Professional Documents
Culture Documents
Experiment # 9:
DIFFERENTIAL PROTECTION
1
Differential circuits are used to
measure the difference between two
(or more) currents. A distinction is
made between longitudinal
differential protection and transverse
differential protection.
In longitudinal differential
protection the current is measured,
for example, at both ends of the
line or both sides of the
transformer. In this case the line or
the transformer is the protected
object. In transverse differential
protection the differential current is
the difference between the currents
in two parallel parts of the system.
2
Differential Protection for Transformers :
The circuit shown in the diagram is for experimental purposes only. The point is to study
some of the difficulties to be overcome in creating a reliable transformer differential protection
and the circuit must not be regarded as an example of protection to be used in practice.
The circuit shows a resistor R1 which is used to simulate faults in the protected object, a
load resistor R2 , which is used to vary the load current, and a load inductor for the same purpose.
Current relay RXIG 2 of the differential protection must always react immediately for
internal faults and must be completely unaffected by external faults. When an internal fault
occurs, the circuit-breakers must disconnect the transformer.
Although transformer protective relays are normally required to operate rapidly, time-lag
relay RXKB 1 or (RXKN 1) has been included to make it possible to observe switching surges
and to get some idea of their duration.
Equipment:
1. Relay units RXIG 2 (25 mA), RXKB 1, RXSF 1.
2. Transformer T1 (single-phase, 1KVA, 220/4 x 55V).
3. Digital Ammeters A1, A2, A3 and A4.
4. Current Transformers T2 and T3.
5. Resistor R1 ( step and smooth resistors ).
6. Load Resistor R2.
7. Load Inductor L.
8. Main Switch S1.
9. Contractors S2 and S3.
10. Push-button enclosure.
Method :
1. Setup the circuit shown in Figure 1, but do not connect the arm R1 - A4 .
2. Set RXKB 1 to 10 x 0.35 and the current transformers T2 & T3 ratios to 10/1 A.
3. Select scale factor 1 on RXIG 2 (i.e. a set operating value of 25 mA).
4. Check that RXSF 1 shows a red flag, indicating that auxiliary voltage is being
supplied to the relays.
5. Adjust the source voltage to 220V and close S1.
6. Close S2 by means of "ON 1".
7. Measure the differential current I3 and enter it in table 1 a.
8. Enter the reading of I1 in Table 1-a.
9. Perform "X" on/off operations, count the number of relay operations at switching-
on, (indicated by the second flag of RXSF 1), and enter this on the appropriate
line of Table 1-a.
10. Set scale factor 3 on RXIG and repeat step 9.
11. Chose some intervening values of the scale factor and take the readings again.
(use the whole table).
12. Alter the current transformers T1 and T2 ratio to 25/1 A.
Circuit Diagram:
13. Set scale factor 1 (25 mA). Repeat steps 9-11 and enter the readings in Table
1-b.
14. Check that R1 is set to maximum, and connect arm R1 - A4 .
15. Close S 2 .
16. Increase I4 until the relay operates, and enter the readings in Table 2.
17. Set R1 to maximum, set R2 for the smallest possible value of I2 , and close S3.
18. Adjust R2 for an I2 of 1.5A.
19. Increase I4 and note the currents at relay operation, repeat for I2 =2.0 A.
Q1. Does it make any difference if the terminal of one of the C.T's is reversed.
1 25 /3 x=3
1.25 31 /3 x=3
1.5 38 /3 x=3
1.75 44 /5 x=5
2 50 /10 x=10
2.5 62 /3 x=3
2.75 69 /3 x=3
3 75 /3 x=3
Primary current I1 = A
Actual differential current I3 = mA
The best setting = mA
Table 1-b: (At no load C.T. ratio 25/1 A).
RXJG2 Number of relay
operations out of "X"
scale factor operating value mA
1 25 /10 x=10
1.25 31 /5 x=5
1.5 38 /5 x=5
1.75 44 /3 x=3
2 50 /3 x=3
2.25 56 /3 x=3
2.5 62 /3 x=3
2.75 69 /3 x=3
3 75 /3 x=3
Primary current I1 = A
Actual differential current I3 = mA
The best setting = mA
Table 2.
measurement transformer RXIG 2 I1 12 13 14
no. load (A) (A) (mA) (mA)
scale factor op. val.(mA)
1 No Load 1.0 0.0
ANALYSIS:
The effect of the switching surges can be studied in any required degree of detail. The value in
Table 1-a and 1-b from several experiment groups can be combined to provide sufficient
information to permit a graph to be drawn showing number of relay functions as a function of
scale factor.
* Draw a graph of relative operation frequency (n) as a function of the scale factor (F).
Where:
/
number of relay operations
n = ————————-————— x 100 (%)
number of switch operations
F = scale factor.
* 03- The difference current I3 is affected by the load current I2 and the
leakage current 14. What conclusions do you draw about this from
measurements 18 -22?
12