Professional Documents
Culture Documents
net/publication/305452472
CITATIONS READS
5 2,344
3 authors:
K. Ghali
American University of Beirut
221 PUBLICATIONS 3,473 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
Sustainable cooling system for Kuwait hot climate combining diurnal radiative cooling and indirect evaporative cooling system View project
Integration of intermittent Personalized Ventilation in office spaces: Thermal comfort, Indoor air quality and Energy savings View project
All content following this page was uploaded by Nesreen Ghaddar on 15 March 2019.
Abstract: Underground spaces normally are at cooler air temperature than ambient air temperature because of earth-sheltered walls. This
cooler air can be circulated to occupied spaces using a solar chimney effect to exhaust air from the basement to where it is needed. This work
aims to study the viability of using natural ventilation induced by a Trombe wall to draw fresh air from underground basement floors for space
cooling in the dry desert climate. Outdoor air is delivered to the basement through an earth tube. A numerical model integrating thermal
models of the basement space and the occupied zone, and the Trombe wall is used to predict the air temperature variation with time in the
occupied space air temperature and to predict thermal comfort. The feasibility of implementing the proposed system is assessed in a case
study of a residence in the inland dry desert climate of Lebanon during the summer. It was found that the proposed system achieved thermally
comfortable conditions at 80% acceptability for a considerable number of hours without the need for mechanical ventilation (83.3% in
June and 58.3% in August). The electric energy consumption of the system over summer (June through September) was estimated at
7.71 kW · h=m2 of floor area. DOI: 10.1061/(ASCE)EY.1943-7897.0000393. © 2016 American Society of Civil Engineers.
Author keywords: Natural ventilation; Trombe wall; Solar energy; Energy efficiency; Basement air modeling.
Fig. 1. Schematic of the combined natural ventilation system with Trombe wall and basement
where
U b ¼ 1=ð1=hi þ d=kw þ wins =kins Þ ð4bÞ
Room Model
Downloaded from ascelibrary.org by AMERICAN UNIV OF BEIRUT on 10/06/16. Copyright ASCE. For personal use only; all rights reserved.
where qintðbÞ = internal heat load in the basement; and qw ðtÞ = heat assumed that the temperature of the soil changed in accordance with
transfer by convection from the air to the wall as follows: the change of season. This change meant that a certain delay and
damping in soil temperature took place as depth of soil increased.
The amplitude of the temperature change was 0.6 and 0.2°C at the
X
4
qw ðtÞ ¼ hcb Ai ½T ba ðtÞ − T i ðx; tÞjx¼0 ð7bÞ depths of 8 m and 10 m, respectively (Kajtar et al. 2015). The location
i¼1 of the underground space determined the reference soil temperature to
be used. Further, the low-thermal diffusivity of the soil (0.316 ×
10−6 m2 =s in the current case study, which is much lower than that
where Ai and T i = surface area and the temperature of the room of the air, 22.5 × 10−6 m2 =s) justified the consideration of the soil
wall i. The heat because of ventilation is given by temperature as quasi-stationary. The temperature fluctuations at the
surface of the ground are diffused very slowly in depth because
of the soil’s high-thermal capacity. Accordingly, daily ground temper-
qs ðtÞ ¼ ṁ cf ½T ba ðtÞ − T a ðtÞ ð7cÞ atures were considered rather than hourly ones (Florides and
Kalogirou 2004). The soil was assumed a homogeneous material
in terms of heat transfer properties with its resultant thermal character-
The outdoor air was assumed to be brought to the basement istics (Kajtar et al. 2015). The concrete walls were considered to have
through a vertical earth tube at the floor level to ensure good mixing similar thermal characteristics as the soil (Kajtar et al. 2015).
with basement air. The outdoor air temperature was moderated be-
cause of the heat exchanges with the basement cool surfaces and to
mix with the mass of air present. The extent of cooling of basement Thermal Comfort Model
air depended on the surrounding ground vertical temperature Thermal comfort models have been reported for mechanically
distribution. ventilated/cooled indoor environments [ASHRAE standard 55
Labs and Cook (1989) modeled and reported the ground temper- (ASHRAE 1992); Fanger 1970; Kruger 2008; Zhang et al. 2010].
ature as a function of the time of year and the depth below the Because proposed systems in this work relied on natural ventila-
surface. Their correlation was adopted by Florides and Kalogirou tion, the new ASHRAE standard 55 (ASHRAE 2001) adaptive
(2004) and was adopted in the current work. The soil temperature comfort model (ACM) was used. The ACM, according to de Dear
correlation is given is given by and Brager (2002) and Taleghani et al. (2014), predicts occupants’
thermal comfort in naturally ventilated rooms using a single input
rffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi! variable, which is the outdoor mean temperature, T a;out .
π The optimal comfort temperature, T comf , is given by
T soil ðz; tÞ ¼ T mean − T amp × exp −z
365 × α
" T comf ¼ 0.31 × T a;out þ 17.8 ð10Þ
rffiffiffiffiffiffiffiffiffiffiffiffi!#
2π z 365
× cos tyear − tshift − ð8Þ where T a;out and T comf are expressed in °C. Eq. (10) applies to
365 2 π×α outdoor dry-bulb temperature ranges between 5 and 32°C, and for
sedentary activity levels less than 1.3 MET (Metabolic Equivalent
of Task; 1 MET = 104 W) (Taleghani et al. 2014). Residential ap-
where T soil = soil temperature; z = depth; tyear = time of the year (in plications consider an 80% acceptability limit as adequate for ther-
days); tshift = day of the year of the minimum surface temperature mal comfort level. For higher standards of thermal comfort level, a
(For Lebanon Inland Plateau, tshift is 35 days corresponding to the 90% acceptability limit may be used. The range of temperatures
date of Feb. 4); T mean = mean annual ground surface temperature, around T comf within the 80% thermal acceptability is determined
which is equal to the average air temperature (°C); T amp = temper- on the basis of outdoor temperature.
ature amplitude at the ground surface amplitude of surface temper-
ature (the maximum surface temperature will be (T mean þ T amp )
and the minimum value will be T mean − T amp ); and α = thermal Numerical Simulation Methodology
diffusivity of the soil (Florides and Kalogirou 2004). The soil tem-
perature below the basement’s floor construction was calculated at A numerical finite difference method was used in this work. An
equal soil depth to the basement depth. Moreover, temperature as implicit first-order time integration scheme was used for room air,
the external temperature of the basement vertical wall in contact external walls, Trombe wall, and basement energy balance equa-
with the soil. This average temperature was obtained by integrating tions, and a second-order spatial discretization was used for the
Eq. (8) with respect to z and divided by the submerged wall depth. wall nodes. Each layer of the wall was divided into control vol-
Al-Temeemi and Harris (2003) reported the expression for the aver- umes. A total of 70 nodes was used for the wall. Input data for the
age vertical soil temperature as follows: geometry, thermal properties, and boundary and initial conditions
were compiled for each model. The system model predicted the Case Study
amount of induced airflow and associated thermal comfort during
natural ventilation hours and during the periods when mechanical The proposed natural ventilation system implementation was con-
ventilation was used. sidered for a small isolated, single living room over a basement
Simulations were performed using a developed MATLAB code (Fig. 1) for the climate of an inland district in Lebanon, character-
to find the room air temperature in response to external and internal ized by a hot arid climate. Table 1 summarizes the outdoor temper-
loads as indicated in the flow chart (Fig. 3). Starting from the ature and solar radiation data for representative summer days at the
Trombe wall model that predicts the absorber-wall outer surface 15th of each month, June through September (Fawaz et al. 2014).
temperature facing glass and using a time step of 360 s, the inner The room base area was 6 × 5 m and its height was taken as 2.8 m.
surface temperatures of the inner walls and the absorber wall were It was exposed to the outside from two sides. The external plastered
computed. Simulations were performed for a representative day on walls used typical construction of Lebanese building material
the 15th of each month from June to September. The representative (15-cm hollow blocks), whereas the insulated roof was made of
day simulation was continued over a number of cycle days until a 20-cm reinforced concrete (Republic of Lebanon Ministry of Pub-
steady periodic solution state was reached for the room air temper- lic Works and Transport 2005b). The overall heat transfer coeffi-
ature. The criterion for convergence was set when the maximum cients for the external wall and roof were 2.36 and 1.67 W=m2 · K,
percentage error in air temperature at time t and t þ 24 h was less respectively. The basement area was similar to the living room with
than 10−4 %. The flow chart shown in Fig. 3 summarizes the path a submerged depth of 2.5 m in soil. The soil thermal diffusivity,
followed to calculate the needed output from the developed model. thermal conductivity, and heat capacity were 0.316 × 10−6 m2 =s,
0.50 W=m · K, 1.59 × 103 kJ=m3 · K, respectively. The basement load during the sunshine hours. The electrical loads were 10 W=m2
vertical walls had similar construction to the roof, but was not in- for lighting fixtures and 800 W for appliances.
sulated, whereas its floor was made of concrete tiles. The Trombe wall was incorporated at the south wall of the living
The occupancy schedule was taken for a six-person family that room, which had a 5-m width and 2.8-m height. Its absorber
at peak time would occupy the living room (Republic of Lebanon masonry wall was covered by a double-glazed wall (emissivity
Ministry of Public Works and Transport 2005a). Fig. 4 shows the of 0.75) and had thickness 0.4 m, thermal conductivity of
living room summertime schedule of occupancy and the electrical 1.8 W=m · K, and emissivity of 0.2. The back of the absorber wall
was insulated by a 5-cm layer of insulation with a thermal conduc-
tivity of 0.032 W=m · K. The air channel width was 0.3 m. The
Trombe wall was operated during sunshine hours to draw the base-
ment’s cool air into the living room, whereas the mechanical ven-
tilation fan was operated during low solar radiation and night hours
to meet minimum ventilation requirements.
The performance of the combined system was evaluated with
respect to the maximum number of hours in which comfort was
achieved with minimum dependence on forced ventilation.
Fig. 5. (a) Predicted temperatures; (b) room supply air mass flow rate
in the occupied room for the representative day of the month of June
Fig. 7. (a) Predicted temperatures; (b) room supply air mass flow rate
in the occupied room for the representative day of the month of August
Fig. 6. (a) Predicted temperatures; (b) room supply air mass flow rate
in the occupied room for the representative day of the month of July
Fig. 8. (a) Predicted temperatures; (b) room supply air mass flow rate
in the occupied room for the representative day of the month of
September
[Fig. 6(a)]. Furthermore, the room air temperature fluctuated in the
range of 22.7–30.1°C. Only two discomfort hours during the
representative day (between hours 13 and 15) were found during
this month; discomfort was determined on the basis of the accept- noticed discomfort hours was that the supply basement air temper-
able operative indoor temperature ranges that were determined for atures were not cool enough to moderate the indoor air tempera-
each month as recommended by the new adaptive comfort standard tures because of the high ambient temperatures during these two
for ASHRAE Standard 55 (ASHRAE 2001) (Table 2). The mean hours. Conversely, during the night and until sunrise, the assisting
outdoor air temperature was evaluated for the whole month, and not mechanical fan was turned on at the constant air flow, which
for the typical day considered, to determine the acceptable opera- brought outside air directly to the living room, unlike the Trombe
tive indoor temperature ranges. The primary reason behind the wall that brought basement air into the room. Thus, the pattern of
September 27.3 22.7 29.7 For the remaining summer months (July through September),
a similar trend of air flow rate variation occurred [Figs. 6(b),
7(b), and 8(b)]; the peak value of the ventilation air occurred
in August at the 12th h when solar intensity was strong enough
(1; 258 W=m2 ) and was close to 0.102 kg=s.
From the previous results, Fig. 9 shows the total number of dis-
comfort hours that occurred during each month in the living room.
Thus, for the sunshine hour period extending from the 7th h to the
18th h (natural airflow mode), the thermal comfort was achieved at
80% acceptability for 83.3% of the time during month of June, 75%
during July, 58.3% during August, and 66.7% during September.
Moreover, these results were benchmarked with a similar study
conducted by Yassine et al. (2014) during the month of August
for the same climatic and solar conditions, and for the same living
room area and schedule at different wall configurations. However,
they tampered air temperature by using an EAHE compared with
Fig. 9. Number of discomfort hours for 80% acceptable thermal com-
this study, in which air tampering was done by using the under-
fort conditions in the living room during the sunshine hours (June
ground basement. Table 3 shows that the current ventilation system
through September)
and that of Yassine et al. (2014) has almost the same potential in
providing indoor thermal comfort for the whole occupied period in
the living zone. However, using EAHE has other problems asso-
the supply air temperature changed after the forced airflow mode ciated with maintenance, cleanness, and its high cost. The proposed
was initiated for the period hour extended from the 19 h to 6 h, with system used existing basement air that is less complex, easier to
the supply ambient air in the range of 12.1–31.2°C [Fig. 5(a)]. In clean, and can be retrofitted to existing rooms if the house has a
addition, there was a large gap between the profiles of basement basement.
and ambient air temperatures during the sunshine hours when the
basement was treated as an open system; this was primarily because
Economic Analysis
of the much greater heat capacity of the sandy clay loam soil (approx-
imately 1,325 times) as compared with air (1.59 versus 0.0012 MJ= The proposed natural ventilation system performance was com-
m3 · K). However, this gap became smaller during the night when the pared with a mechanical cooling system that would lower the
ambient air temperature gradually dropped [Fig. 5(a)]. ambient temperature to the level that matched the basement temper-
Similar behavior was observed for the representative days of the atures obtained by the proposed natural ventilation system. The
other summer months (July through September) as shown in Figs. 6 comparison was made with a mechanical ventilation system that
(a), 7(a) and 8(a), during which three discomfort hours (between used a direct expansion system at a coefficient of performance
hours 11 and 14) were found during July compared with five dis- of 3.0 to cool the outdoor air to the basement air temperature drawn
comfort hours (between hours 11 and 16) during August, and four by the natural ventilation method at each hour. The split unit was
discomfort hours (between hours 11 and 15) during September. used only when the basement temperature was lower than the am-
For the month of June and during the natural cooling mode, the bient air (T ba < T a ). The savings in electrical power were calcu-
Trombe wall was operational for the sunshine hours extending from lated on the basis of the required energy to drop the ambient air
the 7th to the 18th hour. It is clear from Fig. 5(b) that the induced air temperature to the basement air temperature when T ba < T a .
Table 3. Benchmarking with a Case Study Conducted by Yassine et al. (2014) during August
Occupied Natural Number of discomfort
Case study period Wall configurations means hours
Yassine et al. 8–23 h 15 cm hollow concrete (base case) EAHE 7 h (11–18 h)
(2014) 8–23 h 3 cm of straw sandwiched between 2 cm × 6 cm of hempcrete EAHE 3 h (14–17 h)
8–23 h 5 cm of straw sandwiched between 2 cm × 10 cm of hempcrete EAHE 0
Current study 7–18 h 15 cm concrete + 5 cm insulation + 1 cm plaster on the inside Trombe 5 h (11–16 h)
and outside of the wall wall
t = time (s);
T = temperature;
V = wind velocity (m=s);
Fig. 10 demonstrates the energy savings attained in the living V r = room volume (m3 );
zone when adopting the proposed system as compared with a W = width of air channel (m);
100% mechanical ventilation systems. The highest energy saving α = absorptivity;
was reached during the month of July with 68.17 kWh ε = emissivity;
(2.3 kWh=m2 ), whereas it reached its lowest value during the ρ = density (kg=m3 ); and
month of September with 34.52 kWh (1.15 kWh=m2 ). In June τ = transmission coefficient.
and August, the energy savings were found to be 60.68 kWh
(2.02 kWh=m2 ) and 67.93 kWh (2.26 kWh=m2 ), respectively. Subscripts
The results of the case study showed that the proposed natural ven-
tilation system is effective. It reduced the cooling energy demand. a = ambient air;
Moreover, the total electric energy consumption of the system ba = basement air;
over a period of four months (June through September) was esti- f = air in the channel of the Trombe wall;
mated to be 231.3 kWh (7.71 kWh=m2 ). The cost of electricity in g = glass;
Lebanon is estimated as 0.13$=kWh. Therefore, the cost of elec- r = room; and
tricity consumption by the mechanical ventilation system over the w = wall.
four months was $30.1 (1$=m2 ). As for the proposed system,
the incremental cost of adding glazed cover windows in front of
the wall with the required vents and dampers was considered.
Ultimately, the average completed Trombe wall cost $119, at a pay- References
back period of approximately four years. Allard, F., Santamouris, M., Alvarez, S., European Commission, and
ALTENER Programme. (1998). Natural ventilation in buildings: A
design handbook, James & James (Science Publishers), London.
Conclusion Al-Temeemi, A. A., and Harris, D. J. (2003). “The effect of earth-contact on
heat transfer through a wall in Kuwait.” Energy Build., 35(4), 399–404.
This paper evaluated the implementation of an integrated natural Annan, G., Ghaddar, N., and Ghali, K. (2016). “Natural ventilation in Bei-
ventilation system that uses a Trombe wall to supply fresh air and rut residential buildings for extended comfort hours.” Int. J. Sustainable
cooling needs from an underground basement. It was shown that Energy, 35(10), 996–1013.
ASHRAE (American Society of Heating, Refrigerating and Air-Conditioning
using the proposed system for naturally cooling a room is feasible
Engineers). (1992). “Thermal environmental conditions for human occu-
during the daytime hours for an insulated house in hot arid climate pancy.” ASHRAE Standard 55, Atlanta.
of inland Lebanon. The proposed system maximum-induced ven- ASHRAE (American Society of Heating, Refrigerating and Air-Condition-
tilation-flow rate per unit area of the Trombe wall was at noon, the ing Engineers). (2001). “A new adaptive comfort standard for ASHRAE
time of maximum solar radiation, at values of 6.94 × 10−3 kg= standard 55.” Univ. of California, Berkeley, CA.
s · m2 , 7.28 × 10−3 kg=s · m2 , 7.31 × 10−3 kg=s · m2 , and 7.24 × ASHRAE (American Society of Heating, Refrigerating and Air-Conditioning
10−3 kg=s · m2 for the months of June, July, August, and September, Engineers). (2004). “Ventilation for acceptable indoor air quality.”
respectively. Moreover, the difference between the room air and ASHRAE Standard 62.1, American Society of Heating, Refrigerating and
Air-Conditioning Engineers, Atlanta.
basement temperatures was in the range of 1.3–7.2°C in June,
Badescu, V., and Isvoranu, D. (2011). “Pneumatic and thermal design pro-
2.3–4.6°C in July, þ0.9 − 3.8°C in August, and þ0.8 − 3.9°C in cedure and analysis of earth-to-air heat exchangers of registry type.”
September. In addition, the number of discomfort hours resulting Appl. Energy, 88(4), 1266–1280.
from the proposed system and ventilation strategy was low in num- de Dear, R. J., and Brager, G. S. (2002). “Thermal comfort in naturally
ber of hours, with thermal discomfort at values of 60 h for the ventilated buildings: Revisions to ASHRAE standard 55.” Energy Build.,
whole month of June, 93 h in July, 155 h in August, and 120 h 34(6), 549–561.
in September. Fanger, P. O. (1970). Thermal comfort, Danish Technical Press, Copen-
Energy savings were observed when comparing the integrated hagen, Denmark.
Fawaz, H., Abiad, M., Ghaddar, N., and Ghali, K. (2014). “Solar-assisted local-
system that used the Trombe wall and basement air, expressed per
ized ventilation system for poultry brooding.” Energy Build., 71, 142–154.
unit area of the floor at 2.02 kWh=m2 in June, 2.3 kWh=m2 in July, Florides, G., and Kalogirou, S. (2004). “Measurements of ground temper-
2.26 kWh=m2 in August, and 1.15 kWh=m2 in September. The ature at various depths.” Proc., SET 2004, 3rd Int. Conf. on Sustainable
cost saving for the four months was estimated at $1=m2 of floor Energy Technologies on CD-ROM, Univ. of Nottingham, Nottingham,
area with a payback period of less than four years. U.K.