You are on page 1of 39

Test Report issued under the responsibility of:

TEST REPORT
IEC 61727
Photovoltaic (PV) systems –
Characteristics of the utility interface

Report Number. .............................. : 191120145GZU-001


Date of issue ................................... : 28 Nov 2019
Total number of pages ................... 39 Pages

Name of Testing Laboratory Intertek Testing Services Shenzhen Ltd. Guangzhou Branch
preparing the Report ..................... : Block E, No.7-2 Guang Dong Software Science Park, Caipin
Road, Guangzhou Science City, GETDD, Guangzhou, China
Applicant’s name ........................... : Shenzhen Growatt New Energy Technology CO.,Ltd
Address ........................................... : 1st East & 3rd Floor of Building A, Building B, Jiayu Industrial
Park, #28, GuangHui Road, LongTeng Community, Shiyan
Street, Baoan District, Shenzhen, P.R.China
Test specification:
Standard ......................................... : IEC 61727:2004
Test procedure ............................... : Type approval
Non-standard test method ............ : N/A
Test Report Form No. .................... : IEC61727B
Test Report Form(s) Originator .... : TÜV SÜD Product Service GmbH
Master TRF ..................................... : Dated 2017-11-03
Copyright © 2017 IEC System of Conformity Assessment Schemes for Electrotechnical
Equipment and Components (IECEE System). All rights reserved.
This publication may be reproduced in whole or in part for non-commercial purposes as long as the IECEE is acknowledged as
copyright owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting
from the reader's interpretation of the reproduced material due to its placement and context.
If this Test Report Form is used by non-IECEE members, the IECEE/IEC logo and the reference to the
CB Scheme procedure shall be removed.
This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory
and appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02.
General disclaimer:
The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing CB Testing
Laboratory. The authenticity of this Test Report and its contents can be verified by contacting the NCB,
responsible for this Test Report.
Page 2 of 39 Report No. 191120145GZU-001

Test item description ....................... : PV Grid inverter


Trade Mark ........................................ : Growatt
Manufacturer ..................................... : Same as applicant
Model/Type reference ...................... : MAC 15KTL3-XL, MAC 20KTL3-XL, MAC 22KTL3-XL,
MAC 25KTL3-XL, MAC 30KTL3-XL, MAC 36KTL3-XL,
MAC 30KTL3-X LV, MAC 40KTL3-X LV, MAC 50KTL3-X LV,
MAC 60KTL3-X LV, MAC 50KTL3-X MV, MAC 60KTL3-X MV,
MAC 66KTL3-X MV, MAC 70KTL3-X MV
Ratings .............................................. : Model MAC MAC MAC MAC
15KTL3- 20KTL3- 22KTL3- 25KTL3-
XL XL XL XL
Max.PV
1100Vdc
voltage
PV voltage
200V – 1000Vdc
range
Max.input
52A/52A/52A
current
PV Isc 55A*3
Nominal
output 3W/N/PE, 127/220Vac
voltage
Nominal
output 50/60Hz
Frequency
Max.output
43.6A 58.3A 64.0A 73.0A
current
Max.output
15.0KW 20.0KW 22.0KW 25.0KW
power
Max.apparent
16.6KVA 22.2KVA 24.4KVA 27.8KVA
power
Power factor
0.8Leading – 0.8 lagging
range
Safety level Class I
Ingress
IP 65
Protection
Operation
Ambient -25℃ - +60℃
Temperature
Model MAC 30KTL3-XL MAC 36KTL3-XL
Max.PV 1100Vdc

TRF No. IEC 61727B


Page 3 of 39 Report No. 191120145GZU-001

voltage
PV voltage
200V – 1000Vdc
range
Max.input
52A/52A/52A
current
PV Isc 55A*3
Nominal
output 3W/N/PE, 127/220Vac
voltage
Nominal
output 50/60Hz
Frequency
Max.output
87.4A 94.5A
current
Max.output
30.0KW 36.0KW
power
Max.apparent
33.3KVA 36.0KVA
power
Power factor
0.8Leading – 0.8 lagging
range
Safety level Class I
Ingress
IP 65
Protection
Operation
Ambient -25℃ - +60℃
Temperature
Model MAC MAC MAC MAC
50KTL3-X 60KTL3- 66KTL3- 70KTL3-
MV X MV X MV X MV
Max.PV
1100Vdc
voltage
PV voltage
200V – 1000Vdc
range
Max.input 52A/39A
current 52A*3
/39A
PV Isc 55A*3
Nominal
output 3W/PE, 277/480Vac
voltage
Nominal 50/60Hz

TRF No. IEC 61727B


Page 4 of 39 Report No. 191120145GZU-001

output
Frequency
Max.output
66.9A 80.2A 88.2A 93.6A
current
Max.output
50.0KW 60.0KW 66.0KW 70.0KW
power
Max.apparent
55.5KVA 66.6KVA 73.3KVA 77.7KVA
power
Power factor
0.8Leading – 0.8 lagging
range
Safety level Class I
Ingress
IP 65
Protection
Operation
Ambient -25℃ - +60℃
Temperature
Model MAC MAC MAC MAC
30KTL3- 40KTL3- 50KTL3-X 60KTL3-
X LV X LV LV X LV
Max.PV
1100Vdc
voltage
PV voltage
200V – 1000Vdc
range
Max.input 39A*2 /
39A*3 52/39/39A 52A*3
current 26A
PV Isc 45A*3 55A*3
Nominal
output 3W/N/PE, 230/400Vac
voltage
Nominal
output 50/60Hz
Frequency
Max.output
48.3A 64.4A 80.5A 96.6A
current
Max.output
30.0KW 40.0KW 50.0KW 60.0KW
power
Max.apparent
33.3KVA 44.4KVA 55.5KVA 66.6KVA
power
Power factor
0.8Leading – 0.8 lagging
range

TRF No. IEC 61727B


Page 5 of 39 Report No. 191120145GZU-001

Safety level Class I


Ingress
IP 65
Protection
Operation
Ambient -25℃ - +60℃
Temperature
Software
TK1.0
version

TRF No. IEC 61727B


Page 6 of 39 Report No. 191120145GZU-001

Responsible Testing Laboratory (as applicable), testing procedure and testing location(s):

CB Testing Laboratory: Intertek Testing Services Shenzhen Ltd. Guangzhou


Branch
Testing location/ address ............................. : Block E, No.7-2 Guang Dong Software Science Park,
Caipin Road, Guangzhou Science City, GETDD,
Guangzhou, China
Associated CB Testing Laboratory: N/A
Testing location/ address ............................. : N/A

Tested by (name, function, signature) ........ : Jason Fu


Technical Team
Leader
Approved by (name, function, signature) ... : Tommy Zhong
Technical Manager

Testing procedure: TMP/CTF Stage 1: N/A


Testing location/ address ............................. : N/A

Tested by (name, function, signature) ........ : N/A


Approved by (name, function, signature) ... : N/A

Testing procedure: WMT/CTF Stage 2: N/A


Testing location/ address ............................. : N/A

Tested by (name + signature) ...................... : N/A


Witnessed by (name, function, signature) . : N/A
Approved by (name, function, signature) ... : N/A

Testing procedure: N/A


SMT/CTF Stage 3 or 4:
Testing location/ address ............................. : N/A

Tested by (name, function, signature) ........ : N/A


Witnessed by (name, function, signature) . : N/A
Approved by (name, function, signature) ... : N/A
Supervised by (name, function, signature) : N/A

TRF No. IEC 61727B


Page 7 of 39 Report No. 191120145GZU-001

List of Attachments (including a total number of pages in each attachment):


Appendix 1: photos (6 pages)

Summary of testing:

Tests performed (name of test and test Testing location:


clause): Intertek Testing Services Shenzhen Ltd.
All applicable tests Guangzhou Branch
Block E, No.7-2 Guang Dong Software Science
Park, Caipin Road, Guangzhou Science City,
GETDD, Guangzhou, China

Summary of compliance with National Differences:


List of countries addressed
N/A

The product fulfils the requirements of IEC 61727:2004

TRF No. IEC 61727B


Page 8 of 39 Report No. 191120145GZU-001

Copy of marking plate:


The artwork below may be only a draft. The use of certification marks on a product must be
authorized by the respective NCBs that own these marks.

TRF No. IEC 61727B


Page 9 of 39 Report No. 191120145GZU-001

Note:
1. The above markings are the minimum requirements required by the safety standard. For the
final production samples, the additional markings which do not give rise to misunderstanding
may be added.
2. Label is attached on the side surface of enclosure and visible after installation.
3. Other labels are same as model above, except the rating and model name.

TRF No. IEC 61727B


Page 10 of 39 Report No. 191120145GZU-001

Test item particulars...................................................:


Classification of installation and use.......................: Fixed and outdoor use
Supply Connection .....................................................: Permanent connection
.......................................................................................:
Possible test case verdicts:
- test case does not apply to the test object ........... : N/A
- test object does meet the requirement.................. : P (Pass)
- test object does not meet the requirement ........... : F (Fail)
Testing.......................................................................... :
Date of receipt of test item ........................................ : 20 Nov 2019
Date (s) of performance of tests ............................... : 20 Nov 2019 to 27 Nov 2019

General remarks:
"(See Enclosure #)" refers to additional information appended to the report.
"(See appended table)" refers to a table appended to the report.

Throughout this report a comma / point is used as the decimal separator.

This report is based on and superseded original report No.190820065GZU-001, dated 03 Sep 2019
due to below modification /addition
1, Add new models MAC 15KTL3-XL, MAC 20KTL3-XL, MAC 22KTL3-XL, MAC 25KTL3-XL, MAC
30KTL3-XL, MAC 36KTL3-XL, MAC 30KTL3-X LV; All models are identical, except the
output power derating in software.
2, Change the Max input current and update the marking plates
After evaluation, clauses 4.3,4.4, 4.6,4.7, 5.2.1 are re-tested on new models.
This report shall be used together with the report 191120145GZU-002.
Manufacturer’s Declaration per sub-clause 4.2.5 of IECEE 02:
The application for obtaining a CB Test Certificate Yes
includes more than one factory location and a Not applicable
declaration from the Manufacturer stating that the
sample(s) submitted for evaluation is (are)
representative of the products from each factory has
been provided ............................................................... :
When differences exist; they shall be identified in the General product information section.
Name and address of factory (ies) .......................... : Shenzhen Growatt New Energy Technology
CO.,Ltd
1st East & 3rd Floor of Building A, Building B, Jiayu
Industrial Park, #28, GuangHui Road, LongTeng
Community, Shiyan Street, Baoan District,
Shenzhen, P.R.China

TRF No. IEC 61727B


Page 11 of 39 Report No. 191120145GZU-001

General product information:


The unit is a three-phase PV Grid inverter, it can convert the high PV voltage to Grid voltage and
feed into Grid network.
The unit is providing EMC filtering at the PV side and AC side. It is transformerless between the PV
circuit and AC circuit.
The unit has two controllers. The master controller DSP monitor the invert statue; measure the PV
voltage and current, bus voltage, AC voltage, current, GFCI, PV ISO and frequency, also
communicate with the slave controller ARM
The slave controller ARM monitor AC voltage, GFCI and communicate with the master controller
DSP
The relays are designed to redundant structure that controlled by separately.
The master controller and slave controller are used together to control relay open or close, if the
single fault on one controller, the other controller can be capable to open the relay, so that still
providing safety means.
The topology diagram as following:
Inv Module A
S1
Boost HCT & Choke DC Link AC Relay
BOOST A BUS+ INV HCT & Choke
S2
D1 D2 S3

T1 T2 T3
MPPT 1 S4
GFCI
NTC Common mode Output
choke Choke
Inv Module B
BOOST B L3
S1

D1 D2

MPPT 2 BUS.N S2 L2
T1 T2 T3
S3

S4
L1

NTC
BOOST C G

N
D1 D2
Inv Module C AC SPD
MPPT 3 S1
T1 T2 T3

PE
S2
DSP V ac
S3
BUS-
ARM1
DC Switch S4
PV RLY.B
RLY.A
V pv&I pv DSP ISO NTC

BUS.N
DCI
DSP ARM1 DSP I ac
BOOST control/INV
DSP ARM1
DSP ARM1
control/Relay/ISO Relay/ISO,
BUS+ BUS-
/Fan on/Relay,etc. etc.
DC SPD GFCI
Main SPS DSP
Display
Communication ARM2 Control Board DSP ARM1
etc. +15V -15V +24V +22V
SELV

Difference of the models:


All models are identical, except the output power derating in software.

Other than special notice, the model MAC 60KTL3-X LV is as the representative test model in this
report and valid for other models.

TRF No. IEC 61727B


Page 12 of 39 Report No. 191120145GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

4 UTILITY COMPATIBILITY P
The quality of power provided by the PV system for P
the on-site AC loads and for power delivered to the
utility is governed by practices and standards on
voltage, flicker, frequency, harmonics and power
factor.
Deviation from these standards represents out-of- P
bounds conditions and may require the PV system
to sense the deviation and properly disconnect from
the utility system.
4.1 Voltage, current and frequency P
The PV system AC voltage, current and frequency P
are compatible with the utility system.
4.2 Normal voltage operating range P
Utility-interconnected PV systems do not normally P
regulate voltage, they inject current into the utility.
Therefore, the voltage operating range for PV
inverters is selected as a protection function that
responds to abnormal utility conditions, not as a
voltage regulation function.
4.3 Flicker P
The operation of the PV system is not cause voltage P
flicker in excess of limits stated in the relevant
sections of IEC 61000-3-3 for systems less than 16
A or IEC 61000-3-5 for systems with current of 16 A
and above.
4.4 DC injection P
The PV system is not inject DC current greater than (See appended table ) P
1 % of the rated inverter output current, into the
utility AC interface under any operating condition.
4.5 Normal frequency operating range P
The PV system operates in synchronism with the P
utility system, and within the frequency
trip limits defined in 5.2.2.
4.6 Harmonics and waveform distortion P
Total harmonic current distortion is less than 5 % at (See appended table) P
rated inverter output. Each individual harmonic is
limited to the percentages listed in Table 1.
Even harmonics in these ranges is less than 25 % of P
the lower odd harmonic limits listed.

TRF No. IEC 61727B


Page 13 of 39 Report No. 191120145GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

4.7 The PV system has a lagging power factor greater P


than 0,9 when the output is greater than 50 % of the
rated inverter output power.
5 PERSONNEL SAFETY AND EQUIPMENT PROTECTION P
This Clause provides information and considerations P
for the safe and proper operation of the utility-
connected PV systems.
5.1 Loss of utility voltage P
To prevent islanding, a utility connected PV system Complied with IEC 62116, See P
ceases to energize the utility system from a de- the separate report for
energized distribution line irrespective of connected reference
loads or other generators within specified time limits.
A utility distribution line can become de-energized P
for several reasons. For example, a substation
breaker opening due to fault conditions or the
distribution line switched out during maintenance.
5.2 Over/under voltage and frequency P
The abnormal utility conditions of concern are P
voltage and frequency excursions above or below
the values stated in this Clause, and the complete
disconnection of the utility, presenting the potential
for a distributed resource island.
5.2.1 Over/under voltage P
When the interface voltage deviates outside the (See appended table) P
conditions specified in Table 2, the photovoltaic
system ceases to energize the utility distribution
system. This applies to any phase of a multiphase
system.
P

TRF No. IEC 61727B


Page 14 of 39 Report No. 191120145GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

5.2.2 Over/under frequency P


When the utility frequency deviates outside the (See appended table) P
specified conditions the photovoltaic system ceases
to energize the utility line. The unit does not have to
cease to energize if the frequency returns to the
normal utility continuous operation condition within
the specified trip time.
When the utility frequency is outside the range of ±1 P
Hz, the system ceases to energize the utility line
within 0,2 s. The purpose of the allowed range and
time delay is to allow continued operation for short-
term disturbances and to avoid excessive nuisance
tripping in weak-utility system conditions.
5.3 Islanding protection P
The PV system must cease to energize the utility P
line within 2 s of loss of utility.
5.4 Response to utility recovery P
Following an out-of-range utility condition that has (See appended table) P
caused the photovoltaic system to cease energizing,
the photovoltaic system is not energize the utility line
for 20 s to 5 min after the utility service voltage and
frequency have recovered to within the specified
ranges.
5.5 Earthing P
The utility interface equipment is earthed/grounded P
in accordance with IEC 60364-7-712.
5.6 Short circuit protection N/A
The photovoltaic system has short-circuit protection Should consider in the end N/A
in accordance with IEC 60364-7-712. use
5.7 Isolation and switching N/A
A method of isolation and switching is provided in Should consider in the end N/A
accordance with IEC 60364-7-712. use

TRF No. IEC 61727B


Page 15 of 39 Report No. 191120145GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

4.3 TABLE: Flicker P


Starting Stopping Running
Limit 4% 4% Pst = 1.0 Plt = 0.65

Test value L1-N 0.23 0.94 0.32 0.27

Test value L2-N 0.21 1.83 0.34 0.28

Test value L3-N 0.21 0.93 0.33 0.29


Supplementary information:
Test on model MAC 60KTL3-X LV
Starting Stopping Running
Limit 4% 4% Pst = 1.0 Plt = 0.65

Test value L1 0.18 0.99 0.26 0.20

Test value L2 0.12 0.72 0.31 0.22

Test value L3 0.15 1.10 0.24 0.19


Supplementary information:
Test on model MAC 70KTL3-X MV
Starting Stopping Running
Limit 4% 4% Pst = 1.0 Plt = 0.65

Test value L1 0.22 0.94 0.33 0.30

Test value L2 0.21 0.87 0.32 0.29

Test value L3 0.21 1.01 0.33 0.30


Supplementary information:
Test on model MAC 36KTL3-XL
Starting Stopping Running
Limit 4% 4% Pst = 1.0 Plt = 0.65

Test value L1 0.94 0.23 0.32 0.27

Test value L2 0.85 0.21 0.34 0.28

Test value L3 1.08 0.21 0.33 0.29


Supplementary information:
Test on model MAC 30KTL3-X LV

TRF No. IEC 61727B


Page 16 of 39 Report No. 191120145GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

4.4 TABLE: Direct current injection P


Rated Ratio of Measured DC output current between terminals Isolated Limit
output rated transformer ?
L1-L2 L1-L3 L2-L3 L1-N L2-N L3-N (mA)
current output
(mA) (mA) (mA) (mA) (mA) (mA) (Yes/No)
(A) power
(VA)
Model: MAC 40KTL3-X LV
-- -- -- 139.2 89.4 72.3 No 579.7
57.97 25%
-- -- -- 160.0 111.3 105.7 No 579.7
57.97 50%
-- -- -- 170.4 115.5 104.1 No 579.7
57.97 100%
Model: MAC 60KTL3-X LV
-- -- -- 135.0 99.8 47.6 No 869.5
86.95 25%
-- -- -- 113.2 116.7 53.1 No 869.5
86.95 50%
-- -- -- 167.9 115.7 100.1 No 869.5
86.95 100%
Model: MAC 70KTL3-X MV
-- -- -- 89.2 110.0 28.1 No 842.3
84.23 25%
-- -- -- 77.1 79.2 45.0 No 842.3
84.23 50%
-- -- -- 134.9 116.6 78.0 No 842.3
84.23 100%
Model: MAC 15KTL3-X MV
-- -- -- 117.6 82.4 41.8 No 394
39.4 25%
-- -- -- 70.2 77.9 40.1 No 394
39.4 50%
-- -- -- 170.9 169.2 58.5 No 394
39.4 100%
Model: MAC 30KTL3-X LV
-- -- -- 181.9 207.1 217.6 No 434.8
43.48 25%
-- -- -- 233.6 201.5 193.8 No 434.8
43.48 50%
-- -- -- 200.6 217.9 221.9 No 434.8
43.48 100%
Supplementary information:

TRF No. IEC 61727B


Page 17 of 39 Report No. 191120145GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

4.6 TABLE: Harmonics and waveform distortion P


Harmonic % of % of % of Harmonic
fundamen fundamen fundamen
fundamen fundamen fundamen Current
tal L1 (A) tal L2 (A) tal L3 (A)
tal) tal) tal) Limits (%)
Model: MAC 40KTL3-X LV

02 0.0910 0.1558 0.0984 0.1689 0.1008 0.1731 1.0%

03 0.0168 0.0287 0.0300 0.0514 0.0232 0.0399 4.0%

04 0.0598 0.1023 0.0560 0.0962 0.0475 0.0815 1.0%

05 0.2557 0.4377 0.2603 0.4468 0.2672 0.4589 4.0%

06 0.0179 0.0306 0.0149 0.0255 0.0091 0.0156 1.0%

07 0.2245 0.3844 0.2198 0.3772 0.2255 0.3873 4.0%

08 0.0243 0.0416 0.0162 0.0277 0.0230 0.0395 1.0%

09 0.0106 0.0182 0.0138 0.0236 0.0178 0.0306 4.0%

10 0.0135 0.0232 0.0136 0.0234 0.0239 0.0410 0.5%

11 0.2848 0.4875 0.2793 0.4794 0.2936 0.5041 2.0%

12 0.0149 0.0254 0.0121 0.0207 0.0116 0.0199 0.5%

13 0.3037 0.5199 0.3026 0.5195 0.2954 0.5074 2.0%

14 0.0324 0.0555 0.0297 0.0510 0.0142 0.0244 0.5%

15 0.0110 0.0188 0.0113 0.0194 0.0152 0.0261 2.0%

16 0.0345 0.0591 0.0241 0.0414 0.0224 0.0385 0.5%


17 0.2804 0.4800 0.2964 0.5087 0.2934 0.5038 1.5%
18 0.0274 0.0469 0.0159 0.0272 0.0162 0.0278 0.5%
19 0.2781 0.4761 0.2830 0.4858 0.2829 0.4859 1.5%
20 0.0454 0.0778 0.0293 0.0502 0.0203 0.0348 0.5%
21 0.0098 0.0169 0.0111 0.0190 0.0153 0.0263 1.5%
22 0.0437 0.0747 0.0339 0.0583 0.0169 0.0291 0.5%
23 0.1912 0.3273 0.1942 0.3334 0.2130 0.3659 0.6%
24 0.0315 0.0539 0.0128 0.0219 0.0209 0.0359 0.5%
25 0.1885 0.3228 0.1795 0.3081 0.1845 0.3169 0.6%
26 0.0368 0.0630 0.0331 0.0568 0.0139 0.0238 0.5%
27 0.0199 0.0341 0.0069 0.0118 0.0207 0.0355 0.6%
28 0.0255 0.0436 0.0376 0.0645 0.0265 0.0455 0.5%

TRF No. IEC 61727B


Page 18 of 39 Report No. 191120145GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

29 0.0648 0.1109 0.0813 0.1397 0.0665 0.1142 0.6%


30 0.0211 0.0361 0.0135 0.0233 0.0159 0.0274 0.5%
31 0.1154 0.1976 0.1175 0.2017 0.1292 0.2220 0.6%
32 0.0213 0.0364 0.0076 0.0131 0.0226 0.0388 0.5%
33 0.0169 0.0290 0.0064 0.0109 0.0202 0.0346 0.6%

THD 1.348 1.379 1.388 5%


Model: MAC 60KTL3-X LV

02 0.0677 0.0773 0.0844 0.0966 0.0805 0.0921 1.0%

03 0.0619 0.0706 0.0667 0.0764 0.0223 0.0255 4.0%

04 0.0692 0.0790 0.0579 0.0663 0.0426 0.0488 1.0%

05 0.4256 0.4858 0.4554 0.5212 0.4653 0.5326 4.0%

06 0.0247 0.0282 0.0126 0.0145 0.0167 0.0191 1.0%

07 0.4458 0.5088 0.4237 0.4849 0.4363 0.4995 4.0%

08 0.0228 0.0260 0.0142 0.0162 0.0182 0.0208 1.0%

09 0.0129 0.0148 0.0217 0.0248 0.0300 0.0343 4.0%

10 0.0185 0.0212 0.0148 0.0169 0.0245 0.0281 0.5%

11 0.3433 0.3918 0.3510 0.4016 0.3592 0.4112 2.0%

12 0.0116 0.0133 0.0180 0.0206 0.0154 0.0176 0.5%

13 0.3610 0.4120 0.3571 0.4087 0.3468 0.3970 2.0%

14 0.0283 0.0323 0.0308 0.0353 0.0136 0.0155 0.5%

15 0.0142 0.0163 0.0211 0.0241 0.0138 0.0158 2.0%

16 0.0359 0.0410 0.0199 0.0228 0.0255 0.0292 0.5%


17 0.3343 0.3815 0.3455 0.3955 0.3557 0.4072 1.5%
18 0.0263 0.0300 0.0134 0.0153 0.0177 0.0202 0.5%
19 0.3466 0.3956 0.3559 0.4073 0.3440 0.3938 1.5%
20 0.0375 0.0428 0.0326 0.0373 0.0106 0.0122 0.5%
21 0.0103 0.0118 0.0239 0.0273 0.0172 0.0198 1.5%
22 0.0464 0.0530 0.0350 0.0400 0.0260 0.0298 0.5%
23 0.2607 0.2976 0.2626 0.3006 0.2779 0.3182 0.6%
24 0.0195 0.0222 0.0122 0.0139 0.0113 0.0130 0.5%
25 0.2310 0.2636 0.2076 0.2376 0.2121 0.2429 0.6%

TRF No. IEC 61727B


Page 19 of 39 Report No. 191120145GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

26 0.0359 0.0410 0.0321 0.0368 0.0087 0.0100 0.5%


27 0.0304 0.0347 0.0124 0.0142 0.0226 0.0259 0.6%
28 0.0318 0.0364 0.0373 0.0426 0.0381 0.0436 0.5%
29 0.0958 0.1093 0.1171 0.1340 0.1053 0.1205 0.6%
30 0.0183 0.0209 0.0145 0.0166 0.0198 0.0227 0.5%
31 0.1732 0.1977 0.1660 0.1899 0.1821 0.2084 0.6%
32 0.0252 0.0288 0.0170 0.0195 0.0102 0.0117 0.5%
33 0.0074 0.0084 0.0127 0.0146 0.0131 0.0150 0.6%

THD 1.230 1.238 1.250 5%


Model: MAC 70KTL3-X MV

02 0.1808 0.2121 0.1874 0.2205 0.1892 0.2227 1.0%

03 0.0691 0.0811 0.0622 0.0732 0.0425 0.0500 4.0%

04 0.1238 0.1452 0.1152 0.1355 0.1008 0.1187 1.0%

05 0.6377 0.7482 0.6672 0.7849 0.6743 0.7937 4.0%

06 0.0183 0.0214 0.0175 0.0206 0.0139 0.0164 1.0%

07 0.5378 0.6311 0.5175 0.6088 0.5321 0.6263 4.0%

08 0.0441 0.0518 0.0291 0.0343 0.0387 0.0456 1.0%

09 0.0148 0.0173 0.0229 0.0269 0.0274 0.0323 4.0%

10 0.0303 0.0356 0.0164 0.0193 0.0195 0.0229 0.5%

11 0.3323 0.3899 0.3293 0.3875 0.3312 0.3899 2.0%

12 0.0206 0.0242 0.0207 0.0244 0.0177 0.0208 0.5%

13 0.3562 0.4180 0.3476 0.4089 0.3321 0.3909 2.0%

14 0.0522 0.0613 0.0495 0.0582 0.0304 0.0358 0.5%

15 0.0145 0.0170 0.0198 0.0233 0.0142 0.0167 2.0%

16 0.0592 0.0694 0.0432 0.0508 0.0441 0.0519 0.5%


17 0.3380 0.3966 0.3407 0.4009 0.3583 0.4217 1.5%
18 0.0367 0.0431 0.0133 0.0157 0.0291 0.0343 0.5%
19 0.3558 0.4174 0.3599 0.4235 0.3493 0.4111 1.5%
20 0.0566 0.0665 0.0242 0.0285 0.0483 0.0569 0.5%
21 0.0158 0.0185 0.0251 0.0296 0.0141 0.0166 1.5%
22 0.0580 0.0681 0.0361 0.0424 0.0352 0.0414 0.5%

TRF No. IEC 61727B


Page 20 of 39 Report No. 191120145GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

23 0.2544 0.2985 0.2602 0.3061 0.2718 0.3200 0.6%


24 0.0299 0.0350 0.0174 0.0205 0.0158 0.0186 0.5%
25 0.1973 0.2315 0.1958 0.2304 0.1937 0.2280 0.6%
26 0.0521 0.0612 0.0277 0.0326 0.0496 0.0583 0.5%
27 0.0251 0.0294 0.0152 0.0179 0.0250 0.0294 0.6%
28 0.0279 0.0327 0.0128 0.0150 0.0192 0.0227 0.5%
29 0.1409 0.1654 0.1439 0.1693 0.1322 0.1556 0.6%
30 0.0297 0.0348 0.0166 0.0195 0.0159 0.0187 0.5%
31 0.1121 0.1315 0.1234 0.1452 0.1285 0.1512 0.6%
32 0.0157 0.0184 0.0173 0.0204 0.0286 0.0336 0.5%
33 0.0177 0.0208 0.0086 0.0101 0.0150 0.0176 0.6%

THD 1.446 1.465 1.488 5%


Model: MAC 15KTL3-XL

02 0.1371 0.4892 0.1059 0.3764 0.0950 0.3372 1.0%

03 0.0252 0.0901 0.0256 0.0910 0.0305 0.1083 4.0%

04 0.0726 0.2591 0.0531 0.1889 0.0479 0.1696 1.0%

05 0.1094 0.3906 0.1073 0.3817 0.1022 0.3627 4.0%

06 0.0400 0.1427 0.0360 0.1281 0.0313 0.1112 1.0%

07 0.0733 0.2618 0.0693 0.2463 0.0823 0.2919 4.0%

08 0.0320 0.1141 0.0289 0.1029 0.0241 0.0856 1.0%

09 0.0250 0.0891 0.0249 0.0886 0.0248 0.0879 4.0%

10 0.0294 0.1049 0.0266 0.0947 0.0254 0.0901 0.5%

11 0.0732 0.2611 0.0784 0.2788 0.0729 0.2583 2.0%

12 0.0277 0.0988 0.0269 0.0958 0.0225 0.0795 0.5%

13 0.0418 0.1491 0.0502 0.1785 0.0362 0.1285 2.0%

14 0.0260 0.0927 0.0264 0.0939 0.0242 0.0858 0.5%

15 0.0244 0.0870 0.0246 0.0874 0.0237 0.0840 2.0%

16 0.0262 0.0936 0.0270 0.0962 0.0225 0.0799 0.5%


17 0.0388 0.1386 0.0360 0.1279 0.0368 0.1303 1.5%
18 0.0244 0.0871 0.0250 0.0889 0.0259 0.0920 0.5%
19 0.0317 0.1133 0.0349 0.1239 0.0352 0.1250 1.5%

TRF No. IEC 61727B


Page 21 of 39 Report No. 191120145GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

20 0.0241 0.0861 0.0249 0.0886 0.0230 0.0814 0.5%


21 0.0241 0.0861 0.0223 0.0792 0.0244 0.0862 1.5%
22 0.0262 0.0934 0.0281 0.0998 0.0250 0.0888 0.5%
23 0.0289 0.1033 0.0314 0.1116 0.0291 0.1035 0.6%
24 0.0246 0.0879 0.0242 0.0861 0.0241 0.0857 0.5%
25 0.0258 0.0920 0.0311 0.1107 0.0309 0.1099 0.6%
26 0.0255 0.0909 0.0258 0.0918 0.0231 0.0816 0.5%
27 0.0234 0.0836 0.0240 0.0855 0.0227 0.0806 0.6%
28 0.0270 0.0964 0.0244 0.0870 0.0272 0.0964 0.5%
29 0.0282 0.1006 0.0321 0.1141 0.0306 0.1085 0.6%
30 0.0270 0.0963 0.0248 0.0881 0.0228 0.0809 0.5%
31 0.0243 0.0868 0.0295 0.1049 0.0240 0.0850 0.6%
32 0.0273 0.0973 0.0321 0.1140 0.0248 0.0879 0.5%
33 0.0293 0.1044 0.0361 0.1283 0.0361 0.1276 0.6%

THD 1.216 1.181 1.104 5%


Model: MAC 30KTL3-X LV

02 0.1565 0.3561 0.1055 0.2424 0.0965 0.2207 1.0%

03 0.1150 0.2617 0.1071 0.2460 0.1137 0.2601 4.0%

04 0.0596 0.1355 0.0718 0.1647 0.0836 0.1912 1.0%

05 0.2639 0.6005 0.2555 0.5867 0.2419 0.5533 4.0%

06 0.0304 0.0691 0.0411 0.0943 0.0491 0.1122 1.0%

07 0.3631 0.8261 0.3647 0.8375 0.3656 0.8362 4.0%

08 0.0321 0.0732 0.0329 0.0755 0.0319 0.0729 1.0%

09 0.0221 0.0503 0.0241 0.0554 0.0243 0.0555 4.0%

10 0.0255 0.0580 0.0241 0.0554 0.0258 0.0591 0.5%

11 0.2285 0.5200 0.2386 0.5480 0.2315 0.5296 2.0%

12 0.0284 0.0645 0.0346 0.0793 0.0494 0.1131 0.5%

13 0.0716 0.1629 0.0709 0.1628 0.0630 0.1440 2.0%

14 0.0295 0.0670 0.0288 0.0660 0.0318 0.0727 0.5%

15 0.0251 0.0571 0.0265 0.0607 0.0370 0.0846 2.0%

16 0.0289 0.0658 0.0399 0.0916 0.0489 0.1117 0.5%

TRF No. IEC 61727B


Page 22 of 39 Report No. 191120145GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

17 0.0633 0.1441 0.0648 0.1488 0.0657 0.1503 1.5%


18 0.0307 0.0698 0.0657 0.1508 0.1037 0.2371 0.5%
19 0.1069 0.2432 0.0958 0.2200 0.1013 0.2318 1.5%
20 0.0258 0.0588 0.0277 0.0637 0.0241 0.0552 0.5%
21 0.0214 0.0488 0.0290 0.0665 0.0252 0.0576 1.5%
22 0.0321 0.0731 0.0255 0.0586 0.0270 0.0617 0.5%
23 0.0778 0.1771 0.0781 0.1793 0.0791 0.1810 0.6%
24 0.0254 0.0578 0.0243 0.0557 0.0274 0.0626 0.5%
25 0.1264 0.2876 0.1291 0.2964 0.1249 0.2856 0.6%
26 0.0276 0.0628 0.0274 0.0630 0.0264 0.0604 0.5%
27 0.0225 0.0512 0.0259 0.0595 0.0248 0.0567 0.6%
28 0.0287 0.0652 0.0276 0.0633 0.0272 0.0623 0.5%
29 0.0935 0.2128 0.0955 0.2194 0.0860 0.1967 0.6%
30 0.0243 0.0552 0.0232 0.0534 0.0310 0.0708 0.5%
31 0.0816 0.1857 0.0776 0.1782 0.0689 0.1577 0.6%
32 0.0264 0.0600 0.0268 0.0615 0.0236 0.0539 0.5%
33 0.0239 0.0545 0.0270 0.0620 0.0248 0.0566 0.6%

THD 1.661 1.736 1.648 5%


Supplementary information:

4.7 TABLE: Power factor P


Model MAC 40KTL3-X LV
Input Output
Curre
Voltage Power Voltage Current Power Power Rated output
No nt (A
(V d.c.) (W) (V a.c.) (A a.c.) (W) factor (+/-) (V.A)
d.c.)
229.98 12.19 2794.45 0.9970
1 700.29 12.42 8695.45 230.41 12.16 2791.19 0.9965 (20±5)%
230.40 12.11 2780.99 0.9967
230.01 17.68 4060.48 0.9987
2 700.54 17.96 12583.92 230.46 17.64 4058.87 0.9985 (30±5)%
230.44 17.59 4048.51 0.9986

TRF No. IEC 61727B


Page 23 of 39 Report No. 191120145GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

230.04 23.71 5450.33 0.9993


3 700.05 24.03 16824.93 230.46 23.65 5446.83 0.9992 (40±5)%
230.12 23.61 5437.36 0.9992
230.06 29.51 6785.48 0.9996
4 700.04 29.91 20938.47 230.51 29.43 6781.49 0.9995 (50±5)%
230.49 29.39 6771.48 0.9995
230.08 35.42 8145.42 0.9996
5 699.83 35.88 25106.58 230.53 35.32 8139.06 0.9996 (60±5)%
230.52 35.29 8131.39 0.9996
230.11 41.48 9494.71 0.9997
6 699.65 41.84 29274.17 230.56 41.16 9487.84 0.9997 (70±5)%
230.55 41.13 9479.85 0.9997
230.13 46.52 10702.21 0.9997
7 699.47 47.18 32999.34 230.58 46.39 10694.72 0.9997 (80±5)%
230.57 46.36 10686.86 0.9997
230.16 52.56 12093.74 0.9996
8 699.26 53.33 37289.25 230.60 52.42 12083.76 0.9997 (90±5)%
230.60 52.39 12076.43 0.9996

230.18 58.43 13445.27 0.9996


9 699.02 59.32 41466.01 230.63 58.27 13434.17 0.9997 (100±5)%
230.62
58.25 13426.98 0.9996
Model MAC 60KTL3-X LV
Input Output
Curre
Voltage Power Voltage Current Power Power Rated output
No nt (A
(V d.c.) (W) (V a.c.) (A a.c.) (W) factor (+/-) (V.A)
d.c.)
230.01 17.69 4059.70 0.9979
1 700.66 17.98 12599.35 230.45 17.65 4057.71 0.9977 (20±5)%
230.45 17.60 4047.51 0.9979
230.05 26.64 6122.86 0.9992
2 700.23 26.99 18896.61 230.48 26.57 6117.98 0.9991 (30±5)%
230.48 26.52 6108.10 0.9992
230.09 35.48 8161.33 0.9996
3 699.98 35.96 25174.25 230.51 35.39 8153.56 0.9995 (40±5)%
230.52 35.35 8146.22 0.9996

TRF No. IEC 61727B


Page 24 of 39 Report No. 191120145GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

230.14 44.32 10197.66 0.9997


4 699.76 44.90 31421.58 230.54 44.20 10187.43 0.9997 (50±5)%
230.55 44.17 10179.76 0.9997
230.18 52.58 12099.54 0.9997
5 699.61 53.32 37300.51 230.57 52.44 12086.71 0.9997 (60±5)%
230.59 52.40 12080.33 0.9997
230.21 61.22 14088.17 0.9996
6 699.44 62.13 43453.58 230.61 61.05 14074.77 0.9997 (70±5)%
230.63 61.03 14070.31 0.9997
230.24 70.02 16114.53 0.9996
7 699.31 71.12 49737.41 230.65 69.82 16099.47 0.9997 (80±5)%
230.67 69.80 16094.72 0.9996
230.28 78.87 18155.42 0.9996
8 699.13 80.23 56089.06 230.69 78.66 18138.26 0.9996 (90±5)%
230.72 78.63 18134.51 0.9996
230.31 87.64 20176.63 0.9996
9 698.86 89.29 62399.36 230.73 87.40 20157.95 0.9996 (100±5)%
230.77 87.37 20154.89 0.9996
Model MAC 70KTL3-X MV
Input Output
Curre
Voltage Power Voltage Current Power Power Rated output
No nt (A
(V d.c.) (W) (V a.c.) (A a.c.) (W) factor (+/-) (V.A)
d.c.)
276.99 17.14 4742.95 0.9986
1 700.43 20.82 14585.28 277.51 17.12 4742.42 0.9984 (20±5)%
277.51 17.06 4726.61 0.9986
277.04 25.80 7144.61 0.9995
2 700.09 31.32 21929.40 277.54 25.74 7140.91 0.9994 (30±5)%
277.54 25.69 7125.13 0.9995
277.09 34.39 9527.18 0.9997
3 699.83 41.74 29209.03 277.56 34.31 9520.16 0.9997 (40±5)%
277.57 34.26 9506.46 0.9997
277.13 42.98 11909.33 0.9998
4 699.60 52.20 36519.02 277.59 42.88 11900.93 0.9998 (50±5)%
277.61 42.83 11887.90 0.9998

TRF No. IEC 61727B


Page 25 of 39 Report No. 191120145GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

277.17 51.79 14352.47 0.9998


5 699.43 62.96 44034.87 277.63 51.67 14340.83 0.9998 (60±5)%
277.65 51.62 14329.29 0.9998
277.21 60.22 16688.95 0.9997
6 699.24 73.25 51219.58 277.67 60.07 16676.71 0.9998 (70±5)%
277.69 60.03 16665.32 0.9998
277.23 67.81 18793.74 0.9997
7 699.03 82.57 57717.11 277.71 67.64 18780.57 0.9998 (80±5)%
277.74 67.60 18769.28 0.9997
277.27 76.45 21197.68 0.9997
8 698.66 93.22 65129.35 277.75 76.26 21176.32 0.9997 (90±5)%
277.78 76.22 21166.18 0.9997
277.30 85.05 23576.97 0.9997
9 698.65 103.82 72530.61 277.79 84.84 23560.18 0.9997 (100±5)%
277.83 84.79 23549.71 0.9997
Model MAC 40KTL3-X LV
Input Output
Curre
Voltage Power Voltage Current Power Power Rated output
No nt (A
(V d.c.) (W) (V a.c.) (A a.c.) (W) factor (+/-) (V.A)
d.c.)
230.94 8.78 2012.15 0.9922
1 600.24 10.36 6116.92 230.66 8.78 2007.81 0.9913 (20±5)%
230.37 8.84 2019.22 0.9910
230.04 13.27 3045.98 0.9977
2 600.18 15.67 9403.70 229.63 13.18 3019.61 0.9976 (30±5)%
230.66 13.22 3041.08 0.9974
231.12 17.45 4025.44 0.9981
3 600.21 20.66 12400.53 230.78 17.44 4016.89 0.9980 (40±5)%
230.42 17.52 4027.68 0.9976
230.21 22.18 5104.01 0.9993
4 600.07 26.05 15632.70 229.87 21.99 5050.48 0.9990 (50±5)%
230.79 22.09 5090.18 0.9984
231.27 26.21 6054.51 0.9987
5 600.14 31.07 18646.32 230.86 26.20 6039.06 0.9986 (60±5)%
230.54 26.29 6061.27 0.9984

TRF No. IEC 61727B


Page 26 of 39 Report No. 191120145GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

230.36 30.94 7123.92 0.9994


6 600.09 36.34 21806.10 229.88 30.68 7048.63 0.9994 (70±5)%
230.88 30.82 7109.27 0.9992
231.34 34.93 8064.64 0.9982
7 600.04 41.32 24794.50 230.87 34.90 8040.40 0.9980 (80±5)%
230.57 35.01 8055.14 0.9979
231.36 39.28 9068.73 0.9979
8 600.01 46.49 27896.12 230.88 39.37 9041.31 0.9977 (90±5)%
230.63 39.37 9059.46 0.9977
230.42 43.97 10126.40 0.9995
9 599.88 51.64 30979.70 229.96 43.56 10012.90 0.9996 (100±5)%
231.08 43.75 10104.20 0.9994
Supplementary information:
Power factor with “+” indicating leading and “-“ indicating lagging.

TRF No. IEC 61727B


Page 27 of 39 Report No. 191120145GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

5.2.1 & 5.4 TABLE: Under-and over-voltage trip settings and reconnection test P
(1) Under voltage disconnection procedure
Rated Output Required Value of Ratio of Interva Measured Measured
output power min. voltage PCE trip decreased l time tripped disconnectio
voltage (VA) (V) settings (V / s) (s) voltage n time (s)
(V) (V) (V)
230 66600 195.5 195.5 0.1 3 196.1 1.534
Rated Output Required Value of Ratio of Interval Measured Measured
output power min. voltage PCE trip decreased time tripped voltage disconnection
voltage (VA) (V) settings (V / s) (s) (V) time (s)
(V) (V)
230 66600 115 115 0.1 0.2 115.2 0.070

(2) Under voltage reconnection procedure


Ratio of voltage rapidly Reconnection voltage (V) Reconnection time (s)
decreased
(V / s)
0.1 195.5 70.66
(3) Over voltage disconnection procedure
Rated Output Required Value of Ratio of Interva Measured Measured
output power max. voltage PCE trip increased l time tripped disconnectio
voltage (VA) (V) settings (V / s) (s) voltage n time (s)
(V) (V) (V)
230V 66600 253 253 0.1 3 252.6 1.573
Rated Output Required Value of Ratio of Interval Measured Measured
output power max. voltage PCE trip increased time tripped voltage disconnection
voltage (VA) (V) settings (V / s) (s) (V) time (s)
(V) (V)
230V 66600 310.5 310.5 0.1 0.1 309.8 0.041
(4) Over voltage reconnection procedure
Ratio of voltage rapidly Reconnection voltage (V) Reconnection time (s)
decreased
(V / s)
0.1 <253V 70.66
Supplementary information:
Tested on model MAC 60KTL3-X LV

TRF No. IEC 61727B


Page 28 of 39 Report No. 191120145GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

5.2.1 & 5.4 TABLE: Under-and over-voltage trip settings and reconnection test P
(1) Under voltage disconnection procedure
Rated Output Required Value of Ratio of Interva Measured Measured
output power min. voltage PCE trip decreased l time tripped disconnectio
voltage (VA) (V) settings (V / s) (s) voltage n time (s)
(V) (V) (V)
277 77700 235.4 235.0 0.1 3 234.8 1.579
Rated Output Required Value of Ratio of Interval Measured Measured
output power min. voltage PCE trip decreased time tripped voltage disconnection
voltage (VA) (V) settings (V / s) (s) (V) time (s)
(V) (V)
277 77700 138.5 138.0 0.1 0.2 138.4 0.087

(2) Under voltage reconnection procedure


Ratio of voltage rapidly Reconnection voltage (V) Reconnection time (s)
decreased
(V / s)
0.1 >235.4 70.86
(3) Over voltage disconnection procedure
Rated Output Required Value of Ratio of Interva Measured Measured
output power max. voltage PCE trip increased l time tripped disconnectio
voltage (VA) (V) settings (V / s) (s) voltage n time (s)
(V) (V) (V)
277V 77700 304.7 304.0 0.1 3 304.6 1.562
Rated Output Required Value of Ratio of Interval Measured Measured
output power max. voltage PCE trip increased time tripped voltage disconnection
voltage (VA) (V) settings (V / s) (s) (V) time (s)
(V) (V)
277V 77700 373.9 373.0 0.1 0.1 373.6 0.047
(4) Over voltage reconnection procedure
Ratio of voltage rapidly Reconnection voltage (V) Reconnection time (s)
decreased
(V / s)
0.1 <304V 70.71
Supplementary information:
Tested on model MAC 70KTL3-X MV

TRF No. IEC 61727B


Page 29 of 39 Report No. 191120145GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

5.2.1 & 5.4 TABLE: Under-and over-voltage trip settings and reconnection test P
(1) Under voltage disconnection procedure
Rated Output Required Value of Ratio of Interva Measured Measured
output power min. voltage PCE trip decreased l time tripped disconnectio
voltage (VA) (V) settings (V / s) (s) voltage n time (s)
(V) (V) (V)
127 36000 108.0 108.0 0.1 3 108.8 1.08
Rated Output Required Value of Ratio of Interval Measured Measured
output power min. voltage PCE trip decreased time tripped voltage disconnection
voltage (VA) (V) settings (V / s) (s) (V) time (s)
(V) (V)
127 36000 63.5 64.0 0.1 0.2 64.4 0.040

(2) Under voltage reconnection procedure


Ratio of voltage rapidly Reconnection voltage (V) Reconnection time (s)
decreased
(V / s)
0.1 >108 70.86
(3) Over voltage disconnection procedure
Rated Output Required Value of Ratio of Interva Measured Measured
output power max. voltage PCE trip increased l time tripped disconnectio
voltage (VA) (V) settings (V / s) (s) voltage n time (s)
(V) (V) (V)
127V 36000 139.7 139.0 0.1 3 138.6 0.096
Rated Output Required Value of Ratio of Interval Measured Measured
output power max. voltage PCE trip increased time tripped voltage disconnection
voltage (VA) (V) settings (V / s) (s) (V) time (s)
(V) (V)
127V 36000 171.5 170.0 0.1 0.1 170.6 0.040
(4) Over voltage reconnection procedure
Ratio of voltage rapidly Reconnection voltage (V) Reconnection time (s)
decreased
(V / s)
0.1 <139V 71.0
Supplementary information:
Tested on model MAC 36KTL3-XL

TRF No. IEC 61727B


Page 30 of 39 Report No. 191120145GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

5.2.2 & 5.4 TABLE: Over/under frequency trip settings and reconnection test P
(1) Under frequency disconnection procedure
Rated Output Required Value of Ratio of Interva Measured Measured
output power min. PCE trip decreased l time tripped disconnectio
frequency (VA) frequency settings (Hz / s) (s) frequency n time (s)
(Hz) (Hz) (Hz) (Hz)
50 66600 49 49 0.01 0.3 49.02 0.167

(2) Under frequency reconnection procedure


Ratio of frequency rapidly Reconnection frequency (Hz) Reconnection time (s)
decreased (Hz / s)
0.01 >49 72.87
(3) Over frequency disconnection procedure
Rated Output Required Value of Ratio of Interva Measured Measured
output power max. PCE trip increased l time tripped disconnectio
frequency (VA) frequency settings (Hz / s) (s) frequency n time (s)
(Hz) (Hz) (Hz) (Hz)
50 66600 51 51 0.01 0.3 50.99 0.186
(4) Over frequency reconnection procedure
Ratio of frequency rapidly Reconnection frequency (Hz) Reconnection time (s)
decreased (Hz / s)
0.01 <51 71.06
Supplementary information:
Tested on model MAC 60KTL3-X LV with frequency 50Hz
(1) Under frequency disconnection procedure
Rated Output Required Value of Ratio of Interva Measured Measured
output power min. PCE trip decreased l time tripped disconnectio
frequency (VA) frequency settings (Hz / s) (s) frequency n time (s)
(Hz) (Hz) (Hz) (Hz)
60 66600 59 59 0.01 0.3 59.0 0.064

(2) Under frequency reconnection procedure


Ratio of frequency rapidly Reconnection frequency (Hz) Reconnection time (s)
decreased (Hz / s)
0.01 >59 71.50
(3) Over frequency disconnection procedure
Rated Output Required Value of Ratio of Interva Measured Measured
output power max. PCE trip increased l time tripped disconnectio
frequency (VA) frequency settings (Hz / s) (s) frequency n time (s)
(Hz) (Hz) (Hz) (Hz)
60 66600 61 61 0.01 0.3 60.99 0.064
(4) Over frequency reconnection procedure
Ratio of frequency rapidly Reconnection frequency (Hz) Reconnection time (s)
decreased (Hz / s)

TRF No. IEC 61727B


Page 31 of 39 Report No. 191120145GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

0.01 <61 70.31


Supplementary information:
Tested on model MAC 60KTL3-X LV with frequency 60Hz

5.3 TABLE: tested condition and run-on time P


Model MAC 60KTL3-X LV with frequency 50Hz
No. PEUT (% Reactiv PAC QAC Run-on PEUT Actual VDC Which
of EUT e load time(ms) (KW) Qf load is
rating) (% of (Var) selected
normal) to be
adjusted
(R or L)
Test condition A
1 100 100 0 0 194 60.0 1.00 850V /
2 100 100 -5 -5 152 60.0 0.98 850V /
3 100 100 -5 0 129 60.0 0.96 850V /
4 100 100 -5 +5 106 60.0 0.93 850V /
5 100 100 0 -5 168 60.0 1.03 850V /
6 100 100 0 +5 138 60.0 0.98 850V /
7 100 100 +5 -5 127 60.0 1.08 850V /
8 100 100 +5 0 141 60.0 1.05 850V /
9 100 100 +5 +5 115 60.0 1.02 850V /
Test condition B
10 66 66 0 0 173 39.7 1.00 600V /
11 66 66 0 -5 100 39.7 1.03 600V L
12 66 66 0 -4 117 39.7 1.02 600V L
13 66 66 0 -3 120 39.7 1.02 600V L
14 66 66 0 -2 145 39.7 1.01 600V L
15 66 66 0 -1 163 39.7 1.01 600V L
16 66 66 0 1 159 39.7 0.99 600V L
17 66 66 0 2 135 39.7 0.99 600V L
18 66 66 0 3 125 39.7 0.98 600V L
19 66 66 0 4 116 39.7 0.98 600V L
20 66 66 0 5 108 39.7 0.97 600V L
Test condition C
21 33 33 0 0 250 20.0 1.00 360V /
22 33 33 0 -5 120 20.0 1.03 360V L
23 33 33 0 -4 130 20.0 1.03 360V L
24 33 33 0 -3 168 20.0 1.02 360V L
25 33 33 0 -2 197 20.0 1.01 360V L
26 33 33 0 -1 263 20.0 1.01 360V L
27 33 33 0 1 247 20.0 1.00 360V L
28 33 33 0 2 244 20.0 0.99 360V L
29 33 33 0 3 235 20.0 0.99 360V L
30 33 33 0 4 182 20.0 0.98 360V L
31 33 33 0 5 175 20.0 0.98 360V L

TRF No. IEC 61727B


Page 32 of 39 Report No. 191120145GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

Model MAC 60KTL3-X LV with frequency 60Hz


No. PEUT (% Reactiv PAC QAC Run-on PEUT Actual VDC Which
of EUT e load time(ms) (KW) Qf load is
rating) (% of (Var) selected
normal) to be
adjusted
(R or L)
Test condition A
1 100 100 0 0 170 60.0 1.00 850V /
2 100 100 -5 -5 150 60.0 0.98 850V /
3 100 100 -5 0 145 60.0 0.95 850V /
4 100 100 -5 +5 130 60.0 0.93 850V /
5 100 100 0 -5 103 60.0 1.03 850V /
6 100 100 0 +5 106 60.0 0.98 850V /
7 100 100 +5 -5 145 60.0 1.08 850V /
8 100 100 +5 0 110 60.0 1.06 850V /
9 100 100 +5 +5 108 60.0 1.02 850V /
Test condition B
10 66 66 0 0 175 39.7 1.00 600V /
11 66 66 0 -5 100 39.7 1.03 600V L
12 66 66 0 -4 105 39.7 1.02 600V L
13 66 66 0 -3 118 39.7 1.02 600V L
14 66 66 0 -2 126 39.7 1.01 600V L
15 66 66 0 -1 162 39.7 1.01 600V L
16 66 66 0 1 165 39.7 0.99 600V L
17 66 66 0 2 136 39.7 0.99 600V L
18 66 66 0 3 108 39.7 0.98 600V L
19 66 66 0 4 100 39.7 0.98 600V L
20 66 66 0 5 90 39.7 0.97 600V L
Test condition C
21 33 33 0 0 182 19.8 1.00 360V /
22 33 33 0 -5 100 19.8 1.03 360V L
23 33 33 0 -4 118 19.8 1.03 360V L
24 33 33 0 -3 120 19.8 1.02 360V L
25 33 33 0 -2 128 19.8 1.01 360V L
26 33 33 0 -1 146 19.8 1.01 360V L
27 33 33 0 1 166 19.8 0.99 360V L
28 33 33 0 2 131 19.8 0.99 360V L
29 33 33 0 3 117 19.8 0.98 360V L
30 33 33 0 4 102 19.8 0.98 360V L
31 33 33 0 5 80 19.8 0.97 360V L

TRF No. IEC 61727B


Page 33 of 39 Report No. 191120145GZU-001
IEC61727
Cl. Requirement - Test Result Verdict

Supplementary information:
For test condition A:
If any of the recorded run-on times are longer than the one recorded for the rated balance condition, then
the non-shaded parameter combinations also require testing.
For test condition B and C:
If run-on times are still increasing at the 95 % or 105 % points, additional 1 % increments is taken until
run-on times begin decreasing.

TRF No. IEC 61727B


Page 34 of 39 Report No. 191120145GZU-001

Appendix 1: Photos

Overview

Side view

TRF No. IEC 61727B


Page 35 of 39 Report No. 191120145GZU-001

Side view

Connection view (for 12 strings)

TRF No. IEC 61727B


Page 36 of 39 Report No. 191120145GZU-001

Connection view (for 10 strings)

Connection view (for 9 strings)

TRF No. IEC 61727B


Page 37 of 39 Report No. 191120145GZU-001

Internal view (for 12 strings)

Internal view (removed I/O board) (for 12 strings)

TRF No. IEC 61727B


Page 38 of 39 Report No. 191120145GZU-001

Internal view (for 10 strings)

Internal view (removed I/O board) (for 10 strings)

TRF No. IEC 61727B


Page 39 of 39 Report No. 191120145GZU-001

Internal view (for 9 strings)

Internal view (removed I/O board) (for 9 strings)

--- End of test report---

TRF No. IEC 61727B

You might also like