Product information

Capacitive

Point level detection


VEGAPOINT 11
VEGAPOINT 21
VEGAPOINT 23
VEGAPOINT 24
VEGAPOINT 31

Document ID: 62649


Contents

Contents
1 Measuring principle................................................................................................................................................................................................ 3

2 Type overview.......................................................................................................................................................................................................... 6

3 Instrument selection............................................................................................................................................................................................... 7

4 Selection criteria..................................................................................................................................................................................................... 8

5 Mounting.................................................................................................................................................................................................................. 9

6 Transistor output................................................................................................................................................................................................... 11

7 Transistor output with IO-Link............................................................................................................................................................................. 12

8 Adjustment............................................................................................................................................................................................................ 13

9 Dimensions............................................................................................................................................................................................................ 14

Take note of safety instructions for Ex applications


62649-EN-210520

Please note the Ex specific safety information that you can find at www.vega.com and that comes with each instrument. In hazardous areas
you should take note of the appropriate regulations, conformity and type approval certificates of the sensors and power supply units. The sen-
sors must only be operated on intrinsically safe circuits. The permissible electrical values are stated in the certificate.

2 Capacitive
Measuring principle

1 Measuring principle
Functional principle - VEGAPOINT 11, 21, 23, 31 • Line break to the sensor element
An alternating electric field is generated at the tip of the measuring elec-
If a malfunction is detected or in case of voltage supply, the electronics
trode. If the sensor is covered with medium, the capacitance of the sen-
takes on a defined switching status, i.e. the output is open (safe state).
sor changes. This change is detected by the electronics and converted
into a switching command.
Adhesions are compensated as far as possible and therefore have no 5
influence on the measurement. 1

Area of application - VEGAPOINT 21, 23, 31


The VEGAPOINT is a capacitive sensor for point level detection
2
It is designed for industrial use in all areas of process technology and can
be used in water-based liquids or in bulk solids. 3
Typical applications are overfill and dry run protection. With a the small 4
sensor unit, VEGAPOINT can be also mounted e.g. in thin pipelines. The
sensor allows use in vessels, tanks and pipes. Thanks to its simple and Fig. 2: VEGAPOINT 24
robust measuring system, VEGAPOINT is virtually unaffected by the
1 360° status indication
chemical and physical properties of the medium. 2 Instrument housing
It also works under difficult measuring conditions such as turbulence, air 3 Process fitting
bubbles, strong external vibrations or changing media. In addition, the 4 Sensor
sensor can also detect foam. 5 Plug connection

Function monitoring
5 The electronics module of VEGAPOINT continuously monitors the follow-
1
ing criteria via frequency generation:
• Failure of the signal generation
2 • Line break to the sensor element
If a malfunction is detected or in case of voltage supply, the electronics
3 takes on a defined switching status, i.e. the output is open (safe state).
4
1.2 Application examples
Fig. 1: VEGAPOINT 21, 31 Food industry - Bottle cleaning system
1 LED illuminated ring
2 Instrument housing
3 Process fitting
4 Sensor
5 Plug connection

Functional principle - VEGAPOINT 24


The sensor simultaneously detects the capacitive and resistive part of
the measuring signal. If the measuring tip is covered by medium, the sen-
sor can distinguish between adherence and actual coverage. The type of
chamnge is recognised by the intelligent measured value acquisition and
transformed into a switching command.
Adhesions are compensated as far as possible and therefore have no Fig. 3: Point Level detection in bottle cleaning system
influence on the measurement.
Apart from the continuous level measurement, level detection is an es-
Area of application - VEGAPOINT 24 sential safety feature for the process industry. Many modern sensors for
The VEGAPOINT is a combined capacitive and conductive sensor for continuous level measurement are actually approved as overfill protec-
point level detection. tion system, however, a second, physically different measuring system
It is designed for industrial applications and is particularly suitable for provides the best safety and redundance.
point level detection in heavily adhering and/or pasty media or if a front- Thanks to their manifold application possibilities, VEGAPOINT level
flush installation is required. switches are ideal for all applications in the area of liquid detection. Dif-
The mechanical structure prevents abrasion effects. ferent electrical and mechanical versions enable simple integration into
existing control systems.
Typical applications are overfill and dry run protection. With a the small
sensor unit, VEGAPOINT can be also mounted e.g. in thin pipelines. The Advantages:
sensor allows use in vessels, tanks and pipes. Thanks to its simple and • Coloured 360° switching status display for easy recognition of switch-
robust measuring system, VEGAPOINT is virtually unaffected by the ing status
chemical and physical properties of the medium. • Point Level detection also with buildup
It also works under difficult measuring conditions such as turbulence, air • Various hygienic fittings available
bubbles, strong external vibrations or changing media. In addition, the • Highest chemical resistance even with parts that do not come into
sensor can also detect foam. contact with the medium

Function monitoring
The electronics module of VEGAPOINT continuously monitors the follow-
62649-EN-210520

ing criteria via frequency generation:


• Failure of the signal generation

Capacitive 3
Measuring principle

Chemical industry - Condensation vessel • Reliable point level detection even with dust generation
• Simple setup via Bluetooth adjustment

Pipelines

Fig. 4: Dry run protection in condensation vessel

In order to avoid overfilling or dry running of pumps, sensors for point lev- Fig. 6: Dry run protection in pipelines
el detection are an important safety element. The VEGAPOINT 21 point
level switch is ideally suited for universal applications. Even temperatures In order, for example, to transport drinking water even to the remotest
up to +115 °C (+239 °F) and pressure ranges up to 25 bar (+363 psig) do drinking water reservoir, pumping stations generate the required water
not impair the safe function. pressure, which is constantly monitored by a pressure transmitter.
Due to the wide range of applications, the level switches VEGAPOINT Since dry running usually leads to damage or failure of the pumps, a
are ideal for all measuring tasks in the field of stock-keeping of water- VEGAPOINT 21 level switch serves as dry run protection for the drinking
based liquids. water pumps.
Advantages: Advantages:

• High reliability • High plant availability, because wear and maintenance free
• Small mounting dimensions • Exact switching function independent of process condition
• Reliable switching point with water and vapour • Simple setup via Bluetooth adjustment
• Can also be used with oily and adhesive media after media adjust-
ment Food industry - additive mixing plant

Bulk solids

Fig. 7: Pipe monitoring in an additive mixing plant

Pasty mixing additives such as e. g. fruit concentrates or nougat cremes


are often used in food processing plants which are fed into the mixing or
filling plant under pressure.
The pipeline can be cleaned perfectly by the flat sensor.
Advantages:
• Front flush installation
• Ideal for CIP cleaning
• Hygienic fittings available
• Mechanically robust

Food industry - cleaning pig

Fig. 8: Reliable pipe monitoring despite cleaning pig

Viscous or pasty filling materials are often pumped through pipelines in


the food industry. In order to clean the pipes quickly and economically,
Fig. 5: Level switches in bulk solids storage
so-called cleaning pigs are used which push the media out of the pipe
with their sealing lips.
Many processes require bulk solids, granules and powdery substances. The flush front-mounted VEGAPOINT 24 is no obstruction to the cleaning
The special level switch VEGAPOINT 31 is optimised for the special pig. Neither the pig itself nor the cleaning fluid that follows it can harm the
requirements in bulk solids. It also works, for example, with strong dust sensor.
generation.
62649-EN-210520

Advantages:
Advantages: • Front flush installation
• Special level switch VEGAPOINT 31 for requirements in bulk solids • Ideal for cleaning pigs

4 Capacitive
Measuring principle

• Hygiene connections available


• Mechanically robust

Food industry - soft cheese filling

Fig. 9: Level measurement in heated tank with agitator

Cheese is stored in a heated tank for filling or dosing purposes. The liquid
cheese is stirred continuously to prevent thickening or lumping.
The agitator has rubber lips over the whole wall length which scrape off
the media and prevent caking and buildup on the vessel wall.
The VEGAPOINT 24 is front-flush, therefore no invasive sensor parts
protrude into the vessel. The sealing lip thus remains undamaged.
Advantages:
• Permanently temperature-resistant up to +115 °C
• Front flush installation
• No damage to the agitator
62649-EN-210520

Capacitive 5
Type overview

2 Type overview

VEGAPOINT 11 VEGAPOINT 21 VEGAPOINT 23 VEGAPOINT 24 VEGAPOINT 31

Applications Point level detection in wa- Point level detection in wa- Point level detection in wa- Point level measurement Point level detection in
ter-based liquids ter-based liquids ter-based liquids in adhesive and pasty light bulk solids
media
Version Compact version Compact version Compact version with tube Compact version Compact version
extension up to 1 m
Length - - 64 … 1000 mm - -
(2.52 … 39.4 in)
Process fitting Thread G½, G¾, G1 Thread G½, G¾, G1 Thread G½, G¾, G1 Thread G½, G¾, G1 Thread G½, G¾, G1
Thread M24 x 1.5 Thread M24 x 1.5 Thread ½ NPT, ¾ NPT, Thread M24 x 1.5 Thread M24 x 1.5
Thread ½ NPT, ¾ NPT, Thread ½ NPT, ¾ NPT, 1 NPT Clamp 1", 1½", 2" Thread ½ NPT, ¾ NPT,
1 NPT 1 NPT Clamp 1", 1½", 2" Collar socket 1 NPT
Hygienic adapter Clamp 1", 1½", 2" Collar socket Hygienic adapter Clamp 1", 1½", 2"
Collar socket Hygienic adapter Collar socket
Hygienic adapter Hygienic adapter
Process temperature -20 … +100 °C -40 … +115 °C Tube extension < 250 mm -40 … +115 °C -40 … +115 °C
(-4 … +212 °F) (-40 … +239 °F) -40 … +115 °C (-40 … +239 °F) (-40 … +239 °F)
+135 °C for 1 h +135 °C for 1 h (-40 … +239 °F) +150 °C for 15 min +135 °C for 1 h
Tube extension ≥ 250 mm +140 °C for 30 min
-40 … +80 °C +135 °C for 1 h
(-40 … +239 °F)
+135 °C for 1 h
Process pressure -1 … 25 bar (- -1 … 25 bar (- -1 … 25 bar (- -1 … 25 bar (- -1 … 25 bar (-
14.5 … 363 psig) 14.5 … 363 psig) 14.5 … 363 psig) 14.5 … 363 psig) 14.5 … 363 psig)
Signal output Transistor with IO-Link Transistor (PNP/NPN) Transistor (PNP/NPN) Transistor (PNP/NPN) Transistor (PNP/NPN)
Transistor with IO-Link Transistor with IO-Link Transistor with IO-Link Transistor with IO-Link
Bluetooth communi- - Integrated Integrated Integrated Integrated
cation
Approvals EG 1935/2004, FDA, ADI ATEX, EG 1935/2004, ATEX, EG 1935/2004, ATEX, EG 1935/2004, ATEX, IEC, cCSAus,
FDA, 3A, EHEDG, ASME FDA, 3A, EHEDG, ASME FDA, 3A, EHEDG, ASME EG 1935/2004, FDA,
BPE, USP Class VI, ADI, BPE, USP Class VI, ADI, BPE, USP Class VI, ADI, EHEDG, ADI, FDA, ship
China FDA, WHG, VLAR- China FDA, WHG, VLAR- China FDA, WHG, VLAR- approval
EM, SVTI, ship approval EM, SVTI, ship approval EM, SVTI

62649-EN-210520

6 Capacitive
Instrument selection

3 Instrument selection
VEGAPOINT 11 • IO-Link output
VEGAPOINT 11 is an ultra-compact, capacitive point level sensor with • Wireless adjustment
smallest installation dimensions. • M12 x 1 plug
It is suitable for the detection of water-based liquids. • Valve block according to ISO 4400

The optional universal connection for hygienic adapters allows easy


• Ex and hygienic approvals

installation and meets the hygiene requirements of the food, beverage


VEGAPOINT 24
and pharmaceutical industries.
The VEGAPOINT 24 is a combined capacitive and conductive point level
The small point level switch version has a compact stainless steel sensor with small installation dimensions. It is designed for industrial
housing and is available in the electronic version transistor output with applications and is particularly suitable for detecting heavily adhering or
additional digital IO-Link communication. pasty media or when front-flush mounting is required. The mechanical
VEGAPOINT 11 is adjustment free and has a clearly visible, coloured structure prevents abrasion effects.
switching status indication that can be seen all around. It also works under difficult measuring conditions such as turbulence, air
• From DK > 2 bubbles, strong external vibrations or changing media. In addition, the
• From ½ thread sensor can also detect foam.
• Universal connection for hygienic adapter VEGAPOINT 24 is largely independent of medium properties and there-
• Transistor output with IO-Link fore adjustment-free. It has a clearly visible, all-round coloured switching
• M12 x 1 plug status indication.
• Hygienic approvals
The optional universal connection for hygienic adapters allows easy
installation and meets the hygiene requirements of the food, beverage
VEGAPOINT 21 and pharmaceutical industries.
VEGAPOINT 21 is a capacitive point level sensor with small installation
The small point level switch version has a compact stainless steel
dimensions for the detection of water-based liquids.
housing and is available in the electronic version transistor output or as
VEGAPOINT 21 is largely independent of medium properties and there- transistor output with additional digital IO-Link communication.
fore adjustment-free. It has a clearly visible, all-round coloured switching
The sensor can be operated wirelessly via Bluetooth using a tablet or
status indication.
smartphone with an app. This allows you to set the switching behaviour,
The optional universal connection for hygienic adapters allows easy the application and many other parameters as required.
installation and meets the hygiene requirements of the food, beverage
and pharmaceutical industries. • From DK > 1.5
• From ½ thread
The small point level switch version has a compact stainless steel
• Universal connection for hygienic adapter
housing and is available in the electronic version transistor output or as
• Transistor output
transistor output with additional digital IO-Link communication.
• IO-Link output
The sensor can be operated wirelessly via Bluetooth using a tablet or • Wireless adjustment
smartphone with an app. This allows you to set the switching behaviour, • M12 x 1 plug
the application and many other parameters as required. • Valve block according to ISO 4400
• From DK > 1.5 • Ex and hygienic approvals
• From ½ thread
• Universal connection for hygienic adapter VEGAPOINT 31
• Transistor output VEGAPOINT 31 is a capacitive point level sensor with small installation
• IO-Link output dimensions for the measurement of light bulk solids.
• Wireless adjustment VEGAPOINT 31 is largely independent of medium properties and there-
• M12 x 1 plug fore adjustment-free. It has a clearly visible, all-round coloured switching
• Valve block according to ISO 4400 status indication.
• Ex and hygienic approvals
The optional universal connection for hygienic adapters allows easy
installation and meets the hygiene requirements of the food, beverage
VEGAPOINT 23 and pharmaceutical industries.
VEGAPOINT 23 is a capacitive point level sensor with selectable length
The small point level switch version has a compact stainless steel
for the measurement of water-based liquids.
housing and is available in the electronic version transistor output or as
The tube extension of the point level switch is available up to a length of transistor output with additional digital IO-Link communication.
1 m (39.4 in).
The sensor can be operated wirelessly via Bluetooth using a tablet or
VEGAPOINT 23 is largely independent of medium properties and there- smartphone with an app. This allows you to set the switching behaviour,
fore adjustment-free. It has a clearly visible, all-round coloured switching the application and many other parameters as required.
status indication.
• Optimized for light bulk solids
The optional universal connection for hygienic adapters allows easy
• From ½ thread
installation and meets the hygiene requirements of the food, beverage
• Universal connection for hygienic adapter
and pharmaceutical industries.
• Transistor output
The small point level switch version has a compact stainless steel • IO-Link output
housing and is available in the electronic version transistor output or as • Wireless adjustment
transistor output with additional digital IO-Link communication. • M12 x 1 plug
The sensor can be operated wirelessly via Bluetooth using a tablet or • Valve block according to ISO 4400
smartphone with an app. This allows you to set the switching behaviour, • Ex and hygienic approvals
the application and many other parameters as required.
• From DK > 1.5
• From ½ thread
62649-EN-210520

• Universal connection for hygienic adapter


• Tube version up to 1 m (39.4 in) length
• Transistor output

Capacitive 7
Selection criteria

4 Selection criteria
Criteria Feature VEGAPOINT
11 21 23 24 31
Vessel Compact probe ● ● – ● ●
Probe length max. 1 m – – ● – –
Pipelines from DN 20 ● ● – ● ●
Visualization Adjustable colour signalling – ● ● ● ●
Diagnostics IO-Link ● ● ● ● ●
Interfaces
Adjustment via VEGA Tools app – ● ● ● ●
Process fitting Threaded fittings G/NPT ● ● ● ● ●
Hygienic adapter ● ● ● ● ●
Collar socket – ● ● ● –
Clamp – ● ● ● ●
Water-based media > 10 % water content ● ● ● ● ○
Alcohols, acids, cleaning agents
Water-based media < 10 % water content – ○ ○ ● ○
Mineral oils, edible oils
Medium
Light-weight solids – ○ ○ ○ ●
Coffee powder, instant coffee, flour, sugar, salt
Adhesive, sticky media – ○ ○ ● ○
Honey, sugar molasses, cream

● = optimum suitability
○ = with media adjustment possible
– = not recommended / not possible

62649-EN-210520

8 Capacitive
Mounting

5 Mounting
Ambient conditions
The instrument is suitable for standard and extended ambient conditions
acc. to DIN/EN/IEC/ANSI/ISA/UL/CSA 61010-1. It can be used indoors
as well as outdoors.
2 1

Process conditions
Caution:
For safety reasons, the instrument must only be operated within
the permissible process conditions. You can find detailed informa-
tion on the process conditions in chapter " Technical data" of the
operating instructions or on the type label.

Hence make sure before mounting that all parts of the instrument ex-
posed to the process are suitable for the existing process conditions.
These are mainly:
• Active measuring component
• Process fitting
• Process seal
Process conditions in particular are:
• Process pressure
• Process temperature
• Chemical properties of the medium
• Abrasion and mechanical influences

Switching point
In general, VEGAPOINT can be mounted in any position. The instrument
3
must be mounted in such a way that the sensor is at the height of the
requested switching point.
Fig. 11: Installation examples - VEGAPOINT 23
1 Upper level detection (max.) as overflow protection
2 Point level detection e.g. for a process switching point
3 Lower level detection (min.) as dry run protection
1
Note that the switching point varies depending on the type of medium
and the mounting position of the sensor.

Adhesive products (VEGAPOINT 21, 24, 31)


In adhesive and viscous media, the surfaces of the sensor should pro-
2 trude into the vessel to avoid buildup. Therefore mounting bosses should
not exceed a certain length.

Fig. 10: Installation examples - VEGAPOINT 21


1 Upper level detection (max.) as overflow protection
2 Lower level detection (min.) as dry run protection
3 Dry run protection (min.) for a pump Fig. 12: Adhesive products

In horizontal pipelines, avoid mounting in the upper or lower area of the


pipe.
In the upper part of the pipe cavities can form due to air inclusions.
Solids can settle in the lower pipe area. Both can lead to measurement
errors.
In horizontal pipelines, lateral installation is therefore recommended.
62649-EN-210520

Capacitive 9
Mounting

(0.08")
2 mm
Fig. 15: VEGAPOINT 24 - 2 mm (0.08 in) reset in food application
B

Fig. 13: Installation in horizontal pipelines


x Recommended mounting area
A Not recommended - danger of air inclusions
B Not recommended - Danger of buildup

Adhesive products (VEGAPOINT 23)


Solids can settle in the lower tank area.
With adhesive and viscous media, the sensor should protrude into the
vessel.
In case of lateral installation, an instrument version with tube extension
can prevent unwanted detection of these deposits.

Fig. 14: Lateral installation - buildup


1 VEGAPOINT, laterally mounted

Inflowing medium
If VEGAPOINT is mounted in the filling stream, unwanted false measure-
ment signals can be generated. For this reason, mount VEGAPOINT at
a position in the vessel where no disturbances, e.g. from filling openings,
agitators, etc., can occur.

Food applications (VEGAPOINT 24)


In food or pharmaceutical application in which an agitator scrapes the
filling product from the vessel wall, you should install the sensor set back
by 2 mm (0.08 in).
This protects the plastic scrapers of the agitator from being damaged.
62649-EN-210520

10 Capacitive
Transistor output

6 Transistor output
Voltage supply Contact, plug connector Function/Polarity
4 PA - Potential equalisation
Note safety instructions
Always keep in mind the following safety instructions:
• Connect only in the complete absence of line voltage

Take note of safety instructions for Ex applications


In hazardous areas you must take note of the respective regula-
tions, conformity and type approval certificates of the sensors and
power supply units.

Voltage supply
Power the instrument via an energy-limited circuit (power max. 100 W)
acc. to IEC 61010-1, e.g.
• Class 2 power supply unit (acc. to UL1310)
• SELV power supply unit (safety extra-low voltage) with suitable inter-
nal or external limitation of the output current
Keep in mind the following additional factors that influence the operating
voltage:
• Lower output voltage of the power supply unit under nominal load
• Influence of additional instruments in the circuit (see load values in
chapter " Technical data")

Connection cable
Use cable with round cross section. Depending on the plug connection,
you have to select the outer diameter of the cable respectively so that the
seal effect of the cable gland is ensured.
The instrument is connected with standard four-wire cable. If electro-
magnetic interference is expected which is above the test values of
EN 61326-1 for industrial areas, shielded cable should be used.
• Valve plug ISO 4400, ø 4.5 … 7 mm
• Valve plug ISO 4400 with IDC crimping technology, ø 5.5 … 8 mm

Connection
Transistor output
We recommend connecting VEGAPOINT in such a way that the switch-
ing circuit is open when there is a level signal, line break or failure (safe
state).
The instrument is used to control relays, contactors, magnet valves,
warning lights, horns as well as PLC inputs.
For connection to binary inputs of a PLC.

VEGAPOINT 21, 23, 24, 31 - T


For connection to binary inputs of a PLC.

Valve plug ISO 4400


+
4 3
1 2 1
3
2
-
Fig. 16: Wiring plan connector ISO 4400 - transistor output three-wire
1 Voltage supply
2 PNP switching
3 NPN switching
4 PA - Potential equalisation

Contact, plug connector Function/Polarity


1 Voltage supply/+
62649-EN-210520

2 Voltage supply/-
3 Transistor output

Capacitive 11
Transistor output with IO-Link

7 Transistor output with IO-Link


Voltage supply
The data for power supply are specified in chapter " Technical data".
Power the instrument via an energy-limited circuit (power max. 100 W)
acc. to IEC 61010-1, e.g.
• Class 2 power supply unit (acc. to UL1310)
• SELV power supply unit (safety extra-low voltage) with suitable inter-
nal or external limitation of the output current
Keep in mind the following additional factors that influence the operating
voltage:
• Lower output voltage of the power supply unit under nominal load
• Influence of additional instruments in the circuit (see load values in
chapter " Technical data")

Connection cable
The instrument is connected with standard four-wire cable. If electro-
magnetic interference is expected which is above the test values of
EN 61326-1 for industrial areas, shielded cable should be used.
• M12 x 1 plug

Connection
Transistor output with IO-Link
VEGAPOINT 11, 21, 23, 24, 31
For connection to binary inputs of a PLC.

M12 x 1 plug
+
3 3
2 1
3 4 out 2 1
out 1
2 2
-
Fig. 17: Wiring plan M12 x 1 plug - Transistor output, three-wire
1 Voltage supply
2 PNP switching
3 NPN switching

Contact, plug connector Function/Polarity


1 Voltage supply/+
2 Transistor output 2
3 Voltage supply/-
4 Transistor output 1/IO-Link 62649-EN-210520

12 Capacitive
Adjustment

8 Adjustment
8.1 VEGAPOINT 11
The switching status of VEGAPOINT can be checked from outside
(signal lamp).

8.2 VEGAPOINT 21, 23, 24, 31


Local adjustment
The switching status of VEGAPOINT can be checked from outside (LED
illuminated ring).

Wireless adjustment
The optionally integrated Bluetooth module enables in addition a wireless
adjustment of VEGAPOINT via standard adjustment devices:
• Smartphone/tablet (iOS or Android operating system)
• PC/notebook with Bluetooth LE or Bluetooth USB adapter (Windows
operating system)

1
3

4
Fig. 18: Wireless connection to standard adjustment devices with integrated
Bluetooth LE or alternatively Bluetooth USB adapter.
1 Sensor
2 Smartphone/Tablet
3 PC/Notebook
4 Bluetooth USB adapter

With the operating app you can change the parameters of the sensor and
retrieve detailed diagnostic information.
These include, among other things:
• Switching function
• Application
• Switching outputs
• Switching and reset delay
• Display colour and brightness of the illuminated ring
• Units
• Simulation
• Sensor information
• Peak values
• Device status
62649-EN-210520

Capacitive 13
Dimensions

9 Dimensions
VEGAPOINT 11, standard version - thread VEGAPOINT 21, hygienic version - thread
M12 x 1 M12 x 1 M12 x 1 M12 x 1
10 mm

10 mm
(0.39")

(0.39")
ø 36 mm ø 36 mm
ø 21,5 mm ø 21,5 mm (1.42") (1.42")
(0.85") (0.85")
98,4 mm

98,4 mm
(3.87")

(3.87")
SW 21/32 SW 21/32

119 mm
(4.69")

119 mm
(4.69")
G1/2, SW 21/32 SW 21/32
1/2 NPT,
G3/4, G1
3/4 NPT, 1 NPT

15 mm
(0.59")
ø 18 mm G1/2,
41 mm
(1.61")

(0.71") G3/4, G1

12,5 mm
ø 30 mm

47,5 mm

(0.49")
(1.87")
(1.18")
1 2 ø 18 mm
(0.71")

Fig. 19: VEGAPOINT 11, standard version - thread 1 2


1 Thread G½, G¾, G1 (DIN ISO 228/1) with M12 x 1 plug connection ø 50,5 mm
2 Thread ½ NPT, ¾ NPT, 1 NPT with M12 x 1 plug connection (1.99")

Fig. 22: VEGAPOINT 21, hygienic version - thread with M12 x 1 plug
VEGAPOINT 11, hygienic version - thread 1 Thread G½, G¾, G1 for hygienic threaded adapter (DIN ISO 228/1) with
M12 x 1 M12 x 1 plug connection
2 VEGAPOINT, hygienic version in threaded adapter, Clamp
10 mm
(0.39")

ø 21,5 mm VEGAPOINT 23, standard version - thread


(0.85")
98,4 mm
(3.87")

SW22 42 mm 70 mm
36 mm
(1.65") (2.76")
(1.42")
G1/2 28 mm 53 mm
ø 27 mm
(1.10") (2.07")
ø 30 mm (1.06")
12,5 mm
47,5 mm

(0.49")
(1.87")

ø 18 mm (1.18")
(0.71")

42 mm

39 mm
(1.65")

(1.54")
1 2
35 mm
(1.38")

ø 50,5 mm
(1.99")

Fig. 20: VEGAPOINT 11, hygienic version - thread


ø 36 mm ø 36 mm ø 36 mm
1 Thread G½ for hygienic threaded adapter (DIN ISO 228/1) with M12 x 1 plug (1.42") (1.42") (1.42")
73 mm
(2.87")

73 mm

73 mm
(2.87")

(2.87")
connection
2 VEGAPOINT, hygienic version in threaded adapter, Clamp
SW 21/32 SW 21/32 SW 21/32

VEGAPOINT 21, standard version - thread 1/2 NPT, G1/2, G1/2, G3/4, G1
3/4 NPT, 1NPT G3/4, G1 3/4 NPT, 1NPT

M12 x 1 M12 x 1 M12 x 1 ø 18 mm ø 18 mm ø 18 mm


(2.52, 3.94, 5.91, 7.87, 9.84")

(2.52, 3.94, 5.91, 7.87, 9.84")

(0.71") (0.71") (0.71")


64, 100, 150, 200, 250 mm

64, 100, 150, 200, 250 mm

ø 36 mm ø 36 mm ø 36 mm 1 2 3
251...1000 mm
(9.88...39.37")

(1.42") (1.42") (1.42")


119 mm

119 mm
(4.69")

(4.69")

119 mm
(4.69")

15 mm
(0.59")

SW 21/32 SW 21/32

G1/2, G1/2,
1/2 NPT,
G3/4, G1 G3/4, G1
3/4 NPT, 1 NPT
15 mm
(0.59")

ø 18 mm ø 18 mm
41 mm

41 mm
(1.61")

(1.61")

(0.71") (0.71")

1 2 3

Fig. 21: VEGAPOINT 21, standard version - thread with M12 x 1 plug Fig. 23: VEGAPOINT 23, standard version - thread with valve plugs acc. to
1 Thread G½, G¾, G1 (DIN ISO 228/1) with M12 x 1 plug connection ISO 4400
2 Thread G½, G¾, G1 (DIN ISO 228/1), all-metal housing with M12 x 1 plug con- 1 Thread ½ NPT, ¾ NPT, 1 NPT with ISO 4400 valve plug
nection 2 Thread G½, G¾, G1 (DIN ISO 228/1) with ISO 4400 valve plug with IDC
3 Thread ½ NPT, ¾ NPT, 1 NPT with M12 x 1 plug connection method of termination
3 Thread G½, G¾, G1 (DIN ISO 228/1) or thread ½ NPT, ¾ NPT, 1 NPT, with
ISO 4400 valve plug with hinged cover
62649-EN-210520

14 Capacitive
Dimensions

VEGAPOINT 24, standard version - thread VEGAPOINT 31, standard version - thread
42 mm 70 mm 42 mm 70 mm
36 mm 36 mm
(1.65") (2.76") (1.65") (2.76")
(1.42") (1.42")
28 mm 53 mm 28 mm 53 mm
ø 27 mm ø 27 mm
(1.10") (2.07") (1.10") (2.07")
(1.06") (1.06")

39 mm
42 mm

(1.54")
(1.65")

42 mm

39 mm
(1.65")

(1.54")
35 mm
(1.38")

35 mm
(1.38")
ø 36 mm ø 36 mm
(1.42") (1.42")
109,5 mm

109,5 mm

109,5 mm
(4.31")

(4.31")

(4.31")

114 mm

114 mm

114 mm
(4.49")

(4.49")

(4.49")
SW 27 / SW 27 / SW 27 / SW 21/32 SW 21/32 SW 21/32
32 / 36 32 / 36 32 / 36

G1/2, G1/2, G1/2, G1/2,


G3/4, G1 G3/4, G1 G3/4, G1 G3/4, G1 G1/2, 1/2 NPT

15 mm
(0.59")
G3/4, G1 3/4 NPT, 1 NPT
37 mm

37 mm

37 mm
(1.46")

(1.46")

(1.46")

ø 18 mm ø 18 mm ø 18 mm ø 18 mm

41 mm
(1.61")
(0.71") (0.71") (0.71") (0.71")

1 2 3 1 2 3

Fig. 24: VEGAPOINT 24, standard version - thread with valve plugs acc. to
Fig. 26: VEGAPOINT 31, standard version - thread with valve plugs acc. to
ISO 4400
ISO 4400
1 Thread G½, G¾, G1 (DIN ISO 228/1) with ISO 4400 valve plug
1 Thread G½, G¾, G1 (DIN ISO 228/1) with ISO 4400 valve plug
2 Thread G½, G¾, G1 (DIN ISO 228/1) with ISO 4400 valve plug with IDC
2 Thread G½, G¾, G1 (DIN ISO 228/1) with ISO 4400 valve plug with IDC
method of termination
method of termination
3 Thread G½, G¾, G1 (DIN ISO 228/1) with ISO 4400 valve plug with hinged lid
3 Tread ½ NPT, ¾ NPT, 1 NPT with ISO 4400 valve plug with hinged cover

VEGAPOINT 24, hygienic version - thread VEGAPOINT 31, hygienic version - thread
36 mm
(1.42") 36 mm 36 mm
(1.42") (1.42")
ø 27 mm
(1.06") ø 27 mm ø 27 mm
(1.06") (1.06")
35 mm
(1.38")

35 mm

35 mm
(1.38")

(1.38")
ø 36 mm
ø 36 mm ø 36 mm (1.42")
(1.42") (1.42") ø 36 mm ø 36 mm
(1.42") (1.42")
109,5 mm

149 mm

149 mm
(5.87")
(4.31")

(5.87")
109,5 mm
109,5 mm

(4.31")
(4.31")

SW 36 SW 36 SW 21/32 SW 21/32

ø 30 mm G1/2
(1.18")
12,5 mm
28,5 mm

ø 30 mm
47,5 mm
27 mm
(1.06")

(1.12")

(0.08")

(0.49")
(1.87")

G1 G1
2 mm

(1.18")
ø 18 mm
(0.71")

1 2 3 1 2
ø 29,5 mm ø 30 mm ø 50,5 mm
(1.16") (1.18") (1.99")
ø 50,5 mm
(1.99")
Fig. 25: VEGAPOINT 24, hygienic version - thread with ISO 4400 plug
1 Thread G1 for hygienic threaded adapter (DIN ISO 228/1) with ISO 4400 plug Fig. 27: VEGAPOINT 31, hygienic version - thread with ISO 4400 plug
connection 1 Thread G½ for hygienic threaded adapter (DIN ISO 228/1) with ISO 4400 plug
2 Thread G1 with 40° cone for hygienic threaded adapter, metallic sealing, with connection
ISO 4400 plug connection 2 VEGAPOINT, hygienic version in threaded adapter, Clamp
3 VEGAPOINT, hygienic version in threaded adapter, Clamp
62649-EN-210520

Capacitive 15
All statements concerning scope of delivery, application, practical use and operating conditions of the sensors and processing systems correspond to the information
available at the time of printing.
Subject to change without prior notice

© VEGA Grieshaber KG, Schiltach/Germany 2021


62649-EN-210520

VEGA Grieshaber KG
Am Hohenstein 113 Phone +49 7836 50-0
77761 Schiltach E-mail: info.de@vega.com
Germany www.vega.com

You might also like