You are on page 1of 63

CHAPTER 10

TRANSFORMER PROTECTION

Chapter 10 Page 1 Transformer Protection


IMPROVING TRANSFORMER PROTECTION USING
NUMERICAL RELAYS
Transformer Protection Characteristics

• Introduction
• Need for Protection
• Objectives of Protection
• Causes of Transformer Failure
Power Transformer Capability Limits

• Category I Transformers

• Category II and III Transformers

• Category IV Transformers

• Protection Considerations

Through Fault Monitoring

Transformer Over-excitation

• Transformer Differential Relay and Over-excitation

• Over-excitation Protection

Winding Faults

• Phase to Phase Faults

• Inter-turn Faults

• Core Faults

Chapter 10 Page 2 Transformer Protection


Restricted Earth Fault Protection

Differential Protection

• Basic Differential Relaying Schemes

• Transformer Differential Protection

• Magnetizing, Inrush, Over-excitation, and CT Saturation

• Methods for Discriminating Internal Faults for Inrush and Over-excitation


Conditions

Application Example – Setting the ABB RET 521 Transformer


Differential Relay

• Introduction

• Transformer Differential Protection

• Magnetizing Inrush Current

• External Faults

• Internal Faults

• Three Phase Time Overcurrent Protection

• Multi-purpose Time Protection(GP)

• Over/nder Voltage Protection

• Restricted Earth Fault Protection (REF)

Problem 7

Chapter 10 Page 3 Transformer Protection


TRANSFORMER PROTECTION CHARACTERISTICS
INTRODUCTION

The protection characteristics of a transformer can best be explained by answering


the following questions:

o Why does a transformer need protection?


o What are the objectives of transformer protection?
o What are the causes of transformer failure?

NEED FOR PROTECTION

A transformer needs protection for the following reasons:

o If the transformer fails, it usually results in complete loss of service to the plant.
o If the transformer is properly protected, prompt fault clearing will usually prevent
catastrophic damage.
o When a transformer does fail, proper protection and prompt clearing will minimize
damage, system disturbance, and the magnitude and duration of the outage.

OBJECTIVES OF PROTECTION

The objectives of protection are (1) to protect the electrical system from transformer
failure, (2) to protect the transformer from electrical power disturbances, (3) to
protect the transformer as much as possible from malfunctions within the transformer
itself, and (4) to protect the transformer physically as well as electrically from the
environment.

CAUSES OF TRANSFORMER FAILURE

The failure rate of transformers (76 failures per 1000 transformer years) is
statistically less than any other piece of electrical equipment (e.g., motors, cables,
switchgear, etc.), which is the good news. Conversely, the failure out-of-service rate
(342 hours per failure) is statistically very high when compared to other types of
electrical equipment failures. The causes of transformer failures can be grouped as
follows: winding failures (most common), continuous overloading, bushing failures,
phase and ground faults, transient overvoltages, and weather (e.g., ice, wind,
lightning, etc.)

Chapter 10 Page 4 Transformer Protection


THROUGH-FAULT PROTECTION (LIQUID-MMERSED
TRANSFORMERS)
Through-fault protection for liquid-immersed transformers is affected by four factors,
as follows:

o • Transformer category (e.g., number of phases and kVA rating of fault occurrence)
o • Fault incidence zones (e.g., frequency of faults)
o • Transformer connections (e.g., Δ-Δ, Δ-Y, Y-Y, or Y-Δ)
o • Transformer damage curves (e.g., Cat I, II, III, IV)

Transformer Categories: ANSI/IEEE Standard C57 categorizes transformers by


number of phases (e.g., single or three-phase) and size (e.g., kVA ratings), as listed
in Table 10-1.

Minimum Nameplate KVA


(Principal Winding)
Category Single-Phase Three-Phase
I 5 to 500 15 to 500
II 501 to 1667 501 to 5000
III 1666 to 10000 5001 to 30000
IV above 10000 above 30000

Table 10-1. Transformer Categories

Fault Incidence Zones: Transformer damage, when subjected to faults, is


cumulative, and the fact exists that the number of through-faults to which a
transformer can be exposed to is inherently different for different transformer
applications. For example, transformers with secondary side conductors enclosed in
conduit or isolated in some other fashion, such as those that are typically found in
industrial power systems, experience extremely low incidence of through-faults.
Transformers with secondary side overhead lines, such as those that are found in
utility distribution substations have a relatively high incidence of through-faults.
Figure 10-1 shows the fault incidence zones (frequent and infrequent) for a typical
industrial power system.

Chapter 10 Page 5 Transformer Protection


Through-Fault Protection (Liquid-Immersed Transformers)

Figure 10-1. Transformer Through-Fault Incidence Zones

Transformer Connections: Another factor to consider for transformer protection is


the effect of external secondary faults on delta-delta and delta-wye connected
transformers, which is illustrated in Figure 10-2.

Chapter 10 Page 6 Transformer Protection


THROUGH-FAULT PROTECTION (LIQUID-IMMERSED TRANSFORMERS)

The through-fault protection curves are based on three-phase secondary faults. For
Δ-Y connected and solidly grounded transformers, with single line-to-ground faults on
the secondary side (Figure 10-2e), the curve values must be reduced to 58% (1/ 3 )
of the three-phase curve values. For Δ-Δ connected transformers, with line-to-line
faults on the secondary side (Figure 10-2c), the curve values must be reduced to
87% ( 3 /2) of three-phase values. No adjustments are required for any of the other
connections because at least one phase of the primary side will “see” 1.0 per unit
current. See Figures 10-2a, 10-2b, and 10-2d.

Chapter 10 Page 7 Transformer Protection


THROUGH-FAULT PROTECTION (LIQUID-IMMERSED TRANSFORMERS)

Figure 10-200000. Effects of Secondary Faults on Transformers

Chapter 10 Page 8 Transformer Protection


LOCATING GROUND FAULT RELAYS IN LOW RESISTANCE
GROUNDED SYSTEMS

13.8 kV

A B
Direction of Flow 51/50
51/50
of Fault Current N

10 MVA

C D

400 amps 51 51 N
Ground
Fault

4.16 kV

13.8 kV
ON THE PRIMARY SIDE OF THE TRANSFORMER

A B
10,000
Direction of Flow 51/50
51/50
Transformer FLA = = 418 A of Fault Current N

√3 * 13.8
10 MVA

C D
Select CT ratio (Either 600/5 or 800/5) Select 800/5
400 amps 51 51 N
Ground
Fault

4.16 kV
Set Pickup of Phase element of the relay at 1.5 times the transformer FLA

= 1.5 * 418 = 627 A

627

Relay tap = = 3.92 amps

(800/5)

Choose Tap 4 - relay picks up at 640 A [640 = 4 * (800/5)]

Chapter 10 Page 9 Transformer Protection


13.8 kV

A B
Direction of Flow 51/50
51/50
of Fault Current N

10 MVA

C D

400 amps 51 51 N
Ground
Fault

For a ground fault on the transformer secondary bushings 4.16 kV

Ifault (secondary) = 400 amps

Will relay element C see it No (why)

Will relay element D see it No (why)

Will relay element B see it No (why)

13.8 kV

Direction of Flow A B
of Fault Current
51/50
51/50
N
E
51
G 10 MVA

C
200/5
400 amps 51
Ground
Fault

Will relay element A see it (Maybe) 4.16 kV

But it will only see

4.16

0.58 * 400 * ≈ 70amps

13.8

Since the relay is set to operate when the current reaches 640 amps

Relay A will not operate, and the fault will go on undetected “forever”

The only way to detect this fault is to put the CT for the ground relay between the neutral
and the ground

Chapter 10 Page 10 Transformer Protection


13.8 kV

Direction of Flow A B
of Fault Current
51/50
51/50
N
E
51
G 10 MVA

C
200/5
400 amps 51
Ground
Fault
The same ground fault will generate 400 amps
4.16 kV

400

Which produces = 10 amps in the CT secondary

(200/5)

If relay E is set at 1 amps

The fault current will be 10 times the relay pickup

Leading to fast and definite operation

Time

51
G

The same ground fault will generate 400 amps

1 10 Current
amp amps
400

Which produces = 10 amps in the CT secondary

(200/5)

If relay E is set at 1 amps

The fault current will be 10 times the relay pickup

Leading to fast and definite operation

Chapter 10 Page 11 Transformer Protection


POWER TRANSFORMER CAPABILITY LIMITS
A power transformer consists of a set of windings around a magnetic core. The
windings are insulated from each other and the core. Operational stresses can cause
failure of the transformer winding, insulation, and core.

The power transformer windings and magnetic core are subject to a number of
different forces during operation:

• Expansion and contraction caused by thermal cycling.


• Vibration caused by flux in the core changing direction every half cycle.
• Localized heating caused by eddy currents in parts of the winding, induced
by magnetic flux.
• Impact forces caused by through-fault currents.
• Thermal heating caused by overloading.
ANSI/IEEE standards provide operating limits for power transformers. Initially, these
operating limits only considered the thermal effects of transformer overload. Later,
the capability limit was changed to include the mechanical effect of higher fault
currents through the transformer. Power trans-former through-faults produce
physical forces that cause insulation compression, insulation wear, and friction-
induced displacement in the winding. These effects are cumulative and should be
considered over the life of the transformer.

Table 10-2 shows four categories for liquid-immersed power transformers, based on
the transformer nameplate rating.

Category Single Phase Three Phase KVA


KVA
I 5 to 500 15 to 500

II 501 to 1667 501 to 5000


III 1668 to 10000 5001 to 30000
IV Above 10000 Above 30000

TABLE 10-2
TRANSFORMER CATEGORIES

To provide a more comprehensive representation of the long-term effects of system


conditions on power transformers, each category includes through-fault capability
limits, which are a function of the maximum current through the trans-former. The
maximum current (in per unit [p.u.] of the trans-former base rating) is calculated
based on the transformer short-circuit impedance for category I and II transformers.

Maximum current calculation for category III and IV trans-formers is based on the
overall impedance of the transformer short-circuit impedance and the system
impedance.

Chapter 10 Page 12 Transformer Protection


CATEGORY I TRANSFORMERS
Figure 10-3 shows the through-fault capability limit curve for category I transformers.
The curve reflects both thermal and mechanical considerations. For short-circuit
currents at 25–40 times the base current, the I2t limit of 1250 defines the curve,
where I is the symmetrical fault current in multiples of the transformer base current
and t is in seconds.

Current (I) is based on the transformer’s per-unit short circuit impedance. A


transformer with 4 percent impedance will have a maximum short circuit current of
25 p.u. (1/0.04), which results in a time of 2 seconds (1250/252) for its through-fault
capability limit.

Figure 10-3. Through-Fault Capability limit curve for Liquid-Immersed


Category I Transformers

Chapter 10 Page 13 Transformer Protection


CATEGORY II AND III TRANSFORMERS
For Category II and III transformers, the IEEE standard provides an additional
through-fault capability limit curve. The additional curve takes into account the fault
frequency that the transformer is subjected to throughout its entire life. In general, use
a frequent-fault curve if fault frequency is higher than ten through-faults for category
II transformers and higher than five through-faults for category III transformers. Fault
frequency is considered over the life of the transformer.

Figure 10-4 represents the through-fault capability limit curve for category II and III
transformers that experience infrequent faults. The curve is limited to two seconds.

To acknowledge the cumulative nature of damage caused by through-faults, the


standard supplements the through-fault capability limit curve to reflect mechanical
damage. It calculates the I2t curve based on the actual transformer impedance. For
category II transformers, consider the mechanical duty for fault currents higher than
70 percent of maximum possible short-circuit current. For category III and IV
transformers, consider mechanical duty for through-fault currents higher than 50
percent of maximum possible short-circuit current.

Figure 10-5 shows the through-fault capability limit curve for a category II
transformer with 7 percent impedance. The I 2t calculation is at maximum short-circuit
current for a time of 2 seconds.

For a transformer with 7 percent impedance, I2t calculates at 408 as shown below:

I = 1/0.07 = 14.29; this is the maximum short-circuit cur-rent in p.u. of


transformer base rating

I2t = (14.29) 2 • .2 = 408

The lower portion of the curve is 70 percent of maximum

short-circuit current and the I2t calculated above.

I = 0.7 • 14.29 = 10

t = 408/(I)2 = 4.08

Chapter 10 Page 14 Transformer Protection


Figure 10-4. Through-Fault Capability Limit Curve for Liquid-Immersed
Category II and III Transformers with Infrequent Faults

Figure 10-5. Through-Fault Capability Limit Curve for Liquid-Immersed


Category II Transformers with Frequent Faults

Chapter 10 Page 15 Transformer Protection


CATEGORY IV TRANSFORMERS
Figure 10-6 shows the through-fault capability limit curve for category IV
transformers. The curve represents both the frequent and the infrequent fault
occurrences. For category III and IV transformers the mechanical duty limit curve
starts at 50 percent of the short circuit current.

Figure 10-6. Through-Fault Capability Limit Curve for Liquid-Immersed


Category IV Transformers

Chapter 10 Page 16 Transformer Protection


PROTECTION CONSIDERATIONS
After determining the proper through-fault capability limit curve for a particular
transformer, select a time-overcurrent characteristic to coordinate with the through-
fault capability limit curve.

In distribution transformer applications where a number of feeders are connected to


the low-voltage bus, the feeder relays become the first line of defense. IEEE
Standard C37.91 recommends setting the inverse time-overcurrent characteristic of
the feeder relays to coordinate with the through-fault capability limit curve of the
transformer, as shown in Figure 10-7.

Coordinating an overcurrent element with an I2t thermal element requires further


consideration. Although the extremely inverse time-overcurrent characteristic of the
overcurrent relay seems to emulate the shape of the thermal curve, the coordination
is only valid for a fixed initial overcurrent condition. Once an overload or through-fault
condition causes the transformer winding temperature to rise, coordination between
the overcurrent relay and the thermal element is no longer valid. In this situation, the
overcurrent relay does not prevent thermal damage caused by cyclic overloads.

Figure 10-7. TOC Coordination with Category IV Transformer Through-Fault


Capability Limit Curve

Chapter 10 Page 17 Transformer Protection


TRANSFORMER OVEREXCITATION
The flux in the transformer core is directly proportional to the applied voltage and
inversely proportional to the frequency. Overexcitation can occur when the per-unit
ratio of voltage to frequency (Volts/Hz) exceeds 1.05 p.u. at full load and 1.10 p.u. at
no load. An increase in transformer terminal voltage or a decrease in frequency will
result in an increase in the flux.

Overexcitation results in excess flux, which causes trans-former heating and


increases exciting current, noise, and vibration.

Some of the possible causes of overexcitation are:

• Problems with generator excitation system


• Operator error
• Sudden loss-of-load
• Unloaded long transmission lines

Figure 10-8. Harmonic Content of Transformer Exciting Current as a


Function of the Applied Voltage

Chapter 10 Page 18 Transformer Protection


TRANSFORMER DIFERENTIAL RELAY AND OVEREXCITATION
Saturation of the power transformer core, caused by overexcitation, results in the
flow of excitation current. In an extreme case, the increase in excitation current can
cause the trans-former differential relay to operate. Because the characteristic of the
transformer differential relay does not correlate to the transformer overexcitation limit
curve, it is impractical to depend on transformer differential protection to provide
overexcitation protection. Furthermore, operation of the transformer differential relay
for an overexcitation condition, which is a system phenomenon, can lead fault
investigators to start their investigation at the transformer instead of looking for
system disturbances. Use a Volts/Hz element to provide overexcitation protection.
Under overexcitation conditions, block or re-strain the differential element to prevent
false operations.

If a Volts/Hz element is not available, use the harmonic content of the excitation
current to determine the degree of overexcitation of the transformer core. Table 10-3
shows typical harmonic content of the excitation current.

Frequency Magnitude % of Nominal

(primary amps)

Fundamental 22.5 52.0

Third 11.1 26.0

Fifth 4.9 11.0

Seventh 1.8 4.0

Table 10-3
Tr an sfo rme r Exc it at ion Current And Harmonics

The excitation current consists mainly of odd harmonics, with the third harmonic
being the predominant harmonic. The third harmonic is a triplen harmonic. Delta-
connected transformer windings (power or current transformers) filter out triplen
harmonics (3, 9, 15, etc.). Since the next highest harmonic is the fifth harmonic, most
transformer differential relays use the fifth harmonic to detect overexcitation condi-
tions.

In applications where the power transformer might be overexcited, block the


differential element from operating on transformer exciting current.

Chapter 10 Page 19 Transformer Protection


OVEREXCITATION PROTECTION
Obtain the overexcitation limit for a particular transformer through the transformer
manufacturer. The overexcitation limit is either a curve or a set point with a time
delay. Figure 10-9 shows typical overexcitation limit curves for different transformers.

Figure 10-9. Typical Transformer Overexcitation Limit Curves

Provide overexcitation protection for power transformers through a Volts/Hz element


that calculates the ratio of the measured voltage to frequency in p.u. of the nominal
quantities.

In applications that provide overexcitation protection for a generator step-up (GSU)


transformer, consider the overexcitation limits of both the GSU and the generator.
Then set the overexcitation element to coordinate with the limit curves of both the
GSU and the generator.

Chapter 10 Page 20 Transformer Protection


WINDING FAULTS
A fault on a transformer winding is controlled in magnitude by the following factors:

i. source impedance

ii. neutral earthing impedance

iii. transformer leakage reactance

iv. fault voltage

v. winding connection

Several distinct cases arise and are examined below.

Chapter 10 Page 21 Transformer Protection


Star-Connected Winding with Neutral Point Earthed through an
Impedance
The winding earth fault current depends on the earthing impedance value and is also
proportional to the distance of the fault from the neutral point, since the fault voltage
will be directly proportional to this distance.

For a fault on a transformer secondary winding, the corresponding primary current


will depend on the transformation ratio between the primary winding and the short-
circuited secondary turns. This also varies with the position of the fault, so that the
fault current in the transformer primary winding is proportional to the square of the
fraction of the winding that is short circuited. The effect is shown in Figure 10-10
Faults in the lower third of the winding produce very little current in the primary
winding, making fault detection by primary current measurement difficult.

Figure 10-10

Chapter 10 Page 22 Transformer Protection


Star-connected winding with Neutral Point Solidly Earthed
The fault current is controlled mainly by the leakage reactance of the winding, which
varies in a complex manner with the position of the fault. The variable fault point
voltage is also an important factor, as in the case of impedance earthing. For faults
close to the neutral end of the winding, the reactance is very low, and results in the
highest fault currents. The variation of current with fault position is shown in Figure
10-11.

Figure 10-11

For secondary winding faults, the primary winding fault current is determined by the
variable transformation ratio; as the secondary fault current magnitude stays high
throughout the winding, the primary fault current is large for most points along the
winding.

Chapter 10 Page 23 Transformer Protection


Delta-connected Winding
No part of a delta-connected winding operates with a voltage to earth of less than
50% of the phase voltage.

The range of fault current magnitude is therefore less than for a star winding. The
actual value of fault current will still depend on the method of system earthing; it
should also be remembered that the impedance of a delta winding is particularly high
to fault currents flowing to a centrally placed fault on one leg. The impedance can be
expected to be between 25% and 50%, based on the transformer rating, regardless
of the normal balanced through-current impedance. As the prefault voltage to earth
at this point is half the normal phase voltage, the earth fault current may be no more
than the rated current, or even less than this value if the source or system earthing
impedance is appreciable.

The current will flow to the fault from each side through the two half windings, and
will be divided between two phases of the system. The individual phase currents may
therefore be relatively low, resulting in difficulties in providing protection.

PHASE TO PHASE FAULTS


Faults between phases within a transformer are relatively rare; if such a fault does
occur it will give rise to a substantial current comparable to the earth fault currents.

Chapter 10 Page 24 Transformer Protection


INTERTURN FAULTS
In low voltage transformers, interturn insulation breakdown is unlikely to occur unless
the mechanical force on the winding due to external short circuits has caused
insulation degradation, or insulating oil (if used) has become contaminated by
moisture.

A high voltage transformer connected to an overhead transmission system will be


subjected to steep fronted impulse voltages, arising from lightning strikes, faults and
switching operations. A line surge, which may be of several times the rated system
voltage, will concentrate on the end turns of the winding because of the high
equivalent frequency of the surge front. Part-winding resonance, involving voltages
up to 20 times rated voltage may occur. The interturn insulation of the end turns is
reinforced, but cannot be increased in proportion to the insulation to earth, which is
relatively great. Partial winding flashover is therefore more likely. The subsequent
progress of the fault, if not detected in the earliest stage, may well destroy the
evidence of the true cause.

A short circuit of a few turns of the winding will give rise to a heavy fault current in
the short-circuited loop, but the terminal currents will be very small, because of the
high ratio of transformation between the whole winding and the short-circuited turns.

Figure 10-12

The graph in Figure 10-12 shows the corresponding data for a typical transformer of
3.25% impedance with the short-circuited turns symmetrically located in the centre of
the winding.

Chapter 10 Page 25 Transformer Protection


CORE FAULTS
A conducting bridge across the laminated structures of the core can permit sufficient
eddy-current to flow to cause serious overheating. The bolts that clamp the core
together are always insulated to avoid this trouble. If any portion of the core
insulation becomes defective, the resultant heating may reach a magnitude sufficient
to damage the winding. The additional core loss, although causing severe local
heating, will not produce a noticeable change in input current and could not be
detected by the normal electrical protection; it is nevertheless highly desirable that
the condition should be detected before a major fault has been created. In an oil-
immersed transformer, core heating sufficient to cause winding insulation damage
will also cause breakdown of some of the oil with an accompanying evolution of gas.
This gas will escape to the conservator, and is used to operate a mechanical relay.

Fault Type Protection Used

Primary winding Phase-phase fault Differential; Overcurrent

Primary winding Phase-earth fault Differential; Overcurrent

Secondary winding Phase-phase fault Differential

Secondary winding Phase-earth fault Differential; Restricted Earth Fault

Interturn Fault Differential, Buchholz

Core Fault Differential, Buchholz

Tank Fault Differential, Buchholz; Tank-Earth

Overfluxing Overfluxing

Overheating Thermal

Chapter 10 Page 26 Transformer Protection


RESTRICTED EARTH FAULT PROTECTION
Conventional earth fault protection using overcurrent elements fails to provide
adequate protection for transformer windings. This is particularly the case for a star-
connected winding with an impedance-earthed neutral.

The degree of protection is very much improved by the application of restricted earth
fault protection (or REF protection). This is a unit protection scheme for one winding
of the transformer. It can be of the high impedance type as shown in Figure 10-13, or
of the biased low impedance type. For the high-impedance type, the residual current
of three line current transformers is balanced against the output of a current
transformer in the neutral conductor. In the biased low-impedance version, the three
phase currents and the neutral current become the bias inputs to a differential
element. The system is operative for faults within the region between current
transformers, That is, for faults on the star winding in question. The system will
remain stable for all faults outside this zone.

Figure 10-13

Chapter 10 Page 27 Transformer Protection


DIFFERENTIAL PROTECTION
BASIC DIFFERENTIAL RELAYING SCHEME
The basic differential relaying scheme is shown in Figure 10-14. Under normal load
conditions, current flows through the protected equipment (e.g., generator, bus, or
transformer) and the current transformer secondary currents I1 and I2 circulate
through path IA. With a protective relay connected between points 1 and 2, no
current will flow through the relay under normal conditions. Should a fault occur
external to the equipment (Fext), current flow will be increased but it will be in the
same relative direction as under normal conditions, and the relay will not operate for
this external fault condition.

When a fault occurs in the protected equipment (Fint), the current flow on one side is
reversed, upsetting the normal balance and causing current ID to flow through the
relay (operating coil) from point 1 to point 2.

As long as the current transformer secondary currents are nearly equal, no


appreciable current will flow through the relay operating coil. Any error current to
other phases or to ground will upset the balance and send current through the relay
operating coil. If this current exceeds the pickup setting of the relay, it will operate to
trip the breaker (via a lockout relay) and to disconnect the faulty apparatus.

Figure 10-14. Basic Differential Relay Connections

Chapter 10 Page 28 Transformer Protection


TRANSFORMER DIFFERENTIAL PROTECTION

Percentage restraint differential protective relays have been in service for many
years. Figure 10-15 shows a typical differential relay connection diagram.
Differential elements compare an operating current with a restraining current. The
operating current (also called differential current), IOP, can be obtained as the phasor
sum of the currents entering the protected element:

IOP is proportional to the fault current for internal faults and approaches zero
for any other operating (ideal) conditions.

Figure 10-15
Typical Differential Relay Connection Diagram

Following are the most common ways to obtain the restraining current:

Chapter 10 Page 29 Transformer Protection


where k is a compensation factor, usually taken as 1 or 0.5.

Equation 3 and Equation 4 offer the advantage of being applicable to differential


relays with more than two restraint elements.

The differential relay generates a tripping signal if the operating current, IOP, is
greater than a percentage of the restraining current, IRT:

Figure 10-16. Percentage Restraint Margin

Chapter 10 Page 30 Transformer Protection


Operating (Differential) Current

Relay Operating Characteristic

Total False Current

CT False Current

Mismatch False Current


(CT Ratio, Transformer Tap
Changer)

Transformer Magnetizing Current

Bias (Restraint ) Current

Figure 10-17 shows a typical differential relay operating characteristic. This


characteristic consists of a straight line having a slope equal to SLP and a horizontal
straight line defining the relay minimum pickup current, IPU. The relay operating
region is located above the slope characteristic (Equation 5), and the restraining
region is below the slope characteristic.

Figure 10-17. Differential Relay With Dual Slope Characteristic

Chapter 10 Page 31 Transformer Protection


Differential relays perform well for external faults, as the CTs reproduce the primary
currents correctly. When one of the CTs saturates, or if both CTs saturate at different
levels, false operating current appears in the differential relay and could cause relay
misoperation. Some differential relays use the harmonics caused by CT saturation
for added restraint and to avoid misoperations. In addition, the slope characteristic of
the percentage differential relay provides further security for external faults with CT
saturation. A variable-percentage or dual-slope characteristic, further increases relay
security for heavy CT saturation. Figure 10-17 shows this characteristic as a dotted
line.

CT saturation is only one of the causes of false operating current in differential


relays. In the case of power transformer applications other possible sources of error
are:

• Mismatch between the CT ratios and the power transformer ratio


• Variable ratio of the power transformer caused by a tap changer
• Phase shift between the power transformer primary and secondary currents
for delta-wye connections
• Magnetizing inrush currents created by transformer transients because of
energization, voltage recovery after the clearance of an external fault, or
energization of a parallel transformer
• High exciting currents caused by transformer overexcitation

The relay percentage restraint characteristic typically solves the first two problems.
A proper connection of the CTs or emulation of such a connection in a digital relay
(auxiliary CTs historically provided this function) addresses the phase shift problem.
A very complex problem is that of discriminating internal fault currents from the false
differential currents caused by magnetizing inrush and transformer overexcitation.

Chapter 10 Page 32 Transformer Protection


APPLICATION EXAMPLE
SETTING THE ABB RET 521 TRANSFORMER DIFFERENTIAL
RELAY

INTRODUCTION

The numerical transformer terminal RET 521 is designed for fast and selective
protection and control of two- and three-winding transformers, auto-transformers,
generator-transformer blocks and shunt reactors. The RET 521 has low
requirements on the main Current Transformers and no interposing CTs are
necessary.

Flexibility is provided to cover for different applications in form of transformer size,


vector groups, system neutral grounding and extension of protection functions
according to the user’s preference. The selection of functionality from the modular
hardware and software is made according to the requirements for selectivity and
reliability and following the user’s preference. Big and important transformers such
as generator-transformer blocks or large network transformers can use two RET 521
and include the modular protection software selectively to obtain redundancy.

Smaller transformers and shunt reactors can include the modular software in one
RET 521 and can also use the programmable logic to provide trip or indication for
external protections (e.g. Buchholz), thus providing a very compact design for
protection and control. The RET 521 optionally includes a voltage control function for
transformers with onload tap changers, thus providing a very versatile modular unit
for protection and control of the major number of power transformers.

The RET 521 includes setting adaptation to power transformer rating and instrument
transformer ratios to allow protection settings in “per unit” (p.u.) or percent (%), of the
power transformer rating, thus facilitating the protection settings to an optimum.

Chapter 10 Page 33 Transformer Protection


The RET 521 is supplied for 2-winding applications and 3-winding applications.

Chapter 10 Page 34 Transformer Protection


Chapter 10 Page 35 Transformer Protection
TRANSFORMER DIFFERENTIAL PROTECTION (DIFP)

Differential protection is one of the most important and the most commonly used
protection for transformers of approximately 10 MVA and above. The differential
protection simplicity of comparing current into all terminals of the transformer gives it
a very high reliability. The differential protection does an excellent job of meeting a
large number of the protection requirements but must be combined with other
protections to provide full transformer protection.

RET 521 has two variants of transformer differential protections intended for two-
winding and three-winding transformers. Up-to five restrained three-phase current
inputs are available for three-winding applications.

General

The transformer differential protection is a unit protection. It serves as the main


protection of transformers in case of faults in the windings. The protective zone of a
differential protection includes the transformer itself, the bus-work or cables between
the current transformer and the power transformer.

Electrical internal faults are very serious and cause immediate serious damage.
Short circuits and earth-faults on windings and terminals are generally detectable by
the differential protection. Inter-turn fault, which is flashover between conductors
within the same physical winding, is also possible to detect if enough number of turns
are short circuited. Inter-turn faults are the most difficult transformer winding faults to
detect with electrical protections.

A small inter-turn fault including just a few turns will result in an undetectable amount
of current until it has develop into an earth-fault. For this reason it is important that
the differential protection has a high sensitivity and that it is possible to use a
sensitive setting without causing unwanted operations for external faults.

It is important that the faulted transformer should be disconnected as fast as


possible. As the differential protection is a unit protection it can be designed for fast
tripping, thus providing selective disconnection of the faulty transformer. The
differential protection should never operate to faults outside the protective zone.

A transformer differential protection compares the current flowing to the transformer


with the current leaving the transformer. Power transformers introduce often not only
a change in magnitudes of voltages and currents but also a change in phase angle.
These effects must be considered in obtaining the correct analysis of fault conditions
by the differential protection.

Traditional transformer differential protection functions required auxiliary


transformers for correction of the phase shift and ratio. Numerical microprocessor
based differential algorithm as implemented by RET 521 compensate for both the
turns-ratio and the phase shift internally in the software. No auxiliary current
transformers are necessary.

Chapter 10 Page 36 Transformer Protection


The differential current should theoretically be zero during normal load or external
faults if the turn-ratio and the phase shift are correctly compensated. However, there
are several different phenomena other than internal faults that will cause unwanted
and false differential currents. The main reasons for unwanted differential currents
are:

• Mismatch due to different position of the tap changer different characteristics,


loads and operating conditions of the current transformers

• Zero sequence currents that only flow on one side of the power transformer
normal magnetizing currents

• Magnetizing inrush currents

• Overexcitation magnetizing currents

The following paragraphs describe how these reasons of unwanted differential


currents can be taken into consideration.

Magnetizing inrush current

The magnetizing inrush is a transient condition which occurs when a power


transformer is energized. Similar inrush currents flow when the voltage return to
normal after the clearance of shunt faults. The magnetizing current appears as a
differential current to the transformer differential protection. It is not a fault condition
and the protection must remain stable during the inrush transient, a requirement
which is a major factor in the design of differential protection for transformers. With
improved modern steels in the manufacture of power transformers, and application
of very fast differential relays, magnetizing inrush phenomena came into more
prominence.

The shape, magnitude and duration of the inrush current depend on the following
characteristic factors:

• The source impedance

• The size of the transformer

• The location of energized winding (inner or outer)

• The connection of the windings

• The point of wave when the breaker closes

• The magnetic properties of the core

• The remnance of the core

• The use of pre-insertion resistors

Chapter 10 Page 37 Transformer Protection


Initial Inrush: The inrush current can appear in all three phases and in an earthed
neutral. The magnitude of the inrush current to the inner winding is larger than the
inrush current to the outer winding. The magnitude of the inrush current is 10-20
times in the first case and 5-10 times the rated current in the second case. Usually,
the high-voltage winding is the outer winding and the low-voltage winding is the inner
winding. The inrush current decays relatively slowly. The time constant of the
transient is relatively long, being from perhaps 0.1 seconds for a 100 kVA

Chapter 10 Page 38 Transformer Protection


transformer and up to 1.0 second for a large unit. The magnetizing current has been
observed to be still changing up to 30 minutes after switching on.

The maximum inrush current develops if the switching occurs when the voltage is
close to zero and the new flux from the inrush current gets the same direction as the
remnant flux. The sum of the two fluxes can exceed the saturation flux. The inrush
current will be small when the new flux from the inrush current gets the opposite
direction as the remnant flux. The magnitude of the inrush current depends therefore
on the point on wave when we close the transformer switch.

The source impedance of the power system and the air-core reactance of the
energized winding determine the magnitude of the inrush current when the core
saturates. The probability that the maximum inrush current should occur is low. One
out of 5-6 times, the switching should generate an inrush current close to the
maximum.

Recovery Inrush: When the power system voltage is reestablished after a short
circuit has been cleared elsewhere in the power system, the recovery inrush currents
will flow which fortunately are lower than initial inrush currents. Still, a differential
relay which has been stable during a heavy external fault may mis-operate due to
recovery inrush when the fault is cleared. To prevent this, the recovery inrush must
be recognized as well.

Sympathetic Inrush: When a second power transformer is energized in parallel with


another which was already in operation, the sympathetic inrush currents will flow in
the later, which are lower than initial inrush currents. The phenomenon of
sympathetic inrush is quite complex. Although inrush current phenomena associated
with the energizing of one single power transformer are well understood, there are
certain elements of uniqueness encountered when one transformer is suddenly
energized in parallel with another which was already in operation.

Chapter 10 Page 39 Transformer Protection


Inrush restraint methods

The waveform of transformer magnetizing current contains a proportion of harmonics


which increases as the peak flux density is raised to the saturating condition. The
inrush current is an offset current with a waveform which is not symmetrical about
the time axis. The wave typically contains both even and odd harmonics. Typical
inrush currents contain substantial amounts of second and third harmonics and
diminishing amounts of higher orders. The presence of the bi-directional waveforms
substantially increases the proportion of the second harmonic, being up to more than
60% of the fundamental harmonic.

It can also be observed that the inrush wave is distinguished from a fault wave by a
period in each cycle during which very low magnetizing currents flow, when the core
is not in saturation. This property of the inrush current can be exploited to distinguish
inrush condition from an internal fault.

Sensitive differential protections may operate incorrectly when a power transformer


is energized. To make a differential protection stable against inrush currents,
measures must be taken in order to make the algorithm capable to distinguish the
inrush phenomena from a fault. It is necessary to provide some forms of detection of
inrush conditions and restrain the differential protection.

Second harmonic restraint is an effective method to avoid unwanted operations


when energizing a power transformer, as the second harmonic always is present in
the inrush current. The second harmonic content of a differential current is compared
to the fundamental harmonic of the same differential current and if the ratio is higher
than a set limit, then an inrush condition is assumed.

Normal primary fault currents do not contain second or other even harmonics. The
secondary current of a current transformer which is energized into steady state
saturation will also contain odd harmonics but not even harmonics. However, should
the current transformer be saturated by the transient component of the fault current,
the resulting saturation is not symmetrical and even harmonics are introduced into
the output current. This can have the disadvantage of increasing the fault clearance
time for heavy internal faults with current transformer saturation.

With a combination of the second harmonic restraint and the waveform


restraint methods it is possible to get a protection with high security and stability
against inrush effects and at the same time maintain high performance in case of
heavy internal faults even if the current transformers are saturated.

Both these restraint methods are applied by RET 521. Two possible combinations
are available. The default or standard method (conditionally) is to let the harmonic
and the waveform methods operate in parallel only when the power transformer is
not yet energized, and switch off the second harmonic criterion when the power
transformer has been energized. The second harmonic method is also active a short
time when heavy external fault has been detected. The second method (always) is to
let the second harmonic method be active all the time. The waveform method
operates in parallel all the time. The choice of combination of restraint method is
done with a setting parameter. Option Conditionally is recommended as the default

Chapter 10 Page 40 Transformer Protection


setting. Option Always can be used to increase the stability if the current
transformers are sufficiently large so that the harmonics produced by transient
saturation do not delay normal operation of the protection.

The second harmonic restraint function has a settable level. If the ratio of the second
harmonic to fundamental harmonic in the differential current is above the settable
limit, the operation of the differential protection is restrained. It is recommended to
use the setting 15% as a default value in case no special reasons exist to
choose another setting.

Overexcitation magnetizing current

Over-excitation results from excessive applied voltage, possibly in combination with


low frequency, as with generator-transformer units. The risk is greatest for generator
transformers, although over-fluxing trouble has been known to occur for other
transformers as well.

The over-excitation condition itself usually does not call for high speed tripping of the
power transformer, but relatively high magnetizing currents, which are seen as pure
differential currents by the differential protection, may cause a false trip of the
differential protection.

Both excessive voltage and lower frequency will tend to increase transformer flux
density. An overexcited transformer is not a transformer fault. It is an abnormal
network condition for which a transformer differential protection should not operate.
The differential protection must remain stable during the over-excitation condition.

Over-excitation restraint method

Over-excitation current contains odd harmonics, because the waveform is


symmetrical about the time axis. As the third harmonic currents cannot possible flow
into a delta winding, the fifth harmonic is the lowest harmonic which can serve as a
criterion for over-excitation. The over-excitation on the delta side will produce
exciting currents that contain a large fundamental frequency component with little
odd harmonics. In this application the fifth harmonic limit must be set to a relatively
low value.

RET 521 differential protection function is provided with a fifth harmonic restraint to
prevent the protection from operation during an over-excitation condition of a power
transformer. If the ratio of the fifth harmonic to fundamental harmonic in the
differential current is above a settable limit the operation is restrained. It is
recommended to use the setting 25% as a default value in case no special
reasons exist to choose another setting.

Transformers likely to be exposed to over-voltage or under-frequency conditions


should be provided with an over-excitation protection based on V/Hz to achieve trip
before the internal limit is reached.

Chapter 10 Page 41 Transformer Protection


Cross-Blocking between Phases

Basic definition of the cross-blocking is that one of the three phases can block
operation (i.e. tripping) of the other two phases due to the properties of the
differential current in that phase (i.e. waveform, 2nd or 5th harmonic content).

In DIFP algorithm the user can control the cross-blocking between the phases via
the setting parameter “CrossBlock”.

When parameter “CrossBlock” is set to “On”, cross blocking between phases will be
introduced. There is not any time settings involved, but the phase with the operating
point above the set bias characteristic will be able to cross-block other two phases if
it is self-blocked by any of the previously explained restrained criteria. As soon as the
operating point for this phase is below the set bias characteristic cross blocking from
that phase will be inhibited. In this way cross-blocking of the temporary nature is
achieved. In should be noted that this is the default (i.e. recommended) setting value
for this parameter.

When parameter “CrossBlock” is set to “Off”, any cross blocking between phases will
be disabled. It is recommended to use the value “Off” with caution in order to
avoid the unwanted tripping during initial energizing of the power transformer.

Normal service

During normal service a small differential current flows through the differential
protection. The current is due to the excitation current of the power transformer, ratio
errors in the current transformers and changes of the position of the tap changer, if
provided.

Normal magnetizing currents are of the order of 1% or less which is low in


comparison with the operate value of the differential protection and can be
neglected.

The power transformer ratio changes as a result of changing the tap of an on-load
tap changer. This will cause false differential currents to the differential protection
function if not the tap position is known. A tap changer in the end position gives a
differential current of 10-20% of load current depending of the regulating range of the
tap changer. If the tap position is not known, the actual ratio will only match at one
point of the tap changing range. Therefore, the mismatch due to this must be taken
care of by setting a lower base sensitivity of the differential protection. A setting of
10-15% higher than the mismatch is usual.

Tap changer position adaption

If the tap position is known and the differential function is supplied with regularly
updated information about the tap changer position an adaption to the actual turn
ratio can be done. In this case it is possible to set a much higher sensitivity of the
differential protection. RET 521 has this feature and it is recommended to set the
parameter “Idmin” around 15% - 20% for this applications.

Chapter 10 Page 42 Transformer Protection


External faults

For faults outside the protective zone a relatively large differential current can occur
due to the position of the tap changer and differences between the current
transformers. At maximum through fault current the unwanted differential current
produced by a small percentage unbalance may be substantial. There is a risk for
current transformer saturation for heavy faults just outside the protective zone. The
differential protection should not operate for the differential current in these cases.

Restrained differential protection

To make a differential relay as sensitive and stable as possible, restrained differential


protections have been developed and are now adopted as the general practice in the
protection of power transformers. The protection should be provided with a
proportional bias which makes the protection operate for a certain percentage
differential current related to the current through the transformer. This stabilizes the
protection under through fault conditions while still permitting the system to have
good basic sensitivity.

The bias current can be defined in many different ways. One classical way of
defining the bias current has been Ibias = (I1 + I2) / 2, where I1 is the magnitude of the
power transformer primary current, and I2 the magnitude of the power transformer
secondary current. However, it has been found that if the bias current is defined as
the highest power transformer current this will reflect the difficulties met by the
current transformers much better.

The differential protection function in RET 521 uses the highest current of all restrain
inputs as bias current. The currents measured on all sides are converted in pu
values using the power transformer winding rated currents. After that the highest pu
value is taken as bias current in pu. For applications were the power transformer
rated current and the CT primary rated current can differs considerably, (applications
with T-connections), measured currents in the T connections are converted to pu
value using the rated primary current of the CT, but one additional “measuring” point
is introduced as sum of this two T currents. This summed current is converted to pu
value using the power transformer winding rated currents. After that the highest pu
value is taken as bias current in pu. In this way best possible combination between
sensitivity and security for differential protection function with T connection is
obtained.

The main philosophy behind the principle with the operate bias characteristic is to
decrease the operate sensitivity when the current transformers have difficult
operating conditions. This bias quantity gives the best stability against an unwanted
operation of the overall differential protection. Fig. 25 shows the set of 5 operate-bias
characteristics that are available in RET 521.

Chapter 10 Page 43 Transformer Protection


The usual practice for transformer protection is to set the bias characteristic to a
value of at least twice the value of the expected spill current under through faults
conditions. These criteria can vary considerably from application to application and
are often a matter of judgment. The second slope is increased to ensure stability
under heavy through fault conditions which could lead to increased differential
current due to saturation of current transformers.

Characteristic number 3 and the default sensitivity, ldmin set to 30% of the power
transformer rated current can be recommended as a default setting in normal
applications. If the conditions are known more in detail, higher or lower sensitivity
can be chosen. The selection of suitable characteristic should in such cases be
based on the knowledge of the class of the current transformers, availability of
information on the on load tap changer (OLTC) position, short circuit power of the
systems, etc. If the differential function is supplied with regularly updated information
about the OLTC position it is possible to set a higher sensitivity.

Chapter 10 Page 44 Transformer Protection


Elimination of zero sequence currents

A differential protection may operate unwanted due to external earth faults in cases
where the zero sequence current can flow only on one side of the power transformer
but not on the other side. This is the situation when the zero sequence current
cannot be properly transformed to the other side of the power transformer. Power
transformer connection groups of Yd or Dy type cannot transform the zero sequence
current. If a delta winding of a power transformer is earthed via an grounding
transformer inside the zone protected by the differential protection there will be an
unwanted differential current in case of an external earth fault. Therefore it is
necessary to eliminate the zero sequence current from the delta side. It is possible to
do it by setting the DIFP parameter “ZSCSub” (zero-sequence current subtraction) to
“On”.

To make the overall differential protection insensitive to external earth faults in these
situations the zero sequence currents must be eliminated from the power
transformer terminal currents, so that they do not appear as the differential currents.
This had once been achieved by means of intermediate current transformers. The
elimination of zero sequence current is done numerically in RET 521 and no auxiliary
transformers or zero sequence traps are necessary.

It should be noted that this setting will not influence at all the differential current
calculation on the side of power transformer where the difference between two
individual phase currents are used (i.e. for example on primary side of Yd connected
power transformer).

The following table gives the summary of the recommended settings for “ZSCSub”
parameter for different power transformer vector groups and type applications:

This feature enables the user to use DIFP algorithm in RET 521 for differential
protection for some special applications listed below:

• Overall differential protection of common and serial winding for


autotransformers with included star point currents into the scheme
(traditionally high-impedance differential protection has been used for this
application)

• Differential protection of railway power transformers (i.e. split-single-phase


transformers, Scott transformers etc.)

• Differential protection for shunt reactors and generators

Chapter 10 Page 45 Transformer Protection


Chapter 10 Page 46 Transformer Protection
INTERNAL FAULTS

For faults inside the protective zone, a current proportional to the fault current occurs
in the differential circuits and the transformer differential protection will operate.

The transformer differential protection is often provided with an unrestrained


differential function. The unrestrained differential protection offers faster fault
clearance for heavy internal faults and it is not blocked for magnetizing inrush or
over-excitation magnetizing currents. The purpose of the unrestrained differential
protection is also to exclude the risk of excessive restraint resulting from the
harmonic distortions of the secondary currents from the current transformers in case
of heavy internal faults.

The current setting for the unrestrained function has to be set above the maximum
inrush current when the transformer is energized. As the magnitude depends on
several factors it is difficult to accurately predict the maximum anticipated level of
inrush current. The magnitude is normally within the range 5-20 times the rated
current of the power transformer (Ir).

RET 521 differential protection function is provided with an unrestrained differential


function, that measures the fundamental harmonic of the differential current. The
differential current operate value can be set in the range 5 to 25 times the rated
current of the power transformer. The following settings can be recommended

The power transformers are assumed to be step-down transformers with power flow
from the high voltage side to the low voltage side.

A setting of 13 x Ir or higher can be required when very large through fault currents
may saturate the current transformers and cause a large differential current. This can
for example be the case when the bus is included in the protective zone of the
differential protection or when a breaker-and-a-half arrangement is used.

Chapter 10 Page 47 Transformer Protection


THREE-PHASE TIME OVERCURRENT PROTECTION (TOC)

General

A breakdown of the insulation between phase conductors or a phase conductor and


earth results in a short-circuit or an earth fault. Such faults can result in large fault
currents and may cause severe damage to the windings and the transformer core.
Furthermore, a fault with high fault currents may cause a high gas pressure. If the
pressure gets too high, it will damage the transformer tank. Depending on the
magnitude of the fault current overcurrent protections can be used to clear these
faults.

High fault currents may flow through a transformer when an external shunt fault
occurs on the network and may produce a relatively intense rate of heating of the
transformer. This can result in damage to the transformer. The copper losses
increase in proportion to the square of the per unit fault current. If the current is
limited only by the reactance of the transformer, the duration of external short-circuits
that a transformer can withstand without damage is relatively short. Phase
overcurrent protection is an important protection that can be used to clear the
transformer before the transformer is damaged.

Settings

In the CAP531 configuration tool it is possible to chose UserDef side as parameter


setting for SIDE2W or SIDE3W. When UserDef is choose then the setting IrUserDef
will be used as "rated" current for TOC.

For directional TOC the setting UrUserDef also have to be set. The direction for
User-Def side is the same as for the primary side. Observe that for secondary and
tertiary side Reverse direction means currents from power transformer and Forward
direction means currents to power transformer.

The operating current is normally set in per cent of the rated load current Ir of the
power transformer. However, if an overcurrent protection module is configured to
another object it is possible to define another base current not related to the power
transformer.

The lowset stage must be given a setting so that the highest possible load current
does not cause operation. The highest possible load current of the transformer is
given of the overload capacity of the transformer. The overload capacity is
dependent on for example the ambient temperature and the load cycle of the
transformer. Often the overload capacity of a transformer can be up to 1.4 times the
rated power. The corresponding settings of the lowset stage are 13% to 170% of the
overload capacity of the transformer. This setting includes a safety factor and the
reset ratio of the protection. The time setting shall be coordinated with the
protections of the outgoing feeders.

A power transformer can carry substantial overload during an hour or two. Many
utilities want to utilize this capability temporarily. When two or more transformers are
operated in parallel to share a common load, the overcurrent protection settings
should consider the short time overload on one transformer upon loss of the other

Chapter 10 Page 48 Transformer Protection


transformer and maybe set the operate value even higher than the recommendation
above. In such a case it is recommended that the transformer is provided with a
thermal overload protection.

As the overcurrent protection normally shall provide back-up protection functions for
outgoing feeders, it should be checked that the overcurrent protection has the
possibility to operate at minimum fault current within the back-up protection zone.
The backup function is not always possible to fulfill for example in case of a large
transformer and long feeders. In such cases other measures have to be considered.

The highset stage with a short or no time delayed operation must be set so that the
protection is selective to other protections in the power system. For an overcurrent
protection at the high voltage side, from where the fault current is fed, it is wanted to
have fast clearing of as many faults as possible within the transformer. The
protection must not operate for a fault on the low voltage side busbar. The highset
stage is recommended to be set at about 30% above the maximum fault current on
the low voltage side busbar. This setting includes a safety factor and the transient
overreach factor of the protection. The setting should also be above the transformer
inrush current. This should normally not be any problem to fulfill. However, if
problems with inrush should arise there is also a possibility to use the inrush block
signals from the differential protection function to block the phase overcurrent
function.

With this setting fast tripping is only obtained for severe faults on the feeding side of
the transformer. The protection operates delayed for faults on the remaining parts of
the winding and for faults on the load side of the transformer if the fault current and
the duration exceed the set value of the protection.

The highset stage of an overcurrent protection at the low voltage side must be time
delayed to prevent unwanted tripping of the transformer in case of faults on the
outgoing feeders. The current set value must be coordinated to the settings for the
protections of the outgoing feeders. If the transformer is connected to more than one
source of short-circuit current these restrictions are valid also for the highset stage at
the high voltage side.

Chapter 10 Page 49 Transformer Protection


MULTIPURPOSE GENERAL PROTECTION FUNCTION (GF)

General

A breakdown of the insulation between phase conductors or a phase conductor and


earth results in a short-circuit or an earth fault. Such faults can result in large fault
currents and may cause severe damage to the power system primary equipment.
Depending on the magnitude and type of the fault different overcurrent protections,
based on measurement of phase, ground or sequence current components, can be
used to clear these faults. Additionally it is sometimes required that these
overcurrent protections shall be directional and/or voltage controlled/restrained.

The over/under voltage protection is applied on power system elements such as


generators, transformers, motors and power lines in order to detect abnormal voltage
conditions. Depending on the type of voltage deviation and type of power system
abnormal condition different over/under voltage protections based on measurement
of phase-to-ground, phase-to-phase, residual or sequence voltage components can
be used to detect and operate for such incident.

The RET 521 terminal can be provided with up to twelve multipurpose general
function (GF) protection modules. All general function protection modules are
executed in RET 521 in the fastest internal execution cycle (i.e. five times in each
fundamental power system cycle). The function is always connected to three-phase
current and three-phase voltage input in the configuration tool, but it will always
measure only the single current and the single voltage quantity selected by the end
user in the setting tool (i.e. selected current quantity and selected voltage quantity).
Each module can be configured to any side of the power transformer. It is also
possible to configure any number of modules to the same side of the power
transformer. Each multipurpose general function module has got the following
protection elements built into it:

• Two non-directional overcurrent stages working completely independently


from each other but measuring the same quantity. The lowset stage can be
set to have either definite time delay or a user programmable inverse time
delay characteristic. Therefore any inverse curve according to IEC, IEEE or
ANSI standard can be obtained. Additionally the inverse time characteristic
can have instantaneous or time delayed reset. The highset stage can only
have definite time delay. Second harmonic blocking feature is available for
both stages, however it is not possible to use this with all possible choices of
measured current quantities.

• Current restrained feature is available in order to restrain (i.e. prevent) non-


directional overcurrent stages from starting if the measured current quantity is
not bigger than the set percentage of the current restrain quantity. This
feature can be switched off by a setting parameter.

• Voltage restrained/controlled feature is available in order to modify the pick-up


level of the lowset and/or highset non-directional overcurrent stage in
proportion to the magnitude of the measured voltage. This feature can be
switched off by a setting parameter.

Chapter 10 Page 50 Transformer Protection


• A directional criterion is available in order to prevent starting of the non-
directional overcurrent stage/s if the fault location is not in the set direction
(i.e. forward/ reverse)

• One overvoltage and one undervoltage stage. Both stages only have definite
time delay. These features work completely independently from the
overcurrent stages.

All these general protection function features can be individually enabled/disabled. It


is as well possible to simultaneously enable more than one feature (even all at the
same time).

OVER/UNDER VOLTAGE FEATURE

The GF function has one overvoltage and one undervoltage protection stage built-in.
These stages have a fixed hysteresis (i.e. reset ratio) of 99% and 101% respectively.
These two voltage stages use the selected measured voltage for the operating
quantity. The setting parameters are completely independent for these two stages.
However, it is possible to use only definite time delay for both of them. There is not
any correlation or influence between operation of the overcurrent and over/under
voltage stages within the GF function. If such correlation is desired (i.e. fuse-failure
or inadvertent energizing functionality), it have to be performed externally in the
terminal configuration, utilizing internal logical gates and individual stages blocking
inputs which are available on every GF function.

Chapter 10 Page 51 Transformer Protection


RESTRICTED EARTH FAULT PROTECTION (REF)

Break-down of the insulation between a phase conductor and earth in an effectively


or low impedance earthed power system results in a large fault current. A breakdown
of the insulation between a transformer winding and the core or the tank may result
in a large fault current which causes severe damage to the windings and the
transformer core. A high gas pressure may developed, damaging the transformer
tank.

Fast and sensitive detection of earth faults in a power transformer winding can be
obtained by the restricted earth fault protection in solidly earthed or low impedance
earthed networks. The only requirement is that the power transformer winding is
connected to earth in the star point (in case of star-connected windings) or via
separate grounding transformer (in case of delta-connected windings).

General

The restricted earth fault function is used as a unit protection function. It protects the
power transformer winding against the faults involving earth. However, it should be
noted that the earth faults are the most likely and common type of fault.

Overall transformer differential protection (DIFP) may not be sensitive enough to


operate for:

• earth faults in the transformer winding when the network is earthed through an
impedance,

• earth faults in the transformer winding in solidly earthed network when the point
of the fault is close to the winding star point.

For these type of faults the restricted earth fault protection is the fastest and the most
sensitive protection a power transformer winding can have. At the same time REF is
not affected, as differential protection, with the following power transformer related
phenomena:

• magnetizing inrush currents,

• overexcitation magnetizing currents,

• on load tap changer,

• external and internal phase faults which do not involve earth,

• symmetrical overload conditions.

Because of its properties the restricted earth fault protection may be used as main
protection of the transformer winding for faults involving earth. Traditionally restricted
earth fault protection was based on “high impedance” differential principle. However,
REF function available in RET 521 transformer protection terminal is a “low
impedance” type. It can be shortly described as an earth (i.e. zerosequence)
differential function with supplementary directional check feature.

Chapter 10 Page 52 Transformer Protection


Earth Fault current distribution

To successfully detect earth faults in earthed Y-connected or D-connected


transformerwindings the REF function shall discriminate between internal and
external earth faults to the protected zone. REF function in RET 521 do this in two
different ways:

• by diff-bias operating characteristics

• by the directional element

Earth fault current distribution in case of star connected windings for internal and
external fault are shown in Fig. 38 and Fig. 39 respectively.

Chapter 10 Page 53 Transformer Protection


As all differential protection, REF calculates the differential and the bias currents.
The differential current is equal to the vectorial difference between the neutral
current and residual current at the transformer winding terminal. The bias current is
calculated as the relatively highest of the four currents used by REF function (i.e.

Chapter 10 Page 54 Transformer Protection


three-phase currents and one neutral current). If protected winding has “T”
configuration (i.e. one-and- a-half breaker station) than bias current is calculated as
the relatively highest of the seven currents used by REF function (i.e. two sets of
three-phase currents and one neutral current).

The REF has only one operate-bias characteristic which is shown in Fig. 40. By
changing the minimum base sensitivity, REF bias characteristic in moved in the
operating plain. First and second slopes are fixed to 70% and 100% respectively.
First break point corresponds to a bias current of 1,25 pu. Second break point
corresponds to a bias current for which the required differential current for REF
function operation is 1,0 pu.

Differential and bias current from REF function are available as service values.
Additional directional criteria in REF function is pre-set to operate only for internal
earth faults (See Fig. 38 and Fig. 39 for more details). However, it should be noted
that is extremely important to properly set phase and neutral CT earthings (i.e.
parameter “CTearth”) to enable REF directional criteria to work properly. All CT
settings can be found under “Configuration” menu on built in HMI and in PST.

The second harmonic content of a neutral point current is compared to the


fundamental current component. If the ratio is higher than a pre-set limit in the REF
algorithm then the operation of the function is prevented. However this second
harmonic blocking feature is adaptively enabled or disabled within REF internal
algorithm by monitoring, among other quantities, the level of neutral point current

Chapter 10 Page 55 Transformer Protection


and status of the protected object (i.e. energized, not energized). Such solution
offers increased security when protected object is energized and dependable
operation in case of an internal fault.

Measured Quantities

REF is usually configured to measure one neutral current and one three-phase set of
currents. If protected winding has “T” configuration (i.e. one-and-a-half breaker
station) than REF should be configured to measure one neutral current and two sets
of three-phase currents.

Settings

The REF is a unit protection and it is based on zero sequence currents, which only
exist in case of an earth fault. Therefore the REF can be made very sensitive
because no load currents need to be considered. For each REF protection module
there is only three settings.

Parameter “Operation” sets the REF function ON or OFF. The parameter “Idmin”
defines the operating characteristic of the REF function. It is set as percentage of the
rated current of the protected winding. It is therefore very important to properly set
rated winding current. The parameter “roa” defines the operate area for the
directional criteria.

It is recommended to set Idmin to 30% when solidly earthed power transformer


windings should be protected. For low impedance earthed winding it should
be set to on third of the value of the maximum earth fault current for delta
connected windings and to 5% to 10% in case of star connected windings.

Chapter 10 Page 56 Transformer Protection


PROBLEM 7
Determine settings for the shown transformer differential relay

132 kV

200/5

IFL = 87 A

20 MVA
6% RET 521
RET521
200/5
IFL = 837 A 400 A

1200/5
13.8 kV

EI Relay
I3Ø = 14,000 A Ir =5A
51/50
IL-G fault = 12,000 A 600/5
Is = 0.6 X
TMS = 0.8 X
IT = 10 X

Chapter 10 Page 57 Transformer Protection


SETTING EXAMPLE OF TRANSFORMER NUMERICAL RELAY
132 kV
Second Harmonic Restraint Unit
15%
25%

200/5

IFL = 87 A

20 MVA
6% RET521
RET 521

200/5
IFL = 837 A 400 A

1200/5
13.8 kV

EI Relay
Ir =5
I3Ø = 14,000 A Is = 0.6 X
IL-G fault = 12,000 A 51/ TMS = 0.8 X
600/5 50 IT = 10 X

SETTING EXAMPLE OF TRANSFORMER NUMERICAL RELAY


132 kV
Fifth Harmonic Restraint Unit
25%
15%

200/5

IFL = 87 A

20 MVA
6% RET521
RET 521

200/5
IFL = 837 A 400 A

1200/5
13.8 kV

EI Relay
Ir =5
I3Ø = 14,000 A Is = 0.6 X
IL-G fault = 12,000 A 51/ TMS = 0.8 X
600/5 50 IT = 10 X

Chapter 10 Page 58 Transformer Protection


SETTING EXAMPLE OF TRANSFORMER NUMERICAL RELAY
132 kV
Cross-Blocking Between Phases
ON (Default)

200/5

IFL = 87 A

20 MVA
6% RET521
RET 521

200/5
IFL = 837 A 400 A

1200/5
13.8 kV

EI Relay
Ir =5
I3Ø = 14,000 A Is = 0.6 X
IL-G fault = 12,000 A 51/ TMS = 0.8 X
600/5 50 IT = 10 X

SETTING EXAMPLE OF TRANSFORMER NUMERICAL RELAY


132 kV
Zero Sequence Subtraction
OFF (Delta-Wye Transformer)

200/5

IFL = 87 A

20 MVA
6% RET521
RET 521

200/5
IFL = 837 A 400 A

1200/5
13.8 kV

EI Relay
Ir =5
I3Ø = 14,000 A Is = 0.6 X
IL-G fault = 12,000 A 51/ TMS = 0.8 X
600/5 50 IT = 10 X

Chapter 10 Page 59 Transformer Protection


SETTING EXAMPLE OF TRANSFORMER NUMERICAL RELAY
132 kV Internal Faults
(Unrestrained Differential
Functions)

200/5

IFL = 87 A

20 MVA
6% RET521
RET 521

200/5
IFL = 837 A 400 A

9 * Ir
Assuming
1200/5
13.8 kV
Transformer
Energized from High
EI Relay
Ir =5 Voltage Winding
I3Ø = 14,000 A Is = 0.6 X
IL-G fault = 12,000 A 51/ TMS = 0.8 X
600/5 50 IT = 10 X

SETTING EXAMPLE OF TRANSFORMER NUMERICAL RELAY


If tap changer position is available Idmin = 0.2 (20%)
Slope 1 = 15%
Slope 2 = 50%

If tap changer position is not available Idmin = 0.3 (30%)


132 kV Slope 1 = 30%
Slope 2 = 50%

200/5

IFL = 87 A

20 MVA RET521
RET 521
6%
200/5
IFL = 837 A 400
A

1200/5
13.8 kV

EI Relay
5 Ir =5
I3Ø = 14,000 A Is = 0.6 X
1/
IL-G fault = 12,000 A 5 TMS = 0.8 X
600/5
0 IT = 10 X

Chapter 10 Page 60 Transformer Protection


SETTING EXAMPLE OF TRANSFORMER NUMERICAL RELAY

Setting Parameter Parameter


Setting
Three Phase Time
Overcurrent Protection

High Set (S/C Capability) between 1902 and 2342 A


(HV Side) (1.3 *14,000 * (13.8/132)
132 kV 0r
(1.6 *14,000 * (13.8/132)

200/5

IFL = 87 A

20 MVA
RET 521
RET521
6%
200/
IFL = 837 A 5 400
A

1200/5
13.8 kV
EI Relay
Ir =5
I3Ø = 14,000 A 51/ Is = 0.6 X
IL-G fault = 12,000 A 600/5
50
TMS = 0.8 X
IT = 10 X

SETTING EXAMPLE OF TRANSFORMER NUMERICAL RELAY

132 kV

200/5

IFL = 87 A

20 MVA RET521
RET 521
6%
200/
IFL = 837 A 5 400
A

1200/5
13.8 kV
EI Relay
Ir =5
I3Ø = 14,000 A 51/ Is = 0.6 X
IL-G fault = 12,000 A 600/5
50
TMS = 0.8 X
IT = 10 X

Setting Parameter Parameter


Setting
Three Phase Time
Overcurrent Protection

Low Set (O/L Protection) 117 A


(LV Side) 135% of TXMR FLA

Chapter 10 Page 61 Transformer Protection


SETTING EXAMPLE OF TRANSFORMER NUMERICAL RELAY

132 kV

200/5

IFL = 87 A

20 MVA RET521
RET 521
6%
200/
IFL = 837 5 400
A A

1200/5
13.8 kV

Setting
EI Relay Parameter Parameter
Ir =5
I3Ø = 14,000 A
IL-G fault = 12,000 A
51/
50
Setting
Is = 0.6X
0.6
600/5
Three Phase
TMS = 0.8
IT = 10 X
X Time
Overcurrent Protection

High Set (S/C Capability) Disable


(LV Side) For Coordination
Purposes

SETTING EXAMPLE OF TRANSFORMER NUMERICAL RELAY


132 kV

200/5

IFL = 87 A

20 MVA RET521
RET 521
6%
200/
IFL = 837 A 5 400
A

1200/5
Restricted Earth Fault On
13.8 kV

EI Relay
5 Ir =5
I3Ø = 14,000 A 1/ Is = 0.6 X Idmin 10% (L.R. Ground)
IL-G fault = 12,000 A 5
600/5 TMS = 0.8 X
0 IT = 10 X First Slope = 70%
Second Slope = 100%

Earth Fault Current Protection


(High Set) Disable
Low Set 10%

Chapter 10 Page 62 Transformer Protection


SETTING EXAMPLE OF TRANSFORMER NUMERICAL RELAY
Single/Three Phase Time O/V Protection (TOV)

Low Set (Definite time and Inverse Time) 76 V


= 132,000 * (110/132,000) * (1/1.732) * 1.2
132 kV

High Set (Definite time) 89 V


= 132,000 * (110/132,000) * (1/1.732) * 1.4

200/5

IFL = 87 A

20 MVA
RET 521
RET521
6%
200/5
IFL = 837 A 400 A

1200/5
13.8 kV

EI Relay
Ir =5
I3Ø = 14,000 A 51 Is = 0.6 X
IL-G fault = 12,000 A /5 TMS = 0.8 X
600/5 0 IT = 10 X

SETTING EXAMPLE OF TRANSFORMER NUMERICAL RELAY


Single/Three Phase Time U/V Protection (TUV)

High Set (Definite time) 50 V


= 132,000 * (110/132,000) * (1/1.732) * 0.8
132 kV

200/5

IFL = 87 A

20 MVA
RET 521
RET521
6%
200/5
IFL = 837 A 400 A

1200/5
13.8 kV

EI Relay
Ir =5
I3Ø = 14,000 A 51 Is = 0.6 X
IL-G fault = 12,000 A /5 TMS = 0.8 X
600/5 0 IT = 10 X

Chapter 10 Page 63 Transformer Protection

You might also like