FCC Room

This document summarizes the lighting design for the FCC Room located on the ground floor of the M Tower Project. It includes details about the 3 Philips T5 fluorescent luminaires installed at a height of 2.8 meters, as well as illuminance measurements on a reference plane 0.8 meters high, showing average, minimum and maximum illuminance values, and uniformity ratios meeting standards. Charts and tables present the spatial distribution of illuminance across the room.

Uploaded by

Aung Thu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
59 views3 pages

FCC Room

This document summarizes the lighting design for the FCC Room located on the ground floor of the M Tower Project. It includes details about the 3 Philips T5 fluorescent luminaires installed at a height of 2.8 meters, as well as illuminance measurements on a reference plane 0.8 meters high, showing average, minimum and maximum illuminance values, and uniformity ratios meeting standards. Charts and tables present the spatial distribution of illuminance across the room.

Uploaded by

Aung Thu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Object : FCC ROOM @ GROUND FLOOR

Installation : 3NOS OF ABB228 2X28W T5 PHILIPS TUBE @ 2.8M AFFL


Project number : M TOWER PROJECT
Date : 25.11.2020

3D luminance distribution, Variable view

Luminance in the illustration:


Minimum: : 7.48 cd/m²
Maximum: : 799 cd/m²

FCC Room.rdf
Object : FCC ROOM @ GROUND FLOOR
Installation : 3NOS OF ABB228 2X28W T5 PHILIPS TUBE @ 2.8M AFFL
Project number : M TOWER PROJECT
Date : 25.11.2020

Isolines representation, Illuminance, Reference plane No. 1

[m]
9

150
7 3

200
6

5
1

4
30
0

3
200

150

15 2
25

2 0
0

0
0.0 0.8 1.6
[m]
1 : 100

Illuminance [lx]

Height of the reference plane : 0.80 m


Average illuminance Eav : 240 lx
Minimum illuminance Emin : 74 lx
Maximum illuminance Emax : 372 lx
Uniformity g1 Emin/Em : 1 : 3.23 (0.31)
Uniformity g2 Emin/Emax : 1 : 5.01 (0.20)

FCC Room.rdf
Object : FCC ROOM @ GROUND FLOOR
Installation : 3NOS OF ABB228 2X28W T5 PHILIPS TUBE @ 2.8M AFFL
Project number : M TOWER PROJECT
Date : 25.11.2020

Table, Illuminance, Reference plane No. 1

82 91 93 91 (74)
[m] 104 121 128 129 101
9
139 163 178 186 144

174 211 237 259 196


8
205 254 290 321 246

225 279 315 346 265


7
234 292 316 332 259

251 311 314 310 243


6
272 343 327 303 240

295 [372] 341 305 241


5
295 [372] 342 305 240

275 344 326 302 239


4
251 312 315 309 242

238 294 316 331 257


3
229 283 318 348 267

202 251 296 329 253


2
245 272 206

184 194 151


1
124 133 105

88 92 76

-0.4 0.0 0.4 0.8


[m]
Illuminance [lx]

Height of the reference plane : 0.80 m


Average illuminance Eav : 240 lx
Minimum illuminance Emin : 74 lx
Maximum illuminance Emax : 372 lx
Uniformity g1 Emin/Em : 1 : 3.23 (0.31)
Uniformity g2 Emin/Emax : 1 : 5.01 (0.20)

FCC Room.rdf