Professional Documents
Culture Documents
Note that the P543, P544, P545 and P546 relays do not include any of the above features,
except CT ratio mismatch compensation, and as such would not be suitable for the
protection of in-zone transformer feeders.
2.2.5.1 Transformer magnetising inrush and High set differential setting
The magnetising inrush current to a transformer appears as a large operating signal to the
differential protection. Special measures are taken with the relay design to ensure that no
maloperation occurs during inrush.
Figure 6 shows a transformer magnetising characteristic. To minimise material costs, weight
and size, transformers are generally operated near to the ‘knee point’ of the magnetising
characteristic. Consequently, only a small increase in core flux above normal operating
levels will result in a high magnetising current.
Flux, j
2j
jm
Magnetising current, Ie
P1006ENa
V
j
+ jm
Ie
Steady
state
- jm
Ie
j
+2jm
V
Switch on at
voltage zero
P1007ENa
P1007ENa
In addition to compensating for the phase shift of the protected transformer, it is also
necessary to mimic the distribution of primary zero sequence current in the protection
scheme.
Figure 8 shows the need for zero sequence current filtering for differential protection across
a transformer. The power transformer delta winding acts as a ‘trap’ to zero sequence
current. This current is therefore only seen on the star connection side of the transformer
and hence as differential current.
The filtering of zero sequence current has traditionally been provided by appropriate delta
connection of main line CT secondary windings. In the P540 relays, zero sequence current
filtering is automatically implemented in software when a delta connection is set for a
software interposing CT. Where a transformer winding can pass zero sequence current to
an external earth fault, it is essential that some form of zero sequence current filtering is
employed. This would also be applicable where in zone earthing transformers are used.
I0
IR1 I0 IR2
Relay 1 Relay 2
IR1 = 0 IR2 = I0
Received IR2 = I0 Received IR1 = I0
P1008ENa Idiff = I0 Idiff = I0 P1008ENa
For operational reasons, it may be necessary, under certain circumstances, to switch out
one line end and its associated relay on a three terminal circuit. By altering the
‘Reconfiguration’ setting at any end of the line, an operator can command any pair of relays
to work as a two terminal system. The ‘configured out’ relay can then be switched off,
leaving the line to be protected by the other two relays. A restore command can be issued to
reconfigure the system back to three terminal operation.
Four reconfiguration settings are available:
- Three ended
- Two ended local and remote 1 (L & R1)
- Two ended local and remote 2 (L & R2)
- Two ended remote 1 and remote 2 (R1 & R2)
Before a configuration command can be successfully initiated, it is necessary to energise the
‘reconfiguration interlock’ and ‘Inhibit Current Differential’ opto isolated inputs. The latter
input will disable tripping via the current differential elements from all three relays to ensure
that the scheme will remain stable during reconfiguration.
It must be ensured that the line end to be ‘configured out‘ is open before issuing a
reconfiguration command. If this is not done, any current flowing in or out of the ‘configured
out’ end will be seen as fault current and may cause the other relays to operate.
If the new configuration setting issued to the local relay is L & R1 or L & R2, the trip outputs
of the two ‘2-ended’ relays will remain inhibited by the ‘Inhibit Current Differential’ input at the
local relay. The ‘inhibit trip/alarm outputs’ opto should be de-energised to enable the trip
outputs reconfigured scheme. If the new configuration setting is R1 & R2, the output
contacts of the two remote relays will not be inhibited as they will ignore all commands from
the local relay.
The scheme may be restored to a three terminal configuration by selecting ‘three ended‘ at
any terminal. This will occur irrespective of the status of the opto inputs but is subject to a
healthy communications channel being detected.
2.2.7 Mesh corner and 1½ breaker switched substations
Where a line is fed from a mesh corner or 1½ breaker switched substation, as shown in
Figure 9, then two options are available for CT connections to the relay. The first is by
parallelling the two sets of line CTs into a common input, ‘A’. The second is by using two
separate inputs for each set of line CTs, ‘B’. The P544 and P546 relays are designed with
an additional set of input CTs specifically for this purpose.
In the case of a through fault as shown, the relay connected to circuit ‘A’ should see no
current and as such, will remain stable. Under this condition, it should be noted that no bias
is produced in the relay. To ensure relay stability, the two sets of line CTs should be as near
as identical in all characteristics, and equally loaded, such that the relaying connection is at
the equipotential point of the secondary leads.
In the case of circuit ‘B’ no differential current should result. A large bias current will
however exist, providing a high degree of stability in the event of a through fault. This bias
will also ensure stability where CTs are not closely matched. Thus, circuit ‘B’ is the preferred
connection for such applications and so the P544 and P546 relay models would normally be
specified.