This manual provides information for the use of the I/O Modules . The manual has
been written to be used by trained and competent personnel. The definition of such a
person or persons is as follows:
a) Any engineer who is responsible for the planning, design and construction of
automatic equipment using the product associated with this manual should be of a
competent nature, trained and qualified to the local and national standards required to
fulfill that role. These engineers should be fully aware of all aspects of safety with
regards to automated equipment.
b) Any commissioning or service engineer must be of a competent nature, trained and
qualified to the local and national standards required to fulfill that job. These engineers
should also be trained In the use and maintenance of the completed product. This
Includes being completely familiar with all associated documentation for the said
product. All maintenance should be carried out in accordance with established safety
practices.
c) All operators of the completed equipment should be trained to use that product in a
safe and coordinated manner in compliance to established safety practices. The
operators should also be familiar with documentation, which is connected with the
actual operation of the completed equipment.
Note: The term-completed equipment refers to a third party constructed device, which
contains or uses the product associated with this manual.
At various times through out this manual certain symbols will be used to highlight
points of Information, which are Intended to ensure the users personal safety and
protect the integrity of equipment. Whenever any of the following symbols are
encountered it’s associated.
Note must be read and understood. Each of the symbols used is listed below; with a
brief description of its meaning.
Warning !
This product can only function correctly and safely if it is
transported, stored, setup, and installed correctly, and operated
and maintained as recommended.
Warning !
1. Module Overview
This analog voltage/current output module takes digital value data from
the Processor module and output an equivalent analog output voltage.
This is R – 2R type D/A conversion. It provides two isolated channels
with 12-bit resolution (11 bits + 1 sign bit). The channels provide voltage
or current range as
The resolution is 4.88 mV / 7.8 µA.. This module handles digital value
data for generating equivalent analog output just like discrete output type
of module and hence data transfer with the Processor module takes
place in output scan.
The figure 1 on next page shows the front view of 2-channel analog
output module.
4332
ANALOG OUTPUT
2 CH – V /I
Module
NO 24 V SUPPLY Status
Front Shield LED
Plate
Terminal Block
Fixing Screw
VOUT1
01
GND1
02
20 Pin I REF 1
03
Removable SHIELD
04
Terminal Block 05
I OUT1
GND 1
06
SHIELD
07
08
VOUT2
09
GND2
10
I REF 2
11
SHIELD
12
I OUT2
13
GND 2
14
SHIELD
15
16
+24 V.
17
0V
18
EARTH
19
FG
20
Terminal Block
Fixing Screw 2 CH
ANALOG OUTPUT
V/I
2. Module Operation
This chapter helps in getting started with the 2-channel analog output
module. It describes the basic operation of the module. This chapter
explains following points.
• Block Diagram
• Data Range and Resolution
• IO and Memory Mapping
Serial
Data DAC1 Channel 1
Opto Serial
Isolation R-2R
Interface 0 to ± 10 VDC
Output Signal
Control
Opto Output 1
Isolation Driver Voltage to
Current
Conversion 4 to 20 mA
CPU Output Signal
Serial
Data DAC2 Channel 2
Opto Serial
Isolation R-2R
Interface 0 to ± 10 VDC
Output Signal
Module
Interface Output 2
Opto
Circuit Isolation Driver Voltage to
Current
Conversion 4 to 20 mA
Output Signal
No 24 V
Supply
Signal
Opto Miniature
+5V Isolation Glass Fuse
+12 V
+24 VDC
-12 V
GND 0V
Supply for +5 V DC to DC
DAC Circuit Converter Earth
-5 V
GND
0 VDC
$0000
4 mA
$0 20 mA
$ 7FF
The module provides 12-bit resolution (11 bit + 1 sign bit). The figure
above shows digital data and associated output voltage and current
values.
For voltage range of –10 V to +10 V, the digital value ranges from -2048
to +2047. The resolution is the smallest detectable change in analog
output signal. For –10 V to +10 V range, the voltage span is 20 V and
there can be 4096 (12 bits) equal steps. Each step corresponds to –
20 V / 4096 = 4.88 mV
For current range of 4 to 20 mA, the digital value ranges from 0 to +2047.
The resolution is the smallest detectable change in analog output signal.
For 4 to 20 mA range, the current span is 16 mA and there can be 2048
(11 bits) equal steps. Each step corresponds to –
16 mA / 2048 = 7.8 µA
The table below shows typical data values in decimal as well as
hexadecimal format and their equivalent voltage values.
2.3 IO Mapping
The figure below shows I/O mapping related to 2-channel analog output
module.
Channel 1
Input Output
Output Scan
Module
Channel 1 Interface Circuit
Voltage
Output
VOUT1
01
GND1
02
I REF 1
03
Earth SHIELD
04
Connect this shield to Connect this shield 05
I OUT1
Earth busbar or to shield to ‘SHIELD’ GND 1
06
terminal on external terminal. SHIELD
07
Electronic controller to 08
which output signal is VOUT2
09
GND2
connected. 10
I REF 2
11
Current SHIELD
12
Output I OUT2
13
GND 2
14
SHIELD
15
16
+24 V.
17
Earth 0V
18
EARTH
19
FG
20
2 CH
+ 24 V GND Earth ANALOG OUTPUT
Earth V/I
In figure 6, first channel is connected for analog voltage output (-10 VDC
to +10 VDC). For interfacing analog signals, 20-pin removable terminal
block is provided. Voltage output is taken from terminals V OUTn and
GNDn. n is a channel number.
Second channel is connected for analog current output (4 to 20 mA).
Current output is taken from terminals I OUTn and GNDn. n is a channel
number. To get current output, it is necessary to short terminals V OUTn
and I REFn .
Input module in first two slots consumes IB0 to IB7 of input image. 2-
channel analog output module in slot 2 consumes four bytes i.e. QB8 to
QB11 of output image. 16 DC output module in slot 3 consumes QB12
and QB13 of output image.
4.2 Programming
5. Troubleshooting
• Module as a whole
• Specific channel only
• Application Program.
Equipment required
Screw driver
Digital multi-meter with measuring facility for
• DC voltage (with high precision)
• Continuity and resistance
Set up for on line monitoring of application program as follows
PC with Programming and Documentation software.
PC to Nexgen PLC Cable
Diagnosis Over
ON No 24V Supply OFF
LED status? O ERR LED
ON Status ? OFF
Replace Module
Module Error
ON System bit Status? OFF
Replace Module
YES Module NO
working OK?
Diagnosis Over
A
Voltage output OK as
NO per binary data? YES
Voltage output OK as
NO per binary data? YES
Note – For healthy operation of module always ensure that supply to module is within specified
range i.e. 18 VDC to 30 VDC including ripple.
If PLC is in 'STOP' mode, voltage output remains at zero whereas current output remains at 4 mA.