You are on page 1of 6

8th International Conference on Renewable Energy Research and Applications Brasov, ROMANIA, Nov.

3-6, 2019

3URWHFWLRQRI6WDQG$ORQH:LQG(QHUJ\&RQYHUVLRQ
6\VWHPXVLQJ%ULGJH7\SH)DXOW&XUUHQW/LPLWHUV
M.Arun Bhaskar, S.Premalatha, Arjun Parameswaran, Subhransu Sekhar Dash
P.Dinesh Electrical Engineering Department, Government College of
Department of EEE, Velammal Engineering College Engineering, Keonjhar, Odisha, India
Chennai, Tamilnadu, India
m.arunbhaskar@gmail.com*, premsbala@gmail.com, munu_dash_2k@yahoo.com
arjunparameswaran1998@gmail.com,
pdinesh2911@gmail.com

Abstract— There is a need to protect large wind farms from voltage is also included to define the operating characteristics
fault conditions. The paper has a wind turbine generator system [14]. For a typical grid connected wind turbine system,
producing power for single phase loads located at different protection was implemented [16]. Protection schemes were
lengths of the transmission lines. In this paper, initially, over implemented on type 1, 2, 3 and 4 wind turbine generator
current relay was used to protect the system. Over current relay systems [17]. Working of relays and positioning of Fault
employs inverse time- current characteristics to perform the Current Reactors is present [18]. The performance of R- type,
tripping operation. Because of relay operation, the current flow is L- type and LR- type SSFCL’s when used in SMIB with an
intermittent in the lines. Further studies were done on to limit the induction generator are studied [1] and these effects on the
fault current magnitude flowing in the circuit. For this purpose,
parameters related to wind power generation are also taken into
Fault Current Limiter was used. Fault Current Limiter consists
of bridge arrangement of diodes and thyristors for normal
consideration. For proper relay co-ordinations, along with
operation. Anti- parallel arrangement of diodes with thyristors FCLs present in the circuit, the relay constraints are calculated
with a reactance limits the fault current magnitude. It was found and by iteration suitable sizes of FCLs are placed at desired
that by using Fault Current Limiter, the fault current magnitude locations [2]. A series transformer- based solid state fault
was reduced by a greater degree. current limiter is used [7] for a double feeder radial distribution
network to limit the fault current. Bridge- type configuration is
Keywords— Wind Energy Conversion Systems, Transmission used along two- feeder network [8] to limit the fault current.
Lines, Fault Current Limiter and Single Phase Loads. Another type of fault current limiter is arranged with LC tank
circuit to limit the fault current [9]. Bridge- type FCL is used to
I. INTRODUCTION ride- through fault in wind turbines and; the effect on voltage
and torque is also considered [15]. Relay co- ordination along
Wind energy is the most sought after form of renewable with FCL implementation when a Distributed Generation is
source of energy for power generation now-a-days. Its added to the existing system is studied [19][20].
magnitude of power generation makes it reliable for large
amount of energy generation. To maintain an uninterrupted In section 1, the construction and principle of operation of
flow of power to the grid system wind farms or rather Bridge type Fault current limiter is explained. Section 2 deals
individual wind mill has to be protected from any kind of with the modelling of the test system containing a stand alone
contingencies. The contingencies normally occur to wind farms WECS coupled to an infinite bus. Also the performance of the
are faults, over voltage, surges and voltage sags. The effects of test system during fault condition is shown with results. In
faults can be effectively eliminated by using Fault Current section 3, the modelling of bridge type FCL in PSCAD is
Limiters (FCLs) to limit the higher magnitude of fault current. shown and also the performance of the Test system with
proposed FCL during fault condition with results are explained.
The construction of Wind Energy Conversion Systems is Section 4, deals with the comparison of results and conlusion.
studied [4]. There arise power quality issues when inter
connecting renewable energy sources to the grid [3].
Protection of grid along with Distributed Generation is II. BRIDGE TYPE FAULT CURRENT LIMITERS
necessary [6] for situations when fault and network
disturbances occur. Protections setting for the wind inter- A. Construction
connected system is discussed [12]. The principle of operating The bridge type Fault Current Limiter is connected to the
over current relay is studied [5]. The existing relay co- Power Grid through a coupling Transformer. The star
ordination techniques are briefly dealt [13]. For the proper connected secondary windings (Ta, Tb, Tc) of the coupling
operation of relays, a defined operating of relays, a defined Transformer is connected with a Discharging Resistor (R) and
operating time and time dial settings are presented [11]. With a DC Reactor (Ld). The discharging resistor is connected in
dual setting for an over current relay, protection is performed parallel with a semiconductor switch (T).
[10]. Apart from current and time in operating characteristics,

ICRERA 2019 ‹,((( 892

Authorized licensed use limited to: Auckland University of Technology. Downloaded on June 03,2020 at 03:53:01 UTC from IEEE Xplore. Restrictions apply.
8th International Conference on Renewable Energy Research and Applications Brasov, ROMANIA, Nov. 3-6, 2019

unit speed, the slip to the machine until the simulation time and
the electrical torque as a negated value of mechanical torque.
The generation is taking place at a voltage level of 110 kV at a
frequency of 60 Hz. The power factor of the machine is 0.85,
efficiency at rated load is 0.985 per unit and the full load slip is
0.015 per unit. The data are based on EMTP type 40 in
PSCAD.

Fig. 1. Bridge Type Fault Current Limiter.

Fig. 3. Modelled Wind Energy Conversion System

An excitation voltage of 120kV is provided from a voltage


source to the machine. The rated apparent power of the
machine is 1kVA.

IV. TEST SYSTEM


Fig. 2. DC Reactor current, Terminal Voltage and Fault Current
The performance of the proposed bridge type FCL can be
The effect of bridge type Fault current limiter with tested using the system shown in Figure 3. The single line
discharging resistor during normal and fault condition in the diagram of the test system consists of a stand alone WECS
Fault current, Terminal Voltage and DC reactor current values connected to the Power Grid through a bridge type FCL.
is shown in Figure 2.
In normal operating mode, the values of DC reactor current
and terminal voltages are zero. This is due to the bypassing of
discharging resistor when the semiconductor switch (T) is
closed. Therefore, the impedance seen by the primary side of
the coupling transformer is very less.
During the fault mode, there are two operating states. In the
first state, the DC reactor current values are controlled by the
switching periods. Hence the DC reactor current value is Fig. 4. Single Line Diagram of Test System
maintained at i1. During the second state, the DC reactor
current magnitude will increase to i2 and terminal voltage V. SEQUENCE FOR BREAKER TRIPPING
reaches V2. To maintain the DC reactor current at a prescribed
level, the controller absorbs the energy of the DC reactor by In PSCAD, an inverse time over current relay block is
adjusting the switching periods. In turn the terminal voltage present. The input signal is the current and the output signal is
can also be maintained at a predetermined level. the trip signal to the breaker. The relay is set with a pick- up
current of 30 Amperes with a time dial setting of 0.01 second.
The type of curve used in this relay is IEEE Std.C37.112 and
III. WIND ENERGY CONVERSION SYSTEM the type of characteristics is standard inverse. The sequence of
Wind turbine employed here is a horizontal axis type rotor breaker tripping and subsequent re-closure for the three phases
with a three-blade system. The mechanical speed of the turbine is shown in figure 5.
is dictated by the number of pole pairs present. In this case a 5-
pole pair is chosen to meet out the rated power. The turbine is The generator feeds the loads at 110kV and at 60 Hz
set to generate 3 MVA power. frequency. The generator is excited by means of a voltage
source supplying a 1kVA reactive power. Each transmission
The generator used here is squirrel cage induction line is separately modelled as a single-phase line using
generator. This is particularly useful for fixed speed Bergeron model. The line length of phase A is 9 kilometres
application. For simulation, the inputs to the turbine are the per where a single-phase load of 1 Mega Watt is connected. The

ICRERA 2019 893

Authorized licensed use limited to: Auckland University of Technology. Downloaded on June 03,2020 at 03:53:01 UTC from IEEE Xplore. Restrictions apply.
8th International Conference on Renewable Energy Research and Applications Brasov, ROMANIA, Nov. 3-6, 2019

line length of phase B is 6 kilometres where a single-phase


load of 0.5 Mega Watt rating is connected. The line length of
phase C is 7 kilometres where a single-phase load of 1 Mega
Watt rating is connected.

Fig. 8. Breaker A tripping time

During the initial operation in phase B, the load current is


15.5 amperes. When the fault occurs at 3.5 seconds in phase B,
the current rises to 11.8142 kilo amperes. The relay senses the
fault and trips the breaker at 3.5049 seconds and recloses at
3.705 seconds. Phase B fault current waveform is shown in
figure 9. After the breaker is reclosed, the normal operation is
Fig. 5. Sequence for tripping the breaker restored. The breaker tripping instant is shown in figure 10.

Fig. 9. Phase B fault current waveform


Fig. 6. Real power generated by the wind turbine in per unit

Here, the real power is generated as 0.89 per unit. So, with
the rated 3 MVA power, the real power produced is 2.67 MW
as shown in figure 6.A single breaker scheme is utilized here
since it is a radial system. Only, single lines to ground faults
are created. The duration of fault is 0.2 seconds.
During the initial operation in phase A, the load current is
30 amperes. When the fault occurs at 3 seconds for phase A,
the current rises to 14.9613 kilo amperes. The relay senses the
fault and trips the breaker at 3.0065 seconds and recloses at
3.29 seconds. Phase A fault current waveform is shown in
figure 7. After the breaker is reclosed, the normal operation is Fig. 10. Breaker B tripping time
restored. The tripping instant of breaker is shown in figure 8.
During the initial operation in phase C, the load current is
30 amperes. When the fault occurs at 4 seconds in phase C, the
current rises to 4.1842 kilo amperes. The relay senses the fault
and trips the breaker at 4.0050 seconds and recloses at 4.2146
seconds. Phase C fault current waveform is shown in figure 11.
After the breaker is reclosed, the normal operation is restored.

Fig. 7. Phase A fault current waveform

ICRERA 2019 894

Authorized licensed use limited to: Auckland University of Technology. Downloaded on June 03,2020 at 03:53:01 UTC from IEEE Xplore. Restrictions apply.
8th International Conference on Renewable Energy Research and Applications Brasov, ROMANIA, Nov. 3-6, 2019

The simulation diagram along with Fault Current


Limiters is shown in figure 14.

Fig. 11. Phase C fault current waveform

Fig. 14. Simulation diagram of WECS with Fault Current Limiter

Pulse Width Modulation for firing the thyristors in Bridge-


Fig. 12. Breaker C tripping time type Fault Current Limiter
To generate PWM pulses, the comparison is made between
VI. BRIDGE- TYPE FAULT CURRENT LIMITERS the reference signal which is the current quantity in this case
The model for bridge- type fault current limiter is taken and the carrier signal. The carrier signal is produced as a
from [8] and is shown in figure 13. Diodes 1 with thyristor 3 multiple of the reference frequency which is 60 Hertz. The
and diode 2 with thyristor 4 form the rectifier bridge feeding rotary switch present, as is seen in the figure 15 consists of five
the inductor with DC current. During fault operation, the steps representing the dominant harmonic numbers 5, 7, 9, 11
thyristors 3 and 4 are blocked. Thyristors 1 and 2 along with and 13. Any harmonic number can be chosen to be multiplied
diodes 1 and 2 form a short- circuit thereby rendering the with the reference frequency. The comparator compares these
reactance to carry the fault current which is the AC current. two values. When A>B, that is the reference signal has gone
The current is thus reduced to some suitable magnitude. The beyond the magnitude of carrier signal, the comparator fires the
reduction in the fault current is done by the inductor present in thyristors 1 and 2 to turn- on to reduce the magnitude of fault
the circuit. The inductor values are varied to reduce the fault current and, thyristors 3 and 4 are turned off. When A<B, the
current effectively. thyristors 1 and 2 remain in the off- state and, thyristors 3 and 4
remain in operation supplying DC current to the reactor.
G3a

For phase A, the inductance value placed in the bridge-


G3a

type FCL is 0.9 Henry. The reference signal is the measured


current quantity and the carrier frequency is a multiple of fifth
harmonic. The thyristor firing arrangement for phase A is
D1a

D2a

0.9 [H]
Iaf shown in figure 15. Similar arrangements follow for phase B
IinA
G1a G2a
IoutA
and phase C. For phase B, inductance value is 0.6 Henry and
the carrier frequency is a fifth order harmonic multiple. For
G1a

G2a

phase C, the inductance is 0.9 Henry and the carrier frequency


is a multiple of thirteenth harmonic.
G4a
G4a

Fig. 13. Typical set-up of Bridge-type Fault Current Limiter in PSCAD

ICRERA 2019 895

Authorized licensed use limited to: Auckland University of Technology. Downloaded on June 03,2020 at 03:53:01 UTC from IEEE Xplore. Restrictions apply.
8th International Conference on Renewable Energy Research and Applications Brasov, ROMANIA, Nov. 3-6, 2019

Fig. 18. Gating pulses for thyristor 3 in phase A

Fig. 15. PWM generation and subsequent generation of pulses for the
thyristors of phase A

The pulses produced due to Pulse Width Modulation


technique for thyristors 1, 2, 3 and 4 in phase A are shown in
figures 16, 17, 18 and 19 respectively.

Fig. 19. Gating pulses for thyristor 4 in phase A

The phase A current waveform after introducing Fault


Current Limiters to the circuit is shown in figure 20.

Fig. 16. Gating pulses for thyristor 1 in phase A

Fig. 20. Phase A current waveform

Fig. 17. Gating pulses for thyristor 2 in phase A

ICRERA 2019 896

Authorized licensed use limited to: Auckland University of Technology. Downloaded on June 03,2020 at 03:53:01 UTC from IEEE Xplore. Restrictions apply.
8th International Conference on Renewable Energy Research and Applications Brasov, ROMANIA, Nov. 3-6, 2019

TABLE I. COMPARISON TABLE FOR FAULT CURRENT MAGNITUDE BY [4] B.H. Khan, Non-conventional Energy Resources, Tata McGraw-Hill
IMPLEMENTING FAULT CURRENT LIMITER USING DIFFERENT CONTROL Publishing Company Limited, New Delhi, pp. 186.
STRATEGIES
[5] Badri Ram and D. N. Vishwakarma (2001), Power System Protection
Fault Fault Current Fault Current and Switchgear, Tata McGraw-Hill Publishing Company Limited, New
Current Magnitude Magnitude after using Delhi, pp. 68-77.
Phases (kA) FCL Block (kA) [6] Fuchs R. (2004, April), Protection schemes for decentralized power
PHASE A 15.40 kA 1.877 kA generation, IET Eighth IEEE International Conference on In
Developments in Power System Protection 1: 323-326.
PHASE B 12.50 kA 4.0435 kA [7] Hamid Radmanesh, Hamid Fathi, Gevork B. Gharehpetian (2015),
Series Transformer-Based Solid State Fault Current Limiter, IEEE
PHASE C 4.20 kA 2.945 kA Transactions on Smart Grid 6:.1983 -1991.
When using Fault Current Limiters to reduce the magnitude [8] Hamid Radmanesh, Seyed Hamid Fathi, G. B. Gharehpetian and Amir
of fault current during fault instances, the fault current was Heidary (2016), Bridge-Type Solid-State Fault Current Limiter Based on
AC/DC Reactor, IEEE Transactions on Power Delivery 31: 200 - 209.
found to be reduced to a considerable value. By utilizing Fault
Ride Through technique, the fault current was drastically [9] Hamid Radmanesh, S. H. Fathi, G. B. Gharehpetian and Amir Heidary
(2016), A Novel Solid-State Fault Current-Limiting Circuit Breaker for
reduced to that of the load current value. Medium-Voltage Network Applications, IEEE Transactions on Power
Delivery 31: 236 - 244.
VII. CONCLUSION [10] H. H. Zeineldin, Hebatallah M. Sharaf, Doaa K. Ibrahim and Essam El-
Din Abou El-Zahab (2015), Optimal Protection Co-ordination for
In this paper, a bridge type FCL is modelled and the Meshed Distribution Systems with DG using Dual Setting Directional
performance of the proposed FCL is tested with a standalone Over-Current Relays, IEEE Transactions on Smart Grid 6(1): 115-123.
WECS coupled to a power grid. Based on the simulation [11] Hebatallah Mohamed Sharaf, H.H. Zeineldin, Doaa Khalil Ibrahim,
results performed in PSCAD, the following conclusions can be Essam EL-Din Abou EL-Zahab (2015), A proposed coordination
drawn: strategy for meshed distribution systems with DG considering user-
defined characteristics of directional inverse time over current relays,
The DC reactor in the fault current limiter can limit the Electrical Power and Energy Systems 65:49–58.
increase in fault during the instance of fault. It also prevents the [12] Hornak D. and Chau N. H. J. (2004), Green power-wind generated
sudden voltage drop during fault instances. protection and control considerations, 57th Annual Conference for
Protective Relay Engineers, pp. 110-131.
It also reduces the [13] Hussain M. H., Rahim S. R. A. and Musirin I. (2013), Optimal Over
Current Relay Coordination: A Review, Procedia Engineering 53: 332-
1) During the fault condition, the increment of the fault 336.
current is limited by dc reactor without any delay and [14] Khaled A. Saleh, H.H. Zeineldin, A. Al-Hinai and Ehab F. El-Saadany
smoothing the surge current waveform and prevention from (2014), Optimal Coordination of Directional Overcurrent Relays Using a
instantaneously deep voltage drop during fault. New Time–Current–Voltage Characteristic, IEEE Transactions on
Power Delivery 30(2): 537 – 544.
2) Then, by controlling the duration of ON and OFF [15] M. Firouzi and G. B. Gharehpetian (2013), Improving Fault Ride-
periods of semiconductor switch generates a controllable Through Capability of Fixed-Speed Wind Turbine by Using Bridge-
resistor in order to control the terminal voltage of IG at Type Fault Current Limiter, IEEE Transactions on Energy Conversion
28: 361- 369.
threshold value during fault, which causes reducing the rotor
[16] Nima Rezaei, Mohammad Lutfi Othman, Noor Izzri Abdul Wahab,
acceleration and stabilizing the system by consuming the dc Hashim Hizam (2014), Co-ordination of Overcurrent Relays Protection
reactor energy over limiting fault current in acceptable level. Systems for Wind Power Plants, IEEE International Conference on
Power and Energy (PECon), pp. 394-399.
3) The simulation results shows that the bridge-type FCL is
[17] Qureshi W. A. and Nair N. K. C. (2014), Wind Farm Protection in Large
more effective for enhancement of FRT capability Scale Renewable Power Generation, Springer Singapore, pp. 311-329.
[18] Marwan Rosyadi, S. M. Muyeen, Rion Takahashi, Junji Tamura, Fuzzy-
REFERENCES PI Controller Design for PM Wind Generator to Improve Fault Ride
Through of Wind Farm, International Journal of Renewable Energy
[1] Alireza R. Fereidouni, Behrooz Vahidi, Senior Member, IEEE, and
Research, 3(2), 2013
Tahoura Hosseini Mehr (2013), The Impact of Solid State Fault Current
Limiter on Power Network with Wind-Turbine Power Generation, IEEE [19] Takwa sellami, Hanen berriri, Sana jelassi, Abdel moumen darcherif,
Transactions on Smart Grid 4: 1188 -1196. Med faouizi mimouni, Performance Analysis of Grid-Connected Wind
Turbine System Under Inter-Turn-Short-Circuit Fault Conditions,
[2] A.Elmitwally, E. Gouda, S. Eladawy (2015), Optimal allocation of fault
International Journal of Renewable Energy Research, 8(1), 2018.
current limiters for sustaining overcurrent relays coordination in a power
system with distributed generation, Alexandria Engineering Journal [20] Walid El-Khattam and Tarlochan S. Sidhu (2008), Restoration of
54(4): 1077-1089, doi: 10.1016/j.aej.2015.06.009 Directional Over Current Relay Coordination in Distributed Generation
Systems Utilizing Fault Current Limiter, IEEE Transactions on Power
[3] Alaa Mohd, Egon Ortjohann, Andreas Schmelter, Nedzad Hamsic and
Delivery 23(2): 576-585.
Danny Morton (2008), Challenges in integrating distributed energy
storage systems into future smart grid, IEEE International Symposium
on Industrial Electronics, ISIE, pp. 1627-1632.

ICRERA 2019 897

Authorized licensed use limited to: Auckland University of Technology. Downloaded on June 03,2020 at 03:53:01 UTC from IEEE Xplore. Restrictions apply.

You might also like