REPORT OF EXAMINATION AND TEST OF AIR RECEIVER

REPORT NO: AR/R1 JOB NO: ASC-20-2888

CLIENT NAME & ADDRESS: M/S.EMPOL LIMITED LLC, DUBAI, UNITED ARAB EMIRATES

LOCATION: UMM RAMOOL, DUBAI

MAKER OR SUPPLIER OF EQUIPMENT SURVEY REQUESTED BY: TYPE OF INSPECTION:


AIR RECEIVER : OKS M/S BHATIA BROTHERS FZE PERIODIC

Serial No: Year of Installation: Design Pressure: Drive:


AIR RECEIVER : 501368 2003 AIR RECEIVER: 11.0 bar NOT APPLICABLE

Maximum Set Working Pressure: Model/ Type: 3.5282.10290 Test Pressure: Automatic Pressure
VERTICAL AIR RECEIVER
11.0 bar TANK
NIL Load/Switch On: NA

Capacity: Pressure Gauge Range: Test Duration: Automatic Pressure


AIR RECEIVER : 5000 L 0-25.0 bar NIL Load/Switch Off: NA
Shell/Dished End
Safety Valve Set Pressure: Safety Valve Type: Working Temperature:
Thickness:
11.0 bar SPRING LOADED -10̊ C To + 50̊ C
8.4mm/8.5mm
Temperature Gauge:
Equipment Description : VIRTICAL AIR RECEIVER TANK
NOT FITTED
ASC Test Method No: ASC/ITP/11 ASC Test Equipment No: ASC/EQ/12

Standard Reference& Regulation: NBIC PART2: 2017 Year of Next Hydro test: 2023

Date Of Previous Inspection: 30/03/2019 Previous Inspection Done By: ADMIRAL SAFETY CONSULTANTS

Date Of Inspection & Test: 19/03/2020 Next Inspection & Test Due On: ------------------*

INSPECTED BY: APPROVED BY:

JAYAKRISHNAN
After The Inspection and Testing of the equipment described in this report, the equipment found to contain defects likely to affect safety. Due to the highlighted items in the

subsequent pages (Remarks/Recommendation Section), The Equipment is not satisfactory for intended use, Re-inspection will be required along with hydro test..

This Report is granted subject to the condition that is understood and agreed that nothing herein contained shall be deemed to relieve any designer, manufacturer, seller, supplier,
Repairer or operator of any warranty, express or implied, and admiral safety consultants liability shall be limited to the acts or omissions of its employees, agents and Subcontractors.
under no circumstances whatsoever shall Admiral safety Consultants nor their Engineer be liable for any injury or damage to any person or occurring by reason of negligent operation
or any defect in material, machinery, equipment or other items other than such defects ascertainable by normally accepted standards and only those items actually inspected by
Admiral Safety Consultant and which are covered only by this Report. Any person not a party to the contract pursuant to which this document is delivered may not assert claim
against Admiral Safety Consultants for any liability arising out of errors or omissions which may be contained in said document and in connection with any activities for which it may
provide. This Report shall not be reproduced except in full without the approval of Admiral Safety Consultants and the receiving client.

Office No.M06 Sara Building – Algarhoud – Deira – Dubai - UAE, Tel: +971 4 2899389, Fax: +971 4 2840557, P.O.Box:125218
admin@admiralsafetyconsultants.com , www.admiralsafetyconsultants.com

1|Page Doc.No.ASC-ACR-C-52E (Rev.01) (1/06/2019)


REPORT NO: AR/R1 JOB NO: ASC-20-2888

DOCUMENTATION A B C REMARKS
EQUIPMENT MANUFACTURER’S INSTRUCTION &
OPERATIONAL MANUAL & LAST TEST REPORT/ 
CERTIFICATE/ MANUFACTURING DETAILS AVAILABLE.3
VISUAL &FUNCTIONAL TEST
PRESSURE GAUGES 
CORROSION 
LUBRICATION 
SUPPORT 
PAINT/ STRUCTURE & SURFACE 
PIPE CONNECTIONS (SUPPORTS) 
WORKING ENVIRONMENT 
FOUNDATION /FOOTING & ANCHORAGE 
SAFETY VALVE SET PRESSURE 
VALVES 
AIR FILTER /AIR DRYER 
CASING / WELDING 
ATTACHMENT 
FITTINGS 
OIL LEVEL 
AREA HOUSE KEEPING 
EARTH GROUNDING CONTINUITY 
POWER CABLE & WIRING CONDITION 
GENERAL CONDITION  Air leakage observed at inspection hole.
PRESSURE/ HYDRO STATIC TEST
 Pressure Test shall be conducted up on
PRESSURE TEST
rectification
AUTOMATIC PRESSURE LOAD SWITCH ON/ OFF 

A-SATISFACTORY B-NOT SATISFACTORY C-NOT APPLICABLE

RECOMMENDATION/ REMARKS

 NOT SATISFACTORY AT THE TIME OF INSPECTION

1) Air leakage observed at inspection hole, it shall be rectified and re-inspected.

Office No.M06 Sara Building – Algarhoud – Deira – Dubai - UAE, Tel: +971 4 2899389, Fax: +971 4 2840557, P.O.Box:125218
admin@admiralsafetyconsultants.com , www.admiralsafetyconsultants.com

2|Page Doc.No.ASC-ACR-C-52E (Rev.01) (1/06/2019)