You are on page 1of 11

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/305452472

Case Study of Trombe Wall Inducing Natural Ventilation through Cooled


Basement Air to Meet Space Cooling Needs

Article  in  Journal of Energy Engineering · July 2016


DOI: 10.1061/(ASCE)EY.1943-7897.0000393

CITATIONS READS

5 2,344

3 authors:

Mazen Badawiyeh Nesreen Ghaddar


American University of Beirut American University of Beirut
2 PUBLICATIONS   6 CITATIONS    287 PUBLICATIONS   4,779 CITATIONS   

SEE PROFILE SEE PROFILE

K. Ghali
American University of Beirut
221 PUBLICATIONS   3,473 CITATIONS   

SEE PROFILE

Some of the authors of this publication are also working on these related projects:

Sustainable cooling system for Kuwait hot climate combining diurnal radiative cooling and indirect evaporative cooling system View project

Integration of intermittent Personalized Ventilation in office spaces: Thermal comfort, Indoor air quality and Energy savings View project

All content following this page was uploaded by Nesreen Ghaddar on 15 March 2019.

The user has requested enhancement of the downloaded file.


Case Study of Trombe Wall Inducing Natural
Ventilation through Cooled Basement Air to
Meet Space Cooling Needs
Mazen Badawiyeh 1; Nesreen Ghaddar 2; and Kamel Ghali 3
Downloaded from ascelibrary.org by AMERICAN UNIV OF BEIRUT on 10/06/16. Copyright ASCE. For personal use only; all rights reserved.

Abstract: Underground spaces normally are at cooler air temperature than ambient air temperature because of earth-sheltered walls. This
cooler air can be circulated to occupied spaces using a solar chimney effect to exhaust air from the basement to where it is needed. This work
aims to study the viability of using natural ventilation induced by a Trombe wall to draw fresh air from underground basement floors for space
cooling in the dry desert climate. Outdoor air is delivered to the basement through an earth tube. A numerical model integrating thermal
models of the basement space and the occupied zone, and the Trombe wall is used to predict the air temperature variation with time in the
occupied space air temperature and to predict thermal comfort. The feasibility of implementing the proposed system is assessed in a case
study of a residence in the inland dry desert climate of Lebanon during the summer. It was found that the proposed system achieved thermally
comfortable conditions at 80% acceptability for a considerable number of hours without the need for mechanical ventilation (83.3% in
June and 58.3% in August). The electric energy consumption of the system over summer (June through September) was estimated at
7.71 kW · h=m2 of floor area. DOI: 10.1061/(ASCE)EY.1943-7897.0000393. © 2016 American Society of Civil Engineers.
Author keywords: Natural ventilation; Trombe wall; Solar energy; Energy efficiency; Basement air modeling.

Introduction could be a feasible solution for providing thermal comfort in mod-


erate climates and for reducing energy consumption in residential
With increased world population and human development, the en- buildings.
ergy demand of buildings is forecasted to continue rising around Natural ventilation was found promising in moderate climates
the world in the coming decades if measures are not strictly applied for several types of buildings; it was found to reduce building energy
to reduce dependence on electrical energy for air conditioning consumption and offer an acceptable indoor environment (Pfafferott
(Xing et al. 2011; Ibn-Mohammed et al. 2013; IEA 2013a). Res- 2004; Pfafferott et al. 2013; Annan et al. 2016). In the Middle East, a
idential buildings use 27% of the total energy consumption world- 52% possibility of natural ventilation usage is expected in Lebanon
wide (Laustsen 2008). Hence, energy effectiveness should be under current weather data (Annan et al. 2016), compared with
enhanced by adopting energy-efficiency measures that decrease 10–40% energy savings achieved in Dubai, United Arab Emirates
building energy consumption in heating ventilation and air condi- (UAE) during moderate climate months (Taleb et al. 2015). Unfortu-
tioning (HVAC) systems (IEA 2013b). nately, the main disadvantage of using natural ventilation is its
Mechanical ventilation is the most widely used mechanism for dependence on the outdoor conditions, which means that if the out-
building air conditioning in the twentieth century (Kleiven 2003), side air temperature is high, then there would be no possibility of
however, it is associated with substantial initial installation, main- taking advantage of this system except possibly in providing night
tenance, and operating costs (Wigginton and Harris 2002). The ventilation. Providing acceptable thermal comfort conditions all year
energy consumption associated with ventilation in buildings has round is not possible relying on natural ventilation alone.
been steadily increasing (Roodman and Lenssen 1995), which Researchers have considered hybrid mixed ventilation systems
led to consideration of other less energy consuming alternative sys- in which moderating fresh air temperature is achieved through other
tems for building ventilation (Ford et al. 1998). Natural ventilation means. The earth-to-air heat exchanger (EAHE) is a potential
passive cooling system that can be used to reduce ventilation air
1 temperature during high outdoor conditions (U.S. Department of
Graduate Student, Faculty of Engineering and Architecture, Dept. of
Mechanical Engineering, American Univ. of Beirut, P.O. Box 11-0236,
Energy 2007). This technique was implemented in an office build-
Beirut 1107-2020, Lebanon. E-mail: mazen.badawiyeh@gmail.com ing in Marburg, Germany (Voss et al. 2007; Spieler et al. 2000;
2
Qatar Chair in Energy Studies Professor, Faculty of Engineering and Wagner et al. 2000), in a school in Italy (Grosso and Raimondo
Architecture, Dept. of Mechanical Engineering, American Univ. of Beirut, 2008), and in a hospital building in India (Badescu and Isvoranu
P.O. Box 11-0236, Beirut 1107- 2020, Lebanon (corresponding author). 2011). Moreover, some researchers considered integrating the
E-mail: farah@aub.edu.lb mechanical ventilation with earth tubes to increase the effectiveness
3
Professor of Mechanical Engineering and Chair, Faculty of Engineer- of ventilation during the hours of high air temperature (Peretti et al.
ing and Architecture, Dept. of Mechanical Engineering, American Univ. of 2013). However, these techniques are expensive because they
Beirut, P.O. Box 11-0236, Beirut 1107-2020, Lebanon. E-mail: ka04@
require costly excavation and fan power. Yuebin et al. (2014) exper-
aub.edu.lb
Note. This manuscript was submitted on November 4, 2015; approved
imented with alternative passive cooling techniques using a
on May 26, 2016; published online on July 19, 2016. Discussion period Trombe wall and a solar chimney. Trombe walls and solar chimneys
open until December 19, 2016; separate discussions must be submitted are relatively similar because they both rely on solar-induced,
for individual papers. This paper is part of the Journal of Energy Engi- buoyancy-driven convection. Their results showed that the sug-
neering, © ASCE, ISSN 0733-9402. gested passive cooling system operated successfully via natural

© ASCE 04016039-1 J. Energy Eng.

J. Energy Eng., 04016039


ventilation all summer without need of any power source (Yuebin investigated in terms of achieving thermal comfort and economic
et al. 2014). Although the solar chimney or the Trombe wall was feasibility.
shown as a solution to replace the ventilation fan, it still did not
resolve the issue of expensive excavation.
The majority of residential buildings have underground spaces System Description and Mathematical Formulation
that are used for a variety of functions. These underground spaces
Fig. 1 shows the natural ventilation system under consideration.
are characterized by air that is cooler than ambient conditions in
Solar radiation through the glass cover of the Trombe heated the
hot-arid climates (Al-Temeemi and Harris 2003). This feature
absorber wall that, in turn, heated the air in the spacing between
could be used in space cooling of occupied zones in which the
the glass and the wall. Heated channel air moved upward by buoy-
underground space walls are sheltered by earth and protected from
ance and drew air from the living room that, in turn, brought cooler
direct solar radiation (Todorovic and Despotovic 1999). Moder-
basement air into the room. The air in the basement was drawn from
ated basement air could replace air-to-earth expensive heat
Downloaded from ascelibrary.org by AMERICAN UNIV OF BEIRUT on 10/06/16. Copyright ASCE. For personal use only; all rights reserved.

the outdoors through an earth tube and was moderated because of


exchange in which fresh air is drawn into the basement to mix the exchange of heat with the cool underground basement walls.
with basement air and then into the occupied space. Ghaddar et al. The proposed passive cooling system operation depends on
(2015) modeled the combination of the Trombe wall and base- multiple parameters that include ambient and solar conditions,
ment air moderation for ventilation, but the success of system basement size and construction material, a Trombe wall air gap,
operations to attain comfort conditions for the entire summer sea- and glass and absorber wall properties and dimensions. The system
son in hot dry climates, combined with forced ventilation, has not was applied to a case study of a building located in the Inland
been tackled. Plateau of Lebanon. Lebanon is located on the eastern side of the
The objective of this work is to study the performance of a natu- Mediterranean (latitude 33°49N; longitude 35°29E). The Inland
ral ventilation system that uses the Trombe wall to bring fresh air Plateau of Lebanon is a semi-arid region characterized by hot and
into the indoor space from an underground basement in dry arid dry summer days with dry-bulb temperature in the range of
climates. The basement moderated the fresh air drawn through a 33–37°C, but is cool and dry during summer nights during which
vertical earth tube. The system performance was assessed with re- the temperatures are in the range of 21–26°C, and the relative hu-
spect to energy requirements and its ability to provide acceptable midity ranges from 32% to 46%. Given the rural nature of the
thermal comfort to occupants using both natural and mechanical region, common housing in the inland region is detached discon-
modes of operation. The combined passive cooling system was ap- nected houses with basements. The thermal buildings guideline in
plied to a living room of a residential house located in a Lebanon that region requires the use of insulation because of cold winters
inland zone that is characterized by a dry hot climate. A numerical during which ambient temperature could be as low as −6.7°C (Re-
model of the spaces (living room and basement) and the Trombe public of Lebanon Ministry of Public Works and Transport 2005a).
wall was developed to predict air temperature in the room and base- The combined system of the Trombe wall, the room, the soil,
ment, and to predict the associated ventilation flow rate. The effec- and the basement are modeled using the integrated approach pro-
tiveness of natural ventilation using the proposed system was posed by Ghaddar et al. (2015) to determine the hourly living-room

Fig. 1. Schematic of the combined natural ventilation system with Trombe wall and basement

© ASCE 04016039-2 J. Energy Eng.

J. Energy Eng., 04016039


τ αw I ¼ hw ðT w − T f Þ þ hrwg ðT w − T g Þ þ U b ðT w − T r Þ ð4aÞ

where
U b ¼ 1=ð1=hi þ d=kw þ wins =kins Þ ð4bÞ

where the absorbed solar radiation by the vertical wall is balanced


by heat convection with air in the channel, the radiative heat trans-
fer with the glass cover, and the conducted heat transfer to the
room.

Room Model
Downloaded from ascelibrary.org by AMERICAN UNIV OF BEIRUT on 10/06/16. Copyright ASCE. For personal use only; all rights reserved.

The room energy balance used a lumped air modeling approach,


but neglected infiltration to predict the indoor temperature varia-
tions in time. The room air energy balance for when it is drawn
from the basement is given by
Fig. 2. Diagram of the Trombe wall and its parameters
∂T r ðtÞ X 6
: X
ρf V r c f ¼ hcr Ai ðT i − T r Þ þ mcf ðT ba − T r Þ þ qint
∂t i¼1
thermal comfort conditions during representative days of each
summer for the case study. ð5aÞ
During day hours, the system used natural ventilation mode and where ρf , V r , and cf = air density, room volume, and air specific
during night hours the system used a mechanical fan. The compo- heat capacity, respectively; Ai = surface area; T i = temperature of the
nent models used in this study are described briefly, followed by the room internal wall surface element I; ṁ = mass flow rate of the air
case study description. drawn from the basement at basement temperature T ba ; and qint =
internal heat load because of lighting, occupancy, and equipment.
Trombe Wall Model The primary purpose of using the Trombe wall in this study was
to generate the required buoyancy capable of drawing the cool air
Ong and Chow (2003) developed a steady state one-dimensional from the basement as previously mentioned. But to do so, the
(1D) Trombe wall model to predict the air mass flow rate induced Trombe wall needed sufficient solar energy to heat the absorber
by the Trombe wall. Their lumped physical model of the Trombe wall that drives the air flow in the channel, while maintaining con-
wall shown in Fig. 2 is adopted in the current work, in which the stant room temperature. This is the case during the sunshine hours.
energy balances of the glass wall, the buoyant air flow in the sepa- However, during the night when solar energy is not available to
rating channel, and the absorber wall are formulated on the basis of activate the Trombe wall to drive the basement air, a mechanical
an hourly quasi-steady state assumption. The energy balance of the fan was used to draw outdoor air for night ventilation. The fan was
glass cover is given by operated at the minimum outdoor air requirements of 15 cu ft=min
(cfm) (7.5 L=s) per person for ventilation of residential facilities
αg I þ hc ðT w − T g Þ þ hg ðT f − T g Þ ¼ U t ðT g − T a Þ ð1aÞ
as per American Society of Heating, Refrigerating, and Air-
where Conditioning Engineers (ASHRAE) standard 62.1 (ASHRAE
2004) to provide minimum fresh air ventilation needs. Hence, the
hc ¼ σðT 2g þ T 2w ÞðT g þ T w Þ=ð1=εg þ 1=εw − 1Þ ð1bÞ lumped air energy balance when the mechanical fan is used is
given by
where T g , T w , and T f = temperatures of the glass cover, the
absorber wall, and the air in the channel, respectively; U t = com- ∂T r ðtÞ X 6
: X
ρf V r c f ¼ hcr Ai ðT i − T r Þ þ mf cf ðT a − T r Þ þ qint
bined radiative heat loss coefficient (hrs ) and convection heat loss ∂t i¼1
coefficient (hc;wind ) from the glass outer surface; and σ = Stefan
ð5bÞ
Boltzmann constant. The energy balance of the air flow in the chan-
nel is given by where ṁf = fan supply flow rate.
hw ðT w − T f Þ ¼ hg ðT f − T g Þ þ ṁcf ðT f − T f;i Þ=WL ð2Þ The convection heat transfer at each of the room internal walls
depends on the wall temperature. Accordingly, the transient 1D
where the air mass flow rate ṁ (kg=s), because of the stack effect, heat conduction equation presented by Yassine et al. (2012) was
was determined using the buoyancy-driven stack effect equation adopted to determine the space wall temperatures. The 1D heat
presented by Allard et al. (1998) and is given by transfer was assumed in the walls while considering the storage
sffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi effect because of varying outdoor conditions and internal loads.
 ffi Thus, the transient heat conduction equation for the absorber wall
2ΔTgH
ṁ ¼ ρf Cd A ð3Þ and external room walls is given by
Tr
∂2T ∂T
where ρf = density of air (kg=m3 ); Cd = opening’s discharge co- kw 2
− ρ w cw ¼0 ð6Þ
∂x ∂t
efficient [0.6 according to Flourentzou et al. (1998)]; A = channel
inlet/outlet opening’s cross-sectional area (m2 ); ΔT = temperature The absorber wall outer surface temperature was determined
difference between room air T r and T f (°C); g = gravitational ac- from the Trombe wall model. The external wall surfaces used con-
celeration; and H = height between the inlet and the outlet (m) to vective and radiative heat transfer boundary conditions as reported
the channel. Similarly, the absorber wall energy balance leads to by Yassine et al. (2012).

© ASCE 04016039-3 J. Energy Eng.

J. Energy Eng., 04016039


Basement Model T amp
T soil ða − b; tÞ ¼ T mean þ pffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
The basement space model aimed to define the temperature varia- 2ðπ=365αÞða − bÞ
tions of the basement air, T ba , over time. A dynamic heat balance rffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi!
π
equation of the underground space presented by Kajtar et al. (2015) × exp −z
was adopted in this study. The heat balance of the underground 365 × α
space is given by " rffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi!#a
2π π
× cos t − tshift − z ð9Þ
365 year 365 × α
b
∂T ba ðtÞ
ρ f V b cf ¼ qintðbÞ − qw ðtÞ − qs ðtÞ ð7aÞ
∂t The values from Eq. (9) represent the boundary conditions for
each wall in the simulation of the below-grade wall section using
Eq. (6) that was adopted for the absorber wall. The basement model
Downloaded from ascelibrary.org by AMERICAN UNIV OF BEIRUT on 10/06/16. Copyright ASCE. For personal use only; all rights reserved.

where qintðbÞ = internal heat load in the basement; and qw ðtÞ = heat assumed that the temperature of the soil changed in accordance with
transfer by convection from the air to the wall as follows: the change of season. This change meant that a certain delay and
damping in soil temperature took place as depth of soil increased.
The amplitude of the temperature change was 0.6 and 0.2°C at the
X
4
qw ðtÞ ¼ hcb Ai ½T ba ðtÞ − T i ðx; tÞjx¼0  ð7bÞ depths of 8 m and 10 m, respectively (Kajtar et al. 2015). The location
i¼1 of the underground space determined the reference soil temperature to
be used. Further, the low-thermal diffusivity of the soil (0.316 ×
10−6 m2 =s in the current case study, which is much lower than that
where Ai and T i = surface area and the temperature of the room of the air, 22.5 × 10−6 m2 =s) justified the consideration of the soil
wall i. The heat because of ventilation is given by temperature as quasi-stationary. The temperature fluctuations at the
surface of the ground are diffused very slowly in depth because
of the soil’s high-thermal capacity. Accordingly, daily ground temper-
qs ðtÞ ¼ ṁ cf ½T ba ðtÞ − T a ðtÞ ð7cÞ atures were considered rather than hourly ones (Florides and
Kalogirou 2004). The soil was assumed a homogeneous material
in terms of heat transfer properties with its resultant thermal character-
The outdoor air was assumed to be brought to the basement istics (Kajtar et al. 2015). The concrete walls were considered to have
through a vertical earth tube at the floor level to ensure good mixing similar thermal characteristics as the soil (Kajtar et al. 2015).
with basement air. The outdoor air temperature was moderated be-
cause of the heat exchanges with the basement cool surfaces and to
mix with the mass of air present. The extent of cooling of basement Thermal Comfort Model
air depended on the surrounding ground vertical temperature Thermal comfort models have been reported for mechanically
distribution. ventilated/cooled indoor environments [ASHRAE standard 55
Labs and Cook (1989) modeled and reported the ground temper- (ASHRAE 1992); Fanger 1970; Kruger 2008; Zhang et al. 2010].
ature as a function of the time of year and the depth below the Because proposed systems in this work relied on natural ventila-
surface. Their correlation was adopted by Florides and Kalogirou tion, the new ASHRAE standard 55 (ASHRAE 2001) adaptive
(2004) and was adopted in the current work. The soil temperature comfort model (ACM) was used. The ACM, according to de Dear
correlation is given is given by and Brager (2002) and Taleghani et al. (2014), predicts occupants’
thermal comfort in naturally ventilated rooms using a single input
rffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi! variable, which is the outdoor mean temperature, T a;out .
π The optimal comfort temperature, T comf , is given by
T soil ðz; tÞ ¼ T mean − T amp × exp −z
365 × α
" T comf ¼ 0.31 × T a;out þ 17.8 ð10Þ
rffiffiffiffiffiffiffiffiffiffiffiffi!#
2π z 365
× cos tyear − tshift − ð8Þ where T a;out and T comf are expressed in °C. Eq. (10) applies to
365 2 π×α outdoor dry-bulb temperature ranges between 5 and 32°C, and for
sedentary activity levels less than 1.3 MET (Metabolic Equivalent
of Task; 1 MET = 104 W) (Taleghani et al. 2014). Residential ap-
where T soil = soil temperature; z = depth; tyear = time of the year (in plications consider an 80% acceptability limit as adequate for ther-
days); tshift = day of the year of the minimum surface temperature mal comfort level. For higher standards of thermal comfort level, a
(For Lebanon Inland Plateau, tshift is 35 days corresponding to the 90% acceptability limit may be used. The range of temperatures
date of Feb. 4); T mean = mean annual ground surface temperature, around T comf within the 80% thermal acceptability is determined
which is equal to the average air temperature (°C); T amp = temper- on the basis of outdoor temperature.
ature amplitude at the ground surface amplitude of surface temper-
ature (the maximum surface temperature will be (T mean þ T amp )
and the minimum value will be T mean − T amp ); and α = thermal Numerical Simulation Methodology
diffusivity of the soil (Florides and Kalogirou 2004). The soil tem-
perature below the basement’s floor construction was calculated at A numerical finite difference method was used in this work. An
equal soil depth to the basement depth. Moreover, temperature as implicit first-order time integration scheme was used for room air,
the external temperature of the basement vertical wall in contact external walls, Trombe wall, and basement energy balance equa-
with the soil. This average temperature was obtained by integrating tions, and a second-order spatial discretization was used for the
Eq. (8) with respect to z and divided by the submerged wall depth. wall nodes. Each layer of the wall was divided into control vol-
Al-Temeemi and Harris (2003) reported the expression for the aver- umes. A total of 70 nodes was used for the wall. Input data for the
age vertical soil temperature as follows: geometry, thermal properties, and boundary and initial conditions

© ASCE 04016039-4 J. Energy Eng.

J. Energy Eng., 04016039


Downloaded from ascelibrary.org by AMERICAN UNIV OF BEIRUT on 10/06/16. Copyright ASCE. For personal use only; all rights reserved.

Fig. 3. Flow chart of the numerical modeling methodology

were compiled for each model. The system model predicted the Case Study
amount of induced airflow and associated thermal comfort during
natural ventilation hours and during the periods when mechanical The proposed natural ventilation system implementation was con-
ventilation was used. sidered for a small isolated, single living room over a basement
Simulations were performed using a developed MATLAB code (Fig. 1) for the climate of an inland district in Lebanon, character-
to find the room air temperature in response to external and internal ized by a hot arid climate. Table 1 summarizes the outdoor temper-
loads as indicated in the flow chart (Fig. 3). Starting from the ature and solar radiation data for representative summer days at the
Trombe wall model that predicts the absorber-wall outer surface 15th of each month, June through September (Fawaz et al. 2014).
temperature facing glass and using a time step of 360 s, the inner The room base area was 6 × 5 m and its height was taken as 2.8 m.
surface temperatures of the inner walls and the absorber wall were It was exposed to the outside from two sides. The external plastered
computed. Simulations were performed for a representative day on walls used typical construction of Lebanese building material
the 15th of each month from June to September. The representative (15-cm hollow blocks), whereas the insulated roof was made of
day simulation was continued over a number of cycle days until a 20-cm reinforced concrete (Republic of Lebanon Ministry of Pub-
steady periodic solution state was reached for the room air temper- lic Works and Transport 2005b). The overall heat transfer coeffi-
ature. The criterion for convergence was set when the maximum cients for the external wall and roof were 2.36 and 1.67 W=m2 · K,
percentage error in air temperature at time t and t þ 24 h was less respectively. The basement area was similar to the living room with
than 10−4 %. The flow chart shown in Fig. 3 summarizes the path a submerged depth of 2.5 m in soil. The soil thermal diffusivity,
followed to calculate the needed output from the developed model. thermal conductivity, and heat capacity were 0.316 × 10−6 m2 =s,

© ASCE 04016039-5 J. Energy Eng.

J. Energy Eng., 04016039


Table 1. Ambient and Solar Data for Typical Summer Day on 15th of Each Month for the Inland Lebanon Climate
June July August September
Ambient Solar Ambient Solar Ambient Solar Ambient Solar
temperature radiation temperature radiation temperature radiation temperature radiation
Time (h) (°C) (W=m2 ) (°C) (W=m2 ) (°C) (W=m2 ) (°C) (W=m2 )
1 14.4 — 23.7 — 18.3 — 17.9 —
2 14.1 — 21 — 16.4 — 16.8 —
3 13.7 — 18.7 — 16.4 — 14.8 —
4 12.5 — 17.1 — 14.4 — 14.8 —
5 12.1 — 15.6 — 13.7 — 13.7 —
6 14.4 514 16.0 448 15.2 405 13.7 359
7 18.7 762 21.3 707 16.8 671 13.3 631
Downloaded from ascelibrary.org by AMERICAN UNIV OF BEIRUT on 10/06/16. Copyright ASCE. For personal use only; all rights reserved.

8 23.7 979 26.4 934 24.4 904 22.5 867


9 26.0 1,148 28.7 1,113 28.7 1,087 28.0 1,051
10 28.0 1,259 31.2 1,232 31.6 1,208 31.2 1,169
11 30.4 1,303 33.6 1,283 34.1 1,258 33.2 1,215
12 32.4 1,278 34.5 1,263 36.2 1,235 32.8 1,185
13 33.2 1,186 34.5 1,173 35.3 1,139 34.1 1,080
14 33.6 1,032 35.3 1,018 36.6 978 33.6 909
15 34.1 827 34.9 810 36.2 762 32.8 683
16 33.6 586 34.5 563 34.1 506 31.6 417
17 32.0 324 33.2 294 29.9 227 28.3 274
18 31.2 — 32.0 — 26.4 — 26.4 —
19 29.5 — 28.7 — 24.8 — 24 —
20 24.0 — 25.2 — 22.9 — 22.5 —
21 22.1 — 24 — 22.1 — 21.0 —
22 22.1 — 22.1 — 21.0 — 20.2 —
23 19.8 — 20.2 — 20.2 — 20.2 —
24 19.8 — 20.2 — 20.2 — 20.2 —

0.50 W=m · K, 1.59 × 103 kJ=m3 · K, respectively. The basement load during the sunshine hours. The electrical loads were 10 W=m2
vertical walls had similar construction to the roof, but was not in- for lighting fixtures and 800 W for appliances.
sulated, whereas its floor was made of concrete tiles. The Trombe wall was incorporated at the south wall of the living
The occupancy schedule was taken for a six-person family that room, which had a 5-m width and 2.8-m height. Its absorber
at peak time would occupy the living room (Republic of Lebanon masonry wall was covered by a double-glazed wall (emissivity
Ministry of Public Works and Transport 2005a). Fig. 4 shows the of 0.75) and had thickness 0.4 m, thermal conductivity of
living room summertime schedule of occupancy and the electrical 1.8 W=m · K, and emissivity of 0.2. The back of the absorber wall
was insulated by a 5-cm layer of insulation with a thermal conduc-
tivity of 0.032 W=m · K. The air channel width was 0.3 m. The
Trombe wall was operated during sunshine hours to draw the base-
ment’s cool air into the living room, whereas the mechanical ven-
tilation fan was operated during low solar radiation and night hours
to meet minimum ventilation requirements.
The performance of the combined system was evaluated with
respect to the maximum number of hours in which comfort was
achieved with minimum dependence on forced ventilation.

Results and Discussion

Simulations were performed on the case study for the representative


days of each summer month. For the month of June, Fig. 5 shows
the ambient temperature, the indoor room temperature, and the
basement temperature (a); and the associated air supply mass flow
rate into the room (b). Similarly, Figs. 6–8 show the temperatures of
ambient air, indoor air, and basement air (a); and the room air
supply flow rate for the months of July, August, and September,
respectively (b).
The comparison of ambient, basement, and room air tempera-
tures during the month of June are shown in Fig. 5(a). The differ-
ence between the ambient air and basement air temperatures was in
the range of 1.3–7.2°C. It is shown that under the natural airflow
Fig. 4. Plots of (a) the occupancy schedule; (b) electrical load schedule
mode, the supply basement air temperature was in the range of
inside the living room during sunshine hours
19–26.9°C and at least 2.0°C below the outdoor air temperature

© ASCE 04016039-6 J. Energy Eng.

J. Energy Eng., 04016039


Downloaded from ascelibrary.org by AMERICAN UNIV OF BEIRUT on 10/06/16. Copyright ASCE. For personal use only; all rights reserved.

Fig. 5. (a) Predicted temperatures; (b) room supply air mass flow rate
in the occupied room for the representative day of the month of June
Fig. 7. (a) Predicted temperatures; (b) room supply air mass flow rate
in the occupied room for the representative day of the month of August

Fig. 6. (a) Predicted temperatures; (b) room supply air mass flow rate
in the occupied room for the representative day of the month of July
Fig. 8. (a) Predicted temperatures; (b) room supply air mass flow rate
in the occupied room for the representative day of the month of
September
[Fig. 6(a)]. Furthermore, the room air temperature fluctuated in the
range of 22.7–30.1°C. Only two discomfort hours during the
representative day (between hours 13 and 15) were found during
this month; discomfort was determined on the basis of the accept- noticed discomfort hours was that the supply basement air temper-
able operative indoor temperature ranges that were determined for atures were not cool enough to moderate the indoor air tempera-
each month as recommended by the new adaptive comfort standard tures because of the high ambient temperatures during these two
for ASHRAE Standard 55 (ASHRAE 2001) (Table 2). The mean hours. Conversely, during the night and until sunrise, the assisting
outdoor air temperature was evaluated for the whole month, and not mechanical fan was turned on at the constant air flow, which
for the typical day considered, to determine the acceptable opera- brought outside air directly to the living room, unlike the Trombe
tive indoor temperature ranges. The primary reason behind the wall that brought basement air into the room. Thus, the pattern of

© ASCE 04016039-7 J. Energy Eng.

J. Energy Eng., 04016039


Table 2. Calculated Indoor Operative Temperature Limits for Comfort in flow rate increased with increasing solar radiation and that the
Naturally Ventilated Rooms for Inland Climate of Lebanon airflow rate varied from 0.041 kg=s to maximum of 0.097 kg=s
80% Acceptability on the basis during this month. Moreover, it was found that the lowest value
of ASHRAE Standard 55 of the ventilation air occurred during this month at the 18th h, dur-
(ASHRAE 2001) ing which the solar intensity was relatively very low (324 W=m2 )
Lebanon inland Minimum Maximum and close to 0.041 kg=s. However, during the forced airflow mode,
mean monthly permitted room permitted room external air was drawn into the living room using a constant speed
outdoor air temperature for temperature for fan that was turned on continuously at a constant air flow rate of
Month temperature (°C) comfort (°C) comfort (°C) 0.04 kg=s. This provided a sufficient rate of outdoor air replenish-
June 27.7 22.8 29.8 ment to fulfill ventilation requirements during nonsunshine hours
July 30.1 23.5 30.5 [Fig. 5(b)]. During the forced airflow mode, the basement heat bal-
August 29.8 23.4 30.4 ance was treated as a closed room with no air getting in or out.
Downloaded from ascelibrary.org by AMERICAN UNIV OF BEIRUT on 10/06/16. Copyright ASCE. For personal use only; all rights reserved.

September 27.3 22.7 29.7 For the remaining summer months (July through September),
a similar trend of air flow rate variation occurred [Figs. 6(b),
7(b), and 8(b)]; the peak value of the ventilation air occurred
in August at the 12th h when solar intensity was strong enough
(1; 258 W=m2 ) and was close to 0.102 kg=s.
From the previous results, Fig. 9 shows the total number of dis-
comfort hours that occurred during each month in the living room.
Thus, for the sunshine hour period extending from the 7th h to the
18th h (natural airflow mode), the thermal comfort was achieved at
80% acceptability for 83.3% of the time during month of June, 75%
during July, 58.3% during August, and 66.7% during September.
Moreover, these results were benchmarked with a similar study
conducted by Yassine et al. (2014) during the month of August
for the same climatic and solar conditions, and for the same living
room area and schedule at different wall configurations. However,
they tampered air temperature by using an EAHE compared with
Fig. 9. Number of discomfort hours for 80% acceptable thermal com-
this study, in which air tampering was done by using the under-
fort conditions in the living room during the sunshine hours (June
ground basement. Table 3 shows that the current ventilation system
through September)
and that of Yassine et al. (2014) has almost the same potential in
providing indoor thermal comfort for the whole occupied period in
the living zone. However, using EAHE has other problems asso-
the supply air temperature changed after the forced airflow mode ciated with maintenance, cleanness, and its high cost. The proposed
was initiated for the period hour extended from the 19 h to 6 h, with system used existing basement air that is less complex, easier to
the supply ambient air in the range of 12.1–31.2°C [Fig. 5(a)]. In clean, and can be retrofitted to existing rooms if the house has a
addition, there was a large gap between the profiles of basement basement.
and ambient air temperatures during the sunshine hours when the
basement was treated as an open system; this was primarily because
Economic Analysis
of the much greater heat capacity of the sandy clay loam soil (approx-
imately 1,325 times) as compared with air (1.59 versus 0.0012 MJ= The proposed natural ventilation system performance was com-
m3 · K). However, this gap became smaller during the night when the pared with a mechanical cooling system that would lower the
ambient air temperature gradually dropped [Fig. 5(a)]. ambient temperature to the level that matched the basement temper-
Similar behavior was observed for the representative days of the atures obtained by the proposed natural ventilation system. The
other summer months (July through September) as shown in Figs. 6 comparison was made with a mechanical ventilation system that
(a), 7(a) and 8(a), during which three discomfort hours (between used a direct expansion system at a coefficient of performance
hours 11 and 14) were found during July compared with five dis- of 3.0 to cool the outdoor air to the basement air temperature drawn
comfort hours (between hours 11 and 16) during August, and four by the natural ventilation method at each hour. The split unit was
discomfort hours (between hours 11 and 15) during September. used only when the basement temperature was lower than the am-
For the month of June and during the natural cooling mode, the bient air (T ba < T a ). The savings in electrical power were calcu-
Trombe wall was operational for the sunshine hours extending from lated on the basis of the required energy to drop the ambient air
the 7th to the 18th hour. It is clear from Fig. 5(b) that the induced air temperature to the basement air temperature when T ba < T a .

Table 3. Benchmarking with a Case Study Conducted by Yassine et al. (2014) during August
Occupied Natural Number of discomfort
Case study period Wall configurations means hours
Yassine et al. 8–23 h 15 cm hollow concrete (base case) EAHE 7 h (11–18 h)
(2014) 8–23 h 3 cm of straw sandwiched between 2 cm × 6 cm of hempcrete EAHE 3 h (14–17 h)
8–23 h 5 cm of straw sandwiched between 2 cm × 10 cm of hempcrete EAHE 0
Current study 7–18 h 15 cm concrete + 5 cm insulation + 1 cm plaster on the inside Trombe 5 h (11–16 h)
and outside of the wall wall

© ASCE 04016039-8 J. Energy Eng.

J. Energy Eng., 04016039


Notation

The following symbols are used in this paper:


A = area (m2 );
c = specific heat (J=kg · K);
d = thickness of absorber wall (m);
h = convective heat transfer coefficient (W=m2 · K);
I = incident solar radiation on vertical surface (W=m2 );
k = thermal conductivity (W=m · K);
L = length of absorber wall (m);
ṁ = mass flow rate (kg=s);
qint = room internal heat gain (W);
Fig. 10. Energy savings in the occupied room (June through September)
qintðbÞ = internal heat load in the basement (W);
Downloaded from ascelibrary.org by AMERICAN UNIV OF BEIRUT on 10/06/16. Copyright ASCE. For personal use only; all rights reserved.

t = time (s);
T = temperature;
V = wind velocity (m=s);
Fig. 10 demonstrates the energy savings attained in the living V r = room volume (m3 );
zone when adopting the proposed system as compared with a W = width of air channel (m);
100% mechanical ventilation systems. The highest energy saving α = absorptivity;
was reached during the month of July with 68.17 kWh ε = emissivity;
(2.3 kWh=m2 ), whereas it reached its lowest value during the ρ = density (kg=m3 ); and
month of September with 34.52 kWh (1.15 kWh=m2 ). In June τ = transmission coefficient.
and August, the energy savings were found to be 60.68 kWh
(2.02 kWh=m2 ) and 67.93 kWh (2.26 kWh=m2 ), respectively. Subscripts
The results of the case study showed that the proposed natural ven-
tilation system is effective. It reduced the cooling energy demand. a = ambient air;
Moreover, the total electric energy consumption of the system ba = basement air;
over a period of four months (June through September) was esti- f = air in the channel of the Trombe wall;
mated to be 231.3 kWh (7.71 kWh=m2 ). The cost of electricity in g = glass;
Lebanon is estimated as 0.13$=kWh. Therefore, the cost of elec- r = room; and
tricity consumption by the mechanical ventilation system over the w = wall.
four months was $30.1 (1$=m2 ). As for the proposed system,
the incremental cost of adding glazed cover windows in front of
the wall with the required vents and dampers was considered.
Ultimately, the average completed Trombe wall cost $119, at a pay- References
back period of approximately four years. Allard, F., Santamouris, M., Alvarez, S., European Commission, and
ALTENER Programme. (1998). Natural ventilation in buildings: A
design handbook, James & James (Science Publishers), London.
Conclusion Al-Temeemi, A. A., and Harris, D. J. (2003). “The effect of earth-contact on
heat transfer through a wall in Kuwait.” Energy Build., 35(4), 399–404.
This paper evaluated the implementation of an integrated natural Annan, G., Ghaddar, N., and Ghali, K. (2016). “Natural ventilation in Bei-
ventilation system that uses a Trombe wall to supply fresh air and rut residential buildings for extended comfort hours.” Int. J. Sustainable
cooling needs from an underground basement. It was shown that Energy, 35(10), 996–1013.
ASHRAE (American Society of Heating, Refrigerating and Air-Conditioning
using the proposed system for naturally cooling a room is feasible
Engineers). (1992). “Thermal environmental conditions for human occu-
during the daytime hours for an insulated house in hot arid climate pancy.” ASHRAE Standard 55, Atlanta.
of inland Lebanon. The proposed system maximum-induced ven- ASHRAE (American Society of Heating, Refrigerating and Air-Condition-
tilation-flow rate per unit area of the Trombe wall was at noon, the ing Engineers). (2001). “A new adaptive comfort standard for ASHRAE
time of maximum solar radiation, at values of 6.94 × 10−3 kg= standard 55.” Univ. of California, Berkeley, CA.
s · m2 , 7.28 × 10−3 kg=s · m2 , 7.31 × 10−3 kg=s · m2 , and 7.24 × ASHRAE (American Society of Heating, Refrigerating and Air-Conditioning
10−3 kg=s · m2 for the months of June, July, August, and September, Engineers). (2004). “Ventilation for acceptable indoor air quality.”
respectively. Moreover, the difference between the room air and ASHRAE Standard 62.1, American Society of Heating, Refrigerating and
Air-Conditioning Engineers, Atlanta.
basement temperatures was in the range of 1.3–7.2°C in June,
Badescu, V., and Isvoranu, D. (2011). “Pneumatic and thermal design pro-
2.3–4.6°C in July, þ0.9 − 3.8°C in August, and þ0.8 − 3.9°C in cedure and analysis of earth-to-air heat exchangers of registry type.”
September. In addition, the number of discomfort hours resulting Appl. Energy, 88(4), 1266–1280.
from the proposed system and ventilation strategy was low in num- de Dear, R. J., and Brager, G. S. (2002). “Thermal comfort in naturally
ber of hours, with thermal discomfort at values of 60 h for the ventilated buildings: Revisions to ASHRAE standard 55.” Energy Build.,
whole month of June, 93 h in July, 155 h in August, and 120 h 34(6), 549–561.
in September. Fanger, P. O. (1970). Thermal comfort, Danish Technical Press, Copen-
Energy savings were observed when comparing the integrated hagen, Denmark.
Fawaz, H., Abiad, M., Ghaddar, N., and Ghali, K. (2014). “Solar-assisted local-
system that used the Trombe wall and basement air, expressed per
ized ventilation system for poultry brooding.” Energy Build., 71, 142–154.
unit area of the floor at 2.02 kWh=m2 in June, 2.3 kWh=m2 in July, Florides, G., and Kalogirou, S. (2004). “Measurements of ground temper-
2.26 kWh=m2 in August, and 1.15 kWh=m2 in September. The ature at various depths.” Proc., SET 2004, 3rd Int. Conf. on Sustainable
cost saving for the four months was estimated at $1=m2 of floor Energy Technologies on CD-ROM, Univ. of Nottingham, Nottingham,
area with a payback period of less than four years. U.K.

© ASCE 04016039-9 J. Energy Eng.

J. Energy Eng., 04016039


Flourentzou, F., Van der Maas, J., and Roulet, C. (1998). “A natural ven- Republic of Lebanon Ministry of Public Works and Transport. (2005b).
tilation for passive cooling: Measurement of discharge coefficients.” “Energy analysis and economic feasibility.” UNDP/GEF, MPWT/
Energy Build., 27(3), 283–292. DGU, Beirut, Republic of Lebanon.
Ford, B., Patel, N., Zaveri, P., and Hewitt, M. (1998). “Cooling without air Roodman, D. M., and Lenssen, N. (1995). “World watch paper 124, a
conditioning.” Renewable Energy, 15, 177–182. building revolution: How ecology and health concerns are transforming
Ghaddar, N., Badawiyeh, M., and Ghali, K. (2015). “The energy perfor- construction.” Worldwatch Institute, Washington, DC.
mance of a building air conditioning system integrated with a basement Spieler, A., Wagner, R., Beisel, S., and Vajen, K. (2000). “Passive solar
cooling source driven by Trombe wall.” Proc., AIAA Propulsion and office building: First experiences and measurements.” 4th ISES Europe
Energy Forum and Exposition 2015, AIAA, Reston, VA. Solar Congress, International Solar Energy Society, Freiburg, Germany.
Grosso, M., and Raimondo, L. (2008). “Horizontal air to-earth heat Taleb, H. M. (2015). “Natural ventilation as energy efficient solution for
exchangers in Northern Italy–Testing, design and monitoring.” Int. J. achieving low-energy houses in Dubai.” Energy Build., 99, 284–291.
Ventilation, 7(1), 1–10. Taleghani, M., Tenpierik, M., and van den Dobbelsteen, A. (2014). “Energy
Ibn-Mohammed, T., Greenough, R., Taylor, S., Ozawa-Meida, L., and performance and thermal comfort of courtyard/atrium dwellings in
Acquaye, A. (2013). “Operational vs. embodied emissions in buildings—
Downloaded from ascelibrary.org by AMERICAN UNIV OF BEIRUT on 10/06/16. Copyright ASCE. For personal use only; all rights reserved.

the Netherlands in the light of climate change.” Renewable Energy,


A review of current trends.” Energy Build., 66, 232–245. 63, 486–497.
IEA (International Energy Agency). (2013a). “Transition to sustainable Todorovic, B., and Despotovic, B. (1999). “Development of calculation
buildings: Strategies and opportunities to 2050.” Paris. procedure for heat losses of underground spaces.” Proc., Transactions
IEA (International Energy Agency). (2013b). “World energy outlook 2013.” of 30th HVAC Congress, SMElTS, Belgrade, 427–435.
Paris. U.S. Department of Energy. (2007) “EERE consumer’s guide: Earth cool-
Kajtar, L., Nyers, J., and Szabo, J. (2015). “Dynamic thermal dimensioning ing tubes.” http://www.eere.energy.gov/consumer/your_home/space
of underground spaces.” Energy, 87, 361–368. _heating_cooling/index.cfm/mytopic=12460.
Kleiven, T. (2003). “Natural ventilation in buildings: Architectural con- Voss, K., Herkel, S., Pfafferott, J., Lohnert, G., and Wagner, A. (2007).
cepts, consequences and possibilities.” M. Eng. thesis, Norwegian Univ. “Energy efficient office buildings with passive cooling—Results and
of Science and Technology, Norway. experiences from a research and demonstration programme.” Solar
Kruger, E. (2008). “Thermal monitoring and indoor temperature predic- Energy, 81(3), 424–434.
tions in a passive solar building in an arid environment.” Energy Build., Wagner, R., Beisel, S., Spieler, A., Gerber, A., and Vajen, K. (2000).
43(11), 1792–1804. “Measurement, modeling and simulation of an earth-to-air heat
Labs, K., and Cook, J., eds. (1989). Passive cooling, MIT Press, exchanger in Marburg (Germany).” 4th ISES Europe Solar Congress,
Cambridge, MA. International Solar Energy Society, Freiburg, Germany.
Laustsen, J. (2008). “Energy efficiency requirements in building codes, en- Wigginton, M., and Harris, J. (2002). Intelligent skins, Architectural Press,
ergy efficiency policies for new buildings.” International Energy Agency, London.
Paris. Xing, Y., Hewitt, N., and Griffiths, P. (2011). “Zero carbon buildings
MATLAB version R2016a [Computer software]. MathWorks, Natick, MA. refurbishment—A hierarchical pathway.” Renewable Sustainable
Ong, K. S., and Chow, C. C. (2003). “Performance of a solar chimney.” Energy Rev., 15(6), 3229–3236.
Solar Energy, 74(1), 1–17. Yassine, B., Ghali, K., Ghaddar, N., Chehab, G., and Srour, I. (2014).
Peretti, C., Zarrella, A., De Carli, M., and Zecchin, R. (2013). “The design “Effectiveness of the earth tube heat exchanger system coupled to a
and environmental evaluation of earth to-air heat exchangers (EAHE): space model in achieving thermal comfort in rural areas.” Int. J. Sus-
A literature review.” Renewable Sustainable Energy Rev., 28, 107–116. tainable Energy, 33(3), 567–586.
Pfafferott, J. (2004). “Enhancing the design and the operation of passive Yassine, B., Ghali, K., Ghaddar, N., Srour, I., and Chehab, G. (2012). “A
cooling concepts. Monitoring and data analysis in four low-energy of- numerical modeling approach to evaluate efficient mechanical ventila-
fice buildings with night ventilation.” Ph.D. thesis, Univ. of Karlsruhe, tion strategies.” Energy Build., 55, 618–630.
Germany. Yuebin, Y., Haorong, L., Fuxin, N., and Daihong, Y. (2014). “Investigation
Pfafferott, J., Herkel, S., and Wambsganß, M. (2013). “Design, monitoring of a coupled geothermal cooling system with earth tube and solar
and evaluation of a low energy office building with passive cooling by chimney.” Appl. Energy, 114, 209–217.
night ventilation.” Energy Build., 36(5), 455–465. Zhang, H., Arens, E., Huizenga, C., and Han, T. (2010). “Thermal sensation
Republic of Lebanon Ministry of Public Works and Transport. (2005a). and comfort models for non-uniform and transient environments. Part I:
“Climatic zoning for buildings in Lebanon.” United Nations Develop- Local sensation of individual body parts.” Build. Environ., 45(2),
ment Program, Beirut, Republic of Lebanon. 380–388.

© ASCE 04016039-10 J. Energy Eng.

View publication stats J. Energy Eng., 04016039

You might also like