.00 -0.00 -0.00 -0.00 -0.00
9 Pipe 2 250.00 0.32 0.32 0.00 0.00 0.00 0.00
10 Pipe 2 650.00 0.32 0.32 0.00 0.00 0.00 0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 7 / 23
Version: 1.13.1

Solution: Case-12 Date: 28/02/2024


Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
11 Self Weight Support 1 0.00 0.00 0.00 -0.02 0.00 0.00 0.00
12 Self Weight Support 1 1211.90 0.00 0.00 -0.00 0.00 0.00 0.00
13 Self Weight Support 2 900.00 0.00 0.00 -0.00 0.00 0.00 0.00
14 Self Weight Support 3 1211.90 0.00 0.00 -0.02 0.00 0.00 0.00
15 Self Weight Support 3 433.45 0.00 0.00 -0.01 0.00 0.00 0.00
16 Self Weight Support 4 1084.25 0.00 0.00 -0.00 0.00 0.00 0.00
17 Self Weight Support 1 778.45 0.00 0.00 -0.01 0.00 0.00 0.00
18 Self Weight Support 5 1084.25 0.00 0.00 -0.00 0.00 0.00 0.00

3.3 Distributed loads

Start End
Fx Fy Fz Mx My Mz
Load No. Load Type Members Position Position
[kN/m] [kN/m] [kN/m] [kNm/m] [kNm/m] [kNm/m]
[mm] [mm]
19 Self Weight Support 1 0.00 1211.90 0.00 0.00 -0.04 0.00 0.00 0.00
20 Self Weight Support 2 0.00 900.00 0.00 0.00 -0.04 0.00 0.00 0.00
21 Self Weight Support 3 0.00 1211.90 0.00 0.00 -0.04 0.00 0.00 0.00
22 Self Weight Support 4 0.00 1084.25 0.00 0.00 -0.02 0.00 0.00 0.00
23 Self Weight Support 5 0.00 1084.25 0.00 0.00 -0.02 0.00 0.00 0.00

3.4 Area loads

3.4.1 User input

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 8 / 23
Version: 1.13.1

Solution: Case-12 Date: 28/02/2024

4 Load Combinations

Design base EN 1993

Load combination design base EN 1990

4.1 Ultimate Limit State

Design base Load combination and safety factors


ULS - 001a-ULS: SW_inf (Support Only) 1.00 * LC1
ULS - 001b-ULS: SW_sup (Support Only) 1.35 * LC1
ULS - 002a-ULS: SW_inf Support + Media 1.00 * LC1 + 1.00 * LC2
ULS - 002b-ULS: SW_sup Support + Media 1.35 * LC1 + 1.35 * LC2
ULS - 004a-ULS: SW_inf + Design Loads 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC7
ULS - 004b-ULS: SW_sup + Design Loads 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
ULS - 027a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC13
z) + Live + Snow
ULS - 027b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC14
+ Live + Snow
ULS - 029a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC13
z) + Live + Snow
ULS - 030a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC14
+ Live + Snow
ULS - 027a-ULS_Base : SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 027b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 029a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 030a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 031a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC13 + 1.00 * 0.74 * LC7
z) + Design
ULS - 031b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC14 + 1.00 * 0.74 * LC7
+ Design
ULS - 033a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC13 + 1.00 * 0.74 * LC7
z) + Design
ULS - 034a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC14 + 1.00 * 0.74 * LC7
+ Design
ULS - 032a-ULS_Base: SW + Seismic (+x) + Seismic (-y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC13 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 031b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC14 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 033a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC13 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 034a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC14 + 1.00 * 0.74 * LC7
Seismic (-z) + Design

4.2 Serviceability Limit State

Load Case Load combination and safety factors


SLS - 001-SLS: SW (Support Only) 1.00 * LC1
SLS - 002-SLS: SW Support + Media Objects 1.00 * LC1 + 1.00 * LC2
SLS - 004-SLS: SW + Design Loads 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 9 / 23
Version: 1.13.1

Solution: Case-12 Date: 28/02/2024

5 Results

5.1 Calculation summary

5.1.3 Members

Governing load ULS SLS


No Member Status
combination number* [%] [%]
1 MT-40D 002-SLS 50.58 37.86 OK
2 MT-60 004b-ULS 77.64 - OK
3 MT-40D 004-SLS 50.58 37.86 OK
11 MT-40 004b-ULS 14.55 - OK
12 MT-40 004b-ULS 14.55 - OK

5.1.2 Base Connectors

Governing load ULS SLS


No Base connector Status
combination number* [%] [%]
1 MT-B-O2B OC 004b-ULS 78.76 - OK
4 MT-B-O2B OC 004b-ULS 78.76 - OK
6 MT-AB A OC 001b-ULS 14.00 - OK
8 MT-AB A OC 001b-ULS 14.00 - OK

5.1.3 System Connectors

Governing load ULS SLS


No Connector Status
combination number* [%] [%]
2 MT-C-L2 OC 004b-ULS 78.52 - OK
3 MT-C-L2 OC 004b-ULS 75.13 - OK
5 MT-AB-LL2 45 OC 004b-ULS 11.20 - OK
7 MT-AB-LL2 45 OC 004b-ULS 11.20 - OK
*002-SLS: SW Support + Media Objects . Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2
*004b-ULS: SW_sup + Design Loads . Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
*004-SLS: SW + Design Loads . Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7
*001b-ULS: SW_sup (Support Only) . Respective Combination Equation: 1.35 * LC1

Overall Status: Calculation OK, design criteria met!

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 10 / 23
Version: 1.13.1

Solution: Case-12 Date: 28/02/2024

5.2 Members

5.2.1 Member Properties


5.2.1.1 MT-40D Members: 1, 3
5.2.1.1.1 Section properties
t A Iy Iz It
[mm] [mm²] [mm⁴] [mm⁴] [mm⁴]
2.00 429.52 299600.00 131800.00 520.41

Iω M Wy Wz Wy
[mm⁶] [kg/m] [mm³] [mm³] [mm³]
154300000.00 8.40 -7048.65 -6199.90 -7048.65

5.2.1.1.2 Material properties


E G Fu Fy Fy.cold
Steel grade
[N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²]
Steel S 280 GD 210000.00 80769.00 360.00 280.00 305.00

5.2.1.2 MT-60 Members: 2


5.2.1.2.1 Section properties
t A Iy Iz It
[mm] [mm²] [mm⁴] [mm⁴] [mm⁴]
2.75 498.77 285700.00 170800.00 999.88

Iω M Wy Wz Wy
[mm⁶] [kg/m] [mm³] [mm³] [mm³]
158106000.00 3.85 -7804.06 -8037.37 -7804.06

5.2.1.2.2 Material properties


E G Fu Fy Fy.cold
Steel grade
[N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²]
Steel S 280 GD 210000.00 80769.00 360.00 280.00 311.60

5.2.1.3 MT-40 Members: 4, 5


5.2.1.3.1 Section properties
t A Iy Iz It
[mm] [mm²] [mm⁴] [mm⁴] [mm⁴]
2.00 285.00 57717.48 65876.44 259.85

Iω M Wy Wz Wy
[mm⁶] [kg/m] [mm³] [mm³] [mm³]
38410000.00 2.04 -2652.65 -3099.95 -2652.65

5.2.1.3.2 Material properties


E G Fu Fy Fy.cold
Steel grade
[N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²]
Steel S 280 GD 210000.00 80769.00 360.00 280.00 305.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 11 / 23
Version: 1.13.1

Solution: Case-12 Date: 28/02/2024

5.2.2 Member Design

5.2.2.1 Overview

5.2.2.2 Stress Analysis

5.2.2.2.1 Table of Results

Load Combination σ τ σeqv σlimit τlimit Utilization


No. Member
number* [N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²] [%]
I.-Channel MT-40D
1 004b-ULS -90.85 15.67 90.87 277.27 160.08 32.77
OC
I.-Channel MT-60
2 004b-ULS -113.56 19.73 113.70 283.27 163.55 40.14
OC
I.-Channel MT-40D
3 004b-ULS -90.85 -15.67 90.87 277.27 160.08 32.77
OC
I.-Channel MT-40
4 004b-ULS -6.22 0.00 6.25 277.27 0.00 2.26
OC
I.-Channel MT-40
5 004b-ULS -6.22 0.00 6.25 277.27 0.00 2.26
OC

*004b-ULS: SW_sup + Design Loads. Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7

5.2.2.2 Governing Member Loading

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 12 / 23
Version: 1.13.1

Solution: Case-12 Date: 28/02/2024

Beam No. 1

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40D 0.00 004b-ULS -2.52 0.35 0.43 0.00 -0.52 0.08
MT-40D 242.38 004b-ULS -2.51 0.35 0.43 0.00 -0.42 -0.00
MT-40D 484.76 004b-ULS -2.49 0.35 0.43 0.00 -0.31 -0.09
MT-40D 727.14 004b-ULS -2.48 0.35 0.43 0.00 -0.21 -0.17
MT-40D 778.45(-) 004b-ULS -2.48 0.35 0.43 0.00 -0.19 -0.19
MT-40D 778.45(+) 004b-ULS -3.23 -0.43 0.43 0.00 -0.19 -0.19
MT-40D 969.52 004b-ULS -3.22 -0.43 0.43 0.00 -0.10 -0.10
MT-40D 1211.90 004b-ULS -3.21 -0.43 0.43 0.00 0.00 -0.00

Beam No. 2

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-60 0.00 004b-ULS 0.43 0.43 -3.20 0.00 -0.00 0.00
MT-60 180.00 004b-ULS 0.43 0.43 -3.19 0.00 -0.58 -0.08
MT-60 250.00(-) 004b-ULS 0.43 0.43 -3.19 0.00 -0.80 -0.11
MT-60 250.00(+) 004b-ULS -0.00 -0.00 -0.01 0.00 -0.80 -0.11
MT-60 360.00 004b-ULS -0.00 -0.00 -0.00 0.00 -0.80 -0.11
MT-60 540.00 004b-ULS -0.00 -0.00 0.00 0.00 -0.80 -0.11
MT-60 650.00(-) 004b-ULS -0.00 -0.00 0.01 0.00 -0.80 -0.11
MT-60 650.00(+) 004b-ULS -0.43 -0.43 3.19 0.00 -0.80 -0.11
MT-60 720.00 004b-ULS -0.43 -0.43 3.19 0.00 -0.58 -0.08
MT-60 900.00 004b-ULS -0.43 -0.43 3.20 0.00 0.00 0.00

Beam No. 3

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40D 0.00 004b-ULS -3.21 0.43 0.43 -0.00 -0.00 -0.00
MT-40D 242.38 004b-ULS -3.22 0.43 0.43 -0.00 0.10 -0.10
MT-40D 433.45(-) 004b-ULS -3.23 0.43 0.43 -0.00 0.19 -0.19
MT-40D 433.45(+) 004b-ULS -2.48 -0.35 0.43 0.00 0.19 -0.19
MT-40D 484.76 004b-ULS -2.48 -0.35 0.43 0.00 0.21 -0.17
MT-40D 727.14 004b-ULS -2.49 -0.35 0.43 0.00 0.31 -0.09
MT-40D 969.52 004b-ULS -2.51 -0.35 0.43 0.00 0.42 -0.00
MT-40D 1211.90 004b-ULS -2.52 -0.35 0.43 0.00 0.52 0.08

Beam No. 4

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40 0.00 004b-ULS -1.09 0.00 -0.01 -0.00 0.00 -0.00
MT-40 216.85 004b-ULS -1.09 0.00 -0.01 -0.00 -0.00 -0.00
MT-40 433.70 004b-ULS -1.10 0.00 -0.00 -0.00 -0.00 -0.00
MT-40 650.55 004b-ULS -1.10 0.00 0.00 -0.00 -0.00 -0.00
MT-40 867.40 004b-ULS -1.11 0.00 0.01 -0.00 -0.00 -0.00
MT-40 1084.25 004b-ULS -1.11 0.00 0.01 -0.00 -0.00 -0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 13 / 23
Version: 1.13.1

Solution: Case-12 Date: 28/02/2024

Beam No. 5

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40 0.00 004b-ULS -1.09 0.00 -0.01 -0.00 0.00 -0.00
MT-40 216.85 004b-ULS -1.09 0.00 -0.01 -0.00 -0.00 -0.00
MT-40 433.70 004b-ULS -1.10 0.00 -0.00 -0.00 -0.00 -0.00
MT-40 650.55 004b-ULS -1.10 0.00 0.00 -0.00 -0.00 -0.00
MT-40 867.40 004b-ULS -1.11 0.00 0.01 -0.00 -0.00 -0.00
MT-40 1084.25 004b-ULS -1.11 0.00 0.01 -0.00 -0.00 -0.00

*004b-ULS: SW_sup + Design Loads. Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7

Normal load

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 14 / 23
Version: 1.13.1

Solution: Case-12 Date: 28/02/2024

Shear load in Y direction

Shear load in Z direction

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 15 / 23
Version: 1.13.1

Solution: Case-12 Date: 28/02/2024

Torsion around X

Moment around Y

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 16 / 23
Version: 1.13.1

Solution: Case-12 Date: 28/02/2024

Moment around Z

5.2.2.3 Shear Limits

Fy,Ed Fy,Rd Fz,Ed Fz,Rd Utilization


No. Type Load Combination number*
[kN] [kN] [kN] [kN] [%]
1 MT-40D 002b-ULS - - 0.43 4.25 10.16
3 MT-40D 004b-ULS - - 0.43 4.25 10.16

5.2.3 Stability Analysis

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 17 / 23
Version: 1.13.1

Solution: Case-12 Date: 28/02/2024

Buckling ratio

Buckling Max. lateral torsional Max. buckling under Max.


Member Length
Length Buckling ratio buckling under bending compression interaction
No. [mm]
[mm] [%] [%] [%]
1 1211.90 1211.90 1.00 35.54 3.52 50.58
2 900.00 900.00 1.00 69.93 1.00 77.64
3 1211.90 1211.90 1.00 35.54 3.52 50.58
4 1084.25 2168.50 2.00 0.00 14.55 14.55
5 1084.25 2168.50 2.00 0.00 14.55 14.55

5.2.4 Deflection Analysis

Criteria
☑Maximum Allowable Deflection (Beam) L/200
☑Maximum Allowable Deflection (Cantilever)L/150
- Maximum Deflection (Absolute) -
☑No Deflection checks calculated for 1.50mm

Overview

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 18 / 23
Version: 1.13.1

Solution: Case-12 Date: 28/02/2024

Results
Reference
Member Max deflection Utilization
Load Combination number* Governing criteria Length Limit
No. [mm] [%]
[mm]
1 004-SLS Relative(Cantilever) 1211.90 L/150 3.06 37.86
2 004-SLS Relative (Beam) 900.00 L/200 -0.03 0.00
3 004-SLS Relative(Cantilever) 1211.90 L/150 3.06 37.86
4 004-SLS Relative (Beam) 1084.25 L/200 -0.00 0.00
5 004-SLS Relative (Beam) 1084.25 L/200 -0.00 0.00

*004-SLS: SW + Design Loads. Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7

Deflection 1.00 * LC1

Deflection 1.00 * LC1 + 1.00 * LC2

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 19 / 23
Version: 1.13.1

Solution: Case-12 Date: 28/02/2024

Deflection 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 20 / 23
Version: 1.13.1

Solution: Case-12 Date: 28/02/2024

5.3 System Connectors

5.3 Connectors

5.3.1 Overview

Connector: MT-C-L2 OC
Fx Fy Fz Mx My Mz
Connector variant: MT-C-L2 OC (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 2
Local Forces: 0.43 0.43 -3.20 0.00 -0.00 0.00
Resistance: 3.97 1.56 8.00 0.06
Equation: abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)
Utilization: 78.52 % OK

Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
Combination

Connector: MT-AB-LL2 45 OC
Fx Fy Fz Mx My Mz
Connector variant: MT-AB-LL2 45 OC (E)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 5
Local Forces: -1.09 0.00 0.01 -0.00 0.00 0.00
Resistance: 9.72 0.10 0.10 0.10 0.00 0.00
abs(Fx.ed/Fx.rd);abs(Fy.ed/Fy.rd);abs(Fz.ed/Fz.rd);abs(Mx.ed/Mx.rd);abs(My
Equation:
.ed/My.rd);abs(Mz.ed/Mz.rd)
Utilization: 11.20 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 21 / 23
Version: 1.13.1

Solution: Case-12 Date: 28/02/2024

5.4 Base Connectors

5.4 Bases

5.4.1 Overview

Base connector: MT-B-O2B OC


Fx Fy Fz Mx My Mz
Connector variant: MT-B-O2B OC (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 4
Local Forces: -2.55 -0.34 -0.43 0.00 0.52 -0.08
Resistance: 18.37 6.50 26.92 3.00 1.48 0.36
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 78.76 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
Combination
Base connector: MT-AB A OC
Fx Fy Fz Mx My Mz
Connector variant: MT-AB A OC (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 6
Local Forces: -1.11 0.00 0.01 -0.00 0.00 0.00
Resistance: 13.86 0.10 0.10 0.10 0.00 0.00
abs(Fx.ed/Fx.rd);abs(Fy.ed/Fy.rd);abs(Fz.ed/Fz.rd);abs(Mx.ed/Mx.rd);abs(My
Equation:
.ed/My.rd);abs(Mz.ed/Mz.rd)
Utilization: 14.00 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 22 / 23
Version: 1.13.1

Solution: Case-12 Date: 28/02/2024

6 Remarks, Your Cooperation Duties

Any and all information and data contained in the Software concern solely the use of Hilti products and based on the principles, formulas and security
regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly complied with by
the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the relevant Hilti product.
The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole
responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole responsibility for
having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior
to using them for your specific facility. The Software servers only as an aid to interpret norms and permits without any guarantee as to the absence of
errors, the correctness and relevance ot the results or suitability for a specific application.

You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular
backup of programs and, if applicable, carry out the updates of that you are using the current and thus up-to-date version of the Software in each case
by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or
programs, arising from a culpable breach of duty by you.

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 23 / 23
Case-13

Project: SA-13082-SF

Submitted by:

Hilti contact information


Contact name:
Contact e-mail:
Contact phone:
Contact company:

Customer contact information


Customer name:
Customer e-mail:
Customer phone:
Customer company:

Date: 28/02/2024

This submittal is auto-generated based on user-selected inputs.


Therefore, Hilti no representation as to the suitability of these systems for their intended use. 1 / 26
Version: 1.13.1

Solution: Case-13 Date: 28/02/2024

Table of content

1 Geometry and Application


1.1 Supports
1.2 Nodes
1.3 Members
1.4 Connections
1.5 Release Conditions
1.6 Media Interface Channel
1.7 Gliders
2 Part list
2.1 Members
2.2 Base Connectors
2.3 System Connectors
2.4 Other
3 Load Types
3.1 Loading objects
3.2 Point Loads
3.3 Distributed loads
3.4 Area loads
4 Load Combinations
4.1 Ultimate Limit State
4.2 Serviceability Limit State
5 Results
5.1 Calculation summary
5.2 Members
5.3 System Connectors
5.4 Base Connectors
6 Remarks, Your Cooperation Duties

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 2 / 26
Version: 1.13.1

Solution: Case-13 Date: 28/02/2024

1 Geometry and Application

Support Details
Modular Support Spacing [mm] Undefined

Intermediate Supports required?

Pipe Fasteners with Glider and Presetting used? (See


subchapter 'Gliders' in chapter 'Geometry and
Application')

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 3 / 26
Version: 1.13.1

Solution: Case-13 Date: 28/02/2024

1.1 Supports - Concrete

Concrete

Thickness Drilling Depth


Node No. No. Orientation Concrete grade
[mm] [mm]
1 1 Horizontal C20/25 200.00 150
4 2 Horizontal C20/25 200.00 150
6 3 Horizontal C20/25 200.00 150
8 4 Horizontal C20/25 200.00 150

1.2 Nodes

X Y Z
No. No. Connector name Connector variant
[mm] [mm] [mm]
1 1 -190.75 0.00 -500.00 MT-B-O2B OC MT-B-O2B OC (C)
2 - -190.75 0.00 461.90 MT-C-L2 OC MT-C-L2 OC (C)
3 - 709.25 0.00 461.90 MT-C-L2 OC MT-C-L2 OC (C)
4 2 709.25 0.00 -500.00 MT-B-O2B OC MT-B-O2B OC (C)
5 - 709.25 0.00 -19.05 MT-AB-LL2 45 OC MT-AB-LL2 45 OC (E)
6 3 709.25 480.95 -500.00 MT-AB A OC MT-AB A OC (C)
7 - -190.75 0.00 -19.05 MT-AB-LL2 45 OC MT-AB-LL2 45 OC (E)
8 4 -190.75 480.95 -500.00 MT-AB A OC MT-AB A OC (C)

1.3 Members

Member Releases Rotation


No. Node start Node end Member Name
Start End [°]
1 1 2 - 1 MT-40D 180.00
2 2 3 1 2 MT-60 0.00
3 3 4 2 - MT-40D 180.00
4 5 6 3 4 MT-40 0.00
5 7 8 5 6 MT-40 0.00

1.4 Connections

Cross- Cross- Cross- Cross-


Section/Rotation Section/Rotation Section/Rotation Section/Rotation
Node No. Description Variant
Arm1 Arm2 Arm3 Arm4
[-/°] [-/°] [-/°] [-/°]
1 MT-B-O2B OC MT-B-O2B OC (C) MT-40D/180 - - -
2 MT-C-L2 OC MT-C-L2 OC (C) MT-40D/180 MT-60/0 - -
3 MT-C-L2 OC MT-C-L2 OC (C) MT-60/0 MT-40D/180 - -
4 MT-B-O2B OC MT-B-O2B OC (C) MT-40D/180 - - -
5 MT-AB-LL2 45 OC MT-AB-LL2 45 OC (E) MT-40D/180 MT-40/0 - -
6 MT-AB A OC MT-AB A OC (C) MT-40/0 - - -
7 MT-AB-LL2 45 OC MT-AB-LL2 45 OC (E) MT-40D/180 MT-40/0 - -
8 MT-AB A OC MT-AB A OC (C) MT-40/0 - - -

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 4 / 26
Version: 1.13.1

Solution: Case-13 Date: 28/02/2024

1.5 Release Conditions

Spring Constants
Releases
Member Translational Rotational
No. Cu,x Cu,y Cu,z Cφx Cφy Cφz
Ux Uy Uz φx φy φz
[kN/m] [kN/m] [kN/m] [kNm/Rad] [kNm/Rad] [kNm/Rad]
2 no no no no yes yes - - - - 0.001 0.001
2 no no no no yes yes - - - - 0.001 0.001
4 no no no no yes yes - - - - 0.000 0.000
4 no no no no yes yes - - - - 0.000 0.000
5 no no no no yes yes - - - - 0.000 0.000
5 no no no no yes yes - - - - 0.000 0.000

1.6 Media Interface Channel

Start Position Length


No. Member No. Media Interface Z-Position Y-Position
[mm] [mm]

1.7 Gliders

Position Start Travel


No. Member No. Glider Custom Load
[mm] [mm] [mm]

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 5 / 26
Version: 1.13.1

Solution: Case-13 Date: 28/02/2024

2 Part list

2.1 Members

Quantity Weight Length


Position Item Number Description Cutting type
[-] [kg] [mm]
1 2268520 I.-Channel MT-40D OC 2 9.19 1094.88 N - None
2 2268516 I.-Channel MT-60 OC 1 3.14 815.00 N - None
3 2268508 I.-Channel MT-40 OC 1 1.30 639.68 N - None
4 2268508 I.-Channel MT-40 OC 1 1.31 640.14 N - None

2.2 Base Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
5 2282213 2-hole Baseplate MT-B-O2B OC 2 4.14
11 2346396 Angle brace MT-AB A OC set adjustable 2 0.88

2.3 System Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
9 2271519 Angle connector MT-C-L2 OC 2 0.52
10 2273585 Angle brace MT-AB-LL2 45 OC 2 1.11

2.4 Other

Quantity Weight
Position Item Number Description
[-] [kg]
6 2273256 Hexagon bolt MT-TLB OC 22 0.55
7 2272082 Twist-Lock MT-TL M10 OC 22 0.77
8 2105870 Stud anchor HST3-R M12x115 40/20 8 0.81

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 6 / 26
Version: 1.13.1

Solution: Case-13 Date: 28/02/2024

3 Load Types

3. Loads

Custom loads

Load No. Load Distribution Load Case Load Type Comments


1 Point load LC 7: Design Permanent -
2 Point load LC 7: Design Permanent -
3 Point load LC 13: Seismic (+x) Seismic -
4 Point load LC 14: Seismic (-x) Seismic -
5 Point load LC 13: Seismic (+x) Seismic -
6 Point load LC 14: Seismic (-x) Seismic -
7 Point load LC 2: Pipe Permanent -
8 Point load LC 2: Pipe Permanent -
9 Point load LC 8: Wind (+x) Variable -
10 Point load LC 9: Wind (-x) Variable -

3.2 Point Loads

Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
1 Design 2 250.00 0.00 0.00 -3.18 0.00 0.00 0.00
2 Design 2 650.00 0.00 0.00 -3.18 0.00 0.00 0.00
3 Seismic (+x) 2 250.00 0.04 0.00 0.00 0.00 0.00 0.00
4 Seismic (-x) 2 250.00 -0.04 -0.00 -0.00 -0.00 -0.00 -0.00
5 Seismic (+x) 2 650.00 0.04 0.00 0.00 0.00 0.00 0.00
6 Seismic (-x) 2 650.00 -0.04 -0.00 -0.00 -0.00 -0.00 -0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 7 / 26
Version: 1.13.1

Solution: Case-13 Date: 28/02/2024


Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
9 Pipe 2 250.00 0.32 0.32 0.00 0.00 0.00 0.00
10 Pipe 2 650.00 0.32 0.32 0.00 0.00 0.00 0.00
11 Wind (+x) 2 450.00 0.66 0.00 0.00 0.00 0.00 0.00
12 Wind (-x) 2 450.00 -0.66 -0.00 -0.00 -0.00 -0.00 -0.00
13 Self Weight Support 1 0.00 0.00 0.00 -0.02 0.00 0.00 0.00
14 Self Weight Support 1 961.90 0.00 0.00 -0.00 0.00 0.00 0.00
15 Self Weight Support 2 900.00 0.00 0.00 -0.00 0.00 0.00 0.00
16 Self Weight Support 3 961.90 0.00 0.00 -0.02 0.00 0.00 0.00
17 Self Weight Support 3 480.95 0.00 0.00 -0.01 0.00 0.00 0.00
18 Self Weight Support 4 680.17 0.00 0.00 -0.00 0.00 0.00 0.00
19 Self Weight Support 1 480.95 0.00 0.00 -0.01 0.00 0.00 0.00
20 Self Weight Support 5 680.17 0.00 0.00 -0.00 0.00 0.00 0.00

3.3 Distributed loads

Start End
Fx Fy Fz Mx My Mz
Load No. Load Type Members Position Position
[kN/m] [kN/m] [kN/m] [kNm/m] [kNm/m] [kNm/m]
[mm] [mm]
21 Self Weight Support 1 0.00 961.90 0.00 0.00 -0.04 0.00 0.00 0.00
22 Self Weight Support 2 0.00 900.00 0.00 0.00 -0.04 0.00 0.00 0.00
23 Self Weight Support 3 0.00 961.90 0.00 0.00 -0.04 0.00 0.00 0.00
24 Self Weight Support 4 0.00 680.17 0.00 0.00 -0.02 0.00 0.00 0.00
25 Self Weight Support 5 0.00 680.17 0.00 0.00 -0.02 0.00 0.00 0.00

3.4 Area loads

3.4.1 User input

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 8 / 26
Version: 1.13.1

Solution: Case-13 Date: 28/02/2024

4 Load Combinations

Design base EN 1993

Load combination design base EN 1990

4.1 Ultimate Limit State

Design base Load combination and safety factors


ULS - 001a-ULS: SW_inf (Support Only) 1.00 * LC1
ULS - 001b-ULS: SW_sup (Support Only) 1.35 * LC1
ULS - 002a-ULS: SW_inf Support + Media 1.00 * LC1 + 1.00 * LC2
ULS - 002b-ULS: SW_sup Support + Media 1.35 * LC1 + 1.35 * LC2
ULS - 004a-ULS: SW_inf + Design Loads 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC7
ULS - 004b-ULS: SW_sup + Design Loads 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
ULS - 006a-ULS: SW_inf + Wind (+x) 1.00 * LC1 + 1.00 * LC2 + 1.50 * LC8
ULS - 006b-ULS: SW_sup + Wind (+x) 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8
ULS - 007a-ULS: SW_inf + Wind (-x) 1.00 * LC1 + 1.00 * LC2 + 1.50 * LC9
ULS - 007b-ULS: SW_sup + Wind (-x) 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC9
ULS - 015a-ULS: SW_inf + Live + Snow + Wind (+x) 1.00 * LC1 + 1.00 * LC2 + 1.50 * 0.60 * LC8
ULS - 015b-ULS: SW_sup + Live + Snow + Wind (+x) 1.35 * LC1 + 1.35 * LC2 + 1.50 * 0.60 * LC8
ULS - 016a-ULS: SW_inf + Live + Snow + Wind (-x) 1.00 * LC1 + 1.00 * LC2 + 1.50 * 0.60 * LC9
ULS - 016b-ULS: SW_sup + Live + Snow + Wind (-x) 1.35 * LC1 + 1.35 * LC2 + 1.50 * 0.60 * LC9
ULS - 027a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC13
z) + Live + Snow
ULS - 027b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC14
+ Live + Snow
ULS - 029a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC13
z) + Live + Snow
ULS - 030a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC14
+ Live + Snow
ULS - 027a-ULS_Base : SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 027b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 029a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 030a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 031a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC13 + 1.00 * 0.74 * LC7
z) + Design
ULS - 031b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC14 + 1.00 * 0.74 * LC7
+ Design
ULS - 033a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC13 + 1.00 * 0.74 * LC7
z) + Design
ULS - 034a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC14 + 1.00 * 0.74 * LC7
+ Design
ULS - 032a-ULS_Base: SW + Seismic (+x) + Seismic (-y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC13 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 031b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC14 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 033a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC13 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 034a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC14 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 037-ULS: SW_inf + Impact + Live + Snow 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.20 * LC8
ULS - 038-ULS: SW_inf + Impact + Live + Snow 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.20 * LC9

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 9 / 26
Version: 1.13.1

Solution: Case-13 Date: 28/02/2024

4.2 Serviceability Limit State

Load Case Load combination and safety factors


SLS - 001-SLS: SW (Support Only) 1.00 * LC1
SLS - 002-SLS: SW Support + Media Objects 1.00 * LC1 + 1.00 * LC2
SLS - 004-SLS: SW + Design Loads 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7
SLS - 006-SLS: SW + Wind (+x) 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC8
SLS - 007-SLS: SW + Wind (-x) 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC9
SLS - 015-SLS: SW + Live + Snow + Wind (+x) 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC8
SLS - 016-SLS: SW + Live + Snow + Wind (-x) 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC9

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 10 / 26
Version: 1.13.1

Solution: Case-13 Date: 28/02/2024

5 Results

5.1 Calculation summary

5.1.3 Members

Governing load ULS SLS


No Member Status
combination number* [%] [%]
1 MT-40D 006-SLS 50.07 48.83 OK
2 MT-60 004b-ULS 77.64 - OK
3 MT-40D 006-SLS 50.07 48.83 OK
13 MT-40 004b-ULS 10.91 - OK
14 MT-40 004b-ULS 10.91 - OK

5.1.2 Base Connectors

Governing load ULS SLS


No Base connector Status
combination number* [%] [%]
1 MT-B-O2B OC 006b-ULS 95.49 - OK
4 MT-B-O2B OC 006b-ULS 95.50 - OK
6 MT-AB A OC 004b-ULS 10.40 - OK
8 MT-AB A OC 004b-ULS 10.40 - OK

5.1.3 System Connectors

Governing load ULS SLS


No Connector Status
combination number* [%] [%]
2 MT-C-L2 OC 004b-ULS 78.52 - OK
3 MT-C-L2 OC 004b-ULS 75.13 - OK
5 MT-AB-LL2 45 OC 004b-ULS 14.65 - OK
7 MT-AB-LL2 45 OC 004b-ULS 14.65 - OK
*006-SLS: SW + Wind (+x) . Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC8
*004b-ULS: SW_sup + Design Loads . Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
*006b-ULS: SW_sup + Wind (+x) . Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8

Overall Status: Calculation OK, design criteria met!

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 11 / 26
Version: 1.13.1

Solution: Case-13 Date: 28/02/2024

5.2 Members

5.2.1 Member Properties


5.2.1.1 MT-40D Members: 1, 3
5.2.1.1.1 Section properties
t A Iy Iz It
[mm] [mm²] [mm⁴] [mm⁴] [mm⁴]
2.00 429.52 299600.00 131800.00 520.41

Iω M Wy Wz Wy
[mm⁶] [kg/m] [mm³] [mm³] [mm³]
154300000.00 8.40 -7048.65 -6199.90 -7048.65

5.2.1.1.2 Material properties


E G Fu Fy Fy.cold
Steel grade
[N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²]
Steel S 280 GD 210000.00 80769.00 360.00 280.00 305.00

5.2.1.2 MT-60 Members: 2


5.2.1.2.1 Section properties
t A Iy Iz It
[mm] [mm²] [mm⁴] [mm⁴] [mm⁴]
2.75 498.77 285700.00 170800.00 999.88

Iω M Wy Wz Wy
[mm⁶] [kg/m] [mm³] [mm³] [mm³]
158106000.00 3.85 -7804.06 -8037.37 -7804.06

5.2.1.2.2 Material properties


E G Fu Fy Fy.cold
Steel grade
[N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²]
Steel S 280 GD 210000.00 80769.00 360.00 280.00 311.60

5.2.1.3 MT-40 Members: 4, 5


5.2.1.3.1 Section properties
t A Iy Iz It
[mm] [mm²] [mm⁴] [mm⁴] [mm⁴]
2.00 285.00 57717.48 65876.44 259.85

Iω M Wy Wz Wy
[mm⁶] [kg/m] [mm³] [mm³] [mm³]
38410000.00 2.04 -2652.65 -3099.95 -2652.65

5.2.1.3.2 Material properties


E G Fu Fy Fy.cold
Steel grade
[N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²]
Steel S 280 GD 210000.00 80769.00 360.00 280.00 305.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 12 / 26
Version: 1.13.1

Solution: Case-13 Date: 28/02/2024

5.2.2 Member Design

5.2.2.1 Overview

5.2.2.2 Stress Analysis

5.2.2.2.1 Table of Results

Load Combination σ τ σeqv σlimit τlimit Utilization


No. Member
number* [N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²] [%]
I.-Channel MT-40D
1 006b-ULS 137.18 28.92 137.23 277.27 160.08 49.49
OC
I.-Channel MT-60
2 004b-ULS -113.56 19.73 113.70 283.27 163.55 40.14
OC
I.-Channel MT-40D
3 006b-ULS 137.18 -28.92 137.23 277.27 160.08 49.49
OC
I.-Channel MT-40
4 006b-ULS 0.00 0.78 7.15 0.00 160.08 2.58
OC
I.-Channel MT-40
5 006b-ULS 0.00 0.78 7.15 0.00 160.08 2.58
OC

*006b-ULS: SW_sup + Wind (+x). Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8

*004b-ULS: SW_sup + Design Loads. Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7

5.2.2.2 Governing Member Loading

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 13 / 26
Version: 1.13.1

Solution: Case-13 Date: 28/02/2024

Beam No. 1

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40D 0.00 006b-ULS 0.90 0.57 0.93 0.00 -0.89 0.07
MT-40D 192.38 006b-ULS 0.91 0.57 0.93 0.00 -0.71 -0.04
MT-40D 384.76 006b-ULS 0.92 0.57 0.93 0.00 -0.53 -0.15
MT-40D 480.95(-) 006b-ULS 0.93 0.57 0.93 0.00 -0.45 -0.21
MT-40D 480.95(+) 006b-ULS -0.05 -0.43 0.93 0.00 -0.45 -0.21
MT-40D 577.14 006b-ULS -0.05 -0.43 0.93 0.00 -0.36 -0.17
MT-40D 769.52 006b-ULS -0.04 -0.43 0.93 0.00 -0.18 -0.08
MT-40D 961.90 006b-ULS -0.03 -0.43 0.93 0.00 0.00 0.00

Beam No. 2

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-60 0.00 004b-ULS 0.43 0.43 -3.20 0.00 0.00 0.00
MT-60 180.00 004b-ULS 0.43 0.43 -3.19 0.00 -0.58 -0.08
MT-60 250.00(-) 004b-ULS 0.43 0.43 -3.19 0.00 -0.80 -0.11
MT-60 250.00(+) 004b-ULS -0.00 -0.00 -0.01 0.00 -0.80 -0.11
MT-60 360.00 004b-ULS -0.00 -0.00 -0.00 0.00 -0.80 -0.11
MT-60 540.00 004b-ULS -0.00 -0.00 0.00 0.00 -0.80 -0.11
MT-60 650.00(-) 004b-ULS -0.00 -0.00 0.01 0.00 -0.80 -0.11
MT-60 650.00(+) 004b-ULS -0.43 -0.43 3.19 0.00 -0.80 -0.11
MT-60 720.00 004b-ULS -0.43 -0.43 3.19 0.00 -0.58 -0.08
MT-60 900.00 004b-ULS -0.43 -0.43 3.20 0.00 0.00 0.00

Beam No. 3

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40D 0.00 006b-ULS -0.03 0.43 0.93 -0.00 -0.00 -0.00
MT-40D 192.38 006b-ULS -0.04 0.43 0.93 -0.00 0.18 -0.08
MT-40D 384.76 006b-ULS -0.05 0.43 0.93 -0.00 0.36 -0.17
MT-40D 480.95(-) 006b-ULS -0.05 0.43 0.93 -0.00 0.45 -0.21
MT-40D 480.95(+) 006b-ULS 0.93 -0.57 0.93 0.00 0.45 -0.21
MT-40D 577.14 006b-ULS 0.92 -0.57 0.93 0.00 0.53 -0.15
MT-40D 769.52 006b-ULS 0.91 -0.57 0.93 0.00 0.71 -0.04
MT-40D 961.90 006b-ULS 0.90 -0.57 0.93 0.00 0.89 0.07

Beam No. 4

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40 0.00 004b-ULS -1.42 0.00 -0.01 -0.00 0.00 -0.00
MT-40 136.03 004b-ULS -1.43 0.00 -0.00 -0.00 -0.00 -0.00
MT-40 272.07 004b-ULS -1.43 0.00 -0.00 -0.00 -0.00 -0.00
MT-40 408.10 004b-ULS -1.43 0.00 0.00 -0.00 -0.00 -0.00
MT-40 544.13 004b-ULS -1.43 0.00 0.00 -0.00 -0.00 -0.00
MT-40 680.17 004b-ULS -1.44 0.00 0.01 -0.00 0.00 -0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 14 / 26
Version: 1.13.1

Solution: Case-13 Date: 28/02/2024

Beam No. 5

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40 0.00 004b-ULS -1.42 0.00 -0.01 -0.00 0.00 -0.00
MT-40 136.03 004b-ULS -1.43 0.00 -0.00 -0.00 -0.00 -0.00
MT-40 272.07 004b-ULS -1.43 0.00 -0.00 -0.00 -0.00 -0.00
MT-40 408.10 004b-ULS -1.43 0.00 0.00 -0.00 -0.00 -0.00
MT-40 544.13 004b-ULS -1.43 0.00 0.00 -0.00 -0.00 -0.00
MT-40 680.17 004b-ULS -1.44 0.00 0.01 -0.00 0.00 -0.00

*006b-ULS: SW_sup + Wind (+x). Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8

*004b-ULS: SW_sup + Design Loads. Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7

Normal load

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 15 / 26
Version: 1.13.1

Solution: Case-13 Date: 28/02/2024

Shear load in Y direction

Shear load in Z direction

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 16 / 26
Version: 1.13.1

Solution: Case-13 Date: 28/02/2024

Torsion around X

Moment around Y

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 17 / 26
Version: 1.13.1

Solution: Case-13 Date: 28/02/2024

Moment around Z

5.2.2.3 Shear Limits

Fy,Ed Fy,Rd Fz,Ed Fz,Rd Utilization


No. Type Load Combination number*
[kN] [kN] [kN] [kN] [%]
1 MT-40D 006b-ULS - - 0.93 4.25 21.81
3 MT-40D 006b-ULS - - 0.93 4.25 21.81

5.2.3 Stability Analysis

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 18 / 26
Version: 1.13.1

Solution: Case-13 Date: 28/02/2024

Buckling ratio

Buckling Max. lateral torsional Max. buckling under Max.


Member Length
Length Buckling ratio buckling under bending compression interaction
No. [mm]
[mm] [%] [%] [%]
1 961.90 961.90 1.00 50.07 0.00 50.07
2 900.00 900.00 1.00 69.94 1.00 77.64
3 961.90 961.90 1.00 50.07 0.00 50.07
4 680.17 1360.33 2.00 0.00 10.91 10.91
5 680.17 1360.33 2.00 0.00 10.91 10.91

5.2.4 Deflection Analysis

Criteria
☑Maximum Allowable Deflection (Beam) L/200
☑Maximum Allowable Deflection (Cantilever)L/150
- Maximum Deflection (Absolute) -
☑No Deflection checks calculated for 1.50mm

Overview

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 19 / 26
Version: 1.13.1

Solution: Case-13 Date: 28/02/2024

Results
Reference
Member Max deflection Utilization
Load Combination number* Governing criteria Length Limit
No. [mm] [%]
[mm]
1 006-SLS Relative(Cantilever) 961.90 L/150 3.13 48.83
2 016-SLS Relative (Beam) 900.00 L/200 0.00 0.00
3 006-SLS Relative(Cantilever) 961.90 L/150 3.13 48.83
4 016-SLS Relative (Beam) 680.17 L/200 -0.00 0.00
5 016-SLS Relative (Beam) 680.17 L/200 -0.00 0.00

*006-SLS: SW + Wind (+x). Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC8

*016-SLS: SW + Live + Snow + Wind (-x). Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC9

Deflection 1.00 * LC1

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 20 / 26
Version: 1.13.1

Solution: Case-13 Date: 28/02/2024

Deflection 1.00 * LC1 + 1.00 * LC2

Deflection 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 21 / 26
Version: 1.13.1

Solution: Case-13 Date: 28/02/2024

Deflection 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC8

Deflection 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC9

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 22 / 26
Version: 1.13.1

Solution: Case-13 Date: 28/02/2024

Deflection 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC8

Deflection 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC9

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 23 / 26
Version: 1.13.1

Solution: Case-13 Date: 28/02/2024

5.3 System Connectors

5.3 Connectors

5.3.1 Overview

Connector: MT-C-L2 OC
Fx Fy Fz Mx My Mz
Connector variant: MT-C-L2 OC (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 2
Local Forces: 0.43 0.43 -3.20 0.00 0.00 0.00
Resistance: 3.97 1.56 8.00 0.06
Equation: abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)
Utilization: 78.52 % OK

Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
Combination

Connector: MT-AB-LL2 45 OC
Fx Fy Fz Mx My Mz
Connector variant: MT-AB-LL2 45 OC (E)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 5
Local Forces: -1.42 0.00 0.01 -0.00 0.00 0.00
Resistance: 9.72 0.10 0.10 0.10 0.00 0.00
abs(Fx.ed/Fx.rd);abs(Fy.ed/Fy.rd);abs(Fz.ed/Fz.rd);abs(Mx.ed/Mx.rd);abs(My
Equation:
.ed/My.rd);abs(Mz.ed/Mz.rd)
Utilization: 14.65 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 24 / 26
Version: 1.13.1

Solution: Case-13 Date: 28/02/2024

5.4 Base Connectors

5.4 Bases

5.4.1 Overview

Base connector: MT-B-O2B OC


Fx Fy Fz Mx My Mz
Connector variant: MT-B-O2B OC (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 4
Local Forces: 0.87 -0.57 -0.93 0.00 0.89 -0.06
Resistance: 17.64 6.50 26.92 3.00 1.48 0.36
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 95.50 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8
Combination
Base connector: MT-AB A OC
Fx Fy Fz Mx My Mz
Connector variant: MT-AB A OC (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 6
Local Forces: -1.44 0.00 0.01 -0.00 0.00 0.00
Resistance: 13.86 0.10 0.10 0.10 0.00 0.00
abs(Fx.ed/Fx.rd);abs(Fy.ed/Fy.rd);abs(Fz.ed/Fz.rd);abs(Mx.ed/Mx.rd);abs(My
Equation:
.ed/My.rd);abs(Mz.ed/Mz.rd)
Utilization: 10.40 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 25 / 26
Version: 1.13.1

Solution: Case-13 Date: 28/02/2024

6 Remarks, Your Cooperation Duties

Any and all information and data contained in the Software concern solely the use of Hilti products and based on the principles, formulas and security
regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly complied with by
the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the relevant Hilti product.
The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole
responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole responsibility for
having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior
to using them for your specific facility. The Software servers only as an aid to interpret norms and permits without any guarantee as to the absence of
errors, the correctness and relevance ot the results or suitability for a specific application.

You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular
backup of programs and, if applicable, carry out the updates of that you are using the current and thus up-to-date version of the Software in each case
by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or
programs, arising from a culpable breach of duty by you.

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 26 / 26
Case-14

Project: SA-13082-SF

Submitted by:

Hilti contact information


Contact name:
Contact e-mail:
Contact phone:
Contact company:

Customer contact information


Customer name:
Customer e-mail:
Customer phone:
Customer company:

Date: 28/02/2024

This submittal is auto-generated based on user-selected inputs.


Therefore, Hilti no representation as to the suitability of these systems for their intended use. 1 / 26
Version: 1.13.1

Solution: Case-14 Date: 28/02/2024

Table of content

1 Geometry and Application


1.1 Supports
1.2 Nodes
1.3 Members
1.4 Connections
1.5 Release Conditions
1.6 Media Interface Channel
1.7 Gliders
2 Part list
2.1 Members
2.2 Base Connectors
2.3 System Connectors
2.4 Other
3 Load Types
3.1 Loading objects
3.2 Point Loads
3.3 Distributed loads
3.4 Area loads
4 Load Combinations
4.1 Ultimate Limit State
4.2 Serviceability Limit State
5 Results
5.1 Calculation summary
5.2 Members
5.3 System Connectors
5.4 Base Connectors
6 Remarks, Your Cooperation Duties

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 2 / 26
Version: 1.13.1

Solution: Case-14 Date: 28/02/2024

1 Geometry and Application

Support Details
Modular Support Spacing [mm] Undefined

Intermediate Supports required?

Pipe Fasteners with Glider and Presetting used? (See


subchapter 'Gliders' in chapter 'Geometry and
Application')

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 3 / 26
Version: 1.13.1

Solution: Case-14 Date: 28/02/2024

1.1 Supports - Concrete

Concrete

Thickness Drilling Depth


Node No. No. Orientation Concrete grade
[mm] [mm]
1 1 Horizontal C20/25 200.00 150
4 2 Horizontal C20/25 200.00 150
6 3 Horizontal C20/25 200.00 150
8 4 Horizontal C20/25 200.00 150

1.2 Nodes

X Y Z
No. No. Connector name Connector variant
[mm] [mm] [mm]
1 1 -190.75 0.00 -500.00 MT-B-O2B OC MT-B-O2B OC (C)
2 - -190.75 0.00 861.90 MT-C-L2 OC MT-C-L2 OC (C)
3 - 309.25 0.00 861.90 MT-C-L2 OC MT-C-L2 OC (C)
4 2 309.25 0.00 -500.00 MT-B-O2B OC MT-B-O2B OC (C)
5 - 309.25 0.00 -19.05 MT-AB-LL2 45 OC MT-AB-LL2 45 OC (E)
6 3 309.25 480.95 -500.00 MT-AB A OC MT-AB A OC (C)
7 - -190.75 0.00 -19.05 MT-AB-LL2 45 OC MT-AB-LL2 45 OC (E)
8 4 -190.75 480.95 -500.00 MT-AB A OC MT-AB A OC (C)

1.3 Members

Member Releases Rotation


No. Node start Node end Member Name
Start End [°]
1 1 2 - 1 MT-40D 180.00
2 2 3 1 2 MT-40 0.00
3 3 4 2 - MT-40D 180.00
4 5 6 3 4 MT-40 0.00
5 7 8 5 6 MT-40 0.00

1.4 Connections

Cross- Cross- Cross- Cross-


Section/Rotation Section/Rotation Section/Rotation Section/Rotation
Node No. Description Variant
Arm1 Arm2 Arm3 Arm4
[-/°] [-/°] [-/°] [-/°]
1 MT-B-O2B OC MT-B-O2B OC (C) MT-40D/180 - - -
2 MT-C-L2 OC MT-C-L2 OC (C) MT-40D/180 MT-40/0 - -
3 MT-C-L2 OC MT-C-L2 OC (C) MT-40/0 MT-40D/180 - -
4 MT-B-O2B OC MT-B-O2B OC (C) MT-40D/180 - - -
5 MT-AB-LL2 45 OC MT-AB-LL2 45 OC (E) MT-40D/180 MT-40/0 - -
6 MT-AB A OC MT-AB A OC (C) MT-40/0 - - -
7 MT-AB-LL2 45 OC MT-AB-LL2 45 OC (E) MT-40D/180 MT-40/0 - -
8 MT-AB A OC MT-AB A OC (C) MT-40/0 - - -

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 4 / 26
Version: 1.13.1

Solution: Case-14 Date: 28/02/2024

1.5 Release Conditions

Spring Constants
Releases
Member Translational Rotational
No. Cu,x Cu,y Cu,z Cφx Cφy Cφz
Ux Uy Uz φx φy φz
[kN/m] [kN/m] [kN/m] [kNm/Rad] [kNm/Rad] [kNm/Rad]
2 no no no no yes yes - - - - 0.001 0.001
2 no no no no yes yes - - - - 0.001 0.001
4 no no no no yes yes - - - - 0.000 0.000
4 no no no no yes yes - - - - 0.000 0.000
5 no no no no yes yes - - - - 0.000 0.000
5 no no no no yes yes - - - - 0.000 0.000

1.6 Media Interface Channel

Start Position Length


No. Member No. Media Interface Z-Position Y-Position
[mm] [mm]

1.7 Gliders

Position Start Travel


No. Member No. Glider Custom Load
[mm] [mm] [mm]

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 5 / 26
Version: 1.13.1

Solution: Case-14 Date: 28/02/2024

2 Part list

2.1 Members

Quantity Weight Length


Position Item Number Description Cutting type
[-] [kg] [mm]
1 2268520 I.-Channel MT-40D OC 2 12.43 1480.15 N - None
2 2268508 I.-Channel MT-40 OC 1 0.85 415.00 N - None
3 2268508 I.-Channel MT-40 OC 1 1.30 639.68 N - None
4 2268508 I.-Channel MT-40 OC 1 1.31 640.14 N - None

2.2 Base Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
5 2282213 2-hole Baseplate MT-B-O2B OC 2 4.14
11 2346396 Angle brace MT-AB A OC set adjustable 2 0.88

2.3 System Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
9 2271519 Angle connector MT-C-L2 OC 2 0.52
10 2273585 Angle brace MT-AB-LL2 45 OC 2 1.11

2.4 Other

Quantity Weight
Position Item Number Description
[-] [kg]
6 2273256 Hexagon bolt MT-TLB OC 22 0.55
7 2272082 Twist-Lock MT-TL M10 OC 22 0.77
8 2105870 Stud anchor HST3-R M12x115 40/20 8 0.81

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 6 / 26
Version: 1.13.1

Solution: Case-14 Date: 28/02/2024

3 Load Types

3. Loads

Custom loads

Load No. Load Distribution Load Case Load Type Comments


1 Point load LC 7: Design Permanent -
2 Point load LC 13: Seismic (+x) Seismic -
3 Point load LC 14: Seismic (-x) Seismic -
4 Point load LC 2: Pipe Permanent -
5 Point load LC 8: Wind (+x) Variable -
6 Point load LC 9: Wind (-x) Variable -

3.2 Point Loads

Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
1 Design 2 250.00 0.00 0.00 -3.18 0.00 0.00 0.00
3 Seismic (+x) 2 250.00 0.04 0.00 0.00 0.00 0.00 0.00
4 Seismic (-x) 2 250.00 -0.04 -0.00 -0.00 -0.00 -0.00 -0.00
9 Pipe 2 250.00 0.32 0.32 0.00 0.00 0.00 0.00
11 Wind (+x) 2 250.00 0.66 -0.00 -0.00 -0.00 -0.00 -0.00
12 Wind (-x) 2 250.00 -0.66 -0.00 -0.00 -0.00 -0.00 -0.00
13 Self Weight Support 1 0.00 0.00 0.00 -0.02 0.00 0.00 0.00
14 Self Weight Support 1 1361.90 0.00 0.00 -0.00 0.00 0.00 0.00
15 Self Weight Support 2 500.00 0.00 0.00 -0.00 0.00 0.00 0.00
16 Self Weight Support 3 1361.90 0.00 0.00 -0.02 0.00 0.00 0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 7 / 26
Version: 1.13.1

Solution: Case-14 Date: 28/02/2024


Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
17 Self Weight Support 3 880.95 0.00 0.00 -0.01 0.00 0.00 0.00
18 Self Weight Support 4 680.17 0.00 0.00 -0.00 0.00 0.00 0.00
19 Self Weight Support 1 480.95 0.00 0.00 -0.01 0.00 0.00 0.00
20 Self Weight Support 5 680.17 0.00 0.00 -0.00 0.00 0.00 0.00

3.3 Distributed loads

Start End
Fx Fy Fz Mx My Mz
Load No. Load Type Members Position Position
[kN/m] [kN/m] [kN/m] [kNm/m] [kNm/m] [kNm/m]
[mm] [mm]
21 Self Weight Support 1 0.00 1361.90 0.00 0.00 -0.04 0.00 0.00 0.00
22 Self Weight Support 2 0.00 500.00 0.00 0.00 -0.02 0.00 0.00 0.00
23 Self Weight Support 3 0.00 1361.90 0.00 0.00 -0.04 0.00 0.00 0.00
24 Self Weight Support 4 0.00 680.17 0.00 0.00 -0.02 0.00 0.00 0.00
25 Self Weight Support 5 0.00 680.17 0.00 0.00 -0.02 0.00 0.00 0.00

3.4 Area loads

3.4.1 User input

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 8 / 26
Version: 1.13.1

Solution: Case-14 Date: 28/02/2024

4 Load Combinations

Design base EN 1993

Load combination design base EN 1990

4.1 Ultimate Limit State

Design base Load combination and safety factors


ULS - 001a-ULS: SW_inf (Support Only) 1.00 * LC1
ULS - 001b-ULS: SW_sup (Support Only) 1.35 * LC1
ULS - 002a-ULS: SW_inf Support + Media 1.00 * LC1 + 1.00 * LC2
ULS - 002b-ULS: SW_sup Support + Media 1.35 * LC1 + 1.35 * LC2
ULS - 004a-ULS: SW_inf + Design Loads 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC7
ULS - 004b-ULS: SW_sup + Design Loads 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
ULS - 006a-ULS: SW_inf + Wind (+x) 1.00 * LC1 + 1.00 * LC2 + 1.50 * LC8
ULS - 006b-ULS: SW_sup + Wind (+x) 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8
ULS - 007a-ULS: SW_inf + Wind (-x) 1.00 * LC1 + 1.00 * LC2 + 1.50 * LC9
ULS - 007b-ULS: SW_sup + Wind (-x) 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC9
ULS - 015a-ULS: SW_inf + Live + Snow + Wind (+x) 1.00 * LC1 + 1.00 * LC2 + 1.50 * 0.60 * LC8
ULS - 015b-ULS: SW_sup + Live + Snow + Wind (+x) 1.35 * LC1 + 1.35 * LC2 + 1.50 * 0.60 * LC8
ULS - 016a-ULS: SW_inf + Live + Snow + Wind (-x) 1.00 * LC1 + 1.00 * LC2 + 1.50 * 0.60 * LC9
ULS - 016b-ULS: SW_sup + Live + Snow + Wind (-x) 1.35 * LC1 + 1.35 * LC2 + 1.50 * 0.60 * LC9
ULS - 027a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC13
z) + Live + Snow
ULS - 027b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC14
+ Live + Snow
ULS - 029a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC13
z) + Live + Snow
ULS - 030a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC14
+ Live + Snow
ULS - 027a-ULS_Base : SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 027b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 029a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 030a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 031a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC13 + 1.00 * 0.74 * LC7
z) + Design
ULS - 031b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC14 + 1.00 * 0.74 * LC7
+ Design
ULS - 033a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC13 + 1.00 * 0.74 * LC7
z) + Design
ULS - 034a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC14 + 1.00 * 0.74 * LC7
+ Design
ULS - 032a-ULS_Base: SW + Seismic (+x) + Seismic (-y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC13 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 031b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC14 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 033a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC13 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 034a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC14 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 037-ULS: SW_inf + Impact + Live + Snow 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.20 * LC8
ULS - 038-ULS: SW_inf + Impact + Live + Snow 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.20 * LC9

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 9 / 26
Version: 1.13.1

Solution: Case-14 Date: 28/02/2024

4.2 Serviceability Limit State

Load Case Load combination and safety factors


SLS - 001-SLS: SW (Support Only) 1.00 * LC1
SLS - 002-SLS: SW Support + Media Objects 1.00 * LC1 + 1.00 * LC2
SLS - 004-SLS: SW + Design Loads 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7
SLS - 006-SLS: SW + Wind (+x) 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC8
SLS - 007-SLS: SW + Wind (-x) 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC9
SLS - 015-SLS: SW + Live + Snow + Wind (+x) 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC8
SLS - 016-SLS: SW + Live + Snow + Wind (-x) 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC9

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 10 / 26
Version: 1.13.1

Solution: Case-14 Date: 28/02/2024

5 Results

5.1 Calculation summary

5.1.3 Members

Governing load ULS SLS


No Member Status
combination number* [%] [%]
1 MT-40D 006-SLS 53.61 73.01 OK
2 MT-40 004b-ULS 69.21 - OK
3 MT-40D 006-SLS 53.61 73.01 OK
13 MT-40 004b-ULS 8.06 - OK
14 MT-40 004b-ULS 8.06 - OK

5.1.2 Base Connectors

Governing load ULS SLS


No Base connector Status
combination number* [%] [%]
1 MT-B-O2B OC 006b-ULS 96.87 - OK
4 MT-B-O2B OC 006b-ULS 96.87 - OK
6 MT-AB A OC 001b-ULS 10.00 - OK
8 MT-AB A OC 001b-ULS 10.00 - OK

5.1.3 System Connectors

Governing load ULS SLS


No Connector Status
combination number* [%] [%]
2 MT-C-L2 OC 004b-ULS 39.15 - OK
3 MT-C-L2 OC 004b-ULS 37.49 - OK
5 MT-AB-LL2 45 OC 004b-ULS 10.79 - OK
7 MT-AB-LL2 45 OC 004b-ULS 10.79 - OK
*006-SLS: SW + Wind (+x) . Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC8
*004b-ULS: SW_sup + Design Loads . Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
*006b-ULS: SW_sup + Wind (+x) . Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8
*001b-ULS: SW_sup (Support Only) . Respective Combination Equation: 1.35 * LC1

Overall Status: Calculation OK, design criteria met!

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 11 / 26
Version: 1.13.1

Solution: Case-14 Date: 28/02/2024

5.2 Members

5.2.1 Member Properties


5.2.1.1 MT-40D Members: 1, 3
5.2.1.1.1 Section properties
t A Iy Iz It
[mm] [mm²] [mm⁴] [mm⁴] [mm⁴]
2.00 429.52 299600.00 131800.00 520.41

Iω M Wy Wz Wy
[mm⁶] [kg/m] [mm³] [mm³] [mm³]
154300000.00 8.40 -7048.65 -6199.90 -7048.65

5.2.1.1.2 Material properties


E G Fu Fy Fy.cold
Steel grade
[N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²]
Steel S 280 GD 210000.00 80769.00 360.00 280.00 305.00

5.2.1.2 MT-40 Members: 2, 4, 5


5.2.1.2.1 Section properties
t A Iy Iz It
[mm] [mm²] [mm⁴] [mm⁴] [mm⁴]
2.00 285.00 57717.48 65876.44 259.85

Iω M Wy Wz Wy
[mm⁶] [kg/m] [mm³] [mm³] [mm³]
38410000.00 2.04 -2652.65 -3099.95 -2652.65

5.2.1.2.2 Material properties


E G Fu Fy Fy.cold
Steel grade
[N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²]
Steel S 280 GD 210000.00 80769.00 360.00 280.00 305.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 12 / 26
Version: 1.13.1

Solution: Case-14 Date: 28/02/2024

5.2.2 Member Design

5.2.2.1 Overview

5.2.2.2 Stress Analysis

5.2.2.2.1 Table of Results

Load Combination σ τ σeqv σlimit τlimit Utilization


No. Member
number* [N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²] [%]
I.-Channel MT-40D
1 006b-ULS 146.98 24.62 147.02 277.27 160.08 53.02
OC
I.-Channel MT-40
2 004b-ULS -165.32 16.51 165.62 277.27 160.08 59.73
OC
I.-Channel MT-40D
3 006b-ULS 146.98 -24.61 147.02 277.27 160.08 53.02
OC
I.-Channel MT-40
4 006b-ULS 0.00 0.92 5.53 0.00 160.08 2.00
OC
I.-Channel MT-40
5 006b-ULS 0.00 0.92 5.53 0.00 160.08 1.99
OC

*006b-ULS: SW_sup + Wind (+x). Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8

*004b-ULS: SW_sup + Design Loads. Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7

5.2.2.2 Governing Member Loading

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 13 / 26
Version: 1.13.1

Solution: Case-14 Date: 28/02/2024

Beam No. 1

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40D 0.00 006b-ULS 0.64 0.52 0.71 0.00 -0.97 0.06
MT-40D 272.38 006b-ULS 0.65 0.52 0.71 0.00 -0.77 -0.08
MT-40D 480.95(-) 006b-ULS 0.66 0.52 0.71 0.00 -0.63 -0.19
MT-40D 480.95(+) 006b-ULS -0.06 -0.22 0.71 -0.00 -0.63 -0.19
MT-40D 544.76 006b-ULS -0.05 -0.22 0.71 -0.00 -0.58 -0.18
MT-40D 817.14 006b-ULS -0.04 -0.22 0.71 -0.00 -0.39 -0.12
MT-40D 1089.52 006b-ULS -0.03 -0.22 0.71 -0.00 -0.19 -0.06
MT-40D 1361.90 006b-ULS -0.01 -0.22 0.71 -0.00 0.00 0.00

Beam No. 2

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40 0.00 004b-ULS 0.22 0.22 -1.60 0.00 0.00 0.00
MT-40 100.00 004b-ULS 0.22 0.22 -1.59 0.00 -0.16 -0.02
MT-40 200.00 004b-ULS 0.22 0.22 -1.59 0.00 -0.32 -0.04
MT-40 250.00(-) 004b-ULS 0.22 0.22 -1.59 0.00 -0.40 -0.05
MT-40 250.00(+) 004b-ULS -0.22 -0.22 1.59 0.00 -0.40 -0.05
MT-40 300.00 004b-ULS -0.22 -0.22 1.59 0.00 -0.32 -0.04
MT-40 400.00 004b-ULS -0.22 -0.22 1.59 0.00 -0.16 -0.02
MT-40 500.00 004b-ULS -0.22 -0.22 1.60 0.00 0.00 0.00

Beam No. 3

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40D 0.00 006b-ULS -0.01 0.22 0.71 -0.00 -0.00 -0.00
MT-40D 272.38 006b-ULS -0.03 0.22 0.71 -0.00 0.19 -0.06
MT-40D 544.76 006b-ULS -0.04 0.22 0.71 -0.00 0.39 -0.12
MT-40D 817.14 006b-ULS -0.06 0.22 0.71 -0.00 0.58 -0.18
MT-40D 880.95(-) 006b-ULS -0.06 0.22 0.71 -0.00 0.63 -0.19
MT-40D 880.95(+) 006b-ULS 0.66 -0.52 0.71 0.00 0.63 -0.19
MT-40D 1089.52 006b-ULS 0.65 -0.52 0.71 0.00 0.77 -0.08
MT-40D 1361.90 006b-ULS 0.64 -0.52 0.71 0.00 0.97 0.06

Beam No. 4

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40 0.00 004b-ULS -1.05 0.00 -0.01 -0.00 0.00 -0.00
MT-40 136.03 004b-ULS -1.05 0.00 -0.00 -0.00 -0.00 -0.00
MT-40 272.07 004b-ULS -1.05 0.00 -0.00 -0.00 -0.00 -0.00
MT-40 408.10 004b-ULS -1.06 0.00 0.00 -0.00 -0.00 -0.00
MT-40 544.13 004b-ULS -1.06 0.00 0.00 -0.00 -0.00 -0.00
MT-40 680.17 004b-ULS -1.06 0.00 0.01 -0.00 0.00 -0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 14 / 26
Version: 1.13.1

Solution: Case-14 Date: 28/02/2024

Beam No. 5

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40 0.00 004b-ULS -1.05 0.00 -0.01 -0.00 0.00 -0.00
MT-40 136.03 004b-ULS -1.05 0.00 -0.00 -0.00 -0.00 -0.00
MT-40 272.07 004b-ULS -1.05 0.00 -0.00 -0.00 -0.00 -0.00
MT-40 408.10 004b-ULS -1.06 0.00 0.00 -0.00 -0.00 -0.00
MT-40 544.13 004b-ULS -1.06 0.00 0.00 -0.00 -0.00 -0.00
MT-40 680.17 004b-ULS -1.06 0.00 0.01 -0.00 0.00 -0.00

*006b-ULS: SW_sup + Wind (+x). Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8

*004b-ULS: SW_sup + Design Loads. Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7

Normal load

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 15 / 26
Version: 1.13.1

Solution: Case-14 Date: 28/02/2024

Shear load in Y direction

Shear load in Z direction

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 16 / 26
Version: 1.13.1

Solution: Case-14 Date: 28/02/2024

Torsion around X

Moment around Y

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 17 / 26
Version: 1.13.1

Solution: Case-14 Date: 28/02/2024

Moment around Z

5.2.2.3 Shear Limits

Fy,Ed Fy,Rd Fz,Ed Fz,Rd Utilization


No. Type Load Combination number*
[kN] [kN] [kN] [kN] [%]
1 MT-40D 006b-ULS - - 0.71 4.25 16.73
3 MT-40D 006b-ULS - - 0.71 4.25 16.73

5.2.3 Stability Analysis

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 18 / 26
Version: 1.13.1

Solution: Case-14 Date: 28/02/2024

Buckling ratio

Buckling Max. lateral torsional Max. buckling under Max.


Member Length
Length Buckling ratio buckling under bending compression interaction
No. [mm]
[mm] [%] [%] [%]
1 1361.90 1361.90 1.00 53.61 0.00 53.61
2 500.00 500.00 1.00 61.30 0.57 69.21
3 1361.90 1361.90 1.00 53.61 0.00 53.61
4 680.17 1360.33 2.00 0.00 8.06 8.06
5 680.17 1360.33 2.00 0.00 8.06 8.06

5.2.4 Deflection Analysis

Criteria
☑Maximum Allowable Deflection (Beam) L/200
☑Maximum Allowable Deflection (Cantilever)L/150
- Maximum Deflection (Absolute) -
☑No Deflection checks calculated for 1.50mm

Overview

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 19 / 26
Version: 1.13.1

Solution: Case-14 Date: 28/02/2024

Results
Reference
Member Max deflection Utilization
Load Combination number* Governing criteria Length Limit
No. [mm] [%]
[mm]
1 006-SLS Relative(Cantilever) 1361.90 L/150 6.63 73.01
2 016-SLS Relative (Beam) 500.00 L/200 0.00 0.00
3 006-SLS Relative(Cantilever) 1361.90 L/150 6.63 73.01
4 016-SLS Relative (Beam) 680.17 L/200 -0.00 0.00
5 016-SLS Relative (Beam) 680.17 L/200 -0.00 0.00

*006-SLS: SW + Wind (+x). Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC8

*016-SLS: SW + Live + Snow + Wind (-x). Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC9

Deflection 1.00 * LC1

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 20 / 26
Version: 1.13.1

Solution: Case-14 Date: 28/02/2024

Deflection 1.00 * LC1 + 1.00 * LC2

Deflection 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 21 / 26
Version: 1.13.1

Solution: Case-14 Date: 28/02/2024

Deflection 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC8

Deflection 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC9

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 22 / 26
Version: 1.13.1

Solution: Case-14 Date: 28/02/2024

Deflection 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC8

Deflection 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC9

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 23 / 26
Version: 1.13.1

Solution: Case-14 Date: 28/02/2024

5.3 System Connectors

5.3 Connectors

5.3.1 Overview

Connector: MT-C-L2 OC
Fx Fy Fz Mx My Mz
Connector variant: MT-C-L2 OC (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 2
Local Forces: 0.22 0.22 -1.60 0.00 0.00 0.00
Resistance: 3.97 1.56 8.00 0.06
Equation: abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)
Utilization: 39.15 % OK

Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
Combination

Connector: MT-AB-LL2 45 OC
Fx Fy Fz Mx My Mz
Connector variant: MT-AB-LL2 45 OC (E)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 5
Local Forces: -1.05 0.00 0.01 -0.00 0.00 0.00
Resistance: 9.72 0.10 0.10 0.10 0.00 0.00
abs(Fx.ed/Fx.rd);abs(Fy.ed/Fy.rd);abs(Fz.ed/Fz.rd);abs(Mx.ed/Mx.rd);abs(My
Equation:
.ed/My.rd);abs(Mz.ed/Mz.rd)
Utilization: 10.79 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 24 / 26
Version: 1.13.1

Solution: Case-14 Date: 28/02/2024

5.4 Base Connectors

5.4 Bases

5.4.1 Overview

Base connector: MT-B-O2B OC


Fx Fy Fz Mx My Mz
Connector variant: MT-B-O2B OC (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 4
Local Forces: 0.61 -0.52 -0.71 0.00 0.97 -0.06
Resistance: 17.64 6.50 26.92 3.00 1.48 0.36
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 96.87 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8
Combination
Base connector: MT-AB A OC
Fx Fy Fz Mx My Mz
Connector variant: MT-AB A OC (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 6
Local Forces: -1.06 0.00 0.01 0.00 -0.00 -0.00
Resistance: 13.86 0.10 0.10 0.10 0.00 0.00
abs(Fx.ed/Fx.rd);abs(Fy.ed/Fy.rd);abs(Fz.ed/Fz.rd);abs(Mx.ed/Mx.rd);abs(My
Equation:
.ed/My.rd);abs(Mz.ed/Mz.rd)
Utilization: 10.00 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.50 * 0.60 * LC9
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 25 / 26
Version: 1.13.1

Solution: Case-14 Date: 28/02/2024

6 Remarks, Your Cooperation Duties

Any and all information and data contained in the Software concern solely the use of Hilti products and based on the principles, formulas and security
regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly complied with by
the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the relevant Hilti product.
The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole
responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole responsibility for
having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior
to using them for your specific facility. The Software servers only as an aid to interpret norms and permits without any guarantee as to the absence of
errors, the correctness and relevance ot the results or suitability for a specific application.

You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular
backup of programs and, if applicable, carry out the updates of that you are using the current and thus up-to-date version of the Software in each case
by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or
programs, arising from a culpable breach of duty by you.

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 26 / 26
Case-15

Project: SA-13082-SF

Submitted by:

Hilti contact information


Contact name:
Contact e-mail:
Contact phone:
Contact company:

Customer contact information


Customer name:
Customer e-mail:
Customer phone:
Customer company:

Date: 28/02/2024

This submittal is auto-generated based on user-selected inputs.


Therefore, Hilti no representation as to the suitability of these systems for their intended use. 1 / 26
Version: 1.13.1

Solution: Case-15 Date: 28/02/2024

Table of content

1 Geometry and Application


1.1 Supports
1.2 Nodes
1.3 Members
1.4 Connections
1.5 Release Conditions
1.6 Media Interface Channel
1.7 Gliders
2 Part list
2.1 Members
2.2 Base Connectors
2.3 System Connectors
2.4 Other
3 Load Types
3.1 Loading objects
3.2 Point Loads
3.3 Distributed loads
3.4 Area loads
4 Load Combinations
4.1 Ultimate Limit State
4.2 Serviceability Limit State
5 Results
5.1 Calculation summary
5.2 Members
5.3 System Connectors
5.4 Base Connectors
6 Remarks, Your Cooperation Duties

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 2 / 26
Version: 1.13.1

Solution: Case-15 Date: 28/02/2024

1 Geometry and Application

Support Details
Modular Support Spacing [mm] Undefined

Intermediate Supports required?

Pipe Fasteners with Glider and Presetting used? (See


subchapter 'Gliders' in chapter 'Geometry and
Application')

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 3 / 26
Version: 1.13.1

Solution: Case-15 Date: 28/02/2024

1.1 Supports - Concrete

Concrete

Thickness Drilling Depth


Node No. No. Orientation Concrete grade
[mm] [mm]
1 1 Horizontal C20/25 200.00 150
4 2 Horizontal C20/25 200.00 150
6 3 Horizontal C20/25 200.01 150
8 4 Horizontal C20/25 200.00 150

1.2 Nodes

X Y Z
No. No. Connector name Connector variant
[mm] [mm] [mm]
1 1 -190.75 0.00 -500.00 MT-B-GS T OC MT-B-GS T OC (C_MT-70)
2 - -190.75 0.00 1561.90 MT-C-GSP T OC MT-C-GSP T OC (C_D)
3 - 709.25 0.00 1561.90 MT-C-GSP T OC MT-C-GSP T OC (C_D)
4 2 709.25 0.00 -500.00 MT-B-GS T OC MT-B-GS T OC (C_MT-70)
5 - 709.25 0.00 530.95 MT-AB-G T OC MT-AB-G T OC (C_D)
6 3 709.25 1023.42 -492.46 MT-B-GS AB OC MT-B-GS AB OC (C)
7 - -190.75 0.00 530.95 MT-AB-G T OC MT-AB-G T OC (C_D)
8 4 -190.75 1023.41 -492.46 MT-B-GS AB OC MT-B-GS AB OC (C)

1.3 Members

Member Releases Rotation


No. Node start Node end Member Name
Start End [°]
1 1 2 - - MT-70 180.00
2 2 3 - - MT-70 0.00
3 3 4 - - MT-70 180.00
4 5 6 1 2 MT-70 0.00
5 7 8 3 4 MT-70 0.00

1.4 Connections

Cross- Cross- Cross- Cross-


Section/Rotation Section/Rotation Section/Rotation Section/Rotation
Node No. Description Variant
Arm1 Arm2 Arm3 Arm4
[-/°] [-/°] [-/°] [-/°]
MT-B-GS T OC
1 MT-B-GS T OC MT-70/180 - - -
(C_MT-70)
MT-C-GSP T OC
2 MT-C-GSP T OC MT-70/180 MT-70/0 - -
(C_D)
MT-C-GSP T OC
3 MT-C-GSP T OC MT-70/0 MT-70/180 - -
(C_D)
MT-B-GS T OC
4 MT-B-GS T OC MT-70/180 - - -
(C_MT-70)
5 MT-AB-G T OC MT-AB-G T OC (C_D) MT-70/180 MT-70/0 - -
6 MT-B-GS AB OC MT-B-GS AB OC (C) MT-70/0 - - -
7 MT-AB-G T OC MT-AB-G T OC (C_D) MT-70/180 MT-70/0 - -
8 MT-B-GS AB OC MT-B-GS AB OC (C) MT-70/0 - - -

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 4 / 26
Version: 1.13.1

Solution: Case-15 Date: 28/02/2024

1.5 Release Conditions

Spring Constants
Releases
Member Translational Rotational
No. Cu,x Cu,y Cu,z Cφx Cφy Cφz
Ux Uy Uz φx φy φz
[kN/m] [kN/m] [kN/m] [kNm/Rad] [kNm/Rad] [kNm/Rad]
4 no no no no yes yes - - - - 0.000 0.000
4 no no no no yes yes - - - - 0.000 0.000
5 no no no no yes yes - - - - 0.000 0.000
5 no no no no yes yes - - - - 0.000 0.000

1.6 Media Interface Channel

Start Position Length


No. Member No. Media Interface Z-Position Y-Position
[mm] [mm]

1.7 Gliders

Position Start Travel


No. Member No. Glider Custom Load
[mm] [mm] [mm]

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 5 / 26
Version: 1.13.1

Solution: Case-15 Date: 28/02/2024

2 Part list

2.1 Members

Quantity Weight Length


Position Item Number Description Cutting type
[-] [kg] [mm]
1 2268365 I.-Girder MT-70 OC 2 15.86 2028.82 N - None
2 2268365 I.-Girder MT-70 OC 1 4.08 1045.00 N - None
3 2268365 I.-Girder MT-70 OC 1 5.02 1284.76 N - None
4 2268365 I.-Girder MT-70 OC 1 5.02 1284.75 N - None

2.2 Base Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
5 2272100 Baseplate MT-B-GS T OC 2 4.33
10 2332787 Baseplate MT-B-GS AB OC 2 3.30

2.3 System Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
8 2272074 Connector MT-C-GSP T OC plate 4 1.73
9 2272116 Angle brace MT-AB-G T OC adjustable 4 1.39

2.4 Other

Quantity Weight
Position Item Number Description
[-] [kg]
6 2272084 Thread forming bolt MT-TFB OC 44 1.25
7 2105870 Stud anchor HST3-R M12x115 40/20 4 0.41
11 2018429 Anchor rod HIT-Z-R M12x105 4 0.41

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 6 / 26
Version: 1.13.1

Solution: Case-15 Date: 28/02/2024

3 Load Types

3. Loads

Custom loads

Load No. Load Distribution Load Case Load Type Comments


1 Point load LC 7: Design Permanent -
2 Point load LC 7: Design Permanent -
3 Point load LC 13: Seismic (+x) Seismic -
4 Point load LC 14: Seismic (-x) Seismic -
5 Point load LC 13: Seismic (+x) Seismic -
6 Point load LC 14: Seismic (-x) Seismic -
7 Point load LC 2: Pipe Permanent -
8 Point load LC 2: Pipe Permanent -
9 Point load LC 8: Wind (+x) Variable -
10 Point load LC 9: Wind (-x) Variable -

3.2 Point Loads

Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
1 Design 2 250.00 0.00 0.00 -3.18 0.00 0.00 0.00
2 Design 2 650.00 0.00 0.00 -3.18 0.00 0.00 0.00
3 Seismic (+x) 2 250.00 0.04 0.00 0.00 0.00 0.00 0.00
4 Seismic (-x) 2 250.00 -0.04 -0.00 -0.00 -0.00 -0.00 -0.00
5 Seismic (+x) 2 650.00 0.04 0.00 0.00 0.00 0.00 0.00
6 Seismic (-x) 2 650.00 -0.04 -0.00 -0.00 -0.00 -0.00 -0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 7 / 26
Version: 1.13.1

Solution: Case-15 Date: 28/02/2024


Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
9 Pipe 2 250.00 0.32 0.32 0.00 0.00 0.00 0.00
10 Pipe 2 650.00 0.32 0.32 0.00 0.00 0.00 0.00
11 Wind (+x) 2 450.00 0.66 0.00 0.00 0.00 0.00 0.00
12 Wind (-x) 2 450.00 -0.66 -0.00 -0.00 -0.00 -0.00 -0.00
13 Self Weight Support 1 0.00 0.00 0.00 -0.02 0.00 0.00 0.00
14 Self Weight Support 1 2061.90 0.00 0.00 -0.01 0.00 0.00 0.00
15 Self Weight Support 2 900.00 0.00 0.00 -0.01 0.00 0.00 0.00
16 Self Weight Support 3 2061.90 0.00 0.00 -0.02 0.00 0.00 0.00
17 Self Weight Support 3 1030.95 0.00 0.00 -0.01 0.00 0.00 0.00
18 Self Weight Support 4 1447.33 0.00 0.00 -0.02 0.00 0.00 0.00
19 Self Weight Support 1 1030.95 0.00 0.00 -0.01 0.00 0.00 0.00
20 Self Weight Support 5 1447.32 0.00 0.00 -0.02 0.00 0.00 0.00

3.3 Distributed loads

Start End
Fx Fy Fz Mx My Mz
Load No. Load Type Members Position Position
[kN/m] [kN/m] [kN/m] [kNm/m] [kNm/m] [kNm/m]
[mm] [mm]
21 Self Weight Support 1 0.00 2061.90 0.00 0.00 -0.04 0.00 0.00 0.00
22 Self Weight Support 2 0.00 900.00 0.00 0.00 -0.04 0.00 0.00 0.00
23 Self Weight Support 3 0.00 2061.90 0.00 0.00 -0.04 0.00 0.00 0.00
24 Self Weight Support 4 0.00 1447.33 0.00 0.00 -0.04 0.00 0.00 0.00
25 Self Weight Support 5 0.00 1447.32 0.00 0.00 -0.04 0.00 0.00 0.00

3.4 Area loads

3.4.1 User input

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 8 / 26
Version: 1.13.1

Solution: Case-15 Date: 28/02/2024

4 Load Combinations

Design base EN 1993

Load combination design base EN 1990

4.1 Ultimate Limit State

Design base Load combination and safety factors


ULS - 001a-ULS: SW_inf (Support Only) 1.00 * LC1
ULS - 001b-ULS: SW_sup (Support Only) 1.35 * LC1
ULS - 002a-ULS: SW_inf Support + Media 1.00 * LC1 + 1.00 * LC2
ULS - 002b-ULS: SW_sup Support + Media 1.35 * LC1 + 1.35 * LC2
ULS - 004a-ULS: SW_inf + Design Loads 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC7
ULS - 004b-ULS: SW_sup + Design Loads 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
ULS - 006a-ULS: SW_inf + Wind (+x) 1.00 * LC1 + 1.00 * LC2 + 1.50 * LC8
ULS - 006b-ULS: SW_sup + Wind (+x) 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8
ULS - 007a-ULS: SW_inf + Wind (-x) 1.00 * LC1 + 1.00 * LC2 + 1.50 * LC9
ULS - 007b-ULS: SW_sup + Wind (-x) 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC9
ULS - 015a-ULS: SW_inf + Live + Snow + Wind (+x) 1.00 * LC1 + 1.00 * LC2 + 1.50 * 0.60 * LC8
ULS - 015b-ULS: SW_sup + Live + Snow + Wind (+x) 1.35 * LC1 + 1.35 * LC2 + 1.50 * 0.60 * LC8
ULS - 016a-ULS: SW_inf + Live + Snow + Wind (-x) 1.00 * LC1 + 1.00 * LC2 + 1.50 * 0.60 * LC9
ULS - 016b-ULS: SW_sup + Live + Snow + Wind (-x) 1.35 * LC1 + 1.35 * LC2 + 1.50 * 0.60 * LC9
ULS - 027a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC13
z) + Live + Snow
ULS - 027b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC14
+ Live + Snow
ULS - 029a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC13
z) + Live + Snow
ULS - 030a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC14
+ Live + Snow
ULS - 027a-ULS_Base : SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 027b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 029a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 030a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 031a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC13 + 1.00 * 0.74 * LC7
z) + Design
ULS - 031b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC14 + 1.00 * 0.74 * LC7
+ Design
ULS - 033a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC13 + 1.00 * 0.74 * LC7
z) + Design
ULS - 034a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC14 + 1.00 * 0.74 * LC7
+ Design
ULS - 032a-ULS_Base: SW + Seismic (+x) + Seismic (-y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC13 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 031b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC14 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 033a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC13 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 034a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC14 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 037-ULS: SW_inf + Impact + Live + Snow 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.20 * LC8
ULS - 038-ULS: SW_inf + Impact + Live + Snow 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.20 * LC9

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 9 / 26
Version: 1.13.1

Solution: Case-15 Date: 28/02/2024

4.2 Serviceability Limit State

Load Case Load combination and safety factors


SLS - 001-SLS: SW (Support Only) 1.00 * LC1
SLS - 002-SLS: SW Support + Media Objects 1.00 * LC1 + 1.00 * LC2
SLS - 004-SLS: SW + Design Loads 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7
SLS - 006-SLS: SW + Wind (+x) 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC8
SLS - 007-SLS: SW + Wind (-x) 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC9
SLS - 015-SLS: SW + Live + Snow + Wind (+x) 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC8
SLS - 016-SLS: SW + Live + Snow + Wind (-x) 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC9

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 10 / 26
Version: 1.13.1

Solution: Case-15 Date: 28/02/2024

5 Results

5.1 Calculation summary

5.1.3 Members

Governing load ULS SLS


No Member Status
combination number* [%] [%]
1 MT-70 006-SLS 58.25 59.96 OK
2 MT-70 006b-ULS 44.36 - OK
3 MT-70 006-SLS 58.60 59.96 OK
17 MT-70 006-SLS 7.60 38.92 OK
19 MT-70 006-SLS 7.12 38.88 OK

5.1.2 Base Connectors

Governing load ULS SLS


No Base connector Status
combination number* [%] [%]
1 MT-B-GS T OC 006b-ULS 93.45 - OK
4 MT-B-GS T OC 006b-ULS 82.12 - OK
6 MT-B-GS AB OC 006b-ULS 24.88 - OK
8 MT-B-GS AB OC 006b-ULS 22.65 - OK

5.1.3 System Connectors

Governing load ULS SLS


No Connector Status
combination number* [%] [%]
2 MT-C-GSP T OC 006b-ULS 91.06 - OK
3 MT-C-GSP T OC 006b-ULS 97.03 - OK
5 MT-AB-G T OC 006b-ULS 10.62 - OK
7 MT-AB-G T OC 006b-ULS 9.34 - OK
*006-SLS: SW + Wind (+x) . Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC8
*006b-ULS: SW_sup + Wind (+x) . Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8

Overall Status: Calculation OK, design criteria met!

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 11 / 26
Version: 1.13.1

Solution: Case-15 Date: 28/02/2024

5.2 Members

5.2.1 Member Properties


5.2.1.1 MT-70 Members: 1, 2, 3, 4, 5
5.2.1.1.1 Section properties
t A Iy Iz It
[mm] [mm²] [mm⁴] [mm⁴] [mm⁴]
2.75 428.78 158700.00 158700.00 297500.00

Iω M Wy Wz Wy
[mm⁶] [kg/m] [mm³] [mm³] [mm³]
2039000.00 7.82 -6349.48 -6349.48 -6349.48

5.2.1.1.2 Material properties


E G Fu Fy Fy.cold
Steel grade
[N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²]
S350GD 1.0529 210000.00 80769.00 420.00 350.00 350.00

5.2.2 Member Design

5.2.2.1 Overview

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 12 / 26
Version: 1.13.1

Solution: Case-15 Date: 28/02/2024

5.2.2.2 Stress Analysis

5.2.2.2.1 Table of Results

Load Combination σ τ σeqv σlimit τlimit Utilization


No. Member
number* [N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²] [%]
1 I.-Girder MT-70 OC 006b-ULS 185.17 12.97 185.33 318.18 183.70 58.25
2 I.-Girder MT-70 OC 006b-ULS -141.13 0.00 141.14 318.18 0.00 44.36
3 I.-Girder MT-70 OC 006b-ULS -186.35 -11.41 186.45 318.18 183.70 58.60
4 I.-Girder MT-70 OC 006b-ULS -5.44 13.77 24.18 318.18 183.70 7.60
5 I.-Girder MT-70 OC 006b-ULS 0.00 12.95 22.67 0.00 183.70 7.12

*006b-ULS: SW_sup + Wind (+x). Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8

5.2.2.2 Governing Member Loading

Beam No. 1

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-70 0.00 006b-ULS 2.67 0.58 0.92 0.05 -0.98 0.19
MT-70 412.38 006b-ULS 2.69 0.58 0.92 0.05 -0.60 -0.05
MT-70 824.76 006b-ULS 2.71 0.58 0.92 0.05 -0.22 -0.29
MT-70 1030.95(-) 006b-ULS 2.72 0.58 0.92 0.05 -0.03 -0.41
MT-70 1030.95(+) 006b-ULS 1.81 -0.38 0.92 -0.02 -0.10 -0.41
MT-70 1237.14 006b-ULS 1.82 -0.38 0.92 -0.02 0.09 -0.33
MT-70 1649.52 006b-ULS 1.84 -0.38 0.92 -0.02 0.47 -0.17
MT-70 2061.90 006b-ULS 1.86 -0.38 0.92 -0.02 0.85 -0.02

Beam No. 2

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-70 0.00 006b-ULS 0.92 0.38 1.87 -0.02 -0.85 -0.02
MT-70 180.00 006b-ULS 0.92 0.38 1.88 -0.02 -0.51 -0.08
MT-70 250.00(-) 006b-ULS 0.92 0.38 1.89 -0.02 -0.38 -0.11
MT-70 250.00(+) 006b-ULS 0.49 -0.06 1.89 -0.02 -0.38 -0.11
MT-70 360.00 006b-ULS 0.49 -0.06 1.89 -0.02 -0.17 -0.10
MT-70 450.00(-) 006b-ULS 0.49 -0.06 1.90 -0.02 -0.00 -0.10
MT-70 450.00(+) 006b-ULS -0.50 -0.06 1.90 -0.02 -0.00 -0.10
MT-70 540.00 006b-ULS -0.50 -0.06 1.90 -0.02 0.17 -0.09
MT-70 650.00(-) 006b-ULS -0.50 -0.06 1.91 -0.02 0.38 -0.09
MT-70 650.00(+) 006b-ULS -0.93 -0.49 1.91 -0.02 0.38 -0.09
MT-70 720.00 006b-ULS -0.93 -0.49 1.91 -0.02 0.51 -0.05
MT-70 900.00 006b-ULS -0.93 -0.49 1.92 -0.02 0.86 0.03

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 13 / 26
Version: 1.13.1

Solution: Case-15 Date: 28/02/2024

Beam No. 3

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-70 0.00 006b-ULS -1.93 0.49 0.93 -0.03 -0.86 0.02
MT-70 412.38 006b-ULS -1.96 0.49 0.93 -0.03 -0.47 -0.18
MT-70 824.76 006b-ULS -1.98 0.49 0.93 -0.03 -0.09 -0.38
MT-70 1030.95(-) 006b-ULS -1.99 0.49 0.93 -0.03 0.10 -0.48
MT-70 1030.95(+) 006b-ULS -0.86 -0.70 0.93 0.04 0.03 -0.48
MT-70 1237.14 006b-ULS -0.86 -0.70 0.93 0.04 0.22 -0.34
MT-70 1649.52 006b-ULS -0.89 -0.70 0.93 0.04 0.60 -0.05
MT-70 2061.90 006b-ULS -0.91 -0.70 0.93 0.04 0.99 0.23

Beam No. 4

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-70 0.00 006b-ULS -1.65 0.00 -0.03 -0.10 0.00 -0.00
MT-70 289.47 006b-ULS -1.66 0.00 -0.02 -0.10 -0.01 -0.00
MT-70 578.93 006b-ULS -1.67 0.00 -0.01 -0.10 -0.01 -0.00
MT-70 868.40 006b-ULS -1.68 0.00 0.01 -0.10 -0.01 -0.00
MT-70 1157.86 006b-ULS -1.69 0.00 0.02 -0.10 -0.01 -0.00
MT-70 1447.33 006b-ULS -1.70 0.00 0.03 -0.10 -0.00 -0.00

Beam No. 5

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-70 0.00 006b-ULS -1.33 0.00 -0.03 -0.10 0.00 -0.00
MT-70 289.46 006b-ULS -1.34 0.00 -0.02 -0.10 -0.01 -0.00
MT-70 578.93 006b-ULS -1.35 0.00 -0.01 -0.10 -0.01 -0.00
MT-70 868.39 006b-ULS -1.36 0.00 0.01 -0.10 -0.01 -0.00
MT-70 1157.86 006b-ULS -1.37 0.00 0.02 -0.10 -0.01 -0.00
MT-70 1447.32 006b-ULS -1.39 0.00 0.03 -0.10 -0.00 -0.00

*006b-ULS: SW_sup + Wind (+x). Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 14 / 26
Version: 1.13.1

Solution: Case-15 Date: 28/02/2024

Normal load

Shear load in Y direction

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 15 / 26
Version: 1.13.1

Solution: Case-15 Date: 28/02/2024

Shear load in Z direction

Torsion around X

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 16 / 26
Version: 1.13.1

Solution: Case-15 Date: 28/02/2024

Moment around Y

Moment around Z

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 17 / 26
Version: 1.13.1

Solution: Case-15 Date: 28/02/2024

5.2.3 Stability Analysis

Buckling ratio

Buckling Max. lateral torsional Max. buckling under Max.


Member Length
Length Buckling ratio buckling under bending compression interaction
No. [mm]
[mm] [%] [%] [%]
1 2061.90 2061.90 1.00 0.00 5.54 5.54
2 900.00 900.00 1.00 0.00 0.94 0.94
3 2061.90 2061.90 1.00 0.00 8.88 8.88
4 1447.33 2894.65 2.00 0.00 6.20 6.20
5 1447.32 2894.64 2.00 0.00 5.66 5.66

5.2.4 Deflection Analysis

Criteria
☑Maximum Allowable Deflection (Beam) L/150
☑Maximum Allowable Deflection (Cantilever)L/75
- Maximum Deflection (Absolute) -
☑No Deflection checks calculated for 1.50mm

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 18 / 26
Version: 1.13.1

Solution: Case-15 Date: 28/02/2024

Overview

Results
Reference
Member Max deflection Utilization
Load Combination number* Governing criteria Length Limit
No. [mm] [%]
[mm]
1 006-SLS Relative(Cantilever) 2061.90 L/75 16.49 59.96
2 016-SLS Relative (Beam) 900.00 L/150 0.00 0.00
3 006-SLS Relative(Cantilever) 2061.90 L/75 16.49 59.96
4 006-SLS Relative(Cantilever) 1447.33 L/75 7.51 38.92
5 006-SLS Relative(Cantilever) 1447.32 L/75 7.50 38.88

*006-SLS: SW + Wind (+x). Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC8

*016-SLS: SW + Live + Snow + Wind (-x). Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC9

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 19 / 26
Version: 1.13.1

Solution: Case-15 Date: 28/02/2024

Deflection 1.00 * LC1

Deflection 1.00 * LC1 + 1.00 * LC2

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 20 / 26
Version: 1.13.1

Solution: Case-15 Date: 28/02/2024

Deflection 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7

Deflection 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC8

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 21 / 26
Version: 1.13.1

Solution: Case-15 Date: 28/02/2024

Deflection 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC9

Deflection 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC8

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 22 / 26
Version: 1.13.1

Solution: Case-15 Date: 28/02/2024

Deflection 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC9

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 23 / 26
Version: 1.13.1

Solution: Case-15 Date: 28/02/2024

5.3 System Connectors

5.3 Connectors

5.3.1 Overview

Connector: MT-C-GSP T OC
Fx Fy Fz Mx My Mz
Connector variant: MT-C-GSP T OC (C_D)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 3
Local Forces: -1.93 -0.49 0.93 -0.03 0.86 0.02
Resistance: 69.99 8.88 10.65 0.40 1.25 0.57
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 97.03 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8
Combination
Connector: MT-AB-G T OC
Fx Fy Fz Mx My Mz
Connector variant: MT-AB-G T OC (C_D)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 5
Local Forces: -1.64 -0.03 0.00 -0.10 -0.00 0.00
Resistance: 32.99 6.44 1.83
Equation: (( Fx.ed^2 + Fy.ed^2 )^0.5)/Fx.rd + Fz.ed / Fz.rd+Mx.ed/Mx.rd
Utilization: 10.62 % OK

Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 24 / 26
Version: 1.13.1

Solution: Case-15 Date: 28/02/2024

5.4 Base Connectors

5.4 Bases

5.4.1 Overview

Base connector: MT-B-GS T OC


Fx Fy Fz Mx My Mz
Connector variant: MT-B-GS T OC (C_MT-70)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 1
Local Forces: 2.64 -0.58 -0.92 0.05 0.98 -0.19
Resistance: 33.44 18.22 25.91 0.84 1.69 1.35
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 93.45 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8
Combination
Base connector: MT-B-GS AB OC
Fx Fy Fz Mx My Mz
Connector variant: MT-B-GS AB OC (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 6
Local Forces: -1.72 0.04 -0.00 -0.10 -0.00 -0.00
Resistance: 27.10 27.10 4.45 0.56
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 24.88 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 25 / 26
Version: 1.13.1

Solution: Case-15 Date: 28/02/2024

6 Remarks, Your Cooperation Duties

Any and all information and data contained in the Software concern solely the use of Hilti products and based on the principles, formulas and security
regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly complied with by
the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the relevant Hilti product.
The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole
responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole responsibility for
having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior
to using them for your specific facility. The Software servers only as an aid to interpret norms and permits without any guarantee as to the absence of
errors, the correctness and relevance ot the results or suitability for a specific application.

You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular
backup of programs and, if applicable, carry out the updates of that you are using the current and thus up-to-date version of the Software in each case
by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or
programs, arising from a culpable breach of duty by you.

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 26 / 26
Case-16

Project: SA-13082-SF

Submitted by:

Hilti contact information


Contact name:
Contact e-mail:
Contact phone:
Contact company:

Customer contact information


Customer name:
Customer e-mail:
Customer phone:
Customer company:

Date: 28/02/2024

This submittal is auto-generated based on user-selected inputs.


Therefore, Hilti no representation as to the suitability of these systems for their intended use. 1 / 25
Version: 1.13.1

Solution: Case-16 Date: 28/02/2024

Table of content

1 Geometry and Application


1.1 Supports
1.2 Nodes
1.3 Members
1.4 Connections
1.5 Release Conditions
1.6 Media Interface Channel
1.7 Gliders
2 Part list
2.1 Members
2.2 Base Connectors
2.3 System Connectors
2.4 Other
3 Load Types
3.1 Loading objects
3.2 Point Loads
3.3 Distributed loads
3.4 Area loads
4 Load Combinations
4.1 Ultimate Limit State
4.2 Serviceability Limit State
5 Results
5.1 Calculation summary
5.2 Members
5.3 System Connectors
5.4 Base Connectors
6 Remarks, Your Cooperation Duties

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 2 / 25
Version: 1.13.1

Solution: Case-16 Date: 28/02/2024

1 Geometry and Application

Support Details
Modular Support Spacing [mm] Undefined

Intermediate Supports required?

Pipe Fasteners with Glider and Presetting used? (See


subchapter 'Gliders' in chapter 'Geometry and
Application')

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 3 / 25
Version: 1.13.1

Solution: Case-16 Date: 28/02/2024

1.1 Supports - Concrete

Concrete

Thickness Drilling Depth


Node No. No. Orientation Concrete grade
[mm] [mm]
1 1 Horizontal C20/25 200.00 150
4 2 Horizontal C20/25 200.00 150

1.2 Nodes

X Y Z
No. No. Connector name Connector variant
[mm] [mm] [mm]
1 1 -215.00 0.00 -500.00 MT-B-O2 MT-B-O2 (C)
2 - -215.00 0.00 -222.25 MT-C-LL1 MT-C-LL1 (C)
3 - 733.50 0.00 -222.25 MT-C-LL1 MT-C-LL1 (C)
4 2 733.50 0.00 -500.00 MT-B-O2 MT-B-O2 (C)

1.3 Members

Member Releases Rotation


No. Node start Node end Member Name
Start End [°]
1 1 2 - 1 MT-40 180.00
2 2 3 1 2 MT-40 0.00
3 3 4 2 - MT-40 180.00

1.4 Connections

Cross- Cross- Cross- Cross-


Section/Rotation Section/Rotation Section/Rotation Section/Rotation
Node No. Description Variant
Arm1 Arm2 Arm3 Arm4
[-/°] [-/°] [-/°] [-/°]
1 MT-B-O2 MT-B-O2 (C) MT-40/180 - - -
2 MT-C-LL1 MT-C-LL1 (C) MT-40/180 MT-40/0 - -
3 MT-C-LL1 MT-C-LL1 (C) MT-40/0 MT-40/180 - -
4 MT-B-O2 MT-B-O2 (C) MT-40/180 - - -

1.5 Release Conditions

Spring Constants
Releases
Member Translational Rotational
No. Cu,x Cu,y Cu,z Cφx Cφy Cφz
Ux Uy Uz φx φy φz
[kN/m] [kN/m] [kN/m] [kNm/Rad] [kNm/Rad] [kNm/Rad]
2 no no no no yes yes - - - - 0.001 0.001
2 no no no no yes yes - - - - 0.001 0.001

1.6 Media Interface Channel

Start Position Length


No. Member No. Media Interface Z-Position Y-Position
[mm] [mm]
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 4 / 25
Version: 1.13.1

Solution: Case-16 Date: 28/02/2024

1.7 Gliders

Position Start Travel


No. Member No. Glider Custom Load
[mm] [mm] [mm]

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 5 / 25
Version: 1.13.1

Solution: Case-16 Date: 28/02/2024

2 Part list

2.1 Members

Quantity Weight Length


Position Item Number Description Cutting type
[-] [kg] [mm]
1 2268506 I.-Channel MT-40 2 1.44 351.90 N - None
2 2268506 I.-Channel MT-40 1 1.85 906.00 N - None

2.2 Base Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
3 2272094 2-hole Baseplate MT-B-O2 2 2.05

2.3 System Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
7 2272047 Angle connector MT-C-LL1 2 0.67

2.4 Other

Quantity Weight
Position Item Number Description
[-] [kg]
4 2273254 Hexagon bolt MT-TLB 8 0.20
5 2272080 Twist-Lock MT-TL M10 8 0.28
6 2105719 Stud anchor HST3 M12x115 40/20 4 0.40

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 6 / 25
Version: 1.13.1

Solution: Case-16 Date: 28/02/2024

3 Load Types

3. Loads

Custom loads

Load No. Load Distribution Load Case Load Type Comments


1 Point load LC 7: Design Permanent -
2 Point load LC 7: Design Permanent -
3 Point load LC 8: Wind (+x) Variable -
4 Point load LC 9: Wind (-x) Variable -
5 Point load LC 13: Seismic (+x) Seismic -
6 Point load LC 14: Seismic (-x) Seismic -
7 Point load LC 14: Seismic (-x) Seismic -
8 Point load LC 13: Seismic (+x) Seismic -
9 Point load LC 2: Pipe Permanent -
10 Point load LC 2: Pipe Permanent -
11 Point load LC 2: Pipe Permanent -
12 Point load LC 2: Pipe Permanent -

3.2 Point Loads

Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
1 Design 2 275.00 0.00 0.00 -1.79 0.00 0.00 0.00
2 Design 2 673.50 0.00 0.00 -1.79 0.00 0.00 0.00
3 Wind (+x) 2 474.25 0.53 -0.00 -0.00 -0.00 -0.00 -0.00
4 Wind (-x) 2 474.25 -0.53 -0.00 -0.00 -0.00 -0.00 -0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 7 / 25
Version: 1.13.1

Solution: Case-16 Date: 28/02/2024


Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
5 Seismic (+x) 2 275.00 0.02 -0.00 -0.00 -0.00 -0.00 -0.00
6 Seismic (-x) 2 275.00 -0.02 -0.00 -0.00 -0.00 -0.00 -0.00
7 Seismic (-x) 2 673.50 0.02 -0.00 -0.00 -0.00 -0.00 -0.00
8 Seismic (+x) 2 673.50 -0.02 -0.00 -0.00 -0.00 -0.00 -0.00
9 Pipe 2 673.50 0.00 0.18 0.00 0.00 0.00 0.00
10 Pipe 2 275.00 0.00 0.18 0.00 0.00 0.00 0.00
11 Pipe 2 275.00 0.18 0.00 0.00 0.00 0.00 0.00
12 Pipe 2 673.50 0.18 0.00 0.00 0.00 0.00 0.00
13 Self Weight Support 1 0.00 0.00 0.00 -0.01 0.00 0.00 0.00
14 Self Weight Support 1 277.75 0.00 0.00 -0.00 0.00 0.00 0.00
15 Self Weight Support 2 948.50 0.00 0.00 -0.00 0.00 0.00 0.00
16 Self Weight Support 3 277.75 0.00 0.00 -0.01 0.00 0.00 0.00

3.3 Distributed loads

Start End
Fx Fy Fz Mx My Mz
Load No. Load Type Members Position Position
[kN/m] [kN/m] [kN/m] [kNm/m] [kNm/m] [kNm/m]
[mm] [mm]
17 Self Weight Support 1 0.00 277.75 0.00 0.00 -0.02 0.00 0.00 0.00
18 Self Weight Support 2 0.00 948.50 0.00 0.00 -0.02 0.00 0.00 0.00
19 Self Weight Support 3 0.00 277.75 0.00 0.00 -0.02 0.00 0.00 0.00

3.4 Area loads

3.4.1 User input

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 8 / 25
Version: 1.13.1

Solution: Case-16 Date: 28/02/2024

4 Load Combinations

Design base EN 1993

Load combination design base EN 1990

4.1 Ultimate Limit State

Design base Load combination and safety factors


ULS - 001a-ULS: SW_inf (Support Only) 1.00 * LC1
ULS - 001b-ULS: SW_sup (Support Only) 1.35 * LC1
ULS - 002a-ULS: SW_inf Support + Media 1.00 * LC1 + 1.00 * LC2
ULS - 002b-ULS: SW_sup Support + Media 1.35 * LC1 + 1.35 * LC2
ULS - 004a-ULS: SW_inf + Design Loads 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC7
ULS - 004b-ULS: SW_sup + Design Loads 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
ULS - 006a-ULS: SW_inf + Wind (+x) 1.00 * LC1 + 1.00 * LC2 + 1.50 * LC8
ULS - 006b-ULS: SW_sup + Wind (+x) 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8
ULS - 007a-ULS: SW_inf + Wind (-x) 1.00 * LC1 + 1.00 * LC2 + 1.50 * LC9
ULS - 007b-ULS: SW_sup + Wind (-x) 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC9
ULS - 015a-ULS: SW_inf + Live + Snow + Wind (+x) 1.00 * LC1 + 1.00 * LC2 + 1.50 * 0.60 * LC8
ULS - 015b-ULS: SW_sup + Live + Snow + Wind (+x) 1.35 * LC1 + 1.35 * LC2 + 1.50 * 0.60 * LC8
ULS - 016a-ULS: SW_inf + Live + Snow + Wind (-x) 1.00 * LC1 + 1.00 * LC2 + 1.50 * 0.60 * LC9
ULS - 016b-ULS: SW_sup + Live + Snow + Wind (-x) 1.35 * LC1 + 1.35 * LC2 + 1.50 * 0.60 * LC9
ULS - 027a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC13
z) + Live + Snow
ULS - 027b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC14
+ Live + Snow
ULS - 029a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC13
z) + Live + Snow
ULS - 030a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC14
+ Live + Snow
ULS - 027a-ULS_Base : SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 027b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 029a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 030a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 031a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC13 + 1.00 * 0.74 * LC7
z) + Design
ULS - 031b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 1.00 * LC14 + 1.00 * 0.74 * LC7
+ Design
ULS - 033a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC13 + 1.00 * 0.74 * LC7
z) + Design
ULS - 034a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC2 + 0.30 * LC14 + 1.00 * 0.74 * LC7
+ Design
ULS - 032a-ULS_Base: SW + Seismic (+x) + Seismic (-y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC13 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 031b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 1.00 * qa * LC14 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 033a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC13 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 034a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * LC2 + 0.30 * qa * LC14 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 037-ULS: SW_inf + Impact + Live + Snow 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.20 * LC8
ULS - 038-ULS: SW_inf + Impact + Live + Snow 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.20 * LC9

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 9 / 25
Version: 1.13.1

Solution: Case-16 Date: 28/02/2024

4.2 Serviceability Limit State

Load Case Load combination and safety factors


SLS - 001-SLS: SW (Support Only) 1.00 * LC1
SLS - 002-SLS: SW Support + Media Objects 1.00 * LC1 + 1.00 * LC2
SLS - 004-SLS: SW + Design Loads 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7
SLS - 006-SLS: SW + Wind (+x) 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC8
SLS - 007-SLS: SW + Wind (-x) 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC9
SLS - 015-SLS: SW + Live + Snow + Wind (+x) 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC8
SLS - 016-SLS: SW + Live + Snow + Wind (-x) 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC9

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 10 / 25
Version: 1.13.1

Solution: Case-16 Date: 28/02/2024

5 Results

5.1 Calculation summary

5.1.3 Members

Governing load ULS SLS


No Member Status
combination number* [%] [%]
1 MT-40 006b-ULS 40.59 - OK
2 MT-40 004-SLS 84.70 61.05 OK
3 MT-40 006b-ULS 40.59 - OK

5.1.2 Base Connectors

Governing load ULS SLS


No Base connector Status
combination number* [%] [%]
1 MT-B-O2 006b-ULS 79.86 - OK
4 MT-B-O2 006b-ULS 79.90 - OK

5.1.3 System Connectors

Governing load ULS SLS


No Connector Status
combination number* [%] [%]
2 MT-C-LL1 004b-ULS 44.89 - OK
3 MT-C-LL1 004b-ULS 44.93 - OK
*006b-ULS: SW_sup + Wind (+x) . Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8
*004-SLS: SW + Design Loads . Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7
*004b-ULS: SW_sup + Design Loads . Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7

Overall Status: Calculation OK, design criteria met!

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 11 / 25
Version: 1.13.1

Solution: Case-16 Date: 28/02/2024

5.2 Members

5.2.1 Member Properties


5.2.1.1 MT-40 Members: 1, 2, 3
5.2.1.1.1 Section properties
t A Iy Iz It
[mm] [mm²] [mm⁴] [mm⁴] [mm⁴]
2.00 285.00 57717.48 65876.44 259.85

Iω M Wy Wz Wy
[mm⁶] [kg/m] [mm³] [mm³] [mm³]
38410000.00 4.08 -2652.65 -3099.95 -2652.65

5.2.1.1.2 Material properties


E G Fu Fy Fy.cold
Steel grade
[N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²]
Steel S 280 GD 210000.00 80769.00 360.00 280.00 305.00

5.2.2 Member Design

5.2.2.1 Overview

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 12 / 25
Version: 1.13.1

Solution: Case-16 Date: 28/02/2024

5.2.2.2 Stress Analysis

5.2.2.2.1 Table of Results

Load Combination σ τ σeqv σlimit τlimit Utilization


No. Member
number* [N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²] [%]
1 I.-Channel MT-40 006b-ULS -84.86 15.00 84.98 277.27 160.08 30.65
2 I.-Channel MT-40 004b-ULS -205.16 18.60 205.46 277.27 160.08 74.10
3 I.-Channel MT-40 006b-ULS 84.62 -14.99 84.74 277.27 160.08 30.56

*006b-ULS: SW_sup + Wind (+x). Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8

*004b-ULS: SW_sup + Design Loads. Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7

5.2.2.2 Governing Member Loading

Beam No. 1

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40 0.00 006b-ULS -0.03 -0.24 0.64 0.00 -0.18 -0.07
MT-40 55.55 006b-ULS -0.02 -0.24 0.64 0.00 -0.14 -0.05
MT-40 111.10 006b-ULS -0.02 -0.24 0.64 0.00 -0.11 -0.04
MT-40 166.65 006b-ULS -0.02 -0.24 0.64 0.00 -0.07 -0.03
MT-40 222.20 006b-ULS -0.02 -0.24 0.64 0.00 -0.04 -0.01
MT-40 277.75 006b-ULS -0.02 -0.24 0.64 0.00 0.00 0.00

Beam No. 2

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40 0.00 004b-ULS 0.24 0.24 -1.80 0.00 0.00 0.00
MT-40 189.70 004b-ULS 0.24 0.24 -1.80 0.00 -0.34 -0.05
MT-40 275.00(-) 004b-ULS 0.24 0.24 -1.80 0.00 -0.49 -0.07
MT-40 275.00(+) 004b-ULS -0.00 0.00 -0.01 0.00 -0.49 -0.07
MT-40 379.40 004b-ULS -0.00 0.00 -0.00 0.00 -0.50 -0.07
MT-40 569.10 004b-ULS -0.00 0.00 0.00 0.00 -0.50 -0.07
MT-40 673.50(-) 004b-ULS -0.00 0.00 0.01 0.00 -0.49 -0.07
MT-40 673.50(+) 004b-ULS -0.24 -0.24 1.80 0.00 -0.49 -0.07
MT-40 758.80 004b-ULS -0.24 -0.24 1.80 0.00 -0.34 -0.05
MT-40 948.50 004b-ULS -0.24 -0.24 1.80 0.00 0.00 0.00

Beam No. 3

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-40 0.00 006b-ULS -0.02 0.24 0.64 -0.00 -0.00 -0.00
MT-40 55.55 006b-ULS -0.02 0.24 0.64 -0.00 0.04 -0.01
MT-40 111.10 006b-ULS -0.02 0.24 0.64 -0.00 0.07 -0.03
MT-40 166.65 006b-ULS -0.02 0.24 0.64 -0.00 0.11 -0.04
MT-40 222.20 006b-ULS -0.02 0.24 0.64 -0.00 0.14 -0.05
MT-40 277.75 006b-ULS -0.03 0.24 0.64 -0.00 0.18 -0.07

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 13 / 25
Version: 1.13.1

Solution: Case-16 Date: 28/02/2024


*006b-ULS: SW_sup + Wind (+x). Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8

*004b-ULS: SW_sup + Design Loads. Respective Combination Equation: 1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7

Normal load

Shear load in Y direction

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 14 / 25
Version: 1.13.1

Solution: Case-16 Date: 28/02/2024

Shear load in Z direction

Torsion around X

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 15 / 25
Version: 1.13.1

Solution: Case-16 Date: 28/02/2024

Moment around Y

Moment around Z

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 16 / 25
Version: 1.13.1

Solution: Case-16 Date: 28/02/2024

5.2.3 Stability Analysis

Buckling ratio

Buckling Max. lateral torsional Max. buckling under Max.


Member Length
Length Buckling ratio buckling under bending compression interaction
No. [mm]
[mm] [%] [%] [%]
1 277.75 555.50 2.00 32.10 0.07 40.59
2 948.50 948.50 1.00 77.82 1.18 84.70
3 277.75 555.50 2.00 32.10 0.07 40.59

5.2.4 Deflection Analysis

Criteria
☑Maximum Allowable Deflection (Beam) L/200
☑Maximum Allowable Deflection (Cantilever)L/150
- Maximum Deflection (Absolute) -
☑No Deflection checks calculated for 1.50mm

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 17 / 25
Version: 1.13.1

Solution: Case-16 Date: 28/02/2024

Overview

Results
Reference
Member Max deflection Utilization
Load Combination number* Governing criteria Length Limit
No. [mm] [%]
[mm]
1 016-SLS Relative (Beam) 277.75 L/200 0.01 0.00
2 004-SLS Relative (Beam) 948.50 L/200 -2.90 61.05
3 016-SLS Relative (Beam) 277.75 L/200 -0.00 0.00

*016-SLS: SW + Live + Snow + Wind (-x). Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC9

*004-SLS: SW + Design Loads. Respective Combination Equation: 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 18 / 25
Version: 1.13.1

Solution: Case-16 Date: 28/02/2024

Deflection 1.00 * LC1

Deflection 1.00 * LC1 + 1.00 * LC2

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 19 / 25
Version: 1.13.1

Solution: Case-16 Date: 28/02/2024

Deflection 1.00 * LC1 + 1.00 * LC2 + 0.70 * LC7

Deflection 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC8

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 20 / 25
Version: 1.13.1

Solution: Case-16 Date: 28/02/2024

Deflection 1.00 * LC1 + 1.00 * LC2 + 1.00 * LC9

Deflection 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC8

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 21 / 25
Version: 1.13.1

Solution: Case-16 Date: 28/02/2024

Deflection 1.00 * LC1 + 1.00 * LC2 + 1.00 * 0.60 * LC9

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 22 / 25
Version: 1.13.1

Solution: Case-16 Date: 28/02/2024

5.3 System Connectors

5.3 Connectors

5.3.1 Overview

Connector: MT-C-LL1
Fx Fy Fz Mx My Mz
Connector variant: MT-C-LL1 (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 3
Local Forces: -0.24 -0.24 -1.80 0.00 0.00 -0.00
Resistance: 8.20 1.24 8.06 0.03 0.19 0.03
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 44.93 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.00 * LC7
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 23 / 25
Version: 1.13.1

Solution: Case-16 Date: 28/02/2024

5.4 Base Connectors

5.4 Bases

5.4.1 Overview

Base connector: MT-B-O2


Fx Fy Fz Mx My Mz
Connector variant: MT-B-O2 (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 4
Local Forces: -0.04 0.24 -0.64 -0.00 0.18 0.07
Resistance: 14.00 2.43 7.34 0.06 0.55 0.23
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 79.90 % OK
Governing Load
1.35 * LC1 + 1.35 * LC2 + 1.50 * LC8
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 24 / 25
Version: 1.13.1

Solution: Case-16 Date: 28/02/2024

6 Remarks, Your Cooperation Duties

Any and all information and data contained in the Software concern solely the use of Hilti products and based on the principles, formulas and security
regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly complied with by
the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the relevant Hilti product.
The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole
responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole responsibility for
having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior
to using them for your specific facility. The Software servers only as an aid to interpret norms and permits without any guarantee as to the absence of
errors, the correctness and relevance ot the results or suitability for a specific application.

You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular
backup of programs and, if applicable, carry out the updates of that you are using the current and thus up-to-date version of the Software in each case
by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or
programs, arising from a culpable breach of duty by you.

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 25 / 25
Fixpoint Design A

Project: SA-13082-SF

Submitted by:

Hilti contact information


Contact name:
Contact e-mail:
Contact phone:
Contact company:

Customer contact information


Customer name:
Customer e-mail:
Customer phone:
Customer company:

Date: 28/02/2024

This submittal is auto-generated based on user-selected inputs.


Therefore, Hilti no representation as to the suitability of these systems for their intended use. 1 / 21
Version: 1.13.1

Solution: Fixpoint Design A Date: 28/02/2024

Table of content

1 Geometry and Application


1.1 Supports
1.2 Nodes
1.3 Members
1.4 Connections
1.5 Release Conditions
1.6 Media Interface Channel
1.7 Gliders
2 Part list
2.1 Members
2.2 Base Connectors
2.3 System Connectors
2.4 Other
3 Load Types
3.1 Loading objects
3.2 Point Loads
3.3 Distributed loads
3.4 Area loads
4 Load Combinations
4.1 Ultimate Limit State
4.2 Serviceability Limit State
5 Results
5.1 Calculation summary
5.2 Members
5.3 System Connectors
5.4 Base Connectors
6 Remarks, Your Cooperation Duties

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 2 / 21
Version: 1.13.1

Solution: Fixpoint Design A Date: 28/02/2024

1 Geometry and Application

Support Details
Modular Support Spacing [mm] Undefined

Intermediate Supports required?

Pipe Fasteners with Glider and Presetting used? (See


subchapter 'Gliders' in chapter 'Geometry and
Application')

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 3 / 21
Version: 1.13.1

Solution: Fixpoint Design A Date: 28/02/2024

1.1 Supports - Concrete

Concrete

Thickness Drilling Depth


Node No. No. Orientation Concrete grade
[mm] [mm]
1 1 Horizontal C20/25 200.00 150
4 2 Horizontal C20/25 200.00 150

1.2 Nodes

X Y Z
No. No. Connector name Connector variant
[mm] [mm] [mm]
1 1 -15.75 0.00 -500.00 MT-B-GL O4 OC MT-B-GL O4 OC (C)
2 - -15.75 0.00 -122.61 MT-C-GL OC MT-C-GL OC (C_D)
3 - 634.25 0.00 -122.61 MT-C-GL OC MT-C-GL OC (C_D)
4 2 634.25 0.00 -500.00 MT-B-GL O4 OC MT-B-GL O4 OC (C)

1.3 Members

Member Releases Rotation


No. Node start Node end Member Name
Start End [°]
1 1 2 - - MT-90 180.00
2 2 3 - - MT-90 0.00
3 3 4 - - MT-90 180.00

1.4 Connections

Cross- Cross- Cross- Cross-


Section/Rotation Section/Rotation Section/Rotation Section/Rotation
Node No. Description Variant
Arm1 Arm2 Arm3 Arm4
[-/°] [-/°] [-/°] [-/°]
1 MT-B-GL O4 OC MT-B-GL O4 OC (C) MT-90/180 - - -
2 MT-C-GL OC MT-C-GL OC (C_D) MT-90/180 MT-90/0 - -
3 MT-C-GL OC MT-C-GL OC (C_D) MT-90/0 MT-90/180 - -
4 MT-B-GL O4 OC MT-B-GL O4 OC (C) MT-90/180 - - -

1.5 Release Conditions

Spring Constants
Releases
Member Translational Rotational
No. Cu,x Cu,y Cu,z Cφx Cφy Cφz
Ux Uy Uz φx φy φz
[kN/m] [kN/m] [kN/m] [kNm/Rad] [kNm/Rad] [kNm/Rad]

1.6 Media Interface Channel

Start Position Length


No. Member No. Media Interface Z-Position Y-Position
[mm] [mm]

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 4 / 21
Version: 1.13.1

Solution: Fixpoint Design A Date: 28/02/2024

1.7 Gliders

Position Start Travel


No. Member No. Glider Custom Load
[mm] [mm] [mm]

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 5 / 21
Version: 1.13.1

Solution: Fixpoint Design A Date: 28/02/2024

2 Part list

2.1 Members

Quantity Weight Length


Position Item Number Description Cutting type
[-] [kg] [mm]
1 2268369 I.-Girder MT-90 OC 2 5.66 315.39 N - None
2 2268369 I.-Girder MT-90 OC 1 9.42 1050.00 N - None

2.2 Base Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
3 2272103 4-hole Baseplate MT-B-GL O4 OC 2 29.82

2.3 System Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
6 2272066 Angle connector MT-C-GL OC 4 4.64

2.4 Other

Quantity Weight
Position Item Number Description
[-] [kg]
4 2272084 Thread forming bolt MT-TFB OC 80 2.28
5 2105876 Stud anchor HST3-R M16x135 35/15 8 1.74

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 6 / 21
Version: 1.13.1

Solution: Fixpoint Design A Date: 28/02/2024

3 Load Types

3. Loads

Custom loads

Load No. Load Distribution Load Case Load Type Comments


1 Point load LC 7: Design Permanent -
2 Point load LC 7: Design Permanent -
3 Point load LC 13: Seismic (+x) Seismic -
4 Point load LC 14: Seismic (-x) Seismic -
5 Point load LC 14: Seismic (-x) Seismic -
6 Point load LC 13: Seismic (+x) Seismic -

3.2 Point Loads

Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
1 Design 2 75.00 0.00 19.17 -1.79 0.00 0.00 0.00
2 Design 2 575.00 0.00 19.17 -1.79 0.00 0.00 0.00
5 Seismic (+x) 2 75.00 0.02 -0.00 -0.00 -0.00 -0.00 -0.00
6 Seismic (-x) 2 75.00 -0.02 -0.00 -0.00 -0.00 -0.00 -0.00
7 Seismic (-x) 2 575.00 0.02 -0.00 -0.00 -0.00 -0.00 -0.00
8 Seismic (+x) 2 575.00 -0.02 -0.00 -0.00 -0.00 -0.00 -0.00
9 Self Weight Support 1 0.00 0.00 0.00 -0.15 0.00 0.00 0.00
10 Self Weight Support 1 377.39 0.00 0.00 -0.02 0.00 0.00 0.00
11 Self Weight Support 2 650.00 0.00 0.00 -0.02 0.00 0.00 0.00
12 Self Weight Support 3 377.39 0.00 0.00 -0.15 0.00 0.00 0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 7 / 21
Version: 1.13.1

Solution: Fixpoint Design A Date: 28/02/2024

3.3 Distributed loads

Start End
Fx Fy Fz Mx My Mz
Load No. Load Type Members Position Position
[kN/m] [kN/m] [kN/m] [kNm/m] [kNm/m] [kNm/m]
[mm] [mm]
13 Self Weight Support 1 0.00 377.39 0.00 0.00 -0.09 0.00 0.00 0.00
14 Self Weight Support 2 0.00 650.00 0.00 0.00 -0.09 0.00 0.00 0.00
15 Self Weight Support 3 0.00 377.39 0.00 0.00 -0.09 0.00 0.00 0.00

3.4 Area loads

3.4.1 User input

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 8 / 21
Version: 1.13.1

Solution: Fixpoint Design A Date: 28/02/2024

4 Load Combinations

Design base EN 1993

Load combination design base EN 1990

4.1 Ultimate Limit State

Design base Load combination and safety factors


ULS - 001a-ULS: SW_inf (Support Only) 1.00 * LC1
ULS - 001b-ULS: SW_sup (Support Only) 1.35 * LC1
ULS - 004a-ULS: SW_inf + Design Loads 1.00 * LC1 + 1.00 * LC7
ULS - 004b-ULS: SW_sup + Design Loads 1.35 * LC1 + 1.00 * LC7
ULS - 027a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC13
z) + Live + Snow
ULS - 027b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC14
+ Live + Snow
ULS - 029a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 0.30 * LC13
z) + Live + Snow
ULS - 030a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 0.30 * LC14
+ Live + Snow
ULS - 027a-ULS_Base : SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 027b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 029a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 0.30 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 030a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 0.30 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 031a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC13 + 1.00 * 0.74 * LC7
z) + Design
ULS - 031b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC14 + 1.00 * 0.74 * LC7
+ Design
ULS - 033a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 0.30 * LC13 + 1.00 * 0.74 * LC7
z) + Design
ULS - 034a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 0.30 * LC14 + 1.00 * 0.74 * LC7
+ Design
ULS - 032a-ULS_Base: SW + Seismic (+x) + Seismic (-y) +
1.00 * LC1 + 1.00 * qa * LC13 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 031b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * qa * LC14 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 033a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 0.30 * qa * LC13 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 034a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 0.30 * qa * LC14 + 1.00 * 0.74 * LC7
Seismic (-z) + Design

4.2 Serviceability Limit State

Load Case Load combination and safety factors


SLS - 001-SLS: SW (Support Only) 1.00 * LC1
SLS - 004-SLS: SW + Design Loads 1.00 * LC1 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 9 / 21
Version: 1.13.1

Solution: Fixpoint Design A Date: 28/02/2024

5 Results

5.1 Calculation summary

5.1.3 Members

Governing load ULS SLS


No Member Status
combination number* [%] [%]
1 MT-90 004b-ULS 77.61 - OK
2 MT-90 004b-ULS 31.10 - OK
3 MT-90 004b-ULS 77.61 - OK

5.1.2 Base Connectors

Governing load ULS SLS


No Base connector Status
combination number* [%] [%]
1 MT-B-GL O4 OC 004b-ULS 88.49 - OK
4 MT-B-GL O4 OC 004b-ULS 88.49 - OK

5.1.3 System Connectors

Governing load ULS SLS


No Connector Status
combination number* [%] [%]
2 MT-C-GL OC 004b-ULS 76.58 - OK
3 MT-C-GL OC 004b-ULS 76.59 - OK
*004b-ULS: SW_sup + Design Loads . Respective Combination Equation: 1.35 * LC1 + 1.00 * LC7

Overall Status: Calculation OK, design criteria met!

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 10 / 21
Version: 1.13.1

Solution: Fixpoint Design A Date: 28/02/2024

5.2 Members

5.2.1 Member Properties


5.2.1.1 MT-90 Members: 1, 2, 3
5.2.1.1.1 Section properties
t A Iy Iz It
[mm] [mm²] [mm⁴] [mm⁴] [mm⁴]
3.00 976.08 1508000.00 1508000.00 2047000.00

Iω M Wy Wz Wy
[mm⁶] [kg/m] [mm³] [mm³] [mm³]
15470000.00 17.95 -30169.60 -30169.60 -30169.60

5.2.1.1.2 Material properties


E G Fu Fy Fy.cold
Steel grade
[N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²]
S350GD 1.0529 210000.00 80769.00 420.00 350.00 350.00

5.2.2 Member Design

5.2.2.1 Overview

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 11 / 21
Version: 1.13.1

Solution: Fixpoint Design A Date: 28/02/2024

5.2.2.2 Stress Analysis

5.2.2.2.1 Table of Results

Load Combination σ τ σeqv σlimit τlimit Utilization


No. Member
number* [N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²] [%]
1 I.-Girder MT-90 OC 004b-ULS -242.27 66.46 246.93 318.18 183.70 77.61
2 I.-Girder MT-90 OC 004b-ULS -36.50 56.41 98.97 318.18 183.70 31.10
3 I.-Girder MT-90 OC 004b-ULS -242.27 -66.46 246.93 318.18 183.70 77.61

*004b-ULS: SW_sup + Design Loads. Respective Combination Equation: 1.35 * LC1 + 1.00 * LC7

5.2.2.2 Governing Member Loading

Beam No. 1

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-90 0.00 004b-ULS -1.91 -19.17 -0.27 0.39 0.02 -7.23
MT-90 75.48 004b-ULS -1.90 -19.17 -0.27 0.39 -0.00 -5.79
MT-90 150.96 004b-ULS -1.89 -19.17 -0.27 0.39 -0.02 -4.34
MT-90 226.43 004b-ULS -1.88 -19.17 -0.27 0.39 -0.04 -2.89
MT-90 301.91 004b-ULS -1.87 -19.17 -0.27 0.39 -0.06 -1.45
MT-90 377.39 004b-ULS -1.86 -19.17 -0.27 0.39 -0.08 0.00

Beam No. 2

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-90 0.00 004b-ULS -0.27 19.17 -1.83 0.00 0.08 0.39
MT-90 75.00(-) 004b-ULS -0.27 19.17 -1.82 0.00 -0.05 -1.04
MT-90 75.00(+) 004b-ULS -0.27 -0.00 -0.03 0.00 -0.05 -1.04
MT-90 130.00 004b-ULS -0.27 -0.00 -0.02 0.00 -0.05 -1.04
MT-90 260.00 004b-ULS -0.27 -0.00 -0.01 0.00 -0.06 -1.04
MT-90 390.00 004b-ULS -0.27 -0.00 0.01 0.00 -0.06 -1.04
MT-90 520.00 004b-ULS -0.27 -0.00 0.02 0.00 -0.05 -1.04
MT-90 575.00(-) 004b-ULS -0.27 -0.00 0.03 0.00 -0.05 -1.04
MT-90 575.00(+) 004b-ULS -0.27 -19.17 1.82 0.00 -0.05 -1.04
MT-90 650.00 004b-ULS -0.27 -19.17 1.83 0.00 0.08 0.39

Beam No. 3

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-90 0.00 004b-ULS -1.86 19.17 0.27 -0.39 -0.08 -0.00
MT-90 75.48 004b-ULS -1.87 19.17 0.27 -0.39 -0.06 -1.45
MT-90 150.96 004b-ULS -1.88 19.17 0.27 -0.39 -0.04 -2.89
MT-90 226.43 004b-ULS -1.89 19.17 0.27 -0.39 -0.02 -4.34
MT-90 301.91 004b-ULS -1.90 19.17 0.27 -0.39 -0.00 -5.79
MT-90 377.39 004b-ULS -1.91 19.17 0.27 -0.39 0.02 -7.23

*004b-ULS: SW_sup + Design Loads. Respective Combination Equation: 1.35 * LC1 + 1.00 * LC7
Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 12 / 21
Version: 1.13.1

Solution: Fixpoint Design A Date: 28/02/2024

Normal load

Shear load in Y direction

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 13 / 21
Version: 1.13.1

Solution: Fixpoint Design A Date: 28/02/2024

Shear load in Z direction

Torsion around X

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 14 / 21
Version: 1.13.1

Solution: Fixpoint Design A Date: 28/02/2024

Moment around Y

Moment around Z

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 15 / 21
Version: 1.13.1

Solution: Fixpoint Design A Date: 28/02/2024

5.2.3 Stability Analysis

Buckling ratio

Buckling Max. lateral torsional Max. buckling under Max.


Member Length
Length Buckling ratio buckling under bending compression interaction
No. [mm]
[mm] [%] [%] [%]
1 377.39 377.39 1.00 0.00 0.65 0.65
2 650.00 650.00 1.00 0.00 0.10 0.10
3 377.39 377.39 1.00 0.00 0.65 0.65

5.2.4 Deflection Analysis

Criteria
☑Maximum Allowable Deflection (Beam) L/200
☑Maximum Allowable Deflection (Cantilever)L/150
- Maximum Deflection (Absolute) -
☑No Deflection checks calculated for 1.50mm

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 16 / 21
Version: 1.13.1

Solution: Fixpoint Design A Date: 28/02/2024

Overview

Results
Reference
Member Max deflection Utilization
Load Combination number* Governing criteria Length Limit
No. [mm] [%]
[mm]
1 004-SLS Relative (Beam) 377.39 L/200 0.00 0.00
2 004-SLS Relative (Beam) 650.00 L/200 -0.00 0.00
3 004-SLS Relative (Beam) 377.39 L/200 -0.00 0.00

*004-SLS: SW + Design Loads. Respective Combination Equation: 1.00 * LC1 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 17 / 21
Version: 1.13.1

Solution: Fixpoint Design A Date: 28/02/2024

Deflection 1.00 * LC1

Deflection 1.00 * LC1 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 18 / 21
Version: 1.13.1

Solution: Fixpoint Design A Date: 28/02/2024

5.3 System Connectors

5.3 Connectors

5.3.1 Overview

Connector: MT-C-GL OC
Fx Fy Fz Mx My Mz
Connector variant: MT-C-GL OC (C_D)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 3
Local Forces: -1.86 19.17 0.27 -0.39 -0.08 0.00
Resistance: 94.46 35.33 37.95 2.38 2.72 1.99
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 76.59 % OK
Governing Load
1.35 * LC1 + 1.00 * LC7
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 19 / 21
Version: 1.13.1

Solution: Fixpoint Design A Date: 28/02/2024

5.4 Base Connectors

5.4 Bases

5.4.1 Overview

Base connector: MT-B-GL O4 OC


Fx Fy Fz Mx My Mz
Connector variant: MT-B-GL O4 OC (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 1
Local Forces: -2.11 19.17 0.27 0.39 -0.02 7.23
Resistance: 327.93 82.84 82.84 8.66 12.12 12.12
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 88.49 % OK
Governing Load
1.35 * LC1 + 1.00 * LC7
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 20 / 21
Version: 1.13.1

Solution: Fixpoint Design A Date: 28/02/2024

6 Remarks, Your Cooperation Duties

Any and all information and data contained in the Software concern solely the use of Hilti products and based on the principles, formulas and security
regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly complied with by
the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the relevant Hilti product.
The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole
responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole responsibility for
having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior
to using them for your specific facility. The Software servers only as an aid to interpret norms and permits without any guarantee as to the absence of
errors, the correctness and relevance ot the results or suitability for a specific application.

You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular
backup of programs and, if applicable, carry out the updates of that you are using the current and thus up-to-date version of the Software in each case
by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or
programs, arising from a culpable breach of duty by you.

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 21 / 21
Fixpoint Design E

Project: SA-13082-SF

Submitted by:

Hilti contact information


Contact name:
Contact e-mail:
Contact phone:
Contact company:

Customer contact information


Customer name:
Customer e-mail:
Customer phone:
Customer company:

Date: 28/02/2024

This submittal is auto-generated based on user-selected inputs.


Therefore, Hilti no representation as to the suitability of these systems for their intended use. 1 / 23
Version: 1.13.1

Solution: Fixpoint Design E Date: 28/02/2024

Table of content

1 Geometry and Application


1.1 Supports
1.2 Nodes
1.3 Members
1.4 Connections
1.5 Release Conditions
1.6 Media Interface Channel
1.7 Gliders
2 Part list
2.1 Members
2.2 Base Connectors
2.3 System Connectors
2.4 Other
3 Load Types
3.1 Loading objects
3.2 Point Loads
3.3 Distributed loads
3.4 Area loads
4 Load Combinations
4.1 Ultimate Limit State
4.2 Serviceability Limit State
5 Results
5.1 Calculation summary
5.2 Members
5.3 System Connectors
5.4 Base Connectors
6 Remarks, Your Cooperation Duties

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 2 / 23
Version: 1.13.1

Solution: Fixpoint Design E Date: 28/02/2024

1 Geometry and Application

Support Details
Modular Support Spacing [mm] Undefined

Intermediate Supports required?

Pipe Fasteners with Glider and Presetting used? (See


subchapter 'Gliders' in chapter 'Geometry and
Application')

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 3 / 23
Version: 1.13.1

Solution: Fixpoint Design E Date: 28/02/2024

1.1 Supports - Concrete

Concrete

Thickness Drilling Depth


Node No. No. Orientation Concrete grade
[mm] [mm]
1 1 Horizontal C20/25 200.00 150
4 2 Horizontal C20/25 200.00 150
5 3 Horizontal C20/25 200.00 150
8 4 Horizontal C20/25 200.00 150

1.2 Nodes

X Y Z
No. No. Connector name Connector variant
[mm] [mm] [mm]
1 1 -15.75 0.00 -500.00 MT-B-GXL O4 OC MT-B-GXL O4 OC (C)
2 - -15.75 0.00 610.00 MT-C-GL OC MT-C-GL OC (C_D)
3 - 634.25 0.00 610.00 MT-C-GL OC MT-C-GL OC (C_D)
4 2 634.25 0.00 -500.00 MT-B-GXL O4 OC MT-B-GXL O4 OC (C)
5 3 -15.75 500.00 -500.00 MT-B-GXL O4 OC MT-B-GXL O4 OC (C)
8 4 634.25 500.00 -500.00 MT-B-GXL O4 OC MT-B-GXL O4 OC (C)
9 - 634.25 0.00 128.58 MT-C-GL OC MT-C-GL OC (C)
10 - 634.25 500.00 128.58 MT-C-GL OC MT-C-GL OC (C)
11 - -15.75 0.00 128.58 MT-C-GL OC MT-C-GL OC (C)
12 - -15.75 500.00 128.58 MT-C-GL OC MT-C-GL OC (C)

1.3 Members

Member Releases Rotation


No. Node start Node end Member Name
Start End [°]
1 1 2 - - MT-100 90.00
2 2 3 - - MT-100 90.00
3 3 4 - - MT-100 90.00
4 5 6 - - MT-100 90.00
5 7 8 - - MT-100 90.00
6 9 10 1 2 MT-100 0.00
7 11 12 3 4 MT-100 0.00

1.4 Connections

Cross- Cross- Cross- Cross-


Section/Rotation Section/Rotation Section/Rotation Section/Rotation
Node No. Description Variant
Arm1 Arm2 Arm3 Arm4
[-/°] [-/°] [-/°] [-/°]
1 MT-B-GXL O4 OC MT-B-GXL O4 OC (C) MT-100/90 - - -
2 MT-C-GL OC MT-C-GL OC (C_D) MT-100/90 MT-100/90 - -
3 MT-C-GL OC MT-C-GL OC (C_D) MT-100/90 MT-100/90 - -
4 MT-B-GXL O4 OC MT-B-GXL O4 OC (C) MT-100/90 - - -
5 MT-B-GXL O4 OC MT-B-GXL O4 OC (C) MT-100/90 - - -
8 MT-B-GXL O4 OC MT-B-GXL O4 OC (C) MT-100/90 - - -
9 MT-C-GL OC MT-C-GL OC (C) MT-100/90 MT-100/0 - -
10 MT-C-GL OC MT-C-GL OC (C) MT-100/90 MT-100/0 - -
11 MT-C-GL OC MT-C-GL OC (C) MT-100/90 MT-100/0 - -
12 MT-C-GL OC MT-C-GL OC (C) MT-100/90 MT-100/0 - -

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 4 / 23
Version: 1.13.1

Solution: Fixpoint Design E Date: 28/02/2024

1.5 Release Conditions

Spring Constants
Releases
Member Translational Rotational
No. Cu,x Cu,y Cu,z Cφx Cφy Cφz
Ux Uy Uz φx φy φz
[kN/m] [kN/m] [kN/m] [kNm/Rad] [kNm/Rad] [kNm/Rad]
6 no no no no yes yes - - - - 0.001 0.001
6 no no no no yes yes - - - - 0.001 0.001
7 no no no no yes yes - - - - 0.001 0.001
7 no no no no yes yes - - - - 0.001 0.001

1.6 Media Interface Channel

Start Position Length


No. Member No. Media Interface Z-Position Y-Position
[mm] [mm]

1.7 Gliders

Position Start Travel


No. Member No. Glider Custom Load
[mm] [mm] [mm]

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 5 / 23
Version: 1.13.1

Solution: Fixpoint Design E Date: 28/02/2024

2 Part list

2.1 Members

Quantity Weight Length


Position Item Number Description Cutting type
[-] [kg] [mm]
1 2268491 I.-Girder MT-100 OC 2 31.64 1048.00 N - None
2 2268491 I.-Girder MT-100 OC 1 15.85 1050.00 N - None
3 2268491 I.-Girder MT-100 OC 2 25.52 845.15 N - None
4 2268491 I.-Girder MT-100 OC 2 10.57 350.00 N - None

2.2 Base Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
5 2272104 4-hole Baseplate MT-B-GXL O4 OC 4 68.13

2.3 System Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
8 2272066 Angle connector MT-C-GL OC 8 9.29

2.4 Other

Quantity Weight
Position Item Number Description
[-] [kg]
6 2272084 Thread forming bolt MT-TFB OC 184 5.24
7 2105876 Stud anchor HST3-R M16x135 35/15 16 3.49

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 6 / 23
Version: 1.13.1

Solution: Fixpoint Design E Date: 28/02/2024

3 Load Types

3. Loads

Custom loads

Load No. Load Distribution Load Case Load Type Comments


1 Point load LC 7: Design Permanent -
2 Point load LC 7: Design Permanent -
3 Point load LC 13: Seismic (+x) Seismic -
4 Point load LC 14: Seismic (-x) Seismic -
5 Point load LC 14: Seismic (-x) Seismic -
6 Point load LC 13: Seismic (+x) Seismic -

3.2 Point Loads

Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
1 Design 2 75.00 0.00 18.47 -1.79 0.00 0.00 0.00
2 Design 2 575.00 0.00 18.47 -1.79 0.00 0.00 0.00
5 Seismic (+x) 2 75.00 0.02 -0.00 -0.00 -0.00 -0.00 -0.00
6 Seismic (-x) 2 75.00 -0.02 -0.00 -0.00 -0.00 -0.00 -0.00
7 Seismic (-x) 2 575.00 0.02 -0.00 -0.00 -0.00 -0.00 -0.00
8 Seismic (+x) 2 575.00 -0.02 -0.00 -0.00 -0.00 -0.00 -0.00
9 Self Weight Support 1 0.00 0.00 0.00 -0.17 0.00 0.00 0.00
10 Self Weight Support 1 1110.00 0.00 0.00 -0.02 0.00 0.00 0.00
11 Self Weight Support 2 650.00 0.00 0.00 -0.02 0.00 0.00 0.00
12 Self Weight Support 3 1110.00 0.00 0.00 -0.17 0.00 0.00 0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 7 / 23
Version: 1.13.1

Solution: Fixpoint Design E Date: 28/02/2024


Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
13 Self Weight Support 4 0.00 0.00 0.00 -0.17 0.00 0.00 0.00
14 Self Weight Support 5 857.15 0.00 0.00 -0.17 0.00 0.00 0.00
15 Self Weight Support 3 481.42 0.00 0.00 -0.01 0.00 0.00 0.00
16 Self Weight Support 5 228.57 0.00 0.00 -0.01 0.00 0.00 0.00
17 Self Weight Support 1 628.58 0.00 0.00 -0.01 0.00 0.00 0.00
18 Self Weight Support 4 628.58 0.00 0.00 -0.01 0.00 0.00 0.00

3.3 Distributed loads

Start End
Fx Fy Fz Mx My Mz
Load No. Load Type Members Position Position
[kN/m] [kN/m] [kN/m] [kNm/m] [kNm/m] [kNm/m]
[mm] [mm]
19 Self Weight Support 1 0.00 1110.00 0.00 0.00 -0.15 0.00 0.00 0.00
20 Self Weight Support 2 0.00 650.00 0.00 0.00 -0.15 0.00 0.00 0.00
21 Self Weight Support 3 0.00 1110.00 0.00 0.00 -0.15 0.00 0.00 0.00
22 Self Weight Support 4 0.00 857.15 0.00 0.00 -0.15 0.00 0.00 0.00
23 Self Weight Support 5 0.00 857.15 0.00 0.00 -0.15 0.00 0.00 0.00
24 Self Weight Support 6 0.00 500.00 0.00 0.00 -0.15 0.00 0.00 0.00
25 Self Weight Support 7 0.00 500.00 0.00 0.00 -0.15 0.00 0.00 0.00

3.4 Area loads

3.4.1 User input

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 8 / 23
Version: 1.13.1

Solution: Fixpoint Design E Date: 28/02/2024

4 Load Combinations

Design base EN 1993

Load combination design base EN 1990

4.1 Ultimate Limit State

Design base Load combination and safety factors


ULS - 001a-ULS: SW_inf (Support Only) 1.00 * LC1
ULS - 001b-ULS: SW_sup (Support Only) 1.35 * LC1
ULS - 004a-ULS: SW_inf + Design Loads 1.00 * LC1 + 1.00 * LC7
ULS - 004b-ULS: SW_sup + Design Loads 1.35 * LC1 + 1.00 * LC7
ULS - 027a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC13
z) + Live + Snow
ULS - 027b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC14
+ Live + Snow
ULS - 029a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 0.30 * LC13
z) + Live + Snow
ULS - 030a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 0.30 * LC14
+ Live + Snow
ULS - 027a-ULS_Base : SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 027b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 029a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 0.30 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 030a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 0.30 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 031a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC13 + 1.00 * 0.74 * LC7
z) + Design
ULS - 031b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC14 + 1.00 * 0.74 * LC7
+ Design
ULS - 033a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 0.30 * LC13 + 1.00 * 0.74 * LC7
z) + Design
ULS - 034a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 0.30 * LC14 + 1.00 * 0.74 * LC7
+ Design
ULS - 032a-ULS_Base: SW + Seismic (+x) + Seismic (-y) +
1.00 * LC1 + 1.00 * qa * LC13 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 031b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * qa * LC14 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 033a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 0.30 * qa * LC13 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 034a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 0.30 * qa * LC14 + 1.00 * 0.74 * LC7
Seismic (-z) + Design

4.2 Serviceability Limit State

Load Case Load combination and safety factors


SLS - 001-SLS: SW (Support Only) 1.00 * LC1
SLS - 004-SLS: SW + Design Loads 1.00 * LC1 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 9 / 23
Version: 1.13.1

Solution: Fixpoint Design E Date: 28/02/2024

5 Results

5.1 Calculation summary

5.1.3 Members

Governing load ULS SLS


No Member Status
combination number* [%] [%]
1 MT-100 004-SLS 43.93 48.52 OK
2 MT-100 004b-ULS 21.43 - OK
3 MT-100 004-SLS 43.93 48.52 OK
11 MT-100 004-SLS 56.78 30.60 OK
12 MT-100 004-SLS 56.78 30.60 OK
14 MT-100 004a-ULS 4.03 - OK
15 MT-100 004a-ULS 4.03 - OK

5.1.2 Base Connectors

Governing load ULS SLS


No Base connector Status
combination number* [%] [%]
1 MT-B-GXL O4 OC 004b-ULS 31.59 - OK
4 MT-B-GXL O4 OC 004b-ULS 31.59 - OK
5 MT-B-GXL O4 OC 004b-ULS 53.20 - OK
8 MT-B-GXL O4 OC 004b-ULS 53.20 - OK

5.1.3 System Connectors

Governing load ULS SLS


No Connector Status
combination number* [%] [%]
2 MT-C-GL OC 004b-ULS 61.94 - OK
3 MT-C-GL OC 004b-ULS 61.94 - OK
9 MT-C-GL OC 004b-ULS 46.04 - OK
10 MT-C-GL OC 004b-ULS 46.04 - OK
11 MT-C-GL OC 004b-ULS 46.04 - OK
12 MT-C-GL OC 004b-ULS 46.04 - OK
*004-SLS: SW + Design Loads . Respective Combination Equation: 1.00 * LC1 + 0.70 * LC7
*004b-ULS: SW_sup + Design Loads . Respective Combination Equation: 1.35 * LC1 + 1.00 * LC7
*004a-ULS: SW_inf + Design Loads . Respective Combination Equation: 1.00 * LC1 + 1.00 * LC7

Overall Status: Calculation OK, design criteria met!

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 10 / 23
Version: 1.13.1

Solution: Fixpoint Design E Date: 28/02/2024

5.2 Members

5.2.1 Member Properties


5.2.1.1 MT-100 Members: 1, 2, 3, 4, 5, 6, 7
5.2.1.1.1 Section properties
t A Iy Iz It
[mm] [mm²] [mm⁴] [mm⁴] [mm⁴]
4.00 1555.34 4874000.00 2610000.00 4754000.00

Iω M Wy Wz Wy
[mm⁶] [kg/m] [mm³] [mm³] [mm³]
303000000.00 30.19 -65000.00 -52200.00 -65000.00

5.2.1.1.2 Material properties


E G Fu Fy Fy.cold
Steel grade
[N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²]
S350GD 1.0529 210000.00 80769.00 420.00 350.00 350.00

5.2.2 Member Design

5.2.2.1 Overview

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 11 / 23
Version: 1.13.1

Solution: Fixpoint Design E Date: 28/02/2024

5.2.2.2 Stress Analysis

5.2.2.2.1 Table of Results

Load Combination σ τ σeqv σlimit τlimit Utilization


No. Member
number* [N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²] [%]
1 I.-Girder MT-100 OC 004b-ULS -138.51 0.00 139.77 318.18 0.00 43.93
2 I.-Girder MT-100 OC 004b-ULS -20.84 39.34 68.19 318.18 183.70 21.43
3 I.-Girder MT-100 OC 004b-ULS -138.51 0.00 139.77 318.18 0.00 43.93
4 I.-Girder MT-100 OC 004b-ULS -179.91 0.00 180.68 318.18 0.00 56.78
5 I.-Girder MT-100 OC 004b-ULS -179.91 0.00 180.68 318.18 0.00 56.78
6 I.-Girder MT-100 OC 004b-ULS -12.04 0.13 12.04 318.18 183.70 3.79
7 I.-Girder MT-100 OC 004b-ULS -12.04 0.13 12.04 318.18 183.70 3.79

*004b-ULS: SW_sup + Design Loads. Respective Combination Equation: 1.35 * LC1 + 1.00 * LC7

5.2.2.2 Governing Member Loading

Beam No. 1

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-100 0.00 004b-ULS -2.18 0.09 0.11 0.12 8.82 0.03
MT-100 222.00 004b-ULS -2.14 0.09 0.11 0.12 8.85 0.01
MT-100 444.00 004b-ULS -2.09 0.09 0.11 0.12 8.87 -0.01
MT-100 628.58(-) 004b-ULS -2.05 0.09 0.11 0.12 8.89 -0.02
MT-100 628.58(+) 004b-ULS -1.98 0.09 -18.47 0.12 8.89 -0.02
MT-100 666.00 004b-ULS -1.98 0.09 -18.47 0.12 8.20 -0.03
MT-100 888.00 004b-ULS -1.93 0.09 -18.47 0.12 4.10 -0.05
MT-100 1110.00 004b-ULS -1.89 0.09 -18.47 0.12 -0.00 -0.06

Beam No. 2

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-100 0.00 004b-ULS -0.09 -1.86 -18.47 0.00 0.12 -0.06
MT-100 75.00(-) 004b-ULS -0.09 -1.84 -18.47 0.00 -1.26 0.07
MT-100 75.00(+) 004b-ULS -0.09 -0.05 0.00 0.00 -1.26 0.07
MT-100 130.00 004b-ULS -0.09 -0.04 0.00 0.00 -1.26 0.08
MT-100 260.00 004b-ULS -0.09 -0.01 0.00 0.00 -1.26 0.08
MT-100 390.00 004b-ULS -0.09 0.01 0.00 0.00 -1.26 0.08
MT-100 520.00 004b-ULS -0.09 0.04 0.00 0.00 -1.26 0.08
MT-100 575.00(-) 004b-ULS -0.09 0.05 0.00 0.00 -1.26 0.07
MT-100 575.00(+) 004b-ULS -0.09 1.84 18.47 0.00 -1.26 0.07
MT-100 650.00 004b-ULS -0.09 1.86 18.47 0.00 0.12 -0.06

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 12 / 23
Version: 1.13.1

Solution: Fixpoint Design E Date: 28/02/2024

Beam No. 3

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-100 0.00 004b-ULS -1.89 -0.09 18.47 -0.12 0.00 -0.06
MT-100 222.00 004b-ULS -1.93 -0.09 18.47 -0.12 4.10 -0.05
MT-100 444.00 004b-ULS -1.98 -0.09 18.47 -0.12 8.20 -0.03
MT-100 481.42(-) 004b-ULS -1.99 -0.09 18.47 -0.12 8.89 -0.02
MT-100 481.42(+) 004b-ULS -2.06 -0.09 -0.11 -0.12 8.89 -0.02
MT-100 666.00 004b-ULS -2.09 -0.09 -0.11 -0.12 8.87 -0.01
MT-100 888.00 004b-ULS -2.14 -0.09 -0.11 -0.12 8.85 0.01
MT-100 1110.00 004b-ULS -2.18 -0.09 -0.11 -0.12 8.82 0.03

Beam No. 4

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-100 0.00 004b-ULS -0.24 0.00 -18.58 0.00 11.68 0.00
MT-100 171.43 004b-ULS -0.21 0.00 -18.58 0.00 8.49 0.00
MT-100 342.86 004b-ULS -0.17 0.00 -18.58 0.00 5.31 0.00
MT-100 514.29 004b-ULS -0.14 0.00 -18.58 0.00 2.12 0.00
MT-100 628.58(-) 004b-ULS -0.11 0.00 -18.58 0.00 -0.00 0.00
MT-100 628.58(+) 004b-ULS -0.05 0.00 0.00 0.00 0.00 -0.00
MT-100 685.72 004b-ULS -0.03 0.00 0.00 0.00 0.00 -0.00
MT-100 857.15 004b-ULS 0.00 0.00 0.00 0.00 0.00 -0.00

Beam No. 5

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-100 0.00 004b-ULS 0.00 0.00 0.00 0.00 0.00 -0.00
MT-100 171.43 004b-ULS -0.03 0.00 0.00 0.00 0.00 -0.00
MT-100 228.57(-) 004b-ULS -0.05 0.00 0.00 0.00 0.00 -0.00
MT-100 228.57(+) 004b-ULS -0.12 -0.00 18.58 0.00 -0.00 0.00
MT-100 342.86 004b-ULS -0.14 -0.00 18.58 0.00 2.12 0.00
MT-100 514.29 004b-ULS -0.17 -0.00 18.58 0.00 5.31 0.00
MT-100 685.72 004b-ULS -0.21 -0.00 18.58 0.00 8.49 0.00
MT-100 857.15 004b-ULS -0.24 -0.00 18.58 0.00 11.68 0.00

Beam No. 6

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-100 0.00 004a-ULS -18.58 0.00 -0.04 -0.00 -0.00 0.00
MT-100 100.00 004a-ULS -18.58 0.00 -0.02 -0.00 -0.00 0.00
MT-100 200.00 004a-ULS -18.58 0.00 -0.01 -0.00 -0.00 0.00
MT-100 300.00 004a-ULS -18.58 0.00 0.01 -0.00 -0.00 0.00
MT-100 400.00 004a-ULS -18.58 0.00 0.02 -0.00 -0.00 0.00
MT-100 500.00 004a-ULS -18.58 0.00 0.04 -0.00 0.00 -0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 13 / 23
Version: 1.13.1

Solution: Fixpoint Design E Date: 28/02/2024

Beam No. 7

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-100 0.00 004a-ULS -18.58 -0.00 -0.04 0.00 -0.00 -0.00
MT-100 100.00 004a-ULS -18.58 -0.00 -0.02 0.00 -0.00 -0.00
MT-100 200.00 004a-ULS -18.58 -0.00 -0.01 0.00 -0.00 -0.00
MT-100 300.00 004a-ULS -18.58 -0.00 0.01 0.00 -0.00 -0.00
MT-100 400.00 004a-ULS -18.58 -0.00 0.02 0.00 -0.00 -0.00
MT-100 500.00 004a-ULS -18.58 -0.00 0.04 0.00 0.00 0.00

*004b-ULS: SW_sup + Design Loads. Respective Combination Equation: 1.35 * LC1 + 1.00 * LC7

Normal load

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 14 / 23
Version: 1.13.1

Solution: Fixpoint Design E Date: 28/02/2024

Shear load in Y direction

Shear load in Z direction

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 15 / 23
Version: 1.13.1

Solution: Fixpoint Design E Date: 28/02/2024

Torsion around X

Moment around Y

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 16 / 23
Version: 1.13.1

Solution: Fixpoint Design E Date: 28/02/2024

Moment around Z

5.2.3 Stability Analysis

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 17 / 23
Version: 1.13.1

Solution: Fixpoint Design E Date: 28/02/2024

Buckling ratio

Buckling Max. lateral torsional Max. buckling under Max.


Member Length
Length Buckling ratio buckling under bending compression interaction
No. [mm]
[mm] [%] [%] [%]
1 1110.00 1110.00 1.00 0.00 0.52 0.52
2 650.00 650.00 1.00 0.00 0.02 0.02
3 1110.00 1110.00 1.00 0.00 0.52 0.52
4 857.15 857.15 1.00 0.00 0.06 0.06
5 857.15 857.15 1.00 0.00 0.06 0.06
6 500.00 500.00 1.00 0.00 4.03 4.03
7 500.00 500.00 1.00 0.00 4.03 4.03

5.2.4 Deflection Analysis

Criteria
☑Maximum Allowable Deflection (Beam) L/200
☑Maximum Allowable Deflection (Cantilever)L/150
- Maximum Deflection (Absolute) -
☑No Deflection checks calculated for 1.50mm

Overview

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 18 / 23
Version: 1.13.1

Solution: Fixpoint Design E Date: 28/02/2024

Results
Reference
Member Max deflection Utilization
Load Combination number* Governing criteria Length Limit
No. [mm] [%]
[mm]
1 004-SLS Relative(Cantilever) 1110.00 L/150 -3.59 48.52
2 004-SLS Relative (Beam) 650.00 L/200 -0.09 0.00
3 004-SLS Relative(Cantilever) 1110.00 L/150 3.59 48.52
4 004-SLS Relative(Cantilever) 857.15 L/150 -1.75 30.60
5 004-SLS Relative(Cantilever) 857.15 L/150 1.75 30.60
6 004-SLS Relative (Beam) 500.00 L/200 -0.00 0.00
7 004-SLS Relative (Beam) 500.00 L/200 -0.00 0.00

*004-SLS: SW + Design Loads. Respective Combination Equation: 1.00 * LC1 + 0.70 * LC7

Deflection 1.00 * LC1

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 19 / 23
Version: 1.13.1

Solution: Fixpoint Design E Date: 28/02/2024

Deflection 1.00 * LC1 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 20 / 23
Version: 1.13.1

Solution: Fixpoint Design E Date: 28/02/2024

5.3 System Connectors

5.3 Connectors

5.3.1 Overview

Connector: MT-C-GL OC
Fx Fy Fz Mx My Mz
Connector variant: MT-C-GL OC (C_D)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 2
Local Forces: -1.89 -18.47 0.08 0.12 -0.06 -0.00
Resistance: 94.46 35.33 37.95 2.38 2.72 1.99
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 61.94 % OK
Governing Load
1.35 * LC1 + 1.00 * LC7
Combination
Connector: MT-C-GL OC
Fx Fy Fz Mx My Mz
Connector variant: MT-C-GL OC (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 9
Local Forces: -18.58 0.00 -0.05 -0.00 -0.00 0.00
Resistance: 40.71 17.62 20.22 0.64 1.06 0.75
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 46.04 % OK
Governing Load
1.35 * LC1 + 1.00 * LC7
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 21 / 23
Version: 1.13.1

Solution: Fixpoint Design E Date: 28/02/2024

5.4 Base Connectors

5.4 Bases

5.4.1 Overview

Base connector: MT-B-GXL O4 OC


Fx Fy Fz Mx My Mz
Connector variant: MT-B-GXL O4 OC (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 5
Local Forces: -0.47 -0.00 18.58 -0.00 -11.68 -0.00
Resistance: 580.25 131.52 140.16 15.33 29.30 21.11
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 53.20 % OK
Governing Load
1.35 * LC1 + 1.00 * LC7
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 22 / 23
Version: 1.13.1

Solution: Fixpoint Design E Date: 28/02/2024

6 Remarks, Your Cooperation Duties

Any and all information and data contained in the Software concern solely the use of Hilti products and based on the principles, formulas and security
regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly complied with by
the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the relevant Hilti product.
The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole
responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole responsibility for
having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior
to using them for your specific facility. The Software servers only as an aid to interpret norms and permits without any guarantee as to the absence of
errors, the correctness and relevance ot the results or suitability for a specific application.

You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular
backup of programs and, if applicable, carry out the updates of that you are using the current and thus up-to-date version of the Software in each case
by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or
programs, arising from a culpable breach of duty by you.

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 23 / 23
Fixpoint Design G

Project: SA-13082-SF

Submitted by:

Hilti contact information


Contact name:
Contact e-mail:
Contact phone:
Contact company:

Customer contact information


Customer name:
Customer e-mail:
Customer phone:
Customer company:

Date: 28/02/2024

This submittal is auto-generated based on user-selected inputs.


Therefore, Hilti no representation as to the suitability of these systems for their intended use. 1 / 27
Version: 1.13.1

Solution: Fixpoint Design G Date: 28/02/2024

Table of content

1 Geometry and Application


1.1 Supports
1.2 Nodes
1.3 Members
1.4 Connections
1.5 Release Conditions
1.6 Media Interface Channel
1.7 Gliders
2 Part list
2.1 Members
2.2 Base Connectors
2.3 System Connectors
2.4 Other
3 Load Types
3.1 Loading objects
3.2 Point Loads
3.3 Distributed loads
3.4 Area loads
4 Load Combinations
4.1 Ultimate Limit State
4.2 Serviceability Limit State
5 Results
5.1 Calculation summary
5.2 Members
5.3 System Connectors
5.4 Base Connectors
6 Remarks, Your Cooperation Duties

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 2 / 27
Version: 1.13.1

Solution: Fixpoint Design G Date: 28/02/2024

1 Geometry and Application

Support Details
Modular Support Spacing [mm] Undefined

Intermediate Supports required?

Pipe Fasteners with Glider and Presetting used? (See


subchapter 'Gliders' in chapter 'Geometry and
Application')

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 3 / 27
Version: 1.13.1

Solution: Fixpoint Design G Date: 28/02/2024

1.1 Supports - Concrete

Concrete

Thickness Drilling Depth


Node No. No. Orientation Concrete grade
[mm] [mm]
1 1 Horizontal C20/25 200.00 150
4 2 Horizontal C20/25 200.00 150
5 3 Horizontal C20/25 200.00 150
8 4 Horizontal C20/25 200.00 150
13 5 Horizontal C20/25 200.00 150
16 6 Horizontal C20/25 200.00 150
18 7 Horizontal C20/25 200.00 150
19 8 Horizontal C20/25 200.00 150

1.2 Nodes

X Y Z
No. No. Connector name Connector variant
[mm] [mm] [mm]
1 1 -15.75 0.00 -500.00 MT-B-GXL O4 OC MT-B-GXL O4 OC (C)
2 - -15.75 0.00 783.00 MT-C-GL OC MT-C-GL OC (C_D)
3 - 634.25 0.00 783.00 MT-C-GL OC MT-C-GL OC (C_D)
4 2 634.25 0.00 -500.00 MT-B-GXL O4 OC MT-B-GXL O4 OC (C)
5 3 -15.75 500.00 -500.00 MT-B-GXL O4 OC MT-B-GXL O4 OC (C)
6 - -15.75 500.00 783.00 MT-C-GL OC MT-C-GL OC (C_D)
7 - 634.25 500.00 783.00 MT-C-GL OC MT-C-GL OC (C_D)
8 4 634.25 500.00 -500.00 MT-B-GXL O4 OC MT-B-GXL O4 OC (C)
13 5 -15.75 1000.00 -500.00 MT-B-GXL O4 OC MT-B-GXL O4 OC (C)
16 6 634.25 1000.00 -500.00 MT-B-GXL O4 OC MT-B-GXL O4 OC (C)
18 7 634.25 -500.00 -500.00 MT-B-GXL O4 OC MT-B-GXL O4 OC (C)
19 8 -15.75 -500.00 -500.00 MT-B-GXL O4 OC MT-B-GXL O4 OC (C)
21 - 634.25 -500.00 128.58 MT-C-GL A OC MT-C-GL A OC (C_D)
22 - 634.25 1000.00 128.58 MT-C-GL A OC MT-C-GL A OC (C_D)
23 - -15.75 -500.00 128.58 MT-C-GL A OC MT-C-GL A OC (C_D)
24 - -15.75 1000.00 128.58 MT-C-GL A OC MT-C-GL A OC (C_D)
9 - 634.25 0.00 128.58 MT-C-GL OC MT-C-GL OC (C_D)
10 - 634.25 500.00 128.58 MT-C-GL OC MT-C-GL OC (C_D)
11 - -15.75 0.00 128.58 MT-C-GL OC MT-C-GL OC (C_D)
12 - -15.75 500.00 128.58 MT-C-GL OC MT-C-GL OC (C_D)
9 - 634.25 0.00 128.58 MT-C-GL OC MT-C-GL OC (C_D)
10 - 634.25 500.00 128.58 MT-C-GL OC MT-C-GL OC (C_D)
11 - -15.75 0.00 128.58 MT-C-GL OC MT-C-GL OC (C_D)
12 - -15.75 500.00 128.58 MT-C-GL OC MT-C-GL OC (C_D)

1.3 Members

Member Releases Rotation


No. Node start Node end Member Name
Start End [°]
1 1 2 - - MT-100 90.00
2 2 3 - - MT-100 90.00
3 3 4 - - MT-100 90.00
4 5 6 - - MT-100 90.00
5 7 8 - - MT-100 90.00
6 9 10 1 2 MT-100 0.00
7 11 12 3 4 MT-100 0.00
8 7 6 - - MT-100 90.00
9 13 14 - - MT-100 90.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 4 / 27
Version: 1.13.1

Solution: Fixpoint Design G Date: 28/02/2024


Member Releases Rotation
No. Node start Node end Member Name
Start End [°]
10 15 16 - - MT-100 90.00
11 17 18 - - MT-100 90.00
12 19 20 - - MT-100 90.00
13 21 9 5 1 MT-100 0.00
14 10 22 2 6 MT-100 0.00
15 23 11 7 3 MT-100 0.00
16 12 24 4 8 MT-100 0.00

1.4 Connections

Cross- Cross- Cross- Cross-


Section/Rotation Section/Rotation Section/Rotation Section/Rotation
Node No. Description Variant
Arm1 Arm2 Arm3 Arm4
[-/°] [-/°] [-/°] [-/°]
1 MT-B-GXL O4 OC MT-B-GXL O4 OC (C) MT-100/90 - - -
2 MT-C-GL OC MT-C-GL OC (C_D) MT-100/90 MT-100/90 - -
3 MT-C-GL OC MT-C-GL OC (C_D) MT-100/90 MT-100/90 - -
4 MT-B-GXL O4 OC MT-B-GXL O4 OC (C) MT-100/90 - - -
5 MT-B-GXL O4 OC MT-B-GXL O4 OC (C) MT-100/90 - - -
6 MT-C-GL OC MT-C-GL OC (C_D) MT-100/90 MT-100/90 - -
7 MT-C-GL OC MT-C-GL OC (C_D) MT-100/90 MT-100/90 - -
8 MT-B-GXL O4 OC MT-B-GXL O4 OC (C) MT-100/90 - - -
13 MT-B-GXL O4 OC MT-B-GXL O4 OC (C) MT-100/90 - - -
16 MT-B-GXL O4 OC MT-B-GXL O4 OC (C) MT-100/90 - - -
18 MT-B-GXL O4 OC MT-B-GXL O4 OC (C) MT-100/90 - - -
19 MT-B-GXL O4 OC MT-B-GXL O4 OC (C) MT-100/90 - - -
21 MT-C-GL A OC MT-C-GL A OC (C_D) MT-100/90 MT-100/0 - -
22 MT-C-GL A OC MT-C-GL A OC (C_D) MT-100/90 MT-100/0 - -
23 MT-C-GL A OC MT-C-GL A OC (C_D) MT-100/90 MT-100/0 - -
24 MT-C-GL A OC MT-C-GL A OC (C_D) MT-100/90 MT-100/0 - -

1.5 Release Conditions

Spring Constants
Releases
Member Translational Rotational
No. Cu,x Cu,y Cu,z Cφx Cφy Cφz
Ux Uy Uz φx φy φz
[kN/m] [kN/m] [kN/m] [kNm/Rad] [kNm/Rad] [kNm/Rad]
13 no no no no yes yes - - - - 0.001 0.001
14 no no no no yes yes - - - - 0.001 0.001
15 no no no no yes yes - - - - 0.001 0.001
16 no no no no yes yes - - - - 0.001 0.001
13 no no no no yes yes - - - - 0.001 0.001
14 no no no no yes yes - - - - 0.001 0.001
15 no no no no yes yes - - - - 0.001 0.001
16 no no no no yes yes - - - - 0.001 0.001

1.6 Media Interface Channel

Start Position Length


No. Member No. Media Interface Z-Position Y-Position
[mm] [mm]

1.7 Gliders

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 5 / 27
Version: 1.13.1

Solution: Fixpoint Design G Date: 28/02/2024


Position Start Travel
No. Member No. Glider Custom Load
[mm] [mm] [mm]

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 6 / 27
Version: 1.13.1

Solution: Fixpoint Design G Date: 28/02/2024

2 Part list

2.1 Members

Quantity Weight Length


Position Item Number Description Cutting type
[-] [kg] [mm]
1 2268491 I.-Girder MT-100 OC 4 73.73 1221.00 N - None
2 2268491 I.-Girder MT-100 OC 2 31.70 1050.00 N - None
3 2268491 I.-Girder MT-100 OC 6 31.70 350.00 N - None
4 2268491 I.-Girder MT-100 OC 4 52.59 871.00 N - None

2.2 Base Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
5 2272104 4-hole Baseplate MT-B-GXL O4 OC 8 136.25

2.3 System Connectors

Quantity Weight
Position Item Number Description
[-] [kg]
8 2272066 Angle connector MT-C-GL OC 24 27.87
9 2272069 Angle connector MT-C-GL A OC adjustable 8 9.21

2.4 Other

Quantity Weight
Position Item Number Description
[-] [kg]
6 2272084 Thread forming bolt MT-TFB OC 496 14.14
7 2105876 Stud anchor HST3-R M16x135 35/15 32 6.97

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 7 / 27
Version: 1.13.1

Solution: Fixpoint Design G Date: 28/02/2024

3 Load Types

3. Loads

Custom loads

Load No. Load Distribution Load Case Load Type Comments


1 Point load LC 7: Design Permanent -
2 Point load LC 7: Design Permanent -
3 Point load LC 13: Seismic (+x) Seismic -
4 Point load LC 14: Seismic (-x) Seismic -
5 Point load LC 14: Seismic (-x) Seismic -
6 Point load LC 13: Seismic (+x) Seismic -

3.2 Point Loads

Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
1 Design 2, 8 75.00 0.00 26.54 -3.18 0.00 0.00 0.00
2 Design 2, 8 575.00 0.00 26.54 -3.18 0.00 0.00 0.00
5 Seismic (+x) 2 75.00 0.02 -0.00 -0.00 -0.00 -0.00 -0.00
6 Seismic (-x) 2 75.00 -0.02 -0.00 -0.00 -0.00 -0.00 -0.00
7 Seismic (-x) 2 575.00 0.02 -0.00 -0.00 -0.00 -0.00 -0.00
8 Seismic (+x) 2 575.00 -0.02 -0.00 -0.00 -0.00 -0.00 -0.00
9 Self Weight Support 1 0.00 0.00 0.00 -0.17 0.00 0.00 0.00
10 Self Weight Support 1 1283.00 0.00 0.00 -0.02 0.00 0.00 0.00
11 Self Weight Support 2 650.00 0.00 0.00 -0.02 0.00 0.00 0.00
12 Self Weight Support 3 1283.00 0.00 0.00 -0.17 0.00 0.00 0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 8 / 27
Version: 1.13.1

Solution: Fixpoint Design G Date: 28/02/2024


Position Fx Fy Fz Mx My Mz
Load No. Load Type Members
[mm] [kN] [kN] [kN] [kNm] [kNm] [kNm]
13 Self Weight Support 4 0.00 0.00 0.00 -0.17 0.00 0.00 0.00
14 Self Weight Support 4 1283.00 0.00 0.00 -0.02 0.00 0.00 0.00
15 Self Weight Support 5 0.00 0.00 0.00 -0.02 0.00 0.00 0.00
16 Self Weight Support 5 1283.00 0.00 0.00 -0.17 0.00 0.00 0.00
17 Self Weight Support 9 0.00 0.00 0.00 -0.17 0.00 0.00 0.00
18 Self Weight Support 10 883.00 0.00 0.00 -0.17 0.00 0.00 0.00
19 Self Weight Support 11 883.00 0.00 0.00 -0.17 0.00 0.00 0.00
20 Self Weight Support 12 0.00 0.00 0.00 -0.17 0.00 0.00 0.00
21 Self Weight Support 11 254.42 0.00 0.00 -0.02 0.00 0.00 0.00
22 Self Weight Support 10 254.42 0.00 0.00 -0.02 0.00 0.00 0.00
23 Self Weight Support 12 628.58 0.00 0.00 -0.02 0.00 0.00 0.00
24 Self Weight Support 9 628.58 0.00 0.00 -0.02 0.00 0.00 0.00
25 Self Weight Support 3 654.42 0.00 0.00 -0.02 0.00 0.00 0.00
26 Self Weight Support 5 654.42 0.00 0.00 -0.02 0.00 0.00 0.00
27 Self Weight Support 1 628.58 0.00 0.00 -0.02 0.00 0.00 0.00
28 Self Weight Support 4 628.58 0.00 0.00 -0.02 0.00 0.00 0.00
29 Self Weight Support 3 654.42 0.00 0.00 -0.02 0.00 0.00 0.00
30 Self Weight Support 5 654.42 0.00 0.00 -0.02 0.00 0.00 0.00
31 Self Weight Support 1 628.58 0.00 0.00 -0.02 0.00 0.00 0.00
32 Self Weight Support 4 628.58 0.00 0.00 -0.02 0.00 0.00 0.00

3.3 Distributed loads

Start End
Fx Fy Fz Mx My Mz
Load No. Load Type Members Position Position
[kN/m] [kN/m] [kN/m] [kNm/m] [kNm/m] [kNm/m]
[mm] [mm]
33 Self Weight Support 1 0.00 1283.00 0.00 0.00 -0.15 0.00 0.00 0.00
34 Self Weight Support 2 0.00 650.00 0.00 0.00 -0.15 0.00 0.00 0.00
35 Self Weight Support 3 0.00 1283.00 0.00 0.00 -0.15 0.00 0.00 0.00
36 Self Weight Support 4 0.00 1283.00 0.00 0.00 -0.15 0.00 0.00 0.00
37 Self Weight Support 5 0.00 1283.00 0.00 0.00 -0.15 0.00 0.00 0.00
38 Self Weight Support 6 0.00 500.00 0.00 0.00 -0.15 0.00 0.00 0.00
39 Self Weight Support 7 0.00 500.00 0.00 0.00 -0.15 0.00 0.00 0.00
40 Self Weight Support 8 0.00 650.00 0.00 0.00 -0.15 0.00 0.00 0.00
41 Self Weight Support 9 0.00 883.00 0.00 0.00 -0.15 0.00 0.00 0.00
42 Self Weight Support 10 0.00 883.00 0.00 0.00 -0.15 0.00 0.00 0.00
43 Self Weight Support 11 0.00 883.00 0.00 0.00 -0.15 0.00 0.00 0.00
44 Self Weight Support 12 0.00 883.00 0.00 0.00 -0.15 0.00 0.00 0.00
45 Self Weight Support 13 0.00 500.00 0.00 0.00 -0.15 0.00 0.00 0.00
46 Self Weight Support 14 0.00 500.00 0.00 0.00 -0.15 0.00 0.00 0.00
47 Self Weight Support 15 0.00 500.00 0.00 0.00 -0.15 0.00 0.00 0.00
48 Self Weight Support 16 0.00 500.00 0.00 0.00 -0.15 0.00 0.00 0.00

3.4 Area loads

3.4.1 User input

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 9 / 27
Version: 1.13.1

Solution: Fixpoint Design G Date: 28/02/2024

4 Load Combinations

Design base EN 1993

Load combination design base EN 1990

4.1 Ultimate Limit State

Design base Load combination and safety factors


ULS - 001a-ULS: SW_inf (Support Only) 1.00 * LC1
ULS - 001b-ULS: SW_sup (Support Only) 1.35 * LC1
ULS - 004a-ULS: SW_inf + Design Loads 1.00 * LC1 + 1.00 * LC7
ULS - 004b-ULS: SW_sup + Design Loads 1.35 * LC1 + 1.00 * LC7
ULS - 027a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC13
z) + Live + Snow
ULS - 027b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC14
+ Live + Snow
ULS - 029a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 0.30 * LC13
z) + Live + Snow
ULS - 030a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 0.30 * LC14
+ Live + Snow
ULS - 027a-ULS_Base : SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 1.00 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 027b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 029a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 0.30 * qa * LC13
Seismic (-z) + Live + Snow
ULS - 030a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 0.30 * qa * LC14
Seismic (-z) + Live + Snow
ULS - 031a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 1.00 * LC13 + 1.00 * 0.74 * LC7
z) + Design
ULS - 031b-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 1.00 * LC14 + 1.00 * 0.74 * LC7
+ Design
ULS - 033a-ULS: SW + Seismic (+x) + Seismic (+y) + Seismic (-
1.00 * LC1 + 0.30 * LC13 + 1.00 * 0.74 * LC7
z) + Design
ULS - 034a-ULS: SW + Seismic (-x) + Seismic (+y) + Seismic (-z)
1.00 * LC1 + 0.30 * LC14 + 1.00 * 0.74 * LC7
+ Design
ULS - 032a-ULS_Base: SW + Seismic (+x) + Seismic (-y) +
1.00 * LC1 + 1.00 * qa * LC13 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 031b-ULS_Base : SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 1.00 * qa * LC14 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 033a-ULS_Base: SW + Seismic (+x) + Seismic (+y) +
1.00 * LC1 + 0.30 * qa * LC13 + 1.00 * 0.74 * LC7
Seismic (-z) + Design
ULS - 034a-ULS_Base: SW + Seismic (-x) + Seismic (+y) +
1.00 * LC1 + 0.30 * qa * LC14 + 1.00 * 0.74 * LC7
Seismic (-z) + Design

4.2 Serviceability Limit State

Load Case Load combination and safety factors


SLS - 001-SLS: SW (Support Only) 1.00 * LC1
SLS - 004-SLS: SW + Design Loads 1.00 * LC1 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 10 / 27
Version: 1.13.1

Solution: Fixpoint Design G Date: 28/02/2024

5 Results

5.1 Calculation summary

5.1.3 Members

Governing load ULS SLS


No Member Status
combination number* [%] [%]
1 MT-100 004-SLS 85.23 97.61 OK
2 MT-100 004b-ULS 30.80 - OK
3 MT-100 004-SLS 85.23 97.61 OK
11 MT-100 004-SLS 85.23 97.61 OK
12 MT-100 004-SLS 85.23 97.61 OK
14 MT-100 004b-ULS 0.06 - OK
15 MT-100 004b-ULS 0.06 - OK
16 MT-100 004b-ULS 30.80 - OK
21 MT-100 004-SLS 96.45 52.33 OK
22 MT-100 004-SLS 96.45 52.33 OK
23 MT-100 004-SLS 96.45 52.33 OK
24 MT-100 004-SLS 96.45 52.33 OK
25 MT-100 004b-ULS 6.41 - OK
26 MT-100 004a-ULS 6.84 - OK
27 MT-100 004b-ULS 6.41 - OK
28 MT-100 004a-ULS 6.84 - OK

5.1.2 Base Connectors

Governing load ULS SLS


No Base connector Status
combination number* [%] [%]
1 MT-B-GXL O4 OC 004b-ULS 54.07 - OK
4 MT-B-GXL O4 OC 004b-ULS 54.07 - OK
5 MT-B-GXL O4 OC 004b-ULS 54.07 - OK
8 MT-B-GXL O4 OC 004b-ULS 54.07 - OK
13 MT-B-GXL O4 OC 004b-ULS 90.34 - OK
16 MT-B-GXL O4 OC 004b-ULS 90.34 - OK
18 MT-B-GXL O4 OC 004b-ULS 90.34 - OK
19 MT-B-GXL O4 OC 004b-ULS 90.34 - OK

5.1.3 System Connectors

Governing load ULS SLS


No Connector Status
combination number* [%] [%]
2 MT-C-GL OC 004b-ULS 89.16 - OK
3 MT-C-GL OC 004b-ULS 89.16 - OK
6 MT-C-GL OC 004b-ULS 89.16 - OK
7 MT-C-GL OC 004b-ULS 89.16 - OK
21 MT-C-GL A OC 004b-ULS 63.98 - OK
22 MT-C-GL A OC 004b-ULS 33.72 - OK
23 MT-C-GL A OC 004b-ULS 63.98 - OK
24 MT-C-GL A OC 004b-ULS 33.72 - OK
9 MT-C-GL OC 001b-ULS 0.13 - OK
10 MT-C-GL OC 001b-ULS 0.13 - OK
11 MT-C-GL OC 001b-ULS 0.13 - OK
12 MT-C-GL OC 001b-ULS 0.13 - OK
9 MT-C-GL OC 004b-ULS 63.98 - OK
10 MT-C-GL OC 004b-ULS 33.72 - OK
11 MT-C-GL OC 004b-ULS 63.98 - OK
12 MT-C-GL OC 004b-ULS 33.72 - OK
*004-SLS: SW + Design Loads . Respective Combination Equation: 1.00 * LC1 + 0.70 * LC7
*004b-ULS: SW_sup + Design Loads . Respective Combination Equation: 1.35 * LC1 + 1.00 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 11 / 27
Version: 1.13.1

Solution: Fixpoint Design G Date: 28/02/2024


*004a-ULS: SW_inf + Design Loads . Respective Combination Equation: 1.00 * LC1 + 1.00 * LC7
*001b-ULS: SW_sup (Support Only) . Respective Combination Equation: 1.35 * LC1

Overall Status: Calculation OK, design criteria met!

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 12 / 27
Version: 1.13.1

Solution: Fixpoint Design G Date: 28/02/2024

5.2 Members

5.2.1 Member Properties


Members: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12,
5.2.1.1 MT-100
13, 14, 15, 16
5.2.1.1.1 Section properties
t A Iy Iz It
[mm] [mm²] [mm⁴] [mm⁴] [mm⁴]
4.00 1555.34 4874000.00 2610000.00 4754000.00

Iω M Wy Wz Wy
[mm⁶] [kg/m] [mm³] [mm³] [mm³]
303000000.00 60.38 -65000.00 -52200.00 -65000.00

5.2.1.1.2 Material properties


E G Fu Fy Fy.cold
Steel grade
[N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²]
S350GD 1.0529 210000.00 80769.00 420.00 350.00 350.00

5.2.2 Member Design

5.2.2.1 Overview

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 13 / 27
Version: 1.13.1

Solution: Fixpoint Design G Date: 28/02/2024

5.2.2.2 Stress Analysis

5.2.2.2.1 Table of Results

Load Combination σ τ σeqv σlimit τlimit Utilization


No. Member
number* [N/mm²] [N/mm²] [N/mm²] [N/mm²] [N/mm²] [%]
1 I.-Girder MT-100 OC 004b-ULS -269.88 0.00 271.19 318.18 0.00 85.23
2 I.-Girder MT-100 OC 004b-ULS -30.75 56.56 98.01 318.18 183.70 30.80
3 I.-Girder MT-100 OC 004b-ULS -269.88 0.00 271.19 318.18 0.00 85.23
4 I.-Girder MT-100 OC 004b-ULS -269.88 0.00 271.19 318.18 0.00 85.23
5 I.-Girder MT-100 OC 004b-ULS -269.88 0.00 271.19 318.18 0.00 85.23
6 I.-Girder MT-100 OC 004b-ULS -0.10 0.11 0.19 318.18 183.70 0.06
7 I.-Girder MT-100 OC 004b-ULS 0.10 0.11 0.19 318.18 183.70 0.06
8 I.-Girder MT-100 OC 004b-ULS -30.75 -56.56 98.01 318.18 183.70 30.80
9 I.-Girder MT-100 OC 004b-ULS -305.58 0.00 306.89 318.18 0.00 96.45
10 I.-Girder MT-100 OC 004b-ULS -305.58 0.00 306.89 318.18 0.00 96.45
11 I.-Girder MT-100 OC 004b-ULS -305.58 0.00 306.89 318.18 0.00 96.45
12 I.-Girder MT-100 OC 004b-ULS -305.58 0.00 306.89 318.18 0.00 96.45
13 I.-Girder MT-100 OC 004b-ULS 20.39 0.20 20.39 318.18 183.70 6.41
14 I.-Girder MT-100 OC 004b-ULS -20.39 0.20 20.39 318.18 183.70 6.41
15 I.-Girder MT-100 OC 004b-ULS 20.39 0.20 20.39 318.18 183.70 6.41
16 I.-Girder MT-100 OC 004b-ULS -20.39 0.20 20.39 318.18 183.70 6.41

*004b-ULS: SW_sup + Design Loads. Respective Combination Equation: 1.35 * LC1 + 1.00 * LC7

5.2.2.2 Governing Member Loading

Beam No. 1

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-100 0.00 004b-ULS -3.70 0.12 5.02 0.15 14.21 0.05
MT-100 256.60 004b-ULS -3.65 0.12 5.03 0.15 15.50 0.02
MT-100 513.20 004b-ULS -3.60 0.12 5.02 0.15 16.79 -0.01
MT-100 628.58(-) 004b-ULS -3.58 0.12 5.02 0.15 17.37 -0.03
MT-100 628.58(+) 004b-ULS -3.40 0.12 -26.54 0.15 17.37 -0.02
MT-100 769.80 004b-ULS -3.38 0.12 -26.54 0.15 13.62 -0.04
MT-100 1026.40 004b-ULS -3.33 0.12 -26.54 0.15 6.81 -0.07
MT-100 1283.00 004b-ULS -3.28 0.12 -26.54 0.15 -0.00 -0.11

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 14 / 27
Version: 1.13.1

Solution: Fixpoint Design G Date: 28/02/2024

Beam No. 2

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-100 0.00 004b-ULS -0.12 -3.25 -26.54 0.00 0.15 -0.11
MT-100 75.00(-) 004b-ULS -0.12 -3.23 -26.54 0.00 -1.84 0.14
MT-100 75.00(+) 004b-ULS -0.12 -0.05 0.00 0.00 -1.84 0.14
MT-100 130.00 004b-ULS -0.12 -0.04 0.00 0.00 -1.84 0.14
MT-100 260.00 004b-ULS -0.12 -0.01 -0.00 0.00 -1.84 0.14
MT-100 390.00 004b-ULS -0.12 0.01 -0.00 0.00 -1.84 0.14
MT-100 520.00 004b-ULS -0.12 0.04 0.00 0.00 -1.84 0.14
MT-100 575.00(-) 004b-ULS -0.12 0.05 0.00 0.00 -1.84 0.14
MT-100 575.00(+) 004b-ULS -0.12 3.23 26.54 0.00 -1.84 0.14
MT-100 650.00 004b-ULS -0.12 3.25 26.54 0.00 0.15 -0.11

Beam No. 3

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-100 0.00 004b-ULS -3.28 -0.12 26.54 -0.15 0.00 -0.11
MT-100 256.60 004b-ULS -3.33 -0.12 26.54 -0.15 6.81 -0.07
MT-100 513.20 004b-ULS -3.38 -0.12 26.54 -0.15 13.62 -0.04
MT-100 654.42(-) 004b-ULS -3.41 -0.12 26.54 -0.15 17.37 -0.02
MT-100 654.42(+) 004b-ULS -3.58 -0.12 -5.02 -0.15 17.37 -0.03
MT-100 769.80 004b-ULS -3.60 -0.12 -5.03 -0.15 16.79 -0.01
MT-100 1026.40 004b-ULS -3.65 -0.12 -5.03 -0.15 15.50 0.02
MT-100 1283.00 004b-ULS -3.70 -0.12 -5.02 -0.15 14.21 0.05

Beam No. 4

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-100 0.00 004b-ULS -3.70 0.12 5.02 0.15 14.21 0.05
MT-100 256.60 004b-ULS -3.65 0.12 5.03 0.15 15.50 0.02
MT-100 513.20 004b-ULS -3.60 0.12 5.03 0.15 16.79 -0.01
MT-100 628.58(-) 004b-ULS -3.58 0.12 5.02 0.15 17.37 -0.03
MT-100 628.58(+) 004b-ULS -3.40 0.12 -26.54 0.15 17.37 -0.02
MT-100 769.80 004b-ULS -3.38 0.12 -26.54 0.15 13.62 -0.04
MT-100 1026.40 004b-ULS -3.33 0.12 -26.54 0.15 6.81 -0.07
MT-100 1283.00 004b-ULS -3.28 0.12 -26.54 0.15 -0.00 -0.11

Beam No. 5

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-100 0.00 004b-ULS -3.28 -0.12 26.54 -0.15 0.00 -0.11
MT-100 256.60 004b-ULS -3.33 -0.12 26.54 -0.15 6.81 -0.07
MT-100 513.20 004b-ULS -3.38 -0.12 26.54 -0.15 13.62 -0.04
MT-100 654.42(-) 004b-ULS -3.41 -0.12 26.54 -0.15 17.37 -0.02
MT-100 654.42(+) 004b-ULS -3.58 -0.12 -5.02 -0.15 17.37 -0.03
MT-100 769.80 004b-ULS -3.60 -0.12 -5.02 -0.15 16.79 -0.01
MT-100 1026.40 004b-ULS -3.65 -0.12 -5.03 -0.15 15.50 0.02
MT-100 1283.00 004b-ULS -3.70 -0.12 -5.02 -0.15 14.21 0.05

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 15 / 27
Version: 1.13.1

Solution: Fixpoint Design G Date: 28/02/2024

Beam No. 6

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-100 0.00 004b-ULS -0.00 0.00 -0.05 0.00 -0.00 0.00
MT-100 100.00 004b-ULS -0.00 0.00 -0.03 0.00 -0.00 0.00
MT-100 200.00 004b-ULS -0.00 0.00 -0.01 0.00 -0.01 0.00
MT-100 300.00 004b-ULS -0.00 0.00 0.01 0.00 -0.01 0.00
MT-100 400.00 004b-ULS -0.00 0.00 0.03 0.00 -0.00 -0.00
MT-100 500.00 004b-ULS -0.00 0.00 0.05 0.00 0.00 -0.00

Beam No. 7

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-100 0.00 004b-ULS 0.00 -0.00 -0.05 0.00 -0.00 -0.00
MT-100 100.00 004b-ULS 0.00 -0.00 -0.03 0.00 -0.00 -0.00
MT-100 200.00 004b-ULS 0.00 -0.00 -0.01 0.00 -0.01 -0.00
MT-100 300.00 004b-ULS 0.00 -0.00 0.01 0.00 -0.01 -0.00
MT-100 400.00 004b-ULS 0.00 -0.00 0.03 0.00 -0.00 0.00
MT-100 500.00 004b-ULS 0.00 -0.00 0.05 0.00 0.00 0.00

Beam No. 8

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-100 0.00 004b-ULS -0.12 -3.25 26.54 0.00 -0.15 -0.11
MT-100 75.00(-) 004b-ULS -0.12 -3.23 26.54 0.00 1.84 0.14
MT-100 75.00(+) 004b-ULS -0.12 -0.05 -0.00 0.00 1.84 0.14
MT-100 130.00 004b-ULS -0.12 -0.04 -0.00 0.00 1.84 0.14
MT-100 260.00 004b-ULS -0.12 -0.01 -0.00 0.00 1.84 0.14
MT-100 390.00 004b-ULS -0.12 0.01 0.00 0.00 1.84 0.14
MT-100 520.00 004b-ULS -0.12 0.04 -0.00 0.00 1.84 0.14
MT-100 575.00(-) 004b-ULS -0.12 0.05 -0.00 0.00 1.84 0.14
MT-100 575.00(+) 004b-ULS -0.12 3.23 -26.54 0.00 1.84 0.14
MT-100 650.00 004b-ULS -0.12 3.25 -26.54 0.00 -0.15 -0.11

Beam No. 9

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-100 0.00 004b-ULS -0.26 0.00 -31.56 0.00 19.84 0.00
MT-100 176.60 004b-ULS -0.23 0.00 -31.56 0.00 14.27 0.00
MT-100 353.20 004b-ULS -0.19 0.00 -31.57 0.00 8.69 0.00
MT-100 529.80 004b-ULS -0.15 0.00 -31.56 0.00 3.12 0.00
MT-100 628.58(-) 004b-ULS -0.13 0.00 -31.56 0.00 -0.00 0.00
MT-100 628.58(+) 004b-ULS -0.05 0.00 0.00 0.00 0.00 -0.00
MT-100 706.40 004b-ULS -0.04 0.00 0.00 0.00 0.00 -0.00
MT-100 883.00 004b-ULS 0.00 0.00 0.00 0.00 0.00 -0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 16 / 27
Version: 1.13.1

Solution: Fixpoint Design G Date: 28/02/2024

Beam No. 10

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-100 0.00 004b-ULS 0.00 0.00 0.00 0.00 0.00 -0.00
MT-100 176.60 004b-ULS -0.04 0.00 0.00 0.00 0.00 -0.00
MT-100 254.42(-) 004b-ULS -0.05 0.00 0.00 0.00 0.00 -0.00
MT-100 254.42(+) 004b-ULS -0.14 -0.00 31.56 0.00 -0.00 0.00
MT-100 353.20 004b-ULS -0.16 -0.00 31.56 0.00 3.12 0.00
MT-100 529.80 004b-ULS -0.19 -0.00 31.57 0.00 8.69 0.00
MT-100 706.40 004b-ULS -0.23 -0.00 31.56 0.00 14.27 0.00
MT-100 883.00 004b-ULS -0.26 -0.00 31.56 0.00 19.84 0.00

Beam No. 11

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-100 0.00 004b-ULS 0.00 0.00 0.00 0.00 0.00 -0.00
MT-100 176.60 004b-ULS -0.04 0.00 0.00 0.00 0.00 -0.00
MT-100 254.42(-) 004b-ULS -0.05 0.00 0.00 0.00 0.00 -0.00
MT-100 254.42(+) 004b-ULS -0.14 0.00 31.56 0.00 -0.00 0.00
MT-100 353.20 004b-ULS -0.16 0.00 31.56 0.00 3.12 0.00
MT-100 529.80 004b-ULS -0.19 0.00 31.57 0.00 8.69 0.00
MT-100 706.40 004b-ULS -0.23 0.00 31.56 0.00 14.27 0.00
MT-100 883.00 004b-ULS -0.26 0.00 31.56 0.00 19.84 0.00

Beam No. 12

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-100 0.00 004b-ULS -0.26 -0.00 -31.56 0.00 19.84 0.00
MT-100 176.60 004b-ULS -0.23 -0.00 -31.56 0.00 14.27 0.00
MT-100 353.20 004b-ULS -0.19 -0.00 -31.57 0.00 8.69 0.00
MT-100 529.80 004b-ULS -0.15 -0.00 -31.56 0.00 3.12 0.00
MT-100 628.58(-) 004b-ULS -0.13 -0.00 -31.56 0.00 -0.00 0.00
MT-100 628.58(+) 004b-ULS -0.05 0.00 0.00 0.00 0.00 -0.00
MT-100 706.40 004b-ULS -0.04 0.00 0.00 0.00 0.00 -0.00
MT-100 883.00 004b-ULS 0.00 0.00 0.00 0.00 0.00 -0.00

Beam No. 13

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-100 0.00 004b-ULS 31.56 0.00 -0.05 0.00 -0.00 -0.00
MT-100 100.00 004b-ULS 31.56 0.00 -0.03 0.00 -0.00 0.00
MT-100 200.00 004b-ULS 31.56 0.00 -0.01 0.00 -0.01 -0.00
MT-100 300.00 004b-ULS 31.56 0.00 0.01 0.00 -0.01 -0.00
MT-100 400.00 004b-ULS 31.56 0.00 0.03 0.00 -0.00 -0.00
MT-100 500.00 004b-ULS 31.56 0.00 0.05 0.00 0.00 -0.00

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 17 / 27
Version: 1.13.1

Solution: Fixpoint Design G Date: 28/02/2024

Beam No. 14

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-100 0.00 004a-ULS -31.56 0.00 -0.04 -0.00 -0.00 0.00
MT-100 100.00 004a-ULS -31.56 0.00 -0.02 -0.00 -0.00 0.00
MT-100 200.00 004a-ULS -31.56 0.00 -0.01 -0.00 -0.00 0.00
MT-100 300.00 004a-ULS -31.56 0.00 0.01 -0.00 -0.00 0.00
MT-100 400.00 004a-ULS -31.56 0.00 0.02 -0.00 -0.00 0.00
MT-100 500.00 004a-ULS -31.56 0.00 0.04 -0.00 0.00 -0.00

Beam No. 15

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-100 0.00 004b-ULS 31.56 -0.00 -0.05 -0.00 -0.00 -0.00
MT-100 100.00 004b-ULS 31.56 -0.00 -0.03 -0.00 -0.00 -0.00
MT-100 200.00 004b-ULS 31.56 -0.00 -0.01 -0.00 -0.01 0.00
MT-100 300.00 004b-ULS 31.56 -0.00 0.01 -0.00 -0.01 0.00
MT-100 400.00 004b-ULS 31.56 -0.00 0.03 -0.00 -0.00 0.00
MT-100 500.00 004b-ULS 31.56 -0.00 0.05 -0.00 0.00 0.00

Beam No. 16

Location Load Combination N Vy Vz Mx My Mz


Type
[mm] number* [kN] [kN] [kN] [kNm] [kNm] [kNm]
MT-100 0.00 004a-ULS -31.56 -0.00 -0.04 0.00 -0.00 -0.00
MT-100 100.00 004a-ULS -31.56 -0.00 -0.02 0.00 -0.00 -0.00
MT-100 200.00 004a-ULS -31.56 -0.00 -0.01 0.00 -0.00 -0.00
MT-100 300.00 004a-ULS -31.56 -0.00 0.01 0.00 -0.00 -0.00
MT-100 400.00 004a-ULS -31.56 -0.00 0.02 0.00 -0.00 -0.00
MT-100 500.00 004a-ULS -31.56 -0.00 0.04 0.00 0.00 0.00

*004b-ULS: SW_sup + Design Loads. Respective Combination Equation: 1.35 * LC1 + 1.00 * LC7

Normal load

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 18 / 27
Version: 1.13.1

Solution: Fixpoint Design G Date: 28/02/2024

Shear load in Y direction

Shear load in Z direction

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 19 / 27
Version: 1.13.1

Solution: Fixpoint Design G Date: 28/02/2024

Torsion around X

Moment around Y

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 20 / 27
Version: 1.13.1

Solution: Fixpoint Design G Date: 28/02/2024

Moment around Z

5.2.3 Stability Analysis

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 21 / 27
Version: 1.13.1

Solution: Fixpoint Design G Date: 28/02/2024

Buckling ratio

Buckling Max. lateral torsional Max. buckling under Max.


Member Length
Length Buckling ratio buckling under bending compression interaction
No. [mm]
[mm] [%] [%] [%]
1 1283.00 1283.00 1.00 0.00 0.91 0.91
2 650.00 650.00 1.00 0.00 0.03 0.03
3 1283.00 1283.00 1.00 0.00 0.91 0.91
4 1283.00 1283.00 1.00 0.00 0.91 0.91
5 1283.00 1283.00 1.00 0.00 0.91 0.91
6 500.00 500.00 1.00 0.00 0.00 0.00
7 500.00 500.00 1.00 0.00 0.00 0.00
8 650.00 650.00 1.00 0.00 0.03 0.03
9 883.00 883.00 1.00 0.00 0.06 0.06
10 883.00 883.00 1.00 0.00 0.06 0.06
11 883.00 883.00 1.00 0.00 0.06 0.06
12 883.00 883.00 1.00 0.00 0.06 0.06
13 500.00 500.00 1.00 0.00 0.00 0.00
14 500.00 500.00 1.00 0.00 6.84 6.84
15 500.00 500.00 1.00 0.00 0.00 0.00
16 500.00 500.00 1.00 0.00 6.84 6.84

5.2.4 Deflection Analysis

Criteria
☑Maximum Allowable Deflection (Beam) L/200
☑Maximum Allowable Deflection (Cantilever)L/150
- Maximum Deflection (Absolute) -
☑No Deflection checks calculated for 1.50mm

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 22 / 27
Version: 1.13.1

Solution: Fixpoint Design G Date: 28/02/2024

Overview

Results
Reference
Member Max deflection Utilization
Load Combination number* Governing criteria Length Limit
No. [mm] [%]
[mm]
1 004-SLS Relative(Cantilever) 1283.00 L/150 -8.35 97.61
2 004-SLS Relative (Beam) 650.00 L/200 -0.05 0.00
3 004-SLS Relative(Cantilever) 1283.00 L/150 8.35 97.61
4 004-SLS Relative(Cantilever) 1283.00 L/150 -8.35 97.61
5 004-SLS Relative(Cantilever) 1283.00 L/150 8.35 97.61
6 004-SLS Relative (Beam) 500.00 L/200 -0.00 0.00
7 004-SLS Relative (Beam) 500.00 L/200 -0.00 0.00
8 004-SLS Relative (Beam) 650.00 L/200 0.05 0.00
9 004-SLS Relative(Cantilever) 883.00 L/150 -3.08 52.33
10 004-SLS Relative(Cantilever) 883.00 L/150 3.08 52.33
11 004-SLS Relative(Cantilever) 883.00 L/150 3.08 52.33
12 004-SLS Relative(Cantilever) 883.00 L/150 -3.08 52.33
13 004-SLS Relative (Beam) 500.00 L/200 -0.00 0.00
14 004-SLS Relative (Beam) 500.00 L/200 -0.00 0.00
15 004-SLS Relative (Beam) 500.00 L/200 -0.00 0.00
16 004-SLS Relative (Beam) 500.00 L/200 -0.00 0.00

*004-SLS: SW + Design Loads. Respective Combination Equation: 1.00 * LC1 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 23 / 27
Version: 1.13.1

Solution: Fixpoint Design G Date: 28/02/2024

Deflection 1.00 * LC1

Deflection 1.00 * LC1 + 0.70 * LC7

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 24 / 27
Version: 1.13.1

Solution: Fixpoint Design G Date: 28/02/2024

5.3 System Connectors

5.3 Connectors

5.3.1 Overview

Connector: MT-C-GL OC
Fx Fy Fz Mx My Mz
Connector variant: MT-C-GL OC (C_D)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 3
Local Forces: -3.28 26.54 0.12 -0.15 -0.10 0.00
Resistance: 94.46 35.33 37.95 2.38 2.72 1.99
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 89.16 % OK
Governing Load
1.35 * LC1 + 1.00 * LC7
Combination
Connector: MT-C-GL A OC
Fx Fy Fz Mx My Mz
Connector variant: MT-C-GL A OC (C_D)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 21
Local Forces: 31.56 0.00 -0.05 0.00 -0.00 0.00
Resistance: 49.57 35.33 37.95 2.38 2.72 2.22
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 63.98 % OK
Governing Load
1.35 * LC1 + 1.00 * LC7
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 25 / 27
Version: 1.13.1

Solution: Fixpoint Design G Date: 28/02/2024

5.4 Base Connectors

5.4 Bases

5.4.1 Overview

Base connector: MT-B-GXL O4 OC


Fx Fy Fz Mx My Mz
Connector variant: MT-B-GXL O4 OC (C)
[kN] [kN] [kN] [kNm] [kNm] [kNm]
Node No. : 13
Local Forces: -0.49 -0.00 31.56 -0.00 -19.84 -0.00
Resistance: 580.25 131.52 140.16 15.33 29.30 21.11
abs(Fx.ed/Fx.rd)+abs(Fy.ed/Fy.rd)+abs(Fz.ed/Fz.rd)+abs(Mx.ed/Mx.rd)+abs(
Equation:
My.ed/My.rd)+abs(Mz.ed/Mz.rd)
Utilization: 90.34 % OK
Governing Load
1.35 * LC1 + 1.00 * LC7
Combination

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 26 / 27
Version: 1.13.1

Solution: Fixpoint Design G Date: 28/02/2024

6 Remarks, Your Cooperation Duties

Any and all information and data contained in the Software concern solely the use of Hilti products and based on the principles, formulas and security
regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly complied with by
the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using the relevant Hilti product.
The results of the calculations carried out by means of the Software are based essentially on the data you put in. Therefore, you bear the sole
responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you. Moreover, you bear sole responsibility for
having the results of the calculation checked and cleared by an expert, particularly with regard to compliance with applicable norms and permits, prior
to using them for your specific facility. The Software servers only as an aid to interpret norms and permits without any guarantee as to the absence of
errors, the correctness and relevance ot the results or suitability for a specific application.

You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the regular
backup of programs and, if applicable, carry out the updates of that you are using the current and thus up-to-date version of the Software in each case
by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or
programs, arising from a culpable breach of duty by you.

Data and results must be checked for agreement with existing conditions and for plausibility. Changes may be necessary.
Copyright (c) Hilti AG 2010, FL-9494 Schaan 27 / 27
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-GL O4 OC Date: 28/02/2024
Fastening point:

Specifier's comments:

1 Input data
Anchor type and diameter: HST3 M16 hef1
Return period (service life in years): 50
Item number: 2114053 HST3 M16x115 15/-
Effective embedment depth: hef,opti = 68.0 mm (hef,limit = 84.0 mm), hnom = 81.0 mm
Material:
Evaluation Service Report: ETA 98/0001
Issued I Valid: 20/07/2023 | -
Proof: Design Method EN 1992-4, Mechanical
Stand-off installation: eb = 0.0 mm (no stand-off); t = 12.0 mm

Anchor plate :
R lx x ly x t = 350.0 mm x 350.0 mm x 12.0 mm; (Recommended plate thickness: not calculated)

Profile: no profile
Base material: 2
cracked concrete, C25/30, fc,cyl = 25.00 N/mm ; h = 250.0 mm, User-defined partial material safety
factor gc = 1.500
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement
Reinforcement to control splitting acc. to EN 1992-4, 7.2.1.7 (2) b) 2) present

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

1
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-GL O4 OC Date: 28/02/2024
Fastening point:

1.1 Load combination


Case Description Forces [kN] / Moments [kNm] Seismic Fire Max. Util. Anchor [%]
1 Combination 1 N = -2.110; Vx = 0.270; Vy = 19.170; no no 100
Mx = -7.230; My = 0.020; Mz = 0.390;

2 Load case/Resulting anchor forces y


3 4
Compression

Anchor reactions [kN]


Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 11.371 4.475 0.404 4.456
2 11.351 5.145 0.404 5.129 x
3 0.000 4.464 -0.269 4.456
4 0.000 5.136 -0.269 5.129

max. concrete compressive strain: 0.10 [‰]


max. concrete compressive stress: 2.88 [N/mm ]
2

resulting tension force in (x/y)=(0.0/0.0): 0.000 [kN] 1 2


resulting compression force in (x/y)=(175.7/333.5): 24.831 [kN]

Anchor forces are calculated based on the assumption of a rigid anchor plate.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

2
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-GL O4 OC Date: 28/02/2024
Fastening point:

3 Tension load (EN 1992-4, Section 7.2.1)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* 11.371 54.286 21 OK
Pullout Strength* 11.371 14.392 80 OK
Concrete Breakout Failure** 11.371 14.392 80 OK
Splitting failure** N/A N/A N/A N/A

* highest loaded anchor **anchor group (anchors in tension)

3.1 Steel Strength

N
NEd £ NRd,s = Rk,s EN 1992-4, Table 7.1
gM,s

NRk,s [kN] gM,s NRd,s [kN] NEd [kN]


76.000 1.400 54.286 11.371

3.2 Pullout Strength

y c · NRk,p
NEd £ NRd,p = EN 1992-4, Table 7.1
gM,p

NRk,p [kN] yc g M,p NRd,p [kN] NEd [kN]


19.309 1.118 1.500 14.392 11.371

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

3
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-GL O4 OC Date: 28/02/2024
Fastening point:

3.3 Concrete Breakout Failure

N
NEd £ NRd,c = Rk,c EN 1992-4, Table 7.1
gM,c
0 Ac,N
NRk,c = NRk,c · 0
· y s,N · y re,N · y ec1,N · y ec2,N · y M,N EN 1992-4, Eq. (7.1)
Ac,N
0 1,5
NRk,c = k1 · √fck · hef EN 1992-4, Eq. (7.2)
0
Ac,N = scr,N · scr,N EN 1992-4, Eq. (7.3)
c
y s,N = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.4)
ccr,N £
1
y ec1,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eN,1
scr,N )
1
y ec2,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eN,2
scr,N )
y M,N =1 EN 1992-4, Eq. (7.7)

2 0 2 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] fc,cyl [N/mm ]
41,616 41,616 102.0 204.0 25.00

ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N


0.0 1.000 0.0 1.000 1.000 1.000
0
z [mm] y M,N k1 NRk,c [kN] gM,c NRd,c [kN] NEd [kN]
303.5 1.000 7.700 21.589 1.500 14.392 11.371

Group anchor ID
1

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

4
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-GL O4 OC Date: 28/02/2024
Fastening point:

4 Shear load (EN 1992-4, Section 7.2.2)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* 5.145 43.600 12 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 5.145 49.078 11 OK
Concrete edge failure in direction y+** 19.178 43.987 44 OK

* highest loaded anchor **anchor group (relevant anchors)

4.1 Steel Strength (without lever arm)

V
VEd £ VRd,s = Rk,s EN 1992-4, Table 7.2
gM,s
0
VRk,s = k7 · VRk,s EN 1992-4, Eq. (7.35)

0
VRk,s [kN] k7 VRk,s [kN] gM,s VRd,s [kN] VEd [kN]
54.500 1.000 54.500 1.250 43.600 5.145

4.2 Pryout Strength

V
VEd £ VRd,cp = Rk,cp EN 1992-4, Table 7.2
gM,c,p
VRk,cp = k8 · NRk,c EN 1992-4, Eq. (7.39a)
0 A
NRk,c = NRk,c · c,N
0
· y s,N · y re,N · y ec1,N · y ec2,N · y M,N EN 1992-4, Eq. (7.1)
Ac,N
0 1,5
NRk,c = k1 · √fck · hef EN 1992-4, Eq. (7.2)
0
Ac,N = scr,N · scr,N EN 1992-4, Eq. (7.3)
c
y s,N = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.4)
ccr,N £
1
y ec1,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eV,1
scr,N )
1
y ec2,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eV,2
scr,N )
y M,N =1 EN 1992-4, Eq. (7.7)

2 0 2 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] k8 fc,cyl [N/mm ]
41,616 41,616 102.0 204.0 3.410 25.00

ec1,V [mm] y ec1,N ec2,V [mm] y ec2,N y s,N y re,N y M,N


0.0 1.000 0.0 1.000 1.000 1.000 1.000
0
k1 NRk,c [kN] gM,c,p VRd,cp [kN] VEd [kN]
7.700 21.589 1.500 49.078 5.145

Group anchor ID
2

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

5
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-GL O4 OC Date: 28/02/2024
Fastening point:

4.3 Concrete edge failure in direction y+

V
VEd £ VRd,c = Rk,c EN 1992-4, Table 7.2
gM,c
0 Ac,V
VRk,c = kT · VRk,c · 0
· y s,V · y h,V · y a,V · y ec,V · y re,V EN 1992-4, Eq. (7.40)
Ac,V
0 a b 1,5
VRk,c = k9 · dnom · lf · √fck · c1 EN 1992-4, Eq. (7.41)
0,5
a = 0.1 · () lf
c1
EN 1992-4, Eq. (7.42)
0,2

= 0.1 · (
c )
d nom
b EN 1992-4, Eq. (7.43)
1
0 2
Ac,V = 4.5 · c1 EN 1992-4, Eq. (7.44)
c2
y s,V = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.45)
1.5 · c1 £
0,5
y h,V = (1.5h· c ) 1
³ 1.00 EN 1992-4, Eq. (7.46)
1
y ec,V = £ 1.00 EN 1992-4, Eq. (7.47)
1+ ( 2 · eV
3 · c1 )
y a,V = √(cos a ) + (10.5 · sin a )
V
2
V
2 ³ 1.00 EN 1992-4, Eq. (7.48)

'
c1 = max (c1.5 , 1.5h , s 3 )
2,max 2,max
EN 1992-4, Eq. (7.50)

lf [mm] dnom [mm] k9 a b 2


fc,cyl [N/mm ]
68.0 16.00 1.700 0.045 0.054 25.00
' 2 0 2
c1 [mm] c1 [mm] Ac,V [mm ] Ac,V [mm ]
500.0 333.3 322,500 500,000

y s,V y h,V aV [°] y a,V ec,V [mm] y ec,V y re,V


1.000 1.414 1.61 1.000 10.2 0.980 1.000
0
VRk,c [kN] kT gM,c VRd,c [kN] VEd [kN]
73.784 1.0 1.500 43.987 19.178

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

6
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-GL O4 OC Date: 28/02/2024
Fastening point:

5 Combined tension and shear loads (EN 1992-4, Section 7.2.3)


Steel failure

bN bV a Utilization bN,V [%] Status


0.209 0.118 2.000 6 OK

a a
bN + bV £ 1.0

Concrete failure

bN bV a Utilization bN,V [%] Status


0.790 0.436 1.500 100 OK

a a
bN + bV £ 1.0

6 Displacements (highest loaded anchor)


Short term loading:

NSk = 8.408 [kN] dN = 0.5605 [mm]


VSk = 3.811 [kN] dV = 0.5391 [mm]
dNV = 0.7777 [mm]
Long term loading:

NSk = 8.408 [kN] dN = 1.5881 [mm]


VSk = 3.811 [kN] dV = 0.8087 [mm]
dNV = 1.7822 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

7
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-GL O4 OC Date: 28/02/2024
Fastening point:

7 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering
calculates the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions
explained above. The proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results
must be checked for agreement with the existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EN 1992-4, Annex A!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 6.1 of EN 1992-4! For larger diameters
of the clearance hole see section 6.2.2 of EN 1992-4!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• For the determination of the y re,v (concrete edge failure) the minimum concrete cover defined in the design settings is used as the concrete
cover of the edge reinforcement.
• Load transfer from supplementary reinforcement to the structural member shall be verified by the responsible structural engineer.
• With supplementary reinforcement and post-installed anchors, please ensure that in the jobsite the rebars are not drilled through.
• The characteristic bond resistances depend on the return period (service life in years): 50

Fastening meets the design criteria!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

8
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-GL O4 OC Date: 28/02/2024
Fastening point:

8 Installation data
2 2
Anchor plate, steel: S 235; E = 210,000.00 N/mm ; fyk = 235.00 N/mm Anchor type and diameter: HST3 M16 hef1
Profile: no profile Item number: 2114053 HST3 M16x115 15/-
Hole diameter in the fixture: df = 18.0 mm Maximum installation torque: 110 Nm
Plate thickness (input): 12.0 mm Hole diameter in the base material: 16.0 mm
Recommended plate thickness: not calculated Hole depth in the base material: 101.0 mm
Drilling method: Hammer drilled Minimum thickness of the base material: 123.0 mm
Cleaning: No cleaning of the drilled hole is required

Hilti HST3 stud anchor with 68 mm embedment, M16 hef1, Steel galvanized, installation per ETA 98/0001

8.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • No accessory required • Torque controlled cordless impact tool
• Properly sized drill bit • Torque wrench
• Hammer

y
175.0 175.0
30.0

3 4
175.0
290.0

x
175.0

1 2
30.0

30.0 290.0 30.0

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 -145.0 -145.0 500.0 790.0 500.0 790.0
2 145.0 -145.0 790.0 500.0 500.0 790.0
3 -145.0 145.0 500.0 790.0 790.0 500.0
4 145.0 145.0 790.0 500.0 790.0 500.0

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

9
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 10
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-GL O4 OC Date: 28/02/2024
Fastening point:

9 Drilling and installation

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

10
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 11
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-GL O4 OC Date: 28/02/2024
Fastening point:

10 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior
to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you
put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by
you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with
regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to
interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability
for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

11
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-GL O4C OC Date: 28/02/2024
Fastening point:

Specifier's comments:

1 Input data
Anchor type and diameter: HST3 M12 hef1
Return period (service life in years): 50
Item number: 2113979 HST3 M12x95 20/-
Effective embedment depth: hef,opti = 50.0 mm (hef,limit = 69.0 mm), hnom = 60.0 mm
Material:
Evaluation Service Report: ETA 98/0001
Issued I Valid: 20/07/2023 | -
Proof: Design Method EN 1992-4, Mechanical
Stand-off installation: eb = 0.0 mm (no stand-off); t = 12.0 mm

Anchor plate :
R lx x ly x t = 350.0 mm x 350.0 mm x 12.0 mm; (Recommended plate thickness: not calculated)

Profile: no profile
Base material: 2
cracked concrete, C25/30, fc,cyl = 25.00 N/mm ; h = 250.0 mm, User-defined partial material safety
factor gc = 1.500
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement
Reinforcement to control splitting acc. to EN 1992-4, 7.2.1.7 (2) b) 2) present

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

1
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-GL O4C OC Date: 28/02/2024
Fastening point:

1.1 Load combination


Case Description Forces [kN] / Moments [kNm] Seismic Fire Max. Util. Anchor [%]
1 Combination 1 N = -5.130; Vx = 0.770; Vy = 0.240; no no 37
Mx = -1.370; My = 2.450; Mz = 0.010;

2 Load case/Resulting anchor forces y


3 4

Anchor reactions [kN]


Tension force: (+Tension, -Compression) Compression
Anchor Tension force Shear force Shear force x Shear force y
1 3.316 0.208 0.201 0.051
2 0.423 0.213 0.201 0.069 x
3 2.336 0.191 0.184 0.051
4 0.000 0.196 0.184 0.069

max. concrete compressive strain: 0.08 [‰]


max. concrete compressive stress: 2.47 [N/mm ]
2

resulting tension force in (x/y)=(0.0/0.0): 0.000 [kN] 1 2


resulting compression force in (x/y)=(326.0/279.1): 11.204 [kN]

Anchor forces are calculated based on the assumption of a rigid anchor plate.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

2
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-GL O4C OC Date: 28/02/2024
Fastening point:

3 Tension load (EN 1992-4, Section 7.2.1)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* 3.316 32.214 11 OK
Pullout Strength* 3.316 9.075 37 OK
Concrete Breakout Failure** 3.316 9.075 37 OK
Splitting failure** N/A N/A N/A N/A

* highest loaded anchor **anchor group (anchors in tension)

3.1 Steel Strength

N
NEd £ NRd,s = Rk,s EN 1992-4, Table 7.1
gM,s

NRk,s [kN] gM,s NRd,s [kN] NEd [kN]


45.100 1.400 32.214 3.316

3.2 Pullout Strength

y c · NRk,p
NEd £ NRd,p = EN 1992-4, Table 7.1
gM,p

NRk,p [kN] yc g M,p NRd,p [kN] NEd [kN]


12.175 1.118 1.500 9.075 3.316

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

3
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-GL O4C OC Date: 28/02/2024
Fastening point:

3.3 Concrete Breakout Failure

N
NEd £ NRd,c = Rk,c EN 1992-4, Table 7.1
gM,c
0 Ac,N
NRk,c = NRk,c · 0
· y s,N · y re,N · y ec1,N · y ec2,N · y M,N EN 1992-4, Eq. (7.1)
Ac,N
0 1,5
NRk,c = k1 · √fck · hef EN 1992-4, Eq. (7.2)
0
Ac,N = scr,N · scr,N EN 1992-4, Eq. (7.3)
c
y s,N = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.4)
ccr,N £
1
y ec1,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eN,1
scr,N )
1
y ec2,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eN,2
scr,N )
y M,N =1 EN 1992-4, Eq. (7.7)

2 0 2 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] fc,cyl [N/mm ]
22,500 22,500 75.0 150.0 25.00

ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N


0.0 1.000 0.0 1.000 1.000 1.000
0
z [mm] y M,N k1 NRk,c [kN] gM,c NRd,c [kN] NEd [kN]
308.2 1.000 7.700 13.612 1.500 9.075 3.316

Group anchor ID
1

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

4
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-GL O4C OC Date: 28/02/2024
Fastening point:

4 Shear load (EN 1992-4, Section 7.2.2)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* 0.213 27.200 1 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 0.213 25.227 1 OK
Concrete edge failure in direction x+** 0.782 42.312 2 OK

* highest loaded anchor **anchor group (relevant anchors)

4.1 Steel Strength (without lever arm)

V
VEd £ VRd,s = Rk,s EN 1992-4, Table 7.2
gM,s
0
VRk,s = k7 · VRk,s EN 1992-4, Eq. (7.35)

0
VRk,s [kN] k7 VRk,s [kN] gM,s VRd,s [kN] VEd [kN]
34.000 1.000 34.000 1.250 27.200 0.213

4.2 Pryout Strength

V
VEd £ VRd,cp = Rk,cp EN 1992-4, Table 7.2
gM,c,p
VRk,cp = k8 · NRk,c EN 1992-4, Eq. (7.39a)
0 A
NRk,c = NRk,c · c,N
0
· y s,N · y re,N · y ec1,N · y ec2,N · y M,N EN 1992-4, Eq. (7.1)
Ac,N
0 1,5
NRk,c = k1 · √fck · hef EN 1992-4, Eq. (7.2)
0
Ac,N = scr,N · scr,N EN 1992-4, Eq. (7.3)
c
y s,N = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.4)
ccr,N £
1
y ec1,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eV,1
scr,N )
1
y ec2,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eV,2
scr,N )
y M,N =1 EN 1992-4, Eq. (7.7)

2 0 2 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] k8 fc,cyl [N/mm ]
22,500 22,500 75.0 150.0 2.780 25.00

ec1,V [mm] y ec1,N ec2,V [mm] y ec2,N y s,N y re,N y M,N


0.0 1.000 0.0 1.000 1.000 1.000 1.000
0
k1 NRk,c [kN] gM,c,p VRd,cp [kN] VEd [kN]
7.700 13.612 1.500 25.227 0.213

Group anchor ID
2

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

5
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-GL O4C OC Date: 28/02/2024
Fastening point:

4.3 Concrete edge failure in direction x+

V
VEd £ VRd,c = Rk,c EN 1992-4, Table 7.2
gM,c
0 Ac,V
VRk,c = kT · VRk,c · 0
· y s,V · y h,V · y a,V · y ec,V · y re,V EN 1992-4, Eq. (7.40)
Ac,V
0 a b 1,5
VRk,c = k9 · dnom · lf · √fck · c1 EN 1992-4, Eq. (7.41)
0,5
a = 0.1 · () lf
c1
EN 1992-4, Eq. (7.42)
0,2

= 0.1 · (
c )
d nom
b EN 1992-4, Eq. (7.43)
1
0 2
Ac,V = 4.5 · c1 EN 1992-4, Eq. (7.44)
c2
y s,V = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.45)
1.5 · c1 £
0,5
y h,V = (1.5h· c ) 1
³ 1.00 EN 1992-4, Eq. (7.46)
1
y ec,V = £ 1.00 EN 1992-4, Eq. (7.47)
1+ ( 2 · eV
3 · c1 )
y a,V = √(cos a ) + (10.5 · sin a )
V
2
V
2 ³ 1.00 EN 1992-4, Eq. (7.48)

'
c1 = max (c1.5 , 1.5h , s 3 )
2,max 2,max
EN 1992-4, Eq. (7.50)

lf [mm] dnom [mm] k9 a b 2


fc,cyl [N/mm ]
50.0 12.00 1.700 0.039 0.051 25.00
' 2 0 2
c1 [mm] c1 [mm] Ac,V [mm ] Ac,V [mm ]
500.0 333.3 322,500 500,000

y s,V y h,V aV [°] y a,V ec,V [mm] y ec,V y re,V


1.000 1.414 10.11 1.012 6.4 0.987 1.000
0
VRk,c [kN] kT gM,c VRd,c [kN] VEd [kN]
69.650 1.0 1.500 42.312 0.782

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

6
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-GL O4C OC Date: 28/02/2024
Fastening point:

5 Combined tension and shear loads (EN 1992-4, Section 7.2.3)


Steel failure

bN bV a Utilization bN,V [%] Status


0.103 0.008 2.000 2 OK

a a
bN + bV £ 1.0

Concrete failure

bN bV a Utilization bN,V [%] Status


0.365 0.018 1.500 23 OK

a a
bN + bV £ 1.0

6 Displacements (highest loaded anchor)


Short term loading:

NSk = 2.456 [kN] dN = 0.1611 [mm]


VSk = 0.154 [kN] dV = 0.0246 [mm]
dNV = 0.1629 [mm]
Long term loading:

NSk = 2.456 [kN] dN = 0.6442 [mm]


VSk = 0.154 [kN] dV = 0.0373 [mm]
dNV = 0.6453 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

7
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-GL O4C OC Date: 28/02/2024
Fastening point:

7 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering
calculates the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions
explained above. The proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results
must be checked for agreement with the existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EN 1992-4, Annex A!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 6.1 of EN 1992-4! For larger diameters
of the clearance hole see section 6.2.2 of EN 1992-4!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• For the determination of the y re,v (concrete edge failure) the minimum concrete cover defined in the design settings is used as the concrete
cover of the edge reinforcement.
• Load transfer from supplementary reinforcement to the structural member shall be verified by the responsible structural engineer.
• With supplementary reinforcement and post-installed anchors, please ensure that in the jobsite the rebars are not drilled through.
• The characteristic bond resistances depend on the return period (service life in years): 50

Fastening meets the design criteria!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

8
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-GL O4C OC Date: 28/02/2024
Fastening point:

8 Installation data
2 2
Anchor plate, steel: S 235; E = 210,000.00 N/mm ; fyk = 235.00 N/mm Anchor type and diameter: HST3 M12 hef1
Profile: no profile Item number: 2113979 HST3 M12x95 20/-
Hole diameter in the fixture: df = 14.0 mm Maximum installation torque: 60 Nm
Plate thickness (input): 12.0 mm Hole diameter in the base material: 12.0 mm
Recommended plate thickness: not calculated Hole depth in the base material: 80.0 mm
Drilling method: Hammer drilled Minimum thickness of the base material: 100.0 mm
Cleaning: No cleaning of the drilled hole is required

Hilti HST3 stud anchor with 50 mm embedment, M12 hef1, Steel galvanized, installation per ETA 98/0001

8.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • No accessory required • Torque controlled cordless impact tool
• Properly sized drill bit • Torque wrench
• Hammer

y
175.0 175.0
30.0

3 4
175.0
290.0

x
175.0

1 2
30.0

30.0 290.0 30.0

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 -145.0 -145.0 500.0 790.0 500.0 790.0
2 145.0 -145.0 790.0 500.0 500.0 790.0
3 -145.0 145.0 500.0 790.0 790.0 500.0
4 145.0 145.0 790.0 500.0 790.0 500.0

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

9
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 10
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-GL O4C OC Date: 28/02/2024
Fastening point:

9 Drilling and installation

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

10
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 11
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-GL O4C OC Date: 28/02/2024
Fastening point:

10 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior
to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you
put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by
you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with
regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to
interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability
for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

11
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-O2B Date: 28/02/2024
Fastening point:

Specifier's comments:

1 Input data
Anchor type and diameter: HST3 M12 hef1
Return period (service life in years): 50
Item number: 2113978 HST3 M12x85 10/-
Effective embedment depth: hef,opti = 50.0 mm (hef,limit = 69.0 mm), hnom = 60.0 mm
Material:
Evaluation Service Report: ETA 98/0001
Issued I Valid: 20/07/2023 | -
Proof: Design Method EN 1992-4, Mechanical
Stand-off installation: eb = 0.0 mm (no stand-off); t = 8.0 mm

Anchor plate :
R lx x ly x t = 100.0 mm x 200.0 mm x 8.0 mm; (Recommended plate thickness: not calculated)

Profile: no profile
Base material: 2
cracked concrete, C25/30, fc,cyl = 25.00 N/mm ; h = 250.0 mm, User-defined partial material safety
factor gc = 1.500
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement
Reinforcement to control splitting acc. to EN 1992-4, 7.2.1.7 (2) b) 2) present

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

1
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-O2B Date: 28/02/2024
Fastening point:

1.1 Load combination


Case Description Forces [kN] / Moments [kNm] Seismic Fire Max. Util. Anchor [%]
1 Combination 1 N = -0.610; Vx = 0.520; Vy = 0.710; no no 64
Mx = -0.970; My = 0.060; Mz = 0.000;

2 Load case/Resulting anchor forces y

Compression
2
Anchor reactions [kN]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
1 5.793 0.440 0.260 0.355
2 0.000 0.440 0.260 0.355 x

max. concrete compressive strain: 0.16 [‰]


max. concrete compressive stress: 4.76 [N/mm ]
2

resulting tension force in (x/y)=(0.0/0.0): 0.000 [kN]


resulting compression force in (x/y)=(59.4/188.2): 6.403 [kN] 1

Anchor forces are calculated based on the assumption of a rigid anchor plate.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

2
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-O2B Date: 28/02/2024
Fastening point:

3 Tension load (EN 1992-4, Section 7.2.1)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* 5.793 32.214 18 OK
Pullout Strength* 5.793 9.075 64 OK
Concrete Breakout Failure** 5.793 9.075 64 OK
Splitting failure** N/A N/A N/A N/A

* highest loaded anchor **anchor group (anchors in tension)

3.1 Steel Strength

N
NEd £ NRd,s = Rk,s EN 1992-4, Table 7.1
gM,s

NRk,s [kN] gM,s NRd,s [kN] NEd [kN]


45.100 1.400 32.214 5.793

3.2 Pullout Strength

y c · NRk,p
NEd £ NRd,p = EN 1992-4, Table 7.1
gM,p

NRk,p [kN] yc g M,p NRd,p [kN] NEd [kN]


12.175 1.118 1.500 9.075 5.793

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

3
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-O2B Date: 28/02/2024
Fastening point:

3.3 Concrete Breakout Failure

N
NEd £ NRd,c = Rk,c EN 1992-4, Table 7.1
gM,c
0 Ac,N
NRk,c = NRk,c · 0
· y s,N · y re,N · y ec1,N · y ec2,N · y M,N EN 1992-4, Eq. (7.1)
Ac,N
0 1,5
NRk,c = k1 · √fck · hef EN 1992-4, Eq. (7.2)
0
Ac,N = scr,N · scr,N EN 1992-4, Eq. (7.3)
c
y s,N = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.4)
ccr,N £
1
y ec1,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eN,1
scr,N )
1
y ec2,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eN,2
scr,N )
y M,N =1 EN 1992-4, Eq. (7.7)

2 0 2 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] fc,cyl [N/mm ]
22,500 22,500 75.0 150.0 25.00

ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N


0.0 1.000 0.0 1.000 1.000 1.000
0
z [mm] y M,N k1 NRk,c [kN] gM,c NRd,c [kN] NEd [kN]
158.4 1.000 7.700 13.612 1.500 9.075 5.793

Group anchor ID
1

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

4
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-O2B Date: 28/02/2024
Fastening point:

4 Shear load (EN 1992-4, Section 7.2.2)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* 0.440 27.200 2 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 0.880 48.773 2 OK
Concrete edge failure in direction y+** 0.756 34.394 3 OK

* highest loaded anchor **anchor group (relevant anchors)

4.1 Steel Strength (without lever arm)

V
VEd £ VRd,s = Rk,s EN 1992-4, Table 7.2
gM,s
0
VRk,s = k7 · VRk,s EN 1992-4, Eq. (7.35)

0
VRk,s [kN] k7 VRk,s [kN] gM,s VRd,s [kN] VEd [kN]
34.000 1.000 34.000 1.250 27.200 0.440

4.2 Pryout Strength

V
VEd £ VRd,cp = Rk,cp EN 1992-4, Table 7.2
gM,c,p
VRk,cp = k8 · NRk,c EN 1992-4, Eq. (7.39a)
0 A
NRk,c = NRk,c · c,N
0
· y s,N · y re,N · y ec1,N · y ec2,N · y M,N EN 1992-4, Eq. (7.1)
Ac,N
0 1,5
NRk,c = k1 · √fck · hef EN 1992-4, Eq. (7.2)
0
Ac,N = scr,N · scr,N EN 1992-4, Eq. (7.3)
c
y s,N = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.4)
ccr,N £
1
y ec1,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eV,1
scr,N )
1
y ec2,N = £ 1.00 EN 1992-4, Eq. (7.6)
1+ ( 2 · eV,2
scr,N )
y M,N =1 EN 1992-4, Eq. (7.7)

2 0 2 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] k8 fc,cyl [N/mm ]
43,500 22,500 75.0 150.0 2.780 25.00

ec1,V [mm] y ec1,N ec2,V [mm] y ec2,N y s,N y re,N y M,N


0.0 1.000 0.0 1.000 1.000 1.000 1.000
0
k1 NRk,c [kN] gM,c,p VRd,cp [kN] VEd [kN]
7.700 13.612 1.500 48.773 0.880

Group anchor ID
1, 2

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

5
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-O2B Date: 28/02/2024
Fastening point:

4.3 Concrete edge failure in direction y+

V
VEd £ VRd,c = Rk,c EN 1992-4, Table 7.2
gM,c
0 Ac,V
VRk,c = kT · VRk,c · 0
· y s,V · y h,V · y a,V · y ec,V · y re,V EN 1992-4, Eq. (7.40)
Ac,V
0 a b 1,5
VRk,c = k9 · dnom · lf · √fck · c1 EN 1992-4, Eq. (7.41)
0,5
a = 0.1 · () lf
c1
EN 1992-4, Eq. (7.42)
0,2

= 0.1 · (
c )
d nom
b EN 1992-4, Eq. (7.43)
1
0 2
Ac,V = 4.5 · c1 EN 1992-4, Eq. (7.44)
c2
y s,V = 0.7 + 0.3 · 1.00 EN 1992-4, Eq. (7.45)
1.5 · c1 £
0,5
y h,V = (1.5h· c ) 1
³ 1.00 EN 1992-4, Eq. (7.46)
1
y ec,V = £ 1.00 EN 1992-4, Eq. (7.47)
1+ ( 2 · eV
3 · c1 )
y a,V = √(cos a ) + (10.5 · sin a )
V
2
V
2 ³ 1.00 EN 1992-4, Eq. (7.48)

'
c1 = max (c1.5 , 1.5h , s 3 )
2,max 2,max
EN 1992-4, Eq. (7.50)

lf [mm] dnom [mm] k9 a b 2


fc,cyl [N/mm ]
50.0 12.00 1.700 0.039 0.051 25.00
' 2 0 2
c1 [mm] c1 [mm] Ac,V [mm ] Ac,V [mm ]
500.0 333.3 250,000 500,000

y s,V y h,V aV [°] y a,V ec,V [mm] y ec,V y re,V


1.000 1.414 20.11 1.048 0.0 1.000 1.000
0
VRk,c [kN] kT gM,c VRd,c [kN] VEd [kN]
69.650 1.0 1.500 34.394 0.756

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

6
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-O2B Date: 28/02/2024
Fastening point:

5 Combined tension and shear loads (EN 1992-4, Section 7.2.3)


Steel failure

bN bV a Utilization bN,V [%] Status


0.180 0.016 2.000 4 OK

a a
bN + bV £ 1.0

Concrete failure

bN bV a Utilization bN,V [%] Status


0.638 0.022 1.500 52 OK

a a
bN + bV £ 1.0

6 Displacements (highest loaded anchor)


Short term loading:

NSk = 4.291 [kN] dN = 0.2814 [mm]


VSk = 0.326 [kN] dV = 0.0521 [mm]
dNV = 0.2862 [mm]
Long term loading:

NSk = 4.291 [kN] dN = 1.1256 [mm]


VSk = 0.326 [kN] dV = 0.0790 [mm]
dNV = 1.1284 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

7
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-O2B Date: 28/02/2024
Fastening point:

7 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering
calculates the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions
explained above. The proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results
must be checked for agreement with the existing conditions and for plausibility!
• Checking the transfer of loads into the base material is required in accordance with EN 1992-4, Annex A!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 6.1 of EN 1992-4! For larger diameters
of the clearance hole see section 6.2.2 of EN 1992-4!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• For the determination of the y re,v (concrete edge failure) the minimum concrete cover defined in the design settings is used as the concrete
cover of the edge reinforcement.
• Load transfer from supplementary reinforcement to the structural member shall be verified by the responsible structural engineer.
• With supplementary reinforcement and post-installed anchors, please ensure that in the jobsite the rebars are not drilled through.
• The characteristic bond resistances depend on the return period (service life in years): 50

Fastening meets the design criteria!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

8
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-O2B Date: 28/02/2024
Fastening point:

8 Installation data
2 2
Anchor plate, steel: S 235; E = 210,000.00 N/mm ; fyk = 235.00 N/mm Anchor type and diameter: HST3 M12 hef1
Profile: no profile Item number: 2113978 HST3 M12x85 10/-
Hole diameter in the fixture: df = 14.0 mm Maximum installation torque: 60 Nm
Plate thickness (input): 8.0 mm Hole diameter in the base material: 12.0 mm
Recommended plate thickness: not calculated Hole depth in the base material: 80.0 mm
Drilling method: Hammer drilled Minimum thickness of the base material: 100.0 mm
Cleaning: No cleaning of the drilled hole is required

Hilti HST3 stud anchor with 50 mm embedment, M12 hef1, Steel galvanized, installation per ETA 98/0001

8.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • No accessory required • Torque controlled cordless impact tool
• Properly sized drill bit • Torque wrench
• Hammer

y
50.0 50.0
30.0

2
100.0
140.0

x
100.0

1
30.0

50.0 50.0

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 0.0 -70.0 500.0 500.0 500.0 640.0
2 0.0 70.0 500.0 500.0 640.0 500.0

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

9
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 10
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-O2B Date: 28/02/2024
Fastening point:

9 Drilling and installation

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

10
Hilti PROFIS Engineering 3.0.91

www.hilti.de
Company: Page: 11
Address: Specifier:
Phone I Fax: | E-Mail:
Design: MT-B-O2B Date: 28/02/2024
Fastening point:

10 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior
to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you
put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by
you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with
regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to
interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability
for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

11

You might also like