Failure modes
1. Bearing Faults
2. Mechanical Faults (Foundation Looseness, Eccentricity, Misalignment)
3. Rotor Bar
Operating conditions
1. Motor running on load
2. Motor running on no-load
3. Motor not running
External factors
1. Nature of the load on motor
2. Motor power supply
Bearing and Mechanical Faults
1/30/2019 -63.4 -48.9 -51.1 -62.9 -49.4 -51.5 6 1/31/2019 -77.2 -63.2 -66 -80.8 -67.1 -67.1 -13.4 -8.7 -11.9 -17 -13.6 -15.5 6 598
1/30/2019 -63.4 -48.9 -51.1 -62.9 -49.4 -51.5 6 2/1/2019 -70 -54.9 -55.6 -69.7 -55.8 -57 -5.8 -6 -4.5 -6.8 -6.4 -5.5 6 596
1/30/2019 -63.4 -48.9 -51.1 -62.9 -49.4 -51.5 6 2/4/2109 -76.2 -62.3 -60.8 -79.1 -63.5 -64.9 -12.4 -12.5 -8.7 -15.3 -14 -12 6 598
1/30/2019 -63.4 -48.9 -51.1 -62.9 -49.4 -51.5 6 2/5/2019 -71.8 -58.7 -60.1 -72.7 -60 -61.5 -8 -7.3 -7.8 -8.9 -10.7 -10.6 6 599
1/30/2019 -63.4 -48.9 -51.1 -62.9 -49.4 -51.5 6 2/19/2019 -68.5 -52.9 -53 -68 -52.7 -54.3 -3.7 -3.1 -1.9 -3.5 -3.2 -2.8 6 599
Observations
• The changes in the dB values from the Baseline value are less than pickup threshold values at the time of
recording the values
• The last recorded value indicates a reduced margin of the pickup threshold value over the baseline value
Mechanical Fault
MONITO MONITO MONITO MONITO MONITO MONITO
BASELINE BASELINE BASELINE BASELINE BASELINE BASELINE RING RING RING RING RING RING DIFFEREN DIFFEREN DIFFEREN DIFFEREN DIFFEREN DIFFEREN
Mech Mech Mech Mech Mech Mech Mech Mech Mech Mech Mech Mech CE Mech CE Mech CE Mech CE Mech CE Mech CE Mech
Fault - Fault - Fault - Fault - Fault - Fault - Fault - Fault - Fault - Fault - Fault - Fault - Fault - Fault - Fault - Fault - Fault - Fault -
Avg Avg Avg Avg Avg Avg Avg Avg Avg Avg Avg Avg Avg Avg Avg Avg Avg Avg
Time of Norm Norm Norm Energy at Energy at Energy at Time of Norm Norm Norm Energy at Energy at Energy at Norm Norm Norm Energy at Energy at Energy at
Baseline Peak Mag Peak Mag Peak Mag Peak Mag Peak Mag Peak Mag Fault Peak Mag Peak Mag Peak Mag Peak Mag Peak Mag Peak Mag Peak Mag Peak Mag Peak Mag Peak Mag Peak Mag Peak Mag Estimate
computatio @k=1 @k=2 @k=3 @k=1 @k=2 @k=3 Computati @k=1 @k=2 @k=3 @k=1 @k=2 @k=3 @k=1 @k=2 @k=3 @k=1 @k=2 @k=3 d Speed
n (dB) (dB) (dB) (dB) (dB) (dB) Load Bin on (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) (dB) Load Bin (RPM)
1/30/2019 -52.6 -59.5 -62 -53.6 -59.4 -61.9 6 1/31/2019 -67.1 -75.8 -75.7 -72.1 -76.6 -78.4 -14.5 -15.7 -13.6 -18.5 -16.7 -16.9 6 598
1/30/2019 -52.6 -59.5 -62 -53.6 -59.4 -61.9 6 2/1/2019 -59.8 -66.3 -68.5 -61.9 -66.3 -69.6 -6.5 -6.8 -6.5 -7.7 -6.9 -7.7 6 596
1/30/2019 -52.6 -59.5 -62 -53.6 -59.4 -61.9 6 2/4/2109 -65.5 -74 -72.4 -69.2 -75.7 -76.2 -12.8 -13.9 -9.3 -14.7 -15.8 -13.1 6 598
1/30/2019 -52.6 -59.5 -62 -53.6 -59.4 -61.9 6 2/5/2019 -62.4 -68.5 -69.9 -62.8 -69 -71 -9.8 -9 -7.9 -9.2 -9.6 -9.1 6 599
1/30/2019 -52.6 -59.5 -62 -53.6 -59.4 -61.9 6 2/19/2019 -56.1 -63.6 -66.8 -57 -63.2 -66.9 -2.8 -3.5 -3.7 -2.8 -3.3 -3.8 6 599
Observations
• The changes in the dB values from the Baseline value are less than pickup threshold values at the time of
recording the values
• The last recorded value indicates a reduced margin of the pickup threshold value over the baseline value
Conclusions
• Load oscillations
Presence of load oscillations is observed by analyzing the electrical current signatures of the motor
under load and no load conditions
The occurrence of the load oscillations is generally random with respect to time
Harmonics due to load oscillations are spread across the bearing fault and mechanical fault frequency
spectrum
RotorBar - RotorBar -
RotorBar - Load RotorBar - Maximu RotorBar -
RotorBar - Motor Dev. At Maximu m Motor RotorBar -
RotorBar - Compon Load at BRB RotorBar - m Compon Load at Load dev. RotorBar -
Compon ent BRB Calculati Time of Compon ent BRB At BRB Time of
ent level Frequenc calculatio on (x BRB ent level Frequenc maximu Maximu Maximum
Date (dB) y (Hz) n (x FLA) FLA) Calculation (dB) y (Hz) m (x FLA) m (x FLA) BRB
31-Jan -69.8 50.37 0.59 0 1/31/2019 -43.3 50.41 0.57 0.01 1/31/2019
Observation
• The Maximum value of the rotor bar component level is high
~ 9 sec data, Voltage Signal is clean, Current and Va*Ia picks up low frequency load oscillations
GE Internal
Va, Ia and Va* Ia Signal Analysis
13Feb2019_Transient record_03_ no load
~16 Sec, Voltage Signal is clean, Current and Va*Ia picks up low frequency load oscillations
GE Internal
Va, Ia and Va* Ia Signal Analysis
Voltage Harmonics @ Multiple of Fundamental
• The rotor bar component levels are found to be high based on the limited data
available
• The load oscillations found to be influencing the rotor bar pickup values at lower
frequencies (in Va*Ia signal)