Professional Documents
Culture Documents
3-6, 2019
3URWHFWLRQRI6WDQG$ORQH:LQG(QHUJ\&RQYHUVLRQ
6\VWHPXVLQJ%ULGJH7\SH)DXOW&XUUHQW/LPLWHUV
M.Arun Bhaskar, S.Premalatha, Arjun Parameswaran, Subhransu Sekhar Dash
P.Dinesh Electrical Engineering Department, Government College of
Department of EEE, Velammal Engineering College Engineering, Keonjhar, Odisha, India
Chennai, Tamilnadu, India
m.arunbhaskar@gmail.com*, premsbala@gmail.com, munu_dash_2k@yahoo.com
arjunparameswaran1998@gmail.com,
pdinesh2911@gmail.com
Abstract— There is a need to protect large wind farms from voltage is also included to define the operating characteristics
fault conditions. The paper has a wind turbine generator system [14]. For a typical grid connected wind turbine system,
producing power for single phase loads located at different protection was implemented [16]. Protection schemes were
lengths of the transmission lines. In this paper, initially, over implemented on type 1, 2, 3 and 4 wind turbine generator
current relay was used to protect the system. Over current relay systems [17]. Working of relays and positioning of Fault
employs inverse time- current characteristics to perform the Current Reactors is present [18]. The performance of R- type,
tripping operation. Because of relay operation, the current flow is L- type and LR- type SSFCL’s when used in SMIB with an
intermittent in the lines. Further studies were done on to limit the induction generator are studied [1] and these effects on the
fault current magnitude flowing in the circuit. For this purpose,
parameters related to wind power generation are also taken into
Fault Current Limiter was used. Fault Current Limiter consists
of bridge arrangement of diodes and thyristors for normal
consideration. For proper relay co-ordinations, along with
operation. Anti- parallel arrangement of diodes with thyristors FCLs present in the circuit, the relay constraints are calculated
with a reactance limits the fault current magnitude. It was found and by iteration suitable sizes of FCLs are placed at desired
that by using Fault Current Limiter, the fault current magnitude locations [2]. A series transformer- based solid state fault
was reduced by a greater degree. current limiter is used [7] for a double feeder radial distribution
network to limit the fault current. Bridge- type configuration is
Keywords— Wind Energy Conversion Systems, Transmission used along two- feeder network [8] to limit the fault current.
Lines, Fault Current Limiter and Single Phase Loads. Another type of fault current limiter is arranged with LC tank
circuit to limit the fault current [9]. Bridge- type FCL is used to
I. INTRODUCTION ride- through fault in wind turbines and; the effect on voltage
and torque is also considered [15]. Relay co- ordination along
Wind energy is the most sought after form of renewable with FCL implementation when a Distributed Generation is
source of energy for power generation now-a-days. Its added to the existing system is studied [19][20].
magnitude of power generation makes it reliable for large
amount of energy generation. To maintain an uninterrupted In section 1, the construction and principle of operation of
flow of power to the grid system wind farms or rather Bridge type Fault current limiter is explained. Section 2 deals
individual wind mill has to be protected from any kind of with the modelling of the test system containing a stand alone
contingencies. The contingencies normally occur to wind farms WECS coupled to an infinite bus. Also the performance of the
are faults, over voltage, surges and voltage sags. The effects of test system during fault condition is shown with results. In
faults can be effectively eliminated by using Fault Current section 3, the modelling of bridge type FCL in PSCAD is
Limiters (FCLs) to limit the higher magnitude of fault current. shown and also the performance of the Test system with
proposed FCL during fault condition with results are explained.
The construction of Wind Energy Conversion Systems is Section 4, deals with the comparison of results and conlusion.
studied [4]. There arise power quality issues when inter
connecting renewable energy sources to the grid [3].
Protection of grid along with Distributed Generation is II. BRIDGE TYPE FAULT CURRENT LIMITERS
necessary [6] for situations when fault and network
disturbances occur. Protections setting for the wind inter- A. Construction
connected system is discussed [12]. The principle of operating The bridge type Fault Current Limiter is connected to the
over current relay is studied [5]. The existing relay co- Power Grid through a coupling Transformer. The star
ordination techniques are briefly dealt [13]. For the proper connected secondary windings (Ta, Tb, Tc) of the coupling
operation of relays, a defined operating of relays, a defined Transformer is connected with a Discharging Resistor (R) and
operating time and time dial settings are presented [11]. With a DC Reactor (Ld). The discharging resistor is connected in
dual setting for an over current relay, protection is performed parallel with a semiconductor switch (T).
[10]. Apart from current and time in operating characteristics,
Authorized licensed use limited to: Auckland University of Technology. Downloaded on June 03,2020 at 03:53:01 UTC from IEEE Xplore. Restrictions apply.
8th International Conference on Renewable Energy Research and Applications Brasov, ROMANIA, Nov. 3-6, 2019
unit speed, the slip to the machine until the simulation time and
the electrical torque as a negated value of mechanical torque.
The generation is taking place at a voltage level of 110 kV at a
frequency of 60 Hz. The power factor of the machine is 0.85,
efficiency at rated load is 0.985 per unit and the full load slip is
0.015 per unit. The data are based on EMTP type 40 in
PSCAD.
Authorized licensed use limited to: Auckland University of Technology. Downloaded on June 03,2020 at 03:53:01 UTC from IEEE Xplore. Restrictions apply.
8th International Conference on Renewable Energy Research and Applications Brasov, ROMANIA, Nov. 3-6, 2019
Here, the real power is generated as 0.89 per unit. So, with
the rated 3 MVA power, the real power produced is 2.67 MW
as shown in figure 6.A single breaker scheme is utilized here
since it is a radial system. Only, single lines to ground faults
are created. The duration of fault is 0.2 seconds.
During the initial operation in phase A, the load current is
30 amperes. When the fault occurs at 3 seconds for phase A,
the current rises to 14.9613 kilo amperes. The relay senses the
fault and trips the breaker at 3.0065 seconds and recloses at
3.29 seconds. Phase A fault current waveform is shown in
figure 7. After the breaker is reclosed, the normal operation is Fig. 10. Breaker B tripping time
restored. The tripping instant of breaker is shown in figure 8.
During the initial operation in phase C, the load current is
30 amperes. When the fault occurs at 4 seconds in phase C, the
current rises to 4.1842 kilo amperes. The relay senses the fault
and trips the breaker at 4.0050 seconds and recloses at 4.2146
seconds. Phase C fault current waveform is shown in figure 11.
After the breaker is reclosed, the normal operation is restored.
Authorized licensed use limited to: Auckland University of Technology. Downloaded on June 03,2020 at 03:53:01 UTC from IEEE Xplore. Restrictions apply.
8th International Conference on Renewable Energy Research and Applications Brasov, ROMANIA, Nov. 3-6, 2019
D2a
0.9 [H]
Iaf shown in figure 15. Similar arrangements follow for phase B
IinA
G1a G2a
IoutA
and phase C. For phase B, inductance value is 0.6 Henry and
the carrier frequency is a fifth order harmonic multiple. For
G1a
G2a
Authorized licensed use limited to: Auckland University of Technology. Downloaded on June 03,2020 at 03:53:01 UTC from IEEE Xplore. Restrictions apply.
8th International Conference on Renewable Energy Research and Applications Brasov, ROMANIA, Nov. 3-6, 2019
Fig. 15. PWM generation and subsequent generation of pulses for the
thyristors of phase A
Authorized licensed use limited to: Auckland University of Technology. Downloaded on June 03,2020 at 03:53:01 UTC from IEEE Xplore. Restrictions apply.
8th International Conference on Renewable Energy Research and Applications Brasov, ROMANIA, Nov. 3-6, 2019
TABLE I. COMPARISON TABLE FOR FAULT CURRENT MAGNITUDE BY [4] B.H. Khan, Non-conventional Energy Resources, Tata McGraw-Hill
IMPLEMENTING FAULT CURRENT LIMITER USING DIFFERENT CONTROL Publishing Company Limited, New Delhi, pp. 186.
STRATEGIES
[5] Badri Ram and D. N. Vishwakarma (2001), Power System Protection
Fault Fault Current Fault Current and Switchgear, Tata McGraw-Hill Publishing Company Limited, New
Current Magnitude Magnitude after using Delhi, pp. 68-77.
Phases (kA) FCL Block (kA) [6] Fuchs R. (2004, April), Protection schemes for decentralized power
PHASE A 15.40 kA 1.877 kA generation, IET Eighth IEEE International Conference on In
Developments in Power System Protection 1: 323-326.
PHASE B 12.50 kA 4.0435 kA [7] Hamid Radmanesh, Hamid Fathi, Gevork B. Gharehpetian (2015),
Series Transformer-Based Solid State Fault Current Limiter, IEEE
PHASE C 4.20 kA 2.945 kA Transactions on Smart Grid 6:.1983 -1991.
When using Fault Current Limiters to reduce the magnitude [8] Hamid Radmanesh, Seyed Hamid Fathi, G. B. Gharehpetian and Amir
of fault current during fault instances, the fault current was Heidary (2016), Bridge-Type Solid-State Fault Current Limiter Based on
AC/DC Reactor, IEEE Transactions on Power Delivery 31: 200 - 209.
found to be reduced to a considerable value. By utilizing Fault
Ride Through technique, the fault current was drastically [9] Hamid Radmanesh, S. H. Fathi, G. B. Gharehpetian and Amir Heidary
(2016), A Novel Solid-State Fault Current-Limiting Circuit Breaker for
reduced to that of the load current value. Medium-Voltage Network Applications, IEEE Transactions on Power
Delivery 31: 236 - 244.
VII. CONCLUSION [10] H. H. Zeineldin, Hebatallah M. Sharaf, Doaa K. Ibrahim and Essam El-
Din Abou El-Zahab (2015), Optimal Protection Co-ordination for
In this paper, a bridge type FCL is modelled and the Meshed Distribution Systems with DG using Dual Setting Directional
performance of the proposed FCL is tested with a standalone Over-Current Relays, IEEE Transactions on Smart Grid 6(1): 115-123.
WECS coupled to a power grid. Based on the simulation [11] Hebatallah Mohamed Sharaf, H.H. Zeineldin, Doaa Khalil Ibrahim,
results performed in PSCAD, the following conclusions can be Essam EL-Din Abou EL-Zahab (2015), A proposed coordination
drawn: strategy for meshed distribution systems with DG considering user-
defined characteristics of directional inverse time over current relays,
The DC reactor in the fault current limiter can limit the Electrical Power and Energy Systems 65:49–58.
increase in fault during the instance of fault. It also prevents the [12] Hornak D. and Chau N. H. J. (2004), Green power-wind generated
sudden voltage drop during fault instances. protection and control considerations, 57th Annual Conference for
Protective Relay Engineers, pp. 110-131.
It also reduces the [13] Hussain M. H., Rahim S. R. A. and Musirin I. (2013), Optimal Over
Current Relay Coordination: A Review, Procedia Engineering 53: 332-
1) During the fault condition, the increment of the fault 336.
current is limited by dc reactor without any delay and [14] Khaled A. Saleh, H.H. Zeineldin, A. Al-Hinai and Ehab F. El-Saadany
smoothing the surge current waveform and prevention from (2014), Optimal Coordination of Directional Overcurrent Relays Using a
instantaneously deep voltage drop during fault. New Time–Current–Voltage Characteristic, IEEE Transactions on
Power Delivery 30(2): 537 – 544.
2) Then, by controlling the duration of ON and OFF [15] M. Firouzi and G. B. Gharehpetian (2013), Improving Fault Ride-
periods of semiconductor switch generates a controllable Through Capability of Fixed-Speed Wind Turbine by Using Bridge-
resistor in order to control the terminal voltage of IG at Type Fault Current Limiter, IEEE Transactions on Energy Conversion
28: 361- 369.
threshold value during fault, which causes reducing the rotor
[16] Nima Rezaei, Mohammad Lutfi Othman, Noor Izzri Abdul Wahab,
acceleration and stabilizing the system by consuming the dc Hashim Hizam (2014), Co-ordination of Overcurrent Relays Protection
reactor energy over limiting fault current in acceptable level. Systems for Wind Power Plants, IEEE International Conference on
Power and Energy (PECon), pp. 394-399.
3) The simulation results shows that the bridge-type FCL is
[17] Qureshi W. A. and Nair N. K. C. (2014), Wind Farm Protection in Large
more effective for enhancement of FRT capability Scale Renewable Power Generation, Springer Singapore, pp. 311-329.
[18] Marwan Rosyadi, S. M. Muyeen, Rion Takahashi, Junji Tamura, Fuzzy-
REFERENCES PI Controller Design for PM Wind Generator to Improve Fault Ride
Through of Wind Farm, International Journal of Renewable Energy
[1] Alireza R. Fereidouni, Behrooz Vahidi, Senior Member, IEEE, and
Research, 3(2), 2013
Tahoura Hosseini Mehr (2013), The Impact of Solid State Fault Current
Limiter on Power Network with Wind-Turbine Power Generation, IEEE [19] Takwa sellami, Hanen berriri, Sana jelassi, Abdel moumen darcherif,
Transactions on Smart Grid 4: 1188 -1196. Med faouizi mimouni, Performance Analysis of Grid-Connected Wind
Turbine System Under Inter-Turn-Short-Circuit Fault Conditions,
[2] A.Elmitwally, E. Gouda, S. Eladawy (2015), Optimal allocation of fault
International Journal of Renewable Energy Research, 8(1), 2018.
current limiters for sustaining overcurrent relays coordination in a power
system with distributed generation, Alexandria Engineering Journal [20] Walid El-Khattam and Tarlochan S. Sidhu (2008), Restoration of
54(4): 1077-1089, doi: 10.1016/j.aej.2015.06.009 Directional Over Current Relay Coordination in Distributed Generation
Systems Utilizing Fault Current Limiter, IEEE Transactions on Power
[3] Alaa Mohd, Egon Ortjohann, Andreas Schmelter, Nedzad Hamsic and
Delivery 23(2): 576-585.
Danny Morton (2008), Challenges in integrating distributed energy
storage systems into future smart grid, IEEE International Symposium
on Industrial Electronics, ISIE, pp. 1627-1632.
Authorized licensed use limited to: Auckland University of Technology. Downloaded on June 03,2020 at 03:53:01 UTC from IEEE Xplore. Restrictions apply.