EF TD Transformer differential

protection

Transformer differential protection


INGEPAC™ EF TD is a range of intelligent electronic devices that provide all the protection and control functionalities
required for two and three winding power transformers. It also provides instantaneous and biased differential protection,
with harmonics blocking, as well as low impedance restricted earth fault.

Applications
∙ 2 windings transformer protection and control (EF TD0 model)
∙ 3 windings transformer protection and control (EF TD1 model)
∙ Breaker and a half topology transformer protection (EF TD2 model)

Protection functions Data acquisition


Functions SOE (1000), faults (20)
52 W1 W2 52 · 87 Instantaneous and biased Oscillography: 12 analog and 100
differential protection digital channels
G G · 87REF Restricted earth fault Measurements: I, V, P, U, Q, f, T, etc.
· 2nd, 3rd, 4th and 5th harmonic
restraining and blocking
· 24 Over-excitation (5th harmonic) Local HMI
81m
· 24 Over-excitation (V/f) 4,9” display
59N
· 3x50/51 (67), 50N/51N (67N) Graphical displays
74TC 74TC
74CC 74CC · 50G/51G I/O/L/R pushbuttons
81M · 46TOC (67Q), 46IOC (67Q) 19 LEDs
50 50 · 27, 59, 59N, 59Q, 47 Keyboard
46 · 81M/m, 81 ROCOF
59 46
· 49 Thermal image
sutats
xFE

8F 1F 9 8 7

51 50G 50G 51
· 49T Overtemperature through
6 5 4
9F 2F
3 2 1
01F 3F
R 0

RTD (with 11 RTD and 4 SA


11F 4F

49 49
CSE UNEM
21F 5F

27 31F 6F

50N 51G 51G 50N


module) 41F 7F

· 32 Power units
24v 50BF
Hz
50BF · CLP
51N 51N · 51V Voltage restrained / status
EFx

24 87G 87G controlled overcurrent F1

F2

59Q 5º harm
· 50BF Breaker failure F3

F4

· 68FF
F5

MENU ESC

· 79 Recloser
7 8 9

4 5 6

32
1 2 3

0 R

2nd, 2nd + 4th & 5th HARMONIC

BLOCK
68FF
Logics based on IEC 61131-3
0
67 / OR
67N 87
$.PROT.PTRC1.Op51.ST.stVal IN1 OUT $.GEN.pGGIO1.Ind1.ST.stVal 1

$.PROT.PTRC1.Op50.ST.stVal IN2 VAR1 2

Synchrophasors* Synchronization Communications


Phasor measurement unit according to IEEE C37.118 standard; IEEE 1588 v2 Protocols: IEC 61850, IEC 60870-5-103/104, DNP3, Modbus, PROCOME
only class P filter available. IRIG-B Redundancy: PRP, HSR, D-link failure, switch mode
*Only available for EF TD0 models SNTP Web services: HTTP/HTTPs, FTP/sFTP, SSH
EF TD Transformer differential
protection

INSULATION AND
ELECTROMAGNETIC TESTS MAIN FEATURES
Electromagnetic High precision in direct measurements (class 0.2 in currents and voltages)
compatibility IEC 60255-26 Wide range current inputs allowing the same device to be connected to 1 A and 5 A CT
requirements secondary
Dielectric withstand IEC 60255-27 Application software specifically designed for simple and user-friendly access to the
Insulation resistance equipment
IEC 60255-27
measurement Different hardware options allow to define the most suitable configuration for the application
Voltage impulse IEC 60255-27 Through the front USB you can access the equipment to retrieve reports and equipment
Electrostatic discharge CID, load an external CID, load the firewall configuration or update the equipment firmware
IEC 61000-4-2
immunity Synchronization from communications protocols, SNTP, IEEE 1588 v2 (PTP), demodulated

The technical data in this flyer are subject to change without prior notice. TF14IPT_PGA01_C/092023
Radiated radiofrequency IRIG-B input or PPS input, pacFactory or display
electromagnetic field IEC 61000-4-3 Web server for monitoring and setting without needing additional software
immunity
Cybersecurity features: sFTP, HTTPs, firewall, audit log, password accessing, RBAC, LDAP,
Electrical fast transient / session management...
IEC 61000-4-4
burst immunity
Acquisition of sampled values as per IEC 61869-9 (NCIT) and IEC 61850-9-2LE (SAMU)
Surge immunity IEC 61000-4-5 standards (optional)
Immunity to conducted
disturbances, induced IEC 61000-4-6 HARDWARE OPTIONS
by radiofrequency fields
Power frequency
IEC 61000-4-8 Mounting options Boards options
magnetic field immunity
∙ 19” 4U rack (up to 6 I/O slots) ∙ CPU: 6 DI + 4 DO
Impulse magnetic field
IEC 61000-4-9 ∙ 11 DI + 9 DO
immunity
∙ 32 DI
Damped oscillatory ∙ 16 DI + 8 DO
IEC 61000-4-10
magnetic field immunity
∙ 16 DI + 16 DO
Immunity to conducted, ∙ 16 DI + 8 AI (mA)
common mode IEC 61000-4-16 ∙ 8 DI + 8 DO
disturbances ∙ 11 RTD + 4 AO
Ripple on DC input ∙ ½ x 19” 5U rack (up to 2 I/O slots) 100 Ω platinum, 100 Ω nickel, 120
IEC 61000-4-17
power port Ω nickel, 10 Ω copper
Damped oscillatory
IEC 61000-4-18
wave immunity Communication ports
Voltage dips, short Front:
interruptions and voltage IEC 61000-4-29 ∙ RJ45
variations immunity ∙ USB
Withstand to radiated Rear:
electromagnetic ∙ Up to 2 Ethernet (FO or RJ45)
IEEE 37.90.2
interference from ∙ Up to 6 serial (FO, RS232, RS485)
transceivers Optional
∙ High break contact outputs
∙ High speed outputs Power supply
CLIMATIC TESTS
∙ 24, 48, 125 and 220 Vdc
Cold IEC 60068-2-1 ∙ Power: 40 W
Dry heat IEC 60068-2-2 Optional IP54 front protection ∙ Optionally redundant power supply
Change of temperature IEC 60068-2-14
Damp heat cyclic IEC 60068-2-30
SOFTWARE
Damp heat steady IEC 60068-2-78
All the devices in the INGEPAC™ product range can be accessed using powerful software
External protection level IEC 60529
tools developed by Ingeteam which run on Windows
Application specifically designed for simple and user-friendly access to the equipment
MECHANICAL TESTS
Vibrations IEC 60255-21-1 eFS
Shock and bump IEC 60255-21-2
Seismic IEC 60255-21-3

CYBERSECURITY