You are on page 1of 3

DISCREPENCY SWITCH (ILLUMINATED)

FRMM6 Used for control and indication of circuit breakers


and electro-valves

Micro Rotary Switch FRMM6

USES AND APPLICATIONS

Microrotary sender switch suitable for control


of circuit breakers, disconnectors, contactors
and electrovalves

Dimensions number
X=
length
of units
mms

1 80

Dimensions 2 93
3 106
4 119
5 132
6 145
Electrical Diagram

Rotary sender switch “D” is suitable for remote


operations of circuit breakers and
disconnectors.They include elements for
signalling and control. Continuous and flashing
light.

Rotary sender switch with one signalling


element and three control elements.

Rotary sender switch with two signalling


element and two control elements.

Rotary sender switch with one signalling


element, one control element and one
discrepancy element.
Application and use

FRMM6 micro-sender-switches are mounted on switchboards and in telephonic and electric fields, where
small currents are required.

DESCRIPTION AND CONSTRUCTIONAL FEATURES OF THE UNIT

• front plate, round with 25 mms dia. or square shaped with 25 mms sides;
• contacts: stationary and moving. Moving contacts are mounted on the control shaft. The stationary
contacts are mounted on the melamine block either by soldering or with stand clamps for electric wire
connection;
• light supplied got by BA7S lamp for 24, 48, 60 Vdc, with bayonet cap;
Additional resistances are fitted for lamps when different voltages are required;
• trip system allows 2 to 4 positions. The positions supplied by micro-sender-switches are the same as
for type FRM 10.

FRMM 6 micro-sender-switches allow all connections as previously specified for FRM 10 switches
except the ones requiring dragging effect. (FRM 10 T).

RATED ELECTRICAL CHARACTERISTICS

• type FRMM 6

• thermal current Ith= 12 A

• insulation voltages Ui= 690 V

• utilization categories AC 14 AC 15 DC 14

• operational voltage (Ue) 400 V 400 V 110V

• operational current (le) 10A 6A 3,5A

• conditioned short-circuit current

• maximum peak current £ 1400 A

• joule integral (I2t) £ 30 k A2 s

Declaration of conformity to EN 60947-5-I STANDARDS.

All FRMM 6 models comply with EN 60947 -5-I EC directives. Thus they conform to EC directives n° 73/
23,93/68, 89/3396 (EMC), (low voltage directive).
TYPE TEST CARRIED OUT IN CESI LABORATORIES MILAN N° MP-94/032850.

INSTALLATION

Apart from boring, patterns shown in the following pages, the installation process of the FRMM 6 is the
same as that for FRM 10.

ADDRESS: 17 Ramsay Str. POSTAL: P. O. Box 38493 TEL: +27 11 493-5915


Booysens 2091 Booysens 2016 South Africa FAX: +27 11 493-8821
Johannesburg South Africa E-mail : sales@mimic.co.za WEB PAGE: mimic.co.za