IZMX Series Air Circuit Breakers

Small, flexible, efficient

Catalogue 2016
Air Circuit Breaker - IZMX series
IZMX16/IZMX40
Powering electrical systems
worldwide
Buildings Information Technology
• Residential • Data centers
• Healthcare • Telecommunication
• Education • Networks
• Commercial offices • Computer rooms
• Retail
• Public sector • World’s most efficient line of UPSs
to reduce footprint and save energy
• Airports
• Reliable power systems with inherent
redundancy to improve availability

• Power metering and monitoring


• Electrical distribution solutions for to diagnose problems and lower costs
safe and efficient power delivery
• Local service and support for quick
• Power quality systems for uptime response
and reliability

• Power metering and monitoring


to add intelligence and save costs

• Industrial control products


for HVAC applications
Public and private sectors
Buildings, Information Technology, Industrial & Machinery, Energy & Utilities
We provide reliable, efficient and safe power management.

Industrial & Machinery Energy & Utilities


• Machine building: • Renewable energy:
• Food and • Solar
packaging machines • Wind
• Woodworking and processing • Hydropower
machines
• Traditional energy:
• Agriculture
• Oil
• Construction
• Gas
• Mining and metals
• Smart grid
• Paper industry
• Water and waste water
• Chemical and pharmaceutical industry
• Automotive industry
• Electrical balance of system and
• Logistics centers turnkey services for residential, utility
and commercial solar installations
• Electrical distribution equipment to deliver power throughout • Power distribution equipment,
the enterprise control components and system
• Control & automation and power quality equipment for installations services
process control • Network power grid technology for
• Power metering and monitoring to manage energy costs and intelligent data, lower costs and
uptime crew / public safety

• Power and motion control products to optimize productivity,


reliability, safety and operator comfort
Versatile circuit breakers
up to 4000 A – for cost-effective,
optimized solutions.

The IZMX16 of the NRX series The IZMX40 of the NRX series
is the smallest air circuit-break- is a circuit breaker for up to
er (ACB) worldwide: 4000 A with depth less than
With a volume of only 0.024 m³ 400mm for the drawout
and a front surface of only version, without the need to
0.092 m², it is just slightly install any additional “copper
bigger than the size of a A4 mines” in the connection area.
sheet of paper! And all this
without any loss in terms of Tests to integrate it into Eaton
performance. switchgear systems, such as
Modan, xEnergy, Power Xpert
The innovative concept allows and Capitol 40 confirm its Horizontal Terminal
the user to install two circuit outstanding technical data and
breakers side by side in optimal compatibility thanks to
withdrawable design, in a the flexible connection system.
600 mm wide section. This
fact provides for a more The modular structure,
cost-effective setup of the integrated solutions as well as a
section and, in addition, it helps complete range of accessories
to save operating space. And and additional functions make it
where remote switching is easy to adapt the circuit breaker
required, this volume can even to any of the required applica-
accommodate a motor for tions. Optionally it can be Vertical Terminal
charging the stored-energy configured right at the factory – (Available on B, N
spring mechanism and releases without any extra cost for and H type.
for electrical operation. additional installation work at E type can be
High performance combined the circuit breaker. configured as
with reduced space is excep- horizontal terminal
tional value to customer. only)
IZMX Circuit Breakers, INX Switch-disconnectors
Contents

IZMX Circuit Breakers, Technical Overview


INX Switch-disconnectors Breaker Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Trip Unit Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
PXR Software, Arcflash Reduction Maintenance System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Zone Selective Interlocking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
System Overview
IZMX16 Circuit-breakers and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
IZMX40 Circuit-breakers and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Description
System Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Ordering
IZMX Series Air Circuit Breakers Catalog Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Withdrawable Units
Cassette . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Shutter, Cell Switch and Terminal Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Electronic Releases - Trip Unit
Type V Trip Unit with Current Metering (PXR20) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Type U Trip Unit with Power Metering (PXR25) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Communication Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Current Sensor For Neutral Conductor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Electrical Accessories
Motor Operator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Shunt Releases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Closing Releases, Latch Check Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Undervoltage Releases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Time Delay Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Auxiliary Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Overcurrent Trip Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Trip Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Mechanical Accessories
Operation Counters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Locking ON/OFF Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Key Locking In Safe Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Mechanical Interlock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Mechanical Interlock Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Collapsible Hand Lever . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Door Gasket IP41, Door Cover IP55 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Terminals
Main Terminal Sets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Terminal Assignment of Control Circuit Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Tripping Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Accessories Electrical Data
Switches, ST, SR and UVR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Motor Operators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Communication Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Temperature and Altitude Derating Factors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Dimensions
X16 Drawout Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
X16 Fixed Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
X40 Drawout Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Minimum Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99

1
IZMX Series Air Circuit Breakers

Technical Data

IZMX16 IZMX40
General
Standards IEC/EN 60947 IEC/EN 60947
Ambient temperature Storage °C -25 - 85 -25 - 85
Operating (open) °C -25 - 85 -25 - 85
Mounting position 30˚ 30˚ 30˚ 30˚

Utilization category B B
Protection type IP20, IP55 device with protective cover, IP41 with door sealing frame
Direction of incoming supply as required as required
Switching capacity
Rated Current (In) 630A, 800A, 1000A, 1250A, 1600A 800A, 1000A, 1250A, 1600A, 2000A, 2500A,
3200A, 4000A
Type of circuit breaker B N H B N H
Rated impulse withstand voltage (Uimp , VAC) 12000 12000 12000 12000 12000 12000
Rated insulation voltage (Ui , VAC) 1000 1000 1000 1000 1000 1000
Rated operational voltage (Ue , VAC) 690 690 690 690 690 690
Ultimate breaking capacity (Icu , kA) 240V 50/60Hz 42 85 85 66 85 105
440/480V 50/60Hz 42 50 66 66 85 105
690V 50/60Hz 42 42 42 66 75 75
Rated service breaking capacity (Ics , kA) 240V 50/60Hz 42 50 65 66 85 105
440/480V 50/60Hz 42 50 50 66 85 105
690V 50/60Hz 42 42 42 66 75 75
Rated short-time withstand current (Icw , kA) 1s/3s 42/- 42/- 42/- 66/53 85 1)/66 85 1)/66
Rated short-circuit making capacity (Icm , kA) 440/480V 50/60Hz 88 105 145 145 187 231
690V 50/60Hz 88 88 88 145 165 165
Operating delays (ms) Closing delay 25 30
Closing delay electrical (via SR) 30 35
Opening delay electrical (via ST) 25 22
Opening delay electrical (via UVR) 50 37
Maximum operating frequency (Operations/h) 60 60
Durability and installation characteristics
Lifespan 630A-1600A 800A-1600A 2000A 2500A-4000A
Mechanical, w/o 12500 12500 10000 10000
maintenance
Mechanical, w/ 25000 25000 20000 20000
maintenance
Electrical, w/o 10000 10000 8000 2) 6000 3)
maintenance
Dimensions (H × W × D, mm) Fixed 3P 338 × 210 × 184 398 × 376 × 298
Fixed 4P 338 × 279 × 184 398 × 492 × 298
Withdrawable 3P 360 × 254 × 289 456 × 426 × 393
Withdrawable 4P 360 × 324 × 289 456 × 541 × 393
Weight (kg) Fixed 3P/4P 15/20 45/56
Withdrawable 3P/4P 39/47 98/121
1)
75kA at 690VAC
2)
6000 operations for B,N and H type at 690VAC, E type at 480VAC
3)
2500 operations at 690VAC

2
IZMX Series Air Circuit Breakers

Technical Data

V Type (PXR20) U Type (PXR25)


IZMX-PXRV IZMX-PXRU
IZMX16/40…V… IZMX16/40…U…
Protective options LSI; LSIG/LSIA (Optional) LSI; LSIG/LSIA (Optional)
Overload protection (L)
Overload trip (Ir), × In 0.4, 0.5, 0.6, 0.7, 0.75, 0.8, 0.9, 0.95, 0.98, 1.0 0.4, 0.5, 0.6, 0.7, 0.75, 0.8, 0.9, 0.95, 0.98, 1.0
Long delay time tr (6 × Ir) 0.5, 1 , 2, 4, 7, 10, 12, 15, 20, 24 s 0.5, 1 , 2, 4, 7, 10, 12, 15, 20, 24 s
Short-time delayed short-circuit protection (S)
Short delayed pickup (Isd), × Ir 1.5, 2, 2.5, 3, 4, 5, 6, 7, 8, 10 1.5, 2, 2.5, 3, 4, 5, 6, 7, 8, 10
Short delay time, flat characteristic curve (tsd) 0.0, 0.1, 0.2, 0.3, 0.4, 0.5 s 1) 0.0, 0.1, 0.2, 0.3, 0.4, 0.5 s 1)
Short delay time at 8 × Ir, I²t curve (tsd) 0.1, 0.3, 0.4, 0.5 s 0.1, 0.3, 0.4, 0.5 s
Non-delayed short-circuit protection (I)
Non-delayed pickup (Ii), × In OFF, 2, 4, 5, 6, 7, 8, 10, 12, 15 OFF, 2, 4, 5, 6, 7, 8, 10, 12, 15
Optional ground fault protection (G)
Ground/Earth fault alarm (A), × In 0.2, 0.4, 0.6, 1.0 0.2, 0.4, 0.6, 1.0
Ground/Earth pickup (Ig), × In OFF, 0.2, 0.4, 0.6, 0.8, 1.0 OFF, 0.2, 0.4, 0.6, 0.8, 1.0
Short delay time, flat characteristic curve (tg) 0.1, 0.2, 0.3, 0.4, 0.5 s 0.1, 0.2, 0.3, 0.4, 0.5 s
Short delay time at 0.625 x In, I²t curve (tg) 0.1, 0.2, 0.3, 0.4, 0.5 s 0.1, 0.2, 0.3, 0.4, 0.5 s
Over-temperature trip  
Thermal memeory  
Zone selectivity ZSI  
Making current release (MCR)  
Protective functions
System diagnostic
Status/Overload LED  
Cause of trip LEDs  
Current at trip point (display indication)  
High load or ground fault alarm contact  
System monitor
LCD display 2) 2)
Current metering accuracy ±1% of Reading ±1% of Reading
Voltage (%) L to L – ±1% of Reading 3)
Power and energy (%) – ±2% of Reading 3)
Apparent power kVA and demand – 3)
Reactive power kVAR – 3)
Power factor – 3)
Communications
Onboard (ModBus)  
External (CAM Module)  
Power supply requirement +24 V DC, optional +24 V DC, optional
Additional funtions
Test Capability Integral Integral
Maintenance Mode ARMS  
(Arc Flash Reduction Maintenance SystemTM)
Trip log  
Electronic operations counter  
Waveform capture  
Breaker health monitor  
1)
Notes 0.1s: trip time is 0.06s to 0.1s; 0s: nominal clear time is 60ms with auxiliary power and 120ms without.
2)
Requires external 24VDC control voltage supply when continuous current below 20% of In
3)
Requires external PT module(IZMX-PXR-PTM-2) for voltage sensing input to trip unit
 Standard  Optional – not available

3
IZMX Series Air Circuit Breakers

The next generation trip unit platform:


Power Xpert Release (PXR)
• LCD display with multilingual • MicroUSB for computer
capability connection
• Current metering on PXR20 • PXR Configuration and Test
and power metering on Tool to remotely configure
PXR25 and test the trip unit
• Extended range for pickup • Trip test
value and delay timing • Waveform capture
setting
• Diagnostics
• "OFF" setting available for
ground fault(G) and non-de- • Long trip curve setting
layed instantaneous trip(I) • ZSI/Thermal Memory
• Onboard Modbus on/off
communication(standard on
PXR25 and optional on
PXR20)

PXR Trip Unit

Arcflash Reduction Maintenance System™


Eaton’s patented Arcflash The Arcflash Reduction
Reduction Maintenance System Maintenance System function
technology provides mainte- is activated either directly on
nance staff improved safety of the circuit breaker through a
downstream maintenance local switch or remotely
locations using a simple and through communications or a
reliable method to reduce fault contact input.
clearing times and energy in an
arc flash event (radiation, sound, Arcflash Reduction Mainte-
pressure, temperature). nance System is optional on
both PXR20 and PXR25 trip
Arcflash Reduction Maintenance units.
System uses a separate analog
trip circuit providing faster signal
processing and interruption
times than the standard (digital)
“instantaneous” protection.

4
IZMX Series Air Circuit Breakers

CB 1
ZSI
tsd = 300 ms

Zone 1

CB 2 CB 3
tsd = 200 ms ZSI tsd = 200 ms ZSI

Zone 2 2
M
CB 4 CB 5
tsd = 100 ms ZSI tsd = 100 ms ZSI

Zone 3
3

CB = Circuit Breaker
ZSI = Zone Selective Interlocking

Zone Selective Interlocking Zone Selective Interlocking Example


• Zone Selective Interlocking (ZSI) is Example A – Short-circuit at position 3 Example B – Short-circuit at position 2 Example C – Short-circuit at position 1
described in the soon to be pub-lished • Circuit-breakers CB1, CB3, CB4 all see • Circuit-breakers CB1, CB3, see the • Only Circuit breaker CB1sees the short
standard IEC 61912-2 Low voltage the short circuit current and register a short circuit current and register a circuit current and registers a short
switchgear and controlgear. short delay pick-up. short delay pick-up. CB4 and CB5 do delay pick-up. CB2, CB3, CB4 and CB5
• The term zone selective interlocking is • Circuit breaker CB4 sends a ZSI not see the fault current and do not do not see the fault current and do not
used to describe a method of out-put blocking signal to CB3 ZSI send a ZSI output. send ZSI outputs.
con-trolling circuit breakers to provide input. CB3 sends a ZSI output blocking • Circuit breaker CB3 sends a ZSI • CB1 sends a ZSI output signal. In this
selectivity with very short interrup-tion sig-nal to CB1 ZSI input. CB1 sends a out-put blocking signal to CB1 ZSI example that signal is not wired.
times for the breaker closest to the ZSI output signal that is not wired. input. CB1 sends a ZSI output signal. • CB1 gets no input from any lower zone
fault. This signal could be wired to a MV In this example that signal is not circuit breaker. This breaker will then
• There are different levels (zones) of relay on the other side of the wired. trip immediately without any time
protection that isolate the fault in the trans-former with a compatible ZSI • CB1 registers the ZSI input signal and delay. CB1 interrupts the fault and the
distribution system. cir-cuitry. starts a timer for 300ms. CB3 gets no clearance time is re-duced by
• ZSI may be applied for faults • CB1 registers the ZSI input signal and input from any lower zone circuit approximately 250ms.
be-tween phases or earth-faults or starts its timer for 300ms. CB3 breaker. This breaker will then trip
both. registers the ZSI input signal and immediately without any time delay.
• ZSI is applied to the short time faults starts its timer for 200ms. CB4 gets no CB3 interrupts the fault and CB1 stops
where time selectivity can be input from any lower zone circuit short delay timing be-cause the fault
achieved with the breakers be-tween breaker. This breaker will then trip current is gone. The clearance time is
the zones. immediately without any time delay. reduced by ap-proximately 150ms.
• Because ZSI does not require CB4 interrupts the fault and CB1 and
auxil-iary power or additional modules CB3 stop short delay timing because
to operate set up time is minimal and the fault current is gone.
application is easy. • If for some reason CB4 does not open
and interrupt the fault then at the end
of the its short delay time CB3 will
open and interrupt the fault.

5
IZMX Series Air Circuit Breakers

IZMX system overview

IZMX16
8
24
5

2
14 12

13

20 21

11 15
1

18

17

3
16

19

6
7

9 10
22
23

Interchangeable accessories between


Unique parts and accessories for -IZMX16
IZMX16 and IZMX40

1 IZMX Circuit-breaker P10 3 Safety Shutter P12 5 Control circuit terminal units P12
IZMX16: 630 - 1600A +IZMX-SH163 X16, 3P Modular design
IZMX40: 800 - 4000A +IZMX-SH164 X16, 4P
+IZMX-SH403 X40, 3P 6 Trip unit P13
2 Cassette P11 +IZMX-SH404 X40, 4P PXR20, V-type, current metering
+IZMX-CAS163-1600 X16, 1600A, 3P C - Onboard Modbus
+IZMX-CAS164-1600 X16, 1600A, 4P 4 Position cell switches P12 G - Ground fault protection
+IZMX-CAS403-2000 X40, 2000A, 3P Cell switch signals the position of the M - Arcflash Reduction Maintenance
+IZMX-CAS404-2000 X40, 2000A, 4P breaker inside of the cassette. System™
+IZMX-CAS403-2500 X40, 2500A, 3P Connect, Test and Disconnect Position. +IZMX-PXRV-C
+IZMX-CAS404-2500 X40, 2500A, 4P IZMX-CS16-1-2 X16 +IZMX-PXRV-G
+IZMX-CAS403-3200 X40, 3200A, 3P IZMX-CS40-L-2 X40, left +IZMX-PXRV-GC
+IZMX-CAS404-3200 X40, 3200A, 4P IZMX-CS40-R-2 X40, right +IZMX-PXRV-GM
+IZMX-CAS403-4000 X40, 4000A, 3P +IZMX-PXRV-GMC
+IZMX-CAS404-4000 X40, 4000A, 4P

6
IZMX Series Air Circuit Breakers

13 Latch check switch P17


For external application
IZMX40 Usage
24 +IZMX-LCS
14 Latch check switch P17
For use with closing release.
+IZMX-LCS-SR
24
24
15 Undervoltage releases P18
2 Opens the breaker by a voltage-drop
in the control circuit.
+IZMX-UVR24DC 24VDC
20 +IZMX-UVR110AD 110VAC/DC
+IZMX-UVR220AD 220VAC/DC
+IZMX-UVR400AC 380VAC
16 Auxiliary contacts P18
Signaling switch ON-OFF.
2a2b standard. 4a4b maximum for
IZMX16 and 12a12b for IZMX40
4 +IZMX-AS22 X16/X40, add 2a2b
+IZMX-AS44 X40, add 4a4b
+IZMX-AS66 X40, add 6a6b
+IZMX-AS88 X40, add 8a8b
1 +IZMX-AS1010 X40, add 10a10b

17 Trip indicator switches P19


Overcurrent trip switch (OTS) signals
a trip by the trip unit.
+IZMX-OTS
18 Red-pop trip indicator P19
Red-pop trip indicator signals a trip
by the trip unit
Included in breaker with trip unit

19 Switching operations counters P20


Counts the number of operations.
+IZMX-OC

20 Locking facilities P20


3
Plastic or metal
IZMX-PLPC16-P-2 X16, plastic
IZMX-PLPC16-M-2 X16, metal
IZMX-PLPC40-P-2 X40, plastic
IZMX-PLPC40-M-2 X40, metal
21 Key locking P20
Locking of the breaker by a keylock.
IZMX-KLP-SO-CES-2
19 IZMX-KLP-SO-KIRK-2
23 IZMX-KLP-SO-RONIS-2
IZMX-KLP-SO-CASTELL-2

22 Levering tool P23


Lev-in tool to move the breaker in and
9 out of the cassette. Standard Omega
22 shaped handle is included in D/O
breaker. Optional collapsible handle
can be ordered separately
10
23 Door escutcheon P23
Closes the gap between Breaker and
Switchgear-door.
IP41 included in breaker
For IP55:
Unique parts and accessories for IZMX40 IZMX-DC16-W-2 X16
IZMX-DC40-W-2 X40
24 Main terminal kits P24
7 Trip unit P13 9 Current sensor for neutral P14 11 Shunt releases P16
Universal terminals, 3- and 4-pole
PXR25, U-type, power metering conductor Opens the breaker by an electrical
horizontal/vertical
+IZMX-PXRU-G Current sensor for sensing the signal.
IZMX-THV163-2 X16, 3P
+IZMX-PXRU-M neutral-conductor current. +IZMX-ST24DC 24VDC
IZMX-THV164-2 X16, 4P
+IZMX-PXRU-GM IZMX-CT16-N-2 X16 +IZMX-ST110AD 110VAC/DC
IZMX-THV403-3200-2 X40, 3P, 3200A
IZMX-CT40-N-2 X40 +IZMX-ST230AD 220VAC/DC
8 Communication modules P14 IZMX-THV404-3200-2 X40, 4P, 3200A
External modules 10 Motor operator P15 12 Closing releases P17 IZMX-TH403-2 X40, 3P, 4000A, horizontal
IZMX-MCAM-2 Modbus Automatic charging of the spring force Closes the breaker by an electrical IZMX-TV403-2 X40, 3P, 4000A, vertical
IZMX-ECAM-2 Ethernet storage for remote or local operations signal. IZMX-TH404-2 X40, 4P, 4000A, horizontal
IZMX-PCAM-2 Profibus DP +IZMX-M16-24DC X16, 24VDC +IZMX-SR24DC 24VDC IZMX-TV404-2 X40, 4P, 4000A, vertical
+IZMX-M16-110AD X16, 110VAC/DC +IZMX-SR110AD 110AC/DC
+IZMX-M16-230AD X16, 220VAC/DC +IZMX-SR230AD 220AC/DC
+IZMX-M40-24DC X40, 24VDC
+IZMX-M40-110AD X40, 110VAC/DC
+IZMX-M40-230AD X40, 110VAC/DC
7
IZMX Series Air Circuit Breakers

Breaker rear side (withdrawable breaker)

Space-saving circuit-breakers with useful accessories


Eaton Introduces IZMX Series Modular Design, Common Accessories • The number of secondary control cable Additional benefits IZMX Series
The new IZMX Series from Eaton is a The retrofitting of accessories is made terminals depends on the accessories • The “universal” design of the main
new series of air circuit-breakers with an considerably easy thanks to the efficient fitted. terminal offers maximum flexibility.
extensive range of accessories. The new “plug & work” technology. Accessory • If a cassette is ordered without the The horizontal terminal can be
range provides users with two compact drawers and snap-fit mechanisms make it basic device, this can be already fitted rotat-ed simply at the installation so
frame sizes up to 4000A, modular design, possible to fit the latest accessories with with the maximum number of control that it can also be used as a vertical
common accessories, easy to integrate virtually no tools. This flexibility allows cable terminals. For greater economy connection. With withdrawable units,
communications and a full range of trip you to re-spond easily to changing in large plants, the cassette is also additional terminal pieces can even be
units including the new powerful Power requirements within your system. Most offered without control circuit dispensed with. Both the IZMX Series
Xpert Release(PXR) trip unit with a LCD accessories for IZMX Series are common terminals so that fitting can be carried breaker and the cassette offer an
display. The innovative concept of the to both the compact and standard frame out later at the installation or when integrated flange terminal to which
IZMX16 makes it possible to install two sizes. accessories are required at a later the system busbars can be connected
with-drawable circuitbreakers in a 600 time. directly.
mm wide section. This enables more • The withdrawable basic device • Thanks to the separate mounting
Standard scope of delivery includes the primary finger clusters
eco-nomical section design and also position, a switching operations
saves operating space. The compact • With the new IZMX Series range, you and levering-in mechanism. NOTE: counter can now be used also
modu-lar design of the IZMX40 offers select a basic device that is already Some manufacturers mount the inde-pendently of a motor operator.
customers a full range of high fitted with an electronic release. primary finger clusters inside the • Withdrawable unit operation: The unit
performance ratings in a single frame • The standard mounting for both cassette cell, which requiring is actuated with a hand crank supplied
size simplifying the integration process frames is on a horizontal mounting shutdown of the panel board for as a standard feature and has a
into panel boards and switch boards. plate or on horizontal traverses in the inspection and maintenance. secure position in the basic device.
IZMX Series, a new generation and new switching cabinet. The IZMX16 can • 2 changeover contacts are provided as
standard in circuit protection. also be fastened to vertical mounting standard for ON/OFF status indication.
plates. • A coding mechanism between the External 24 V supply
• With four-pole devices, the neutral basic device and the cassette prevents • The standard protection functions of
Applications conductor is arranged on the left (front impermissible combinations IZMX Series operate independently of
The circuit breakers can be used in four view). (“Rejection Interlock”). an external control voltage supply. The
main application areas depending on the • The neutral conductor can be loaded • The door escutcheon is always power supply of the electronics unit,
type of equipment to be protected: 100% like the phase conductors. included in the scope of delivery. With for example for overload and
• System protection • The circuit-breakers are provided with withdrawable designs this is supplied short-circuit protection, is implement-
• Motor protection a standard mechanical reclosing with the cassette (withrawable unit). ed via the current transformers
• Transformer protection lockout. After an overload trip, the • On withdrawable units the circuit integrated in the circuit-breaker.
• Generator protection fault is usually examined first. After breaker can be pulled out to inspect • The universal and power measure-
These key applications make different the fault is identified and rectified, the the arc chutes. With fixed units, it is ment release units with display can be
demands on the switches, which are met mechanical reclosing lock-out is reset recommended that sufficient space is fed with a 24 V DC supply so that the
with a range of control units. by pressing the red mechanical trip provided above the circuit breaker to display function can be used without a
indicator on the front of the enable inspection. An addi-tional load. An external 24 V DC power
Switches with closing release cover is not required.
circuit-breaker. supply is needed if communication
They are particularly suitable for • If a motor operator is ordered, the
• A “remote-reset” feature and an functions are required.
synchronization tasks. “Spring-operated stored energy
“automatic reset” are offered as
Coupler switches ad-ditional ordering options. The mechanism tensioned” indicator
In addition to the circuit-breakers, remote reset enables resetting the switch is automatically provided.
switch-disconnectors are also available. breaker after an over current trip via a
These are used, for example, as coupler control voltage. The automatic reset
switches between different power option enables the circuit breaker to
supplies. The switch-disconnectors are be restored to normal operation
used as coupler switches for different immediately after an over current trip
sections of a network in conjunction with (i.e. there is no mechanical reclosing
our automatic network switching device. lockout). In these applications
compulsory fault analysis is
intentionally avoided.

8
IZMX Series Air Circuit Breakers

Greater safety for maintenance Selection criteria for PROFIBUS-DP configuration Ethernet configuration
personnel with ARMS™ circuit-breakers Dommunications module IZMX-PCAM has standard RJ45 socket for connection
Personnel safety is of paramount Fundamental criteria for the selection of has a 9-pin D-Sub socket for connection to Ethernet. This module has a configured
im-portance in today’s work environment. circuit-breakers: to PROFIBUS. The module works as a web server on board and supports Simple
Of recent concern is the potential for • Max short-circuit current Ik max at slave on PROFIBUS-DP; the data is Network Mail Protocol (SNMP) for alarm
serious injury due to exposure to the circuit-breaker’ point of defined through a standardized device or event notifications.
electrical arcs. Eaton’s IZMX Series trip installation: this value determines the master data file, which permits smooth • IP address and related parameters are
units offer the patented ARMS system short-circuit breaking capacity or the integration of IZMX in a DP line. set through the trip unit’s display.
(Arcflash Reduction Maintenance short-circuit current carrying capacity • On the PROFIBUS-DP side the module • The data connection to the
System™), which offers a non-delayed of the circuit-breaker. It is compared supports automatic baud rate circuitbreaker is implemented
immediate disconnection in the event of with the Icu, Ics and Icw values of the detection; the PROFIBUS-DP bus internally through a serial high speed
an arc fault. This disconnection is even switch and essentially determines its address is set through the trip unit’s data connection.
faster than that of a non-delayed size (see technical data). display. The maximum cable length is • To operate the IZMX-ECAM, a supply
short-circuit release. This function can be • Rated operational current In which 2.4 km. voltage of 24 V DC is required.
activated directly on the circuit-breaker or should flow through the respective • To operate the IZMX-PCAM, a supply
Data access via Ethernet
via an external switch, such as when branch circuit: This value must not be voltage of 24 V DC is required.
The data is contained in different web
maintenance personnel enter a hazardous greater than the maximum switch • The data connection to the
pages structured according to the topics
area. rated operational current of the circuitbreaker is implemented
„Data View”, „Alarms”, „Logs” and
circuit-breaker. The rated operational internally through a serial highspeed
Major Benefits of ARMS: „Configuration”. This variance allows the
current can be adjusted down using data connection.
• Increased personnel safety – by integration of the IZMX to be adapted to
additional rated operational current
limiting the available arc flash energy Data access via PROFIBUS-DP all Ethernet networks supporting http
modules.
• Simple to operate The data on PROFIBUS-DP are offered protocol. An „around the world access”
• Ambient temperature of the circuit
• Enabled with circuit breaker door according to the profile for low-voltage to the breaker becomes reality and using
breaker: This is generally the internal
closed by a door mounted lockable switchgear (LVSG) of PROFIBUS the SNMP protocol alarm messages can
temperature in the control panel.
switch International (PROFIBUS and PROFINET be transported everywhere.
Observe the derating values with
• Enabled only for the time required to User Group). Five different data
in-creased ambient temperature (see
perform the desired maintenance work structures with varying numbers of
Technical data).
• Preserves overcurrent coordination parameters are available through the Profibus-DP
• Circuit-breaker type: fixed mounted or
under normal conditions device master data file. This allows a
withdrawable units, 3 or 4 pole. Modbus
• Reduction in incident energy levels data filter to be easily implemented,
• Minimum short-circuit current, which
may permit reduced levels of Personal which simplifies integration of the Series Ethernet
flows through the switching device:
Protective Equipment (PPE), therefore NRX data into the control system.
The release must recognize this value
improving worker comfort and mobility
as a short-circuit and may react with a
Other components of the ARCON arc fault
trip. Modbus configuration
protection system, in conjunction with
• Protection functions of the circuit Communications module IZMX-MCAM
Series NRX, enable an expansion of arc
breaker: This is determined by the has a plug-in screw terminal for
fault protection in stages. ARCON on the
selection of the respective overcurrent connection to Modbus. The module
Internet: www.moeller.net/arcon
release. operates as a Modbus slave.
For additional resources and tools for • Baud rate, data format and address
selecting Eaton Air Circuit Breakers (max. 247) for Modbus are set with Onboard Modbus
please visit us as the input keys of the trip unit. The
www.eaton.com/seriesnrx. maximum cable length is 1.2 km.
• The Modbus must be terminated with
Communication Options for a 120 Ω terminating resistor.
IZMX Series • To operate the IZMX-MCAM, a supply
voltage of 24 V DC is required.
With the respective communication
• The data connection to the
module - PCAM, MCAM or ECAM
circuitbreaker is implemented
(Profibus-DP / Modbus/ Ethernet
internally through a serial highspeed
Communications Adapter Module) - every
data connection.
circuit breaker of the NRX series is
equipped for modern communication and Data access via Modbus
is fit for the future. The databus not only The data is contained in comprehensive
allows to transmit information, but also data tables. Each data point is available
to receive commands/settings. as floating-point (IEEE) or fixed-point
Onboard Modbus communication is value. This variance allows the
standard on the PXR25 (U type) trip unit integration of the IZMX to be adapted to
and optional on the PXR20(V type) trip the Modbus architecture. This enables a
unit upon order. Additional PCAM, simple means of implementing a data
MCAM or ECAM module can be installed filter, which facilitates the integration of
externally for PXR25 to expand the IZMX data in the control system.
communication capability. (No more than
one external CAM module can be
installed)

9
IZMX Series Air Circuit Breakers

IZMX Series Air Circuit Breakers Catalog Number

IZMX 16 B 4 - V 16 W EO2

Product Type Configuration


IZMX = Air circuit breaker Blank = Basic breaker
INX = Switch disconnector MO = Manually operated
EO2 = 220VAC electrically operated
Frame Size
16 = 630A-1600A Mounting Form
40 = 800A-4000A W = Withdrawable
F = Fixed
Switching Capacity
E = Economy: (IZMX40E:66kA@440VAC)
Rated Current
B = Basic: (IZMX16B:42kA, IZMX40B:66kA)
N = Normal: (IZMX16N:50kA, IZMX40B:85kA) IZMX16
H = High: (IZMX16H:66kA, IZMX40H:105kA) 06 = 600A 08 = 800A 10 = 1000A
12 = 1250A 16 = 1600A
Trip Unit Type IZMX40
Poles 08 = 800A 10 = 1000A 12 = 1250A
V = Selective-current
3 = 3 pole 16 = 1600A 20 = 2000A 25 = 2500A
U = Universal-power
4 = 4 pole 32 = 3200A 40 = 4000A
P = Professional
E type: 800~2000A only

Recommended Selection Examples


IZMX40 fixed 220VAC electrically operated example (item 1~2 for manually operated MO):
a IZMX40B3-V16F Fixed parent breaker, including 2a2b Aux contact
b IZMX-THV403-3200-2 Main terminal adapter – horizontal (3200A and below)
c +IZMX-M40-230AD 208-250 VAC/DC Charging motor
d +IZMX-ST230AD 220-240 VAC/DC Shunt trip
e +IZMX-SR230AD 220-240 VAC/DC Closing spring release
f +IZMX-AS22 Additional 2a2b Aux contact (4a4b total)
g +IZMX-OTS Over current trip switch(OTS) 2CO
h EASY400-POW External power module to converter 220VAC to 24VDC to power trip unit

IZMX40 withdrawable 220VAC electrically operated EO2 example (item 1~4 for manually operated MO):
a IZMX40B3-U16W Withdrawable parent breaker, including 2a2b Aux contact
b +IZMX-CAS403-2000 Cassette(2000A and below)
c +IZMX-SH403 Safety shutters
d IZMX-THV403-3200-2 Main terminal adapter – horizontal (3200A and below)
e +IZMX-M40-230AD 208-250 VAC/DC Charging motor
f +IZMX-ST230AD 220-240 VAC/DC Shunt trip
g +IZMX-SR230AD 220-240 VAC/DC Closing spring release
h +IZMX-AS22 Additional 2a2b Aux contact (4a4b total)
i +IZMX-OTS Over current trip switch(OTS) 2CO
j EASY400-POW External power module to converter 220VAC to 24VDC to power trip unit

10
IZMX Series Air Circuit Breakers
Cassette

IZMX-CAS…
Pole- For use with Cat. No. Instructions
Part no.
Article no.
Cassettes
Equipment supplied: arcing chamber cover, Safety coding for basic device
3 IZMX16…3-…W +IZMX-CAS163-1600 With control circuit
INX16…3-…W 101536 terminals according
up to 1600 A to ordered options.
3 IZMX16…3-…W IZMX-CAS163-1600-SEC-2 With control
INX16…3-…W 180198 conductor terminals
up to 1600 A fully fitted.
4 IZMX16…4-…W +IZMX-CAS164-1600 With control circuit
INX16…4-…W 101538 terminals according
up to 1600 A to ordered options.
4 IZMX16…4-…W IZMX-CAS164-1600-SEC-2 With control
INX16…4-…W 180135 conductor terminals
up to 1600 A fully fitted.
3 IZMX40…3-…W +IZMX-CAS403-2000 With control circuit
INX40…3-…W 150067 terminals according
up to 2000 A to ordered options.
3 IZMX40…3-…W IZMX-CAS403-2000-SEC-2 With control
INX40…3-…W 180329 conductor terminals
800A-2000A, 65kA fully fitted.
4 IZMX40…4-…W +IZMX-CAS404-2000 With control circuit
INX40…4-…W 150086 terminals according
up to 2000 A to ordered options.
4 IZMX40…4-…W IZMX-CAS404-2000-SEC-2 With control
INX40…4-…W 180331 conductor terminals
800A-2000A, 65kA fully fitted.
3 IZMX40…3-…W +IZMX-CAS403-2500 With control circuit
INX40…3-…W 122787 terminals according
2500 A to ordered options.
3 IZMX40…3-…W IZMX-CAS403-2500-SEC-2 With control
INX40…3-…W 180158 conductor terminals
2500A, 65kA fully fitted.
4 IZMX40…4-…W +IZMX-CAS404-2500 With control circuit
INX40…4-…W 122890 terminals according
2500 A to ordered options.
4 IZMX40…4-…W IZMX-CAS404-2500-SEC-2 With control
INX40…4-…W 180166 conductor terminals
2500A, 65kA fully fitted.
3 IZMX40…3-…W +IZMX-CAS403-3200 With control circuit
INX40…3-…W 150061 terminals according
3200 A to ordered options.
3 IZMX40…3-…W IZMX-CAS403-3200-SEC-2 With control
INX40…3-…W 180325 conductor terminals
800A-3200A, 65kA/85kA/100kA fully fitted.
4 IZMX40…4-…W +IZMX-CAS404-3200 With control circuit
INX40…4-…W 150064 terminals according
3200 A to ordered options.
4 IZMX40…4-…W IZMX-CAS404-3200-SEC-2 With control
INX40…4-…W 180327 conductor terminals
800A-3200A, 65kA/85kA/100kA fully fitted.
3 IZMX40…3-…W +IZMX-CAS403-4000 With control circuit
INX40…3-…W 122886 terminals according
4000 A to ordered options.
3 IZMX40…3-…W IZMX-CAS403-4000-SEC-2 With control
INX40…3-…W 180160 conductor terminals
4000A, 65kA/85kA/100kA fully fitted.
4 IZMX40…4-…W +IZMX-CAS404-4000 With control circuit
INX40…4-…W 122900 terminals according
4000 A to ordered options.
4 IZMX40…4-…W IZMX-CAS404-4000-SEC-2 With control
INX40…4-…W 180168 conductor terminals
4000A, 65kA/85kA/100kA fully fitted.

11
IZMX Series Air Circuit Breakers
Shutter, Cell Switch and Terminal Block

IZMX-SH…, IZMX-CS…, IZMX-SEC-TB…


Pole- For use with Cat. No. Instructions
Part no.
Article no.
Cassette safety shutters
When the breaker is withdrawn from its con- 3 (+)IZMX-CAS163... IZMX-SH163-2 –
nected position, the shutters automatically 180151
cover the cassette’s live main terminals.
3 (+)IZMX-CAS163... +IZMX-SH163 –
101541

4 (+)IZMX-CAS164... IZMX-SH164-2 –
180152

4 (+)IZMX-CAS164... +IZMX-SH164 –
101543

3 (+)IZMX-CAS403... IZMX-SH403-2 –
180171

3 (+)IZMX-CAS403... +IZMX-SH403 –
122905

4 (+)IZMX-CAS404... IZMX-SH404-2 –
180174

4 (+)IZMX-CAS404... +IZMX-SH404 –
122908

Cell switches
One changeover contact for position Disconnected, Test, Connected.
Installation on left in the cassette (+)IZMX-CAS16… IZMX-CS16-1-2 –
180153

Installation on left in the cassette (+)IZMX-CAS40… IZMX-CS40-L-2 –


180143

Installation on right in the cassette (+)IZMX-CAS40… IZMX-CS40-R-2 –


180144

Control circuit terminal block for withdrawable mounting


IZMX16 has maximum 14 kits and IZMX40 has 24 maximum
Control circuit terminals, 8 units (+)IZMX-CAS… IZMX-SEC-TB8-W-2 –
180355

Control circuit terminals, 20 units (+)IZMX-CAS… IZMX-SEC-TB20-W-2 –


180356

Control circuit terminals, 30 units (+)IZMX-CAS… IZMX-SEC-TB30-W-2 –


180357

Control circuit terminal units for fixed mounting


IZMX16 has maximum 14 kits and IZMX40 has 24 maximum
Control circuit terminals, 8 units IZMX16…, INX16… IZMX-SEC-TB8-F-2 –
IZMX40…, INX40… 180358

Control circuit terminals, 20 units IZMX16…, INX16… IZMX-SEC-TB20-F-2 –


IZMX40…, INX40… 180359

Control circuit terminals, 30 units IZMX16…, INX16… IZMX-SEC-TB30-F-2 –


IZMX40…, INX40… 180360

12
IZMX Series Air Circuit Breakers
Electronic Releases

IZMX-PXRV..., IZMX-PXRU
For use with Ground ARMS Onboard Cat. No.
Earth-Fault ModBUS Part no.
Protection Communication Article no.
(G) (M) (C)
Type V trip unit with current metering (PXR20)
– – – – IZMX-PXRV

Add-on functions for current metering Type V (PXR20)


Add onboard Modbus IZMX...V... – –  +IZMX-PXRV-C
180394

Add ground fault protection IZMX...V...  – – +IZMX-PXRV-G


180386

Add ground fault protection and IZMX...V...  –  +IZMX-PXRV-GC


onboard Modbus 180396

Add ground fault protection and IZMX...V...   – +IZMX-PXRV-GM


ARMs 180398

Add ground fault protection, IZMX...V...    +IZMX-PXRV-GMC


onboard Modbus and ARMs 180400

Type U Trip Unit with Power Metering (PXR25)


Onboard ModBUS is standard on – – –  IZMX-PXRU
all PXR25 trip units

Add-on functions for power metering Type U (PXR25)


Add ground fault protection IZMX...U...  –  +IZMX-PXRU-G
180388

Add ARMs IZMX...U... –   +IZMX-PXRU-M


180390

Add ground fault protection and IZMX...U...    +IZMX-PXRU-GM


ARMs 180392

13
IZMX Series Air Circuit Breakers
Accessories for Electronic Releases, Current Sensors

Accessories for Electronic Releases


Description For use with Rated control Cat. No. Note
voltage Part no.
Article no.
Us
V
Power supply
External trip unit power adapter IZMX16… 115/230VAC input EASY400-POW DIN rail mount
IZMX40… 24VDC, 1.25A output 212319 Order seperately

Externally mounted voltage transformer to provide IZMX16… – IZMX-PXR-PTM-2 DIN rail mount
voltage sensing input to U type trip unit. IZMX40… 183125 Order separately,
One PT Module may connect up to 16 IZMX breakers, not included in U
to a maximum of 75 meters distance type trip unit

Communication modules
Communication module – – – IZMX-ECAM-2 DIN rail mount
ETHERNET IZMX40… 180133 Order seperately

Communication module – – – IZMX-MCAM-2 DIN rail mount


MODBus IZMX40… 180161 Order seperately

Communication module – – – IZMX-PCAM-2 DIN rail mount


PROFIBUS IZMX40… 180176 Order seperately

IZMX-CT…
Rated current For use with Cat. No.
Part no.
Article no.
In
A
Current sensor for neutral conductor on 3-pole circuit-breakers
for IZMX16 – IZMX16… IZMX-CT16-N-2
Externally mounted neutral sensor 180138
for residual ground.

for IZMX40 – IZMX40… IZMX-CT40-N-2


Externally mounted neutral sensor 180381
for residual ground.

14
IZMX Series Air Circuit Breakers
Motor Operator

IZMX-M…
Rated control For use with Cat. No. Instructions
voltage Part no.
Article no.
Us
V
Motor operator
The motor automatically tensions the spring force storage mechanism for remote or
local actuation.
A signaling switch for the „Spring force storage charged” message is included as standard
for IZMX16 24 V DC IZMX16… IZMX-M16-24DC-2 For retrofitting, two addi-
INX16… 180182 tional control circuit
terminal units are
24 V DC IZMX16… +IZMX-M16-24DC required. page 12
INX16… 123593

48 V DC IZMX16… IZMX-M16-48DC-2
INX16… 180183

48 V DC IZMX16… +IZMX-M16-48DC
INX16… 123595

110 - 127 V AC 50/60 Hz IZMX16… IZMX-M16-110AD-2


110 - 125 V DC INX16… 180141

110 - 127 V AC 50/60 Hz IZMX16… +IZMX-M16-110AD


110 - 125 V DC INX16… 124265

208 - 240 V AC 50/60 Hz IZMX16… IZMX-M16-230AD-2


220 - 250 V DC INX16… 180142

208 - 240 V AC 50/60 Hz IZMX16… +IZMX-M16-230AD


220 - 250 V DC INX16… 124267

for IZMX40 24 V DC IZMX40… IZMX-M40-24DC-2


INX40… 180091

24 V DC IZMX40… +IZMX-M40-24DC
INX40… 124290

48 V DC IZMX40… IZMX-M40-48DC-2
INX40… 180092

48 V DC IZMX40… +IZMX-M40-48DC
INX40… 124292

110 - 127 V AC 50/60 Hz IZMX40… IZMX-M40-110AD-2


110 - 125 V DC INX40… 180094

110 - 127 V AC 50/60 Hz IZMX40… +IZMX-M40-110AD


110 - 125 V DC INX40… 124296

208 - 240 V AC 50/60 Hz IZMX40… IZMX-M40-230AD-2


220 - 250 V DC INX40… 180378

208 - 240 V AC 50/60 Hz IZMX40… +IZMX-M40-230AD


220 - 250 V DC INX40… 156647

15
IZMX Series Air Circuit Breakers
Releases

IZMX-ST…, IZMX-STS…
Rated control- For use with Cat. No. Instructions
voltage Part no.
Article no.
Us
V
Shunt releases
Can be combined with an undervoltage
release or a second shunt release.
24 V DC IZMX16..., IZMX40... IZMX-ST24DC-2 An additional control
INX16..., INX40... 180185 circuit terminal block is
required for retrofitting.
24 V DC IZMX16..., IZMX40... +IZMX-ST24DC page 12
INX16..., INX40... 123607

48 V DC IZMX16..., IZMX40... IZMX-ST48DC-2


INX16..., INX40... 180186

48 V DC IZMX16..., IZMX40... +IZMX-ST48DC


INX16..., INX40... 123616

110 - 125 V AC/DC IZMX16..., IZMX40... IZMX-ST110AD-2


INX16..., INX40... 180187

110 - 125 V AC/DC IZMX16..., IZMX40... +IZMX-ST110AD


INX16..., INX40... 123696

220 - 240 V AC/DC IZMX16..., IZMX40... IZMX-ST230AD-2


INX16..., INX40... 180188

220 - 240 V AC/DC IZMX16..., IZMX40... +IZMX-ST230AD


INX16..., INX40... 123729

Second shunt release


Cannot be combined with an
undervoltage release..
24 V DC IZMX16..., IZMX40... +IZMX-STS24DC An additional control
INX16..., INX40... 123731 circuit terminal block is
required for retrofitting.
48 V DC IZMX16..., IZMX40... +IZMX-STS48DC page 12
INX16..., INX40... 123732

110 - 125 V AC/DC IZMX16..., IZMX40... +IZMX-STS110AD


INX16..., INX40... 123733

220 - 240 V AC/DC IZMX16..., IZMX40... +IZMX-STS230AD


INX16..., INX40... 123734

16
IZMX Series Air Circuit Breakers
Releases

IZMX-SR…, IZMX-LCS…
Rated control- For use with Cat. No. Instructions
voltage Part no.
Article no.
Us
V
Closing releases
Without latch check switch.
24 V DC IZMX16..., IZMX40... IZMX-SR24DC-2
INX16..., INX40... 180189

24 V DC IZMX16..., IZMX40... +IZMX-SR24DC


INX16..., INX40... 123735

48 V DC IZMX16..., IZMX40... IZMX-SR48DC-2


INX16..., INX40... 180190

48 V DC IZMX16..., IZMX40... +IZMX-SR48DC


INX16..., INX40... 123737

110 - 125 V AC/DC IZMX16..., IZMX40... IZMX-SR110AD-2


INX16..., INX40... 180191

110 - 125 V AC/DC IZMX16..., IZMX40... +IZMX-SR110AD


INX16..., INX40... 123739

220 - 240 V AC/DC IZMX16..., IZMX40... IZMX-SR230AD-2


INX16..., INX40... 180192

220 - 240 V AC/DC IZMX16..., IZMX40... +IZMX-SR230AD


INX16..., INX40... 123741

Latch check switches


1 changeover contact
Only in combination with closing release
– IZMX16..., IZMX40... IZMX-LCS-2 For external application
INX16..., INX40... 180104

– IZMX16..., IZMX40... IZMX-LCS40


INX16..., INX40... 124348

– IZMX16..., IZMX40... +IZMX-LCS


INX16..., INX40... 124347

Automatic closing after readiness for operation.


Only in combination with closing release.
– IZMX16..., IZMX40... IZMX-LCS-SR-2 For use with closing
INX16..., INX40... 180113 release IZMX-SR…

– IZMX16..., IZMX40... +IZMX-LCS-SR


INX16..., INX40... 124349

17
IZMX Series Air Circuit Breakers
Electrical Accessories

IZMX-UVR(-TD)…, IZMX-AS…
Rated control- For use with Cat. No. Instructions
voltage Part no.
Article no.
Us
V
Undervoltage releases
Cannot be combined with a second shunt release.
24 V DC IZMX16..., IZMX40... IZMX-UVR24DC-2 An additional control
INX16..., INX40... 180193 circuit terminal block is
24 V DC IZMX16..., IZMX40... +IZMX-UVR24DC required for retrofitting.
INX16..., INX40... 123743 page 12
48 V DC IZMX16..., IZMX40... IZMX-UVR48DC-2
INX16..., INX40... 180194
48 V DC IZMX16..., IZMX40... +IZMX-UVR48DC
INX16..., INX40... 123747
380-415V AC IZMX16..., IZMX40... IZMX-UVR400AC-2
INX16..., INX40... 180197
380-415V AC IZMX16..., IZMX40... +IZMX-UVR400AC
INX16..., INX40... 123874
110 - 125 V AC/DC IZMX16..., IZMX40... IZMX-UVR110AD-2
INX16..., INX40... 180195
110 - 125 V AC/DC IZMX16..., IZMX40... +IZMX-UVR110AD
INX16..., INX40... 123761
220 - 240 V AC/DC IZMX16..., IZMX40... IZMX-UVR220AD-2
INX16..., INX40... 180196
220 - 240 V AC/DC IZMX16..., IZMX40... +IZMX-UVR220AD
INX16..., INX40... 123841
Time delay modules
For combination with an undervoltage release.
Delay times: 0.1 s, 0.5 s, 1.0 s, 2.0 s.
120 V AC IZMX16..., IZMX40... IZM-UVR-TD-120AC Only in combination with
INX16..., INX40... 122956 undervoltage release
IZMX-UVR110AD.
230 V AC IZMX16..., IZMX40... IZM-UVR-TD-230AC Only in combination with
INX16..., INX40... 122957 undervoltage release
IZMX-UVR220AD.
Auxiliary contacts
Standard auxiliary switch for On-Off signaling. The basic device already contains two changeover contacts.
IZMX16 (NF): Two additional changeover contacts possible. IZMX40 (RF): up to 10 additional changeover contacts possible.
(Note: for changeover contacts of IZMX40, when being ordered separately with part number without ‘+’, the wire length varies when being
installed in different location, and the article number/part number also varies).
Additionally 2 NO / NC IZMX16... IZMX-AS22-16-2 Same for changeover contacts
contacts INX16.... 180361 of No.1&2 or No.3&4
Additionally 2 NO / NC IZMX40... IZMX-AS22-40-2-34 No.3&4 changeover
contacts INX40... 90000019000114 contacts
Additionally 2 NO / NC IZMX40... IZMX-AS22-40-2-56 No.5&6 changeover
contacts INX40... 90000019000115 contacts
Additionally 2 NO / NC IZMX40... IZMX-AS22-40-2-78 No.7&8 changeover
contacts INX40... 90000019000116 contacts
Additionally 2 NO / NC IZMX40... IZMX-AS22-40-2-9A No.9&10 changeover
contacts INX40... 90000019000117 contacts
Additionally 2 NO / NC IZMX40... IZMX-AS22-40-2-BC No.11&12 changeover
contacts INX40... 90000019000118 contacts
Additionally 2 NO / NC IZMX16..., IZMX40... +IZMX-AS22 –
contacts INX16..., INX40... 123880
Additionally 4 NO / NC IZMX40... +IZMX-AS44 –
contacts INX40... 123882
Additionally 6 NO / NC IZMX40... +IZMX-AS66 –
contacts INX40... 124344
Additionally 8 NO / NC IZMX40... +IZMX-AS88 –
contacts INX40... 124345
Additionally 10 NO / NC IZMX40... +IZMX-AS1010 –
contacts INX40... 124346

18
IZMX Series Air Circuit Breakers
Electrical Accessories

IZMX-OTS…, IZMX-TI…, IZMX-RA…, IZMX-RR…


Rated control- For use with Cat. No. Instructions
voltage Part no.
Article no.
Us
V
Overcurrent trip switches
Overcurrent trip switch (OTS) with two changeover contacts. Not available on INX switch disconnector.
– IZMX16... IZMX-OTS16-2 –
180364
– IZMX40... IZMX-OTS40-2 –
180366

– IZMX16..., IZMX40... +IZMX-OTS –


123888
Interlocked Trip Indicators
Can be used in combination with Overcurrent Trip Switches
and Remote Reset function. Not available on INX switch disconnector.
– IZMX16... IZMX-TI16 Included in IZMX breaker
156634
– IZMX40... IZMX-TI40 Included in IZMX breaker
156600
Non-Interlocked Trip Indicators
The switch does contain the mechanical trip-indicator (red pin).
Does not interlock with mechanism, allowing for automatic reset of breaker.
Can be used in combination with Overcurrent Trip Switches.
Cannot be combined with remote reset. Not available on INX switch disconnector.
– IZMX16... IZMX-RA16-2 Instead of standard
180354 delivery.

– IZMX40... IZMX-RA40-2
180365
– IZMX16..., IZMX40... +IZMX-RA
123897
Remote reset
The breaker can be switched on after a trip as
far the trip indicator is resetted manually.
The remote reset allows resetting remotely by an electrical signal. Not available on INX switch disconnector
24 V DC IZMX16.... IZMX-RR24DC-16-2 –
180095
24 V DC IZMX40... IZMX-RR24DC-40-2 –
180096
24 V DC IZMX16..., IZMX40... +IZMX-RR24DC –
123890
110 - 125 V AC/DC IZMX16... IZMX-RR110AD-16-2 –
180097
110 - 125 V AC/DC IZMX40... IZMX-RR110AD-40-2 –
180098

110 - 125 V AC/DC IZMX16..., IZMX40... +IZMX-RR110AD –


123892
220 - 240 V AC IZMX16... IZMX-RR230AD-16-2 –
180100
220 - 240 V AC IZMX40... IZMX-RR230AD-40-2 –
180101
220 - 240 V AC/DC IZMX16..., IZMX40... +IZMX-RR230AD –
123895

19
IZMX Series Air Circuit Breakers
Mechanical Accessories

IZMX-OC…, IZMX-PLPC…, IZMX-KLP-SO…


For use with Cat. No.
Part no.
Article no.
Operation counters
Counts the number of ON-OFF operations. Can also be installed without motor operator.
IZMX16… IZMX-OC16-2
INX16… 180184
IZMX40… IZMX-OC40-2
INX40… 180102
IZMX16…, IZMX40… +IZMX-OC
INX16…, INX40… 124341
Locking ON/OFF buttons
Padlockable front cover for ON-OFF pushbutton.
P = Insulated material IZMX16… IZMX-PLPC16-P-2
180379
IZMX40… IZMX-PLPC40-P-2
180107
IZMX16…, IZMX40… +IZMX-PLPC-P
124357
M = Metal IZMX16… IZMX-PLPC16-M-2
180380
IZMX40… IZMX-PLPC40-M-2
180105
IZMX16…, IZMX40… +IZMX-PLPC-M
124352
OFF = Safe OFF; then it is also impossible to switch IZMX40… IZMX-PLPC40-M-OFF-2
on via the closing release 180106
IZMX16…, IZMX40… +IZMX-PLPC-M-OFF
124355
Safe OFF lock mechanism for cylinder locks
The “Safe OFF” interlock prevents switching on. Neither
remote nor local switching on is possible.
For corresponding typ of lock cylinder see installation instructions.
Lock cylinder and key are required for installation..
CES installation kit without lock cylinder and key. IZMX16…, IZMX40… IZMX-KLP-SO-CES-2
Compatible CES cylinder #5256-LAG, key #90134. INX16…, INX40… 180108
Kirk installation kit without lock cylinder and key. IZMX16…, IZMX40… IZMX-KLP-SO-KIRK-2
Compatible Kirk Keylock #KC40.10. INX16…, INX40… 180109
Ronis installation kit without lock cylinder and key. IZMX16…, IZMX40… IZMX-KLP-SO-RONIS-2
Compatible Ronis lock 1351-10B (Dim A = 7 mm). INX16…, INX40… 180111
Castell installation kit without lock cylinder and key. IZMX16…, IZMX40… IZMX-KLP-SO-CASTELL-2
Compatible Castell Cylinder #CL1019(modified to 90°), INX16…, INX40… 180112
key #FKW6-NI
Kirk installation kit without lock cylinder and key, A type IZMX16…, IZMX40… IZMX-1L1K
INX16…, INX40… 90000019000039
Kirk installation kit without lock cylinder and key, B type IZMX16…, IZMX40… IZMX-1L1K-B The key and lock cylinder of -B
INX16…, INX40… 90000019000046 and -C are not interchangeable
with IZMX-1L1K
Kirk installation kit without lock cylinder and key, C type IZMX16…, IZMX40… IZMX-1L1K-C The key and lock cylinder of -B
INX16…, INX40… 90000019000047 and -C are not interchangeable
with IZMX-1L1K
Notes:
It is recommended to request factory installation for IZMX-1L1K(-B/-C), with no additional installation charge. Service fee will be applied if
requesting Eaton field installation service. Contact our sales specialists before ordering.

20
IZMX Series Air Circuit Breakers
Mechanical Interlock

IZMX-MIL…W…, IZMX-MIL…-F…, IZMX-MIL-CAB…


For use with Cat. No.
Part no.
Article no.
Mechanical interlock, drawout mounting
Type 2, for 2 circuit-breakers: A normal power supply (A) and an IZMX16... IZMX-MIL2C-W16-2
emergency network supply (B). IMX16... 180336

IZMX40... IZMX-MIL2C-W40-2
IMX40... 180344
Type 2 requires 2 interlock
Type 31, for 3 circuit-breakers: Two normal power supplies(A, IZMX16... IZMX-MIL3133C-W16-2
mounting kits and 1 set of
C) and an emergency network supply (B). When B in Off, A and IMX16... 183117
cables
C can be switched on. B can be switched on only when A and
Type 31 requires 3 C are in Off. IZMX40... IZMX-MIL3133C-W40-2
interlock mounting kits IMX40... 183119
or
and 2 sets of cables Type 33, for 3 circuit-breakers: Three incoming units (A, B, C),
Type 32 or 33 requires 3 normal or emergency network. Only one of the three circuit
interlock mounting kits breakers can be switched on at any one time.
and 3 sets of cables
Type 32, for 3 circuit-breakers: Two normal incoming units (A, C) IZMX16... IZMX-MIL32C-W16-2
and one coupling (B). Any one or two circuitbreakers can be clo- IMX16... 180338
sed at the same time.
IZMX40... IZMX-MIL32C-W40-2
IMX40... 180346
Mechanical interlock, fixed mounting
Type 2, for 2 circuit-breakers: A normal power supply (A) IZMX16..., INX16... IZMX-MIL2C-F16-2
and an emergency network supply (B). 180332
IZMX40..., INX40... IZMX-MIL2C-F40-2
180340
Type 2 requires 2 interlock Type 31, for 3 circuit-breakers: Two normal power supplies(A, IZMX16..., INX16... IZMX-MIL3133C-F16-2
mounting kits and 1 set of C) and an emergency network supply (B). When B in Off, A and 183118
cables
C can be switched on. B can be switched on only when A and
Type 31 requires 3 C are in Off. IZMX40..., INX40... IZMX-MIL3133C-F40-2
interlock mounting kits or 183120
and 2 sets of cables Type 33, for 3 circuit-breakers: Three incoming units (A, B, C),
Type 32 or 33 requires 3 normal or emergency network. Only one of the three circuit
interlock mounting kits breakers can be switched on at any one time. Three sets of
and 3 sets of cables cables are required in addition.
Type 32, for 3 circuit-breakers: Two normal incoming IZMX16..., INX16... IZMX-MIL32C-F16-2
units (A, C) and one coupling (B). Any one or two circuit- 180334
breakers can be closed at the same time.
IZMX40..., INX40... IZMX-MIL32C-F40-2
180342

Cable kits for mechanical interlock


Depending on the type of interlock, a particular number of cable connectors is required. With the flexible cable
connectors, various different switch arrangements can be implemented.
One set contains two cables.
1520 mm long IZMX-MIL...C-F... IZMX-MIL-CAB1520-2
IZMX-MIL...C-W... 180348
1830 mm long IZMX-MIL...C-F... IZMX-MIL-CAB1830-2
IZMX-MIL...C-W... 180349
2440 mm long IZMX-MIL...C-F... IZMX-MIL-CAB2440-2
IZMX-MIL...C-W... 180350
3050 mm long IZMX-MIL...C-F... IZMX-MIL-CAB3050-2
IZMX-MIL...C-W... 180351

Interlock among X16, X40, fixed or withdrawable:


Example: A type 33 configuration including 1 IZMX40 drawout, 1 IZMX40 fixed, and 1 IZMX16 drawout with 3050mm cables,
order:
1. IZMX-MIL3133C-W40-2, QTY: 1, for 1 IZMX40 drawout
2. IZMX-MIL3133C-F40-2, QTY: 1, for 1 IZMX40 fixed
3. IZMX-MIL3133C-W16-2, QTY: 1, for 1 IZMX16 drawout
4. IZMX-MIL-CAB3050-2, QTY:3, for type 33 configuration

21
IZMX Series Air Circuit Breakers
Mechanical Interlock Configurations

IZMX16, INX16, IZMX40, INX40


Mechanical Interlock configurations Type of interlock Typical circuit Interlocks possible
Type 2 Across Two Circuit Breakers Circuit breaker A can only be
TR
One normal power supply and one closed if B is open and vice versa.,
emergency power supply.

A = Normal power supply


B = Emergency power supply.
A B
A B
0 0
1 0
0 1
Interlock: A against B

Type 31 Across Three Circuit Breakers Circuit breaker A and C can only be
TR1 TR2
Two normal power supplies and closed if B is open. B can only be
one emergency power supply. closed when A and C are open.

A B C
A B C
0 0 0
1 0 0
0 1 0
0 0 1
Interlock: A, C against B 1 0 1

Type 32 Across Three Circuit Breakers TR1 TR2 One of two circuit breakers out of
The two half-bus bars can be pow- three can be closed at the same
ered by a single transformer (bustie time.
closed) or by both at the same
time (bus-tie open). A B C
0 0 0
A B C 1 0 0
0 1 0
0 0 1
1 1 0
0 1 1
Interlock: 2 against 1 or max. 2 of 3 1 0 1

Type 33 Across Three Circuit Breakers TR1 Only one of three circuit breakers
Three power supplies (generators can be closed.
or transformers) on the same bus
bar, making operation in parallel A B C
impossible. 0 0 0
1 0 0
A B C 0 1 0
0 0 1

Interlock: 1 against 2 or max. 1 of 3

22
IZMX Series Air Circuit Breakers
Mechanical Accessories

IZMX-LT…, IZMX-DEG…, IZMX-DC…


For use with Cat. No. Instructions
Part no.
Article no.
Collapsible hand lever
Standard Omega shaped handle is included IZMX16…-…W IZMX-LT16-2 –
in D/O breaker. Optional collapsible handle INX16…-…W 180134
can be ordered separately
IZMX40…-…W IZMX-LT40-2 –
INX40…-…W 180206

Door gasket, IP41, for withdrawable breaker


IZMX16…-…W IZMX-DEG16-W-2 Spare part; supplied
INX16…-…W 180110 as standard with every
breaker.
IZMX40…-…W IZMX-DEG40-W-2
INX40…-…W 180205

Door cover, IP55, for withdrawable breaker


The protective cover allows a higher protection type. IZMX16…-…W IZMX-DC16-W-2 –
IP55 INX16…-…W 180145

IZMX40…-…W IZMX-DC40-W-2 –
INX40…-…W 180202

Door gasket, IP41, for fixed breaker


IZMX16…F IZMX-DEG16-F-2 Spare part; supplied
INX16…F 180099 as standard with every
breaker.
IZMX40…F IZMX-DEG40-F-2
INX40…F 180204

Door cover, IP55, for fixed breaker


The protective cover allows a higher protection type. IZMX16…F IZMX-DC16-F-2 –
IP55 INX16…F 180146

IZMX40…F IZMX-DC40-F-2 –
INX40…F 180203

23
IZMX Series Air Circuit Breakers
Terminals

IZMX-T(H)(F)(V)…
Connection Rated Pole For use with Cat. No. Note
current Part no.
Article no.
In
A
Main terminal component adapter
IBasic cassettes are delivered with flange terminals as standard. Following adapters are optional and for INX16,
IZMX16 fixed version requested. Each set contains the connections for top and bottom. 3 pole = 6 off; 4 pole = 8 off
Universal connection 800 - 1600 3 IZMX16… IZMX-THV163-2
horizontal, vertical INX16… 180137
Universal connection 800 - 1600 4 IZMX16… IZMX-THV164-2
horizontal, vertical INX16… 180136
Universal connection 800 - 1600 3 IZMX16… IZMX-THVL163-2 Temp.
horizontal, vertical, long INX16… 180139 N/A
Universal connection 800 - 1600 4 IZMX16… IZMX-THVL164-2 Temp.
horizontal, vertical, long INX16… 180140 N/A

Universal connection 800 - 3200 3 IZMX16… IZMX-THV403-3200-2


horizontal, vertical INX16… 180175

Connection 4000 3 IZMX40… IZMX-TH403-2


horizontal INX40… 180177
Connection 4000 3 IZMX40… IZMX-TV403-2
vertical INX40… 180178

Universal connection 800 - 3200 4 IZMX40… IZMX-THV404-3200-2


horizontal, vertical INX40… 180179

Connection 4000 4 IZMX40… IZMX-TH404-2


horizontal INX40… 180180
Connection 4000 4 IZMX40… IZMX-TV404-2
vertical INX40… 180181
Connection 800 - 1600 3 IZMX40…F IZMX-TF403-1600F Temp.
front INX40…F 173363 N/A
fixed breaker
2000 - 2500 3 IZMX40…F IZMX-TF403-2500F Temp.
INX40…F 173367 N/A
3200 3 IZMX40…F IZMX-TF403-3200F Temp.
INX40…F 173371 N/A
800 - 1600 4 IZMX40…F IZMX-TF404-1600F Temp.
INX40…F 173365 N/A

2000 - 2500 4 IZMX40…F IZMX-TF404-2500F Temp.


INX40…F 173369 N/A
3200 4 IZMX40…F IZMX-TF404-3200F Temp.
INX40…F 173373 N/A
Connection 800 - 1600 3 IZMX40…W IZMX-TF403-1600W Temp.
front INX40…W 173364 N/A
withdrawable cassette
2000 - 2500 3 IZMX40…W IZMX-TF403-2500W Temp.
INX40…W 173368 N/A

3200 3 IZMX40…W IZMX-TF403-3200W Temp.


INX40…W 173372 N/A
800 - 1600 4 IZMX40…W IZMX-TF404-1600W Temp.
INX40…W 173366 N/A

2000 - 2500 4 IZMX40…W IZMX-TF404-2500W Temp.


INX40…W 173370 N/A
3200 4 IZMX40…W IZMX-TF404-3200W Temp.
INX40…W 173374 N/A

24
IZMX Series Air Circuit Breakers
Terminal Assignment of Control Circuit Terminals

IZMX16 Control Circuit Terminal Assignment

1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47 49 51 53 55
+ +

MODBA

MODBG
ACCY2

CMM1

CMM3

ACCY5

ACCY7
ZCOM
ALMC

ALM2
OT1C

OT1B

PTVA

PTVC
+24V
UV1

EO1

SR1
ST1

ZIN
N1

G1

C1

B1

C2

C3

B3

C4
ARMSIN
-
-

MODBB
ACCY1

ACCY3

CMM2

CMM4

ACCY4

ACCY6
AGND
OT1M

ALM1

ALM3

ZOUT

PTVN
PTVB
UV2

EO2

SR2
ST2

N2

G2

SC

A1

A2

A3

A4
B2

B4
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56

1, 2 - Shunt trip 20,22 - ARMs


3, 4 - UVR/2nd shunt trip 25-28 - External CAM module
5~7 - Overload trip switch 1 (OTS) ( 5-COM, 6-N.O, 7-N.C.) 29~32 - PT module
8~10 - Overload trip switch 2 (OTS)/ Remote reset 33~35 - Onboard ModBus
(8-N.C., 9-COM, 10-N.O./9-RR1, 10-RR2) 36 - ACCY4 (Reserved)
11,12 - External netural sensor 37~39 - Latch check switch (37-COM, 38-N.O, 39-N.C.)
13~16 - Alarm 40 - Message :Spring energy store tensioned
17,18 - Ground fault source sensor 41,42 - Motor operator
19, 20 - Control voltage supply 24VDC 43,44 - Spring closing release
21,23,24 - Zone selectivity ZSI 45~56 - Auxiliary contact On/off, C-COM, A-N.O., B-N.C.

IZMX40 Control Circuit Terminal Assignment

1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 47
+ + ARCON2
MODBA

MODBG

2CMM3

2CMM1
CMM1

CMM3
ZCOM
ALMC

ALM2
OT1C

OT1B

OT2C

PTVA

PTVC
+24V
UV1

RR1
ST1

ZIN
N1

G1

ARMSIN

ARCON1

ARCON3
-
-

2CMM2

2CMM4
MODBB
CMM2

CMM4
AGND
OT1M

OT2M

ALM1

ALM3

ZOUT

PTVN
OT2B

PTVB
UV2

RR2
ST2

N2

G2

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48

1, 2 - Shunt trip 20,22 - ARMs


3, 4 - UVR/2nd shunt trip 25-28 - External CAM module
5~7 - Overload trip switch 1 (OTS) (5-COM, 6-N.O, 7-N.C.) 29~32 - PT module
8~10 - Overload trip switch 2 (OTS) (8-N.C., 9-COM, 10-N.O.) 33~35 - Onboard ModBus
11,12 - External netural sensor 36~39 - External CAM module (future)
13~16 - Alarm 40~42 - ARCON
17,18 - Ground fault source sensor 43,44 - Remote reset
19, 20 - Control voltage supply 24VDC 45~48 - Reserved
21,23,24 - Zone selectivity ZSI

49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 85 87 89 91 93 95
+
SR1
LCC

LCB

C10

C11

B11

C12
E01

C1

B1

C2

C3

B3

C4

C5

B5

C6

C7

B7

C8

C9

B9
-
LCM

SR2

A10

A11

A12
B10

B12
E02
SC

A1

A2

A3

A4

A5

A6

A7

A8

A9
B2

B4

B6

B8

50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96

49~51 Latch check switch (49-COM, 50-N.O., 51-N.C.)


52 - Message :Spring energy store tensioned
53, 54 - Motor operator
55~56 - Spring closing release
57~92 - Auxiliary contact On/off, C-COM, A-N.O., B-N.C.

25
Aux Box Tray

26
To Frame
Module JP4

5 6 7 8 9 10 36 37 38 39 Secondary Terminals MCR TA


Secondary
Wiring Diagram

11 12
46 45 47 48 49 50 52 51 53 54 55 56 Terminals

OT1C
OT1B
N1
N2

OT1M
ACCY1
ACCY2
ACCY3
ACCY4
ACCY5
ACCY6
ACCY7
C2

C1
C3
C4

B1
B2
B3

A2
A3
A4

A1

+24V
G2

AGND

SC
ALMC
G1

ALM3
ZOUT

ALM2

ST1+
ST2-
UV1+
UV2-
SR1+
E01+

SR2-
E02-
ALM1
PTVC
PTVN
CMM3
B4 ARMSIN
ZIN

ZCOM

CMM2

PTVB
MODBB

CMM4
MODBG

PTVA
CMM1
MODBA
1 4 44 41 40 42 14 15 16 20 19 18 17 29 31 30 32 25 28 26 27 24 22 23 21 34 35 33

TA-
2 3 43 13

TA+

MCR1
MCR2
X16 Master connection diagram

7 6 5 4 3 2 1 8 7 6 5 4 3 2 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
ST UVR SR M

JP5 8 JP1
A B C N JP6
Rogo Coils
ROG 1 2
2 Ground Fault (G21,G22)
2
6 3V3
3 JP1
IZMX Series Air Circuit Breakers

1 1.2VRef
CT 4
5
5V
ROG 1
2 5.1V_Start
2
6 3V_BAT
3
1 JP2 5
CT 4 SPI
5 Fame Module Trip Unit Board
ROG 1
2
2 VAUX_EX
6
3 JP3
1 VAUX1
CT 4
5 ST2
11 N1
ROG ST-
1 12 N2
2 3
2 Relay_DR
6
3 JP4
1
CT 4 40 Pins
5 Connector J2
J1

2 1 1 2 3 4 5
Circuit Breaker
GND

Data-

Data+

VBUS

VAUX-
VAUX+

Aux Power USB


5 6 7 8 9 10 36 37 38 39 40 41 42 43 44 45 46 47 48 Secondary Terminals 1 MCR TA Secondary Terminals 1

RR1
RR2

OT2B
OT2C

OT1C
OT1B
OT2M

OT1M
2CMM4

2CMM2
2CMM3
2CMM1
ARCON3

ARCON1
ARCON2
+24V

ALMC
ZOUT

ALM3

N2
ALM2
G2

AGND

ST1+
ST2-
UV1+
UV2-
N1
ALM1
G1
PTVC
PTVN
CMM3
ARMSIN
ZCOM
ZIN

CMM2

PTVB
MODBB

CMM4
MODBG

PTVA
CMM1
MODBA
1 4 11 12 13 14 15 16 20 19 18 17 29 31 30 32 25 28 26 27 24 22 23 21 34 35 33

TA-
2 3

TA+

MCR1
MCR2
7 6 5 4 3 2 1 8 7 6 5 4 3 2 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
ST UVR
To Frame
Module JP4

JP5 8 JP1
A B C N JP6
Rogo Coils
ROG 1 2
X40 Master connection diagram

2 Ground Fault (G21,G22)


2
6 3V3
3 JP1
1 1.2VRef
CT 4
5
5V
ROG 1
2 5.1V_Start
2
6 3V_BAT
3 1 Trip Unit Board
JP2 Fame Module 5
CT 4 SPI
5
ROG 1
2
2 VAUX_EX
6
3 JP3
1 VAUX1
CT 4
5 ST2
11 N1
ROG ST-
1 12 N2
2 3
2 Relay_DR
6 J1 J2
3 JP4
1
CT 4
5 40 Pins 2 1 1 2 3 4 5
Circuit Breaker Connector

Aux Box Tray


GND

Data-

Data+

VBUS

VAUX-
VAUX+

Aux Power USB

58 57 59 60 61 62 64 63 65 66 67 68 70 69 71 72 73 74 76 75 77 78 79 80 82 81 83 84 85 86 88 87 89 90 91 92

A1
C9
B9

A9

C1
B1
B2
C3
B3
B4
C5
B5
B6
C7
B7
B8
C8

A2
A3
A4
A5
A6
A7
A8

C2
C6

C4
B10
C10
C11
B11
B12
C12

A10
A11
A12

LCC
SC

LCM
LCB
EO1+
EO2-
SR1+
SR2-
49 50 51 53 52 54 55 56 93 94 95 96
Secondary Terminals 2

M SR

27
Wiring Diagram
IZMX Series Air Circuit Breakers
IZMX Series Air Circuit Breakers
Wiring Diagram

X16 Circuit Breaker Control

43 41 40

44 42

Series NRX Circuit Breaker

Legend:
MOT – Motor Operator for Charging Closing Spring
ST – Shunt Trip
SR – Spring Release

Description of Operation:
1. The motor is energized and runs, charges closing spring, and is cut off by switch.
2. When the spring is charged, the SC closes and the green indicating light will illuminate (if applicable).
3. Closing the CS-C contact energizes the Spring Release Coil and closes the circuit breaker. The Spring Release internal electronics
pulse the SR coil and then provides a high impedance circuit. This provides anti-pumping.
4. When the spring discharges its energy, the motor switch will re-energize the charging motor until the spring is charged again.
5. To detect the presence of voltage (Health Light), use Omron Red indicator LED Port # C22-L-R-120 for 120 Vac application. For 230 Vac
application, use C22-L-R-230. For 24 Vdc application, use C22-L- R-24. Remove the white (22 mm [0.89 in.]) diameter pilot light) Light
Diffuser from the assembly to give better indication of voltage present. Activate the push-button to trip the circuit breaker. See Eaton
for other voltages.
6. For secondary contacts, odd numbers should be treated as positive for any accessory. This will not apply to AC ratings.
7. ReferencePage 26 for internal circuit breaker wiring.

28
IZMX Series Air Circuit Breakers
Wiring Diagram

X40 Circuit Breaker Control

55 53 52
56 54

Series NRX Circuit Breaker

Legend:
MOT – Motor Operator for Charging Closing Spring
ST – Shunt Trip
SR – Spring Release
Description of Operation:
1. The motor is energized and runs, charges the closing spring, and is cut off by the switch.
2. When the spring is charged, SC closes and the green indicating light will illuminate (if applicable).
3. Closing the CS-C contact energizes Spring Release coil and closes circuit breaker. The Spring Release internal electronics pulse the
SR coil and then provides a high impedance circuit. This provides anti-pumping.
4. When the spring discharges its energy, the motor switch will re-energize the charging motor until the spring is charged again.
5. To detect presence of voltage (Health Light), use Omron Red indicator LED Port # C22-L-R-120 for 120 Vac application. For 230 Vac
application, use C22-L-R-230 . For 24 Vdc application, use C22-L- R-24. Remove the white (22 mm [0.89 in.]) diameter pilot light) Light
Diffuser from the assembly to give better indication of voltage present. Activate the push-button to trip the circuit breaker. See Eaton
for other voltages.
6. For secondary contacts, odd numbers should be treated as positive for any accessory. This will not apply to AC ratings.
7. Reference Page 27 for internal circuit breaker wiring.

29
IZMX Series Air Circuit Breakers
Wiring Diagram

Under Voltage Release

Series NRX Circuit Breaker

Notes:
1. Treated as the positive voltage for DC ratings.

30
IZMX Series Air Circuit Breakers
Wiring Diagram

PXR Alarm Wiring

24VDC ±10%

Control Power
ALM2 ALM3
ALM-Com ALM1
13 15 19

14 16 d 20
a b c

Series NRX Circuit Breaker

Notes:
1. For the PXR20/25, the Alarm 1 is for Remote Indication/ Maintenance Mode indication. Contact rating 1 A @ 120 Vac, 1 A @ 24 Vdc, and 0.5 A @ 230 Vac.
2. For the PXR20/25, the Alarm 2 is for High Load alarm/Ground Fault alarm. Contact rating 1 A @ 120 Vac, 1 A @ 24 Vdc, and 0.5 A @ 230 Vac.
3. For the PXR20/25, the Alarm 3 is for Trip N.O. contact. Contact rating 1 A @ 120 Vac, 1 A @ 24 Vdc, and 0.5 A @ 230 Vac.
4. If the control voltage is +24 Vdc, the trip unit should be fed from a separate, galvanically isolated + 24 V voltage dc supply.

31
IZMX Series Air Circuit Breakers
Wiring Diagram

Ground Fault Residual 3-Phase, 4-Wire

11

12

PXR

Series NRX Circuit Breaker

Notes:
1. Sensor is customer wired to sense neutral currents. This is required for 3-phase, 4-wire Residual Ground Fault (applicable for trip units having G protection).

32
IZMX Series Air Circuit Breakers
Wiring Diagram

Source Ground Fault Sensing

External
Sensor

PXR

Series NRX Circuit Breaker

Notes:
1. Sensor NFGFSKIT (IZMX-EFS) is used to sense and detect Ground Fault currents. The Part number is 70C1527G04.

33
IZMX Series Air Circuit Breakers
Wiring Diagram

Zero Sequence Ground Fault Sensing

PXR

Series NRX Circuit Breaker

Notes:
1. Sensor NFGFSKIT (IZMX-EFS) is used to sense and detect Ground Fault currents of 3-wire or 4-wire. The Part number is 70C1527G04.

34
13 19 22 20
14 20 22
Maintenance Mode Wiring

Series NRX Circuit Breaker Series NRX Circuit Breaker

Maintenance Mode Wiring Alternate Customer Wiring (partial)

Notes:
1. PXR20/25 can locally be placed in Maintenance Mode via a two position switch located on the trip unit. The function can be armed via a remote switch as shown.
In addition, the function can be activated via communication modules. A blue LED on the PXR verifies the PXR release in Maintenance Mode.
2. The recommended selector switch for this low voltage application is Eaton part number 10250T133-2E which includes a contact block rated for logic level and
corrosive use.
3. The maximum length of this wiring to remotely arm the switch (or alternate relay contact) is 9.78 feet (3 m). Use #20 AWG wire or larger.
4. A remote Stack Light Annunciator panel or other remote indication device can be connected to verify that PXR is in the Maintenance Mode.
5. The relay in the PXR release makes when in Maintenance Mode. Contact is rated 1 A @ 120 Vac, 1 A @ 24 Vdc, and 0.5 A @ 230 Vac.
6. The PXR release can also be placed remotely in its Maintenance Mode via a general purpose relay (ice cube type with logic level contacts) and activated by a
remote control switch. A recommended type is IDEC Relay RY22. Choose the voltage as desired.
7. If a Communication Module is used, The Communication Module will require 24 Vdc power and will provide isolated
power to the PXR release in the circuit breaker. If a Communication Module is not used, the PXR release that requires auxiliary voltage for alarms which should
be fed from a galvanically isolated, 24 Vdc supply.

35
Wiring Diagram
IZMX Series Air Circuit Breakers
IZMX Series Air Circuit Breakers
Wiring Diagram

External PT Module for PXR25 U type trip unit


0-600 L-L INPUT
A B C

Secondary
1 3 5 Contacts
TP2 LA
PT
32 MODULE LB
31 PTVC
LC
30 PTVB
29 PTVA

To additional
breakers (16 max)

BREAKER

Series NRX Mounted Breakers - 3 pole - 3 wire

0-600 L-L INPUT


N A B C

Secondary
1 3 5 Contacts
TP2 LA
PT
32 PTVN MODULE LB
31 PTVC
LC
30 PTVB
29 PTVA
LN

To additional
breakers (16 max)

BREAKER

Series NRX Mounted Breakers - 3 pole or 4 pole - 4 wire

36
23 21 23 21 23 21
24 24 24

PXR PXR PXR


Zone Interlock Wiring

23 21
24

PXR

Notes:
1. Twisted together AWG #14 to #20 copper wire. Route the Zone Interlock wiring
separate from power conductors. DO NOT GROUND any Zone Interlock wiring.
2. The maximum distance between two farthest breakers on different zones (from the
Zout downstream to the Zin upstream terminals) is 250 feet (75 m).
3. A maximum of 20 breakers may be contained in parallel in one zone.
4. Provide a self interlocking jumper (on Zone 3), if coordination is desired with other
downstream breakers not providing the Zone Interlock feature.

37
Wiring Diagram
IZMX Series Air Circuit Breakers
IZMX Series Air Circuit Breakers
Tripping Characteristics

IZMX16(40)…V(U)… PXR20/25 Long Delay(L) and Short Delay(S) Curves


L-Protection: I²t-Characteristic curve and S-Protection: Flat characteristic curve
10000
9000
8000
7000
6000
5000
4000
3000

2000

1000
900
800
700
600
500
400
300

200

100
90
80
70
60
Time in Seconds

50
40
30
24
20

15

10
9 0.5
8 1
7 7
6
5
10
4 2 4 b
3
2 3
2

a 7
1 4 5
.9
.8 1.5
.7 8
.6 2.5
.5 0.5
.4
0.4
.3
6 0.3
.2
0.2

.1
.09
c
.08 0.1
.07
.06
.05
.04
.03
0

.02

.01
100
10

20

30

40

50

60

70
80
90
.1

.2

.3

.4

.5

.6

.7
.8
.9
1

7
8
9

Current in Multiples of Long Delay Pickup (Ir)


Notes:
1. Short slope: Flat, the actual pickup point has 100% ±10% tolerance.
2. Long delay I²T slopes flattens out at 6x of Ir.
3. Short time delay from 0(50ms) to 0.5s, with +0 / -80ms tolerance except 0.1s and 0s setting
0.1s setting, trip time is 0.06s to 0.1s
0s settting, nominal clear time is 60ms with auxiliary power and 120ms without.
4. If long delay thermal memory is enabled, trip times may be shorter than indicated in this chart.
5. Curves applies from -20°C to +50°C ambient. Temperatures above +85°C will cause over temperature trip.
6. This curve is for 50Hz, 60Hz applications.
7. These curves are comprehensive for series NRX NF&RF(IZMX16/40) circuit breakers including all frame sizes, ratings, and constructions.
The total clearing times shown include the response time for trip unit, the breaker opening and the interruption of the current

38
IZMX Series Air Circuit Breakers
Tripping Characteristics

IZMX16(40)…V(U)… PXR20/25 Long Delay(L) and Short Delay(S) Curves


S-Protection with: I²t-Characteristic curve ON
10000
9000
8000
7000
6000
5000
4000
3000

2000
a
1000
900
800
700
600
500
400
300

200

100
90
80
70 24
60
50
Timein Seconds

40 15
30
1.5
20 7
c
0.5 4
10
9
8
7 1
6
2
5
4
b
0.5
3
3 6 10
2

1
.9
.8
.7
.6
.5
0.5
.4
0.4
.3
0.3
.2
d
e
.1
.09
.08 0.1
.07
.06
.05
.04
.03

.02

.01
100
10

20

30

40

50

60
70
80
90
1

6
7
8
9

Current in Multiples of Long Delay Pickup (Ir)


Notes:
1. This curve shown as a multiple of the LONG PU setting(Ir). The actual pickup point occurs at 110% of the Ir, with ±5% tolerance.
2. SDPU = 1.5x to 10x of Ir, have 100% ± 10% tolerance.
3. LD Time = 0.5s to 24s, have 100% +0 / -30% tolerance.
4. SD Slope = I²T. The short pickup points have ±10% tolerance.
time setting from 0.1s to 0.5s, with steps of 0.1s, except 0.2s.
tolerance is 100% +0 / -30% except 0. 1s, has tolerance 100% +0 / -40%.
5. I²T slopes flattens out at 8x of Ir for top of band with FLAT time minimum value prevailing for bottom of band. For all curves the lower flat
response time value projected to I²T line will determine the other break point and shape of the curve.
6. If long delay thermal memory is enabled, trip times may be shorter than indicated in this chart.
7. Curves applies from -20°C to +50°C ambient. Temperatures above +85°C will cause over temperature trip.
8. This curve is for 50Hz, 60Hz applications.
9. These curves are comprehensive for series NRX NF&RF(IZMX16/40) circuit breakers including all frame sizes, ratings, and constructions.

39
IZMX Series Air Circuit Breakers
Tripping Characteristics

IZMX16(40)…V(U)… PXR20/25 Instantaneous(I) Curves


I-Protection: Adjustable
10000
9000
8000
7000
6000
5000
4000
3000

2000

1000
900
800
700
600
500
400
300

200

100
90
80
70
60
Timein Seconds

50
40
30

20

10
9
8
7
6
5
4
3

2 4 6 12 15
a

1
.9
.8
.7
.6
.5
.4 2 5 8
.3

.2
7 b
10
.1
.09
.08
.07
.06
.05
.04
.03

.02

.01
100
10

20

30

40

50

60

70
80
90
1

7
8
9

Current in Multiples of Rating (In)


Notes:
1. The Instantaneous settings have conventional 100% ±10% as the pickup points.
2. The nominal Instantaneous trip time is 60ms with auxiliary power supply and 100ms without.
3. Instantaneous protection could be disabled by setting Instantaneous PU switch to OFF position.
4. The curve is shown as a multiple of the Current Rating (In).
5. The end of the curve is determined by the interrupting rating of the circuit breaker.
6. Curves applies from -20°C to +50°C ambient. Temperatures above +85°C will cause over temperature trip.
7. This curve is for 50Hz, 60Hz applications.
8. These curves are comprehensive for series NRX NF&RF(IZMX16/40) circuit breakers including all frame sizes, ratings, and constructions.
The total clearing times shown include the response time for trip unit, the breaker opening and the interruption of the current.

40
IZMX Series Air Circuit Breakers
Tripping Characteristics

IZMX16(40)…V(U)… PXR20/25 Instantaneous(I) Curves


Instantaneous Trip at High Fault Currents
10000
9000
8000
7000
6000
5000
4000
3000

2000

1000
900
800
700
600
500
400
300

200

100
90
80
70
60
50
Timein Seconds

40
30

20

10
9
8
7
6
5
4
3

1
.9
.8
.7
.6
.5
.4
.3

.2

.1
.09
.08
.07
.06
.05
.04
a b
.03

.02
90kA 167kA

.01
1000
100

200

300

400

500

600

700
800
900
10

20

30

40

50

60

70
80
90

Instantaneous Asymmetrical Peak Current (kA)


Notes:
1. Fixed High Instantaneous Trip function is provided in the circuit breaker for Series NRX - Type NF(IZMX16) set to pickup at 90kA.
Instantaneous peak current level. The tolerance is 100% ±10% as the pickup points.
2. The peak current level setting for NRX - Type RF(IZMX40) is fixed at 167kA.
3. This protection is functional even when the Instantaneous is set to the OFF position.
4. The PXR will light the Instantaneous LED for a High Instantaneous trip.
5. The total Instantaneous clearing times shown are conservative and consider the maximum response times of the trip unit, the circuit breaker opening,
and the interruption of the current under factors that contribute to worst case conditions, like:
maximum rated voltages, single phase interruption, and minimum power factor. Faster clearing times are possible depending on the specific system
conditions, the type of circuit breaker applied, and if any arc reduction settings are employed.

41
IZMX Series Air Circuit Breakers
Tripping Characteristics

IZMX16(40)…V(U)… PXR20/25 Ground(G) Curves


G: Ground fault protection - Flat characteristic curve
10000
9000
8000
7000
6000
5000
4000
3000

2000

1000
900
800
700
600
500
400
300

200

100
90
80
70
60
50
Timein Seconds

40
30

20

10
9
8
7
6 a
5
4
3 0.2 0.6 1.0
2

1 0.4 0.8
.9
.8
.7
.6
.5 0.5
.4
0.4
.3
0.3
.2
b
0.2
.1
.09
.08 0.1
.07
.06
.05
.04
.03

.02

.01
10

20

30

40

50
.1

.2

.3

.4

.5
.6
.7
.8
.9
1

5
6
7
8
9

Current in Multiples of Rating(In)


Notes:
1. Ground PU setting from 0.2 to 1.0 of In with steps of 0.2 , have tolerance of 100% ± 10%.
2. Ground Flat time from 0.1s to 0.5s, with 0.1s increments.
3. Ground slope: Flat, trip time tolerance is +0 / -80ms for all settings except 0.1s setting is 0.06s to 0.1s.
4. The curve is shown as a multiple of the Current Rating (In).
5. The end of the curve is determined by the interrupting rating of the circuit breaker.
6. Curves applies from -20°C to +50°C ambient. Temperatures above +85°C will cause over temperature trip.
7. This curve is for 50Hz, 60Hz applications.
8. These curves are comprehensive for series NRX NF&RF(IZMX16/40) breakers including all frame sizes, ratings, and constructions.
The total clearing times shown include the response time for trip unit, the breaker opening and the interruption of the current.

42
IZMX Series Air Circuit Breakers
Tripping Characteristics

IZMX16(40)…V(U)… PXR20/25 Ground(G) Curves


G: Ground fault protection-I²t-Characteristic curve ON
10000
9000
8000
7000
6000
5000
4000
3000

2000

1000
900
800
700
600
500
400
300

200

100
90
80
70
60
Timein Seconds

50
40
30

20

10
9
8
7 a
6
5 0.8
4
3 0.2 0.4 0.6 1.0
2

1
.9
.8
.7
.6
.5
0.5
.4 b 0.4
.3
0.3
.2
0.2 c
.1
.09
.08 0.1
.07
.06
.05
.04
.03

.02

.01
10

20

30

40

50
.1

.2

.3

.4

.5
.6
.7
.8
.9
1

5
6
7
8
9

Current in Multiples of Rating (In)


Notes:
1. Ground PU setting from 0.2 to 1.0 of In with steps of 0.2 , have tolerance of 100%± 10%.
2. Beak points at 0.625 x In to flat.
3. Ground I²T time from 0.1s to 0.5s, with 0.1s increments.
4. Ground slope: Flat, trip time tolerance is +0 / -80ms for all settings except 0.1s setting is 0.06s to 0.1s.
Ground slope: I²T , tolerance is
0.1s, 0.2s : +0 / -40%
0.3s, 0.4s, 0.5s : +0 / -30%
5. The curve is shown as a multiple of the Current Rating (In).
6. The end of the curve is determined by the interrupting rating of the circuit breaker.
7. Curves applies from -20 °C to +50°C ambient. Temperatures above +85 °C will cause over temperature trip.
8. This curve is for 50Hz ,60Hz applications.
9. These curves are comprehensive for series NRX NF&RF(IZMX16/40) circuit breakers including all frame sizes, ratings, and constructions.
The total clearing times shown include the response time for trip unit, the breaker opening and the interruption of the current.

43
IZMX Series Air Circuit Breakers
Tripping Characteristics

IZMX16…V(U)… PXR20/25 Maintenance Mode Curve


Arc-flash Reduction Maintenance Mode for IZMX16 up to 1600A
10000
9000
8000
7000
6000
5000
4000
3000

2000

1000
900
800
700
600
500
400
300

200

100
90
80
70
60
50
Timein Seconds

40
30

20

10
9
8
7
6
5
4
3
3.0
2

1
.9
.8
.7 1.0
.6 4.0
.5
.4 2.0
.3

.2

a
.1
.09
b
.08
.07
.06
5.0
.05
.04

.03

.02

.01
10

20

30

40

50
.1

.2

.3

.4

.5

.6

.7
.8
.9
1

7
8
9

RMS Current (kA)


Notes:
1. Nominal reduction values have a tolerance of ±20%.
2. The nominal ARMs trip time is 40ms with auxiliary power supply.
3. The Maintenance Mode feature must be ENABLED via setting Maintenance Mode switch to ON position
remote switch, or communications for these curves to apply.
Maintenance Mode is in use being shown by blue LED.
4. The PXR will light the Instantaneous LED for a Maintenance Mode Trip.
5. The end of the curve is determined by the interrupting rating of the circuit breaker.
6. Curves applies from -20 °C to +50°C ambient. Temperatures above +85 °C will cause over temperature trip.
7. This curve is for 50Hz ,60Hz applications.
8. These curves are comprehensive for series NRX NF(IZMX16) circuit breakers including all frame sizes, ratings, and constructions.
The total clearing times shown include the response time for trip unit, the breaker opening and the interruption of the current.

44
IZMX Series Air Circuit Breakers
Tripping Characteristics

IZMX40…V(U)… PXR20/25 Maintenance Mode Curve


Arc-flash Reduction Maintenance Mode for IZMX40 up to 4000A
10000
9000
8000
7000
6000
5000
4000
3000

2000

1000
900
800
700
600
500
400
300

200

100
90
80
70
60
50
Timein Seconds

40
30

20

10
9
8
7
6
5
4
3
12.0
2

1
.9
.8
.7
.6
.5 4.0
16.0
.4
8.0
.3

.2
a

.1
.09
.08
.07
20.0
.06
.05
b
.04

.03

.02

.01
.1

.2

.3

.4

.5

.6

.7
.8
.9

10

20

30

40

50
1

7
8
9

RMS Current (kA)


Notes:
1. Nominal reduction values have a tolerance of ±20%.
2. The nominal ARMs trip time is 40ms with auxiliary power supply.
3. The Maintenance Mode feature must be ENABLED via setting Maintenance Mode switch to ON position
remote switch, or communications for these curves to apply.
Maintenance Mode is in use being shown by blue LED.
4. The PXR will light the Instantaneous LED for a Maintenance Mode Trip.
5. The end of the curve is determined by the interrupting rating of the circuit breaker.
6. Curves applies from -20 °C to +50°C ambient. Temperatures above +85 °C will cause over temperature trip.
7. This curve is for 50Hz ,60Hz applications.
8. These curves are comprehensive for series NRX RF(IZMX40) circuit breakers including all frame sizes, ratings, and constructions.
The total clearing times shown include the response time for trip unit, the breaker opening and the interruption of the current.

45
IZMX Series Air Circuit Breakers
Tripping Characteristics

IZMX16(40)…V(U)… PXR20/25 Long Delay(L) Curves


L-Protection: I0.5t-Characteristic curve
10000
9000
8000
7000
6000
5000
4000

3000

2000
a
1000
900
800
700
600
500
400

300

200

100
90
80
70
60
50
Timein Seconds

40

30
24
20

15

10
9
8
7 7
6 c
5
4 4
3 b
10
2 2

1
4
1 0.5
.9 6
.8
.7
.6
.5
.4 f 0.5
0.4
.3
0.3
.2
d
e
.1
.09
.08 0.1
.07
.06
.05
.04

.03

.02

.01
100
10

20

30

40

50

60
70
80
90
.1

.2

.3

.4

.5

.6

.7
.8
.9
1

6
7
8
9

Current in Multiples of Long Delay Pickup (Ir)


Notes:
1. This curve shown as a multiple of the LONG PU setting (Ir). The actual pickup point occurs at 110% of the Ir, with ±5% tolerance.
2. SDPU = 1.5x to 10x of Ir, have 100% ± 10% tolerance. 3. LD Time = 0.5s to 24s, have 100% +0 / -30% tolerance.
4. SD Slope = I²T. The short pickup points have ±10% tolerance. time setting from 0.1s to 0.5s, with steps of 0.1s, except 0.2s.
tolerance is 100% +0 / -30% except 0.1s, has tolerance 100% +0 / -40%.
5. I²T slopes flattens out at 8x of Ir for top of band with FLAT time minimum value prevailing for bottom of band. For all curves the lower flat response
time value projected to I²T line will determine the other break point and shape of the curve.
6. If the short delay time is longer than long delay time, the short delay trip time will follow the long time setting.
7. If long delay thermal memory is enabled, trip times may be shorter than indicated in this chart.
8. Curves applies from -20°C to +50°C ambient. Temperatures above +85°C will cause over temperature trip. 9. This curve is for 50Hz, 60Hz applications.
10. These curves are comprehensive for series NRX NF&RF(IZMX16/40) circuit breakers including all frame sizes, ratings, and constructions.
The total clearing times shown include the response time for trip unit, the breaker opening and the interruption of the current.

46
IZMX Series Air Circuit Breakers
Tripping Characteristics

IZMX16(40)…V(U)… PXR20/25 Long Delay(L) Curves


L-Protection: I1t-Characteristic curve
10000
9000
8000
7000
6000
5000
4000
3000

2000

a
1000
900
800
700
600
500
400
300

200

100
90
80
70
60
50
Timein Seconds

40
30
24
20
15

10
9 c
8
7 7
6
5
4 4
b
3 1.5
1 10
2 0.5 2
3

1
.9 6
.8
.7
.6
.5
0.5
.4
0.4
.3
0.3
.2
d
e
.1
.09
.08 0.1
.07
.06
.05
.04
.03

.02

.01
100
10

20

30

40

50

60

70
80
90
.1

.2

.3

.4

.5

.6

.7
.8
.9
1

7
8
9

Current in Multiples of Long Delay Pickup (Ir)


Notes:
1. This curve shown as a multiple of the LONG PU setting(Ir). The actual pickup point occurs at 110% of the Ir, with ±5% tolerance.
2. SDPU = 1.5x to 10x of Ir, have 100% ± 10% tolerance.
3. LD Time = 0.5s to 24s, have 100% +0 / -30% tolerance.
4. SD Slope = I²T. The short pickup points have ±10% tolerance.
time setting from 0.1s to 0.5s, with steps of 0.1s, except 0.2s.
tolerance is 100% +0 / -30% except 0. 1s, has tolerance 100% +0 / -40%.
5. I²T slopes flattens out at 8x of Ir for top of band with FLAT time minimum value prevailing for bottom of band. For all curves the lower flat
response time value projected to I²T line will determine the other break point and shape of the curve.
6. If long delay thermal memory is enabled, trip times may be shorter than indicated in this chart.
7. Curves applies from -20°C to +50°C ambient. Temperatures above +85°C will cause over temperature trip.
8. This curve is for 50Hz, 60Hz applications.
9. These curves are comprehensive for series NRX NF&RF(IZMX16/40) circuit breakers including all frame sizes, ratings, and constructions.

47
IZMX Series Air Circuit Breakers
Tripping Characteristics

IZMX16(40)…V(U)… PXR20/25 Long Delay(L) Curves


L-Protection: I4t-Characteristic curve
100000
90000
80000
70000
60000
50000
40000
30000
a
20000

10000
9000
8000
7000
6000
5000
4000
3000

2000

1000
900
800
700
600
500
400
300
0.5
200
Timein Seconds

c
1
100
90
80
70
60
50
40
30
0.5 24
20 1.5
15

10
9
8 7
7
6
5 4
4 3
3
2
2 b
10
1 6
.9
.8
.7
.6
.5
.4
0.5
0.4
.3
0.3
.2

e d
.1
.09
.08 0.1
.07
.06
.05
.04
.03

.02

.01
100
40

50

60
70
80
90
10

20

30
.1

.2

.3

.4

.5

.6
.7
.8
.9

6
7
8
9
1

Current in Multiples of Long Delay Pickup (Ir)


Notes:
1. This curve shown as a multiple of the LONG PU setting(Ir). The actual pickup point occurs at 110% of the Ir, with ±5% tolerance.
2. SDPU = 1.5x to 10x of Ir, have 100% ± 10% tolerance.
3. LD Time = 0.5s to 24s, have 100% +0 / -30% tolerance.
4. SD Slope = I²T. The short pickup points have ±10% tolerance.
time setting from 0.1s to 0.5s, with steps of 0.1s, except 0.2s.
tolerance is 100% +0 / -30% except 0. 1s, has tolerance 100% +0 / -40%.
5. I²T slopes flattens out at 8x of Ir for top of band with FLAT time minimum value prevailing for bottom of band. For all curves the lower flat
response time value projected to I²T line will determine the other break point and shape of the curve.
6. If long delay thermal memory is enabled, trip times may be shorter than indicated in this chart.
7. Curves applies from -20°C to +50°C ambient. Temperatures above +85°C will cause over temperature trip.
8. This curve is for 50Hz, 60Hz applications.
9. These curves are comprehensive for series NRX NF&RF(IZMX16/40) circuit breakers including all frame sizes, ratings, and constructions.
The total clearing times shown include the response time for trip unit, the breaker opening and the interruption of the current.

48
IZMX Series Air Circuit Breakers
Electrical Accessories

IZMX-AS22, IZMX-OTS...
Signalling switch ON-OFF Tripped signalling contact Latch Check Switch Cell switch
IZMX-AS... IZMX-OTS... IZMX-LCS...(SR) IZMX-CS...
Rated breaking capacity
Inductive load
250 V AC A 10 10 10 10
125 V DC A 0.5 0.5 0.5 0.5
250 V DC A 0.25 0.25 0.25 0.25

IZMX-S...
Shunt releases Closing releases
IZMX- IZMX- IZMX- IZMX- IZMX- IZMX- IZMX- IZMX-
ST(S)24DC ST(S)48DC ST(S)110AD ST(S)230AD SR24DC SR48DC SR110AD SR230AD
Rated control voltage
AC 50/60 Hz Us V – – 110 - 127 208 - 240 – – 110 - 127 208 - 240
DC Us V 24 48 110 - 125 208 - 250 24 48 110 - 125 220 - 250
Power consumption
AC VA – – 5 5 – – (450 pick-up) (450 pick-up)
(540 pick-up) (500 pick-up)
DC W 5 5 5 5 (400 pick-up) (500 pick-up) (450 pick-up) (450 pick-up)
(500 pick-up) (530 pick-up) (540 pick-up) (515 pick-up)
Circuit-breaker ms 25 25 25 25 25 25 25 25
response time
at Us
Operating range
Drop-out voltage
AC operated, Drop- x Uc – – – – – – – –
50/60 Hz, out
pick-up
Pick-up voltage Pick-up x Uc 0.85 - 1.1 0.85 - 1.1 0.85 - 1.1 0.85 - 1.1 0.85 - 1.1 0.85 - 1.1 0.85 - 1.1 0.85 - 1.1

IZMX-U...
Undervoltage releases
IZMX-UVR24DC IZMX-UVR48DC IZMX-UVR110AD IZMX-UVR220AD IZMX-UVR400AC
Rated control voltage
AC 50/60 Hz Us V – – 110 - 127 208 - 240 –
DC Us V 24 48 110 - 125 208 - 250 380 - 415
Power consumption
AC VA – – 5 (500 pick-up) 5 (500 pick-up) 5 (500 pick-up)
DC W 5 (500 pick-up) 5 (500 pick-up) 5 (500 pick-up) 5 (500 pick-up) –
Circuit-breaker ms 50 50 50 50 50
response time
at Us
Operating range
Drop-out voltage
AC operated, Drop- x Uc 0.35 - 0.7 0.35 - 0.7 0.35 - 0.7 0.35 - 0.7 0.35 - 0.7
50/60 Hz, out
pick-up
Pick-up voltage Pick-up x Uc 0.85 - 1.1 0.85 - 1.1 0.85 - 1.1 0.85 - 1.1 0.85 - 1.1

49
IZMX Series Air Circuit Breakers
Motor Operators

IZMX-M16...
Motor operators
IZMX-M16-24DC IZMX-M16-48DC IZMX-M16-110AD IZMX-M16-230AD
Rated control voltage Us V 24 V DC 48 V DC 110 - 127 V AC 50/60 Hz 220 - 240 V AC 50/60 Hz
110 - 125 V DC 220 - 250 V DC
Necessary time required for 4s 3s 3s 4s
charging the spring-operated
stored energy mechanism
at 1 × Us
Rated operational current In A 6A 3A 2 A AC 50/60 Hz 1 A AC 50/60 Hz
1 A DC 1 A DC

Starting current A 20 A 15 A 6 A AC 50/60 Hz 10 A AC 50/60 Hz


5 A DC 10 A DC

Power consumption 160 W 150 W 280 VA AC 50/60 Hz 280 VA AC 50/60 Hz


150 W DC 280 W DC

IZMX-M40...
Motor operators
IZMX-M40-24DC IZMX-M40-48DC IZMX-M40-110AD IZMX-M40-230AD
Rated control voltage Us V 24 V DC 48 V DC 110 - 127 V AC 50/60 Hz 220 - 240 V AC 50/60 Hz
110 - 125 V DC 220 - 250 V DC

ENecessary time required for 6s 6s 6s 6s


charging the spring-operated
stored energy mechanism
at 1 × Us DC

Rated operational current In A 7 A DC 3 A DC 3 A AC 50/60 Hz 1.5 A AC 50/60 Hz


2 A DC 1 A DC

Starting current A 25 A DC 14 A DC 9 A AC 50/60 Hz 5 A AC 50/60 Hz


5 A DC 4 A DC

Power consumption 200 W 175 W 425 VA AC 50/60 Hz 400 VA AC 50/60 Hz


275 W DC 250 W DC

50
IZMX Series Air Circuit Breakers
Communication Modules

Technical Data
IZMX-PCAM-2 IZMX-MCAM-2 IZMX-ECAM-2
General
Dimensions (W x H x D) mm 24 x 105 x 80 24 x 105 x 80 24 x 105 x 80
Mounting 35mm DIN rail 35mm DIN rail 35mm DIN rail
Protection type IP20 IP20 IP20
Power supply V DC 24 V DC 24 V DC 24 V DC
LED display Status Status Status
SF Transmit
BF Receive
Network
Ethernet – – RJ45, socket
PROFIBUS SUB-D 9 pole, socket – –
Modbus – Plug-in screw terminals –
Function Slave Slave TCP/IP user
Interfaces RS485 RS485 Ethernet
Protocol PROFIBUS DP Modbus-RTU Modbus TCP, http(s), SMTP
Baud Rates automatic search up to 12 MBit/s 1200/4800/9600/19200 Bit/s, automatic search
adjustable via Digitrip up to 100 MBit/s
Bus terminating resistors In plug as required 120 external –
Bus addresses 1 - 127, can be set via Digitrip 1 - 247, can be set via Digitrip IP, can be set via Digitrip
Maximum distance 2.4 km 1.2 km 100 m
Supported functions Cyclical data transfer Function: Webserver on board
03 = read register
04 = read word variables
08 = connection test
16 = write register

51
IZMX Series Air Circuit Breakers
Temperature and Altitude Derating Factors

Temperature Derating
IZMX16
Rated Current 630A 800A 1000A 1250A 1600A
40°C [A] 630 800 1000 1250 1600
50°C [A] 630 800 1000 1250 1500
60°C [A] 630 800 1000 1250 1400
70°C [A] 630 800 1000 1250 1350

IZMX40
Rated Current 800A 1000A 1250A 1600A 2000A 2500A 3200A 4000A
40°C [A] 800 1000 1250 1600 2000 2500 3200 4000
50°C [A] 800 1000 1250 1600 2000 2500 3200 4000 1)
60°C [A] 800 1000 1250 1600 2000 2500 3200 3650 1)
70°C [A] 800 1000 1250 1600 2000 2280 3200 3500 1)
1)
Rated continuous current stated applies only with 4 × 120 × 10mm vertical terminal rails painted black.
The values are reduced by 100A each with 4 × 100 × 10mm

Altitude Derating Factors


Altitude Voltage Current
[m] Correction Correction
2000 1.000 1.000
2150 0.989 0.998
2300 0.976 0.995
2450 0.963 0.993
2600 0.950 0.990
2750 0.933 0.987
2900 0.917 0.983
3050 0.900 0.980
3200 0.883 0.977
3350 0.867 0.973
3500 0.850 0.970
3650 0.833 0.967
3800 0.817 0.963
3950 0.800 0.960
5000 0.700 0.940
Notes
Series NRX (IZMX) circuit breakers can be applied at their full voltage
and current ratings up to a maximum altitude of 2000 meters above sea
level. When installed at higher altitudes, the ratings are subject to
correction factors. Short circuit current is not affected as long as the
voltage is rated in accordance with the table.

52
IZMX Series Air Circuit Breakers
X16 Drawout Dimensions

Three-pole Drawout Cassette - Rear/Top Views in. Inches (mm)

M8 x 1.25 Tapped
0.35-in Max. Thread
Depth from Copper
Surface

Copper
6 Places Surface

Alternate Mounting Locations.


Must Use Reduced Head Height
Hardware in These Locations
(Minimum of 4 Mounting
Locations are Suggested.)

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

53
IZMX Series Air Circuit Breakers
X16 Drawout Dimensions

Three-pole Drawout Cassette - Side Views CONNECTED and TEST Positions in Inches (mm).

90° Travel
(10° Free Travel)
(80° Charge Stroke)

CONNECTED Position

TEST Position

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

54
IZMX Series Air Circuit Breakers
X16 Drawout Dimensions

Three-pole Drawout Cassette - Side Views DISCONNECTED and WITHDRAWN Positions in Inches (mm).

DISCONNECTED Position

WITHDRAWN Position

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

55
IZMX Series Air Circuit Breakers
X16 Drawout Dimensions

Three-pole Drawout Cassette—Top/Side Views with Horizontal Universal Bus Adapters in Inches (mm).

Recommended
Barrier

Recommended
Barrier

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

56
IZMX Series Air Circuit Breakers
X16 Drawout Dimensions

Three-pole Drawout Cassette - Top/Side Views with Vertical Universal Bus Adapters in Inches (mm).
Recommended
Barrier

Recommended
Barrier

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

57
IZMX Series Air Circuit Breakers
X16 Drawout Dimensions

Three-pole Drawout Cassette—Front View Door and Cassette Cutout Details in Inches (mm).
8.39 12 × Ø 0.19
[213.1] [4.8]
1.46 Cassette
[37.1] Sheet Metal

3.25
[82.5]

13.43
[341]
4.00 12.22
[101.6] [310.4]

3.25
[82.5]
0.01
[0.2]

0.86
[21.8]
2.72 4.00 2.20 0.78
[69.2] [101.6] [55.8] [19.9]
DOOR CUT OUT OUTLINE

9.00
(228,6)
4.50
(114,3) Ø 0.38
(9,7)

3.75
(95,3)

9.86 7.50
(250,5) (190,5)

8.75
(222,3)

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

58
IZMX Series Air Circuit Breakers
X16 Drawout Dimensions

Four-pole Drawout Cassette—Rear/Top Views in Inches (mm).

M8 x 1.25
Tapped
0.35 in Max.
Thread Depth
from Copper
Surface

Copper
Surface
8 Places

8 x Ø0.32 (8.1)
Alternate Mounting Locations.
Must Use Reduced Head Height
Hardware at These Locations.
(Minimum of 4 Mounting
Locations are Suggested.)

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

59
IZMX Series Air Circuit Breakers
X16 Drawout Dimensions

Four-pole Drawout Cassette—Top/Side Views with Horizontal Universal Bus Adapters in Inches (mm).

Recommended
Barrier

Recommended
Barrier

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

60
IZMX Series Air Circuit Breakers
X16 Drawout Dimensions

Four-pole Drawout Cassette—Top/Side Views with Vertical Universal Bus Adapters in Inches (mm).

Recommended
Barrier

Recommended
Barrier

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

61
IZMX Series Air Circuit Breakers
X16 Drawout Dimensions

Four-Pole Drawout Cassette—Side Views CONNECTED and TEST Positions in Inches (mm).

90° Travel
(10° Free Travel)
(80° Charge
Stroke)

CONNECTED Position

TEST Position

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

62
IZMX Series Air Circuit Breakers
X16 Drawout Dimensions

Four-pole Drawout Cassette - Side Views DISCONNECTED and WITHDRAWN Positions in Inches and (mm).

DISCONNECTED Position

WITHDRAWN Position

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

63
IZMX Series Air Circuit Breakers
X16 Drawout Dimensions

Four-pole Drawout Cassette—Front View Door and Cassette Cutout Details in Inches (mm).
12 × Ø 0.19
8.39 [4.8]
1.46 [213.1]
Cassette
[37.1] Sheet Metal

Ø 0.38
[9.7]

3.25
[82.5]

4.00 13.43
[101.6] [341]
12.22
[310.4]

3.25
[82.5]
0.01
[0.2]

0.86
[21.8]
2.72 4.00 2.20 0.78
[69.2] [101.6] [55.8] [19.9]
DOOR CUT OUT OUTLINE

11.75
(298,5)
5.88
(149,2)

Ø 0.38
(9,7)

3.75
(95,6)

9.86 7.50
(250,5) (190,5)

11.50 4P - Front View Cassette Cut Out Detail


(292,1)

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

64
IZMX Series Air Circuit Breakers
X16 Fixed Dimensions

Three-pole Fixed Breaker Overall Views and Dimensions in Inches (mm) (UL 800–1200 A/IEC 630–1600 A).

Arc Exhaust Area


Do Not Obstruct

Top View

Front View

Side View

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

65
IZMX Series Air Circuit Breakers
X16 Fixed Dimensions

Three-pole Fixed Breaker Overall Views and Dimensions in Inches (mm) (UL 800–1200 A/IEC 630–1600 A).

M8 x 1.25
Tapped
0.35” in
Max. Thread
Depth from
Copper Surface

Copper
Surface
8 Places

Rear View

Side View with Rear Barriers

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

66
IZMX Series Air Circuit Breakers
X16 Fixed Dimensions

Three-pole Fixed Breaker Foot Mount Dimensions in Inches (mm) (UL 800–1200 A/IEC 630–1600 A).

90° Travel
(10° Free Travel)
(80° Charge
Stroke)

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

67
IZMX Series Air Circuit Breakers
X16 Fixed Dimensions

Three-pole Fixed Breaker Surface Mount, Cable Connect Dimensions in Inches (mm)
(UL 800–1200 A/IEC 630–1600 A, 800 MCM, 750 MCM, and 500 MCM Lugs).

90° Travel
(10° Free Travel)
(80° Charge
Stroke)

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

68
IZMX Series Air Circuit Breakers
X16 Fixed Dimensions

Three-pole Fixed Breaker Parallel Bus Mounting Dimensions in Inches (mm) (UL 800–1200 A/IEC 630–1600 A).
Arc Exhaust Area
Do Not Obstruct

Bus
Mounting
Plane

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

69
IZMX Series Air Circuit Breakers
X16 Fixed Dimensions

Three-pole Fixed Breaker Vertical Universal Bus Adapters Dimensions in Inches (mm)
(UL 800–1200 A/IEC 630–1600 A).

Note: Views shown with mounting feet option installed.

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

70
IZMX Series Air Circuit Breakers
X16 Fixed Dimensions

Three-pole Fixed Breaker Horizontal Universal Bus Adapter Dimensions in Inches (mm)
(UL 800–1200 A/IEC 630–1600 A).

Note: Views shown with mounting feet option installed.

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

71
IZMX Series Air Circuit Breakers
X16 Fixed Dimensions

Three-pole Fixed Breaker Accessory Tray Installation and Removal Clearance Dimensions in Inches (mm).

Right
Accessory
Tray

Note: A minimum of 2-inches (50.8 mm) of side clearance is required.

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

72
IZMX Series Air Circuit Breakers
X16 Fixed Dimensions

Three-pole Fixed Breaker—Front View Door Cutout Detail Dimensions in Inches (mm).

8.39
(213,1)

2 x 4.00
(101,6)

2 x 10.50
(266,7)

10.38
2 x 4.00 (263,5)
(101,6)

12 x Ø0.188
(4,78) 2 x 9.45
(101,6)

Door Cutout

5.16
(131,1)

12.00
(304,8)

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

73
IZMX Series Air Circuit Breakers
X16 Fixed Dimensions

Four-pole Fixed Breaker Overall Views and Dimensions in Inches (mm) (UL 800–1200 A/IEC 630–1600 A).

Arc Exhaust Area


Do Not Obstruct

Top View

Front View

Side View

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

74
IZMX Series Air Circuit Breakers
X16 Fixed Dimensions

Four-pole Fixed Breaker Overall Views and Dimensions in Inches (mm) (UL 800–1200 A/IEC 630–1600 A).

M8 x 1.25
Tapped
0.35 in.
Max. Thread
Depth from
Copper Surface

See
Detail
A
Copper
Surface
6 Places

Rear View

Side View with Rear Barriers

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

75
IZMX Series Air Circuit Breakers
X16 Fixed Dimensions

Four-pole Fixed Breaker Foot Mount Dimensions in Inches (mm) (UL 800–1200 A/IEC 630–1600 A).
Arc
Hood

90° Travel
(10° Free Travel)
(80° Charge
Stroke)

Bus
Mounting
Plane

Charging
Handle

Bottom Mounting Surface

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

76
IZMX Series Air Circuit Breakers
X16 Fixed Dimensions

Four-pole Fixed Breaker Surface Mount, Cable Connect Dimensions in Inches (mm)
(UL 800–1200 A/IEC 630–1600 A, 800 MCM, 750 MCM, and 600 MCM Lugs).
6 x M8 x 1.25
(recessed)

Arc Hood

6 x Ø0.217
(5.5)
Mounting
Holes

Recommended Barriers

4.37
(110,9)

Shroud
9.83
(249,7)

90° Travel
(10° Free
Travel)
(80° Charge
Stroke)

Charging 2.90
Handle (73,7)

2 x 5.24
(133,1)
15.99
(406,3)

11.00
(279,4)

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

77
IZMX Series Air Circuit Breakers
X16 Fixed Dimensions

Four-pole Fixed Breaker Parallel Bus Mounting Dimensions in Inches (mm) (UL 800–1200 A/IEC 630–1600 A).

Arc Exhaust Area


Do Not Obstruct

Bus
Mounting
Plane

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

78
IZMX Series Air Circuit Breakers
X16 Fixed Dimensions

Four-pole Fixed Breaker Universal Bus Adapters Vertical Dimensions in Inches (mm)
(UL 800–1200 A/IEC 630–1600 A) .

Note: Versions shown with mounting feet option installed.

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

79
IZMX Series Air Circuit Breakers
X16 Fixed Dimensions

Four-pole Fixed Breaker Universal Bus Adapters Horizontal Dimensions in Inches (mm)
(UL 800–1200 A/IEC 630–1600 A).

Note: Views shown with mounting feet option installed.

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

80
IZMX Series Air Circuit Breakers
X16 Fixed Dimensions

Four-pole Fixed Breaker Accessory Tray Installation and Removal Clearance Dimensions in Inches (mm).

Note: A minimum of 2-inches (50.8 mm) of side clearance is required.

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

81
IZMX Series Air Circuit Breakers
X16 Fixed Dimensions

Four-pole Fixed Breaker—Front View Door Cutout Detail Dimensions in Inches (mm).
8.39
(213.1)
2x4.00
(101.6)

2x10.50
(266.7)

2x4.00 10.38
(101.6) (263.5)

12xø0.188
(4.78) 2x9.45
(101.6)

Door Cutout

5.16
(131.1)

12.00
(304.8)

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

82
IZMX Series Air Circuit Breakers
X40 Drawout Dimensions

Three-pole Drawout Cassette - Rear/Bottom Views in Inches (mm).

MOUNTING LOCATIONS
FOR BACK INSTALLATION

6 X MOUNTING HOLES FOR BOTTOM INSTALLATION


MUST USE REDUCED HEAD HEIGHT HARDWARE AT
THESE LOCATIONS

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

83
IZMX Series Air Circuit Breakers
X40 Drawout Dimensions

Three-pole Drawout Cassette - Side Views CONNECTED and TEST Positions in Inches (mm).

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

84
IZMX Series Air Circuit Breakers
X40 Drawout Dimensions

Three-pole Drawout Cassette - Side Views DISCONNECTED and WITHDRAWN Positions in Inches (mm).

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

85
IZMX Series Air Circuit Breakers
X40 Drawout Dimensions

Three-pole Drawout Cassette - Top/Side Views with 800-3200 A Horizontal Bus Adapters in Inches (mm).

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

86
IZMX Series Air Circuit Breakers
X40 Drawout Dimensions

Three-pole Drawout Cassette - Top/Side Views with 800-3200 A Vertical Bus Adapters in Inches (mm).

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

87
IZMX Series Air Circuit Breakers
X40 Drawout Dimensions

Three-pole Drawout Cassette - Top/Side Views with 4000 A Horizontal Bus Adapters in Inches (mm).

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

88
IZMX Series Air Circuit Breakers
X40 Drawout Dimensions

Three-pole Drawout Cassette - Top/Side Views with 4000 A Vertical Bus Adapters in Inches (mm).

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

89
IZMX Series Air Circuit Breakers
X40 Drawout Dimensions

Three-pole Drawout Cassette - Front View Door Cutout Details in Inches (mm).

EXTERNAL SIDE OF CASSETTE


SHEET METAL

CASSETTE EXTERNAL SIDE OF CASSETTE


SHEET METAL SHEET METAL

REFER TO THE UPPER DRAWING


ON PAGE 83 FOR MOUNTING
HOLES ON CASSETTE.
FOR BACK INSTALLATION ONLY

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

90
IZMX Series Air Circuit Breakers
X40 Drawout Dimensions

Four-pole Drawout Cassette - Rear/Bottom Views in Inches (mm).

MOUNTING LOCATIONS
FOR BACK INSTALLATION

6 X MOUNTING HOLES FOR BOTTOM


INSTALLATION MUST USE REDUCED HEAD
HEIGHT HARDWARE AT THESE LOCATIONS

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

91
IZMX Series Air Circuit Breakers
X40 Drawout Dimensions

Four-pole Drawout Cassette - Side Views DISCONNECTED and TEST Positions in Inches and (mm).

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

92
IZMX Series Air Circuit Breakers
X40 Drawout Dimensions

Four-pole Drawout Cassette - Side Views DISCONNECTED and WITHDRAWN Positions in Inches and (mm).

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

93
IZMX Series Air Circuit Breakers
X40 Drawout Dimensions

Four-pole Drawout Cassette - Top/Side Views with 800-3200 A Horizontal Bus Adapters in Inches (mm).

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

94
IZMX Series Air Circuit Breakers
X40 Drawout Dimensions

Four-pole Drawout Cassette-Top/Side Views with 800-3200 A Vertical Bus Adapters in Inches (mm).

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

95
IZMX Series Air Circuit Breakers
X40 Drawout Dimensions

Four-pole Drawout Cassette- Top/Side Views with 4000 A Horizontal Bus Adapters in Inches (mm).

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

96
IZMX Series Air Circuit Breakers
X40 Drawout Dimensions

Four-pole Drawout Cassette - Top/Side Views with 4000 A Vertical Bus Adapters in Inches (mm).

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

97
IZMX Series Air Circuit Breakers
X40 Drawout Dimensions

Four-pole Drawout Cassette - Front View Door Cutout Details in Inches (mm).

EXTERNAL SIDE OF CASSETTE


SHEET METAL

EXTERNAL SIDE OF CASSETTE


SHEET METAL
CASSETTE
SHEET METAL

REFER TO THE UPPER DRAWING


ON PAGE 91 FOR MOUNTING
HOLES ON CASSETTE.
FOR BACK INSTALLATION ONLY

2D DWG and 3D STP drawings are available from www.eaton.com/izmx-ea

98
IZMX Series Air Circuit Breakers
Minimum Clearances

Recommended safety clearances


The following information about safety distances is intended to provide a guideline for the installation of circuit-breakers in an enclosure.

100

a Cell switch (optional)


a

a
b Locking facilities (optional)
a c Ventilation openings (do not cover!)

b b

Enclosure To insulated surface To grounded With cell switch or locking


clearance metal surface facilities
mm mm mm
Withdrawable a 0 0 0
b 25 25 25/75
Fixed a 150 250 –
b 30 70 –

Recommended enclosure clearance and ventilation


The illustration shows a typical enclosure.
The table below lists the associated minimum distances between enclosures and ventilation openings.
This information is intended as a guideline for constructing a suitable circuit-breaker enclosure. Ensure the integration complies with IEC 61439.

d
c Width of cassette + 75 mm
d 550 mm
e 450 mm (front control panel bay)

d
Ventilation
holes
160 cm² (800 - 3200 A)
320 cm² (4000 A) } Top and bottom

d Top or rear vent


e Rear or lower vent

99
Eaton is a power management company with approximately
97,000 employees. The company provides energy-efficient
solutions that help our customers effectively manage electrical,
hydraulic and mechanical power more efficiently, safely and
sustainably. Eaton sells products to customers in more than 175
countries. For more information, visit www.eaton.com.
For IZMX product page, Visit www.eaton.com/izmx-ea.

Eaton Corporation
Asia Pacific Headquarter
No.3, Lane 280, Linhong Road,
Changning District,
Shanghai 200335
Tel: 86-21-52000099
Fax: 86-21-52000200
Eaton is a registered trademark
© 2016 Eaton Corporation of Eaton Corporation.
All Rights Reserved
Printed in China All trademarks are property of their
IZMX-APAC-EN(11-2016) respective owners.

You might also like