You are on page 1of 5

V.

Thermal Efficiency

Winter: Summer:
Coldness The rooms are protected
remains outdoor against the heat from outside

Heat A comfortably
remains cool climate
indoor against the heat
from the outside

The highly effective thermal insulation and heat storage of AERCON


provides a comfortable room climate and excellent thermal energy efficiency.

A. Basic Principles Page V-2


B. Equivalent R-Value Page V-3
C. Florida Energy Code Compliance with AERCON Page V-5
V - Thermal Efficiency

A. Basic Principles

Thermal protection in buildings tection in the summer is mainly minimize “uncontrolled” venti-
directly influences the use of determined by the capability of lation air. By providing an air-
energy for heating and cooling, the exterior building elements tight building envelope,
as well as the ability to control to store and dissipate heat. This AERCON minimizes the
the room climate. Less thermal property is determined by the “uncontrolled” air changes and
protection results in more mass and thermal conductivity allows the ventilation air to be
energy usage for heating and of the building material. As “controlled”. Elements such as
cooling and a much less com- shown below, the thermal mass dust and pollen can be filtered
fortable room environment. and thermal conductivity estab- out of the ventilation air before
lish the thermal inertia, which they invade the building. By
The thermal protection require-
causes a damping and time lag use of a dehumidifier, the
ments for the external con-
of the temperature peaks. moisture content of the ventila-
struction elements of buildings
tion air can also be controlled
are generally categorized into With AERCON, a construction
which optimizes the comfort-
one of two groups, either sum- material is available that opti-
able indoor environment.
mer or winter. mally combines the material
Overall, the volume and quality
properties necessary to provide
The thermal protection for of ventilation air can be easily
excellent thermal energy effi-
winter conditions is intended to and accurately controlled in an
ciency for the building.
minimize heat loss from the AERCON building - thus pro-
Additional thermal protection is
building, thus allowing the viding a comfortable, economi-
not required.
building to be economically cal and healthy environment.
heated. Furthermore, the interi- An AERCON building system
These excellent thermal protec-
or surfaces of the building’s also provides a nearly airtight
tion properties of AERCON
external thermal envelope envelope, which is critical in
exterior walls were confirmed
should not drop below a certain controlling the comfortable and
in a study by the Florida Solar
minimum temperature in order healthy indoor environment. A
Energy Center.
to avoid condensation. The major emphasis in heating and
thermal protection properties cooling system design is to
must, therefore, be determined Maximum Exterior Time Lag
by considering both criteria. Wall Temperature (hours)
Damping
at Mid-Afternoon
(°F)
In contrast, the thermal protec-
Temperature

tion for summer conditions is


intended to minimize heat gain Average
Temperature
from the warm outside temper-
atures and sun rays, thus allow- Interior AAC Surface
Temperature
ing the building environment to
Minimum Exterior
be economically controlled in a Wall Temperature Exterior AAC Surface
at Early-Morning Temperature
comfortable state. Thermal pro-
Time

06/03 / V-2
V - Thermal Efficiency

B. Equivalent R-Value

In order to compare an AERCON The study compared an 8-inch glass batt insulation or an 8-
exterior wall with conventional thick AERCON wall to both a inch CMU block wall insulated
wall construction methods conventional wood stud frame with R-8.6 rigid insulation. That
(wood stud frame and concrete wall and CMU block wall. The means that nearly 6 inches of
masonry), the Florida Solar typical wall sections studied batt insulation would have to
Energy Center determined are shown in Figure A. The cal- be added to a wood stud frame
equivalent R-values for an culated static R- and U-Values, wall and over 2 inches of rigid
AERCON wall. Weather data for neglecting thermal mass polystyrene insulation to a
Orlando, Florida, as developed in effects, are shown in Table 1. CMU block wall to equal the
the Typical Meteorological Year performance of the AERCON
(TMY 1981) database, served The results of the study, which wall, as illustrated in Figure B!
as the basis for the outside con- include the thermal mass
effects, are shown in Table 2. It should be pointed out that
ditions. In order to uncouple the
They represent the insulation one of the simplifying assump-
effect of wall orientation, it was
value required to be added to tions made for this study was
assumed that only diffuse radia-
that only diffuse radiation
tion would be present on the out- either a wood stud frame wall
would be present on the out-
side wall surfaces. or a CMU block wall to achieve
side wall surfaces, i.e. no direct
an equivalent thermal system.
The study included calculations sunlight would strike the walls.
For example, during an average
for six conditions, winter and If the study would be expanded
summer day, the 8-inch
summer average days, winter to include the effects of the
AERCON wall performs like
direct radiation, the results
and summer peak days, and either a wood stud frame wall
would show that an AERCON
cooling and heating seasons. insulated with R-20.4 fiber- wall would perform even better!

3/8" THICK STUCCO 5/8" STUCCO


5/8" STUCCO
8" AERCON 1/2" PLYWOOD 8" CMU
3/16" PLASTER FIBERGLASS INSULATION RIGID INSULATION
1/2" GYPSUM BOARD 1/2" GYPSUM BOARD

WOOD FRAMING WOOD FURRING


(16" O.C.)

AERCON CONSTRUCTION WOOD CONSTRUCTION MASONRY CONSTRUCTION

Figure A Typical Wall Constructions

06/03 / V-3
V - Thermal Efficiency

Table 1
Nominal Overall R- (and U-) Values of Wall Systems including Air Film Coefficients
Wall System R-Value, (R) U-Value, (U)
(h ft2 °F/BTU) (BTU/h ft2 °F)
8 inch AERCON Wall (AC2) 11.5 0.087

R-11 Frame Wall (25% framing) 9.0 0.111

R-19 Frame Wall (25% framing) 13.2 0.076

CMU Block Wall w/R-3 Added Insulation 4.9 0.204

CMU Block Wall w/R-5 Added Insulation 6.6 0.151

CMU Block Wall w/R-8 Added Insulation 11.2 0.090

CMU Block Wall w/R-10 Added Insulation 13.1 0.076

Table 2
Insulation Value Required to Match an 8" AERCON Wall

Simulation Basis Wood Stud Frame Wall 8" CMU Block Wall
Equivalence Based on the Fluxes Equivalence Based on the Fluxes
Summed in Load Direction Only Summed in Load Direction Only

Peak Summer Day 17.9 8.6

Average Summer Day 20.4 8.6

Peak Winter Day 16.7 8.5

Average Winter Day 16.5 8.5

Cooling Season 19.6 8.5

Heating Season 16.9 8.5

8 7/16" 8 7/8" 11"

2X2

3/8" THICK STUCCO 5/8" STUCCO 5/8" STUCCO

8" AERCON 1/2" PLYWOOD 8" CMU


2-1/4" THICK
3/16" PLASTER 6" THICK FIBERGLASS RIGID
INSULATION INSULATION
1/2" GYPSUM BOARD 1/2" GYPSUM BOARD
1X2
2x8 WOOD FRAMING
(16" O.C.)

AERCON CONSTRUCTION WOOD CONSTRUCTION MASONRY CONSTRUCTION

Figure B Equivalent Thermal Resistance Constructions

06/03 / V-4
V - Thermal Efficiency

C. Florida Energy Code Compliance


with AERCON
In a separate study performed lated the EPI for the same shown in Figure A, assuming
by the Florida Solar Energy building, substituting R-11 the minimum code allowance
Center, the Energy Performance wood frame exterior walls and on residential construction for
Index (EPI) according to then substituting standard con- ceiling insulation, air condition-
Method A of the Florida Energy crete block exterior walls with ing efficiency (SEER), and sin-
Code was calculated for an R-5 additional insulation. All gle pane windows. In each case
actual building in Central other components of the build- the building was rotated in
Florida. To meet the thermal ing were held constant for the increments of 45 degrees to
efficiency requirements of that study. The results of the calcu- examine all possible building
code, the EPI must not exceed lation are shown in Table 3. orientations.
a value of 100. The lower the
EPI for a building, the more As shown by this EPI calcula- The resulting EPI values indi-
energy efficient and, therefore, tion, the AERCON walls clearly cate that a house built with
the lower the energy costs for provide the most energy effi- AERCON walls complies with
heating and cooling. cient walls! the code regardless of the
building orientation. The other
This study calculated the EPI As an additional comparison, wall systems would fail to com-
for a building which utilized 8- the Florida Solar Energy Center ply with the Florida Energy
inch thick AERCON block for calculated the EPI for the same Code.
the exterior walls. It also calcu- three wall constructions,

Table 3
Energy Performance Index (EPI)
AERCON Wood Frame Wall Standard Concrete Block

84.40 91.85 89.71

06/03 / V-5

You might also like