INDEX OF SINGLE LINE DIAGRAMS:

SL. # DRAWING NUMBER DESCRIPTION REV. DATE

IEC-E01-C12-001 05/01/17
1 TYPICAL PROTECTION MV SINGLE LINE DIAGRAM - MOTOR CONTROLLED BY FUSE/CONTACTOR. 1

2 IEC-E01-C12-002 TYPICAL PROTECTION MV SINGLE LINE DIAGRAM - MOTOR CONTROLLED BY CIRCUIT BREAKER 1 05/01/17

3 IEC-E01-C12-003 05/01/17
TYPICAL PROTECTION MV SINGLE LINE DIAGRAM - MOTOR WITH UNIT TRANSFORMER 1

4 IEC-E01-C12-004 1 05/01/17
TYPICAL PROTECTION MV SINGLE LINE DIAGRAM - LARGE SYNCHRONOUS MOTOR

IEC-E01-C12-005 25/03/18
5 TYPICAL PROTECTION LV SINGLE LINE DIAGRAM - MOTOR CONTROLLED BY FUSE/CONTACTOR 2

6 IEC-E01-C12-006 TYPICAL PROTECTION LV SINGLE LINE DIAGRAM - MOTOR CONTROLLED BY CIRCUIT BREAKER 2 25/03/18

IEC-E01-C12-007 05/01/17
7 TYPICAL PROTECTION MV SINGLE LINE DIAGRAM - MV/LV TRANSFORMER 750KVA AND 3000 KVA CONTROLLED BY FUSE-SWITCH COMBINATION 1

IEC-E01-C12-008 TYPICAL PROTECTION MV SINGLE LINE DIAGRAM - MV/LV TRANSFORMER 750KVA AND 3000 KVA CONTROLLED BY CIRCUIT BREAKER 05/01/17
8 1

IEC-E01-C12-009 TYPICAL PROTECTION MV SINGLE LINE DIAGRAM - MV/MV TRANSFORMER ( 3000 KVA) WITH FEEDER CABLE 500M 1 05/01/17
9

10 IEC-E01-C12-010 TYPICAL PROTECTION MV SINGLE LINE DIAGRAM - MV/MV TRANSFORMER ( 3000 KVA) WITH FEEDER CABLE 500M 1 05/01/17

IEC-E01-C12-011 05/01/17
11 TYPICAL PROTECTION MV SINGLE LINE DIAGRAM - SINGLE PLAIN FEEDER 1
REFERENCE DRAWINGS
12 IEC-E01-C12-012 TYPICAL PROTECTION MV SINGLE LINE DIAGRAM - MV SWITCHGEAR INCOMER AND BUSBAR 1 05/01/17
DRAWING NO. TITLE
IEC-E01-C12-013 05/01/17
1

t cannot be
13 TYPICAL PROTECTION LV SINGLE LINE DIAGRAM - LV SWITCHGEAR INCOMER AND BUSBAR -
-

14 IEC-E01-C12-014 TYPICAL PROTECTION LV/MV SINGLE LINE DIAGRAM -LV/MV CAPACITOR BANK 1 05/01/17

C
SABI
15 IEC-E01-C12-015 TYPICAL PROTECTION LV/MV SINGLE LINE DIAGRAM - EMERGENCY DIESEL GENERATOR 1 05/01/17

C. I
tten approval from
al property of SABI
MAR UPDATED WITH MINOR
1 AMY MAA MAA
25,2018 CORRECTION

or wri
JAN
0 UPDATE FOR SES KK MAA MAA
05,2017

denti
thout pri
REV. DATE DESCRIPTION DRAWN CHECKED APPROVED

s the confi
Saudi Basic Industries Corporation
Engineering and Project Management

ed or used for any other purpose wi


Jubail, Kingdom of Saudi Arabia

s docum ent i
PROJECT DESCRIPTION

n thi
STANDARD DRAWING
FOR SABIC PROJECT

ned i
-

on contai
DRAWING TITLE

TYPICAL PROTECTION SINGLE LINE DIAGRAM -


INDEX & SYMBOLS

osed, copi
nform ati
SCALE PLANT NAME AREA/UNIT SIZE

NTS SABIC - A3

The i
scl
A.I.D. DRAWING NUMBER SHT. NO. REVISION

di
- IEC-E01-C12 1 OF 2 1
FILE NAME: IEC-E01-C12.DGN
CONDUCTOR AND CABLES LAMPS TRANSFORMERS AND CONTACTS, SWITCHES STARTING EQUIPMENT AND
TRANDUCERS AND SWITCHGEARS REMOTE CONTROL UNITS

SIGNAL LAMP AUXILIARY MAKE REMOTE ON-OFF


CONDUCTOR OFF ON
RD - RED MAKE CONTACT C-1 CONTACT ENERGISED SAFETY SWITCH ON
PUSH BUTTON
GN - GREEN TRANSFORMER, SINGLE A BY CONTACTOR (ON/OFF) OFF WITHOUT
EARTHED CONDUCTOR PHASE, GENERAL AMMETER
AUXILIARY MAKE
DISCHARGE LAMP BREAK CONTACT EMERGENCY PUSH
PROTECTIVE EARTHED C-2 BREAK CONTACT
Hg - MERCURY BUTTON
CONDUCTOR A BY CONTACTOR
No - SODIUM REMOTE ON-OFF
OFF ON
EARTHED CONDUCTOR SWITCH WITHOUT
TRANSFORMER, THREE MAKE CONTACT VOLTMETER AMMETER
CONNECTING DEVICES PHASE, GENERAL EARLT CLOSING SELECTOR A REMOTE ON-OFF
OFF ON
SWITCH SWITCH WITH
PROTECTIVE EARTHED SOCKET OUTLET (POWER) AMMETER
CONDUCTOR GENERAL SYMBOL
BREAK CONTACT RELAY COILS
LATE OPEN
TRANSFORMER, THREE
PHASE, DELTA-STAR A REMOTE ON-OFF
EARTHING BOSS PLUG AND SOCKET
GROUNDED ON PUSH BUTTON
MAKE CONTACT RELAY COIL WITH AMMETER
DELAYED CLOSING GENERAL OFF
T-CONNECTION
CURRENT TRANSFORMER RELAY COIL OF A
DRAWOUT CONNECTION BREAK CONTACT
CONDUIT ENTRY GENERAL SYMBOL SLOW RELEASING
(ELECTRICAL DISCONNECTION) DELAYED OPENING RELAY (ON DELAY)

STUFFING GLAND RELAY COIL OF A


(CABLE GLAND) CURRENT TRANSFORMER MAKE CONTACT SLOW RELEASING REFERENCE DRAWINGS
TERMINAL STRIP SURROUNDING THREE DELAYED OPENING RELAY (OFF DELAY)
CONDUCTOR (CORE DRAWING NO. TITLE
BALANCE)
BATTERIES,

t cannot be
RELAY COIL OF A - -
MECHANICAL CONTROLS BREAK CONTACT MECHANICALLY
SEMI-CONDUCTORS DELAYED CLOSING LATCHED

C
A

SABI
CURRENT TRANSDUCER
ELECTRICAL MACHINES LINK mA RELAY
AND POWER CONVERTERS

C. I
A AMMETER

tten approval from


LINK CHANGE-OVER BREAK
BEFORE MAKE CONTACT

al property of SABI
BATTERY OF ACCUMMULATORS
DR PRIMARY CELLS
V VOLTMETER
WITHDRAWABLE
LOCKING DEVICE, PADLOCK
FUSED CONTACTOR
FACILITY w WATT-HOUR METER DISCONNECTOR COMBINATION
RECTIFIER, POWER CONVERTER
ISOLATOR
AC/DC C POWER FACTOR METER
AUTOMATIC RETURN JAN UPDATE AS PER
1 JA MAA MAA
05,2017 DC-DC-16120315

or wri
INVERTER, POWER CONVERTER SWITCH DISCONNECTOR FEB
0 UPDATE FOR SES JA MAA MAA
AC/DC NON-AUTOMATIC RETURN ON-LOAD ISOLATING 08,2016
PROTECTIVE DEVICES AND

denti
SWITCH

thout pri
REV. DATE DESCRIPTION DRAWN CHECKED APPROVED
MEASURING RELAYS
SEMI-CONDUCTOR DIODE AUTOMATIC MANUAL

s the confi
CONTROL POWER
GENERAL SYMBOL CONTACTOR TRANSFORMER (CPT) Saudi Basic Industries Corporation
WITH PRIMARY Engineering and Project Management

ed or used for any other purpose wi


MANUALLY OPERATED FUSE, GENERAL CURRENT LIMITING Jubail, Kingdom of Saudi Arabia
LIGHT EMITTING DIODE (LED) CONTROL WITH LOCKING FUSE AND
DEVICE SECONDARY

s docum ent i
CIRCUIT BREAKER
SYMBOLS INDICATING THE FUNCTION MCB PROTECTION
ACTUATOR, OPERATED BY 2
STATIC SWITCH PUSHING WHICH CAUSES RELAY TO OPERATE:

ACTUATOR, OPERATED BY
TURNING THERMAL EFFECT PROJECT DESCRIPTION
INDUCTION
M E EXCITER WITHDRAWABLE

n thi
MOTOR
ACTUATOR, (ACTUATED BY CIRCUIT BREAKER
STANDARD DRAWING
THERMAL DEVICE) FOR SABIC PROJECT

ned i
SYNCHRONOUS EARTH-FAULT CURRENT
MS
MOTOR ACTUATOR, (ACTUATED BY -

on contai
LIQUID LEVEL) DRAWING TITLE
TERMINAL IDENTIFICATION MINIATURE
OVERCURRENT
rpm TACHOMETER CIRCUIT BREAKER TYPICAL PROTECTION SINGLE LINE
TERMINAL IN INTERFACING PANEL DIAGRAM - INDEX & SYMBOLS

osed, copi
nform ati
CONTACTOR
TERMINAL IN FIELD INSTRUMENT N C (ENERGISING COIL) SCALE PLANT NAME AREA/UNIT SIZE
NEUTRAL EARTHING RESISTOR
G NTS SABIC - A3
R

The i
scl
TERMINAL IN LV PANEL A.I.D. DRAWING NUMBER SHT. NO. REVISION

di
- IEC-E01-C12 2 OF 2 1
FILE NAME: IEC-E01-C12.DGN
LEGEND:-
125 VDC DC SUPPLY BUS :DIRECTION OF SIGNAL

:CONTROL CABLE (INSIDE THE PANEL)


230V,1PH,AC SPACE HEATER SUPPLY BUS NOTES:- :WINDING TEMPERATURE DETECTOR
26R
LV BUS PHASE BUS :UNDER VOLTAGE RELAY
1. THIS IS A TYPICAL PROTECTION SINGLE LINE DIAGRAM. THIS DRAWING SHALL 27
3 BE READ ALONGWITH E03-G02-GUIDELINE FOR LV & MV POWER SYSTEM 38B :BEARING TEMPERATURE DETECTOR
230V,1PH,AC PT SUPPLY BUS PROTECTION APPLICATIONS. OTHER SPECIFIC PROTECTION OPTIONS SHALL BE
49 :THERMAL OVERLOAD RELAY
SELECTED AS PER SPECIFIC REQUIREMENTS OF THE PROJECT IN CONJUNCTION
AND APPROVAL OF SABIC. 50N :INSTANTANEOUS EARTH FAULT RELAY

51 :OVER CURRENT RELAY


2. THE RELAY PROTECTION FUNCTIONS ARE SHOWN USING ANSI NUMBER CODES EVEN
FOR IEC SET OF DRAWINGS, FOR EASE OF READING. 51N :EARTH FAULT RELAY (CORE BALANCE)

51LR :OVERCURRENT (LOCKED ROTOR PROTECTION RELAY)


3. REFER TO IEC *(FIGURE II-ELECTRICAL-PROCESS CONTROL INTERFACE SCHEME)
2
IN SES IEC-E02-G01-ELECTRICAL SYSTEM DESIGN CRITERIA*. RELAYS SHALL MCB :MINIATURE CIRCUIT BREAKER
HAVE COMMUNICATION CAPABILITY WITH SCADA SYSTEM.
3
2
N.C.
NOTE-4 NOTE-5 4. FOR SPACE HEATER CONTROL, N.C AUXILIARY CONTACT OF CONTACTOR SHALL BE
PROVIDED IN PARALLEL WITH CONTACT OF WITHDRAWABLE UNIT (CLOSED IF
WITHDRAWN).
CONTROL
SUPPLY
5. ALL CPT PRIMARIES SHALL BE PROTECTED WITH CURRENT LIMITING FUSES.
FUSE FAILURE ALARM CONTACTS SHALL BE PROVIDED.
2
ON TRIP 6. POSITION INDICATION REQUIRED AS SHOWN FOR ON-OFF OF LCS.
3
7. WINDING AND BEARING TEMPERATURE DETECTION AND MONITORING SHALL BE
OFF CONTACTOR PROVIDED FOR MOTORS 75HP/55KW AND LARGER.
NOTE-6 CONTROL
SUPPLY 8. REFER SES IEC-E17-S01 CLAUSE 13.3 FOR MINIMUM ALARM REQUIREMENTS TO
ALARM ANNUNCIATOR PANEL.
3 27 49 50N

51 51N 51LR

REFERENCE DRAWINGS
DRAWING NO. TITLE

t cannot be
- -

C
SABI
C. I
tten approval from
al property of SABI
MAR UPDATED WITH
2 AMY MAA MAA
25,2018 MINOR CORRECTION
JAN UPDATE AS PER
1 JA MAA MAA
05,2017 DC-DC-16120315

or wri
OCT
0 UPDATE FOR SES JA MAA MAA
23,2016

denti
thout pri
REV. DATE DESCRIPTION DRAWN CHECKED APPROVED

s the confi
Saudi Basic Industries Corporation
2 3 6
Engineering and Project Management

ed or used for any other purpose wi


N N 2
Jubail, Kingdom of Saudi Arabia

s docum ent i
A

M OFF ON

SPACE NOTE-6
PROJECT DESCRIPTION
ATOR PANEL
PROCESS CONTROL

ON
STATUS TO CONTROL ROOM
NOTE- 3

NOTE- 8

HEATER
TO SUBSTATI

n thi
STANDARD DRAWING
FOR SABIC PROJECT

ned i
ANNUNCI

-
ALARM

on contai
DRAWING TITLE
FROM

TYPICAL PROTECTION LV SINGLE LINE DIAGRAM-


26R MOTOR CONTROLLED BY

osed, copi
38B

nform ati
NOTE-7
FUSE/CONTACTOR
SCALE PLANT NAME AREA/UNIT SIZE

NTS SABIC - A3

The i
scl
A.I.D. DRAWING NUMBER SHT. NO. REVISION

di
- IEC-E01-C12-005 1 OF 1 2
FILE NAME: IEC-E01-C12-005.DGN
LEGEND:-
125 VDC
NOTES:- :DIRECTION OF SIGNAL
DC SUPPLY BUS
1. THIS IS A TYPICAL PROTECTION SINGLE LINE DIAGRAM. THIS DRAWING SHALL :CONTROL CABLE (INSIDE THE PANEL)
230V, 1PH, AC
SPACE HEATER SUPPLY BUS BE READ ALONGWITH E03-G02-GUIDELINE FOR LV & MV POWER SYSTEM
27 :UNDER VOLTAGE RELAY
PROTECTION APPLICATIONS’. OTHER SPECIFIC PROTECTION OPTIONS SHALL BE
LV BUS 46 :PHASE UNBALANCE RELAY
LV BUS SELECTED AS PER SPECIFIC REQUIREMENTS OF THE PROJECT IN CONJUNCTION
230V, 1PH, AC AND APPROVAL OF SABIC 49 :THERMAL OVERLOAD RELAY
PT SUPPLY BUS
49S :STALLING RELAY
2. THE RELAY PROTECTION FUNCTIONS ARE SHOWN USING ANSI NUMBER CODES EVEN
50 :INSTANTANEOUS OVERCURRENT RELAY (HIGH SET)
FOR IEC SET OF DRAWINGS, FOR EASE OF READING.
50N :INSTANTANEOUS EARTH FAULT RELAY
2 3. REFER TO *(FIGURE II-ELECTRICAL-PROCESS CONTROL INTERFACE SCHEME) IN
51 :OVER CURRENT RELAY
SES E02-G01-ELECTRICAL SYSTEM DESIGN CRITERIA*. RELAYS SHALL HAVE
2 51N :EARTH FAULT RELAY (CORE BALANCE)
COMMUNICATION CAPABILITY WITH SCADA SYSTEM.
CONTROL 51LR :OVERCURRENT (LOCKED ROTOR PROTECTION RELAY)
TRIP
SUPPLY 4. FOR SPACE HEATER CONTROL, N.C AUXILIARY CONTACT OF CONTACTOR SHALL BE
MCB :MINIATURE CIRCUIT BREAKER
N.C. PROVIDED IN PARALLEL WITH CONTACT OF WITHDRAWABLE UNIT (CLOSED IF
NOTE-4 3
WITHDRAWN).

5. ALL VT PRIMARIES SHALL BE PROTECTED WITH CURRENT LIMITING FUSES. FUSE


FAILURE ALARM CONTACTS SHALL BE PROVIDED.

6. POSITION INDICATION REQUIRED AS SHOWN FOR ON-OFF OF LCS.

27 46 49 7. WINDING AND BEARING TEMPERATURE DETECTION AND MONITORING SHALL BE


3
PROVIDED FOR MOTORS 75HP/55KW AND LARGER.
49S 50 50N 8. REFER TO SES IEC-E17-S01 CLAUSE 13.3 FOR MINIMUM ALARM REQUIREMENTS
TO ALARM ANNUNCIATOR PANEL.
51 51LR 51N

REFERENCE DRAWINGS
DRAWING NO. TITLE

t cannot be
- -

C
SABI
C. I
tten approval from
al property of SABI
MAR UPDATED WITH
2 AMY MAA MAA
25,2018 MINOR CORRECTION
JAN UPDATE AS PER
1 JA MAA MAA
05,2017 DC-DC-16120315

or wri
OCT
0 UPDATE FOR SES JA MAA MAA
23,2016

denti
thout pri
REV. DATE DESCRIPTION DRAWN CHECKED APPROVED

s the confi
2 3 7 N N 2
Saudi Basic Industries Corporation
Engineering and Project Management

ed or used for any other purpose wi


Jubail, Kingdom of Saudi Arabia

s docum ent i
M OFF ON

SPACE NOTE-6
ATOR PANEL
PROCESS CONTROL

NOTE- 3

ON

NOTE- 8
STATUS TO CONTROL ROOM

HEATER
TO SUBSTATI

PROJECT DESCRIPTION

n thi
STANDARD DRAWING
ANNUNCI

FOR SABIC PROJECT

ned i
ALARM

-
FROM

on contai
DRAWING TITLE

26R TYPICAL PROTECTION LV SINGLE LINE DIAGRAM-


38B
NOTE-7 MOTOR CONTROLLED BY CIRCUIT BREAKER

osed, copi
nform ati
-
SCALE PLANT NAME AREA/UNIT SIZE

NTS SABIC - A3

The i
scl
A.I.D. DRAWING NUMBER SHT. NO. REVISION

di
- IEC-E01-C12-006 1 OF 1 2
FILE NAME: IEC-E01-C12-006.DGN
LEGEND:
NOTE:
:DIRECTION OF SIGNAL
1. THIS IS A TYPICAL PROTECTION SINGLE LINE DIAGRAM. THIS DRAWING SHALL BE
:CONTROL CABLE (INSIDE THE PANEL)
READ ALONGWITH E03-G02-'GUIDELINE FOR LV & MV POWER SYSTEM
125 VDC DC SUPPLY BUS 26WT :WINDING TEMPERATURE DETECTOR
PROTECTIONAPPLICATIONS;OTHER SPECIFIC PROTECTION OPTIONS SHALL BE
SELECETED AS PER SPECIFIC REQUIREMENTS OF THE PROJECT IN CONJUNCTION 26OT :OIL TEMPERATURE DETECTOR

AND APPROVAL OF SABIC. 51G :TIME DEPENDANT (IDMT) STANDBY EARTH FAULT RELAY

MV BUS PHASE BUS 63 :SUDDEN PRESSURE RELAY


2. THE RELAY PROTECTION FUNCTIONS ARE SHOWN USING ANSI NUMBER CODES
3 EVEN FOR IEC SET OF DRAWINGS, FOR EASE OF READING. 64 :GROUND FAULT DETECTOR RELAY

94X :AUXILIARY ALARM AND TRIP RELAY


3. REFER TO IEC *(FIGURE II-ELECTRICAL-PROCESS CONTROL INTERFACE SCHEME)
IN SES IEC-E02-G01-ELECTRICAL SYSTEM DESIGN CRITERIA*. RELAYS SHALL NER :NEUTRAL EARTHING RESISTOR
HAVE COMMUNICATION CAPABILITY WITH SCADA SYSTEM.

4. ALL VT PRIMARIES SHALL BE PROTECTED WITH CURRENT LIMITING FUSES. FUSE


2
FAILURE ALARM CONTACTS SHALL BE PROVIDED
3
5. 94X REPRESENTS THREE (03) AUXILIARY ALARM AND TRIP RELAYS; 94S,
94WT, AND 94OT ONE EACH FOR 63, 26WT, AND 26OT RESPECTIVELY.

6. IN CASE OF HIGH RESISTANCE GROUNDING, GROUND FAULT MONITORING


RELAYS SHALL BE PROVIDED IN ACCORDANCE WITH IEC-E11-S02.

MV SIDE

ALARM TO SUBSTATION
ANNUNCIATOR PANEL

REFERENCE DRAWINGS

63 DRAWING NO. TITLE

t cannot be
- -
26WT

26OT

C
SABI
1

C. I
NOTE- 6

tten approval from


NER

al property of SABI
3
LV SIDE

94X NOTE-5

A JAN UPDATE AS PER


1 JA MAA MAA
05,2017 DC-DC-16120315

or wri
51G
OCT
0 UPDATE FOR SES JA MAA MAA
23,2016

denti
thout pri
REV. DATE DESCRIPTION DRAWN CHECKED APPROVED
64

s the confi
NOTE-6

3
TRIP Saudi Basic Industries Corporation
Engineering and Project Management

ed or used for any other purpose wi


2
Jubail, Kingdom of Saudi Arabia

s docum ent i
230V, 1PH, AC PT SUPPLY BUS

LV BUS
PHASE BUS PROJECT DESCRIPTION

n thi
3
STANDARD DRAWING
DC SUPPLY BUS FOR SABIC PROJECT

ned i
125 VDC
-

on contai
DRAWING TITLE

TYPICAL PROTECTION MV SINGLE LINE DIAGRAM-


MV/LV TRANSFORMER > 750KVA AND ≤ 30

osed, copi
nform ati
CONTROLLED BY FUSE-SWITCH COMBINATION
SCALE PLANT NAME AREA/UNIT SIZE

NTS SABIC - A3

The i
scl
A.I.D. DRAWING NUMBER SHT. NO. REVISION

di
- IEC-E01-C12-007 1 OF 1 1
FILE NAME: IEC-E01-C12-007.DGN
125 VDC DC SUPPLY BUS LEGEND:-
NOTES:-
MV BUS PHASE BUS :DIRECTION OF SIGNAL
1. THIS IS A TYPICAL PROTECTION SINGLE LINE DIAGRAM. THIS DRAWING SHALL
3 :CONTROL CABLE (INSIDE THE PANEL)
230V, 1PH, AC PT SUPPLY BUS BE READ ALONGWITH E03-G02-GUIDELINE FOR LV & MV POWER SYSTEM
26WT :WINDING TEMPERATURE DETECTOR
PROTECTION APPLICATIONS. OTHER SPECIFIC PROTECTION OPTIONS SHALL BE
26OT :OIL TEMPERATURE DETECTOR
SELECTED AS PER SPECIFIC REQUIREMENTS OF THE PROJECT IN CONJUNCTION
AND APPROVAL OF SABIC 50 :INSTANTANEOUS OVERCURRENT RELAY (HIGH SET)

50N :INSTANTANEOUS EARTH FAULT RELAY (RESIDUAL CURRENT


2. THE RELAY PROTECTION FUNCTIONS ARE SHOWN USING ANSI NUMBER CODES EVEN
2 OR CORE BALANCE)
FOR IEC SET OF DRAWINGS, FOR EASE OF READING.
51G :TIME DEPENDANT (IDMT) STANDBY EARTH FAULT RELAY

3. REFER TO *(FIGURE II-ELECTRICAL-PROCESS CONTROL INTERFACE SCHEME) IN 51 :TIME DEPENDANT (IDMT) OVERCURRENT RELAY
TRIP
3 SES IEC-E02-G01-ELECTRICAL SYSTEM DESIGN CRITERIA*. RELAYS SHALL HAVE :SUDDEN PRESSURE RELAY
63
COMMUNICATION CAPABILITY WITH SCADA SYSTEM.
64 :EARTH FAULT DETECTOR RELAY

4. ALL VT PRIMARIES SHALL BE PROTECTED WITH CURRENT LIMITING FUSES. 94X :AUXILIARY ALARM AND TRIP RELAY
FUSEFAILURE ALARM CONTACTS SHALL BE PROVIDED :AUXILIARY RELAY
94

5. NORMALLY STANDBY EARTH FAULT RELAY (51G) SHALL BE INSTALLED IN MV NER :NEUTRAL EARTHING RESISTOR

SWITCHGEAR. IN CASE OF MV AND LV SWITCHGEAR ARE NOT LOCATED IN THE


SAME SUBSTATION, 51G SHALL BE INSTALLED IN LV SWITCHGEAR WITH AN
NOTE-5 INTERTRIP SIGNAL TO MV SWITCHGEAR.
6. 94X REPRESENTS THREE (03) AUXILIARY ALARM AND TRIP RELAYS; 94S,94WT,
3
AND 94OT ONE EACH FOR 63, 26WT, AND 26OT RESPECTIVELY
50 50N

7. AN INTERTRIP SIGNAL SHALL BE SENT TO TRIP UPSTREAM OR DOWNSTREAM


51 51G DUE TO EITHER ELECTRICAL OR MANUAL TRIP OF CIRCUIT BREAKER.

64

MV SIDE
REFERENCE DRAWINGS
TO
UPSTREAM DRAWING NO. TITLE
3

t cannot be
- -
ALARM TO SUBSTATION
3
ANNUNCIATOR PANEL

C
SABI
P
NTER- TRI

63
NOTE 7

C. I
tten approval from
26WT
I

al property of SABI
26OT

NER

JAN UPDATE AS PER


1 JA MAA MAA
05,2017 DC-DC-16120315

or wri
4
OCT
LV SIDE 0 UPDATE FOR SES JA MAA MAA
23,2016

denti
thout pri
REV. DATE DESCRIPTION DRAWN CHECKED APPROVED

A 94X NOTE-6

s the confi
Saudi Basic Industries Corporation
Engineering and Project Management

ed or used for any other purpose wi


Jubail, Kingdom of Saudi Arabia

s docum ent i
2
TRIP
94 4

NOTE-6

LV BUS PHASE BUS PROJECT DESCRIPTION


4

n thi
125 VDC DC SUPPLY BUS STANDARD DRAWING
FOR SABIC PROJECT

ned i
-

on contai
DRAWING TITLE

TYPICAL PROTECTION HV SINGLE LINE DIAGRAM-


MV/LV TRANSFORMER > 750KVA AND

osed, copi
nform ati
≤ 3000KVA CONTROLLED BY CIRCUIT BR
SCALE PLANT NAME AREA/UNIT SIZE

NTS SABIC - A3

The i
scl
A.I.D. DRAWING NUMBER SHT. NO. REVISION

di
- IEC-E01-C12-008 1 OF 1 1
FILE NAME: IEC-E01-C12-008.DGN
125 VDC DC SUPPLY BUS LEGEND:-
NOTES:-
PHASE BUS :DIRECTION OF SIGNAL
MV BUS
3 :CONTROL CABLE (INSIDE THE PANEL)
1. .THIS IS A TYPICAL PROTECTION SINGLE LINE DIAGRAM. THIS DRAWING SHALL
PT SUPPLY BUS 26WT :WINDING TEMPERATURE INDICATOR
230V, 1PH, AC BE READ ALONGWITH E03-G02-GUIDELINE FOR LV & MV POWER SYSTEM
PROTECTION APPLICATIONS. OTHER SPECIFIC PROTECTION OPTIONS SHALL BE 26OT :OIL TEMPERATURE INDICATOR

SELECTED AS PER SPECIFIC REQUIREMENTS OF THE PROJECT IN CONJUNCTION 50 :INSTANTANEOUS OVERCURRENT RELAY (HIGH SET)
AND APPROVAL OF SABIC 50N :INSTANTANEOUS EARTH FAULT RELAY

2 (RESIDUAL CURRENT OR CORE BALANCE)


2. THE RELAY PROTECTION FUNCTIONS ARE SHOWN USING ANSI NUMBER CODES EVEN
51 :TIME DEPENDANT (IDMT) OVERCURRENT RELAY
FOR IEC SET OF DRAWINGS, FOR EASE OF READING.
51G :TIME DEPENDENT STANDBY EARTH FAULT RELAY
3. REFER TO *(FIGURE II-ELECTRICAL-PROCESS CONTROL INTERFACE SCHEME) IN
63 :BUCHHOLZ RELAY
SES IEC-E02-G01-ELECTRICAL SYSTEM DESIGN CRITERIA*. RELAYS SHALL HAVE
TRIP COMMUNICATION CAPABILITY WITH SCADA SYSTEM. 64 :EARTH FAULT DETECTOR RELAY

86-1 :INTERTRIP/LOCK-OUT RELAY


4. ALL VT PRIMARIES SHALL BE PROTECTED WITH CURRENT LIMITING FUSES. FUSE
3 86-2
FAILURE ALARM CONTACTS SHALL BE PROVIDED
87T :DIFFERENTIAL PROTECTION RELAY (TRANSFORMER)

94B :BUCHHOLZ ALARM AND TRIP RELAY


5. .94X REPRESENTS THREE (03) AUXILIARY ALARM AND TRIP RELAYS: 94S, 94WT,
AND 94OT ONE EACH FOR 63, 26WT, AND 26OT RESPECTIVELY. 26WT AND 26OT 94OT :TRANSFORMER OIL TEMPERATURE ALARM AND TRIP RELAY

SHALL NOT SEND SIGNAL TO 86-2. 94WT :WINDING TEMPERATURE ALARM AND TRIP RELAY

6. THE TRANSFORMER DIFFERENTIAL PROTECTION (87) ZONE OF PROTECTION CT :CURRENT TRANSFORMER


3 50 51 INCLUDES CABLES. INRUSH STABILITY SHALL BE PROVIDED IN THE RELAY.
NER :NEUTRAL EARTHING RESISTOR

50N
7. INTER TRIP SHALL NOT LOCKOUT THE RECEIVING END LOCKOUT RELAY.
NOTE-7
RECEIVING END RELAYS TRIPS AND SHOWS "INTER-TRIP RECEIVED".

3 86-1

87T

NOTE-6

MV SIDE
REFERENCE DRAWINGS
DRAWING NO. TITLE
3 2

t cannot be
- -
ALARM TO SUBSTATION
ANNUNCIATOR PANEL

C
SABI
63

26WT

C. I
tten approval from
26OT INTER TRIP

al property of SABI
1 1

NER
ALARM TO SUBSTATION
ANNUNCIATOR PANEL

JAN UPDATE AS PER


1 JA MAA MAA
05,2017 DC-DC-16120315

or wri
3
MV SIDE OCT
UPDATE FOR SES JA MAA MAA
0 23,2016

denti
thout pri
REV. DATE DESCRIPTION DRAWN CHECKED APPROVED
3 NOTE-5

s the confi
94X
Saudi Basic Industries Corporation
Engineering and Project Management

ed or used for any other purpose wi


86-2
Jubail, Kingdom of Saudi Arabia
3 51G 64 NOTE-7

s docum ent i
PROJECT DESCRIPTION

n thi
STANDARD DRAWING
TRIP
FOR SABIC PROJECT

ned i
3
2 -

on contai
DRAWING TITLE

230V, 1PH, AC PT SUPPLY BUS TYPICAL PROTECTION MV SINGLE LINE DIAGRAM-


MV/MV TRANSFORMER (>3000 KVA)

osed, copi
nform ati
MV BUS 3 PHASE BUS WITH FEEDER CABLE <500M
SCALE PLANT NAME AREA/UNIT SIZE

NTS SABIC - A3
125 VDC DC SUPPLY BUS

The i
scl
A.I.D. DRAWING NUMBER SHT. NO. REVISION

di
- IEC-E01-C12-009 1 OF 1 1
FILE NAME: IEC-E01-C12-009.DGN
125 VDC DC SUPPLY BUS
NOTES:- LEGEND:-
:DIRECTION OF SIGNAL
MV BUS PHASE BUS
1. THIS IS A TYPICAL PROTECTION SINGLE LINE DIAGRAM. THIS DRAWING SHALL
:CONTROL CABLE (INSIDE THE PANEL)
BE READ ALONGWITH E03-G02-GUIDELINE FOR LV & MV POWER SYSTEM
230V,1PH,AC PT SUPPLY BUS 26WT :WINDING TEMPERATURE INDICATOR
PROTECTION APPLICATIONS. OTHER SPECIFIC PROTECTION OPTIONS SHALL BE
3 SELECTED AS PER SPECIFIC REQUIREMENTS OF THE PROJECT IN CONJUNCTION 26OT :OIL TEMPERATURE INDICATOR

AND APPROVAL OF SABIC 50 :INSTANTANEOUS OVERCURRENT RELAY (HIGH SET)

50N :INSTANTANEOUS EARTH FAULT RELAY (RESIDUAL CURRENT OR CORE BALANCE)


2. THE RELAY PROTECTION FUNCTIONS ARE SHOWN USING ANSI NUMBER CODES EVEN
2 51 :TIME DEPENDANT (IDMT) OVERCURRENT RELAY
FOR IEC SET OF DRAWINGS, FOR EASE OF READING.
51G :TIME DEPENDENT STANDBY EARTH FAULT RELAY

51N :EARTH FAULT RELAY


3. REFER TO *(FIGURE II-ELECTRICAL-PROCESS CONTROL INTERFACE SCHEME) IN
SES E02-G01-ELECTRICAL SYSTEM DESIGN CRITERIA*. RELAYS SHALL 63 :BUCHHOLZ RELAY

HAVECOMMUNICATION CAPABILITY WITH SCADA SYSTEM. 64 :EARTH FAULT DETECTOR RELAY


TRIP
86-1 :INTERTRIP/LOCK-OUT RELAY
4. ALL VT PRIMARIES SHALL BE PROTECTED WITH CURRENT LIMITING FUSES. FUSE 86-2
3
FAILURE ALARM CONTACTS SHALL BE PROVIDED
87L/T :DIFFERENTIAL PROTECTION RELAY (LINE / TRANSFORMER)

94B :BUCHHOLZ ALARM AND TRIP RELAY


5. 94X REPRESENTS THREE (03) AUXILIARY ALARM AND TRIP RELAYS: 94S, 94WT,
AND 94OT ONE EACH FOR 63, 26WT, AND 26OT RESPECTIVELY. 26WT AND 26OT 94OT :TRANSFORMER OIL TEMPERATURE ALARM AND TRIP RELAY

SHALL NOT SEND SIGNAL TO 86-2. 94WT :WINDING TEMPERATURE ALARM AND TRIP RELAY

3 CT :CURRENT TRANSFORMER
6. THE TRANSFORMER DIFFERENTIAL PROTECTION (87) ZONE OF PROTECTION
50 51 NER :NEUTRAL EARTHING RESISTOR
INCLUDES CABLES AND NEED FOR INRUSH STABILITY.
1
50N 51N
7. INTER TRIP SHALL NOT LOCKOUT THE RECEIVING END LOCKOUT RELAY.
NOTE-7
RECEIVING END RELAYS TRIPS AND SHOWS "INTER TRIP RECEIVED".

3 86-1
8. A DIFFERENTIAL PROTECTION SHALL BE USED FOR MV/MV TRANSFORMERS USING
87L/T OPTIC FIBER CABLE FOR CURRENT COMPARISON AND COMMUNICATION BETWEEN
THE TWO ENDS IF THE PRIMARY CONNECTION IS MORE THAN 500 M DISTANT.
NOTE-6

NOTE-8
MV SIDE
REFERENCE DRAWINGS
DRAWING NO. TITLE
3

t cannot be
- -
ALARM TO SUBSTATION
ANNUNCIATOR PANEL

C
SABI
63

26WT

C. I
tten approval from
26OT INTER TRIP

al property of SABI
94B 1 1

NER
ALARM TO SUBSTATION
ANNUNCIATOR PANEL

JAN UPDATE AS PER


2 1 JA MAA MAA
05,2017 DC-DC-16120315

or wri
3
OCT
MV SIDE 0 23,2016
UPDATE FOR SES JA MAA MAA

denti
thout pri
REV. DATE DESCRIPTION DRAWN CHECKED APPROVED
4
NOTE-5

s the confi
94X
Saudi Basic Industries Corporation
Engineering and Project Management

ed or used for any other purpose wi


86-2 Jubail, Kingdom of Saudi Arabia

s docum ent i
NOTE-7
3 51G 64

3
87
PROJECT DESCRIPTION

n thi
STANDARD DRAWING
FOR SABIC PROJECT

ned i
TRIP -
3

on contai
DRAWING TITLE
2
TYPICAL PROTECTION MV SINGLE LINE DIAGRAM-
125 VDC PT SUPPLY BUS MV/MV TRANSFORMER (>3000 KVA)

osed, copi
nform ati
WITH FEEDER CABLE >500M
MV BUS 3 PHASE BUS
SCALE PLANT NAME AREA/UNIT SIZE

NTS SABIC - A3
230V,1PH,AC DC SUPPLY BUS

The i
scl
A.I.D. DRAWING NUMBER SHT. NO. REVISION

di
- IEC-E01-C12-010 1 OF 1 1
FILE NAME: IEC-E01-C12-010.DGN
125 VDC DC SUPPLY BUS LEGEND:-
NOTES:- :DIRECTION OF SIGNAL
MV BUS PHASE BUS
:CONTROL CABLE (INSIDE THE PANEL)
3
1. THIS IS A TYPICAL PROTECTION SINGLE LINE DIAGRAM. THIS DRAWING SHALL
:PILOT WIRE PROTECTION
PT SUPPLY BUS
BE READ ALONGWITH E03-G02-GUIDELINE FOR LV & MV POWER SYSTEM
230V,1PH,AC
PROTECTION APPLICATIONS’. OTHER SPECIFIC PROTECTION OPTIONS SHALL BE 51 :TIME DEPENDANT (IDMT) OVERCURRENT RELAY
SELECTED AS PER SPECIFIC REQUIREMENTS OF THE PROJECT IN CONJUNCTION 51G :GROUND OVERCURRENT FAULT RELAY
AND APPROVAL OF SABIC
87L :LINE DIFFERENTIAL RELAY
2. THE RELAY PROTECTION FUNCTIONS ARE SHOWN USING ANSI NUMBER CODES EVEN
2 FOR IEC SET OF DRAWINGS, FOR EASE OF READING. NER :NEUTRAL EARTHING RESISTOR

3. REFER TO *(FIGURE II-ELECTRICAL-PROCESS CONTROL INTERFACE SCHEME) IN


SES E02-G01-ELECTRICAL SYSTEM DESIGN CRITERIA*. RELAYS SHALL HAVE
COMMUNICATION CAPABILITY WITH SCADA SYSTEM.
TRIP
4. RELAYS WITH TRIP FUNCTION SHOULD HAVE HAND RESET FACILITY. A SEPARATE
3 LOCK OUT RELAY (86) SHALL NOT BE PROVIDED TO TRIP THE CIRCUIT BREAKER
IN PARALLEL TO THE DIRECT TRIP, UNLESS APPROVEDBY SABIC.

5. ALL VT PRIMARIES SHALL BE PROTECTED WITH CURRENT LIMITING FUSES. FUSE


FAILURE ALARM CONTACTS SHALL BE PROVIDED.

3 6. LINE DIFFERENTIAL PROTECTION SHALL BE A CURRENT DIFFERENTIAL RELAY


USING FIBER OPTIC CABLE FOR CURRENT COMPARISON AND COMMUNICATION
BETWEEN THE TWO ENDS IF THE PRIMARY CONNECTION IS MORE THAN 500 M
1 51 51G DISTANCE.

3
87L NOTE-6

REFERENCE DRAWINGS
DRAWING NO. TITLE
3 2

t cannot be
- -
ALARM TO SUBSTATION
ANNUNCIATOR PANEL

C
SABI
C. I
FIBER OPTIC

tten approval from


CABLES
P
NTER- TRI

al property of SABI
I

94
JAN UPDATE AS PER
1 JA MAA MAA
05,2017 DC-DC-16120315

or wri
OCT
0 UPDATE FOR SES JA MAA MAA
23,2016

denti
thout pri
REV. DATE DESCRIPTION DRAWN CHECKED APPROVED

s the confi
87L NOTE-6
Saudi Basic Industries Corporation
Engineering and Project Management

ed or used for any other purpose wi


Jubail, Kingdom of Saudi Arabia

s docum ent i
PROJECT DESCRIPTION

n thi
STANDARD DRAWING
FOR SABIC PROJECT

ned i
-

on contai
TRIP DRAWING TITLE
3
TYPICAL PROTECTION MV SINGLE LINE DIAGRAM-
2
SINGLE PLAIN FEEDER

osed, copi
nform ati
MV BUS 3 PHASE BUS
-
SCALE PLANT NAME AREA/UNIT SIZE

NTS SABIC - A3
125 VDC DC SUPPLY BUS

The i
scl
A.I.D. DRAWING NUMBER SHT. NO. REVISION

di
- IEC-E01-C12-011 1 OF 1 1
FILE NAME: IEC-E01-C12-011.DGN
LEGEND:-
FROM LV UPSTREAM FROM LV UPSTREAM 25 : SYNCHRONISM CHECK RELAY

27 : UNDER VOLTAGE RELAY


125V DC BUS 125V DC BUS
47 : PHASE BALANCE VOLTAGE RELAY

NOTES:- 50BF : BREAKER FAILURE RELAY

51 : AC INVERSE TIME OVERCURRENT RELAY


1. THIS IS A TYPICAL PROTECTION SINGLE LINE DIAGRAM. THIS DRAWING SHALL
V V BE READ ALONGWITH E03-G02-GUIDELINE FOR LV & MV POWER SYSTEM 59 : OVER VOLTAGE RELAY
PROTECTION APPLICATIONS. OTHER SPECIFIC PROTECTION OPTIONS SHALL BE
SELECTED AS PER SPECIFIC REQUIREMENTS OF THE PROJECT IN CONJUNCTION 67/67N : DIRECTIONAL PHASE OVERCURRENT/ EARTH FAULT RELAY

VS VS AND APPROVAL OF SABIC


74TC : TRIP COIL MONITORING RELAY
2. THE RELAY PROTECTION FUNCTIONS ARE SHOWN USING ANSI NUMBER CODES EVEN
NOTE-5 NOTE-5 86I : LOCK OUT RELAY - INCOMER
FOR IEC SET OF DRAWINGS, FOR EASE OF READING.

3. REFER TO *(FIGURE II-ELECTRICAL-PROCESS CONTROL INTERFACESCHEME) IN 86BT : LOCK OUT RELAY - BUS-TIE
SES IEC-E02-G01-ELECTRICAL SYSTEM DESIGNCRITERIA*. RELAYS SHALL HAVE ATS : AUTOMATIC TRANSFER SWITCH
COMMUNICATION CAPABILITY WITHSCADA SYSTEM.
K KEY LOCKED
4. RELAYS WITH TRIP FUNCTION SHOULD HAVE HAND RESET FACILITY.A SEPARATE
LOCK OUT RELAY (86) SHALL NOT BE PROVIDED TO TRIP THE CIRCUIT BREAKER
IN PARALLEL TO THE DIRECT TRIP, UNLESS APPROVED BY SABIC

3 25 27 47 47 27 25 5. ALL VT PRIMARIES SHALL BE PROTECTED WITH CURRENT LIMITING FUSES. FUSE


3
FAILURE ALARM CONTACTS SHALL BE PROVIDED.

51 59 86I 86I 59 51

67/67N 74TC 74TC 67/67N

50BF 50BF

NOTE-4 NOTE-4

REFERENCE DRAWINGS
DRAWING NO. TITLE

t cannot be
51 50BF 25

C
SABI
K 86BT ATS 74TC K
KEY LOCKED KEY LOCKED

C. I
tten approval from
NOTE-4

al property of SABI
3
LV BUS (PHASE BUS) LV BUS (PHASE BUS)
JAN UPDATE AS PER
1 JA MAA MAA
PT SUPPLY BUS PT SUPPLY BUS 05,2017 DC-DC-16120315

or wri
OCT
0 UPDATE FOR SES JA MAA MAA
23,2016

denti
thout pri
K

REV. DATE DESCRIPTION DRAWN CHECKED APPROVED


KEY LOCKED

s the confi
Saudi Basic Industries Corporation
Engineering and Project Management

ed or used for any other purpose wi


Jubail, Kingdom of Saudi Arabia
NOTE-5 NOTE-5

s docum ent i
PROJECT DESCRIPTION

n thi
STANDARD DRAWING
FOR SABIC PROJECT

ned i
3 3 3 3 3 3
-
27

on contai
27 DRAWING TITLE

TYPICAL PROTECTION LV SINGLE LINE DIAGRAM-


VS VS
LV SWITCHGEAR INCOMER & BUSBAR

osed, copi
nform ati
V V
SCALE PLANT NAME AREA/UNIT SIZE

M M M M NTS SABIC - A3

The i
scl
A.I.D. DRAWING NUMBER SHT. NO. REVISION

di
- IEC-E01-C12-013 1 OF 1 1
FILE NAME: IEC-E01-C12-013.DGN
LEGEND:-
NOTES:-
:DIRECTION OF SIGNAL

1. THIS IS A TYPICAL PROTECTION SINGLE LINE DIAGRAM. THIS DRAWING SHALL :CONTROL CABLE (INSIDE THE PANEL)

BE READ ALONGWITH E03-G02-‘GUIDELINE FOR LV & MV POWER SYSTEM 27 :UNDER VOLTAGE RELAY
PROTECTION APPLICATIONS’. OTHER SPECIFIC PROTECTION OPTIONS SHALL BE
47 :NEGATIVE SEQUENCE RELAY
125V DC DC BUS SELECTED AS PER SPECIFIC REQUIREMENTS OF THE PROJECT IN CONJUNCTION
50 :AC TIME OVERCURRENT PROTECTION
AND APPROVAL OF SABIC
50BF :BREAKER FAILURE RELAY
2. THE RELAY PROTECTION FUNCTIONS ARE SHOWN USING ANSI NUMBER CODES EVEN
MV/LV BUS FOR IEC SET OF DRAWINGS, FOR EASE OF READING. 50N :INSTANTANEOUS EARTH OVER CURRENT RELAY (RESIDUAL METHOD)
PHASE BUS
3. REFER TO *(FIGURE II-ELECTRICAL-PROCESS CONTROL INTERFACE SCHEME) IN 51 :OVERCURRENT PROTECTION

SES IEC-E02-G01-ELECTRICAL SYSTEM DESIGN CRITERIA*. RELAYS SHALL HAVE 51N :EARTH OVERCURRENT RELAY

COMMUNICATION CAPABILITY WITH SCADA SYSTEM. 59 :OVERCURRENT PROTECTION

59N/60N :NEUTRAL VOLTAGE DISPLACEMENT/CURRENT UNBALANCE


4. RELAYS WITH TRIP FUNCTION SHOULD HAVE HAND RESET FACILITY. A SEPARATE
2 86 :LOCK-OUT RELAY
LOCK OUT RELAY (86) SHALL NOT BE PROVIDED TO TRIP THE CONTRACTOR IN
PARALLEL TO THE DIRECT TRIP, UNLESS APPROVED BY SABIC C :POWER FACTOR METER

5. ALL VT PRIMARIES SHALL BE PROTECTED WITH CURRENT LIMITING FUSES. FUSE DS :DISCONNECTING SWITCH

NOTE 8 FAILURE ALARM CONTACTS SHALL BE PROVIDED. LA :LIGHTNING ARRESTOR

6. FOR LARGE CAPACITOR BANKS EXCEEDING 1000 KVAR, THE CAPACITORS SHALL E.S. :EARTHING SWITCH

BE CONNECTED IN DOUBLE STAR WITH UNBALANCE PROTECTION MONITORING THE


STAR POINT VOLTAGES OF THE CAPACITOR BANK.

7. MEDIUM VOLTAGE CAPACITOR UNITS SHALL HAVE AN INTERNAL DISCHARGE


RESISTOR IN ORDER TO REDUCE THE RESIDUAL VOLTAGE TO 50 V OR LESS IN 5
MIN.

3 51 59 C 8. IN CASE OF LV, WITH DRAWABLE FUSE, CONTACTOR SHALL PROVIDED IN THE
UPSTREAM LV SWITCHGEAR
27 47 50
9. FOR INTERLOCKS, REFER TO SES E16-S01 CLAUSE 5.4 REQUIREMENTS.
NTERLOCK

51N 86

50BF 50N REFERENCE DRAWINGS


I

NOTE-4
NOTE 9 3 DRAWING NO. TITLE

t cannot be
(IF REQUIRED) - -

C
SABI
C. I
tten approval from
DS

al property of SABI
MECHANICAL
INTERLOCK

E.S.
JAN UPDATE AS PER
L.A. 1 JA MAA MAA
05,2017 DC-DC-16120315

or wri
OCT
0 UPDATE FOR SES JA MAA MAA
23,2016

denti
thout pri
REV. DATE DESCRIPTION DRAWN CHECKED APPROVED

s the confi
Saudi Basic Industries Corporation
Engineering and Project Management

ed or used for any other purpose wi


Jubail, Kingdom of Saudi Arabia

s docum ent i
1

SHUNT
NOTE-6 PROJECT DESCRIPTION

n thi
59N/60N
STANDARD DRAWING
NOTE-6
FOR SABIC PROJECT

ned i
POWER FACTOR -
CORRECTION CAPACITOR

on contai
DRAWING TITLE

TYPICAL PROTECTION LV/MV SINGLE LINE DIAGRAM


LV/MV CAPACITOR BANK

osed, copi
nform ati
SCALE PLANT NAME AREA/UNIT SIZE

NTS SABIC - A3

The i
scl
A.I.D. DRAWING NUMBER SHT. NO. REVISION

di
- IEC-E01-C12-014 1 OF 1 1
FILE NAME: IEC-E01-C12-014.DGN
LEGEND:-
NOTES:-
230V, 1PH, AC SPACE HEATER SUPPLY BUS
1. THIS IS A TYPICAL PROTECTION SINGLE LINE DIAGRAM. THIS DRAWING :DIRECTION OF SIGNAL
SHALL BE READ ALONGWITH E03-G02-'GUIDELINE FOR LV & MV POWER :CONTROL CABLE (INSIDE THE PANEL)
125 VDC DC SUPPLY BUS
SYSTEM PROTECTION APPLICATIONS'. OTHER SPECIFIC PROTECTION
26R :WINDING TEMPERATURE DETECTOR
LV/MV EMERGENCY BUS PHASE BUS OPTIONS SHALL BE SELECTED AS PER SPECIFIC REQUIREMENTS OF
27 :UNDER VOLTAGE RELAY
3 THE PROJECT IN CONJUNCTION AND APPROVAL OF SABIC.
32P :DIRECTIONAL ACTIVE OVERPOWER

2. THE RELAY PROTECTION FUNCTIONS ARE SHOWN USING ANSI NUMBER CODES EVEN 32Q :DIRECTIONAL REACTIVE OVERPOWER
FOR IEC SET OF DRAWINGS, FOR EASE OF READING. 38B :BEARING TEMPERATURE DETECTOR
39V :VIBRATION DETECTOR
2 3. REFER TO IEC *(FIGURE II-ELECTRICAL-PROCESS CONTROL INTERFACE SCHEME) 40 :FIELD LOSS (UNDER IMPEDANCE)/UNDER EXCITATION

IN SES IEC-E02-G01-ELECTRICAL SYSTEM DESIGN CRITERIA*. RELAYS SHALL 46 :NEGATIVE SEQUENCE/ UNBALANCE RELAY
2 ON
TRIP 47 :PHASE VOLTAGE BALANCE RELAY
HAVE COMMUNICATION CAPABILITY WITH SCADA SYSTEM.
49 :THERMAL OVERLOAD RELAY
NOTE-5 N.C. OFF 49T :TEMPERATURE MONITORING
4. RELAYS WITH TRIP FUNCTION SHOULD HAVE HAND RESET FACILITY. A SEPARATE
NOTE-7 50 :INSTANTANEOUS OVERCURRENT RELAY
LOCK OUT RELAY (86) SHALL NOT BE PROVIDED TO TRIP THE CONTRACTOR IN
50G :INSTANTANEOUS EARTH FAULT RELAY
PARALLEL TO THE DIRECT TRIP, UNLESS APPROVED BY SABIC.
50N :INSTANTANEOUS EARTH FAULT RELAY (CORE BALANCE)

5. 51N :IDMT EARTH FAULT RELAY (CORE BALANCE)


N.C AUXILIARY CONTACT OF CONTACTOR IN PARALLEL WITH CONTACT
50BF :BREAKER FAILURE RELAY
OFWITHDRAWABLE UNIT (CLOSED IF WITHDRAWN)FOR SPACE HEATER CONTROL.
51 :PHASE OVERCURRENT RELAY

2 6. ALL VT PRIMARIES SHALL BE PROTECTED WITH CURRENT LIMITING FUSES. FUSE 51G :EARTH OVERCURRENT RELAY
NOTE-4
FAILURE ALARM CONTACTS SHALL BE PROVIDED. 59 :OVER VOLTAGE (L-L OR L-N)

27 32P 32R 40
59N :NEUTRAL VOLTAGE DISPLACEMENT
7. POSITION INDICATION REQUIRED AS SHOWN FOR ON-OFF OF LCP.
81H :OVER FREQUENCY RELAY
8. FOR VIBRATION MEASUREMENTS AND ANNUNCIATIONS, REFER TO SES G19-S01. 81L :UNDER FREQUENCY RELAY
3 46 47 49 49T

P
NTER- TRI
86 :LOCK OUT RELAY
9. GENERATORS SHALL BE PROTECTED WITH WINDING AND BEARTING TEMPERATURE
50N 50G
50/51 50BF
51N 51G
87G :GENERATOR DIFFERENTIAL RELAY
RTD'S.

I
59 81H
86 87G
59N 81L

REFERENCE DRAWINGS
DRAWING NO. TITLE

t cannot be
- -

C
SABI
3

C. I
tten approval from
al property of SABI
ON

OFF NOTE-4
NOTE-7
2 50 50N

JAN UPDATE AS PER


1 JA MAA MAA
3 51 74
05,2017 DC-DC-16120315

or wri
SEP
0 UPDATE FOR SES JA MAA MAA
51N
04,2016
NOTE-7

denti
SELF CONTAINED MULTIPLE

thout pri
REV. DATE DESCRIPTION DRAWN CHECKED APPROVED
G STEPS WITH METERING, CONTROL

s the confi
AND TEST INSTRUMENTATION
Saudi Basic Industries Corporation
SPACE
Engineering and Project Management

ed or used for any other purpose wi


HEATER
GENERATOR LOAD BANK BREAKER RESISTIVE LOAD BANKS
3 Jubail, Kingdom of Saudi Arabia

s docum ent i
1

PROJECT DESCRIPTION
26R

n thi
38B STANDARD DRAWING
NER

39V
FOR SABIC PROJECT

ned i
NOTE-8,9

on contai
DRAWING TITLE

TYPICAL PROTECTION LV/MV SINGLE LINE-


DIAGRAM - EMERGENCY DIESEL

osed, copi
nform ati
GENERATOR
SCALE PLANT NAME AREA/UNIT SIZE

NTS SABIC - A3

The i
scl
A.I.D. DRAWING NUMBER SHT. NO. REVISION

di
- IEC-E01-C12-015 1 OF 1 1
FILE NAME: IEC-E01-C12-015.DGN