You are on page 1of 4

Document Cover Page Document Ref.

1TB02011-011C49-FFC-CHK-PH-0002

Policy Document Management Revision C0

Document No - 1TB02011-011C49-FFC-CHK-PH-0002

Rev - C0

Inspection Checklist for Domestic Water Distribution Valves Installation

Page 1 of 2
Document Cover Page Document Ref. 1TB02011-011C49-FFC-CHK-PH-0002

Policy Document Management Revision C0

Revision History
Revision Revision - Revision Approved
No. June-Date by by Description of Revision Status
Inspection Checklist for For Review
Rashad Domestic Water
C0 11-09-23 SIHJ Distribution Valves
Arab
Installation

Distribution
Name Title Department Date Issued

Page 2 of 2
TRIPPLE BAY ROSEWOOD HOTEL PROJECT

MEP WORKS PACKAGE

CONTRACT NUMBER : 1TB02-011C49-5010

Checklist Description: Domestic Water Supply Valves Installation and Inspection ITP No: ITP-ME-0001

WIR Description: Inspection Checklist No:CHK-PH-0002

Location of Inspection: Date of Inspection:

Drawing No: Work Inspection Request No:

SL.NO. Description of Inspection YES NO N/A REMARKS

1. GENERAL

1.1 Ensure the Shop Drawing is Approved

Ensure the Material Technical Submittal & Method statement is


1.2
Approved

1.3 Ensure the Material Inspection Request ( MIR ) Approved

1.4 All piping works are completed before Valve installation

2. HANGERS & SUPPORTS

Support the Valves where necessary to reduce load on the piping


2.1
assembly..

Hangers and supports with galvanized metallic coatings for piping


2.2
and equipment are utilized

3. Valve Installation

Ensure Operation Valves , that it fully opens and closes smoothly


3.1
and fully functional prior to Installation.

Ensure Valves are adequately supported and installed as per


3.2
manufacturer written instructions.

Valves are located easily accessible as per approved shop drawings


3.3
& details and provide separate support wherever necessary.

Install valves in horizontal piping with stem at or above center of


3.4
pipe.

Ensure Valves are positioned to allow full stem movement. (Rising


3.5
Stem Type) , complete open/close movement for Lever type.

Install drain valves for equipment at base of each water riser, at


3.6 low points in horizontal piping, and where required to drain water
piping.

Page 1 of 2
TRIPPLE BAY ROSEWOOD HOTEL PROJECT

MEP WORKS PACKAGE

CONTRACT NUMBER : 1TB02-011C49-5010

Checklist Description: Domestic Water Supply Valves Installation and Inspection ITP No: ITP-ME-0001

WIR Description: Inspection Checklist No:CHK-PH-0002

Location of Inspection: Date of Inspection:

Drawing No: Work Inspection Request No:

SL.NO. Description of Inspection YES NO N/A REMARKS

3.7 Ensure Check Valves are installed for proper direction of flow.

4. THREADED VALVES

Install shutoff valve close to water main on each branch and riser
serving plumbing fixtures or equipment, on each water supply to
4.1 equipment, and on each water supply to plumbing fixtures that do
not have supply stops. Use ball or gate valves for piping NPS 2 (DN
50) and smaller

Ensure that the inlet and outlet threads are undamaged and free of
4.2
debris.

Tighten to the desired orientation using a wrench on the hex on


4.3
the inlet side of the valve with teflon tape.

5. FLANGED GENERAL VALVES

Ensure Butterfly or Gate valves are utilized for piping NPS 2-1/2
5.1
(DN 65) and larger.

Make sure there is no warpage of the flange or misalignment of the


5.2
Valve in relation to the flange.

Examine Flange faces for conditions that might cause leakage.


Check bolting for proper size, length, and material. Verify that
5.3
gasket is of proper size, that its material composition is suitable for
service, and that it is free from defects and damage.

REMARKS: Status of Inspection:


1. Approved

2. Approved with Comments


3. Revise and resubmit
REQUESTED BY WITNESSED BY APPROVED BY
FIRST FIX QC ENGINEER SUPERVISON CONSULTANT CLIENT - AMAALA

Name: Name: Name:

Signature: Signature: Signature:

Date: Date: Date:

Page 2 of 2