G5 G5 G5 G5 G5

MI FLS: Provide handrails on


both sides of the ramp.

MI FLS:

All Floor Plans:


It appears that the hotel and non-hotel areas share the exit stairs.
If the stair doors are locked on the non-hotel floors, re-entry to MI FLS: Reverse the door swing.
exit stairs must be possible on every 4th floor and it should not be
locked in the direction of egress travel. MI FLS: Dead-end condition exceeds
15m limit. Revise the floor plan to
eliminate the excessive dead-end.
0.78 m
MI FLS: Common path of travel exceeds 30m
limit. It is recommended to punch the wall to

GREASE TRAP KAP. 2 M3

DIM (3750X3000x2700)mm
SEWAGE PIT KAP. 25 M3
eliminate the excessive common path.

0.76 m
0.76 m
46
GREASE TRAP KAP. 6 M3
.41
m 41.18 m
0.76 m

0.77 m
28.94 m
0.75 m

LA NEUTRALIZIR KAP. 4 M3
22
0.77 m

57.06 m
LA
05

MI FLS: Relocate the LPG storage away LA

at least 10m without sprinklers or 3m with


06

sprinklers from the building structure.


LA LA
29 21

MI FLS: Provide two remote exit doors 0.76 m


swinging in the direction of egress travel and
the distance between two remote exit doors
shall be not less than 1/3 of the diagonal of
the space. MI FLS: Door openings in means of egress
Egress path shall not pass through kitchen. shall be not less than 0.81m in clear width.
Where a pair of door leaves are provided, one
door leaf shall be not less than 0.81m in clear
MI FLS: Provide a dedicated floor marking width. Revise the floor plan.
indicating exit route with at least 1.12m width
to lead occupants to the street.

20.26 m
0.76 m

31.48 m

MI FLS: Dead-end condition exceeds 15m


0.76 m

limit. Revise the floor plan to eliminate the


excessive dead-end condition.
MI FLS: Clarify the usage of this area. MI FLS: Common path of travel exceeds 6.1m MI FLS: Reverse the door swing.
Additional comments may be provided limit. Provide additional exit door at ballroom
after the confirmation. lobby to eliminate common path issue.
MI FLS: Door openings in means of egress
shall be not less than 0.81m in clear width.

0.61 m
Where a pair of door leaves are provided, one
door leaf shall be not less than 0.81m in clear
width. Revise the floor plan.
MI FLS: Replace the sliding door 0.79 m
with side hinged swing door. TOILET MI FLS: Dead-end condition exceeds 6.1m
limit. Revise the floor plan to eliminate the
excessive dead-end condition.
MI FLS: Reverse the door swing. 0.62 m

7.95 m
MI FLS: Common path of travel exceeds
23m limit. Revise the floor plan to
eliminate the excessive common path.

66.98 m
3.82 m
MI FLS: Ensure that the ramp shall MI FLS: Dead-end condition exceeds 6.1m
not be sloped more than 1:12. limit. Revise the floor plan to eliminate the
excessive dead-end condition.
MI FLS: Provide handrails on 7
m
.3
the both sides of the ramp. 45

3.82 m
2.31 m 2.31 m

MI FLS: Indicate partition arrangement to confirm


how the ballroom will be divided into 5 smaller
ballrooms.

Ensure that each ballroom bay requires minimum


2 exits if 50 or more persons, 3 exits if 500 or
more persons, 4 exits if 1000 or more persons.
MI FLS: Provide two remote exit doors and the
distance between two remote exit doors shall be
not less than 1/3 of the diagonal of the space.
MI FLS: Provide handrails on
the both sides of the steps.
30991,57
MI FLS: Door openings in means of egress shall be
not less than 0.81m in clear width. Where a pair of
door leaves are provided, one door leaf shall be not
less than 0.81m in clear width. Revise the floor plan.
MI FLS: Common path of travel exceeds
6.1m limit. Revise the floor plan to
eliminate the excessive common path.

0.68 m
0.69 m
MI FLS: Dead-end condition exceeds 15m
limit. Revise the floor plan to eliminate the
59.64 m excessive dead-end condition.

9.76 m
13.40 m
MI FLS: Dead-end corridor exceeds 6.1m limit.
Revise the floor plan to eliminate the excessive
m dead-end corridor.

m
1

3
.6

.7
11

10
MI FLS: Provide two remote exit doors and
the distance between two remote exit doors
shall be not less than 1/3 of the diagonal of
the space.

MI FLS: Provide two remote exit doors and the


distance between two remote exit doors shall be
not less than 1/3 of the diagonal of the space.
MI FLS: Clarify the usage of the marked
area. Additional comment may be provided
after the confirmation.

MI FLS: The occupant load for this floor is 1,248 persons;


however, the egress capacity for the floor is approximately
882 persons. Additional egress capacity for 254 persons
(or additional width 1.94 m in total for egress) is needed.

0.90 m
1.54 m

Stair 3

MI FLS: Dead-end condition exceeds 15m


limit. Revise the floor plan to eliminate the
excessive dead-end condition.
29 1.26 m 60.01 m

0.84 m
16
Total: 167 12
0.97 m
1.26 m

20 36 10
22 22

MI FLS: Egress route shall not pass MI FLS: Reverse door swing, and utilize
through any intervening rooms other this double door as an exit for meeting
than a corridor or public circulation area. room occupants. Doors should remain MI FLS: Egress route shall not pass through any
Provide a vestibule in the dining area. unlocked and unlatched at all time. intervening rooms other than a corridor or public
circulation area. Provide a dedicated corridor at
business office to lead occupants to the exit.

MI FLS: Arrange doors to swing


in both directions.
MI FLS: Door openings in means of egress shall be
not less than 0.81m in clear width. Where a pair of
door leaves are provided, one door leaf shall be not
less than 0.81m in clear width. Revise the floor plan.

0.61 m
28.70 m

0.61 m
0.61 m
0.61 m
0.61 m

0.61 m
MI FLS: Common path of travel exceeds
6.1m limit. Revise the floor plan to 20.69 m
1.83 m
eliminate the excessive common path.

2.55 m
m
.36
m 43
.55
2m 34
31.2
Stair 4

15
.2
3
m MI FLS: Dead-end condition exceeds 6.1m MI FLS: Common path of travel exceeds
limit. Revise the floor plan to eliminate the 23m limit. Revise the floor plan to eliminate
excessive dead-end condition. the excessive common path of travel.
MI FLS: Provide two remote exits in the meeting
room bay and the distance between two exits shall
be not less than 1/3 of the diagonal of the area MI FLS: Clarify the usage of the room.
served. Recommend to change this meeting room Ensure that non-occupiable rooms
to boardroom to resolve this issues. shall not open directly to the exit stair.

MI FLS: Reverse the door swing.


MI FLS: Door openings in means of egress shall be
not less than 0.81m in clear width. Where a pair of
door leaves are provided, one door leaf shall be not
less than 0.81m in clear width. Revise the floor plan.

MI FLS: Provide handrails on


the both sides of the stair.
OS RD
BASEMENT/GF
FLAT ROOF
EA FA KITCHEN FA FA FA EA EA SHAFT KITCHEN EA

PANTRY &
SINGLE SINGLE
STAFF ROOM
TREATMENT TREATMENT ROOF
MEP ROOM ROOM DECK
BALANCING TANK KAP. 7 M3
EA
ELEC. SHAFT
SE01/ PE01 PE03
1200x500.KFD
FE01

AHU UNITS SERVICE ELEV.


LOBBY LOBBY SINGLE SINGLE
TREATMENT TREATMENT
ROOM ROOM
SWIMMING POOL SE02 PE02 PE04
PUMP ROOM
STAIR POWDER
1100x400.RD

1100x400.RD
1100x400.SD

1100x400.SD

FA 02 RM.
SE PS SEALED
HR SPACE
HR SPA WATER
FA
FEATURE
CORRIDOR E.J.

UP
PS

0.70 m STAFF
TOILET
PREP.
ROOM

UP DN
RELAXATION
VIP ROOM
RELAXATION
VOID ABOVE ALL DAY DINING SINGLE
ROOM
TREATMENT
MULTI-PURPOSE ROOM ROOM

STAIR 01 LINK TO EXISTING OFFICES SINGLE SINGLE


TREATMENT TREATMENT
ROOM ROOM

RL FA SHAFT
FOR
LAUNDRY

ROOF DECK

MI FLS: The MEP area shall not open E.J.

directly to the exit stair. Provide a


vestibule to the exit staircase.
OFFICE

Non-Hotel
MI FLS: Dead-end corridor exceeds 15m limit. MI FLS: Reverse the door swing
Revise the floor plan to eliminate the excessive in the direction of egress travel.
dead-end corridor.

28.09 m

MI FLS: Provide handrails on


the both sides of the stair.

69.83 m
MI FLS: Swimming pool and spa area require two MI FLS: Please clarify whether the roof garden will be
remote exits, and egress route shall not pass used for assembly space. Common path at this area
through any intervening rooms such as swimming should not be more than 23m, and number of occupants
pool and spa area other than a corridor or public to occupy this space should not be more than 50 people.
circulation area. Provide exit corridor to connect
both staircases to resolve the issue.

MI FLS: Ensure that the ramp shall


not be sloped more than 1:12.

MI FLS: Provide handrails on


the both sides of the ramp.
MI FLS: Door openings in means of egress shall be not
less than 0.81m in clear width. Where a pair of door
leaves are provided, one door leaf shall be not less than
0.81m in clear width. Revise the floor plan.

0.70 m
0.66 m
0.74 m

MI FLS: Reverse the door swing MI FLS: Provide two remote exit doors swinging in
in the direction of egress travel. the direction of egress travel and the distance
between two remote exit doors shall be not less
than 1/3 of the diagonal of the space.
Egress path shall not pass through pantry.
A B C D E F G H

46 Kim Yam Road


The Herencia, #01/10,
Singapore 239351
T + 65 633 2511
F + 65 6337 2460

WWW.HBA.COM

SWISS BEL HOTEL, PEKANBARU


2

RIAU, INDONESIA
REVISIONS
Non-Hotel

FIXTURE & FURNISHING PLAN


5

PENT HOUSE
20TH FLOOR
This drawing is for information only to be
used by the contractors as a general
arrangement of interior conditions. It has
been made from available information,
however measurements are to be verified
on project site.
This drawing must be verified and approved
prior to final detailing and fabrication. This
drawing is the property of HIRSCH BEDNER
AND ASSOCIATES and is not to be
reproduced or copied in whole or in part. It
is only to be used for the project and site
specifically identified herein and is not to
be used on any other project. It is to be
returned upon request.

6 APPROVED SM

DRAWN BY RG

DATE MARCH 16

SCALE AS SHOWN

SHEET No.

FF 20.00
1 FIXTURE & FURNISHING PLAN PROJECT No.
-
Scale 1 : 100 (A1) / 1 : 200 (A3) 70083
A B C D E F G H
A B C D E F G H

46 Kim Yam Road


The Herencia, #01/10,
Singapore 239351
T + 65 6337 2511
F + 65 6337 2460

WWW.HBA.COM

SWISS BEL HOTEL, PEKANBARU


2

HD

HC.8
3

RIAU, INDONESIA
HC

REVISIONS
Non-Hotel

4
HB

FIXTURE & FURNISHING PLAN


HA

5
H1 H1.6 H2 H3 H4 H5 H6 H7 H8

PENT HOUSE
21ST FLOOR
This drawing is for information only to be
used by the contractors as a general
arrangement of interior conditions. It has
been made from available information,
however measurements are to be verified
on project site.
This drawing must be verified and approved
prior to final detailing and fabrication. This
drawing is the property of HIRSCH BEDNER
AND ASSOCIATES and is not to be
reproduced or copied in whole or in part. It
is only to be used for the project and site
specifically identified herein and is not to
be used on any other project. It is to be
returned upon request.

6 APPROVED SM

DRAWN BY RG

DATE MARCH 16

SCALE AS SHOWN

SHEET No.

FF 20.00
1 FIXTURE & FURNISHING PLAN PROJECT No.
-
Scale 1 : 100 (A1) / 1 : 200 (A3) 70083
A B C D E F G H
MI FLS: Linen chutes must extend 910mm above
the roof (same size as chute) and vent to the
exterior, with automatic closing intake doors and
fire damper or an automatic closing fire door at
the final discharge.

63.95 m

MI FLS: Common path of travel


exceeds 30m limit. Extend the exit stair
to the roof floor to resolve this issue.