Professional Documents
Culture Documents
PL PM5000 PM51xx 53xx Reg List 140616 en
PL PM5000 PM51xx 53xx Reg List 140616 en
PM5310
PM5330/31
PM5320
PM5340/41
Size Unresolved Full IEC Tag
Category Description Register Units Data Type Access Range Default NV User Notes Developer Notes Tag Software Tag Subsystem ION Tag SMS Topic ID IEC Tag name Publish
(INT16) Issues (may not be 100% accurate)
System Setup & Status Y Y Y Y Y 1 --- --- --- --- --- --- S_SYSTEM Y
Miscellaneous Control & Status Y Y Y Y Y 1 --- --- --- --- --- --- S_SYSTEM
Y Y Y Y Y 1 --- 1 INT16U R 0x1234 0x1234 Y If value is anything other than 0x1234, then meter will initialize R_NVRAM_INIT
NVRAM Initialization Signature all register values to default. S_SYSTEM
Y Y Y Y Y 2 --- 1 INT16U R 100 Y This is the maximum value of the watchdog countdown timer. Comes from design R_WATCHDOG_MAX
Watchdog Timer Constant S_SYSTEM
Its value may vary from one design to another.
Y Y Y Y Y 3 --- 1 INT16U RW 0 – Watchdog Timer Constant 32767 Y Record of the minimum value of the watchdog countdown timer The minimum value is 0 at which point the meter will reset. R_WATCHDOG_MIN
Minimum Watchdog Timer S_SYSTEM
The maximum value is the Watchdog Timer Constant.
Reserved 4 --- 26 INT16U R --- --- Y R_RESERVED_4 S_SYSTEM
Product & Features Y Y Y Y Y 30 --- --- --- --- --- --- S_SYSTEM Y
Meter Name Y Y Y Y Y 30 --- 20 UTF8 RWC --- PM5xxx = "Power Meter" Y R_METER_NAME Y
S_SYSTEM
Manufacturer Y Y Y Y Y 70 --- 20 UTF8 RWC --- "Schneider Electric" Y R_METER_MANUFACTURER S_SYSTEM Y
Product ID Number Y Y Y Y Y 90 --- 1 INT16U RWC PM5000 = 15240 Y R_PRODUCT_ID Y
PM5010 = 15241 PM5350 = 15244
PM5200 = 15242
PM5250 = 15243 PM5110 = 15270 S_SYSTEM
PM5350 = 15244 PM5111 = 15271
15245 - 15254 PM5310 = 15272
Hardware Detected Y Y Y Y Y 91 --- 4 BITMAP R 0x0000 – 0xFFFF N PM5330 = 15273 Need to coordinate with software R_HARDWARE_DETECTED
PM5000 = 0x0001 Bitmap indicating base hardware options detected S_SYSTEM
PM5010 = 0x0019 Bit 01 = HMI
Supported Features Y Y Y Y Y 95 --- 4 BITMAP R 0x0000 – 0xFFFF 0 N Bitmap indicating features supported Need to coordinate with software R_SUPPORTED_FEATURES
PM5110 = 0x161D Bit 01 = 1 Cycle Metering S_SYSTEM
PM5111 = 0x161D Bit 02 = 5/6 Cycle Metering
Reserved 99 --- 21 INT16U R PM5310---
= 0x169D --- N Bit 03 = 50/60 Cycle Metering R_RESERVED_99 S_SYSTEM
Manufacturing Data Y Y Y Y Y 120 --- --- --- --- --- --- S_SYSTEM Y
Meter Y Y Y Y Y 120 --- --- --- --- --- --- S_SYSTEM Y
Reserved 120 --- 9 INT16U R 0 N Reserved for future expansion of Serial Number R_RESERVED_120 S_SYSTEM
Y Y Y Y Y 129 1 INT16U R --- 0 Y Manufacturing Unit ID R_METER_MFG_UNIT_ID Y
Manufacturing Unit Id (To be prefixed in Serial Number S_SYSTEM
While Displaying)
Serial Number Y Y Y Y Y 130 --- 2 INT32U R 0 Y coordinate with production test R_METER_SERIAL_NUMBER S_SYSTEM Y
Date of Manufacture Y Y Y Y Y 132 --- 4 DATETIME R --- 0 Y R_METER_DATE_MFG S_SYSTEM Y
Hardware Revision Y Y Y Y Y 136 --- 5 UTF8 R --- 0 Y R_METER_HARDWARE_REV S_SYSTEM Y
Production History 01 Y Y Y Y Y 141 --- 1 INT16U R --- 0 Y This is encoded into a packed binary format R_METER_PROD_HIST_01 S_SYSTEM
Production History 02 Y Y Y Y Y 142 --- 1 INT16U R --- 0 Y R_METER_PROD_HIST_02 S_SYSTEM
Production History 03 Y Y Y Y Y 143 --- 1 INT16U R --- 0 Y R_METER_PROD_HIST_03 S_SYSTEM
Production History 04 Y Y Y Y Y 144 --- 1 INT16U R --- 0 Y R_METER_PROD_HIST_04 S_SYSTEM
Production History 05 Y Y Y Y Y 145 --- 1 INT16U R --- 0 Y R_METER_PROD_HIST_05 S_SYSTEM
Production History 06 Y Y Y Y Y 146 --- 1 INT16U R --- 0 Y R_METER_PROD_HIST_06 S_SYSTEM
Production History 07 Y Y Y Y Y 147 --- 1 INT16U R --- 0 Y R_METER_PROD_HIST_07 S_SYSTEM
Production History 08 Y Y Y Y Y 148 --- 1 INT16U R --- 0 Y R_METER_PROD_HIST_08 S_SYSTEM
Production History 09 Y Y Y Y Y 149 --- 1 INT16U R --- 0 Y R_METER_PROD_HIST_09 S_SYSTEM
Production History 10 Y Y Y Y Y 150 --- 1 INT16U R --- 0 Y R_METER_PROD_HIST_10 S_SYSTEM
Production History 11 Y Y Y Y Y 151 --- 1 INT16U R --- 0 Y R_METER_PROD_HIST_11 S_SYSTEM
Production History 12 Y Y Y Y Y 152 --- 1 INT16U R --- 0 Y R_METER_PROD_HIST_12 S_SYSTEM
Production History 13 Y Y Y Y Y 153 --- 1 INT16U R --- 0 Y R_METER_PROD_HIST_13 S_SYSTEM
Production History 14 Y Y Y Y Y 154 --- 1 INT16U R --- 0 Y R_METER_PROD_HIST_14 S_SYSTEM
Production History 15 Y Y Y Y Y 155 --- 1 INT16U R --- 0 Y R_METER_PROD_HIST_15 S_SYSTEM
Production History 16 Y Y Y Y Y 156 --- 1 INT16U R --- 0 Y R_METER_PROD_HIST_16 S_SYSTEM
Production History 17 Y Y Y Y Y 157 --- 1 INT16U R --- 0 Y R_METER_PROD_HIST_17 S_SYSTEM
Production History 18 Y Y Y Y Y 158 --- 1 INT16U R --- 0 Y R_METER_PROD_HIST_18 S_SYSTEM
Production History 19 Y Y Y Y Y 159 --- 1 INT16U R --- 0 Y R_METER_PROD_HIST_19 S_SYSTEM
Production History 20 Y Y Y Y Y 160 --- 1 INT16U R --- 0 Y R_METER_PROD_HIST_20 S_SYSTEM
Checksum Y Y Y Y Y 161 --- 1 INT16U R --- 0 Y R_METER_PROD_HIST_CHECKSUM S_SYSTEM
Firmware Versions Y Y Y Y Y 1637 --- --- --- --- --- --- S_SYSTEM Y
Operating System Y Y Y Y Y 1637 --- --- --- --- --- --- S_SYSTEM Y
Present Firmware Version (DLF Format) X.Y.T Y Y Y Y Y 1637 --- 1 INT16U R 0 – 32,767 0 Y The firmware version takes the following form: XXYYT R_VERSION_OS_PRES S_SYSTEM Y
X – Major Y Y Y Y Y 1638 --- 1 INT16U R 00 – 99 0 Y R_VERSION_OS_PRES_MAJOR S_SYSTEM
Y – Minor Y Y Y Y Y 1639 --- 1 INT16U R 0000 – 9999 0 Y R_VERSION_OS_PRES_MINOR S_SYSTEM
Z – Quality Y Y Y Y Y 1640 --- 1 INT16U R 0000 – 9999 0 Y R_VERSION_OS_PRES_QUALITY S_SYSTEM
T – Internal evolutions Y Y Y Y Y 1641 --- 1 INT16U R 0000 – 9999 0 Y R_VERSION_OS_PRES_INTERNAL S_SYSTEM
Previous Firmware Version (DLF Format) X.Y.T Y Y Y Y Y 1642 --- 1 INT16U R 0 – 32,767 0 Y The firmware version takes the following form: XXYYT R_VERSION_OS_PREV S_SYSTEM Y
X – Major Y Y Y Y Y 1643 --- 1 INT16U R 00 – 99 0 Y R_VERSION_OS_PREV_MAJOR S_SYSTEM
Y – Minor Y Y Y Y Y 1644 --- 1 INT16U R 0000 – 9999 0 Y R_VERSION_OS_PREV_MINOR S_SYSTEM
Z – Quality Y Y Y Y Y 1645 --- 1 INT16U R 0000 – 9999 0 Y R_VERSION_OS_PREV_QUALITY S_SYSTEM
T – Internal evolutions Y Y Y Y Y 1646 --- 1 INT16U R 0000 – 9999 0 Y R_VERSION_OS_PREV_INTERNAL S_SYSTEM
Date/Time of Last Firmware Download Y Y Y Y Y 1647 --- 4 DATETIME R --- N/A Y R_VERSION_OS_PRES_DT S_SYSTEM Y
Reset Y Y Y Y Y 1669 --- --- --- --- --- --- S_SYSTEM Y
Present Firmware Version (DLF Format) X.Y.T Y Y Y Y Y 1669 --- 1 INT16U R 0 – 32,767 0 Y The firmware version takes the following form: XXYYT R_VERSION_RS_PRES S_SYSTEM Y
X – Major Y Y Y Y Y 1670 --- 1 INT16U R 00 – 99 0 Y R_VERSION_RS_PRES_MAJOR S_SYSTEM
Y – Minor Y Y Y Y Y 1671 --- 1 INT16U R 0000 – 9999 0 Y R_VERSION_RS_PRES_MINOR S_SYSTEM
Z – Quality Y Y Y Y Y 1672 --- 1 INT16U R 0000 – 9999 0 Y R_VERSION_RS_PRES_QUALITY S_SYSTEM
T – Internal evolutions Y Y Y Y Y 1673 --- 1 INT16U R 0000 – 9999 0 Y R_VERSION_RS_PRES_INTERNAL S_SYSTEM
Previous Firmware Version (DLF Format) X.Y.T Y Y Y Y Y 1674 --- 1 INT16U R 0 – 32,767 0 Y Not supported in PM5xxx. Space reserved to preserve The firmware version takes the following form: XXYYT R_VERSION_RS_PREV
S_SYSTEM
NVRAM locations.
X – Major Y Y Y Y Y 1675 --- 1 INT16U R 00 – 99 0 Y Not supported in PM5xxx. Space reserved to preserve R_VERSION_RS_PREV_MAJOR
S_SYSTEM
NVRAM locations.
Y – Minor Y Y Y Y Y 1676 --- 1 INT16U R 0000 – 9999 0 Y Not supported in PM5xxx. Space reserved to preserve R_VERSION_RS_PREV_MINOR
S_SYSTEM
NVRAM locations.
Z – Quality Y Y Y Y Y 1677 --- 1 INT16U R 0000 – 9999 0 Y Not supported in PM5xxx. Space reserved to preserve R_VERSION_RS_PREV_QUALITY
S_SYSTEM
NVRAM locations.
T – Internal evolutions Y Y Y Y Y 1678 --- 1 INT16U R 0000 – 9999 0 Y Not supported in PM5xxx. Space reserved to preserve R_VERSION_RS_PREV_INTERNAL
S_SYSTEM
NVRAM locations.
Date/Time of Last Firmware Download Y Y Y Y Y 1679 --- 4 DATETIME R --- N/A Y Not supported in PM5xxx. Space reserved to preserve R_VERSION_RS_PRES_DT
S_SYSTEM
NVRAM locations.
Language Y Y Y Y Y 1701 --- --- --- --- --- --- S_SYSTEM Y
Present Firmware Version (DLF Format) X.Y.T Y Y Y Y Y 1701 --- 1 INT16U R 0 – 32,767 0 Y The firmware version takes the following form: XXYYT R_VERSION_LL_PRES S_SYSTEM Y
X – Major Y Y Y Y Y 1702 --- 1 INT16U R 00 – 99 0 Y R_VERSION_LL_PRES_MAJOR S_SYSTEM
Y – Minor Y Y Y Y Y 1703 --- 1 INT16U R 0000 – 9999 0 Y R_VERSION_LL_PRES_MINOR S_SYSTEM
Z – Quality Y Y Y Y Y 1704 --- 1 INT16U R 0000 – 9999 0 Y R_VERSION_LL_PRES_QUALITY S_SYSTEM
T – Internal evolutions Y Y Y Y Y 1705 --- 1 INT16U R 0000 – 9999 0 Y R_VERSION_LL_PRES_INTERNAL S_SYSTEM
Previous Firmware Version (DLF Format) X.Y.T Y Y Y Y Y 1706 --- 1 INT16U R 0 – 32,767 0 Y The firmware version takes the following form: XXYYT R_VERSION_LL_PREV S_SYSTEM
X – Major Y Y Y Y Y 1707 --- 1 INT16U R 00 – 99 0 Y R_VERSION_LL_PREV_MAJOR S_SYSTEM
Y – Minor Y Y Y Y Y 1708 --- 1 INT16U R 0000 – 9999 0 Y R_VERSION_LL_PREV_MINOR S_SYSTEM
Z – Quality Y Y Y Y Y 1709 --- 1 INT16U R 0000 – 9999 0 Y R_VERSION_LL_PREV_QUALITY S_SYSTEM
T – Internal evolutions Y Y Y Y Y 1710 --- 1 INT16U R 0000 – 9999 0 Y R_VERSION_LL_PREV_INTERNAL S_SYSTEM
Date/Time of Last Firmware Download Y Y Y Y Y 1711 --- 4 DATETIME R --- N/A Y R_VERSION_LL_PRES_DT S_SYSTEM
Checksum Y Y Y Y Y 1715 --- 1 INT16U R --- 0 Y R_VERSION_LL_PRES_CHECKSUM S_SYSTEM
Bridge Code Version Y Y Y Y Y 1716 --- 1 INT16U R --- 0 Y R_VERSION_LL_PRES_BRIDGE S_SYSTEM
Firmware Download DLF Interface Y Y Y Y Y 1747 --- --- --- --- --- --- These registers are used by DLF-3000 for firmware downloads.
S_SYSTEM
Download – CRC of Last FW Download Y Y Y Y Y 1747 --- 1 INT16U R --- 0 N R_DLF_CRC S_SYSTEM
Download – Flash Write Failure Y Y Y Y Y 1748 --- 1 INT16U R --- 0 N R_DLF_FLASH_FAIL S_SYSTEM
Download – % Complete Y Y Y Y Y 1749 --- 1 INT16U R 0 – 100 0 N R_DLF_PERCENT S_SYSTEM
Reserved For Download Software Use Y Y Y Y Y 1750 --- 1 INT16U RW --- 0 N R_DLF_INTERFACE S_SYSTEM
Download Mode Y Y Y Y Y 1751 --- --- --- --- --- --- S_SYSTEM
Meter Resets Y Y Y Y Y 1822 --- --- --- --- --- --- S_SYSTEM Y
Last Unit Restart DateTime Y Y Y Y Y 1824 --- 4 DATETIME R --- N/A Y R_LAST_RESET_DT S_SYSTEM Y
Number of Metering System Restarts Y Y Y Y Y 1828 --- 1 INT16U R --- 0 Y R_NUMBER_RESTARTS S_SYSTEM Y
Number of Control Power Failures Y Y Y Y Y 1829 --- 1 INT16U R --- 0 Y R_CONTROL_POWER_FAIL_COUNT S_SYSTEM Y
Date/Time of Last Control Power Failure Y Y Y Y Y 1830 --- 4 DATETIME R --- N/A Y R_CONTROL_POWER_FAIL_DT S_SYSTEM Y
Duration of Last Control Power Failure Y Y Y Y Y 1834 seconds 2 INT32U R --- 0 Y R_CONTROL_POWER_FAIL_DUR S_SYSTEM Y
Y Y Y Y Y 1836 --- 1 INT16U R 0–2 0 Y 0 = Unknown R_LAST_RESET_CAUSE Y
1 = Reset command
Cause of Last Meter Reset 2 = Power failure S_SYSTEM
Nominal Frequency Y Y Y Y Y 2017 Hz 1 INT16U RWC 50, 60, 400 50 Y PM5350 does not support 400Hz R_METER_SETUP_NOM_FREQUENCY Y
PM5350: 50, 60 Ashoka: EM32xx does not support 400Hz S_METERING
Ashoka and Akbar: 50, 60 Akbar: PM5xxx does not support 400Hz
Nominal Voltage Y Y Y Y Y 2018 V 2 FLOAT32 RWC 0 – (2xVT Primary or 2,000,000) 230 Y 690 for VT Connection Type == Direct Connect MID requirement? Need final decision. R_METER_SETUP_NOM_VOLT S_METERING Y
Nominal Current Y Y Y Y Y 2020 A 2 FLOAT32 RWC 0 – (4xCT Primary or 50,000) 5 Y MID requirement? Need final decision. R_METER_SETUP_NOM_CUR S_METERING Y
Nominal Power Factor Y Y Y Y Y 2022 --- 2 RWC +/- 0.0 – 2.0 0.8 Y R_METER_SETUP_NOM_PF S_METERING Y
Normal Phase Rotation Y Y Y Y Y 2024 --- 1 INT16U RWC 0–1 0 Y R_METER_SETUP_PHASE_ROTATION S_METERING Y
Instrument Transformers Y Y Y Y Y 2025 --- --- --- --- --- --- S_METERING Y
Number VTs Y Y Y Y Y 2025 --- 1 INT16U RWC Depends on Power System 0 Y R_METER_SETUP_VT_NUM S_METERING Y
VT Primary Y Y Y Y Y 2026 V 2 FLOAT32 RWC VT Secondary – 1,000,000 120 Y R_METER_SETUP_VT_PRI S_METERING Y
VT Secondary Y Y Y Y Y 2028 V 1 INT16U RWC 100, 110, 115, 120 120 Y R_METER_SETUP_VT_SEC S_METERING Y
Number CTs Y Y Y Y Y 2029 --- 1 INT16U RWC Depends on Power System 0 Y R_METER_SETUP_CT_NUM S_METERING Y
CT Primary Y Y Y Y Y 2030 A 1 INT16U RWC 1 – 32,767 5 Y R_METER_SETUP_CT_PRI_PHASE S_METERING Y
CT Secondary Y Y Y Y Y 2031 A 1 INT16U RWC 1, 5 5 Y R_METER_SETUP_CT_SEC_PHASE S_METERING Y
CT Location for 1 or 2 CT Metering Y Y Y Y Y 2034 --- 1 INT16U RWC 1–3 1 Y If 1 CT, value is meter terminal connected R_METER_SETUP_CT_PHASE Y
If 2 CT, value is meter terminal not connected
1 = Phase A, 2 = Phase B, 3 = Phase C S_METERING
VT Location for 1 or 2 VT Metering Y Y Y Y Y 2035 --- 1 INT16U RWC 1–3 1 Y Must match CT Location R_METER_SETUP_VT_PHASE S_METERING Y
VT Connection Type Y Y Y Y Y 2036 --- 1 INT16U RWC 0 –4 0 Y 0 = Direct Connect R_METER_SETUP_CONNECTION Y
1 = Delta (2 VT)
2 = Wye (3 VT)
3 = L-N (1 VT) S_METERING
4 = L-L (1 VT)
5 = L-L W/N (2 VT)
Operating Modes Y Y Y Y Y 2046 --- --- --- --- --- --- S_METERING Y
Peak Current Demand Over Last Year Y Y Y Y Y 2048 A 2 FLOAT32 RWC 0 Y Entered by the user for use in calculation of Total Demand R_METER_SETUP_TDD_DEM Y
Distortion. 0 = Calculation performed using peak demand of 3-
phase average current. S_METERING
Active Load Timer Setpoint Y Y Y Y Y 2050 A 2 FLOAT32 RWC 0 – (10 * CT Ratio) 5 Y R_TIMER_ACTIVE_LOAD_SETPOINT S_METERING Y
Reserved 2052 --- 54 INT16U R N/A N R_RESERVED_2052 S_METERING
2106 --- --- --- --- --- --- S_METERING
Energy Pulse Output Setup Y Y Y Y Y 2126 --- --- --- --- --- --- S_METERING Y
Alarm / Ener Alarm / Energy LED Mode Y Y Y Y Y 2126 --- 1 INT16U RWC 0–2 1 Y 0 = Disable, 1 = Active Alarm (default), 2 = Energy R_ENG_LED_ENABLE S_METERING Y
Energy Pulse Output Channel 01 Y Y Y Y Y 2130 --- --- --- --- --- --- S_METERING Y
Energy Channel Y Y Y Y Y 2130 --- 1 INT16U RWC 0 – 18 0 Y 0 = Not Used R_METER_SETUP_ENG_CH01 Y
PM5350: 0 - 9 1 = Active Energy Delivered (Into Load)
2 = Active Energy Received (Out of Load)
3 = Active Energy Delivered + Received
4 = Reactive Energy Delivered
5 = Reactive Energy Received
6 = Reactive Energy Delivered + Received
7 = Apparent Energy Delivered
8 = Apparent Energy Received
9 = Apparent Energy Delivered + Received
10 = Active Energy Delivered Phase A
11 = Active Energy Delivered Phase B S_METERING
12 = Active Energy Delivered Phase C
13 = Reactive Energy Delivered Phase A
14 = Reactive Energy Delivered Phase B
15 = Reactive Energy Delivered Phase C
16 = Apparent Energy Delivered Phase A
17 = Apparent Energy Delivered Phase B
18 = Apparent Energy Delivered Phase C
Pulse Weight Y Y Y Y Y 2132 kWh, kVAh, kVAh 2 UINT32 RWC 1E-10 – 1E10 0 Y If the Energy Channel is not 0, a non-zero pulse weight must R_METER_SETUP_ENG_PW01 Y
S_METERING
be entered.
Energy Pulse Output Channel 02 Y Y Y Y Y 2134 --- --- --- --- --- --- See Energy Pulse Output Channel 01 S_METERING
Energy Channel Y Y Y Y Y 2134 --- 1 INT16U RWC 0 – 18 0 Y R_METER_SETUP_ENG_CH02 S_METERING
Digital Output Association Y Y Y Y Y 2135 --- 1 INT16U RWC 0 – 99 0 Y R_METER_SETUP_ENG_DO02 S_METERING
Pulse Weight Y Y Y Y Y 2136 kWh, kVAh, kVAh 2 UINT32 RWC 1E-10 – 1E10 0 Y R_METER_SETUP_ENG_PW02 S_METERING
Energy Pulse Output Channel 03 Y Y Y Y 2138 --- --- --- --- --- --- See Energy Pulse Output Channel 01 S_METERING
Energy Channel Y Y Y Y 2138 --- 1 INT16U RWC 0 – 18 0 Y R_METER_SETUP_ENG_CH03 S_METERING
Digital Output Association Y Y Y Y 2139 --- 1 INT16U RWC 0 – 99 0 Y R_METER_SETUP_ENG_DO03 S_METERING
Pulse Weight Y Y Y Y 2140 kWh, kVAh, kVAh 2 UINT32 RWC 1E-10 – 1E10 0 Y R_METER_SETUP_ENG_PW03 S_METERING
Meter Data (Basic) Y Y Y Y Y 3000 --- --- --- --- --- --- S_METERING Y
1s Metering (50/60 Cycles) Y Y Y Y Y 3000 --- --- --- --- --- --- S_METERING Y
Current Y Y Y Y Y 3000 --- --- --- --- --- --- S_METERING Y
Current A Y Y Y Y Y 3000 A 2 FLOAT32 R N R_IA_50_60_CYC_RMS IA_50_60_CYC_RMS S_METERING 1003 MMXU1\A\phsA MMXU1\A\phsA\cVal\mag\f Y
Current B Y Y Y Y Y 3002 A 2 FLOAT32 R N R_IB_50_60_CYC_RMS IB_50_60_CYC_RMS S_METERING 1004 MMXU1\A\phsB MMXU1\A\phsB\cVal\mag\f Y
Current C Y Y Y Y Y 3004 A 2 FLOAT32 R N R_IC_50_60_CYC_RMS IC_50_60_CYC_RMS S_METERING 1005 MMXU1\A\phsC MMXU1\A\phsC\cVal\mag\f Y
Current N Y Y Y Y Y 3006 A 2 FLOAT32 R N Reportable only in systems where there is a N current and R_IN_50_60_CYC_RMS IN_50_60_CYC_RMS 1006 MMXU1\A\neut MMXU1\A\neut\cVal\mag\f Y
S_METERING
when all wired phase currents are metered
Current G Y Y Y Y Y 3008 A 2 FLOAT32 R N Reportable only in systems where there is not a N current and R_IG_50_60_CYC_RMS IG_50_60_CYC_RMS 1007 MMXU1\A\zgnd MMXU1\A\zgnd\cVal\mag\f Y
S_METERING
when all wired phase currents are metered
Current Avg Y Y Y Y Y 3010 A 2 FLOAT32 R N R_IAVG_50_60_CYC_RMS S_METERING 1008 MMXU1\A\zavg MMXU1\A\zavg\cVal\mag\f Y
Current Unbalance Y Y Y Y Y 3012 --- --- --- --- --- --- S_METERING Y
Current Unbalance A Y Y Y Y Y 3012 % 2 FLOAT32 R N R_IA_50_60_CYC_UNB IA_50_60_CYC_UNBAL S_METERING 1010 MSQI1\ImbA\phsA MSQI1\ImbA\phsA\cVal\mag\f Y
Current Unbalance B Y Y Y Y Y 3014 % 2 FLOAT32 R N R_IB_50_60_CYC_UNB IB_50_60_CYC_UNBAL S_METERING 1011 MSQI1\ImbA\phsB MSQI1\ImbA\phsB\cVal\mag\f Y
Current Unbalance C Y Y Y Y Y 3016 % 2 FLOAT32 R N R_IC_50_60_CYC_UNB IC_50_60_CYC_UNBAL S_METERING 1012 MSQI1\ImbA\phsC MSQI1\ImbA\phsC\cVal\mag\f Y
Current Unbalance Worst Y Y Y Y Y 3018 % 2 FLOAT32 R N R_I_50_60_CYC_UNB_MAX I_50_60_CYC_UNBAL_MAX S_METERING 1013 SLR_MSQI1\MaxImbA SLR_MSQI1\MaxImbA\mag\f Y
Voltage Y Y Y Y Y 3020 --- --- --- --- --- --- S_METERING Y
Voltage A-B Y Y Y Y Y 3020 V 2 FLOAT32 R N R_VAB_50_60_CYC_RMS VAB_50_60_CYC_RMS S_METERING 1014 MMXU1\PPV\phsAB MMXU1\PPV\phsAB\cVal\mag\f Y
Voltage B-C Y Y Y Y Y 3022 V 2 FLOAT32 R N R_VBC_50_60_CYC_RMS VBC_50_60_CYC_RMS S_METERING 1015 MMXU1\PPV\phsBC MMXU1\PPV\phsBC\cVal\mag\f Y
Voltage C-A Y Y Y Y Y 3024 V 2 FLOAT32 R N R_VCA_50_60_CYC_RMS VCA_50_60_CYC_RMS S_METERING 1016 MMXU1\PPV\phsCA MMXU1\PPV\phsCA\cVal\mag\f Y
Voltage L-L Avg Y Y Y Y Y 3026 V 2 FLOAT32 R N R_VLL_50_60_CYC_RMS_AVG VLL_50_60_CYC_RMS_AVG S_METERING 1017 MMXU1\PPV\zavg MMXU1\PPV\zavg\cVal\mag\f Y
Voltage A-N Y Y Y Y Y 3028 V 2 FLOAT32 R N Reportable only in systems where Van is connected R_VAN_50_60_CYC_RMS VAN_50_60_CYC_RMS S_METERING 1018 MMXU1\PhV\phsA MMXU1\PhV\phsA\cVal\mag\f Y
Voltage B-N Y Y Y Y Y 3030 V 2 FLOAT32 R N Reportable only in systems where Vbn is connected R_VBN_50_60_CYC_RMS VBN_50_60_CYC_RMS S_METERING 1019 MMXU1\PhV\phsB MMXU1\PhV\phsB\cVal\mag\f Y
Voltage C-N Y Y Y Y Y 3032 V 2 FLOAT32 R N Reportable only in systems where Vcn is connected R_VCN_50_60_CYC_RMS VCN_50_60_CYC_RMS S_METERING 1020 MMXU1\PhV\phsC MMXU1\PhV\phsC\cVal\mag\f Y
Voltage N-G 3034 V 2 FLOAT32 R N Need to indicate under what conditions this value will be reported. R_VNG_50_60_CYC_RMS VNG_50_60_CYC_RMS
S_METERING
Voltage L-N Avg Y Y Y Y Y 3036 V 2 FLOAT32 R N Reportable only in systems where a L-N voltage is applied R_VLN_50_60_CYC_RMS_AVG VLN_50_60_CYC_RMS_AVG S_METERING 1021 MMXU1\PhV\zavg MMXU1\PhV\zavg\cVal\mag\f Y
Voltage Unbalance Y Y Y Y Y 3038 --- --- --- --- --- --- S_METERING Y
Voltage Unbalance A-B Y Y Y Y Y 3038 % 2 FLOAT32 R N R_VAB_50_60_CYC_UNB VAB_50_60_CYC_UNBAL S_METERING 1022 MSQI1\ImbPPV\phsAB MSQI1\ImbPPV\phsAB\cVal\mag\f Y
Voltage Unbalance B-C Y Y Y Y Y 3040 % 2 FLOAT32 R N R_VBC_50_60_CYC_UNB VBC_50_60_CYC_UNBAL S_METERING 1023 MSQI1\ImbPPV\phsBC MSQI1\ImbPPV\phsBC\cVal\mag\f Y
Voltage Unbalance C-A Y Y Y Y Y 3042 % 2 FLOAT32 R N R_VCA_50_60_CYC_UNB VCA_50_60_CYC_UNBAL S_METERING 1024 MSQI1\ImbPPV\phsCA MSQI1\ImbPPV\phsCA\cVal\mag\f Y
Voltage Unbalance L-L Worst Y Y Y Y Y 3044 % 2 FLOAT32 R N R_VLL_50_60_CYC_UNB_MAX VLL_50_60_CYC_UNBAL_MAX S_METERING 1025 SLR_MSQI1\MaxImbPPV SLR_MSQI1\MaxImbPPV\mag\f Y
Voltage Unbalance A-N Y Y Y Y Y 3046 % 2 FLOAT32 R N R_VAN_50_60_CYC_UNB VAN_50_60_CYC_UNBAL S_METERING 1026 MSQI1\ImbV\phsA MSQI1\ImbV\phsA\cVal\mag\f Y
Voltage Unbalance B-N Y Y Y Y Y 3048 % 2 FLOAT32 R N R_VBN_50_60_CYC_UNB VBN_50_60_CYC_UNBAL S_METERING 1027 MSQI1\ImbV\phsB MSQI1\ImbV\phsB\cVal\mag\f Y
Voltage Unbalance C-N Y Y Y Y Y 3050 % 2 FLOAT32 R N R_VCN_50_60_CYC_UNB VCN_50_60_CYC_UNBAL S_METERING 1028 MSQI1\ImbV\phsC MSQI1\ImbV\phsC\cVal\mag\f Y
Voltage Unbalance L-N Worst Y Y Y Y Y 3052 % 2 FLOAT32 R N R_VLN_50_60_CYC_UNB_MAX VLN_50_60_CYC_UNBAL_MAX S_METERING 1029 SLR_MSQI1\MaxImbV SLR_MSQI1\MaxImbV\mag\f Y
Power Y Y Y Y Y 3054 --- --- --- --- --- --- S_METERING Y
Active Power A Y Y Y Y Y 3054 kW 2 FLOAT32 R N R_PA_50_60_CYC_RMS PA_50_60_CYC S_METERING 1039 MMXU1\W\phsA MMXU1\W\phsA\cVal\mag\f Y
Active Power B Y Y Y Y Y 3056 kW 2 FLOAT32 R N R_PB_50_60_CYC_RMS PB_50_60_CYC S_METERING 1040 MMXU1\W\phsB MMXU1\W\phsB\cVal\mag\f Y
Active Power C Y Y Y Y Y 3058 kW 2 FLOAT32 R N R_PC_50_60_CYC_RMS PC_50_60_CYC S_METERING 1041 MMXU1\W\phsC MMXU1\W\phsC\cVal\mag\f Y
Active Power Total Y Y Y Y Y 3060 kW 2 FLOAT32 R N R_PTOT_50_60_CYC_RMS PTOT_50_60_CYC S_METERING 1042 MMXU1\TotW MMXU1\TotW\mag\f Y
Reactive Power A Y Y Y Y Y 3062 kVAR 2 FLOAT32 R N R_QA_50_60_CYC_RMS QA_50_60_CYC S_METERING 1043 MMXU1\VAr\phsA MMXU1\VAr\phsA\cVal\mag\f Y
Reactive Power B Y Y Y Y Y 3064 kVAR 2 FLOAT32 R N R_QB_50_60_CYC_RMS QB_50_60_CYC S_METERING 1044 MMXU1\VAr\phsB MMXU1\VAr\phsB\cVal\mag\f Y
Reactive Power C Y Y Y Y Y 3066 kVAR 2 FLOAT32 R N R_QC_50_60_CYC_RMS QC_50_60_CYC S_METERING 1045 MMXU1\VAr\phsC MMXU1\VAr\phsC\cVal\mag\f Y
Reactive Power Total Y Y Y Y Y 3068 kVAR 2 FLOAT32 R N R_QTOT_50_60_CYC_RMS QTOT_50_60_CYC S_METERING 1046 MMXU1\TotVAr MMXU1\TotVAr\mag\f Y
Apparent Power A Y Y Y Y Y 3070 kVA 2 FLOAT32 R N R_SA_50_60_CYC_RMS SA_50_60_CYC S_METERING 1047 MMXU1\VA\phsA MMXU1\VA\phsA\cVal\mag\f Y
Apparent Power B Y Y Y Y Y 3072 kVA 2 FLOAT32 R N R_SB_50_60_CYC_RMS SB_50_60_CYC S_METERING 1048 MMXU1\VA\phsB MMXU1\VA\phsB\cVal\mag\f Y
Apparent Power C Y Y Y Y Y 3074 kVA 2 FLOAT32 R N R_SC_50_60_CYC_RMS SC_50_60_CYC S_METERING 1049 MMXU1\VA\phsC MMXU1\VA\phsC\cVal\mag\f Y
Apparent Power Total Y Y Y Y Y 3076 kVA 2 FLOAT32 R N R_STOT_50_60_CYC_RMS STOT_50_60_CYC S_METERING 1050 MMXU1\TotVA MMXU1\TotVA\mag\f Y
Power Factor Y Y Y Y Y 3078 --- --- --- --- --- --- S_METERING Y
Power Factor A Y Y Y Y Y 3078 --- 2 4Q FP PF R +/- 0.0 – 2.0 N R_PFA_50_60_CYC_TRUE PFA_50_60_CYC_TRUE S_METERING 1031 MMXU1\PF\phsA MMXU1\PF\phsA\cVal\mag\f Y
Power Factor B Y Y Y Y Y 3080 --- 2 4Q FP PF R +/- 0.0 – 2.0 N R_PFB_50_60_CYC_TRUE PFB_50_60_CYC_TRUE S_METERING 1032 MMXU1\PF\phsB MMXU1\PF\phsB\cVal\mag\f Y
Power Factor C Y Y Y Y Y 3082 --- 2 4Q FP PF R +/- 0.0 – 2.0 N R_PFC_50_60_CYC_TRUE PFC_50_60_CYC_TRUE S_METERING 1033 MMXU1\PF\phsC MMXU1\PF\phsC\cVal\mag\f Y
Power Factor Total Y Y Y Y Y 3084 --- 2 4Q FP PF R +/- 0.0 – 2.0 N R_PFTOT_50_60_CYC_TRUE PFTOT_50_60_CYC_TRUE S_METERING 1034 MMXU1\TotPF MMXU1\TotPF\mag\f Y
Displacement Power Factor A Y Y Y Y Y 3086 --- 2 4Q FP PF R +/- 0.0 – 2.0 N R_PFA_50_60_CYC_DISP PFA_50_60_CYC_DISP S_METERING 1035 MMXU1\ZPFDsp\phsA MMXU1\ZPFDsp\phsA\cVal\mag\f Y
Displacement Power Factor B Y Y Y Y Y 3088 --- 2 4Q FP PF R +/- 0.0 – 2.0 N R_PFB_50_60_CYC_DISP PFB_50_60_CYC_DISP S_METERING 1036 MMXU1\ZPFDsp\phsB MMXU1\ZPFDsp\phsB\cVal\mag\f Y
Displacement Power Factor C Y Y Y Y Y 3090 --- 2 4Q FP PF R +/- 0.0 – 2.0 N R_PFC_50_60_CYC_DISP PFC_50_60_CYC_DISP S_METERING 1037 MMXU1\ZPFDsp\phsC MMXU1\ZPFDsp\phsC\cVal\mag\f Y
Displacement Power Factor Total Y Y Y Y Y 3092 --- 2 4Q FP PF R +/- 0.0 – 2.0 N R_PFTOT_50_60_CYC_DISP PFTOT_50_60_CYC_DISP S_METERING 1038 MMXU1\ZTotPFDsp MMXU1\ZTotPFDsp\mag\f Y
Frequency Frequency Y Y Y Y Y 3110 Hz 2 FLOAT32 R 42 – 70 N R_FREQ_50_60_CYC_AVG S_METERING 1001 MMXU1\Hz MMXU1\Hz\mag\f Y
Energy Y Y Y Y Y 3200 --- --- --- --- --- --- S_METERING Y
Accumulated Energy Y Y Y Y Y 3200 --- --- --- --- --- --- S_METERING Y
Accumulated Energy Reset Date/Time Y Y Y Y Y 3200 --- 4 DATETIME R --- N/A Y R_ENG_ACC_RESET_DT S_METERING Y
Active Energy Delivered (Into Load) Y Y Y Y Y 3204 Wh 4 INT64 R --- 0 Y R_ENG_ACC_KWH_DEL MMTR1\DmdWh S_METERING Y
Active Energy Received (Out of Load) Y Y Y Y Y 3208 Wh 4 INT64 R --- 0 Y R_ENG_ACC_KWH_REC MMTR1\SupWh S_METERING Y
Active Energy Delivered + Received Y Y Y Y Y 3212 Wh 4 INT64 R --- 0 Y R_ENG_ACC_KWH_D_AND_R S_METERING Y
Active Energy Delivered – Received Y Y Y Y Y 3216 Wh 4 INT64 R --- 0 Y R_ENG_ACC_KWH_DEL_REC S_METERING Y
Reactive Energy Delivered Y Y Y Y Y 3220 VARh 4 INT64 R --- 0 Y R_ENG_ACC_KVARH_DEL MMTR1\DmdVArh S_METERING Y
Reactive Energy Received Y Y Y Y Y 3224 VARh 4 INT64 R --- 0 Y R_ENG_ACC_KVARH_REC MMTR1\SupVArh S_METERING Y
Reactive Energy Delivered + Received Y Y Y Y Y 3228 VARh 4 INT64 R --- 0 Y R_ENG_ACC_KVARH_D_AND_R S_METERING Y
Reactive Energy Delivered – Received Y Y Y Y Y 3232 VARh 4 INT64 R --- 0 Y R_ENG_ACC_KVARH_DEL_REC S_METERING Y
Apparent Energy Delivered Y Y Y Y Y 3236 VAh 4 INT64 R --- 0 Y R_ENG_ACC_KVAH_DEL S_METERING Y
Apparent Energy Received Y Y Y Y Y 3240 VAh 4 INT64 R --- 0 Y R_ENG_ACC_KVAH_REC S_METERING Y
Apparent Energy Delivered + Received Y Y Y Y Y 3244 VAh 4 INT64 R --- 0 Y R_ENG_ACC_KVAH_D_AND_R S_METERING Y
Apparent Energy Delivered – Received Y Y Y Y Y 3248 VAh 4 INT64 R --- 0 Y R_ENG_ACC_KVAH_DEL_REC S_METERING Y
Power Demand Interval Duration Y Y Y Y Y 3702 minutes 1 INT16U RWC 1 – 60 15 Y R_DMD_SYS_1_INT S_METERING Y
Power Demand Subinterval Duration Y Y Y Y Y 3703 minutes 1 INT16U RWC 1 – 60 15 Y The value must be evenly divisable into Interval Duration for R_DMD_SYS_1_SUBINT Y
Rolling Block.
For Thermal and Fixed Block demand methods, this value S_METERING
must be same as Interval Duration.
Power Demand Elapsed Time in Interval Y Y Y Y Y 3704 seconds 1 INT16U R 0 – 3,600 0 N R_DMD_SYS_1_INT_ELAPSED S_METERING Y
Power Demand Elapsed Time in Subinterval Y Y Y Y Y 3705 seconds 1 INT16U R 0 – 3,600 0 N R_DMD_SYS_1_SUBINT_ELAPSED S_METERING Y
Power Demand Peak Reset Date/Time Y Y Y Y Y 3706 --- 4 DATETIME R --- N/A Y R_DMD_SYS_1_PEAK_RESET_DT S_METERING Y
Reserved 3710 --- 1 INT16U R N/A N R_RESERVED_3710 S_METERING
Demand System 2 (Current) Y Y Y Y Y 3711 --- --- --- --- --- --- Current S_METERING Y
Current Demand Method Y Y Y Y Y 3711 --- 1 INT16U RWC 0-11 2 Y 0 = Thermal Demand R_DMD_SYS_2_METHOD Y
PM5350: 0-7 1 = Timed Interval Sliding Block
2 = Timed Interval Block
3 = Timed Interval Rolling Block
4 = Input Synchronized Block
5 = Input Synchronized Rolling Block
6 = Command Synchronized Block
7 = Command Synchronized Rolling Block S_METERING
8 = Clock Synchronized Block
9 = Clock Synchronized Rolling Block
10 = Slave to System 1 (Power) Demand Interval
11 = Slave to Incremental Energy Interval
Current Demand Interval Duration Y Y Y Y Y 3712 minutes 1 INT16U RWC 1 – 60 15 Y R_DMD_SYS_2_INT S_METERING Y
Current Demand Subinterval Duration Y Y Y Y Y 3713 minutes 1 INT16U RWC 1 – 60 15 Y The value must be evenly divisable into Interval Duration for R_DMD_SYS_2_SUBINT Y
Rolling Block.
For Thermal and Fixed Block demand methods, this value S_METERING
must be same as Interval Duration.
Current Demand Elapsed Time in Interval Y Y Y Y Y 3714 seconds 1 INT16U R 0 – 3,600 0 N R_DMD_SYS_2_INT_ELAPSED S_METERING Y
Current Demand Elapsed Time in Subinterval Y Y Y Y Y 3715 seconds 1 INT16U R 0 – 3,600 0 N R_DMD_SYS_2_SUBINT_ELAPSED S_METERING Y
Current Demand Peak Reset Date/Time Y Y Y Y Y 3716 --- 4 DATETIME R --- N/A Y R_DMD_SYS_2_PEAK_RESET_DT S_METERING Y
Reserved 3720 --- 1 INT16U R N/A N R_RESERVED_3720 S_METERING
Demand Channel 1 (Active Power) Y Y Y Y Y 3761 --- --- --- --- --- --- Active Power Total S_METERING Y
Demand System Assignment Y Y Y Y Y 3761 --- 1 INT16U R 0–6 1 Y Power Demand R_DMD_CH_01_SYSTEM S_METERING Y
Register Number of Metered Quantity Y Y Y Y Y 3762 --- 1 INT16U R 1 – 32,767 R_PTOT_50_60_CYC_RMS Y Active Power Total R_DMD_CH_01_REG S_METERING Y
Units Code Y Y Y Y Y 3763 --- 1 INT16U R 0 – 100 12 Y R_DMD_CH_01_UNITS S_METERING Y
Last Demand Y Y Y Y Y 3764 kW 2 FLOAT32 R --- 0 Y R_DMD_CH_01_LAST S_METERING Y
Present Demand Y Y Y Y Y 3766 kW 2 FLOAT32 R --- 0 N R_DMD_CH_01_PRES S_METERING Y
Predicted Demand Y Y Y Y Y 3768 kW 2 FLOAT32 R --- 0 N R_DMD_CH_01_PREDICTED S_METERING Y
Peak Demand Y Y Y Y Y 3770 kW 2 FLOAT32 R --- 0 Y R_DMD_CH_01_PEAK S_METERING Y
Peak Demand DateTime Y Y Y Y Y 3772 --- 4 DATETIME R --- N/A Y R_DMD_CH_01_PEAK_DT S_METERING Y
Reserved 3776 --- 1 INT16U R N/A N R_RESERVED_3777 S_METERING
Demand Channel 2 (Reactive Power) Y Y Y Y Y 3777 --- --- --- --- --- --- Reactive Power Total S_METERING Y
Demand System Assignment Y Y Y Y Y 3777 --- 1 INT16U R 0–6 1 Y Power Demand R_DMD_CH_02_SYSTEM S_METERING Y
Register Number of Metered Quantity Y Y Y Y Y 3778 --- 1 INT16U R 1 – 32,767 R_QTOT_50_60_CYC_RMS Y Reactive Power Total R_DMD_CH_02_REG S_METERING Y
Units Code Y Y Y Y Y 3779 --- 1 INT16U R 0 – 100 15 Y R_DMD_CH_02_UNITS S_METERING Y
Last Demand Y Y Y Y Y 3780 kVAR 2 FLOAT32 R --- 0 Y R_DMD_CH_02_LAST S_METERING Y
Present Demand Y Y Y Y Y 3782 kVAR 2 FLOAT32 R --- 0 N R_DMD_CH_02_PRES S_METERING Y
Predicted Demand Y Y Y Y Y 3784 kVAR 2 FLOAT32 R --- 0 N R_DMD_CH_02_PREDICTED S_METERING Y
Peak Demand Y Y Y Y Y 3786 kVAR 2 FLOAT32 R --- 0 Y R_DMD_CH_02_PEAK S_METERING Y
Peak Demand DateTime Y Y Y Y Y 3788 --- 4 DATETIME R --- N/A Y R_DMD_CH_02_PEAK_DT S_METERING Y
Reserved 3792 --- 1 INT16U R N/A N R_RESERVED_3793 S_METERING
Demand Channel 3 (Apparent Power) Y Y Y Y Y 3793 --- --- --- --- --- --- Apparent Power Total S_METERING Y
Demand System Assignment Y Y Y Y Y 3793 --- 1 INT16U R 0–6 1 Y Power Demand R_DMD_CH_03_SYSTEM S_METERING Y
Register Number of Metered Quantity Y Y Y Y Y 3794 --- 1 INT16U R 1 – 32,767 R_STOT_50_60_CYC_RMS Y Apparent Power Total R_DMD_CH_03_REG S_METERING Y
Units Code Y Y Y Y Y 3795 --- 1 INT16U R 0 – 100 18 Y R_DMD_CH_03_UNITS S_METERING Y
Last Demand Y Y Y Y Y 3796 kVA 2 FLOAT32 R --- 0 Y R_DMD_CH_03_LAST S_METERING Y
Present Demand Y Y Y Y Y 3798 kVA 2 FLOAT32 R --- 0 N R_DMD_CH_03_PRES S_METERING Y
Predicted Demand Y Y Y Y Y 3800 kVA 2 FLOAT32 R --- 0 N R_DMD_CH_03_PREDICTED S_METERING Y
Peak Demand Y Y Y Y Y 3802 kVA 2 FLOAT32 R --- 0 Y R_DMD_CH_03_PEAK S_METERING Y
Peak Demand DateTime Y Y Y Y Y 3804 --- 4 DATETIME R --- N/A Y R_DMD_CH_03_PEAK_DT S_METERING Y
Reserved 3808 --- 1 INT16U R N/A N R_RESERVED_3809 S_METERING
Demand Channel 8 (Current Avg) Y Y Y Y Y 3873 --- --- --- --- --- --- Current, Average S_METERING Y
Demand System Assignment Y Y Y Y Y 3873 --- 1 INT16U R 0–6 2 Y Current Demand R_DMD_CH_08_SYSTEM S_METERING Y
Register Number of Metered Quantity Y Y Y Y Y 3874 --- 1 INT16U R 1 – 32,767 R_IAVG_50_60_CYC_RMS Y Current, Average R_DMD_CH_08_REG S_METERING Y
Units Code Y Y Y Y Y 3875 --- 1 INT16U R 0 – 100 6 Y R_DMD_CH_08_UNITS S_METERING Y
Last Demand Y Y Y Y Y 3876 A 2 FLOAT32 R --- 0 Y R_DMD_CH_08_LAST S_METERING Y
Present Demand Y Y Y Y Y 3878 A 2 FLOAT32 R --- 0 N R_DMD_CH_08_PRES S_METERING Y
Predicted Demand Y Y Y Y Y 3880 A 2 FLOAT32 R --- 0 N R_DMD_CH_08_PREDICTED S_METERING Y
Peak Demand Y Y Y Y Y 3882 A 2 FLOAT32 R --- 0 Y R_DMD_CH_08_PEAK S_METERING Y
Peak Demand DateTime Y Y Y Y Y 3884 --- 4 DATETIME R --- N/A Y R_DMD_CH_08_PEAK_DT S_METERING Y
Reserved 3888 --- 1 INT16U R N/A N R_RESERVED_3888 S_METERING Y
Miscellaneous Demand Setup & Data 4145 --- --- --- --- --- --- S_METERING
Clock Sync Time of Day Y Y Y Y Y 4147 --- 1 INT16U RWC 0-2359 0 Y Time of day to which the demand interval is to be R_DMD_CLK_SYNC_TIME Y
synchronized. Applies to demand intervals configured as S_METERING
Clock Synchronized. Default = midnight.
4188 --- --- --- --- --- --- S_METERING
Energy TOU/MT Y Y Y Y
Time-of-Use/Mult-Tariff Energy Y Y Y Y
TOU/MT Mode Y Y Y Y 4190 --- 1 INT16U RWC 0-2 0 Y R_ENG_TOU_MT_MODE S_METERING_MT Y
TOU/MT Energy Active Rate Y Y Y Y 4191 --- 1 INT16U R 0–8 0 Y R_ENG_TOU_MT_ACTIVE_RATE S_METERING_MT Y
TOU/MT Energy Reset Date/Time Y Y Y Y 4192 --- 4 DATETIME R --- N/A Y R_ENG_TOU_MT_RESET_DT S_METERING_MT Y
Active Energy Delivered Rate 1 Y Y Y Y 4196 Wh 4 INT64 R --- 0 Y R_ENG_TOU_MT_KWH_DEL_RATE_1 S_METERING_MT Y
Active Energy Delivered Rate 2 Y Y Y Y 4200 Wh 4 INT64 R --- 0 Y R_ENG_TOU_MT_KWH_DEL_RATE_2 S_METERING_MT Y
Active Energy Delivered Rate 3 Y Y Y Y 4204 Wh 4 INT64 R --- 0 Y R_ENG_TOU_MT_KWH_DEL_RATE_3 S_METERING_MT Y
Active Energy Delivered Rate 4 Y Y Y Y 4208 Wh 4 INT64 R --- 0 Y R_ENG_TOU_MT_KWH_DEL_RATE_4 S_METERING_MT Y
Active Energy Received Rate 1 Y Y Y Y 4228 Wh 4 INT64 R --- 0 Y R_ENG_TOU_MT_KWH_REC_RATE_1 S_METERING_MT Y
Active Energy Received Rate 2 Y Y Y Y 4232 Wh 4 INT64 R --- 0 Y R_ENG_TOU_MT_KWH_REC_RATE_2 S_METERING_MT Y
Active Energy Received Rate 3 Y Y Y Y 4236 Wh 4 INT64 R --- 0 Y R_ENG_TOU_MT_KWH_REC_RATE_3 S_METERING_MT Y
Active Energy Received Rate 4 Y Y Y Y 4240 Wh 4 INT64 R --- 0 Y R_ENG_TOU_MT_KWH_REC_RATE_4 S_METERING_MT Y
Reactive Energy Delivered Rate 1 Y Y Y Y 4260 VARh 4 INT64 R --- 0 Y R_ENG_TOU_MT_KVARH_DEL_RATE_1 S_METERING_MT Y
Reactive Energy Delivered Rate 2 Y Y Y Y 4264 VARh 4 INT64 R --- 0 Y R_ENG_TOU_MT_KVARH_DEL_RATE_2 S_METERING_MT Y
Reactive Energy Delivered Rate 3 Y Y Y Y 4268 VARh 4 INT64 R --- 0 Y R_ENG_TOU_MT_KVARH_DEL_RATE_3 S_METERING_MT Y
Reactive Energy Delivered Rate 4 Y Y Y Y 4272 VARh 4 INT64 R --- 0 Y R_ENG_TOU_MT_KVARH_DEL_RATE_4 S_METERING_MT Y
Reactive Energy Received Rate 1 Y Y Y Y 4292 VARh 4 INT64 R --- 0 Y R_ENG_TOU_MT_KVARH_REC_RATE_1 S_METERING_MT Y
Reactive Energy Received Rate 2 Y Y Y Y 4296 VARh 4 INT64 R --- 0 Y R_ENG_TOU_MT_KVARH_REC_RATE_2 S_METERING_MT Y
Reactive Energy Received Rate 3 Y Y Y Y 4300 VARh 4 INT64 R --- 0 Y R_ENG_TOU_MT_KVARH_REC_RATE_3 S_METERING_MT Y
Reactive Energy Received Rate 4 Y Y Y Y 4304 VARh 4 INT64 R --- 0 Y R_ENG_TOU_MT_KVARH_REC_RATE_4 S_METERING_MT Y
Apparent Energy Delivered Rate 1 Y Y Y Y 4324 VAh 4 INT64 R --- 0 Y R_ENG_TOU_MT_KVAH_DEL_RATE_1 S_METERING_MT Y
Apparent Energy Delivered Rate 2 Y Y Y Y 4328 VAh 4 INT64 R --- 0 Y R_ENG_TOU_MT_KVAH_DEL_RATE_2 S_METERING_MT Y
Apparent Energy Delivered Rate 3 Y Y Y Y 4332 VAh 4 INT64 R --- 0 Y R_ENG_TOU_MT_KVAH_DEL_RATE_3 S_METERING_MT Y
Apparent Energy Delivered Rate 4 Y Y Y Y 4336 VAh 4 INT64 R --- 0 Y R_ENG_TOU_MT_KVAH_DEL_RATE_4 S_METERING_MT Y
Apparent Energy Received Rate 1 Y Y Y Y 4356 VAh 4 INT64 R --- 0 Y R_ENG_TOU_MT_KVAH_REC_RATE_1 S_METERING_MT Y
Apparent Energy Received Rate 2 Y Y Y Y 4360 VAh 4 INT64 R --- 0 Y R_ENG_TOU_MT_KVAH_REC_RATE_2 S_METERING_MT Y
Apparent Energy Received Rate 3 Y Y Y Y 4364 VAh 4 INT64 R --- 0 Y R_ENG_TOU_MT_KVAH_REC_RATE_3 S_METERING_MT Y
Apparent Energy Received Rate 4 Y Y Y Y 4368 VAh 4 INT64 R --- 0 Y R_ENG_TOU_MT_KVAH_REC_RATE_4 S_METERING_MT Y
MT Day Type Rate 1 Y Y Y Y 4516 --- 1 INT16U RWC 1 -10 1 Y 1 = Everyday, 2-8 = Mon-Sunday, 9 = Weekday, R_ENG_MT_DAY_TYPE_RATE_1 Y
S_METERING_MT
10 = Weekend
MT Start Time Rate 1 Y Y Y Y 4517 --- 1 INT16U RWC 0-2359 0 Y R_ENG_MT_START_TIME_RATE_1 S_METERING_MT Y
MT End Time Rate 1 Y Y Y Y 4518 --- 1 INT16U RWC 0-2359 0 Y R_ENG_MT_END_TIME_RATE_1 S_METERING_MT Y
MT Start Month Rate1 Y Y Y Y 4519 --- 1 INT16U RWC 0-12 0 Y R_ENG_MT_START_MON_RATE_1 S_METERING_MT Y
MT Start Day Rate 1 Y Y Y Y 4520 --- 1 INT16U RWC 0-31 0 Y R_ENG_MT_START_DAY_RATE_1 S_METERING_MT Y
MT End Month Rate 1 Y Y Y Y 4521 --- 1 INT16U RWC 0-12 0 Y R_ENG_MT_END_MON_RATE_1 S_METERING_MT Y
MT End Day Rate 1 Y Y Y Y 4522 --- 1 INT16U RWC 0-31 0 Y R_ENG_MT_END_DAY_RATE_1 S_METERING_MT Y
MT Day Type Rate 2 Y Y Y Y 4523 --- 1 INT16U RWC 1 -10 1 Y 1 = Everyday, 2-8 = Mon-Sunday, 9 = Weekday, R_ENG_MT_DAY_TYPE_RATE_2 Y
S_METERING_MT
10 = Weekend
MT Start Time Rate 2 Y Y Y Y 4524 --- 1 INT16U RWC 0-2359 0 Y R_ENG_MT_START_TIME_RATE_2 S_METERING_MT Y
MT End Time Rate 2 Y Y Y Y 4525 --- 1 INT16U RWC 0-2359 0 Y R_ENG_MT_END_TIME_RATE_2 S_METERING_MT Y
MT Start Month Rate2 Y Y Y Y 4526 --- 1 INT16U RWC 0-12 0 Y R_ENG_MT_START_MON_RATE_2 S_METERING_MT Y
MT Start Day Rate 2 Y Y Y Y 4527 --- 1 INT16U RWC 0-31 0 Y R_ENG_MT_START_DAY_RATE_2 S_METERING_MT Y
MT End Month Rate 2 Y Y Y Y 4528 --- 1 INT16U RWC 0-12 0 Y R_ENG_MT_END_MON_RATE_2 S_METERING_MT Y
MT End Day Rate 2 Y Y Y Y 4529 --- 1 INT16U RWC 0-31 0 Y R_ENG_MT_END_DAY_RATE_2 S_METERING_MT Y
MT Day Type Rate 3 Y Y Y Y 4530 --- 1 INT16U RWC 1 -10 1 Y 1 = Everyday, 2-8 = Mon-Sunday, 9 = Weekday, R_ENG_MT_DAY_TYPE_RATE_3 Y
S_METERING_MT
10 = Weekend
MT Start Time Rate 3 Y Y Y Y 4531 --- 1 INT16U RWC 0-2359 0 Y R_ENG_MT_START_TIME_RATE_3 S_METERING_MT Y
MT End Time Rate 3 Y Y Y Y 4532 --- 1 INT16U RWC 0-2359 0 Y R_ENG_MT_END_TIME_RATE_3 S_METERING_MT Y
MT Start Month Rate3 Y Y Y Y 4533 --- 1 INT16U RWC 0-12 0 Y R_ENG_MT_START_MON_RATE_3 S_METERING_MT Y
MT Start Day Rate 3 Y Y Y Y 4534 --- 1 INT16U RWC 0-31 0 Y R_ENG_MT_START_DAY_RATE_3 S_METERING_MT Y
MT End Month Rate 3 Y Y Y Y 4535 --- 1 INT16U RWC 0-12 0 Y R_ENG_MT_END_MON_RATE_3 S_METERING_MT Y
MT End Day Rate 3 Y Y Y Y 4536 --- 1 INT16U RWC 0-31 0 Y R_ENG_MT_END_DAY_RATE_3 S_METERING_MT Y
MT Day Type Rate 4 Y Y Y Y 4537 --- 1 INT16U RWC 1 -10 1 Y 1 = Everyday, 2-8 = Mon-Sunday, 9 = Weekday, R_ENG_MT_DAY_TYPE_RATE_4 Y
S_METERING_MT
10 = Weekend
MT Start Time Rate 4 Y Y Y Y 4538 --- 1 INT16U RWC 0-2359 0 Y R_ENG_MT_START_TIME_RATE_4 S_METERING_MT Y
MT End Time Rate 4 Y Y Y Y 4539 --- 1 INT16U RWC 0-2359 0 Y R_ENG_MT_END_TIME_RATE_4 S_METERING_MT Y
MT Start Month Rate4 Y Y Y Y 4540 --- 1 INT16U RWC 0-12 0 Y R_ENG_MT_START_MON_RATE_4 S_METERING_MT Y
MT Start Day Rate 4 Y Y Y Y 4541 --- 1 INT16U RWC 0-31 0 Y R_ENG_MT_START_DAY_RATE_4 S_METERING_MT Y
MT End Month Rate 4 Y Y Y Y 4542 --- 1 INT16U RWC 0-12 0 Y R_ENG_MT_END_MON_RATE_4 S_METERING_MT Y
MT End Day Rate 4 Y Y Y Y 4543 --- 1 INT16U RWC 0-31 0 Y R_ENG_MT_END_DAY_RATE_4 S_METERING_MT Y
HMI Date Format Y Y Y Y Y 6004 --- 1 INT16U RWC 0–2 0 Y 0 = MM/DD/YYYY R_HMI_DATE_FORMAT Y
1 = YYYY/MM/DD
2 = DD/MM/YYYY S_HMI
HMI Time Format Y Y Y Y Y 6005 --- 1 INT16U RWC 0–1 0 Y 0 = 2400hr R_HMI_TIME_FORMAT Y
1 = AM/PM S_HMI
HMI IEC/IEEE Mode Y Y Y Y Y 6006 --- 1 INT16U RWC 0–1 0 Y 0 = IEC R_HMI_IEC_IEEE_MODE Y
1 = IEEE S_HMI
HMI Screen Timeout Y Y Y Y Y 6007 minutes 1 INT16U RWC 0 – 60 0 Y 0 = disabled R_HMI_SCREEN_TIMEOUT S_HMI Y
HMI Backlight Timeout Y Y Y Y Y 6008 minutes 1 INT16U RWC 0 – 60 5 Y 0 = disabled R_HMI_BACKLIGHT_TIMEOUT S_HMI Y
HMI Energy Resolution Y Y Y Y Y 6009 --- 1 INT16U RWC 0 – 23 10 Y 0 = Auto range R_HMI_ENG_RESOLUTION
10 = 000000 kilo
11 = 00000.0 kilo
12 = 0000.00 kilo
13 = 000.000 kilo
20 = 000000 mega
21 = 00000.0 mega S_HMI
22 = 0000.00 mega
23 = 000.000 mega
All other values will default to auto range.
HMI Current Resolution Y Y Y Y Y 6010 --- 1 INT16U RWC 0 – 23 0 Y 0 = Auto range R_HMI_CUR_RESOLUTION
10 = 000000 mA
20 = 000000 A
21 = 00000.0 A
22 = 0000.00 A S_HMI
23 = 000.000 A
All other values will default to auto range.
HMI Voltage Resolution Y Y Y Y Y 6011 --- 1 INT16U RWC 0 – 32 0 Y 0 = Auto range R_HMI_VOLT_RESOLUTION
10 = 000000 V
11 = 00000.0 V
12 = 0000.00 V
13 = 000.000 V
20 = 000000 kV
21 = 00000.0 kV
22 = 0000.00 kV S_HMI
23 = 000.000 kV
30 = 000000 MV
31 = 00000.0 MV
32 = 0000.00 MV
All other values will default to auto range.
HMI Power Resolution Y Y Y Y Y 6012 --- 1 INT16U RWC 0 – 32 0 Y 0 = Auto range R_HMI_POWER_RESOLUTION
10 = 000000 W / VAR / VA
20 = 000000 kW / kVAR / kVA
21 = 00000.0 kW / kVAR / kVA
22 = 0000.00 kW / kVAR / kVA
23 = 000.000 kW / kVAR / kVA
30 = 000000 MW / MVAR / MVA S_HMI
31 = 00000.0 MW / MVAR / MVA
32 = 0000.00 MW / MVAR / MVA
All other values will default to auto range.
RS-485 Comm Port (M/S) Address Y Y Y 6501 --- 1 INT16U RWC 1 – 255 1 Y Valid Addresses: R_COMMS_485_1_ADDRESS Y
Modbus: 1 – 247
Jbus: 1 – 255 S_COMMUNICATIONS
RS-485 Comm Port (M/S) Baud Rate Y Y Y 6502 --- 1 INT16U RWC 0–2 1 Y 0 = 9600 R_COMMS_485_1_BAUD Y
1 = 19200
2 = 38400 S_COMMUNICATIONS
RS-485 Comm Port (M/S) Parity Y Y Y 6503 --- 1 INT16U RWC 0–2 0 Y 0 = Even R_COMMS_485_1_PARITY Y
1 = Odd
2 = None S_COMMUNICATIONS
Inputs & Outputs Y Y Y Y 7000 --- --- --- --- --- --- S_IO Y
Multi-tariff Setup Y Y Y Y 7012 --- --- --- --- --- --- S_IO
Number of Multi-tariff Rates Active Y Y Y Y 7012 --- 1 INT16U RWC 1–4 1 Y R_MULTI_RATE_NUM S_IO Y
Number of Digital Inputs Used to Control Multi-tariff Y Y Y Y 7013 --- 1 INT16U RWC 1–4 1 Y R_DIGIN_MULTI_RATE_NUM S_IO Y
Demand Sync Setup Y Y Y Y 7020 --- --- --- --- --- --- S_IO Y
Digital Input Associations With Demand Systems Y Y Y Y 7020 --- --- --- --- --- --- S_IO Y
Demand System 1 (Power) Y Y Y Y 7020 --- 1 INT16U RWC 0 – 68 0 Y R_DIGIN_DEM_SYSTEM_1 S_IO Y
Demand System 2 (Current) Y Y Y Y 7021 --- 1 INT16U RWC 0 – 68 0 Y R_DIGIN_DEM_SYSTEM_2 S_IO Y
Digital Output Associations With Demand Systems Y Y Y Y 7026 --- --- --- --- --- --- S_IO Y
Demand System 1 (Power) Y Y Y Y 7026 --- 1 INT16U RWC 0 – 68 0 Y R_DIGOUT_DEM_SYSTEM_1 S_IO Y
Demand System 2 (Current) Y Y Y Y 7027 --- 1 INT16U RWC 0 – 68 0 Y R_DIGOUT_DEM_SYSTEM_2 S_IO Y
7032 --- S_IO
Digital Inputs Setup Y Y Y Y 7273 --- --- --- --- --- --- S_IO Y
Base Unit - Digital Input DI1 Y Y Y Y 7273 --- --- --- --- --- --- Digital Input ID 1 S_IO Y
Type Y Y Y Y 7273 --- 1 INT16U R 100 – 199 102 N First digit (1) indicates point is digital input R_DIGIN_TYP_S01 Y
Second digit indicates the digital input module type
Second digit can be used to identify specific hardware options.
0 = Generic digital input
Third digit indicates input type S_IO
1 = AC
2 = DC
Control Mode Y Y Y Y 7274 --- 1 INT16U RWC 0–5 0 N 0 = Normal (Alarm) R_DIGIN_CONTROL_MODE_S01 Y
1 = Demand Interval Sync Pulse
2 = Multi-tariff Control
3 = Input Metering S_IO
4 = Conditional Energy Control
5 = Incremental Energy Reset
Label Y Y Y Y 7275 --- 20 UTF8 RWC --- "Digital Input DI1" Y R_DIGIN_LABEL_S01 S_IO Y
Debounce Time Y Y Y Y 7295 msec 1 INT16U RWC 10 – 1000 10 Y Must be entered in increments of 10ms. R_DIGIN_DEBOUNCE_S01 S_IO Y
Reserved 7296 --- 1 INT16U R N/A N R_RESERVED_7312 S_IO
Base Unit - Digital Input DI2 Y Y Y Y 7297 --- --- --- --- --- --- Digital Input ID 2 S_IO Y
Type Y Y Y Y 7297 --- 1 INT16U R 100 – 199 102 N R_DIGIN_TYP_S02 S_IO Y
Control Mode Y Y Y Y 7298 --- 1 INT16U RWC 0–5 0 N R_DIGIN_CONTROL_MODE_S02 S_IO Y
Label Y Y Y Y 7299 --- 20 UTF8 RWC --- "Digital Input DI2" Y R_DIGIN_LABEL_S02 S_IO Y
Debounce Time Y Y Y Y 7319 msec 1 INT16U RWC 10 – 1000 10 Y Must be entered in increments of 10ms. R_DIGIN_DEBOUNCE_S02 S_IO Y
Reserved 7320 --- 1 INT16U R N/A N R_RESERVED_7338 S_IO
8905 --- --- --- --- --- --- S_IO
Digital Inputs Status Y Y Y Y 8905 --- --- --- --- --- --- S_IO Y
On/Off Status Y Y Y Y 8905 --- --- --- --- --- --- S_IO Y
Digital Input Status – Base Unit Y Y Y Y 8905 --- 2 BITMAP R 0x0000 – 0x000F 0x0000 N R_DIGIN_STATUS_S S_IO Y
Base Unit - Digital Input DI1 Y Y Y Y 8915 --- --- --- --- --- --- Digital Input ID 1 S_IO Y
Count Y Y Y Y 8915 --- 2 INT32U R --- 0 Y R_DIGIN_COUNT_S01 S_IO Y
On Time Y Y Y Y 8917 seconds 2 INT32U R --- 0 Y R_DIGIN_TIME_S01 S_IO Y
Base Unit - Digital Input DI2 Y Y Y Y 8919 --- --- --- --- --- --- Digital Input ID 2 S_IO Y
Count Y Y Y Y 8919 --- 2 INT32U R --- 0 Y R_DIGIN_COUNT_S02 S_IO Y
On Time Y Y Y Y 8921 seconds 2 INT32U R --- 0 Y R_DIGIN_TIME_S02 S_IO Y
9187 --- --- --- --- --- --- S_IO
Digital Outputs Setup Y Y Y Y 9187 --- --- --- --- --- --- S_IO Y
Base Unit - Digital Output DO1 Y Y Y Y 9187 --- --- --- --- --- --- Digital Ouput ID 1 S_IO Y
Type Y Y Y Y 9187 --- 1 INT16U R 201 – 299 201 N First digit (2) indicates point is digital output R_DIGOUT_TYP_S1 Y
Second digit indicates module type
0 = Generic Digital output
Third digit indicates output type S_IO
1 = solid state relay
2 = electromechanical relay
Label Y Y Y Y 9188 --- 20 UTF8 RWC --- "Digital Output DO1" Y R_DIGOUT_LABEL_S1 S_IO Y
Enable/Disable 9208 --- 1 INT16U RWC 0–1 1 Y 0 = Disable, 1 = Enable R_DIGOUT_ENABLE_S1 S_IO
Behavioral Mode Y Y Y Y 9209 --- 1 INT16U RWC 0–2 0 Y 0 = Normal (forced by a control mode of Energy) R_DIGOUT_BEH_MODE_SETUP_S1 Y
1 = Timed (forced by a control mode of Demand Sync) S_IO
2 = Coil Hold
On Time For Timed Mode Y Y Y Y 9210 seconds 1 INT16U RWC --- 1 Y The time for the output to remain energized when the output is R_DIGOUT_TIMER_S1 Y
energized in timed mode. S_IO
Base Unit - Digital Output DO2 Y Y Y Y 9211 --- --- --- --- --- --- Digital Ouput ID 2 S_IO Y
Type Y Y Y Y 9211 --- 1 INT16U R 201 – 299 201 N R_DIGOUT_TYP_S2 S_IO Y
Label Y Y Y Y 9212 --- 20 UTF8 RWC --- "Digital Output DO2" Y R_DIGOUT_LABEL_S2 S_IO Y
Enable/Disable 9232 --- 1 INT16U RWC 0–1 1 Y 0 = Disable, 1 = Enable R_DIGOUT_ENABLE_S2 S_IO
Behavioral Mode Y Y Y Y 9233 --- 1 INT16U RWC 0–2 0 Y 0 = Normal R_DIGOUT_BEH_MODE_SETUP_S2 Y
1 = Timed
2 = Coil Hold S_IO
On Time For Timed Mode Y Y Y Y 9234 seconds 1 INT16U RWC --- 1 Y The time for the output to remain energized when the output is R_DIGOUT_TIMER_S2 Y
energized in timed mode. S_IO
Relay Base Unit - Digital Output DO3 Y Y 9235 --- --- --- --- --- --- Digital Ouput ID 3 S_IO Y
Type Y Y 9235 --- 1 INT16U R 201 – 299 202 N R_DIGOUT_TYP_S3 S_IO Y
Label Y Y 9236 --- 20 UTF8 RWC --- "Relay Output 01" Y R_DIGOUT_LABEL_S3 S_IO Y
Enable/Disable 9256 --- 1 INT16U RWC 0–1 1 Y 0 = Disable, 1 = Enable R_DIGOUT_ENABLE_S3 S_IO
Behavioral Mode Y Y 9257 --- 1 INT16U RWC 0–2 0 Y 0 = Normal R_DIGOUT_BEH_MODE_SETUP_S3 Y
1 = Timed
2 = Coil Hold S_IO
On Time For Timed Mode Y Y 9258 seconds 1 INT16U RWC --- 1 Y The time for the output to remain energized when the output is R_DIGOUT_TIMER_S3 Y
energized in timed mode. S_IO
Relay Base Unit - Digital Output DO4 Y Y 9259 --- --- --- --- --- --- Digital Ouput ID 4 S_IO Y
Type Y Y 9259 --- 1 INT16U R 201 – 299 202 N R_DIGOUT_TYP_S4 S_IO Y
Label Y Y 9260 --- 20 UTF8 RWC --- "Relay output 02" Y R_DIGOUT_LABEL_S4 S_IO Y
Enable/Disable 9280 --- 1 INT16U RWC 0–1 1 Y 0 = Disable, 1 = Enable R_DIGOUT_ENABLE_S4 S_IO
Behavioral Mode Y Y 9281 --- 1 INT16U RWC 0–2 0 Y 0 = Normal R_DIGOUT_BEH_MODE_SETUP_S4 Y
1 = Timed
2 = Coil Hold S_IO
On Time For Timed Mode Y Y 9282 seconds 1 INT16U RWC --- 1 Y The time for the output to remain energized when the output is R_DIGOUT_TIMER_S4 Y
energized in timed mode. S_IO
Enabled Alarm Bitmaps Y Y Y Y Y 11040 --- --- --- --- --- --- S_ALARMS Y
Standard – 1 second 1 Y Y Y Y Y 11040 --- 1 BITMAP R 0 N 0 = Disabled; 1 = Enabled R_ALM_1ST_ENABLED_1 S_ALARMS Y
Standard – 1 second 2 Y Y Y Y Y 11041 --- 1 BITMAP R 0 N R_ALM_1ST_ENABLED_2 S_ALARMS Y
Standard – 1 second 3 Y Y Y Y Y 11042 --- 1 BITMAP R 0 N R_ALM_1ST_ENABLED_3 S_ALARMS Y
Custom – 1 second Y Y Y Y Y 11043 --- 1 BITMAP R 0 N R_ALM_1C_ENABLED S_ALARMS
Standard – High Speed 1 Y Y Y Y Y 11044 --- 1 BITMAP R 0 N R_ALM_HSS_ENABLED_1 S_ALARMS
Standard – High Speed 2 Y Y Y Y Y 11045 --- 1 BITMAP R 0 N R_ALM_HSS_ENABLED_2 S_ALARMS
Custom – High Speed Y Y Y Y Y 11046 --- 1 BITMAP R 0 N R_ALM_HSC_ENABLED S_ALARMS
Disturbance Y Y Y Y Y 11047 --- 1 BITMAP R 0 N R_ALM_DIST_ENABLED S_ALARMS
Transient Y Y Y Y Y 11048 --- 1 BITMAP R 0 N R_ALM_TRANS_ENABLED S_ALARMS
Waveshape Y Y Y Y Y 11049 --- 1 BITMAP R 0 N R_ALM_WS_ENABLED S_ALARMS
Unary Y Y Y Y Y 11050 --- 1 BITMAP R 0 N R_ALM_UNARY_ENABLED S_ALARMS Y
Digital 1 Y Y Y Y Y 11051 --- 1 BITMAP R 0 N R_ALM_DIG_ENABLED_1 S_ALARMS Y
Digital 2 Y Y Y Y Y 11052 --- 1 BITMAP R 0 N R_ALM_DIG_ENABLED_2 S_ALARMS
Digital 3 Y Y Y Y Y 11053 --- 1 BITMAP R 0 N R_ALM_DIG_ENABLED_3 S_ALARMS
Digital 4 Y Y Y Y Y 11054 --- 1 BITMAP R 0 N R_ALM_DIG_ENABLED_4 S_ALARMS
Digital 5 Y Y Y Y Y 11055 --- 1 BITMAP R 0 N R_ALM_DIG_ENABLED_5 S_ALARMS
Binary Y Y Y Y Y 11056 --- 1 BITMAP R 0 N R_ALM_BOOL_ENABLED S_ALARMS
Time_of_day Y Y Y Y Y 11057 --- 1 BITMAP R 0 N R_ALM_TOD_ENABLED S_ALARMS
Logic Y Y Y Y Y 11058 --- 1 BITMAP R 0 N R_ALM_LOGIC_ENABLED S_ALARMS
Detected Alarm Bitmaps Y Y Y Y Y 11059 --- --- --- --- --- --- S_ALARMS Y
Standard – 1 second Group 1 Y Y Y Y Y 11059 --- 1 BITMAP R 0 N 0 = Not Detected; 1 = Detected R_ALM_1ST_DETECTED_1 S_ALARMS Y
Standard – 1 second Group 2 Y Y Y Y Y 11060 --- 1 BITMAP R 0 N R_ALM_1ST_DETECTED_2 S_ALARMS Y
Standard – 1 second Group 3 Y Y Y Y Y 11061 --- 1 BITMAP R 0 N R_ALM_1ST_DETECTED_3 S_ALARMS Y
Custom – 1 second Y Y Y Y Y 11062 --- 1 BITMAP R 0 N R_ALM_1C_DETECTED S_ALARMS
Standard – High Speed Group 1 Y Y Y Y Y 11063 --- 1 BITMAP R 0 N R_ALM_HSS_DETECTED_1 S_ALARMS
Standard – High Speed Group 2 Y Y Y Y Y 11064 --- 1 BITMAP R 0 N R_ALM_HSS_DETECTED_2 S_ALARMS
Custom – High Speed Y Y Y Y Y 11065 --- 1 BITMAP R 0 N R_ALM_HSC_DETECTED S_ALARMS
Disturbance Y Y Y Y Y 11066 --- 1 BITMAP R 0 N R_ALM_DIST_DETECTED S_ALARMS
Transient Y Y Y Y Y 11067 --- 1 BITMAP R 0 N R_ALM_TRANS_DETECTED S_ALARMS
Waveshape Y Y Y Y Y 11068 --- 1 BITMAP R 0 N R_ALM_WS_DETECTED S_ALARMS
Unary Y Y Y Y Y 11069 --- 1 BITMAP R 0 N R_ALM_UNARY_DETECTED S_ALARMS Y
Digital Group 1 Y Y Y Y Y 11070 --- 1 BITMAP R 0 N R_ALM_DIG_DETECTED_1 S_ALARMS Y
Digital Group 2 Y Y Y Y Y 11071 --- 1 BITMAP R 0 N R_ALM_DIG_DETECTED_2 S_ALARMS
Digital Group 3 Y Y Y Y Y 11072 --- 1 BITMAP R 0 N R_ALM_DIG_DETECTED_3 S_ALARMS
Digital Group 4 Y Y Y Y Y 11073 --- 1 BITMAP R 0 N R_ALM_DIG_DETECTED_4 S_ALARMS
Digital Group 5 Y Y Y Y Y 11074 --- 1 BITMAP R 0 N R_ALM_DIG_DETECTED_5 S_ALARMS
Binary Y Y Y Y Y 11075 --- 1 BITMAP R 0 N R_ALM_BOOL_DETECTED S_ALARMS
Time_of_day Y Y Y Y Y 11076 --- 1 BITMAP R 0 N R_ALM_TOD_DETECTED S_ALARMS
Logic Y Y Y Y Y 11077 --- 1 BITMAP R 0 N R_ALM_LOGIC_DETECTED S_ALARMS
Unacknowledged High Priority Alarm Bitmaps Y Y Y Y Y 11078 --- --- --- --- --- --- S_ALARMS Y
Standard – 1 second 1 Y Y Y Y Y 11078 --- 1 BITMAP R 0 N 0 = Acknowledged; 1 = Unacknowledged R_ALM_1ST_UNACK_1 S_ALARMS Y
Standard – 1 second 2 Y Y Y Y Y 11079 --- 1 BITMAP R 0 N R_ALM_1ST_UNACK_2 S_ALARMS Y
Standard – 1 second 3 Y Y Y Y Y 11080 --- 1 BITMAP R 0 N R_ALM_1ST_UNACK_3 S_ALARMS Y
Custom – 1 second Y Y Y Y Y 11081 --- 1 BITMAP R 0 N R_ALM_1C_UNACK S_ALARMS
Standard – High Speed 1 Y Y Y Y Y 11082 --- 1 BITMAP R 0 N R_ALM_HSS_UNACK_1 S_ALARMS
Standard – High Speed 2 Y Y Y Y Y 11083 --- 1 BITMAP R 0 N R_ALM_HSS_UNACK_2 S_ALARMS
Custom – High Speed Y Y Y Y Y 11084 --- 1 BITMAP R 0 N R_ALM_HSC_UNACK S_ALARMS
Disturbance Y Y Y Y Y 11085 --- 1 BITMAP R 0 N R_ALM_DIST_UNACK S_ALARMS
Transient Y Y Y Y Y 11086 --- 1 BITMAP R 0 N R_ALM_TRANS_UNACK S_ALARMS
Waveshape Y Y Y Y Y 11087 --- 1 BITMAP R 0 N R_ALM_WS_UNACK S_ALARMS
Unary Y Y Y Y Y 11088 --- 1 BITMAP R 0 N R_ALM_UNARY_UNACK S_ALARMS Y
Digital 1 Y Y Y Y Y 11089 --- 1 BITMAP R 0 N R_ALM_DIG_UNACK_1 S_ALARMS Y
Digital 2 Y Y Y Y Y 11090 --- 1 BITMAP R 0 N R_ALM_DIG_UNACK_2 S_ALARMS
Digital 3 Y Y Y Y Y 11091 --- 1 BITMAP R 0 N R_ALM_DIG_UNACK_3 S_ALARMS
Digital 4 Y Y Y Y Y 11092 --- 1 BITMAP R 0 N R_ALM_DIG_UNACK_4 S_ALARMS
Digital 5 Y Y Y Y Y 11093 --- 1 BITMAP R 0 N R_ALM_DIG_UNACK_5 S_ALARMS
Binary Y Y Y Y Y 11094 --- 1 BITMAP R 0 N R_ALM_BOOL_UNACK S_ALARMS
Time_of_day Y Y Y Y Y 11095 --- 1 BITMAP R 0 N R_ALM_TOD_UNACK S_ALARMS
Logic Y Y Y Y Y 11096 --- 1 BITMAP R 0 N R_ALM_LOGIC_UNACK S_ALARMS
Reserved 11097 --- 14 INT16U R --- N/A N R_RESERVED_9067 S_ALARMS
11111 --- --- --- --- --- --- S_ALARMS
11111 --- S_ALARMS
Alarm Event Queue Y Y Y Y Y 11111 --- --- --- --- --- --- S_ALARMS Y
Version of Event Queue Y Y Y Y Y 11111 --- 1 INT16U R 0 N R_ALM_EVT_QUE_VERSION S_ALARMS Y
Event Types to Log 11112 1 INT16U RWC 0x0000 - 0xFFFF 0xFFFF Y R_ALM_EVT_QUE_EVT_TYPES S_ALARMS
Size of Event Queue Y Y Y Y Y 11113 --- 1 INT16U R 100 N R_ALM_EVT_QUE_SIZE S_ALARMS Y
Number of Entries in Event Queue Y Y Y Y Y 11114 --- 1 INT16U R 0 – 100 0 Y R_ALM_EVT_QUE_NUM_EVENTS S_ALARMS Y
Entry Number of Most Recent Event Y Y Y Y Y 11115 --- 1 INT16U R 0 Y Rolls over from 65535 to 0. R_ALM_EVT_QUE_MOST_RECENT S_ALARMS Y
Entry 001 Y Y Y Y Y 11116 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11116 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_001 S_ALARMS Y
Date/Time Y Y Y Y Y 11117 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_001 S_ALARMS Y
Record Type Y Y Y Y Y 11121 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_001 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11122 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_001 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11123 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_001 S_ALARMS Y
Sequence Number Y Y Y Y Y 11127 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_001 S_ALARMS Y
Entry 002 Y Y Y Y Y 11128 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11128 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_002 S_ALARMS Y
Date/Time Y Y Y Y Y 11129 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_002 S_ALARMS Y
Record Type Y Y Y Y Y 11133 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_002 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11134 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_002 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11135 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_002 S_ALARMS Y
Sequence Number Y Y Y Y Y 11139 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_002 S_ALARMS Y
Entry 003 Y Y Y Y Y 11140 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11140 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_003 S_ALARMS Y
Date/Time Y Y Y Y Y 11141 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_003 S_ALARMS Y
Record Type Y Y Y Y Y 11145 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_003 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11146 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_003 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11147 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_003 S_ALARMS Y
Sequence Number Y Y Y Y Y 11151 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_003 S_ALARMS Y
Entry 004 Y Y Y Y Y 11152 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11152 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_004 S_ALARMS Y
Date/Time Y Y Y Y Y 11153 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_004 S_ALARMS Y
Record Type Y Y Y Y Y 11157 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_004 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11158 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_004 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11159 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_004 S_ALARMS Y
Sequence Number Y Y Y Y Y 11163 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_004 S_ALARMS Y
Entry 005 Y Y Y Y Y 11164 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11164 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_005 S_ALARMS Y
Date/Time Y Y Y Y Y 11165 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_005 S_ALARMS Y
Record Type Y Y Y Y Y 11169 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_005 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11170 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_005 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11171 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_005 S_ALARMS Y
Sequence Number Y Y Y Y Y 11175 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_005 S_ALARMS Y
Entry 006 Y Y Y Y Y 11176 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11176 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_006 S_ALARMS Y
Date/Time Y Y Y Y Y 11177 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_006 S_ALARMS Y
Record Type Y Y Y Y Y 11181 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_006 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11182 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_006 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11183 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_006 S_ALARMS Y
Sequence Number Y Y Y Y Y 11187 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_006 S_ALARMS Y
Entry 007 Y Y Y Y Y 11188 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11188 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_007 S_ALARMS Y
Date/Time Y Y Y Y Y 11189 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_007 S_ALARMS Y
Record Type Y Y Y Y Y 11193 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_007 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11194 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_007 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11195 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_007 S_ALARMS Y
Sequence Number Y Y Y Y Y 11199 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_007 S_ALARMS Y
Entry 008 Y Y Y Y Y 11200 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11200 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_008 S_ALARMS Y
Date/Time Y Y Y Y Y 11201 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_008 S_ALARMS Y
Record Type Y Y Y Y Y 11205 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_008 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11206 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_008 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11207 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_008 S_ALARMS Y
Sequence Number Y Y Y Y Y 11211 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_008 S_ALARMS Y
Entry 009 Y Y Y Y Y 11212 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11212 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_009 S_ALARMS Y
Date/Time Y Y Y Y Y 11213 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_009 S_ALARMS Y
Record Type Y Y Y Y Y 11217 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_009 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11218 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_009 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11219 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_009 S_ALARMS Y
Sequence Number Y Y Y Y Y 11223 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_009 S_ALARMS Y
Entry 010 Y Y Y Y Y 11224 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11224 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_010 S_ALARMS Y
Date/Time Y Y Y Y Y 11225 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_010 S_ALARMS Y
Record Type Y Y Y Y Y 11229 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_010 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11230 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_010 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11231 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_010 S_ALARMS Y
Sequence Number Y Y Y Y Y 11235 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_010 S_ALARMS Y
Entry 011 Y Y Y Y Y 11236 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11236 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_011 S_ALARMS Y
Date/Time Y Y Y Y Y 11237 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_011 S_ALARMS Y
Record Type Y Y Y Y Y 11241 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_011 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11242 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_011 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11243 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_011 S_ALARMS Y
Sequence Number Y Y Y Y Y 11247 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_011 S_ALARMS Y
Entry 012 Y Y Y Y Y 11248 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11248 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_012 S_ALARMS Y
Date/Time Y Y Y Y Y 11249 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_012 S_ALARMS Y
Record Type Y Y Y Y Y 11253 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_012 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11254 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_012 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11255 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_012 S_ALARMS Y
Sequence Number Y Y Y Y Y 11259 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_012 S_ALARMS Y
Entry 013 Y Y Y Y Y 11260 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11260 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_013 S_ALARMS Y
Date/Time Y Y Y Y Y 11261 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_013 S_ALARMS Y
Record Type Y Y Y Y Y 11265 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_013 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11266 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_013 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11267 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_013 S_ALARMS Y
Sequence Number Y Y Y Y Y 11271 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_013 S_ALARMS Y
Entry 014 Y Y Y Y Y 11272 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11272 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_014 S_ALARMS Y
Date/Time Y Y Y Y Y 11273 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_014 S_ALARMS Y
Record Type Y Y Y Y Y 11277 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_014 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11278 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_014 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11279 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_014 S_ALARMS Y
Sequence Number Y Y Y Y Y 11283 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_014 S_ALARMS Y
Entry 015 Y Y Y Y Y 11284 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11284 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_015 S_ALARMS Y
Date/Time Y Y Y Y Y 11285 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_015 S_ALARMS Y
Record Type Y Y Y Y Y 11289 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_015 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11290 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_015 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11291 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_015 S_ALARMS Y
Sequence Number Y Y Y Y Y 11295 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_015 S_ALARMS Y
Entry 016 Y Y Y Y Y 11296 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11296 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_016 S_ALARMS Y
Date/Time Y Y Y Y Y 11297 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_016 S_ALARMS Y
Record Type Y Y Y Y Y 11301 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_016 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11302 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_016 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11303 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_016 S_ALARMS Y
Sequence Number Y Y Y Y Y 11307 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_016 S_ALARMS Y
Entry 017 Y Y Y Y Y 11308 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11308 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_017 S_ALARMS Y
Date/Time Y Y Y Y Y 11309 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_017 S_ALARMS Y
Record Type Y Y Y Y Y 11313 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_017 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11314 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_017 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11315 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_017 S_ALARMS Y
Sequence Number Y Y Y Y Y 11319 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_017 S_ALARMS Y
Entry 018 Y Y Y Y Y 11320 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11320 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_018 S_ALARMS Y
Date/Time Y Y Y Y Y 11321 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_018 S_ALARMS Y
Record Type Y Y Y Y Y 11325 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_018 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11326 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_018 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11327 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_018 S_ALARMS Y
Sequence Number Y Y Y Y Y 11331 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_018 S_ALARMS Y
Entry 019 Y Y Y Y Y 11332 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11332 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_019 S_ALARMS Y
Date/Time Y Y Y Y Y 11333 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_019 S_ALARMS Y
Record Type Y Y Y Y Y 11337 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_019 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11338 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_019 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11339 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_019 S_ALARMS Y
Sequence Number Y Y Y Y Y 11343 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_019 S_ALARMS Y
Entry 020 Y Y Y Y Y 11344 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11344 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_020 S_ALARMS Y
Date/Time Y Y Y Y Y 11345 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_020 S_ALARMS Y
Record Type Y Y Y Y Y 11349 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_020 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11350 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_020 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11351 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_020 S_ALARMS Y
Sequence Number Y Y Y Y Y 11355 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_020 S_ALARMS Y
Entry 021 Y Y Y Y Y 11356 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11356 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_021 S_ALARMS Y
Date/Time Y Y Y Y Y 11357 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_021 S_ALARMS Y
Record Type Y Y Y Y Y 11361 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_021 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11362 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_021 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11363 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_021 S_ALARMS Y
Sequence Number Y Y Y Y Y 11367 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_021 S_ALARMS Y
Entry 022 Y Y Y Y Y 11368 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11368 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_022 S_ALARMS Y
Date/Time Y Y Y Y Y 11369 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_022 S_ALARMS Y
Record Type Y Y Y Y Y 11373 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_022 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11374 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_022 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11375 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_022 S_ALARMS Y
Sequence Number Y Y Y Y Y 11379 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_022 S_ALARMS Y
Entry 023 Y Y Y Y Y 11380 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11380 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_023 S_ALARMS Y
Date/Time Y Y Y Y Y 11381 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_023 S_ALARMS Y
Record Type Y Y Y Y Y 11385 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_023 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11386 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_023 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11387 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_023 S_ALARMS Y
Sequence Number Y Y Y Y Y 11391 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_023 S_ALARMS Y
Entry 024 Y Y Y Y Y 11392 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11392 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_024 S_ALARMS Y
Date/Time Y Y Y Y Y 11393 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_024 S_ALARMS Y
Record Type Y Y Y Y Y 11397 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_024 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11398 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_024 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11399 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_024 S_ALARMS Y
Sequence Number Y Y Y Y Y 11403 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_024 S_ALARMS Y
Entry 025 Y Y Y Y Y 11404 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11404 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_025 S_ALARMS Y
Date/Time Y Y Y Y Y 11405 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_025 S_ALARMS Y
Record Type Y Y Y Y Y 11409 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_025 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11410 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_025 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11411 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_025 S_ALARMS Y
Sequence Number Y Y Y Y Y 11415 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_025 S_ALARMS Y
Entry 026 Y Y Y Y Y 11416 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11416 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_026 S_ALARMS Y
Date/Time Y Y Y Y Y 11417 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_026 S_ALARMS Y
Record Type Y Y Y Y Y 11421 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_026 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11422 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_026 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11423 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_026 S_ALARMS Y
Sequence Number Y Y Y Y Y 11427 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_026 S_ALARMS Y
Entry 027 Y Y Y Y Y 11428 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11428 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_027 S_ALARMS Y
Date/Time Y Y Y Y Y 11429 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_027 S_ALARMS Y
Record Type Y Y Y Y Y 11433 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_027 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11434 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_027 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11435 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_027 S_ALARMS Y
Sequence Number Y Y Y Y Y 11439 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_027 S_ALARMS Y
Entry 028 Y Y Y Y Y 11440 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11440 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_028 S_ALARMS Y
Date/Time Y Y Y Y Y 11441 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_028 S_ALARMS Y
Record Type Y Y Y Y Y 11445 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_028 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11446 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_028 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11447 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_028 S_ALARMS Y
Sequence Number Y Y Y Y Y 11451 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_028 S_ALARMS Y
Entry 029 Y Y Y Y Y 11452 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11452 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_029 S_ALARMS Y
Date/Time Y Y Y Y Y 11453 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_029 S_ALARMS Y
Record Type Y Y Y Y Y 11457 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_029 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11458 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_029 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11459 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_029 S_ALARMS Y
Sequence Number Y Y Y Y Y 11463 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_029 S_ALARMS Y
Entry 030 Y Y Y Y Y 11464 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11464 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_030 S_ALARMS Y
Date/Time Y Y Y Y Y 11465 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_030 S_ALARMS Y
Record Type Y Y Y Y Y 11469 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_030 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11470 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_030 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11471 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_030 S_ALARMS Y
Sequence Number Y Y Y Y Y 11475 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_030 S_ALARMS Y
Entry 031 Y Y Y Y Y 11476 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11476 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_031 S_ALARMS Y
Date/Time Y Y Y Y Y 11477 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_031 S_ALARMS Y
Record Type Y Y Y Y Y 11481 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_031 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11482 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_031 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11483 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_031 S_ALARMS Y
Sequence Number Y Y Y Y Y 11487 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_031 S_ALARMS Y
Entry 032 Y Y Y Y Y 11488 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11488 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_032 S_ALARMS Y
Date/Time Y Y Y Y Y 11489 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_032 S_ALARMS Y
Record Type Y Y Y Y Y 11493 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_032 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11494 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_032 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11495 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_032 S_ALARMS Y
Sequence Number Y Y Y Y Y 11499 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_032 S_ALARMS Y
Entry 033 Y Y Y Y Y 11500 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11500 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_033 S_ALARMS Y
Date/Time Y Y Y Y Y 11501 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_033 S_ALARMS Y
Record Type Y Y Y Y Y 11505 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_033 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11506 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_033 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11507 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_033 S_ALARMS Y
Sequence Number Y Y Y Y Y 11511 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_033 S_ALARMS Y
Entry 034 Y Y Y Y Y 11512 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11512 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_034 S_ALARMS Y
Date/Time Y Y Y Y Y 11513 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_034 S_ALARMS Y
Record Type Y Y Y Y Y 11517 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_034 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11518 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_034 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11519 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_034 S_ALARMS Y
Sequence Number Y Y Y Y Y 11523 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_034 S_ALARMS Y
Entry 035 Y Y Y Y Y 11524 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11524 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_035 S_ALARMS Y
Date/Time Y Y Y Y Y 11525 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_035 S_ALARMS Y
Record Type Y Y Y Y Y 11529 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_035 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11530 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_035 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11531 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_035 S_ALARMS Y
Sequence Number Y Y Y Y Y 11535 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_035 S_ALARMS Y
Entry 036 Y Y Y Y Y 11536 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11536 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_036 S_ALARMS Y
Date/Time Y Y Y Y Y 11537 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_036 S_ALARMS Y
Record Type Y Y Y Y Y 11541 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_036 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11542 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_036 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11543 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_036 S_ALARMS Y
Sequence Number Y Y Y Y Y 11547 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_036 S_ALARMS Y
Entry 037 Y Y Y Y Y 11548 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11548 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_037 S_ALARMS Y
Date/Time Y Y Y Y Y 11549 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_037 S_ALARMS Y
Record Type Y Y Y Y Y 11553 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_037 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11554 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_037 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11555 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_037 S_ALARMS Y
Sequence Number Y Y Y Y Y 11559 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_037 S_ALARMS Y
Entry 038 Y Y Y Y Y 11560 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11560 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_038 S_ALARMS Y
Date/Time Y Y Y Y Y 11561 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_038 S_ALARMS Y
Record Type Y Y Y Y Y 11565 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_038 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11566 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_038 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11567 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_038 S_ALARMS Y
Sequence Number Y Y Y Y Y 11571 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_038 S_ALARMS Y
Entry 039 Y Y Y Y Y 11572 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11572 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_039 S_ALARMS Y
Date/Time Y Y Y Y Y 11573 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_039 S_ALARMS Y
Record Type Y Y Y Y Y 11577 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_039 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11578 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_039 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11579 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_039 S_ALARMS Y
Sequence Number Y Y Y Y Y 11583 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_039 S_ALARMS Y
Entry 040 Y Y Y Y Y 11584 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 11584 --- 1 INT16U R N/A N R_ALM_EVT_QUE_ENTRY_040 S_ALARMS Y
Date/Time Y Y Y Y Y 11585 --- 4 DATETIME R N/A N R_ALM_EVT_QUE_DT_040 S_ALARMS Y
Record Type Y Y Y Y Y 11589 --- 1 INT16U R N/A N The high byte shall be 0xFF R_ALM_EVT_QUE_REC_TYPE_040 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 11590 --- 1 INT16U R N/A N See Event Codes for secondary events and R_ALM_EVT_QUE_EVT_ID_040 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 11591 --- 4 INT16U R N/A N R_ALM_EVT_QUE_VAL_040 S_ALARMS Y
Sequence Number Y Y Y Y Y 11595 --- 1 INT16U R N/A N R_ALM_EVT_QUE_SN_040 S_ALARMS Y
12316 --- --- --- --- --- --- S_ALARMS
Alarm History Log Y Y Y Y Y 12316 --- --- --- --- --- --- S_ALARMS Y
Size of History Log Y Y Y Y Y 12316 --- 1 INT16U R 25 N R_ALM_AGG_HIST_SIZE S_ALARMS Y
Number of Entries in History Log Y Y Y Y Y 12317 --- 1 INT16U R 0 Y R_ALM_AGG_HIST_NUM_EVENTS S_ALARMS Y
Entry Number of Most Recent Event Y Y Y Y Y 12318 --- 1 INT16U R 0 Y Value rolls over from 65535 (0xFFFF) to 0. R_ALM_AGG_HIST_MOST_RECENT S_ALARMS Y
Entry 001 Y Y Y Y Y 12319 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12319 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_001 S_ALARMS Y
Date/Time Y Y Y Y Y 12320 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_001 S_ALARMS Y
Record Type Y Y Y Y Y 12324 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_001 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12325 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_001 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12326 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_001 S_ALARMS Y
Sequence Number Y Y Y Y Y 12330 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_001 S_ALARMS Y
Entry 002 Y Y Y Y Y 12331 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12331 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_002 S_ALARMS Y
Date/Time Y Y Y Y Y 12332 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_002 S_ALARMS Y
Record Type Y Y Y Y Y 12336 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_002 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12337 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_002 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12338 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_002 S_ALARMS Y
Sequence Number Y Y Y Y Y 12342 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_002 S_ALARMS Y
Entry 003 Y Y Y Y Y 12343 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12343 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_003 S_ALARMS Y
Date/Time Y Y Y Y Y 12344 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_003 S_ALARMS Y
Record Type Y Y Y Y Y 12348 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_003 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12349 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_003 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12350 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_003 S_ALARMS Y
Sequence Number Y Y Y Y Y 12354 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_003 S_ALARMS Y
Entry 004 Y Y Y Y Y 12355 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12355 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_004 S_ALARMS Y
Date/Time Y Y Y Y Y 12356 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_004 S_ALARMS Y
Record Type Y Y Y Y Y 12360 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_004 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12361 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_004 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12362 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_004 S_ALARMS Y
Sequence Number Y Y Y Y Y 12366 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_004 S_ALARMS Y
Entry 005 Y Y Y Y Y 12367 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12367 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_005 S_ALARMS Y
Date/Time Y Y Y Y Y 12368 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_005 S_ALARMS Y
Record Type Y Y Y Y Y 12372 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_005 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12373 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_005 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12374 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_005 S_ALARMS Y
Sequence Number Y Y Y Y Y 12378 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_005 S_ALARMS Y
Entry 006 Y Y Y Y Y 12379 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12379 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_006 S_ALARMS Y
Date/Time Y Y Y Y Y 12380 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_006 S_ALARMS Y
Record Type Y Y Y Y Y 12384 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_006 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12385 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_006 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12386 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_006 S_ALARMS Y
Sequence Number Y Y Y Y Y 12390 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_006 S_ALARMS Y
Entry 007 Y Y Y Y Y 12391 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12391 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_007 S_ALARMS Y
Date/Time Y Y Y Y Y 12392 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_007 S_ALARMS Y
Record Type Y Y Y Y Y 12396 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_007 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12397 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_007 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12398 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_007 S_ALARMS Y
Sequence Number Y Y Y Y Y 12402 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_007 S_ALARMS Y
Entry 008 Y Y Y Y Y 12403 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12403 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_008 S_ALARMS Y
Date/Time Y Y Y Y Y 12404 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_008 S_ALARMS Y
Record Type Y Y Y Y Y 12408 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_008 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12409 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_008 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12410 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_008 S_ALARMS Y
Sequence Number Y Y Y Y Y 12414 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_008 S_ALARMS Y
Entry 009 Y Y Y Y Y 12415 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12415 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_009 S_ALARMS Y
Date/Time Y Y Y Y Y 12416 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_009 S_ALARMS Y
Record Type Y Y Y Y Y 12420 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_009 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12421 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_009 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12422 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_009 S_ALARMS Y
Sequence Number Y Y Y Y Y 12426 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_009 S_ALARMS Y
Entry 010 Y Y Y Y Y 12427 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12427 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_010 S_ALARMS Y
Date/Time Y Y Y Y Y 12428 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_010 S_ALARMS Y
Record Type Y Y Y Y Y 12432 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_010 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12433 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_010 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12434 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_010 S_ALARMS Y
Sequence Number Y Y Y Y Y 12438 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_010 S_ALARMS Y
Entry 011 Y Y Y Y Y 12439 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12439 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_011 S_ALARMS Y
Date/Time Y Y Y Y Y 12440 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_011 S_ALARMS Y
Record Type Y Y Y Y Y 12444 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_011 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12445 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_011 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12446 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_011 S_ALARMS Y
Sequence Number Y Y Y Y Y 12450 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_011 S_ALARMS Y
Entry 012 Y Y Y Y Y 12451 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12451 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_012 S_ALARMS Y
Date/Time Y Y Y Y Y 12452 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_012 S_ALARMS Y
Record Type Y Y Y Y Y 12456 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_012 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12457 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_012 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12458 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_012 S_ALARMS Y
Sequence Number Y Y Y Y Y 12462 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_012 S_ALARMS Y
Entry 013 Y Y Y Y Y 12463 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12463 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_013 S_ALARMS Y
Date/Time Y Y Y Y Y 12464 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_013 S_ALARMS Y
Record Type Y Y Y Y Y 12468 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_013 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12469 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_013 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12470 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_013 S_ALARMS Y
Sequence Number Y Y Y Y Y 12474 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_013 S_ALARMS Y
Entry 014 Y Y Y Y Y 12475 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12475 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_014 S_ALARMS Y
Date/Time Y Y Y Y Y 12476 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_014 S_ALARMS Y
Record Type Y Y Y Y Y 12480 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_014 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12481 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_014 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12482 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_014 S_ALARMS Y
Sequence Number Y Y Y Y Y 12486 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_014 S_ALARMS Y
Entry 015 Y Y Y Y Y 12487 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12487 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_015 S_ALARMS Y
Date/Time Y Y Y Y Y 12488 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_015 S_ALARMS Y
Record Type Y Y Y Y Y 12492 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_015 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12493 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_015 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12494 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_015 S_ALARMS Y
Sequence Number Y Y Y Y Y 12498 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_015 S_ALARMS Y
Entry 016 Y Y Y Y Y 12499 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12499 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_016 S_ALARMS Y
Date/Time Y Y Y Y Y 12500 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_016 S_ALARMS Y
Record Type Y Y Y Y Y 12504 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_016 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12505 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_016 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12506 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_016 S_ALARMS Y
Sequence Number Y Y Y Y Y 12510 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_016 S_ALARMS Y
Entry 017 Y Y Y Y Y 12511 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12511 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_017 S_ALARMS Y
Date/Time Y Y Y Y Y 12512 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_017 S_ALARMS Y
Record Type Y Y Y Y Y 12516 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_017 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12517 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_017 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12518 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_017 S_ALARMS Y
Sequence Number Y Y Y Y Y 12522 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_017 S_ALARMS Y
Entry 018 Y Y Y Y Y 12523 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12523 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_018 S_ALARMS Y
Date/Time Y Y Y Y Y 12524 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_018 S_ALARMS Y
Record Type Y Y Y Y Y 12528 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_018 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12529 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_018 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12530 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_018 S_ALARMS Y
Sequence Number Y Y Y Y Y 12534 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_018 S_ALARMS Y
Entry 019 Y Y Y Y Y 12535 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12535 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_019 S_ALARMS Y
Date/Time Y Y Y Y Y 12536 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_019 S_ALARMS Y
Record Type Y Y Y Y Y 12540 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_019 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12541 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_019 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12542 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_019 S_ALARMS Y
Sequence Number Y Y Y Y Y 12546 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_019 S_ALARMS Y
Entry 020 Y Y Y Y Y 12547 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12547 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_020 S_ALARMS Y
Date/Time Y Y Y Y Y 12548 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_020 S_ALARMS Y
Record Type Y Y Y Y Y 12552 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_020 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12553 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_020 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12554 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_020 S_ALARMS Y
Sequence Number Y Y Y Y Y 12558 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_020 S_ALARMS Y
Entry 021 Y Y Y Y Y 12559 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12559 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_021 S_ALARMS Y
Date/Time Y Y Y Y Y 12560 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_021 S_ALARMS Y
Record Type Y Y Y Y Y 12564 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_021 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12565 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_021 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12566 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_021 S_ALARMS Y
Sequence Number Y Y Y Y Y 12570 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_021 S_ALARMS Y
Entry 022 Y Y Y Y Y 12571 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12571 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_022 S_ALARMS Y
Date/Time Y Y Y Y Y 12572 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_022 S_ALARMS Y
Record Type Y Y Y Y Y 12576 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_022 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12577 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_022 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12578 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_022 S_ALARMS Y
Sequence Number Y Y Y Y Y 12582 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_022 S_ALARMS Y
Entry 023 Y Y Y Y Y 12583 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12583 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_023 S_ALARMS Y
Date/Time Y Y Y Y Y 12584 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_023 S_ALARMS Y
Record Type Y Y Y Y Y 12588 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_023 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12589 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_023 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12590 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_023 S_ALARMS Y
Sequence Number Y Y Y Y Y 12594 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_023 S_ALARMS Y
Entry 024 Y Y Y Y Y 12595 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12595 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_024 S_ALARMS Y
Date/Time Y Y Y Y Y 12596 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_024 S_ALARMS Y
Record Type Y Y Y Y Y 12600 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_024 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12601 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_024 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12602 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_024 S_ALARMS Y
Sequence Number Y Y Y Y Y 12606 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_024 S_ALARMS Y
Entry 025 Y Y Y Y Y 12607 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12607 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_025 S_ALARMS Y
Date/Time Y Y Y Y Y 12608 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_025 S_ALARMS Y
Record Type Y Y Y Y Y 12612 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_025 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12613 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_025 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12614 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_025 S_ALARMS Y
Sequence Number Y Y Y Y Y 12618 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_025 S_ALARMS Y
Entry 026 Y Y Y Y Y 12619 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12619 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_026 S_ALARMS Y
Date/Time Y Y Y Y Y 12620 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_026 S_ALARMS Y
Record Type Y Y Y Y Y 12624 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_026 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12625 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_026 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12626 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_026 S_ALARMS Y
Sequence Number Y Y Y Y Y 12630 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_026 S_ALARMS Y
Entry 027 Y Y Y Y Y 12631 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12631 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_027 S_ALARMS Y
Date/Time Y Y Y Y Y 12632 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_027 S_ALARMS Y
Record Type Y Y Y Y Y 12636 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_027 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12637 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_027 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12638 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_027 S_ALARMS Y
Sequence Number Y Y Y Y Y 12642 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_027 S_ALARMS Y
Entry 028 Y Y Y Y Y 12643 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12643 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_028 S_ALARMS Y
Date/Time Y Y Y Y Y 12644 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_028 S_ALARMS Y
Record Type Y Y Y Y Y 12648 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_028 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12649 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_028 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12650 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_028 S_ALARMS Y
Sequence Number Y Y Y Y Y 12654 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_028 S_ALARMS Y
Entry 029 Y Y Y Y Y 12655 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12655 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_029 S_ALARMS Y
Date/Time Y Y Y Y Y 12656 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_029 S_ALARMS Y
Record Type Y Y Y Y Y 12660 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_029 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12661 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_029 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12662 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_029 S_ALARMS Y
Sequence Number Y Y Y Y Y 12666 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_029 S_ALARMS Y
Entry 030 Y Y Y Y Y 12667 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12667 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_030 S_ALARMS Y
Date/Time Y Y Y Y Y 12668 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_030 S_ALARMS Y
Record Type Y Y Y Y Y 12672 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_030 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12673 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_030 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12674 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_030 S_ALARMS Y
Sequence Number Y Y Y Y Y 12678 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_030 S_ALARMS Y
Entry 031 Y Y Y Y Y 12679 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12679 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_031 S_ALARMS Y
Date/Time Y Y Y Y Y 12680 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_031 S_ALARMS Y
Record Type Y Y Y Y Y 12684 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_031 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12685 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_031 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12686 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_031 S_ALARMS Y
Sequence Number Y Y Y Y Y 12690 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_031 S_ALARMS Y
Entry 032 Y Y Y Y Y 12691 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12691 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_032 S_ALARMS Y
Date/Time Y Y Y Y Y 12692 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_032 S_ALARMS Y
Record Type Y Y Y Y Y 12696 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_032 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12697 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_032 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12698 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_032 S_ALARMS Y
Sequence Number Y Y Y Y Y 12702 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_032 S_ALARMS Y
Entry 033 Y Y Y Y Y 12703 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12703 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_033 S_ALARMS Y
Date/Time Y Y Y Y Y 12704 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_033 S_ALARMS Y
Record Type Y Y Y Y Y 12708 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_033 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12709 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_033 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12710 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_033 S_ALARMS Y
Sequence Number Y Y Y Y Y 12714 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_033 S_ALARMS Y
Entry 034 Y Y Y Y Y 12715 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12715 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_034 S_ALARMS Y
Date/Time Y Y Y Y Y 12716 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_034 S_ALARMS Y
Record Type Y Y Y Y Y 12720 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_034 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12721 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_034 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12722 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_034 S_ALARMS Y
Sequence Number Y Y Y Y Y 12726 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_034 S_ALARMS Y
Entry 035 Y Y Y Y Y 12727 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12727 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_035 S_ALARMS Y
Date/Time Y Y Y Y Y 12728 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_035 S_ALARMS Y
Record Type Y Y Y Y Y 12732 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_035 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12733 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_035 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12734 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_035 S_ALARMS Y
Sequence Number Y Y Y Y Y 12738 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_035 S_ALARMS Y
Entry 036 Y Y Y Y Y 12739 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12739 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_036 S_ALARMS Y
Date/Time Y Y Y Y Y 12740 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_036 S_ALARMS Y
Record Type Y Y Y Y Y 12744 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_036 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12745 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_036 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12746 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_036 S_ALARMS Y
Sequence Number Y Y Y Y Y 12750 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_036 S_ALARMS Y
Entry 037 Y Y Y Y Y 12751 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12751 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_037 S_ALARMS Y
Date/Time Y Y Y Y Y 12752 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_037 S_ALARMS Y
Record Type Y Y Y Y Y 12756 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_037 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12757 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_037 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12758 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_037 S_ALARMS Y
Sequence Number Y Y Y Y Y 12762 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_037 S_ALARMS Y
Entry 038 Y Y Y Y Y 12763 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12763 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_038 S_ALARMS Y
Date/Time Y Y Y Y Y 12764 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_038 S_ALARMS Y
Record Type Y Y Y Y Y 12768 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_038 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12769 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_038 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12770 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_038 S_ALARMS Y
Sequence Number Y Y Y Y Y 12774 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_038 S_ALARMS Y
Entry 039 Y Y Y Y Y 12775 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12775 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_039 S_ALARMS Y
Date/Time Y Y Y Y Y 12776 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_039 S_ALARMS Y
Record Type Y Y Y Y Y 12780 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_039 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12781 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_039 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12782 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_039 S_ALARMS Y
Sequence Number Y Y Y Y Y 12786 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_039 S_ALARMS Y
Entry 040 Y Y Y Y Y 12787 --- --- --- --- --- --- S_ALARMS Y
Entry Number Y Y Y Y Y 12787 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_ENTRY_040 S_ALARMS Y
Date/Time Y Y Y Y Y 12788 --- 4 DATETIME R N/A Y R_ALM_AGG_HIST_DT_040 S_ALARMS Y
Record Type Y Y Y Y Y 12792 --- 1 INT16U R N/A Y The high byte shall be 0xFF R_ALM_AGG_HIST_REC_TYPE_040 Y
0x0000 Boolean
0x0010 INT16U
0x0011 INT16
0x0020 INT32U S_ALARMS
0x0021 INT32
0x0030 INT64U
0x0031 INT64
0x0040 FLOAT32
0x0041 FLOAT64
Register Number or Event Code Y Y Y Y Y 12793 --- 1 INT16U R N/A Y See Event Codes for secondary events and R_ALM_AGG_HIST_EVT_ID_040 Y
S_ALARMS
Alarm Attributes for Primary events
Value Y Y Y Y Y 12794 --- 4 INT16U R N/A Y R_ALM_AGG_HIST_VAL_040 S_ALARMS Y
Sequence Number Y Y Y Y Y 12798 --- 1 INT16U R N/A Y R_ALM_AGG_HIST_SN_040 S_ALARMS Y
Alarm Counters Y Y Y Y Y 13519 --- --- --- --- --- --- S_ALARMS Y
Summary Y Y Y Y Y 13519 --- --- --- --- --- --- S_ALARMS Y
Total Counter Y Y Y Y Y 13519 --- 1 INT16U R --- 0 Y R_ALM_COUNT_TOTAL S_ALARMS Y
Low Priority Counter Y Y Y Y Y 13520 --- 1 INT16U R --- 0 Y R_ALM_COUNT_P3 S_ALARMS Y
Medium Priority Counter Y Y Y Y Y 13521 --- 1 INT16U R --- 0 Y R_ALM_COUNT_P2 S_ALARMS Y
High Priority Counter Y Y Y Y Y 13522 --- 1 INT16U R --- 0 Y R_ALM_COUNT_P1 S_ALARMS Y
1-Second Alarms - Standard Y Y Y Y Y 13523 --- --- --- --- --- --- S_ALARMS Y
Over Current, Phase Y Y Y Y Y 13523 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_001 S_ALARMS Y
Under Current, Phase Y Y Y Y Y 13524 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_002 S_ALARMS Y
Over Current, Neutral Y Y Y Y Y 13525 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_003 S_ALARMS Y
Over Current, Ground Y Y Y Y Y 13526 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_004 S_ALARMS Y
Over Voltage, L-L Y Y Y Y Y 13527 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_005 S_ALARMS Y
Under Voltage, L-L Y Y Y Y Y 13528 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_006 S_ALARMS Y
Over Voltage, L-N Y Y Y Y Y 13529 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_007 S_ALARMS Y
Under Voltage, L-N Y Y Y Y Y 13530 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_008 S_ALARMS Y
Over Power, Active Y Y Y Y Y 13531 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_009 S_ALARMS Y
Over Power, Reactive Y Y Y Y Y 13532 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_010 S_ALARMS Y
Over Power, Apparent Y Y Y Y Y 13533 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_011 S_ALARMS Y
Lead Power Factor, True Y Y Y Y Y 13534 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_012 S_ALARMS Y
Lag Power Factor, True Y Y Y Y Y 13535 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_013 S_ALARMS Y
Lead Power Factor, Displacement Y Y Y Y Y 13536 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_014 S_ALARMS Y
Lag Power Factor, Displacement Y Y Y Y Y 13537 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_015 S_ALARMS Y
Over Demand, Active Power, Present Y Y Y Y Y 13538 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_016 S_ALARMS Y
Over Demand, Active Power, Last Y Y Y Y Y 13539 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_017 S_ALARMS Y
Over Demand, Active Power, Predicted Y Y Y Y Y 13540 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_018 S_ALARMS Y
Over Demand, Reactive Power, Present Y Y Y Y Y 13541 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_019 S_ALARMS Y
Over Demand, Reactive Power, Last Y Y Y Y Y 13542 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_020 S_ALARMS Y
Over Demand, Reactive Power, Predicted Y Y Y Y Y 13543 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_021 S_ALARMS Y
Over Demand, Apparent Power, Present Y Y Y Y Y 13544 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_022 S_ALARMS Y
Over Demand, Apparent Power, Last Y Y Y Y Y 13545 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_023 S_ALARMS Y
Over Demand, Apparent Power, Predicted Y Y Y Y Y 13546 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_024 S_ALARMS Y
Over Frequency Y Y Y Y Y 13547 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_025 S_ALARMS Y
Under Frequency Y Y Y Y Y 13548 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_026 S_ALARMS Y
Over Voltage Unbalance Y Y Y Y Y 13549 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_027 S_ALARMS Y
Over Voltage Total Harmonic Distortion Y Y Y Y Y 13550 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_028 S_ALARMS Y
Phase Loss Y Y Y Y Y 13551 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_029 S_ALARMS Y
Unary Alarms Y Y Y Y Y 13623 --- --- --- --- --- --- S_ALARMS Y
Meter Powerup (Control Power Loss) Y Y Y Y Y 13623 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_101 S_ALARMS Y
Meter Reset Y Y Y Y Y 13624 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_102 S_ALARMS Y
Meter Diagnostic Y Y Y Y Y 13625 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_103 S_ALARMS Y
Phase Reversal Y Y Y Y Y 13626 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_104 S_ALARMS Y
Digital Alarms Y Y Y Y 13633 --- --- --- --- --- --- S_ALARMS Y
Digital Alarm DI1 Y Y Y Y 13633 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_111 S_ALARMS Y
Digital Alarm DI2 Y Y Y Y 13634 --- 1 INT16U R 0 – 9999 0 Y R_ALM_COUNT_112 S_ALARMS Y
1-Second Alarms - Standard Y Y Y Y Y 14000 --- --- --- --- --- --- S_ALARMS Y
Over Current, Phase Y Y Y Y Y 14000 --- --- --- --- --- --- Alarm ID 1 S_ALARMS Y
Attributes Y Y Y Y Y 14000 --- 2 INT32U RWC 0x10848B80 Y See Alarm Attributes for details. R_ALM_1ST_OVR_CUR_ATTR S_ALARMS Y
Source Register A Y Y Y Y Y 14002 --- 1 INT16U R R_IA_50_60_CYC_RMS N R_ALM_1ST_OVR_CUR_REG_A S_ALARMS Y
Source Register B Y Y Y Y Y 14003 --- 1 INT16U R R_IB_50_60_CYC_RMS N R_ALM_1ST_OVR_CUR_REG_B S_ALARMS Y
Source Register C Y Y Y Y Y 14004 --- 1 INT16U R R_IC_50_60_CYC_RMS N R_ALM_1ST_OVR_CUR_REG_C S_ALARMS Y
Pickup Setpoint Y Y Y Y Y 14005 A 2 FLOAT32 RWC See User Notes 0 Y The maximum pickup setpoint allowed is the maximum R_ALM_1ST_OVR_CUR_PU Y
current that can be reported under the present configuration of S_ALARMS
CT ratio.
Pickup Time Delay Y Y Y Y Y 14007 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_OVR_CUR_PUTD S_ALARMS Y
Dropout Setpoint Y Y Y Y Y 14009 A 2 FLOAT32 RWC See User Notes 0 Y Must be < Pickup Setpoint. R_ALM_1ST_OVR_CUR_DO S_ALARMS Y
Dropout Time Delay Y Y Y Y Y 14011 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_OVR_CUR_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y Y 14013 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_1ST_OVR_CUR_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
Digital Outputs to Associate – Option Modules 14014 --- 4 BITMAP RWC 0 Y S_ALARMS
Datalogs to Trigger 14018 --- 1 BITMAP RWC 0 Y R_ALM_1ST_OVR_CUR_DLG S_ALARMS
Waveform Capture to Trigger 14019 --- 1 BITMAP RWC 0 Y R_ALM_1ST_OVR_CUR_WFC S_ALARMS
Under Current, Phase Y Y Y Y Y 14020 --- --- --- --- --- --- Alarm ID 2 S_ALARMS Y
Attributes Y Y Y Y Y 14020 --- 2 INT32U RWC 0x11048B80 Y See Alarm Attributes for details. R_ALM_1ST_UND_CUR_ATTR S_ALARMS Y
Source Register A Y Y Y Y Y 14022 --- 1 INT16U R R_IA_50_60_CYC_RMS N R_ALM_1ST_UND_CUR_REG_A S_ALARMS Y
Source Register B Y Y Y Y Y 14023 --- 1 INT16U R R_IB_50_60_CYC_RMS N R_ALM_1ST_UND_CUR_REG_B S_ALARMS Y
Source Register C Y Y Y Y Y 14024 --- 1 INT16U R R_IC_50_60_CYC_RMS N R_ALM_1ST_UND_CUR_REG_C S_ALARMS Y
Pickup Setpoint Y Y Y Y Y 14025 A 2 FLOAT32 RWC See User Notes 0 Y Must be < Dropout Setpoint. R_ALM_1ST_UND_CUR_PU S_ALARMS Y
Pickup Time Delay Y Y Y Y Y 14027 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_UND_CUR_PUTD S_ALARMS Y
Dropout Setpoint Y Y Y Y Y 14029 A 2 FLOAT32 RWC See User Notes 0 Y The maximum pickup setpoint allowed is the maximum R_ALM_1ST_UND_CUR_DO Y
current that can be reported under the present configuration of S_ALARMS
CT ratio.
Dropout Time Delay Y Y Y Y Y 14031 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_UND_CUR_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y Y 14033 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_1ST_UND_CUR_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
Over Current, Neutral Y Y Y Y Y 14040 --- --- --- --- --- --- Alarm ID 3 S_ALARMS Y
Attributes Y Y Y Y Y 14040 --- 2 INT32U RWC 0x10849400 Y See Alarm Attributes for details. R_ALM_1ST_OVR_IN_ATTR S_ALARMS Y
Source Register A Y Y Y Y Y 14042 --- 1 INT16U R R_IN_50_60_CYC_RMS N R_ALM_1ST_OVR_IN_REG_A S_ALARMS Y
Source Register B Y Y Y Y Y 14043 --- 1 INT16U R N/A N R_ALM_1ST_OVR_IN_REG_B S_ALARMS Y
Source Register C Y Y Y Y Y 14044 --- 1 INT16U R N/A N R_ALM_1ST_OVR_IN_REG_C S_ALARMS Y
Pickup Setpoint Y Y Y Y Y 14045 A 2 FLOAT32 RWC See User Notes 0 Y The maximum pickup setpoint allowed is the maximum R_ALM_1ST_OVR_IN_PU Y
current that can be reported under the present configuration of S_ALARMS
CT ratio.
Pickup Time Delay Y Y Y Y Y 14047 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_OVR_IN_PUTD S_ALARMS Y
Dropout Setpoint Y Y Y Y Y 14049 A 2 FLOAT32 RWC See User Notes 0 Y Must be < Pickup Setpoint. R_ALM_1ST_OVR_IN_DO S_ALARMS Y
Dropout Time Delay Y Y Y Y Y 14051 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_OVR_IN_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y Y 14053 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_1ST_OVR_IN_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
Over Current, Ground 14060 --- --- --- --- --- --- Alarm ID 4 S_ALARMS Y
Attributes Y Y Y Y Y 14060 --- 2 INT32U RWC 0x10849C80 Y See Alarm Attributes for details. R_ALM_1ST_OVR_IG_ATTR S_ALARMS Y
Source Register A Y Y Y Y Y 14062 --- 1 INT16U R R_IG_50_60_CYC_RMS N R_ALM_1ST_OVR_IG_REG_A S_ALARMS Y
Source Register B Y Y Y Y Y 14063 --- 1 INT16U R N/A N R_ALM_1ST_OVR_IG_REG_B S_ALARMS Y
Source Register C Y Y Y Y Y 14064 --- 1 INT16U R N/A N R_ALM_1ST_OVR_IG_REG_C S_ALARMS Y
Pickup Setpoint Y Y Y Y Y 14065 A 2 FLOAT32 RWC See User Notes 0 Y The maximum pickup setpoint allowed is the maximum R_ALM_1ST_OVR_IG_PU Y
current that can be reported under the present configuration of S_ALARMS
CT ratio.
Pickup Time Delay Y Y Y Y Y 14067 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_OVR_IG_PUTD S_ALARMS Y
Dropout Setpoint Y Y Y Y Y 14069 A 2 FLOAT32 RWC See User Notes 0 Y Must be < Pickup Setpoint. R_ALM_1ST_OVR_IG_DO S_ALARMS Y
Dropout Time Delay Y Y Y Y Y 14071 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_OVR_IG_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y Y 14073 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_1ST_OVR_IG_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
Over Voltage, L-L Y Y Y Y Y 14080 --- --- --- --- --- --- Alarm ID 5 S_ALARMS Y
Attributes Y Y Y Y Y 14080 --- 2 INT32U RWC 0x1082AB80 Y See Alarm Attributes for details. R_ALM_1ST_OVR_VLL_ATTR S_ALARMS Y
Source Register A Y Y Y Y Y 14082 --- 1 INT16U R R_VAB_50_60_CYC_RMS N R_ALM_1ST_OVR_VLL_REG_A S_ALARMS Y
Source Register B Y Y Y Y Y 14083 --- 1 INT16U R R_VBC_50_60_CYC_RMS N R_ALM_1ST_OVR_VLL_REG_B S_ALARMS Y
Source Register C Y Y Y Y Y 14084 --- 1 INT16U R R_VCA_50_60_CYC_RMS N R_ALM_1ST_OVR_VLL_REG_C S_ALARMS Y
Pickup Setpoint Y Y Y Y Y 14085 V 2 FLOAT32 RWC See User Notes 0 Y The maximum pickup setpoint allowed is the maximum R_ALM_1ST_OVR_VLL_PU Y
voltage that can be reported under the present configuration S_ALARMS
of VT ratio.
Pickup Time Delay Y Y Y Y Y 14087 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_OVR_VLL_PUTD S_ALARMS Y
Dropout Setpoint Y Y Y Y Y 14089 V 2 FLOAT32 RWC See User Notes 0 Y Must be < Pickup Setpoint. R_ALM_1ST_OVR_VLL_DO S_ALARMS Y
Dropout Time Delay Y Y Y Y Y 14091 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_OVR_VLL_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y Y 14093 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_1ST_OVR_VLL_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
Under Voltage, L-L Y Y Y Y Y 14100 --- --- --- --- --- --- Alarm ID 6 S_ALARMS Y
Attributes Y Y Y Y Y 14100 --- 2 INT32U RWC 0x1102AB80 Y See Alarm Attributes for details. R_ALM_1ST_UND_VLL_ATTR S_ALARMS Y
Source Register A Y Y Y Y Y 14102 --- 1 INT16U R R_VAB_50_60_CYC_RMS N R_ALM_1ST_UND_VLL_REG_A S_ALARMS Y
Source Register B Y Y Y Y Y 14103 --- 1 INT16U R R_VBC_50_60_CYC_RMS N R_ALM_1ST_UND_VLL_REG_B S_ALARMS Y
Source Register C Y Y Y Y Y 14104 --- 1 INT16U R R_VCA_50_60_CYC_RMS N R_ALM_1ST_UND_VLL_REG_C S_ALARMS Y
Pickup Setpoint Y Y Y Y Y 14105 V 2 FLOAT32 RWC See User Notes 0 Y Must be < Dropout Setpoint. R_ALM_1ST_UND_VLL_PU S_ALARMS Y
Pickup Time Delay Y Y Y Y Y 14107 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_UND_VLL_PUTD S_ALARMS Y
Dropout Setpoint Y Y Y Y Y 14109 V 2 FLOAT32 RWC See User Notes 0 Y The maximum dropout setpoint allowed is the maximum R_ALM_1ST_UND_VLL_DO Y
voltage that can be reported under the present configuration of
VT ratio. S_ALARMS
Dropout Time Delay Y Y Y Y Y 14111 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_UND_VLL_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y Y 14113 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_1ST_UND_VLL_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
Over Voltage, L-N Y Y Y Y Y 14120 --- --- --- --- --- --- Alarm ID 7 S_ALARMS Y
Attributes Y Y Y Y Y 14120 --- 2 INT32U RWC 0x1082A380 Y See Alarm Attributes for details. R_ALM_1ST_OVR_VLN_ATTR S_ALARMS Y
Source Register A Y Y Y Y Y 14122 --- 1 INT16U R R_VAN_50_60_CYC_RMS N R_ALM_1ST_OVR_VLN_REG_A S_ALARMS Y
Source Register B Y Y Y Y Y 14123 --- 1 INT16U R R_VBN_50_60_CYC_RMS N R_ALM_1ST_OVR_VLN_REG_B S_ALARMS Y
Source Register C Y Y Y Y Y 14124 --- 1 INT16U R R_VCN_50_60_CYC_RMS N R_ALM_1ST_OVR_VLN_REG_C S_ALARMS Y
Pickup Setpoint Y Y Y Y Y 14125 V 2 FLOAT32 RWC See User Notes 0 Y The maximum pickup setpoint allowed is the maximum R_ALM_1ST_OVR_VLN_PU Y
voltage that can be reported under the present configuration S_ALARMS
of VT ratio.
Pickup Time Delay Y Y Y Y Y 14127 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_OVR_VLN_PUTD S_ALARMS Y
Dropout Setpoint Y Y Y Y Y 14129 V 2 FLOAT32 RWC See User Notes 0 Y Must be < Pickup Setpoint. R_ALM_1ST_OVR_VLN_DO S_ALARMS Y
Dropout Time Delay Y Y Y Y Y 14131 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_OVR_VLN_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y Y 14133 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_1ST_OVR_VLN_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
Under Voltage, L-N Y Y Y Y Y 14140 --- --- --- --- --- --- Alarm ID 8 S_ALARMS Y
Attributes Y Y Y Y Y 14140 --- 2 INT32U RWC 0x1102A380 Y See Alarm Attributes for details. R_ALM_1ST_UND_VLN_ATTR S_ALARMS Y
Source Register A Y Y Y Y Y 14142 --- 1 INT16U R R_VAN_50_60_CYC_RMS N R_ALM_1ST_UND_VLN_REG_A S_ALARMS Y
Source Register B Y Y Y Y Y 14143 --- 1 INT16U R R_VBN_50_60_CYC_RMS N R_ALM_1ST_UND_VLN_REG_B S_ALARMS Y
Source Register C Y Y Y Y Y 14144 --- 1 INT16U R R_VCN_50_60_CYC_RMS N R_ALM_1ST_UND_VLN_REG_C S_ALARMS Y
Pickup Setpoint Y Y Y Y Y 14145 V 2 FLOAT32 RWC See User Notes 0 Y Must be < Dropout Setpoint. R_ALM_1ST_UND_VLN_PU S_ALARMS Y
Pickup Time Delay Y Y Y Y Y 14147 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_UND_VLN_PUTD S_ALARMS Y
Dropout Setpoint Y Y Y Y Y 14149 V 2 FLOAT32 RWC See User Notes 0 Y The maximum dropout setpoint allowed is the maximum R_ALM_1ST_UND_VLN_DO Y
voltage that can be reported under the present configuration of
VT ratio. S_ALARMS
Dropout Time Delay Y Y Y Y Y 14151 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_UND_VLN_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y Y 14153 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_1ST_UND_VLN_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
Over Power, Active Y Y Y Y Y 14160 --- --- --- --- --- --- Alarm ID 9 S_ALARMS Y
Attributes Y Y Y Y Y 14160 --- 2 INT32U RWC 0x10875580 Y See Alarm Attributes for details. R_ALM_1ST_OVR_KW_ATTR S_ALARMS Y
Source Register A Y Y Y Y Y 14162 --- 1 INT16U R R_PTOT_50_60_CYC_RMS N R_ALM_1ST_OVR_KW_REG_A S_ALARMS Y
Source Register B Y Y Y Y Y 14163 --- 1 INT16U R N/A N R_ALM_1ST_OVR_KW_REG_B S_ALARMS Y
Source Register C Y Y Y Y Y 14164 --- 1 INT16U R N/A N R_ALM_1ST_OVR_KW_REG_C S_ALARMS Y
Pickup Setpoint Y Y Y Y Y 14165 kW 2 FLOAT32 RWC See User Notes 0 Y The maximum pickup setpoint allowed is the maximum power R_ALM_1ST_OVR_KW_PU Y
that can be reported under the present configuration of CT and
VT ratio. S_ALARMS
Pickup Time Delay Y Y Y Y Y 14167 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_OVR_KW_PUTD S_ALARMS Y
Dropout Setpoint Y Y Y Y Y 14169 kW 2 FLOAT32 RWC See User Notes 0 Y Must be < Pickup Setpoint. R_ALM_1ST_OVR_KW_DO S_ALARMS Y
Dropout Time Delay Y Y Y Y Y 14171 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_OVR_KW_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y Y 14173 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_1ST_OVR_KW_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
Over Power, Reactive Y Y Y Y Y 14180 --- --- --- --- --- --- Alarm ID 10 S_ALARMS Y
Attributes Y Y Y Y Y 14180 --- 2 INT32U RWC 0x10895580 Y See Alarm Attributes for details. R_ALM_1ST_OVR_KVAR_ATTR S_ALARMS Y
Source Register A Y Y Y Y Y 14182 --- 1 INT16U R R_QTOT_50_60_CYC_RMS N R_ALM_1ST_OVR_KVAR_REG_A S_ALARMS Y
Source Register B Y Y Y Y Y 14183 --- 1 INT16U R N/A N R_ALM_1ST_OVR_KVAR_REG_B S_ALARMS Y
Source Register C Y Y Y Y Y 14184 --- 1 INT16U R N/A N R_ALM_1ST_OVR_KVAR_REG_C S_ALARMS Y
Pickup Setpoint Y Y Y Y Y 14185 kVAR 2 FLOAT32 RWC See User Notes 0 Y The maximum pickup setpoint allowed is the maximum power R_ALM_1ST_OVR_KVAR_PU Y
that can be reported under the present configuration of CT and
VT ratio. S_ALARMS
Pickup Time Delay Y Y Y Y Y 14187 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_OVR_KVAR_PUTD S_ALARMS Y
Dropout Setpoint Y Y Y Y Y 14189 kVAR 2 FLOAT32 RWC See User Notes 0 Y Must be < Pickup Setpoint. R_ALM_1ST_OVR_KVAR_DO S_ALARMS Y
Dropout Time Delay Y Y Y Y Y 14191 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_OVR_KVAR_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y Y 14193 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_1ST_OVR_KVAR_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
Over Power, Apparent Y Y Y Y Y 14200 --- --- --- --- --- --- Alarm ID 11 S_ALARMS Y
Attributes Y Y Y Y Y 14200 --- 2 INT32U RWC 0x108B5580 Y See Alarm Attributes for details. R_ALM_1ST_OVR_KVA_ATTR S_ALARMS Y
Source Register A Y Y Y Y Y 14202 --- 1 INT16U R R_STOT_50_60_CYC_RMS N R_ALM_1ST_OVR_KVA_REG_A S_ALARMS Y
Source Register B Y Y Y Y Y 14203 --- 1 INT16U R N/A N R_ALM_1ST_OVR_KVA_REG_B S_ALARMS Y
Source Register C Y Y Y Y Y 14204 --- 1 INT16U R N/A N R_ALM_1ST_OVR_KVA_REG_C S_ALARMS Y
Pickup Setpoint Y Y Y Y Y 14205 kVA 2 FLOAT32 RWC See User Notes 0 Y The maximum pickup setpoint allowed is the maximum power R_ALM_1ST_OVR_KVA_PU Y
that can be reported under the present configuration of CT and
VT ratio. S_ALARMS
Pickup Time Delay Y Y Y Y Y 14207 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_OVR_KVA_PUTD S_ALARMS Y
Dropout Setpoint Y Y Y Y Y 14209 kVA 2 FLOAT32 RWC See User Notes 0 Y Must be < Pickup Setpoint. R_ALM_1ST_OVR_KVA_DO S_ALARMS Y
Dropout Time Delay Y Y Y Y Y 14211 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_OVR_KVA_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y Y 14213 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_1ST_OVR_KVA_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
Leading Power Factor, True Y Y Y Y Y 14220 --- --- --- --- --- --- Alarm ID 12 S_ALARMS Y
Attributes Y Y Y Y Y 14220 --- 2 INT32U RWC 0x118EC380 Y See Alarm Attributes for details. R_ALM_1ST_LEDPFT_ATTR S_ALARMS Y
Source Register A Y Y Y Y Y 14222 --- 1 INT16U R R_PFA_50_60_CYC_TRUE N R_ALM_1ST_LEDPFT_REG_A S_ALARMS Y
Source Register B Y Y Y Y Y 14223 --- 1 INT16U R R_PFB_50_60_CYC_TRUE N R_ALM_1ST_LEDPFT_REG_B S_ALARMS Y
Source Register C Y Y Y Y Y 14224 --- 1 INT16U R R_PFC_50_60_CYC_TRUE N R_ALM_1ST_LEDPFT_REG_C S_ALARMS Y
Pickup Setpoint Y Y Y Y Y 14225 --- 2 FLOAT32 RWC 0 Y R_ALM_1ST_LEDPFT_PU S_ALARMS Y
Pickup Time Delay Y Y Y Y Y 14227 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_LEDPFT_PUTD S_ALARMS Y
Dropout Setpoint Y Y Y Y Y 14229 --- 2 FLOAT32 RWC 0 Y R_ALM_1ST_LEDPFT_DO S_ALARMS Y
Dropout Time Delay Y Y Y Y Y 14231 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_LEDPFT_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y Y 14233 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_1ST_LEDPFT_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
Lagging Power Factor, True Y Y Y Y Y 14240 --- --- --- --- --- --- Alarm ID 13 S_ALARMS Y
Attributes Y Y Y Y Y 14240 --- 2 INT32U RWC 0x120EC380 Y See Alarm Attributes for details. R_ALM_1ST_LAGPFT_ATTR S_ALARMS Y
Source Register A Y Y Y Y Y 14242 --- 1 INT16U R R_PFA_50_60_CYC_TRUE N R_ALM_1ST_LAGPFT_REG_A S_ALARMS Y
Source Register B Y Y Y Y Y 14243 --- 1 INT16U R R_PFB_50_60_CYC_TRUE N R_ALM_1ST_LAGPFT_REG_B S_ALARMS Y
Source Register C Y Y Y Y Y 14244 --- 1 INT16U R R_PFC_50_60_CYC_TRUE N R_ALM_1ST_LAGPFT_REG_C S_ALARMS Y
Pickup Setpoint Y Y Y Y Y 14245 --- 2 FLOAT32 RWC 0 Y R_ALM_1ST_LAGPFT_PU S_ALARMS Y
Pickup Time Delay Y Y Y Y Y 14247 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_LAGPFT_PUTD S_ALARMS Y
Dropout Setpoint Y Y Y Y Y 14249 --- 2 FLOAT32 RWC 0 Y R_ALM_1ST_LAGPFT_DO S_ALARMS Y
Dropout Time Delay Y Y Y Y Y 14251 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_LAGPFT_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y Y 14253 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_1ST_LAGPFT_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
Leading Power Factor, Displacement Y Y Y Y Y 14260 --- --- --- --- --- --- Alarm ID 14 S_ALARMS Y
Attributes Y Y Y Y Y 14260 --- 2 INT32U RWC 0x118ECB80 Y See Alarm Attributes for details. R_ALM_1ST_LEDPFD_ATTR S_ALARMS Y
Source Register A Y Y Y Y Y 14262 --- 1 INT16U R R_PFA_50_60_CYC_DISP N R_ALM_1ST_LEDPFD_REG_A S_ALARMS Y
Source Register B Y Y Y Y Y 14263 --- 1 INT16U R R_PFB_50_60_CYC_DISP N R_ALM_1ST_LEDPFD_REG_B S_ALARMS Y
Source Register C Y Y Y Y Y 14264 --- 1 INT16U R R_PFC_50_60_CYC_DISP N R_ALM_1ST_LEDPFD_REG_C S_ALARMS Y
Pickup Setpoint Y Y Y Y Y 14265 --- 2 FLOAT32 RWC 0 Y R_ALM_1ST_LEDPFD_PU S_ALARMS Y
Pickup Time Delay Y Y Y Y Y 14267 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_LEDPFD_PUTD S_ALARMS Y
Dropout Setpoint Y Y Y Y Y 14269 --- 2 FLOAT32 RWC 0 Y R_ALM_1ST_LEDPFD_DO S_ALARMS Y
Dropout Time Delay Y Y Y Y Y 14271 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_LEDPFD_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y Y 14273 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_1ST_LEDPFD_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
Lagging Power Factor, Displacement Y Y Y Y Y 14280 --- --- --- --- --- --- Alarm ID 15 S_ALARMS Y
Attributes Y Y Y Y Y 14280 --- 2 INT32U RWC 0x120ECB80 Y See Alarm Attributes for details. R_ALM_1ST_LAGPFD_ATTR S_ALARMS Y
Source Register A Y Y Y Y Y 14282 --- 1 INT16U R R_PFA_50_60_CYC_DISP N R_ALM_1ST_LAGPFD_REG_A S_ALARMS Y
Source Register B Y Y Y Y Y 14283 --- 1 INT16U R R_PFB_50_60_CYC_DISP N R_ALM_1ST_LAGPFD_REG_B S_ALARMS Y
Source Register C Y Y Y Y Y 14284 --- 1 INT16U R R_PFC_50_60_CYC_DISP N R_ALM_1ST_LAGPFD_REG_C S_ALARMS Y
Pickup Setpoint Y Y Y Y Y 14285 --- 2 FLOAT32 RWC 0 Y R_ALM_1ST_LAGPFD_PU S_ALARMS Y
Pickup Time Delay Y Y Y Y Y 14287 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_LAGPFD_PUTD S_ALARMS Y
Dropout Setpoint Y Y Y Y Y 14289 --- 2 FLOAT32 RWC 0 Y R_ALM_1ST_LAGPFD_DO S_ALARMS Y
Dropout Time Delay Y Y Y Y Y 14291 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_LAGPFD_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y Y 14293 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_1ST_LAGPFD_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
Over Demand, Active Power, Present Y Y Y Y Y 14300 --- --- --- --- --- --- Alarm ID 16 S_ALARMS Y
Attributes Y Y Y Y Y 14300 --- 2 INT32U RWC 0x1086E580 Y See Alarm Attributes for details. R_ALM_1ST_KWD_P_ATTR S_ALARMS Y
Source Register A Y Y Y Y Y 14302 --- 1 INT16U R R_DMD_CH_01_PRES N R_ALM_1ST_KWD_P_REG_A S_ALARMS Y
Source Register B Y Y Y Y Y 14303 --- 1 INT16U R N/A N R_ALM_1ST_KWD_P_REG_B S_ALARMS Y
Source Register C Y Y Y Y Y 14304 --- 1 INT16U R N/A N R_ALM_1ST_KWD_P_REG_C S_ALARMS Y
Pickup Setpoint Y Y Y Y Y 14305 kW 2 FLOAT32 RWC See User Notes 0 Y The maximum pickup setpoint allowed is the maximum power R_ALM_1ST_KWD_P_PU Y
that can be reported under the present configuration of CT and
VT ratio. S_ALARMS
Pickup Time Delay Y Y Y Y Y 14307 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_KWD_P_PUTD S_ALARMS Y
Dropout Setpoint Y Y Y Y Y 14309 kW 2 FLOAT32 RWC See User Notes 0 Y Must be < Pickup Setpoint. R_ALM_1ST_KWD_P_DO S_ALARMS Y
Dropout Time Delay Y Y Y Y Y 14311 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_KWD_P_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y Y 14313 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_1ST_KWD_P_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
Over Demand, Active Power, Last Y Y Y Y Y 14320 --- --- --- --- --- --- Alarm ID 17 S_ALARMS Y
Attributes Y Y Y Y Y 14320 --- 2 INT32U RWC 0x1086D580 Y See Alarm Attributes for details. R_ALM_1ST_KWD_L_ATTR S_ALARMS Y
Source Register A Y Y Y Y Y 14322 --- 1 INT16U R R_DMD_CH_01_LAST N R_ALM_1ST_KWD_L_REG_A S_ALARMS Y
Source Register B Y Y Y Y Y 14323 --- 1 INT16U R N/A N R_ALM_1ST_KWD_L_REG_B S_ALARMS Y
Source Register C Y Y Y Y Y 14324 --- 1 INT16U R N/A N R_ALM_1ST_KWD_L_REG_C S_ALARMS Y
Pickup Setpoint Y Y Y Y Y 14325 kW 2 FLOAT32 RWC See User Notes 0 Y The maximum pickup setpoint allowed is the maximum power R_ALM_1ST_KWD_L_PU Y
that can be reported under the present configuration of CT and
VT ratio. S_ALARMS
Pickup Time Delay Y Y Y Y Y 14327 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_KWD_L_PUTD S_ALARMS Y
Dropout Setpoint Y Y Y Y Y 14329 kW 2 FLOAT32 RWC See User Notes 0 Y Must be < Pickup Setpoint. R_ALM_1ST_KWD_L_DO S_ALARMS Y
Dropout Time Delay Y Y Y Y Y 14331 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_KWD_L_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y Y 14333 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_1ST_KWD_L_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
Over Demand, Active Power, Predicted Y Y Y Y Y 14340 --- --- --- --- --- --- Alarm ID 18 S_ALARMS Y
Attributes Y Y Y Y Y 14340 --- 2 INT32U RWC 0x1086DD80 Y See Alarm Attributes for details. R_ALM_1ST_KWD_D_ATTR S_ALARMS Y
Source Register A Y Y Y Y Y 14342 --- 1 INT16U R R_DMD_CH_01_PREDICTE N R_ALM_1ST_KWD_D_REG_A S_ALARMS Y
Source Register B Y Y Y Y Y 14343 --- 1 INT16U R N/A N R_ALM_1ST_KWD_D_REG_B S_ALARMS Y
Source Register C Y Y Y Y Y 14344 --- 1 INT16U R N/A N R_ALM_1ST_KWD_D_REG_C S_ALARMS Y
Pickup Setpoint Y Y Y Y Y 14345 kW 2 FLOAT32 RWC See User Notes 0 Y The maximum pickup setpoint allowed is the maximum power R_ALM_1ST_KWD_D_PU Y
that can be reported under the present configuration of CT and
VT ratio. S_ALARMS
Pickup Time Delay Y Y Y Y Y 14347 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_KWD_D_PUTD S_ALARMS Y
Dropout Setpoint Y Y Y Y Y 14349 kW 2 FLOAT32 RWC See User Notes 0 Y Must be < Pickup Setpoint. R_ALM_1ST_KWD_D_DO S_ALARMS Y
Dropout Time Delay Y Y Y Y Y 14351 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_KWD_D_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y Y 14353 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_1ST_KWD_D_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
Over Demand, Reactive Power, Present Y Y Y Y Y 14360 --- --- --- --- --- --- Alarm ID 19 S_ALARMS Y
Attributes Y Y Y Y Y 14360 --- 2 INT32U RWC 0x1088E580 Y See Alarm Attributes for details. R_ALM_1ST_KVARD_P_ATTR S_ALARMS Y
Source Register A Y Y Y Y Y 14362 --- 1 INT16U R R_DMD_CH_02_PRES N R_ALM_1ST_KVARD_P_REG_A S_ALARMS Y
Source Register B Y Y Y Y Y 14363 --- 1 INT16U R N/A N R_ALM_1ST_KVARD_P_REG_B S_ALARMS Y
Source Register C Y Y Y Y Y 14364 --- 1 INT16U R N/A N R_ALM_1ST_KVARD_P_REG_C S_ALARMS Y
Pickup Setpoint Y Y Y Y Y 14365 kVAR 2 FLOAT32 RWC See User Notes 0 Y The maximum pickup setpoint allowed is the maximum power R_ALM_1ST_KVARD_P_PU Y
that can be reported under the present configuration of CT and
VT ratio. S_ALARMS
Pickup Time Delay Y Y Y Y Y 14367 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_KVARD_P_PUTD S_ALARMS Y
Dropout Setpoint Y Y Y Y Y 14369 kVAR 2 FLOAT32 RWC See User Notes 0 Y Must be < Pickup Setpoint. R_ALM_1ST_KVARD_P_DO S_ALARMS Y
Dropout Time Delay Y Y Y Y Y 14371 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_KVARD_P_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y Y 14373 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_1ST_KVARD_P_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
Over Demand, Reactive Power, Last Y Y Y Y Y 14380 --- --- --- --- --- --- Alarm ID 20 S_ALARMS Y
Attributes Y Y Y Y Y 14380 --- 2 INT32U RWC 0x1088D580 Y See Alarm Attributes for details. R_ALM_1ST_KVARD_L_ATTR S_ALARMS Y
Source Register A Y Y Y Y Y 14382 --- 1 INT16U R R_DMD_CH_02_LAST N R_ALM_1ST_KVARD_L_REG_A S_ALARMS Y
Source Register B Y Y Y Y Y 14383 --- 1 INT16U R N/A N R_ALM_1ST_KVARD_L_REG_B S_ALARMS Y
Source Register C Y Y Y Y Y 14384 --- 1 INT16U R N/A N R_ALM_1ST_KVARD_L_REG_C S_ALARMS Y
Pickup Setpoint Y Y Y Y Y 14385 kVAR 2 FLOAT32 RWC See User Notes 0 Y The maximum pickup setpoint allowed is the maximum power R_ALM_1ST_KVARD_L_PU Y
that can be reported under the present configuration of CT and
VT ratio. S_ALARMS
Pickup Time Delay Y Y Y Y Y 14387 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_KVARD_L_PUTD S_ALARMS Y
Dropout Setpoint Y Y Y Y Y 14389 kVAR 2 FLOAT32 RWC See User Notes 0 Y Must be < Pickup Setpoint. R_ALM_1ST_KVARD_L_DO S_ALARMS Y
Dropout Time Delay Y Y Y Y Y 14391 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_KVARD_L_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y Y 14393 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_1ST_KVARD_L_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
Over Demand, Reactive Power, Predicted Y Y Y Y Y 14400 --- --- --- --- --- --- Alarm ID 21 S_ALARMS Y
Attributes Y Y Y Y Y 14400 --- 2 INT32U RWC 0x1088DD80 Y See Alarm Attributes for details. R_ALM_1ST_KVARD_D_ATTR S_ALARMS Y
Source Register A Y Y Y Y Y 14402 --- 1 INT16U R R_DMD_CH_02_PREDICTED N R_ALM_1ST_KVARD_D_REG_A S_ALARMS Y
Source Register B Y Y Y Y Y 14403 --- 1 INT16U R N/A N R_ALM_1ST_KVARD_D_REG_B S_ALARMS Y
Source Register C Y Y Y Y Y 14404 --- 1 INT16U R N/A N R_ALM_1ST_KVARD_D_REG_C S_ALARMS Y
Pickup Setpoint Y Y Y Y Y 14405 kVAR 2 FLOAT32 RWC See User Notes 0 Y The maximum pickup setpoint allowed is the maximum power R_ALM_1ST_KVARD_D_PU Y
that can be reported under the present configuration of CT and
VT ratio. S_ALARMS
Pickup Time Delay Y Y Y Y Y 14407 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_KVARD_D_PUTD S_ALARMS Y
Dropout Setpoint Y Y Y Y Y 14409 kVAR 2 FLOAT32 RWC See User Notes 0 Y Must be < Pickup Setpoint. R_ALM_1ST_KVARD_D_DO S_ALARMS Y
Dropout Time Delay Y Y Y Y Y 14411 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_KVARD_D_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y Y 14413 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_1ST_KVARD_D_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
Over Demand, Apparent Power, Present Y Y Y Y Y 14420 --- --- --- --- --- --- Alarm ID 22 S_ALARMS Y
Attributes Y Y Y Y Y 14420 --- 2 INT32U RWC 0x108AE580 Y See Alarm Attributes for details. R_ALM_1ST_KVAD_P_ATTR S_ALARMS Y
Source Register A Y Y Y Y Y 14422 --- 1 INT16U R R_DMD_CH_03_PRES N R_ALM_1ST_KVAD_P_REG_A S_ALARMS Y
Source Register B Y Y Y Y Y 14423 --- 1 INT16U R N/A N R_ALM_1ST_KVAD_P_REG_B S_ALARMS Y
Source Register C Y Y Y Y Y 14424 --- 1 INT16U R N/A N R_ALM_1ST_KVAD_P_REG_C S_ALARMS Y
Pickup Setpoint Y Y Y Y Y 14425 kVA 2 FLOAT32 RWC See User Notes 0 Y The maximum pickup setpoint allowed is the maximum power R_ALM_1ST_KVAD_P_PU Y
that can be reported under the present configuration of CT and
VT ratio. S_ALARMS
Pickup Time Delay Y Y Y Y Y 14427 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_KVAD_P_PUTD S_ALARMS Y
Dropout Setpoint Y Y Y Y Y 14429 kVA 2 FLOAT32 RWC See User Notes 0 Y Must be < Pickup Setpoint. R_ALM_1ST_KVAD_P_DO S_ALARMS Y
Dropout Time Delay Y Y Y Y Y 14431 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_KVAD_P_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y Y 14433 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_1ST_KVAD_P_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
Over Demand, Apparent Power, Last Y Y Y Y Y 14440 --- --- --- --- --- --- Alarm ID 23 S_ALARMS Y
Attributes Y Y Y Y Y 14440 --- 2 INT32U RWC 0x108AD580 Y See Alarm Attributes for details. R_ALM_1ST_KVAD_L_ATTR S_ALARMS Y
Source Register A Y Y Y Y Y 14442 --- 1 INT16U R R_DMD_CH_03_LAST N R_ALM_1ST_KVAD_L_REG_A S_ALARMS Y
Source Register B Y Y Y Y Y 14443 --- 1 INT16U R N/A N R_ALM_1ST_KVAD_L_REG_B S_ALARMS Y
Source Register C Y Y Y Y Y 14444 --- 1 INT16U R N/A N R_ALM_1ST_KVAD_L_REG_C S_ALARMS Y
Pickup Setpoint Y Y Y Y Y 14445 kVA 2 FLOAT32 RWC See User Notes 0 Y The maximum pickup setpoint allowed is the maximum power R_ALM_1ST_KVAD_L_PU Y
that can be reported under the present configuration of CT and
VT ratio. S_ALARMS
Pickup Time Delay Y Y Y Y Y 14447 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_KVAD_L_PUTD S_ALARMS Y
Dropout Setpoint Y Y Y Y Y 14449 kVA 2 FLOAT32 RWC See User Notes 0 Y Must be < Pickup Setpoint. R_ALM_1ST_KVAD_L_DO S_ALARMS Y
Dropout Time Delay Y Y Y Y Y 14451 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_KVAD_L_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y Y 14453 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_1ST_KVAD_L_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
Over Demand, Apparent Power, Predicted Y Y Y Y Y 14460 --- --- --- --- --- --- Alarm ID 24 S_ALARMS Y
Attributes Y Y Y Y Y 14460 --- 2 INT32U RWC 0x108ADD80 Y See Alarm Attributes for details. R_ALM_1ST_KVAD_D_ATTR S_ALARMS Y
Source Register A Y Y Y Y Y 14462 --- 1 INT16U R R_DMD_CH_03_PREDICTED N R_ALM_1ST_KVAD_D_REG_A S_ALARMS Y
Source Register B Y Y Y Y Y 14463 --- 1 INT16U R N/A N R_ALM_1ST_KVAD_D_REG_B S_ALARMS Y
Source Register C Y Y Y Y Y 14464 --- 1 INT16U R N/A N R_ALM_1ST_KVAD_D_REG_C S_ALARMS Y
Pickup Setpoint Y Y Y Y Y 14465 kVA 2 FLOAT32 RWC See User Notes 0 Y The maximum pickup setpoint allowed is the maximum power R_ALM_1ST_KVAD_D_PU Y
that can be reported under the present configuration of CT and
VT ratio. S_ALARMS
Pickup Time Delay Y Y Y Y Y 14467 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_KVAD_D_PUTD S_ALARMS Y
Dropout Setpoint Y Y Y Y Y 14469 kVA 2 FLOAT32 RWC See User Notes 0 Y Must be < Pickup Setpoint. R_ALM_1ST_KVAD_D_DO S_ALARMS Y
Dropout Time Delay Y Y Y Y Y 14471 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_KVAD_D_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y Y 14473 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_1ST_KVAD_D_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
Over Frequency Y Y Y Y Y 14480 --- --- --- --- --- --- Alarm ID 25 S_ALARMS Y
Attributes Y Y Y Y Y 14480 --- 2 INT32U RWC 0x108C0000 Y See Alarm Attributes for details. R_ALM_1ST_OVR_FREQ_ATTR S_ALARMS Y
Source Register A Y Y Y Y Y 14482 --- 1 INT16U R R_FREQ_50_60_CYC_AVG N R_ALM_1ST_OVR_FREQ_REG_A S_ALARMS Y
Source Register B Y Y Y Y Y 14483 --- 1 INT16U R N/A N R_ALM_1ST_OVR_FREQ_REG_B S_ALARMS Y
Source Register C Y Y Y Y Y 14484 --- 1 INT16U R N/A N R_ALM_1ST_OVR_FREQ_REG_C S_ALARMS Y
Pickup Setpoint Y Y Y Y Y 14485 Hz 2 FLOAT32 RWC 0 Y R_ALM_1ST_OVR_FREQ_PU S_ALARMS Y
Pickup Time Delay Y Y Y Y Y 14487 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_OVR_FREQ_PUTD S_ALARMS Y
Dropout Setpoint Y Y Y Y Y 14489 Hz 2 FLOAT32 RWC See User Notes 0 Y Must be < Pickup Setpoint. R_ALM_1ST_OVR_FREQ_DO S_ALARMS Y
Dropout Time Delay Y Y Y Y Y 14491 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_OVR_FREQ_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y Y 14493 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_1ST_OVR_FREQ_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
Under Frequency Y Y Y Y Y 14500 --- --- --- --- --- --- Alarm ID 26 S_ALARMS Y
Attributes Y Y Y Y Y 14500 --- 2 INT32U RWC 0x110C0000 Y See Alarm Attributes for details. R_ALM_1ST_UND_FREQ_ATTR S_ALARMS Y
Source Register A Y Y Y Y Y 14502 --- 1 INT16U R R_FREQ_50_60_CYC_AVG N R_ALM_1ST_UND_FREQ_REG_A S_ALARMS Y
Source Register B Y Y Y Y Y 14503 --- 1 INT16U R N/A N R_ALM_1ST_UND_FREQ_REG_B S_ALARMS Y
Source Register C Y Y Y Y Y 14504 --- 1 INT16U R N/A N R_ALM_1ST_UND_FREQ_REG_C S_ALARMS Y
Pickup Setpoint Y Y Y Y Y 14505 Hz 2 FLOAT32 RWC See User Notes 0 Y Must be < Dropout Setpoint. R_ALM_1ST_UND_FREQ_PU S_ALARMS Y
Pickup Time Delay Y Y Y Y Y 14507 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_UND_FREQ_PUTD S_ALARMS Y
Dropout Setpoint Y Y Y Y Y 14509 Hz 2 FLOAT32 RWC 0 Y R_ALM_1ST_UND_FREQ_DO S_ALARMS Y
Dropout Time Delay Y Y Y Y Y 14511 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_UND_FREQ_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y Y 14513 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_1ST_UND_FREQ_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
Over Voltage Unbalance Y Y Y Y Y 14520 --- --- --- --- --- --- Alarm ID 27 S_ALARMS Y
Attributes Y Y Y Y Y 14520 --- 2 INT32U RWC 0x1082BB80 Y See Alarm Attributes for details. R_ALM_1ST_OVR_V_UNB_ATTR S_ALARMS Y
Source Register A Y Y Y Y Y 14522 --- 1 INT16U R R_VAB_50_60_CYC_UNB N R_ALM_1ST_OVR_V_UNB_REG_A S_ALARMS Y
Source Register B Y Y Y Y Y 14523 --- 1 INT16U R R_VBC_50_60_CYC_UNB N R_ALM_1ST_OVR_V_UNB_REG_B S_ALARMS Y
Source Register C Y Y Y Y Y 14524 --- 1 INT16U R R_VCA_50_60_CYC_UNB N R_ALM_1ST_OVR_V_UNB_REG_C S_ALARMS Y
Pickup Setpoint Y Y Y Y Y 14525 % 2 FLOAT32 RWC 0 Y R_ALM_1ST_OVR_V_UNB_PU S_ALARMS Y
Pickup Time Delay Y Y Y Y Y 14527 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_OVR_V_UNB_PUTD S_ALARMS Y
Dropout Setpoint Y Y Y Y Y 14529 % 2 FLOAT32 RWC See User Notes 0 Y Must be < Pickup Setpoint. R_ALM_1ST_OVR_V_UNB_DO S_ALARMS Y
Dropout Time Delay Y Y Y Y Y 14531 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_OVR_V_UNB_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y Y 14533 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_1ST_OVR_V_UNB_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
Over Voltage Total Harmonic Distortion Y Y Y Y Y 14540 --- --- --- --- --- --- Alarm ID 28 S_ALARMS Y
Attributes Y Y Y Y Y 14540 --- 2 INT32U RWC 0x1082B000 Y See Alarm Attributes for details. R_ALM_1ST_OVR_V_THD_ATTR S_ALARMS Y
Source Register A Y Y Y Y Y 14542 --- 1 INT16U R R_VAB_50_60_CYC_THD N R_ALM_1ST_OVR_V_THD_REG_A S_ALARMS Y
Source Register B Y Y Y Y Y 14543 --- 1 INT16U R R_VBC_50_60_CYC_THD N R_ALM_1ST_OVR_V_THD_REG_B S_ALARMS Y
Source Register C Y Y Y Y Y 14544 --- 1 INT16U R R_VCA_50_60_CYC_THD N R_ALM_1ST_OVR_V_THD_REG_C S_ALARMS Y
Pickup Setpoint Y Y Y Y Y 14545 % 2 FLOAT32 RWC 0 Y R_ALM_1ST_OVR_V_THD_PU S_ALARMS Y
Pickup Time Delay Y Y Y Y Y 14547 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_OVR_V_THD_PUTD S_ALARMS Y
Dropout Setpoint Y Y Y Y Y 14549 % 2 FLOAT32 RWC See User Notes 0 Y Must be < Pickup Setpoint. R_ALM_1ST_OVR_V_THD_DO S_ALARMS Y
Dropout Time Delay Y Y Y Y Y 14551 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_OVR_V_THD_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y Y 14553 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_1ST_OVR_V_THD_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
Phase Loss Y Y Y Y Y 14560 --- --- --- --- --- --- Alarm ID 29 S_ALARMS Y
Attributes Y Y Y Y Y 14560 --- 2 INT32U RWC 0x12820380 Y See Alarm Attributes for details. R_ALM_1ST_PHASE_LOSS_ATTR S_ALARMS Y
Source Register A Y Y Y Y Y 14562 --- 1 INT16U R R_VAB_50_60_CYC_RMS N R_ALM_1ST_PHASE_LOSS_REG_A S_ALARMS Y
Source Register B Y Y Y Y Y 14563 --- 1 INT16U R R_VBC_50_60_CYC_RMS N R_ALM_1ST_PHASE_LOSS_REG_B S_ALARMS Y
Source Register C Y Y Y Y Y 14564 --- 1 INT16U R R_VCA_50_60_CYC_RMS N R_ALM_1ST_PHASE_LOSS_REG_C S_ALARMS Y
Pickup Setpoint Y Y Y Y Y 14565 V 2 FLOAT32 RWC 0 Y Must be < Dropout Setpoint. R_ALM_1ST_PHASE_LOSS_PU S_ALARMS Y
Pickup Time Delay Y Y Y Y Y 14567 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_PHASE_LOSS_PUTD S_ALARMS Y
Dropout Setpoint Y Y Y Y Y 14569 V 2 FLOAT32 RWC See User Notes 0 Y R_ALM_1ST_PHASE_LOSS_DO S_ALARMS Y
Dropout Time Delay Y Y Y Y Y 14571 seconds 2 INT32U RWC --- 0 Y R_ALM_1ST_PHASE_LOSS_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y Y 14573 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_1ST_PHASE_LOSS_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
Digital Outputs to Associate – Standard Y Y Y Y Y 16222 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_UNARY_DIA_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
S_ALARMS
For PM5xxx series, the maximum value is 0x0003. (There are
2 digital outputs.)
Phase Reversal Y Y Y Y Y 16230 --- --- --- --- --- --- Alarm ID 104 S_ALARMS Y
Attributes Y Y Y Y Y 16230 --- 2 INT32U RWC --- 0x83000000 Y See Alarm Attributes for details. R_ALM_UNARY_PHASEREV_ATTR S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y Y 16232 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_UNARY_PHASEREV_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
S_ALARMS
For PM5xxx series, the maximum value is 0x0003. (There are
2 digital outputs.)
Reserved 16240 --- 60 --- --- --- --- --- R_RESERVED_13523 S_ALARMS
16300 --- --- --- --- --- --- S_ALARMS
Digital Alarms Y Y Y Y 16300 --- --- --- --- --- --- S_ALARMS Y
Digital Alarm DI1 Y Y Y Y 16300 --- --- --- --- --- --- Alarm ID 111 S_ALARMS Y
Attributes Y Y Y Y 16300 --- 2 INT32U RWC --- 0x95900800 Y See Alarm Attributes for details. R_ALM_DIG_S01_ATTR S_ALARMS Y
Pickup Time Delay Y Y Y Y 16302 seconds 2 INT32U RWC --- --- Y R_ALM_DIG_S01_PUTD S_ALARMS Y
Dropout Time Delay Y Y Y Y 16304 seconds 2 INT32U RWC --- --- Y R_ALM_DIG_S01_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y 16306 --- 1 BITMAP RWC --- --- Y Bitmap of digital outputs to associate with this alarm. R_ALM_DIG_S01_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
S_ALARMS
For PM5xxx series, the maximum value is 0x0003. (There are
2 digital outputs.)
Digital Alarm DI2 Y Y Y Y 16314 --- --- --- --- --- --- Alarm ID 112 S_ALARMS Y
Attributes Y Y Y Y 16314 --- 2 INT32U RWC --- 0x95901000 Y See Alarm Attributes for details. R_ALM_DIG_S02_ATTR S_ALARMS Y
Pickup Time Delay Y Y Y Y 16316 seconds 2 INT32U RWC --- --- Y R_ALM_DIG_S02_PUTD S_ALARMS Y
Dropout Time Delay Y Y Y Y 16318 seconds 2 INT32U RWC --- --- Y R_ALM_DIG_S02_DOTD S_ALARMS Y
Digital Outputs to Associate – Standard Y Y Y Y 16320 --- 1 BITMAP RWC 0 Y Bitmap of digital outputs to associate with this alarm. R_ALM_DIG_S02_DIGOUT Y
Bitmap is right-justified with the least significant bit associated
with digital output ID of 1.
S_ALARMS
For PM5xxx series, the maximum value is 0x0003. (There are
2 digital outputs.)
17252 --- --- --- --- --- --- S_ALARMS
Number of records in file Y Y Y Y 19005 --- 1 INT16U R --- 0 Y Number of records wriiten, resets to 0 on file clear R_LOG_NUM_OF_RECORDS S_FILES Y
First Record Sequence Number Y Y Y Y 19006 --- 1 INT16U R --- 0 Y First record in log R_LOG_FIRST_SEQ_NUM S_FILES Y
Last Record Sequence Number Y Y Y Y 19007 --- 1 INT16U R --- 0 Y Last record in the log R_LOG_LAST_SEQ_NUM S_FILES Y
Topic Mode Y Y Y Y 19008 --- 1 INT16U RWC --- 1 Y 0 = Power data model, 1 = Modbus register format R_LOG_TOPIC_MODE S_FILES Y
Start Time Y Y Y Y 19009 Minuites 1 INT16U RWC --- 0 Y Not used in PM5500 R_LOG_START_TIME S_FILES Y
Stop Time Y Y Y Y 19010 seconds 1 INT16U RWC --- 1440 Y Not used in PM5500 R_LOG_STOP_TIME S_FILES Y
Interval Control Minutes Y Y Y Y 19011 Minuites 1 INT16U RWC 1,5,10,15,30,60.1440 15 Y R_LOG_INT_CNTRL_MIN S_FILES Y
Interval Control Seconds Y Y Y Y 19012 seconds 1 INT16U RWC 0-59 0 Y R_LOG_INT_CNTRL_SEC S_FILES Y
Date/Time Last clear Y Y Y Y 19013 --- 4 DATETIME RWC --- N/A Y R_LOG_DT_LAST_CLEAR S_FILES Y
Record Item 1 Y Y Y Y 19017 --- 1 INT16U RWC --- 0 Y R_LOG_ITEM_1 S_FILES Y
Record Item 2 Y Y Y Y 19018 --- 1 INT16U RWC --- 0 Y R_LOG_ITEM_2 S_FILES Y
Frequency Voltage Channel Y Y Y Y Y 20013 --- 1 INT16U R 0–2 0 N 0 = Van, 1 = Vab, 2 = Vca, 3 = Var R_FREQUENCY_CHANNEL S_METERING
Input Signal Clipping (Over Range) Present 20014 --- 1 BITMAP R 0x0000 – 0x0003 0x0000 N Bitmap of input channels which are over range at this time. R_DIA_CLIPPING_PRES S_METERING
20015 --- 1 BITMAP R 0x0000 – 0x0003 0x0000 Y Bitmap of input channels which have been over range since should these bits be reset after the occurrence of a swell R_DIA_CLIPPING_SINCE_RESET
Input Signal Clipping (Over Range) Since Last Meter Reset S_METERING
last startup or reset condition?
Y Y Y Y Y 20016 --- 1 BITMAP R 0x0000 – 0x0007 0x0007 N 0 = Disabled, 1 = Enabled R_DIA_CAL_ENABLE_STATUS
Calibration Enabled/Disabled Status Bit 1 = Voltage, Bit 2 = Current, Bit 3 = Phase Shift S_METERING
EtherBrick Host Registers Y Y 64000 --- 1536 --- --- --- --- --- These are writeable from EB not from user serial port S_COMMUNICATIONS
EtherBrick AS Reserved from 64000 to 65535 Y Y 64000 --- --- --- --- --- --- S_COMMUNICATIONS
Host Registers Y Y 64000 --- --- --- --- --- --- S_COMMUNICATIONS
FDR Action Y Y 64000 --- 1 INT16U RW --- See EtherBrick document 31006337N FDR action register, used to provide status and request actions R_EB_FDR_ACTION S_COMMUNICATIONS
General Action Y Y 64001 --- 1 INT16U RW --- See EtherBrick document 31006337N Used to convey status and request actions R_EB_GENERAL_ACTION S_COMMUNICATIONS
Start ID code Y Y 64002 --- 2 INT16U R --- 0x4C,0x43,0x45,0x01 Y Register 1 MSB = 0x4C LSB = 0x43 Register 2 MSB = 0x45 R_EB_START_CODE
S_COMMUNICATIONS
LSB = 0x01
Config control Y Y 64004 --- 1 INT16U R --- See EtherBrick document 31006337Y Controls the options present in the Host registers R_EB_CONFIG_CONTROL S_COMMUNICATIONS
Config Action Y Y 64005 --- 1 INT16U RW --- See EtherBrick document 31006338N Action info passed to EtherBrick. EB will write to this. R_EB_CONFIG_ACTION S_COMMUNICATIONS
Protocol Options Y Y 64006 --- 1 INT16U RW --- See EtherBrick document 31006339Y R_EB_PROTOCOL_PARM S_COMMUNICATIONS
Device Name Length Y Y 64007 --- 1 INT16U R --- See EtherBrick document 31006340Y When a change is made on the EB side via web page for R_EB_DEVICE_NAME_LEN
example EB will write data via MB to the host registers the
host must then alert EB (trigger) that host reg have changed. S_COMMUNICATIONS
Device Name Characters Y Y 64008 --- 8 INT16U R --- See EtherBrick document 31006340Y R_EB_DEVICE_NAME_CHARS S_COMMUNICATIONS
Device Null Chars Y Y 64016 --- 1 INT16U R --- See EtherBrick document 31006341Y R_EB_DEVICE_NAME_NULL S_COMMUNICATIONS
Rotary Switch Override Y Y 64017 --- 1 INT16U RW --- See EtherBrick document 31006342Y R_EB_ROTARY_SW_OVR S_COMMUNICATIONS
IP Address Y Y 64018 --- 2 INT16U RW --- See EtherBrick document 31006341Y R_EB_IP_ADDRESS S_COMMUNICATIONS
IP Subnet Mask Y Y 64020 --- 2 INT16U RW --- See EtherBrick document 31006341Y R_EB_IP_SUBNET_MASK S_COMMUNICATIONS
IP Gateway Address Y Y 64022 --- 2 INT16U RW --- See EtherBrick document 31006341Y R_EB_IP_GATE_ADDRESS S_COMMUNICATIONS
FDR Config Control Y Y 64024 --- 1 INT16U RW --- See EtherBrick document 31006339Y R_EB_FDR_CONFIG_CONTROL S_COMMUNICATIONS
FDR Server1 Address Y Y 64025 --- 2 INT16U RW --- See EtherBrick document 31006340Y R_EB_FDR_SERVER_1_ADDRESS S_COMMUNICATIONS
FDR Server 2 Address Y Y 64027 --- 2 INT16U RW --- See EtherBrick document 31006341Y R_EB_FDR_SERVER_2_ADDRESS S_COMMUNICATIONS
FDR Control Interval Y Y 64029 --- 1 INT16U RW --- See EtherBrick document 31006342Y R_EB_FDR_CONTROL_INTERVAL S_COMMUNICATIONS
Gateway Control Y Y 64030 --- 1 INT16U RW --- See EtherBrick document 31006340Y R_EB_GW_CONTROL S_COMMUNICATIONS
Unit Id table Length Y Y 64031 --- 1 INT16U RW --- See EtherBrick document 31006341Y R_EB_UNIT_ID_TABLE_LEN S_COMMUNICATIONS
Unit Id Y Y 64032 --- 1 INT16U RW --- See EtherBrick document 31006342Y R_EB_UNIT_ID S_COMMUNICATIONS
Port Configuration Y Y 64033 --- 1 INT16U RW --- See EtherBrick document 31006343Y R_EB_PORT_CONFIG S_COMMUNICATIONS
Control Register SW Y Y 64034 --- 1 INT16U RW --- See EtherBrick document 31006339Y R_EB_SW_CONTOL_REG S_COMMUNICATIONS
Max filter DB size Y Y 64035 --- 1 INT16U RW --- See EtherBrick document 31006340Y R_EB_SW_FILTER_SIZE S_COMMUNICATIONS
Global age time Y Y 64036 --- 2 INT16U RW --- See EtherBrick document 31006341Y R_EB_SW_GLOBAL_TIME S_COMMUNICATIONS
Number of Ports SW Y Y 64038 --- 1 INT16U RW --- See EtherBrick document 31006342Y R_EB_SW_NUMBER_PORTS S_COMMUNICATIONS
Port control 1 Y Y 64039 --- 1 INT16U RW --- See EtherBrick document 31006343Y R_EB_SW_PORT_1_CONTROL S_COMMUNICATIONS
Port control 2 Y Y 64040 --- 1 INT16U RW --- See EtherBrick document 31006344Y R_EB_SW_PORT_2_CONTROL S_COMMUNICATIONS
Master IP Event Control Y Y 64144 --- 1 INT16U RW --- See EtherBrick document 31006354Y R_EB_MASTER_IP_EVENT_CNTRL S_COMMUNICATIONS
Master IP Comm Timout Y Y 64145 --- 1 INT16U RW --- See EtherBrick document 31006355Y R_EB_MASTER_IP_COM_TO S_COMMUNICATIONS
Master IP Holdup Time Y Y 64146 --- 1 INT16U R --- See EtherBrick document 31006356Y R_EB_MASTER_IP_HOLD_TM S_COMMUNICATIONS
Master IP Fallback mode Y Y 64147 --- 1 INT16U R --- See EtherBrick document 31006357Y R_EB_MASTER_IP_FALLBCK S_COMMUNICATIONS
Master IP 1 address Y Y 64148 --- 2 INT16U RW --- See EtherBrick document 31006358Y R_EB_MASTER_IP_1_ADDRESS S_COMMUNICATIONS
Master IP 2 address Y Y 64150 --- 2 INT16U RW --- See EtherBrick document 31006359Y R_EB_MASTER_IP_2_ADDRESS S_COMMUNICATIONS
Master IP 3 address Y Y 64152 --- 2 INT16U RW --- See EtherBrick document 31006360Y R_EB_MASTER_IP_3_ADDRESS S_COMMUNICATIONS
Extended Configuration Control 1 Y Y 64169 --- 1 INT16U RW --- See EtherBrick document 31006382Y R_EB_EXTENDED_CONFIG_CNTRL1 S_COMMUNICATIONS
Extended Configuration Control 2 Y Y 64455 --- 1 INT16U RW --- See EtherBrick document 31006407Y R_EB_EXTENDED_CONFIG_CNTRL2 S_COMMUNICATIONS
END Identifier Y Y 64465 --- 2 INT16U R --- 0x46,0x69,0x72,0x65 Y Fire' R_EB_END_ID S_COMMUNICATIONS
PM5110/11
PM5310
PM5330/31
PM5320
PM5340/41
PM5350
PM5550
Publish
Prohibited
When Allowed for
Command
Subsystem Command Name Command Tag Parameters User Notes Revenue Unprotected
Number
Security Command Interface
Active
REGISTER_ACCESS (0-999) Y Y Y Y Y Y Y Y
Reset Subsystem(s) to Default 1 C_RESET_SUBSYS_TO_DEFAULT Y Y Y Y Y Y Y Y (1) Command Semaphore Subsystem IDs Y
(2) 1 or -1 (For All Subsystems) 0 = Register Access
(3) Subsystem ID or -1 (For All Subsystems) 1 = System
2 = Metering
3 = Commands
4 = HMI
5 = Communications
6 = IO
7 = Alarms
8 = Files
9 = Diagnostics
10 = Security
SYSTEM (1000-1999) Y Y Y Y Y Y Y Y
Warm Start Reset 1000 C_WARM_START_RESET Y Y Y Y Y Y Y Y (1) Command Semaphore This command does not provide a Y
command status or result.
Cold Start Reset 1001 C_COLD_START_RESET N (1) Command Semaphore This command does not provide a Y
command status or result.
Set MAC Address 1500 C_SET_MAC_ID Y Y N (1) Command Semaphore This is applicable for meters
(2) Production Test Password having Ethernet as only
(3-8 ) MAC Address ["aabbcc112233" in UTF8 format] communication Interface
Set IP Parameters Address 1501 C_SET_IP_PARAM Y Y Y (1) Command Semaphore This is applicable for meters
(2-3) IP Address having Ethernet as only
(4-5) Sub net Mask communication Interface
(6-7) Gateway
( For example Eg: 0xC0A8 and 0x0201 for 192.168.2.1)
Set Default IP Param 1502 C_SET_IP_DEFAULT Y Y Y (1) Command Semaphore
METERING (2000-2999) Y Y Y Y Y Y Y Y
Basic Meter Setup 2000 C_BASIC_METER_SETUP Y Y Y Y Y Y Y N (1) Command Semaphore (13) Number VTs Y
(2) Number of Phases (14-15) VT Primary
(3) Number of Wires (16) VT Secondary
(4) Power System Configuration (17) Number CTs
(5) Nominal Frequency (18) CT Primary, Phase
(6-7) Nominal Voltage (19) CT Secondary, Phase
(8-9) Nominal Current (20) CT Primary, Neutral
(10-11) Nominal Power Factor (21) CT Secondary, Neutral
(12) Normal Phase Rotation (22) CT Location for 1 CT Metering
(23) VT Location for 1 VT Metering
(24) VT Connection Type
Demand System Setup 2002 C_DMD_SETUP Y Y Y Y Y Y Y Y (1) Command Semaphore Demand System ID Y
(2) Demand System ID 1 = Power
(3) Demand Method 2 = Current
(4) Demand Interval Duration 3 = Input Metering
(5) Demand Subinterval Duration
Energy Pulse Output Setup 2003 C_ENERGY_PULSE_OUTPUT_SETUP Y Y Y Y Y Y Y Y (1) Command Semaphore Digital Output ID Y
(2) Energy Channel 1 = Digital Output S01
(3) Digital Output ID 2 = Digital Output S02
(4-5) Pulse Weight 99 = Energy LED
(6) Energy Channel
(7) Digital Output ID For PM5110/11 reference below
(8-9) Pulse Weight parameters not applicable
(10) Energy Channel 1 = Digital Output S01
(11) Digital Output ID 99 = Energy LED
(12-13) Pulse Weight (10) Energy Channel = NaN
(11) Digital Output ID = NaN
(12-13) Pulse Weight = NaN
Field Calibration Setup 2004 C_SETUP_FIELD_CAL N (1) Command Semaphore (10-11) VT Ratio Correction Factor, Phase A Y
(2-3) CT Ratio Correction Factor, Phase A (12-13) VT Ratio Correction Factor, Phase B
(4-5) CT Ratio Correction Factor, Phase B (14-15) VT Ratio Correction Factor, Phase C
(6-7) CT Ratio Correction Factor, Phase C (16-17) Neutral-Ground Correction Factor
(8-9) CT Ratio Correction Factor, Neutral (Scout Only) (Scout Only)
Setup Remapping 2005 C_SETUP_REMAPPING N (1) Command Semaphore (6) Logical Phase A Current Y
(2) Phase A Voltage (7) Logical Phase B Current
(3) Phase B Voltage (8) Logical Phase C Current
(4) Phase C Voltage (9) Logical Phase N Current
(5) Phase N Voltage
Preset Accumuated Energy 2006 C_PRESET_ACCUMULATED_ENG N (1) Command Semaphore (18-21) Reactive Energy Delivered (34-37) Apparent Energy Delivered Y
(2-5) Active Energy Delivered (Into Load) (22-25) Reactive Energy Received (38-41) Apparent Energy Received
(6-9) Active Energy Received (Out of Load) (26-29) Reactive Energy Delivered + Received (42-45) Apparent Energy Delivered +
(10-13) Active Energy Delivered + Received (30-33) Reactive Energy Delivered - Received Received
(14-17) Active Energy Delivered - Received (46-49) Apparent Energy Delivered -
Received
Reset Cycle Count 2007 C_RESET_CYCLE_COUNT Y Y Y Y Y Y Y Y (1) Command Semaphore Y
Reset All Demands 2011 C_RESET_ALL_DMDS Y Y Y Y Y Y Y Y (1) Command Semaphore The Demand Reset Password is See Y
(2-5) Demand Reset Password verified if Revenue Security is User Note
active.
Reset Current Demand 2012 C_RESET_CUR_DMD Y Y Y Y Y Y Y Y (1) Command Semaphore Y
Reset Power Demand 2013 C_RESET_POWER_DMD Y Y Y Y Y Y Y Y (1) Command Semaphore The Demand Reset Password is See Y
(2-5) Demand Reset Password verified if Revenue Security is User Note
active.
Reset Input Metering Demand 2014 C_RESET_INPUT_MET_DMD Y Y (1) Command Semaphore Y
Reset All Peak Demands 2015 C_RESET_ALL_PEAK_DMDS Y Y Y Y Y Y Y Y (1) Command Semaphore The Demand Reset Password is See Y
(2-5) Demand Reset Password verified if Revenue Security is User Note
active.
Reset Current Peak Demands 2016 C_RESET_CUR_PEAK_DMDS Y Y Y Y Y Y Y Y (1) Command Semaphore Y
Reset Power Peak Demands 2017 C_RESET_POWER_PEAK_DMDS Y Y Y Y Y Y Y Y (1) Command Semaphore The Demand Reset Password is See Y
(2-5) Demand Reset Password verified if Revenue Security is User Note
active.
Reset Input Metering Peak Demand 2018 C_RESET_INPUT_MET_PEAK_DMD Y Y (1) Command Semaphore Y
Reset All Time-of-Use Multi-Tariff Energies 2022 C_RESET_ALL_TOU_MT_ENG Y Y Y Y Y Y (1) Command Semaphore Y Y
Reset All Energy Pulse Output Channels 2024 C_RESET_ALL_ENG_PULSE_OUTPUT Y Y Y Y Y Y Y Y (1) Command Semaphore Y Y
Reset Energy by Phase 2025 C_RESET_ALL_ENG_PHASE N (1) Command Semaphore Y
Set Calibration - Voltage Magnitude 2029 C_SAVE_CAL_VOLT_MAG Y Y Y Y Y Y Y N (1) Command Semaphore (4-5) Voltage Applied 01 (24-25) Voltage Reading 01 Y
(2) Production Test Password (6-7) Voltage Applied 02 (26-27) Voltage Reading 02
(3) Phase (8-9) Voltage Applied 03 (28-29) Voltage Reading 03
0 = A - LG, (10-11) Voltage Applied 04 (30-31) Voltage Reading 04
1 = B- LG, (12-13) Voltage Applied 05 (32-33) Voltage Reading 05
2 = C- LG, (14-15) Voltage Applied 06 (34-35) Voltage Reading 06
3 = N- LG, (16-17) Voltage Applied 07 (36-37) Voltage Reading 07
10 = A - HG, (18-19) Voltage Applied 08 (38-39) Voltage Reading 08
11 = B- HG, (20-21) Voltage Applied 09 (40-41) Voltage Reading 09
12 = C- HG, (22-23) Voltage Applied 10 (42-43) Voltage Reading 10
13 = N- HG
Set Calibration - Current Magnitude 50Hz 2030 C_SAVE_CAL_CUR_MAG_50HZ Y Y Y Y Y Y Y N (1) Command Semaphore (4-5) Current Applied 50Hz 01 (24-25) Current Reading 50Hz 01 Y
(2) Production Test Password (6-7) Current Applied 50Hz 02 (26-27) Current Reading 50Hz 02
(3) Phase (8-9) Current Applied 50Hz 03 (28-29) Current Reading 50Hz 03
0 = A - LG, (10-11) Current Applied 50Hz 04 (30-31) Current Reading 50Hz 04
1 = B- LG, (12-13) Current Applied 50Hz 05 (32-33) Current Reading 50Hz 05
2 = C- LG, (14-15) Current Applied 50Hz 06 (34-35) Current Reading 50Hz 06
3 = N- LG, (16-17) Current Applied 50Hz 07 (36-37) Current Reading 50Hz 07
10 = A - HG, (18-19) Current Applied 50Hz 08 (38-39) Current Reading 50Hz 08
11 = B- HG, (20-21) Current Applied 50Hz 09 (40-41) Current Reading 50Hz 09
12 = C- HG, (22-23) Current Applied 50Hz 10 (42-43) Current Reading 50Hz 10
13 = N- HG
Set Calibration - Current Phase Shift 50Hz 2031 C_SAVE_CAL_CUR_PH_SHIFT_50HZ Y Y Y Y Y Y Y N (1) Command Semaphore (4-5) Phase Shift Applied 50Hz 01 (24-25) Phase Shift Reading 50Hz 01 Y
(2) Production Test Password (6-7) Phase Shift Applied 50Hz 02 (26-27) Phase Shift Reading 50Hz 02
(3) Phase (8-9) Phase Shift Applied 50Hz 03 (28-29) Phase Shift Reading 50Hz 03
0 = A - LG, (10-11) Phase Shift Applied 50Hz 04 (30-31) Phase Shift Reading 50Hz 04
1 = B- LG, (12-13) Phase Shift Applied 50Hz 05 (32-33) Phase Shift Reading 50Hz 05
2 = C- LG, (14-15) Phase Shift Applied 50Hz 06 (34-35) Phase Shift Reading 50Hz 06
3 = N- LG, (16-17) Phase Shift Applied 50Hz 07 (36-37) Phase Shift Reading 50Hz 07
10 = A - HG, (18-19) Phase Shift Applied 50Hz 08 (38-39) Phase Shift Reading 50Hz 08
11 = B- HG, (20-21) Phase Shift Applied 50Hz 09 (40-41) Phase Shift Reading 50Hz 09
12 = C- HG, (22-23) Phase Shift Applied 50Hz 10 (42-43) Phase Shift Reading 50Hz 10
13 = N- HG
Set Calibration - Current Magnitude 60Hz 2032 C_SAVE_CAL_CUR_MAG_60HZ Y Y Y Y Y Y Y N (1) Command Semaphore (4-5) Current Applied 60Hz 01 (24-25) Current Reading 60Hz 01 Y
(2) Production Test Password (6-7) Current Applied 60Hz 02 (26-27) Current Reading 60Hz 02
(3) Phase (8-9) Current Applied 60Hz 03 (28-29) Current Reading 60Hz 03
0 = A - LG, (10-11) Current Applied 60Hz 04 (30-31) Current Reading 60Hz 04
1 = B- LG, (12-13) Current Applied 60Hz 05 (32-33) Current Reading 60Hz 05
2 = C- LG, (14-15) Current Applied 60Hz 06 (34-35) Current Reading 60Hz 06
3 = N- LG, (16-17) Current Applied 60Hz 07 (36-37) Current Reading 60Hz 07
4 = A - HG, (18-19) Current Applied 60Hz 08 (38-39) Current Reading 60Hz 08
5 = B- HG, (20-21) Current Applied 60Hz 09 (40-41) Current Reading 60Hz 09
6 = C- HG, (22-23) Current Applied 60Hz 10 (42-43) Current Reading 60Hz 10
7 = N- HG
Set Calibration - Current Phase Shift 60Hz 2033 C_SAVE_CAL_CUR_PH_SHIFT_60HZ Y Y Y Y Y Y Y N (1) Command Semaphore (4-5) Phase Shift Applied 60Hz 01 (24-25) Phase Shift Reading 60Hz 01 Y
(2) Production Test Password (6-7) Phase Shift Applied 60Hz 02 (26-27) Phase Shift Reading 60Hz 02
(3) Phase (8-9) Phase Shift Applied 60Hz 03 (28-29) Phase Shift Reading 60Hz 03
0 = A - LG, (10-11) Phase Shift Applied 60Hz 04 (30-31) Phase Shift Reading 60Hz 04
1 = B- LG, (12-13) Phase Shift Applied 60Hz 05 (32-33) Phase Shift Reading 60Hz 05
2 = C- LG, (14-15) Phase Shift Applied 60Hz 06 (34-35) Phase Shift Reading 60Hz 06
3 = N- LG, (16-17) Phase Shift Applied 60Hz 07 (36-37) Phase Shift Reading 60Hz 07
10 = A - HG, (18-19) Phase Shift Applied 60Hz 08 (38-39) Phase Shift Reading 60Hz 08
11 = B- HG, (20-21) Phase Shift Applied 60Hz 09 (40-41) Phase Shift Reading 60Hz 09
12 = C- HG, (22-23) Phase Shift Applied 60Hz 10 (42-43) Phase Shift Reading 60Hz 10
13 = N- HG
Set Calibration Point - Voltage Magnitude 2034 C_SAVE_CAL_POINT_VOLT_MAG N (1) Command Semaphore Y
(2) Production Test Password
(3) Calibration Table Index
(4-5) Applied Voltage Phase A
(6-7) Applied Voltage Phase B
(8-9) Applied Voltage Phase C
(10-11) Applied Voltage Neutral
Set Calibration Point - Current Magnitude 2035 C_SAVE_CAL_POINT_CUR_MAG N (1) Command Semaphore Meter will apply calibration values Y
(2) Production Test Password to table based on metered
(3) Calibration Table Index frequency.
(4-5) Applied Current Phase A
(6-7) Applied Current Phase B
(8-9) Applied Current Phase C
(10-11) Applied Current Neutral (Scout Only)
Set Calibration Point - Phase Shift 2036 C_SAVE_CAL_POINT_PH_SHIFT N (1) Command Semaphore Meter will apply calibration values Y
(2) Production Test Password to table based on metered
(3) Calibration Table Index frequency.
(4-5) Applied Phase Shift Phase A
(6-7) Applied Phase Shift Phase B
(8-9) Applied Phase Shift Phase C
(10-11) Applied Phase Shift Neutral (Scout Only)
Meter Test Mode Steady-State Control 2041 C_METER_TEST_MODE_CONTROL Y Y N (1) Command Semaphore
(2) Engineering Password
(3) Enable/Disable (1 = Enable, 0 = Disable)
(4) Control (1 = Nonvolatile, 0 = Volatile)
Start New Incremental Energy Interval 2047 C_START_NEW_INC_ENG_INTERVAL N (1) Command Semaphore Y
Get Calibration Coefficient 2051 C_GET_CALIBRATION Y Y Y Y Y Y Y N (1) Command Semaphore Response Field Only Response Field Only
(2) Production Test Password (5-6) Applied 01 (25-26) Reading 01
(3) Calibration type (7-8) Applied 02 (27-28) Reading 02
0 - Vlr Gain; (9-10) Applied 03 (29-20) Reading 03
1 - I 50hz Gain; (11-12) Applied 04 (31-32) Reading 04
2 - I 50hz Ph Shift; (13-14) Applied 05 (33-34) Reading 05
3 - I 60hz Gain; (15-16) Applied 06 (35-36) Reading 06
4 - I 60hz Ph Shift; (17-18) Applied 07 (37-38) Reading 07
(4) Phase (19-10) Applied 08 (39-30) Reading 08
0 = A - LG, (21-22) Applied 09 (41-42) Reading 09
1 = B- LG, (23-24) Applied 10 (43-44) Reading 10
2 = C- LG,
3 = N- LG,
10 = A - HG,
11 = B- HG,
12 = C- HG,
13 = N- HG
The response shall include these 4 parameters plus the applied and the reading values for the
respective calibration
Set gain for calibration calculation 2061 C_HIGH_LOW_GAIN_MANAGEMENT N (1) Command Semaphore
(2) Production Test Password
(3) Gain (0 = High gain,1 = Low gain)
Set RTC calibration value 2062 C_RTC_CALIBRATION N (1) Command Semaphore
(2) Production Test Password
(3) Calibration value
Set Time for Demand Synch 2063 C_DMD_SYNCH_TIME Y Y Y Y Y Y Y (1) Command Semaphore Time is 0000 to 2359 Y N
(2) Synch Time
COMMANDS (3000-3999) Y Y Y Y Y Y Y Y
Read Flash 3000 C_READ_FLASH N
Assign Pseudo Address 3001 C_ASSIGN_PSEUDO_ADDRESS Y Y Y Y Y Y Y N Y Y
De-assign Pseudo Address 3002 C_DE_ASSIGN_PSEUDO_ADDRESS Y Y Y Y Y Y Y N Y Y
Erase Block of Flash 3003 C_ERASE_BLOCK_OF_FLASH N (1) Command Semaphore
(2) Engineering Password
(3) Block of Flash to Erase
HMI (4000-4999) Y Y Y Y Y Y Y Y
HMI Setup 4000 C_HMI_SETUP Y Y Y Y Y Y Y Y (1) Command Semaphore
(2) HMI Contrast Setting
(3) HMI Backlight On/Off
(4) HMI Language
(5) HMI IEC/IEEE Mode
(6) HMI Date Format
(7) HMI Time Format
(8) HMI Backlight Timeout
(9) HMI Screen Timeout
(10) HMI Energy Resolution
(11) HMI Current Resolution
(12) HMI Voltage Resulution
(13) HMI Power Resolution
HMI Test 4002 C_HMI_TEST Y Y Y Y Y Y Y N (1) Command Semaphore If parameter (3) is 1 then
(2) Production Test Password parameter (4) is the screen
(3) Enable/Disable Test Mode number to be displayed. If
0 = Meter Control parameter (3) is -1 then
1 = Display Single Screen parameter (4) must also be -1 in
-1 = Display Test Screens in Auto-Scroll order to display a sequence of
(4) Screen To Be Displayed test screens in auto-scroll fashion.
COMMUNICATIONS (5000-5999) Y Y Y Y Y Y
Communications Setup 5000 C_COMMS_SETUP Y Y Y Y Y Y (1) Command Semaphore Communications Port ID Y
(2) Communications Port ID 1 = Standard RS-485
(3) RS-485 Comm Port (M/S) Protocol
(4) RS-485 Comm Port (M/S) Address
(5) RS-485 Comm Port (M/S) Baud Rate
(6) RS-485 Comm Port (M/S) Parity
(7) RS-485 Comm Port (M/S) Modbus ASCII Default Timeout
Reset Comm Port Counters 5001 C_RESET_COMM_CHANNEL_COUNT Y Y Y Y Y Y (1) Command Semphore Communications Port ID Y
(2) Communications Port ID 1 = Standard RS-485
IO (6000-6999) Y Y Y Y Y Y Y Y
Digital Output Setup 6000 C_DO_SETUP Y Y Y Y Y Y Y (1) Command Semaphore Digital Output ID
(2) Digital Output ID 1 = Digital Output S01
(3-22) Label 2 = Digital Output S02
(23) Behavioral Mode
(24) On Time For Timed Mode
Digital Input Setup 6001 C_DI_SETUP Y Y Y Y Y Y Y (1) Command Semaphore Digital Input ID
(2) Digital Input ID 1 = Digital Input S01
(3-22) Label 2 = Digital Input S02
(23) Debounce Time 3 = Digital Input S03
4 = Digital Input S04
De-energize Digital Output 6002 C_DE_ENERGIZE_DO Y Y Y Y Y Y Y Y (1) Command Semaphore Digital Output ID Y
(2) Digital Output ID 1 = Digital Output S01
2 = Digital Output S02
Energize Digital Output 6003 C_ENERGIZE_DO Y Y Y Y Y Y Y Y (1) Command Semaphore Digital Output ID Y
(2) Digital Output ID 1 = Digital Output S01
2 = Digital Output S02
Release Digital Output From Coil Hold 6004 C_RELEASE_DO_FROM_COIL_HOLD Y Y Y Y Y Y Y (1) Command Semaphore Digital Output ID Y
(2) 1 or -1 (For All Digital Outputs) 1 = Digital Output S01
(3) Digital Output ID or -1 (For All Digital Outputs) 2 = Digital Output S02
Release Digital Output From Override Control 6005 C_RELEASE_DO_FROM_OVERRIDE Y Y Y Y Y Y Y (1) Command Semaphore Digital Output ID
(2) 1 or -1 (For All Digital Outputs) 1 = Digital Output S01
(3) Digital Output ID or -1 (For All Digital Outputs) 2 = Digital Output S02
Place Digital Output In Override Control 6006 C_PLACE_DO_IN_OVERRIDE Y Y Y Y Y Y Y (1) Command Semaphore Digital Output ID
(2) 1 or -1 (For All Digital Outputs) 1 = Digital Output S01
(3) Digital Output ID or -1 (For All Digital Outputs) 2 = Digital Output S02
Reset Operation Counter for Digital Output 6007 C_RESET_COUNT_FOR_DO Y Y Y Y Y Y Y (1) Command Semaphore Digital Output ID Y
(2) 1 or -1 (For All Digital Outputs) 1 = Digital Output S01
(3) Digital Output ID or -1 (For All Digital Outputs) 2 = Digital Output S02
Reset On-Time for Digital Output 6008 C_RESET_ON_TIME_FOR_DO Y Y Y Y Y Y Y (1) Command Semaphore Digital Output ID Y
(2) 1 or -1 (For All Digital Outputs) 1 = Digital Output S01
(3) Digital Output ID or -1 (For All Digital Outputs) 2 = Digital Output S02
Reset Operation Counter for Digital Input 6009 C_RESET_COUNT_FOR_DI Y Y Y Y Y Y Y (1) Command Semaphore Digital Input ID Y
(2) 1 or -1 (For All Digital Inputs) 1 = Digital Input S01
(3) Digital Input ID or -1 (For All Digital Inputs) 2 = Digital Input S02
3 = Digital Input S03
4 = Digital Input S04
Reset On-Time for Digital Input 6010 C_RESET_ON_TIME_FOR_DI Y Y Y Y Y Y Y (1) Command Semaphore Digital Input ID Y
(2) 1 or -1 (For All Digital Inputs) 1 = Digital Input S01
(3) Digital Input ID or -1 (For All Digital Inputs) 2 = Digital Input S02
3 = Digital Input S03
4 = Digital Input S04
Setup Digital Input to Demand Associations 6011 C_DI_SETUP_DEMAND Y Y Y Y Y Y Y (1) Command Semaphore
(2) Digital Input ID for Demand System 1
(3) Digital Input ID for Demand System 2
(4) Digital Input ID for Demand System 3
(5) Digital Input ID for Demand System 4
(6) Digital Input ID for Demand System 5
(7) Digital Input ID for Demand System 6
Setup Digital Output to Demand Associations 6012 C_DO_SETUP_DEMAND Y Y Y Y Y Y Y (1) Command Semaphore
(2) Digital Output ID for Demand System 1
(3) Digital Output ID for Demand System 2
(4) Digital Output ID for Demand System 3
(5) Digital Output ID for Demand System 4
(6) Digital Output ID for Demand System 5
(7) Digital Output ID for Demand System 6
Setup Digital Input to Multi-Tariff Associations 6013 C_DI_SETUP_MULTI_TARIFF Y Y Y Y Y Y (1) Command Semaphore Y N
(2) Number of Multi-tariff Rates Active
(3) Number of Digital Inputs Used to Control Multi-tariff
Input Metering Setup 6014 C_INPUT_METERING_SETUP Y Y (1) Command Semaphore
(2) Input Metering Channel
(3-22) Label
(23) Mode
(24-25) Metering Pulse Weight
(26) Consumption Units Code
(27) Demand Units Code
(28) Digital Input Association
De-energize Digital Output While in Override 6015 C_DE_ENERGIZE_DO_OVERRIDE Y Y Y Y Y Y Y (1) Command Semaphore Digital Output ID
(2) Digital Output ID 1 = Digital Output S01
2 = Digital Output S02
Energize Digital Output While in Override 6016 C_ENERGIZE_DO_OVERRIDE Y Y Y Y Y Y Y (1) Command Semaphore Digital Output ID
(2) Digital Output ID 1 = Digital Output S01
2 = Digital Output S02
Setup Digital Input to Reset Incremental Energy 6017 C_DI_SETUP_INC_ENERGY Y (1) Command Semaphore Y
(2) Digital Input ID assigned to reset Incremental Energy
ALARMS (7000-7999) Y Y Y Y Y Y Y Y
Over/Under Alarm Setup 7000 C_OVR_UND_ALM_SETUP Y Y Y Y Y Y Y Y (1) Command Semaphore (16-19) Digital Outputs to Associate - Options Alarm ID
(2) Alarm ID (Scout Only) 1 = Over Current, Phase
(3) Priority (0=None, 1=High, 2=Medium, 3=Low) (20) Datalogs to Trigger (Scout Only) 2 = Under Current, Phase
(4) Setpoints (0 = Fixed, 1 = Variable) (21) Waveform Capture to Trigger (Scout Only) 3 = Over Current, Neutral
(5) Learning (0 = Not Learning, 1 = Learning) 4 = Over Current, Ground
(6) Enable (0 = Disabled, 1 = Enabled) 5 = Over Voltage, L-L
(7-8) Pickup Setpoint 6 = Under Voltage, L-L
(9-10) Pickup Time Delay 7 = Over Voltage, L-N
(11-12) Dropout Setpoint 8 = Under Voltage, L-N
(13-14) Dropout Time Delay 9 = Over Power, Active
(15) Digital Outputs to Associate - Standard 10 = Over Power, Reactive
11 = Over Power, Apparent
12 = Leading Power Factor,
True
13 = Lagging Power Factor,
True
14 = Leading Power Factor,
Displacement
15 = Lagging Power Factor,
Displacement
16 = Over Demand, Active
Power, Present
17 = Over Demand, Active
Power, Last
18 = Over Demand, Active
Power, Predicted
19 = Over Demand, Reactive
Power, Present
20 = Over Demand, Reactive
Power, Last
21 = Over Demand, Reactive
Power, Predicted
22 = Over Demand, Apparent
Power, Present
23 = Over Demand, Apparent
Power, Last
Custom Over/Under Alarm Creation 7001 C_CUSTOM_OVR_UND_ALM_CREATE Y Y (1) Command Semaphore 24 = Over Demand, Apparent
(28) Priority Alarm ID
Power, Predicted
(2) Alarm ID (29) Setpoints 41 = Custom Alarm 1
(3-22) Label (30) Learning 42 = Custom Alarm 2
(23) Subtype (31) Enable 43 = Custom Alarm 3
(24) Parameter (32) Source Register 44 = Custom Alarm 4
(25) Modifier (33) Data Type 45 = Custom Alarm 5
(26) Phases 46 = Custom Alarm 6
(27) Level 47 = Custom Alarm 7
48 = Custom Alarm 8
49 = Custom Alarm 9
50 = Custom Alarm 10
PM5500 only supports 1-5
Digital Alarm Setup 7007 C_DIGITAL_ALARM_SETUP Y Y Y Y Y Y Y (1) Command Semaphore (11-14) Digital Outputs to Associate - Options Alarm ID
(2) Alarm ID (Scout Only) 111 = Digital Input S01
(3) Priority (0=None, 1=High, 2=Medium, 3=Low) (15) Datalogs to Trigger (Scout Only) 112 = Digital Input S02
(4) Enable (0 = Disabled, 1 = Enabled) (16) Waveform Capture to Trigger (Scout Only) 113 = Digital Input S03
(5) Subtype (0 = Off, 1 = On) 114 = Digital Input S04
(6-7) Pickup Time Delay
(8-9) Dropout Time Delay
(10) Digital Outputs to Associate - Standard
Unary Alarm Setup 7008 C_UNARY_ALARM_SETUP Y Y Y Y Y Y Y Y (1) Command Semaphore (6-9) Digital Outputs to Associate - Options Alarm ID
(2) Alarm ID (Scout Only) 101 = Meter Power Up (Control
(3) Priority (0=None, 1=High, 2=Medium, 3=Low) (10) Datalogs to Trigger (Scout Only) Power Loss)
(4) Enable (0 = Disabled, 1 = Enabled) (11) Waveform Capture to Trigger (Scout Only) 102 = Meter Reset
(5) Digital Outputs to Associate - Standard 103 = Meter Diagnostics
104 = Phase Reversal
Smart Alarm Setup 7009 C_SMART_ALARM_SETUP N (1) Command Semaphore (9-10) THD
(2) Smart Alarm Enable (11-12) Phase Loss
(3-4) Voltage Tolerance (13-14 ) Over Current
(5-6) Frequency Tolerance (15-16) Power Factor
(7-8) Unbalance
Per Circuit Over Alarm Setup 7021 C_CIRCUIT_OVR_ALM_SETUP Y Y Y (1) Command Semaphore (16-19) Digital Outputs to Associate - Options Alarm ID
(2) Alarm ID (Scout Only) 9 = Over Power, Active
(3) Priority (0=None, 1=High, 2=Medium, 3=Low) (20) Datalogs to Trigger (Scout Only) 16 = Over Demand, Active
(4) Setpoints (0 = Fixed, 1 = Variable) (21) Waveform Capture to Trigger (Scout Only) Power, Present
(5) Learning (0 = Not Learning, 1 = Learning)
(6) Enable (0 = Disabled, 1 = Enabled)
(7) Circuit ( 1,2,3 )
(8-9) Pickup Setpoint
(10-11) Pickup Time Delay
(12-13) Dropout Setpoint
(14-15) Dropout Time Delay
(16) Digital Outputs to Associate - Standard
FILES (8000-8999) Y
Enable Data Log 8001 C_ENABLE_DATA_LOG Y Y Y Y Y Y Y (1) Command Semaphore Y
(2) File ID
(3) Enable/Disable (0=Disable, 1=Enable)
Setup Data Log 8002 C_SETUP_DATA LOG Y Y Y Y Y Y Y (1) Command Semaphore Y
(2) File ID
(3) Record Management Method
(4) Topic List Reference
(5) Start time
(6) Stop time
(7) Interval Control minutes (1,5,10,15,30,60,1440)
(8) ID Item 1
(9) ID Item 2
(10) ID Item 3
(11) ID Item 4
(12) ID Item 5
(13) ID Item 6
(14) ID Item 7
(15) ID Item 8
(16) ID Item 9
(17) ID Item 10
(18) ID Item 11
(19) ID Item 12
(20) ID Item 13
(21) ID Item 14
DIAGNOSTICS (9000-9999) Y Y Y
Reset Diagnostic Log 9000 C_RESET_DIA_ERROR_LOG Y Y Y (1) Command Semaphore Y
Get Data from a Block of Memory 9002 C_GET_DATA_FROM_MEMORY N (1) Command Semaphore Y
(2-3) Start Address
(4) Data Size
(5) Number of Elements to Retreive
Digital Input Override 9006 C_DI_OVERRIDE N (1) Command Semaphore Digital Input ID
(2) Engineering Password 1 = Digital Input S01
(3) 1 or -1 (For All Digital Inputs) 2 = Digital Input S02
(4) Digital Input ID or -1 (For All Digital Inputs) 3 = Digital Input S03
(5) Step Time In Seconds 4 = Digital Input S04
9007 C_TASK_SUSPEND N
9008 C_TASK_RESUME N
Alarm Event Queue Entry 9009 C_ALM_EVT_QUE_ENTRY N (1) Command Semaphore
(2) Engineering Password
(3) Entry Number
(4-7) Date/Time
(8) Record Type
(9) Register Number or Event ID
(10-13) Value
(14) Sequence Number
SECURITY (10000-10999) Y
Data Type Description Native Range N/A Value
UTF8 Alphanumeric 0-3 bytes 0x00
INT16 Signed Integer, 16 bits -32,768 - 32,767 0x8000
INT16U Unsigned Integer, 16 bits 0 - 65,535 0xFFFF
INT32 Signed Integer, 32 bits -2,147,483,648 – 2,147,483,647 0x80000000
INT32U Unsigned Integer, 32 bits 0 - 4,294,967,295 0xFFFFFFFF
INT64 Signed Integer, 64 bits 0x8000000000000000
FLOAT32 Floating Point, 32 bits +/- 1*10^38 0xFFC00000
FLOAT64 Floating Point, 64 bits +/-1.798*10^308 0xFFF8000000000000
BITMAP 0x8000
PORTAL A portal provides a means to access data of a size up to 125 registers by doing a Modbus block read of a single
without using a large number of registers. An example might be a data type of PORTAL100 located at register 1
would do a block read of 100 registers beginning at register 1000. The data at PORTAL100 could be stored in a
meter communications firmware as 100 16 bit quantities.
4Q FP PF Four Quadrant Floating -2 - 2 0xFFC00000
Point Power Factor
Notes
For status bitmaps that are multiple registers long, the most significant bit will
be set to indicate the entire bitmap is N/A.This does not apply to
configuration bitmaps. So, in setup commands that include a bitmap as a
parameter, the user must always include the desired value for these bitmaps.
Word 1
b0-b6: Year (0 - 127)
b7-b15: Reserved
Word 2
b0-b4: Day (1-31)
b5-b7: Weekday (1-7, 0 if not used)
b8-b11: Month (1-12)
b12-b15: Reserved
Word 3
b0-b5: Minutes (0-59)
b6: Reserved
b7: Time synchronization quality, 1 = non valid or non synchronization
b8-b12: Hour (0-23)
b13-b14: Reserved
b15: 0 = Standard time, 1 = Daylight Savings Time
Word 4
b0-b15: Millisecond (0 - 59999)
Word 1
b0-b7: Year (0 - 99)
b8-b15: Reserved
Word 2
b0-b4: Day (1-31)
b5-b7: Weekday (1-7, 0 if not used)
b8-b11: Month (1-12)
b12-b15: Reserved
Word 1
b0-b5: Minutes (0-59)
b6: Reserved
b7: Time synchronization quality, 1 = non valid or non synchronization
b8-b12: Hour (0-23)
b13-b14: Reserved
b15: 0 = Standard time, 1 = Daylight Savings Time
Word 2
b0-b15: Millisecond (0 - 59999)
ng a Modbus block read of a single register. This allows large data sets to be accessed
of PORTAL100 located at register 1000. In order to read the 100 registers, the user