DOCUMENTATION TESTING & COMMISSIONING

Location : Living - WPV 2213 Test Date : 06--04-23


Title : Physical Checks Unit Code : FCU-LV-WPV-2213

UNIT CLEANING BOLT & NUT TIGHTENING

FILTER CLEANING INSTALLATION COMPLETE


DOCUMENTATION TESTING & COMMISSIONING
Location : Living - WPV 2213 Test Date : 06--04-23
Title : Electrical Test Unit Code : FCU-LV-WPV-2213

VOLTAGE = 218,3 Volt CURRENT = 1,2 A

CIRCUIT BREAKER 16 A (FIXED TYPE) THERMOSTAT (FAN LOW SPEED)

THERMOSTAT (FAN MEDIUM SPEED) THERMOSTAT (FAN HIGH SPEED)


DOCUMENTATION TESTING & COMMISSIONING
Location : Living - WPV 2213 Test Date : 06--04-23
Title : Electrical Test Unit Code : FCU-LV-WPV-2213

MOTORIZED VALVE FUNCTION


DOCUMENTATION TESTING & COMMISSIONING
Location : Living - WPV 2213 Test Date : 06--04-23
Title : Mechanical Test Unit Code : FCU-LV-WPV-2213

AIR FLOW TEST : 1.397CFM SUPPLY AIR TEMPERATURE : 15,5 °C

WATER FLOW / BALANCING VALVE : 5 GPM SUPPLY WATER TEMP. (OUT CHILLER : 7,5 °C)

RETURN WATER TEMP. (IN CHILLER : 12,5 °C) WATER PRES. DROP BALANCING VALVE : 105,24 kPA
DOCUMENTATION TESTING & COMMISSIONING
Location : Living - WPV 2213 Test Date : 06--04-23
Title : Final Test Unit Code : FCU-LV-WPV-2213

ROOM TEMPERATURE : 21°C (DB) ROOM TEMPERATURE : 19°C (WB)