Features Technical Data


• Microprocessor based numerical relay RATINGS
• Current measurement based on Rated current ( In ) : 5A
Rated frequency : 50 Hz

MK204A Overcurrent Relay


fundamental frequency
Burden : < 0.3 VA at In
• Low-set inverse definite time relay (IDT) Thermal withstand : 4 x In continuous

• High-set instantaneous relay AUXILIARY SUPPLY


• Separate low-set and high-set trip Model MK204A-240A : 198 ~ 265 V AC
indicators Model MK204A-110A : 94 ~ 127V AC
Supply frequency : 50 Hz
• Option to disable high-set relay VA rating : 3 VA typical

• Front panel access to test function


SETTING RANGES
• Complies with IEC 60255-26 standard Low-set ( I > ) : 2.0 A to 6.0 A
: 40% to 120%
Time multiplier ( TM ) : 0.05 to 1.0
High-set ( I >> ) : I > to 10 x I > or disable
High-set delay time (t >>) : Instantaneous

CONTACTS
Trip contact (R1) : Manual reset type
Contact Arrangement : Change-over
Contact rating : 5 A, 250 V AC ( cosϕ = 1 )
Contact material : Silver alloy
Expected electrical life : 100,000 operations at
rated current
Expected mechanical life: 5 x 106 operations

INDICATORS
Auxiliary supply : Green indicator
Pick-up : Red indicator
Trip : Red indicator

PERFORMANCE
Adjustable accuracy : Less than ±5%.
Repeatability : Less than 0.5% of full scale.

MECHANICAL
Mounting : Panel mounting
Front panel : Standard DIN
96 mm x 96 mm
Approximate weight : 0.7 kg

ENVIRONMENTAL CONDITIONS
Temperature : -5˚C to +55˚C
Humidity : 56 days at 93% RH and
40˚C non-condensing
TYPICAL APPLICATION DIAGRAM IDT INVERSE

Aux
L N MK 204A t/s
NO NC COM
1 2 3 4 5 6 7 8

R1

9 10 11 12 13 14 15 16 10

L1
MK204A Overcurrent Relay

L2
k
L3
1.0
0.9
N 0.8
0.7
1 0.6
0.5
0.4
0.3

0.2

0.1

0.1
1 10 20 I/I>

COMBINED OVERCURRENT & EARTH FAULT RELAYS

AUX AUX
L N MK 204A L N MK 201A
NO NC COM NO NC COM
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8

R1 R1

9 10 11 12 13 14 15 16 9 10 11 12 13 14 15 16

L1
L2
L3
N

CASE DIMENSIONS
110 mm
96 mm 100 mm 91.0 ± 0.5 mm
91.0 ± 0.5 mm
96 mm

Front Side Panel Cutout

Ordering Information

MODEL DESCRIPTION
MK204A - 240A For 50 Hz system, auxiliary voltage 198 ~ 265 V AC
MK204A - 110A For 50 Hz system, auxiliary voltage 94 ~ 127 V AC