You are on page 1of 6

Series of PLCs A U T O M AT I O N P E O P L E

USER MANUAL
16-Point 24 VDC Output Module
The digital output module receives commands from the 4716
24VDC OUTPUT
Processor Module in order to switch ON or OFF various field 16 OP
actuators and elements like relays, contactors, indicating
lamps and solenoid valves. The module provides 24 VDC
source type output through solid-state MOSFET type of NO 24V SUPPLY
GROUP 1 ERROR
devices. GROUP 2 ERROR
GROUP 3 ERROR
On the front side, red LEDs indicate individual output status. GROUP 4 ERROR
LED glows if the Processor puts ON corresponding output. I/O
label is provided on the front side for I/O identification. Under
the front door, a removable 20-pin terminal block is provided Q .0
.1
for wiring of field output devices. This is easily removable .2
which facilitates wiring and module replacement without .3
.4
removing a single wire. This module can be inserted in any of .5
the I/O slots. .6
.7
Technical specifications Q .0
.1
.2
Number of outputs 16 .3
.4
Voltage rating 24 VDC (18-30 VDC including ripple) .5
.6
Type of Output Source (in groups of 8) .7

Output device MOSFET


Indication for output 3mm Red LED for each channel at digital side
ON Voltage 22 VDC Minimum
OFF Voltage 1.5 VDC Maximum
Response time OFF to ON (0.1ms) ON to OFF (0.4ms)
1.5 Amp
Current per output
Maximum 4 Amp per group Figure 1 : Front view
9 Amp maximum for 3ms duration at 25 °C
Inrush current
5 Amp maximum for 3ms duration at 150 °C
OFF state leakage current 10 µA at 24 VDC typical
Protections • Reverse voltage.
• Over voltage above 40 VDC
• Short circuit at output device side
(electronic protection)
• Fast demagnetization for inductive loads
I/O point consumption 16 output points
Optical (1.5 KV from internal bus)
Isolation
No isolation between channels
Back-plane current 200 mA (All outputs ON)

1
• Low load sensing (below 300 mA) and short circuit indication common
Fault Indications
for groups of four outputs
• No 24 V Supply
External control power 18 - 30 VDC including ripple 0.1Amp
supply
Load Power Supply 18-30 VDC including ripple, current capacity depends on the output load.
Connection Removable 20-pin terminal block
Dimension (WxHxD) 42mm x 190mm x 120mm
Ordering code 4716

Module wiring
This is source type of output module. Two 24VDC load supply common points (terminal
numbers 1 and 18), each for group of consecutive eight outputs are provided. Connect
output devices (load less than 1.5 Amps) to output points as shown in figure 2 with
other terminals of output devices connected to ground of load supply. The module
requires 24 VDC control supply for its operation which should be connected in between
terminals 19 and 20. If this supply is not healthy, Yellow LED 'NO 24 V SUPPLY' glows.
The module control supply and load supply may be different but their supply grounds
should be made common. If module control supply and load supply is not connected
and output is switched ON, it is indicated by respective red LED. But corresponding on
board MOSFET device is not switched ON and hence connected field device is not
switched ON.

Recommended wires Front shield plate


1-1.5 mm2 (AWG 20-16)

Terminal block fixing


01 01
+ 24V
screw
02 L
● 03 L
04
Connection details
● L
● 05 L
● 06 L label
● 07 L
– 08 L
– 09 L 0V
● 10 L
● 11 L


12 L
LED Status
13 L
– 14 L indication
– 15 L
– 16 L
24 VDC ●
0V
17 L
Load
20 pin removable
● + 24V
18 18
Supply – + ● 19 0V
20 +24 V terminal block
– +
24 VDC 1.5 AMP SOURCE
Terminal block fixing
Control Supply OUTPUT
screw

Figure 2 : Connecting output devices

2
Four yellow LEDs are provided at the top for error indications. One indication is
provided per group of four outputs. If any single output in a group is put ON by the
processor, corresponding error LED glows
• If load connected to output point is less than 300 mA or
• If total load current of a group exceeds permissible limit.

Figure 3 : Output section circuit

Installation
Refer printed manual PD-2002-052 Nexgen 5000 PLC Installation Manual to know
• the installation of the module in the PLC rack.
• the installation of entire PLC system and safety precautions to be followed.
• the wiring inside the control panel and outside the control panel.
The latest manual in pdf format ED-2002-052 along with all the related manuals are
available on the website:
www.messungautomation.com/download/manual

Precautions
Ensure that the total load in a group at any time does not exceed 4 Amps
and the total load on a module at any time does not exceed 8 Amp.
To protect output devices from voltage surges generated by the inductive
loads, freewheeling diodes are required to be put across the loads
directly. Failure to put diode may damage the output devices on the
module and or create EMI interference problems. Suggested device is
1N4007 or IN5408.
User should take care of external supplies by providing appropriate fuse,
MCB protections where ever required. Similarly user can insert
appropriate safety control interlocks to ensure safe working of the module
in the application.
The application of AC voltage to any terminal of the module may damage
individual / group outputs or the entire module permanently.

3
Troubleshooting
Diagnostic Flowchart
The following flow charts illustrate various possibilities of faults with digital output
module and corrective action to be taken.

LED on Output module is ON

Output device is energized but not working as per Output device is not energized.
application requirement.

Probable reason Recommended action Probable reason Recommended action


1. Output is Unforce output.Forcing is 1. Low / no Check output device
forced to ON indicated by blinking 'ON' LED voltage across specifications. Check module
on Processor module. output specifications. Check load
2. Output circuit Check output specifications. supply voltage.
incompatibility Check for sink /source type of 2. Incorrect Check output device
connection for DC output wiring connections. Check common
device. connection on the module.
3. Application Check the application require- 3. Open circuit Output device may be faulty.
program fault ment and application program, Replace it. Check wiring for
double output updation open circuit, if any.
through coil or functions, etc.
4. Output switch- Check output device
4. Output circuit Try spare output channel if ing frequency specifications and the
damaged any or replace module. is high application need
5. Output device Check output device operation. 5. Output circuit Check freewheeling diode if
faulty damaged connected. Try spare output
channel if any or replace the
module

Figure 4 : Diagnostic flow chart if LED on output module is ON.

4
LED on Output module is OFF

Output device is de-energized but not working as Output device is energized.


per application requirement.

Probable reason Recommended action Probable reason Recommended action


1. Output is Unforce output. Forcing is 1. Output device is Check output device
forced to zero, indicated by blinking 'ON' LED incompatible specifications. Check module
on Processor module. specifications. If output device
2. Output circuit Check output specifications. is faulty, replace it.
incompatibility Check for sink I source type 2. Incorrect wiring Check output device
of connections for DC outputs. connections.
3. Application Check the application 3. Output OFF Check output device
program fault requirement and application state leakage specifications. Check module
program, double output current may specifications. If required
updation through coil or drive output connect dummy load across
functions, etc device output device
4. Output circuit Try spare output channel if 4. Short circuit Output device may be faulty.
damaged any or replace module. Replace it. Check wiring for
5. Output device Check output device operation. any short circuit, if any.
faulty 5. Output circuit Check freewheeling diode. Try
damaged spare output channel if any or
replace the module.

Figure 5 : Diagnostic flow chart if LED on output module is OFF

5
User safety guidelines
This manual provides information for the use of I/O Module. The manual has been written to
be used by trained and competent personnel. The definition of such a person or persons is as
follows:
a) DESIGN ENGINEER Any engineer who is responsible for the planning, design, and
construction of automatic equipment using the product associated with this manual
should be of a competent nature, trained and qualified to the local and national standards
required to fulfill the role.. These engineers should be fully aware of all the aspects of safety
with regards to automated equipment.
b) COMMISSIONING/SERVICE ENGINEER. Any engineer who is responsible for the
commissioning, use and maintenance of automatic equipment using the product
associated with this manual should be of a competent nature, trained and qualified to the
local and national standards required to fulfill the role. This includes being completely
familiar with all the associated documentation for the said system. Maintenance to be
carried out in accordance to the established safety practices.
c) OPERATORS. The personnel using the completed equipment should be trained to use
the product in a safe and coordinated manner in compliance to established safety
practices. They should be also familiar with documentation, which is relevant to the actual
operation of the equipment.
Note : The term-completed equipment refers to a third party constructed device, which
contains or uses the product associated with this manual.

Warning !
The specifications of product and contents of manual are subject to change without
notice. This manual has been prepared taking utmost care; the performance of the
final equipment depends on many other parameters beyond any control of Messung
Systems. Messung systems does not assume any responsibility/liability of any
damage to life or property that might result due to any malfunction due to design,
use, of the equipment using this component.

Revisions :
Edition Date Version Description
January 2004 1.0 First release

NEXGEN PLC I/O Module


16-Point 24 VDC Output Module (4716)
Document No.: PD-2002-008 V.1.0 A U T O M AT I O N P E O P L E
Published January, 2004
MESSUNG SYSTEMS
EL-2, J-Block, MIDC Bhosari,
Pune - 411026 (INDIA)
Tel. : (+91)-20-2712 0807, 2712 2807.
Email : marketing@ms.messung.com
PRINTED IN INDIA WEB : www.messungautomation.com

You might also like