Professional Documents
Culture Documents
Thermal Efficiency
Winter: Summer:
Coldness The rooms are protected
remains outdoor against the heat from outside
Heat A comfortably
remains cool climate
indoor against the heat
from the outside
A. Basic Principles
Thermal protection in buildings tection in the summer is mainly minimize “uncontrolled” venti-
directly influences the use of determined by the capability of lation air. By providing an air-
energy for heating and cooling, the exterior building elements tight building envelope,
as well as the ability to control to store and dissipate heat. This AERCON minimizes the
the room climate. Less thermal property is determined by the “uncontrolled” air changes and
protection results in more mass and thermal conductivity allows the ventilation air to be
energy usage for heating and of the building material. As “controlled”. Elements such as
cooling and a much less com- shown below, the thermal mass dust and pollen can be filtered
fortable room environment. and thermal conductivity estab- out of the ventilation air before
lish the thermal inertia, which they invade the building. By
The thermal protection require-
causes a damping and time lag use of a dehumidifier, the
ments for the external con-
of the temperature peaks. moisture content of the ventila-
struction elements of buildings
tion air can also be controlled
are generally categorized into With AERCON, a construction
which optimizes the comfort-
one of two groups, either sum- material is available that opti-
able indoor environment.
mer or winter. mally combines the material
Overall, the volume and quality
properties necessary to provide
The thermal protection for of ventilation air can be easily
excellent thermal energy effi-
winter conditions is intended to and accurately controlled in an
ciency for the building.
minimize heat loss from the AERCON building - thus pro-
Additional thermal protection is
building, thus allowing the viding a comfortable, economi-
not required.
building to be economically cal and healthy environment.
heated. Furthermore, the interi- An AERCON building system
These excellent thermal protec-
or surfaces of the building’s also provides a nearly airtight
tion properties of AERCON
external thermal envelope envelope, which is critical in
exterior walls were confirmed
should not drop below a certain controlling the comfortable and
in a study by the Florida Solar
minimum temperature in order healthy indoor environment. A
Energy Center.
to avoid condensation. The major emphasis in heating and
thermal protection properties cooling system design is to
must, therefore, be determined Maximum Exterior Time Lag
by considering both criteria. Wall Temperature (hours)
Damping
at Mid-Afternoon
(°F)
In contrast, the thermal protec-
Temperature
06/03 / V-2
V - Thermal Efficiency
B. Equivalent R-Value
In order to compare an AERCON The study compared an 8-inch glass batt insulation or an 8-
exterior wall with conventional thick AERCON wall to both a inch CMU block wall insulated
wall construction methods conventional wood stud frame with R-8.6 rigid insulation. That
(wood stud frame and concrete wall and CMU block wall. The means that nearly 6 inches of
masonry), the Florida Solar typical wall sections studied batt insulation would have to
Energy Center determined are shown in Figure A. The cal- be added to a wood stud frame
equivalent R-values for an culated static R- and U-Values, wall and over 2 inches of rigid
AERCON wall. Weather data for neglecting thermal mass polystyrene insulation to a
Orlando, Florida, as developed in effects, are shown in Table 1. CMU block wall to equal the
the Typical Meteorological Year performance of the AERCON
(TMY 1981) database, served The results of the study, which wall, as illustrated in Figure B!
as the basis for the outside con- include the thermal mass
effects, are shown in Table 2. It should be pointed out that
ditions. In order to uncouple the
They represent the insulation one of the simplifying assump-
effect of wall orientation, it was
value required to be added to tions made for this study was
assumed that only diffuse radia-
that only diffuse radiation
tion would be present on the out- either a wood stud frame wall
would be present on the out-
side wall surfaces. or a CMU block wall to achieve
side wall surfaces, i.e. no direct
an equivalent thermal system.
The study included calculations sunlight would strike the walls.
For example, during an average
for six conditions, winter and If the study would be expanded
summer day, the 8-inch
summer average days, winter to include the effects of the
AERCON wall performs like
direct radiation, the results
and summer peak days, and either a wood stud frame wall
would show that an AERCON
cooling and heating seasons. insulated with R-20.4 fiber- wall would perform even better!
06/03 / V-3
V - Thermal Efficiency
Table 1
Nominal Overall R- (and U-) Values of Wall Systems including Air Film Coefficients
Wall System R-Value, (R) U-Value, (U)
(h ft2 °F/BTU) (BTU/h ft2 °F)
8 inch AERCON Wall (AC2) 11.5 0.087
Table 2
Insulation Value Required to Match an 8" AERCON Wall
Simulation Basis Wood Stud Frame Wall 8" CMU Block Wall
Equivalence Based on the Fluxes Equivalence Based on the Fluxes
Summed in Load Direction Only Summed in Load Direction Only
2X2
06/03 / V-4
V - Thermal Efficiency
Table 3
Energy Performance Index (EPI)
AERCON Wood Frame Wall Standard Concrete Block
06/03 / V-5