You are on page 1of 1

Copper/Aluminium

Conductor Screen

XLPE Insulation
Insulation Screen
PVC Outer Sheath Aluminium Wire PVC Separation Binder Tape Metalic Screen
Sheath
DIMENSIONAL
Nominal Cross Sectional mm² 16 25 35 50 70 95 120 150 185 240 300 400 500 630
Area

Conductor Dia. (Approx.) mm 4.7 5.9 7.0 8.1 9.7 11.4 12.8 14.3 16.0 18.4 20.6 23.3 26.3 30.3

Nominal Insulation mm 3.4


Thickness

Nominal Separation mm 1.2 1.3 1.4


Thickness

Separation Sheath Dia. mm 18.1 19.3 20.6 21.7 23.5 25.2 26.6 28.1 29.8 32.2 34.4 37.1 40.3 45.1

Nominal of Hard-Drawn mm 1.6 2.0 2.5 2.5


Al Wire

Nominal Outer- Sheath mm 1.8 1.9 2.0 2.1 2.2 2.4 2.5 2.6

Approx. Overall Dia. mm 25.0 26.5 27.5 28.5 30.5 32.5 34.0 36.5 38.0 41.0 43.0 46.0 50.5 55.5

Cu 820 970 1110 1270 1560 1880 2180 2600 3010 3700 4340 5280 6550 8200
Cable Net. Weight kg/km
(Approx.)
Al - 810 890 970 1130 1280 1420 1670 1850 2150 2420 2820 3450 4190

ELECTRICAL DATA
Nominal Cross Sectional mm² 16 25 35 50 70 95 120 150 185 240 300 400 500 630
Area

Cu 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 0.0366 0.0283
Max. Conductor Resistance Ω/km
DC at 20°C
Al - 1.2 0.868 0.641 0.443 0.32 0.253 0.206 0.164 0.125 0.10 0.0778 0.0605 0.0469

Cu 1.47 0.927 0.668 0.494 0.342 0.247 0.196 0.159 0.127 0.0976 0.0785 0.0624 0.0499 0.0402
Max. Conductor Resistance
50Hz at 90°C Ω/km
Al - 1.54 1.11 0.822 0.568 0.411 0.325 0.265 0.211 0.161 0.129 0.101 0.0796 0.0628

Capacitance µF/km Cu 0.17 0.19 0.22 0.24 0.27 0.31 0.33 0.36 0.40 0.44 0.48 0.53 0.59 0.68

Reactance at 50Hz Ω/km Cu 0.158 0.147 0.139 0.132 0.125 0.118 0.113 0.111 0.107 0.102 0.0991 0.0957 0.0942 0.0921

Cu 115 150 180 215 270 325 375 430 495 585 665 770 890 1030
Current Rating in Air A
at 40°C
Al - 115 140 165 210 255 290 335 385 455 520 610 710 830

Cu 115 145 175 205 255 305 345 390 435 505 570 645 725 815
Current Rating in
Ground at 25°C A
Al - 115 135 160 195 235 270 300 340 395 445 510 580 660

Cu 2.41 3.72 5.18 7.36 10.2 13.8 17.4 21.8 26.8 34.7 43.4 57.7 72.1 90.8
Short Circuit Current
for 1 sec. kA
Al - 2.48 3.45 4.89 6.80 9.19 11.5 14.4 17.7 22.9 28.6 38.1 47.6 59.8

All of the above information, including drawings, illustrations and graphic designs, reflects our present understanding and is to the best of our knowledge and belief correct and
reliable. Users, however, should independently evaluate the suitability of each product for the desired application. Under no circumstances does this constitute an assurance of
any particular quality or performance. Such an assurance is only provided in the context of our product specifications or explicit contractual arrangements. Our liability for these
products is set forth in our standard terms and conditions of sale.