Messung Systems NEXGEN-2000 PLC I/O Modules

NEXGEN-2000 Series of PLCs


8- Point Relay Output Module (2711)

Document No.: ED-2002-210

Version: 1.0

Published July 2005

MESSUNG SYSTEMS
EL-2, J- Block MIDC Bhosari,
Pune – 411026.(INDIA)

Tel: (+91)-020-27102000
Fax: (+91)-020-27102100
Email : marketing@ms.messung.com
WEB: www.messungautomation.com

ED-2002-210 8 Pt Relay Output Module (2711) Published July 2005


Document No.: ED-2002-210/V1.0 Page 1 of 12
NEXGEN PLC I/O Modules Messung Systems

Revision

Version Date Description

8- Point P.F. Relay Output Module (2711) for


1.0 July 2005
NEXGEN-2000 Series of PLCs.

Published July 2005 ED-2002-210 8 Pt Relay Output Module (2711)


Page 2 of 12 Document No.: ED-2002-210/V1.0
Messung Systems NEXGEN-2000 PLC I/O Modules

INDEX
1. 8- POINT P.F. RELAY OUTPUT MODULE (2711) ................................................................. 5
1.1 MODULE SPECIFICATIONS ........................................................................................................ 5
1.2 ELECTRICAL LIFE OF RELAYS –................................................................................................ 6
2. MODULE WIRING ...................................................................................................................... 7
3. TROUBLESHOOTING................................................................................................................ 9
3.1 OUTPUT SECTION ..................................................................................................................... 9
3.2 DIAGNOSTIC FLOWCHART ...................................................................................................... 10

INDEX OF FIGURES
FIGURE 1 : FRONT VIEW OF 8- POINT P.F. RELAY OUTPUT MODULE ....................................................... 5
FIGURE 2 : FIELD CONNECTIONS FOR 8- POINT P.F. RELAY OUTPUT MODULE ......................................... 7
FIGURE 3 : OUTPUT SECTION CIRCUIT....................................................................................................... 9
FIGURE 4 : DIAGNOSTIC FLOW CHART IF LED ON OUTPUT MODULE IS ON. .......................................... 10
FIGURE 5 : DIAGNOSTIC FLOW CHART IF LED ON OUTPUT MODULE IS OFF ......................................... 11

ED-2002-210 8 Pt Relay Output Module (2711) Published July 2005


Document No.: ED-2002-210/V1.0 Page 3 of 12
NEXGEN PLC I/O Modules Messung Systems

Guidelines for the safety of the user and protection of I/O modules

This manual provides information for the use of I/O Module. The manual has
been written to be used by trained and competent personnel. The definition of
such a person or persons is as follows:
a) DESIGN ENGINEER: Any engineer who is responsible for the planning,
design, and construction of automatic equipment using the product
associated with this manual should be of a competent nature, trained
and qualified to the local and national standards required to fulfill the
role. These engineers should be fully aware of all the aspects of safety
with regards to automated equipment.
b) COMMISSIONING/SERVICE ENGINEER: Any engineer who is
responsible for the commissioning, use and maintenance of automatic
equipment using the product associated with this manual should be of a
competent nature, trained and qualified to the local and national
standards required to fulfill the role .This includes being completely
familiar with all the associated documentation for the said system.
Maintenance to be carried out in accordance to the established safety
practices.
c) OPERATORS: The personnel using the completed equipment should
be trained to use the product in a safe and co-coordinated manner in
compliance to established safety practices. They should be also familiar
with documentation, which is relevant to the actual operation of the
equipment.
Note: The term-completed equipment refers to a third party constructed
device, which contains or uses the product associated with this manual.

Warning !

This product can only function correctly and safely if it is


installed correctly and operated and maintained as
recommended.

Warning !

The specifications of product and contents of manual are subject


to change without notice.

Published July 2005 ED-2002-210 8 Pt Relay Output Module (2711)


Page 4 of 12 Document No.: ED-2002-210/V1.0
Messung Systems NEXGEN-2000 PLC I/O Modules

1. 8- Point P.F. Relay Output Module (2711)


This is NEXGEN-2000 PLC family I/O module. This is 8-point
discrete output module which controls 24-240 VAC and 24 VDC
output through electro-mechanical relay contacts.
The discrete output module receives status from Processor Module
in order to switch ON or OFF various field actuators and elements
like relays, contactors, solenoid valves, etc.

1.1 Module Specifications


The technical specifications are given in table.
Number of outputs 8
24 – 250 VAC, 47-53Hz
Voltage rating
24 VDC
Non Latching Normally Open (NO)
Type of Output
contact (in groups of 2 and 1)
Output device Electro-mechanical relay
Provided on CPU module via
Indication for output
multiplexed dot matrix LED display.
1 Amp at 250 VAC
(Resistive load)
Contact Rating
1 Amp at 30 VDC
(Resistive load)
Response OFF to ON 10 ms
time ON to OFF 5 ms
Minimum load 1 mA
0.5 Amp
Current per output (Maximum 2 Amp per group)
(Maximum 12 Amp per module)
Refer table and graphs given on next
Electrical Life
page.
Mechanical Life 20,000,000
No on board protection for relay
contacts
• Use external RC snubber across
Protections
relay contact for AC loads.
• Use external Free-Wheeling
diode across DC loads.
Relay Coil Optical (1.5 KV from internal bus)
Isolation
Field devices Galvanic
Back-plane current 275 mA (All outputs ON)
Relay coil supply
5 VDC (25 mA per output)
(Internal)
IO point consumption 8 Output points
Two removable 10-pin terminal
Connection
blocks
Ordering code 2711

Figure 1 : Front View of 8- Point P.F. Relay Output Module

ED-2002-210 8 Pt Relay Output Module (2711) Published July 2005


Document No.: ED-2002-210/V1.0 Page 5 of 12
NEXGEN PLC I/O Modules Messung Systems

1.2 Electrical Life of Relays –

Voltage Current Type of Load Electrical Life (cycles)


250 VAC 1 Amp Resistive 500,000
Inductive 200,000
500 mA Resistive 1000,000
Inductive 300,000
30 VDC 1 Amp Resistive 500,000
Inductive 200,000
500 mA Resistive 1000,000
Inductive 300,000

* The graphs shown below are provided by relay manufacturer specification sheet.
There is some degree of variation in relay characteristics and so this data should be
used only for reference purpose.

Published July 2005 ED-2002-210 8 Pt Relay Output Module (2711)


Page 6 of 12 Document No.: ED-2002-210/V1.0
Messung Systems NEXGEN-2000 PLC I/O Modules

2. Module Wiring
The front side of the module is provided with two 10-pin terminal blocks for wiring of
field output devices. These are easily removable terminal blocks which facilitate
immediate replcement of module without removing wiring. This module can be
inserted in any of the I/O slots.

L1

L2

L3

L4

L5

L6

L7

L8

24-250 VAC Neutral


OR OR
+24 VDC GND

Figure 2 : Field Connections for 8- point P.F. Relay Output Module

ED-2002-210 8 Pt Relay Output Module (2711) Published July 2005


Document No.: ED-2002-210/V1.0 Page 7 of 12
NEXGEN PLC I/O Modules Messung Systems

This is potential free relay contact type of output module. In all 8 outputs are available
as potential free output points. Common points (C0, C1, C2,…C7) per output point
are provided to connect either 24-250 VAC or 24 VDC supply. Connect output
device ( AC or DC as per specifications) to output point as shown in figure with other
terminal of output device connected to Neutral or GND.

User should ensure that total load current per point should not exceed
1 Amp and it should not exceed 8 Amp per module.

No external power supply is required for energizing relays on module.

Recommendations for using relay type of outputs –

Use external RC snubber across relay contact for AC loads.


Use external Free-Wheeling diode across DC loads.
It is always recommended to insert external fuse protection (1 Amp) for
each output to avoid damage to output relay contact in case of short circuit
at output device side.

Maximum voltage between any two pins not to exceed 250 VAC. Hence
connection to two and three phase supply not permitted, if line voltage exceeds
110 VAC.

Replacement of Module:
From user safety point of view, replacement of live modules is not allowed.
Module replacement is allowed only after PLC and machine power is switched
off and the voltage at terminal blocks is confirmed to be safe.
Switching off PLC power does not guarantee that a voltage at terminal blocks is
also turned off.
In order to ensure that user is consciously removing the module from the slot,
HV-Clips are provided at top surface of the base rack. This is safety feature in
addition to locking clips provided towards fascia of the module. Thus before
unlocking the HV-Clip for the module, user must ensure that the power supply
for actuating the field devices connected at output terminals is turned off.

Published July 2005 ED-2002-210 8 Pt Relay Output Module (2711)


Page 8 of 12 Document No.: ED-2002-210/V1.0
Messung Systems NEXGEN-2000 PLC I/O Modules

3. Troubleshooting
This section explains the output section of relay output module and diagnostic
flowchart.

3.1 Output Section


The figure below shows output section of relay output module.

24 – 250 VAC
OR
+5V +24 V DC

COM
Electro-
Mechanical
Relay

Output
Output Device like
From digital Relay / contactor/
circuit solenoid valve, etc

External RC Snubber
0V for AC loads
Neutral
OR
OR
Free-Wheeling Diode
GND
for DC loads

Figure 3 : Output section circuit

ED-2002-210 8 Pt Relay Output Module (2711) Published July 2005


Document No.: ED-2002-210/V1.0 Page 9 of 12
NEXGEN PLC I/O Modules Messung Systems

3.2 Diagnostic Flowchart


The following flow chart illustrates various possibilities of faults with discrete output
module and corrective action to be taken.

Output status indicating LED on CPU module is ON.


There is no I/O error indication for the module.

Output device is energized but not working Output device is not energized.
as per application requirement.

Probable reason Recommended action Probable reason Recommended action


1. Output is forced Un-force output. 1. Low / no voltage Check output device
to TRUE state Forcing is indicated by across output specifications. Check
blinking ‘R’ LED on module specifications.
Processor module. Check source voltage.
2. Output circuit Check output 2. Incorrect wiring Check output device
incompatibility specifications. connections. Check
3. Application Check for the effect of common connection
program fault (JMP), double output 3. Open circuit Output device may be
updating through coil or faulty. Replace it. Check
functions, etc. wiring for open circuit, if
4. Output circuit Try changing to spare any.
damaged output channel if 4. Output switching Check output
available, otherwise frequency is high specification and
replace module. application requirement.
5. Output device Check output device 5. Output circuit Try changing to spare
faulty operation. damaged output channel if
available, otherwise
replace module.

Figure 4 : Diagnostic Flow chart if LED on Output Module is ON.

Published July 2005 ED-2002-210 8 Pt Relay Output Module (2711)


Page 10 of 12 Document No.: ED-2002-210/V1.0
Messung Systems NEXGEN-2000 PLC I/O Modules

Output status indicating LED on CPU module is OFF.


There is no I/O error indication for the module.

Output device is de-energized but not Output device is energized.


working as per application requirement.

Probable reason Recommended action Probable reason Recommended action


1. Output is forced Un-force output. 1. Output device is Check output device
to zero. Forcing is indicated by incompatible specification. Check
blinking 'R' LED on module specifications.
Processor module. If output device is
2. Output circuit Check output faulty, replace it.
incompatibility specifications. 2. Incorrect wiring Check output device
3. Application Check for the effect of connections.
program fault (JMP), double output 3. Short circuit Output device may be
updating through coil or faulty. Replace it.
functions. etc Check wiring for any
4. Output circuit Try changing to spare short circuit, if any.
damaged output channel if 4. Output circuit Try changing to spare
available, otherwise damaged output channel if
replace module. available, otherwise
5. Output device Check output device replace module.
faulty operation.

Figure 5 : Diagnostic Flow chart if LED on Output Module is OFF

ED-2002-210 8 Pt Relay Output Module (2711) Published July 2005


Document No.: ED-2002-210/V1.0 Page 11 of 12
NEXGEN PLC I/O Modules Messung Systems

MESSUNG SYSTEMS
EL – 2, J - Block, MIDC, Bhosari,
PUNE – 411 026. INDIA
Tel. – (+91) –020 – 2712 2000
Fax. – (+91) –020 – 2712 2100

NEXGEN PLC I/O Modules


8- Point P. F. Relay Output Module (2711)

Document No.: ED-2002-210

Published July 2005 ED-2002-210 8 Pt Relay Output Module (2711)


Page 12 of 12 Document No.: ED-2002-210/V1.0