Professional Documents
Culture Documents
Issued By:
Jun 2003
CONTENTS Page
1 INTRODUCTION 2
3 TECHNICAL REQUIREMENTS 3
8 CONCLUSION 12
1 Jun 2003
1 INTRODUCTION
This Guidelines serves as a reference to the QPs who are responsible for the
planning, design, construction and commissioning of household or storey
shelters.
The Qualified Persons (QPs) are advised to follow the guidelines described
herein so as to obtain necessary acceptance of shelter plans from the Civil
Defence Shelter Engineering Department (CDSD) of Special Functions
Division (SF) in Building and Construction Authority (BCA). During the
design phase of household or storey shelters, Notice of Acceptance (NOA) is
issued separately for compliance of shelter architectural and structural
requirements in accordance with the Household Shelter or Storey Shelter
Technical Requirements. At the final stage of household or storey shelters
construction, Notice of Acceptance (NOA) is issued when household or
storey shelter meets the commissioning requirements in accordance with
the Household Shelter or Storey Shelter Technical Requirements. Refer to
Flowchart at Annex A-1 for details.
2 Jun 2003
design requirements. Hence, design architect shall be the overall co-
ordinator to co-ordinate closely with the professional engineer in all stages
of household or storey shelter design. This is to avoid abortive structural
design works by PE if shelter architectural requirements are not compiled
with.
3 TECHNICAL REQUIREMENTS
3 Jun 2003
For effective consultation, QPs are requested to bring along their
preliminary design plans showing the following:
CDSD of BCA will issue Notice of Acceptance (NOA) for shelter structural
plans after shelter architectural plans have been accepted.
This is to avoid amendments to shelter structural plans should there be any
changes made to the shelter architectural plans in order to comply with the
written directions issued by CDSD. QPs are to take note that construction
works pertaining to household or storey shelter can only commenced after
Notice of Acceptance (NOA) for shelter structural plans has been obtained.
4 Jun 2003
should indicate the same project reference number issued by the architect
on their plans. The following abbreviation should be used for the respective
plan type: CD for shelter architectural plans and CS for shelter structural
Plans. For example: A1234-001-2001-CD01 & A1234-001-2001-CS01.
For response to written direction within the time frame stipulated in the
written direction, QP shall indicate the respective same plan type number
for re-submission in the application form SF_HS/PF4 or e-Form BCA-CDAS-
REAHSSS. To enable QP to take early follow-up action, BCA will fax copy of
WDs to QPs before sending out hard copy
Site layout plan, key plan and location plan of household shelter or storey
shelter shall be submitted. All types of shelter plans must bear the
following standard acceptance stamp on the right-hand column on every
plan (refer to below specimen).
5 Jun 2003
____ Sheet of____
......................................................……
…...
for Commissioner of Building Control Date
6 Jun 2003
5.5 Types of Shelter Plan Submission
QP shall submit the application form together with shelter structural plans
also to BCA Service Centre on 2nd Storey, Tower Block, MND Complex,
Maxwell Road. Upon acceptance of shelter structural plans by CDSD of
BCA, a Notice of Acceptance (NOA) of shelter structural plans will be issued
to the QP.
8 Jun 2003
5.5.3 If there are non-compliant items found in the shelter architectural or shelter
structural plans, a written direction will be issued to the QP. The original
set of shelter architectural or structural plans will be returned to the QP to
comply with the written direction within the time frame stipulated in the
written direction. Failing which, a Notice of Non-Acceptance (NONA) would
be issued to QP who are then required to make a new application
accompanied by Application Form SF_HS/PF2 or SF_HS/PF3 (e-form BCA-
CDAS-ACHSSS1 or e-form BCA-CDAS-ACHSSS2 respectively).
Where a formal application for acceptance of the shelter plans has already
been made to CDSD, the application shall be treated by CDSD as
“Withdrawn” as the outcome or the decision by SCDF is still pending.
9 Jun 2003
CDAS-ACHSSS1 or e-form BCA-CDAS-ACHSSS2 respectively) for our
processing and acceptance.
After QPs have obtained all the necessary acceptance of the shelter plans
(including shelter structural plans), they may proceed with the shelter
construction works. QP shall take note that permit to commence building
works has to be obtained from BE Division of BCA. To facilitate CDSD staff
in conducting shelter regulatory inspection during its construction, QP is
advised to submit shelter works schedule and the site location plan to
CDSD. QP shall ensure that household or storey shelters are constructed in
accordance with the accepted shelter plans.
10 Jun 2003
been fully complied with. CDSD would then witness the commissioning
inspection with the QP and the builder. 3 different types of test, i.e. chalk
mark, light penetration and air-tightness test, are to be carried out.
When all the commissioning requirements for the first household or storey
shelter are met, CDSD will issue a Notice of Acceptance (NOA) of
commissioning of the first household or storey shelter. It should be noted
that it is the responsibility of the QP to ensure that the rest of the
household or storey shelters in the same project development are
constructed in accordance with the same standards as laid out in the first
household or storey shelter.
11 Jun 2003
requirements, CDSD will issue a Notice of Acceptance (NOA) of
commissioning of project household or storey shelters. This notice of
acceptance for project household or storey shelters has to be submitted
when QP applies for TOP.
In both 7.1 and 7.2, QP would be issued with a written direction if there
were non-compliant items discovered during commissioning inspection. QP
shall re-apply for the commissioning test of the first or project household or
storey shelters by submitting either Application Form SF_HS/CFP (or e-Form
BCA-CDAS-ACHSSS with plan type suffix “CN” and unique number, to CDSD
upon rectification of the shelter defects. Depending on the circumstances,
commissioning re-inspection may be required before Notice of Acceptance is
issued. To enable QPs to take early follow-up action, BCA will fax copy of
WDs to QPs before sending out hard copies. Please refer to “Guidelines for
Selection of Household Shelter (HS) Sample for Project Commissioning
Inspection” in Annex A-4.
8 CONCLUSION
12 Jun 2003
Annex A-1
13 Jun 2003
Annex A-2
QP amends and
re-submit plans
CDSD Vets submission
WD to QP
Yes
Any non-
conformances?
No
END
14 Jun 2003
Annex A-3
End
15 Jun 2003
GUIDELINES FOR SELECTION OF HOUSEHOLD SHELTER (HS) SAMPLES
FOR PROJECT COMMISSIONING INSPECTION
Table 1 enumerates required sample size of HS to be selected in each project or each block-
basis request for commissioning inspection and over-pressure air-tightness tests.
Table 1
21-100 5
It is deemed that HS in the entire project or in each block-basis have failed the
commissioning inspection and 2nd commissioning inspection is required after
completion of remedial works. At the 2nd commissioning inspection, number of
shelters to be selected shall be in accordance with Table 1. Once all the shelter
samples have passed the commissioning inspection, Notice of Acceptance for
Commissioning of Project Household Shelter would be issued.
It is deemed that shelters in the entire project or in each block-basis have partially
passed the commissioning inspection. Hence, 2nd commissioning inspection is also
required. At the 2nd commissioning inspection, only those shelters which failed the
commissioning inspection during the 1st inspection plus an additional same number of
shelters which failed the 1st inspection would be selected from outside the original
sample group are to be commissioned.
16 Jun 2003
(ii) 2nd Commissioning Inspection:
All the selected shelters should pass the commissioning inspection before Notice of
Acceptance for Commissioning of Project Household Shelter is issued for the project or block-
basis request. Otherwise, a 3rd commissioning inspection is still required. The criteria for
selection of shelter samples shall follow item (i) (b) above. This will continue until all selected
shelter samples have passed the commissioning inspection.
Legend:
Legend:
i) “Retest 5%” means five percent of the project shelters to be re-commissioned and
those originally tested on previous inspections can be included.
ii) “Retest 2% + 2%” means to re-commission the original 2% shelters that failed plus
another 2% shelters from outside the original group tested on the previous inspection.
17 Jun 2003
Annex B
18 Jun 2003