Ansaldo Sistemi Industriali SpA Silcovert S

Description • Power factor control (motor and net) ground insulation. The internal closed-loop
liquid circuit is cooled by a secondary heat
A high-speed CPU manages the control
The Silcovert S is composed of a DC exchanger, either liquid to air or liquid to
functions, based on sophisticated
rectifier section, DC link and AC inverter. water. For lower power ratings, where
algorithms, in order to obtain high static
converter generated heat is less
The rectifier consists of a thyristor and dynamic performances.
significant, the Silcovert S uses forced air-
controlled Graetz bridge, converting AC to
A diagnostic system and flexible operator cooling.
DC and regulating the current on a DC
interface provide user-friendly control. The
link. The inverter section is a thyristor The converter can be supplied with a
operator can check the status of the drive
bridge, identical to the rectifier, which is redundant semiconductor (n+1) in each
through menu-organized diagnostics. This
commutated by the motor. It converts DC leg of the bridges. The advantage is
feature provides detailed fault analysis,
to variable frequency AC by feeding the increased drive reliability and availability.
assistance in troubleshooting and displays
current into the stator windings at the If a fault occurs to one semiconductor
any critical occurring waveform.
frequency requested by the motor. (short circuit) the drive continues
operating at nominal full power, with no
The Inverter is always locked to the motor
derating.
frequency by an encoder or voltage
feedback.
Variable Frequency Drive Any emergency maintenance is simple
VFD’s normally include the exciter
System enough to be carried out on site. A special
clamping system facilitates the
converter for the motor field. Two types The VFD system can be air or water- replacement of semiconductors, without
are available: an AC to DC rectifier for cooled and uses large semiconductors (up dismantling the complete stack assembly.
slip-ring motors or a three-phase AC to 100 mm silicon diameter and 7,5 kV
chopper for machines with brushless blocking voltage). Both solutions provide a
excitation. compact design. The water-cooled system
The drive control module is based on new significantly reduces ventilation and air Drive configuration
microprocessor technology with the conditioning costs for high power The Silcovert S drive is available in four
following functions: applications. Deionised water (mixed with basic configurations: six to six-pulse,
glycol in low temperature applications) twelve to six-pulse, twenty-four to twelve-
• Speed regulation passes through the heat sinks of the pulse or twelve to twelve-pulse.
power semiconductors; where low thermal
• Motoring and braking torque limitation
impedance is achieved, granting high

6/6 pulse

24/12 pulse 12/6 pulse

Some examples of available configurations

For further information: www.asiansaldo.com Page 2 of 4


Ansaldo Sistemi Industriali SpA Silcovert S

Air-cooled Converter

Air-cooled LCI

Control Board

Air-cooled (enclosed)

Control Rack

Water-cooled Thyristor Stack

Control Card

Water-cooled DC-link Reactor

For further information: www.asiansaldo.com Page 3 of 4


Ansaldo Sistemi Industriali SpA Silcovert S

Overall Parameters
LCI DRIVE
OUTPUT
PULSES COOLING IDC Approx. Dim. (L x W x H) Approx. Weight
POWER
(kW) Line Side Mot. Side A/W Amps mm (kg)
2500 12 6 A 1470 (4000 x 1600 x 2700) 6500
5000 12 6 A 1140 (4000 x 1600 x 2700) 6500
2 x 5000 12 12 A 1370 (5000 x 1600 x 2700) 9100
2 x 7500 12 12 A 2x1550 (7000 x 1600 x 2700) 10400
2 x 10000 12 12 A 2x1900 (7000 x 1600 x 2700) 10400
2 x 15000 12 12 W 2x2700 2 x (7000 x 1600 x 2700) 18150
2 x 20000 12 12 W 2x3500 2 x (8000 x 1600 x 2700) 20750

SOFT STARTER APPLICATION

OUTPUT
PULSES COOLING IDC Approx. Dim. (L x W x H) Approx. Weight
POWER
(kW) Line Side Mot. Side A/W Amps mm (kg)
1500 6 6 A 1000 (3000 x 1600 x 2300) 3900
2 x 750 12 6 A 1000 (3000 x 1600 x 2300) 3900
3000 6 6 A 2000 (3000 x 1600 x 2300) 5200
2 x 1500 12 6 A 2000 (3000 x 1600 x 2300) 5200
3000 6 6 A 1000 (3000 x 1600 x 2300) 5200
2 x 1500 12 6 A 1000 (3000 x 1600 x 2300) 5200
5000 6 6 A 1670 (3000 x 1600 x 2300) 6500
2 x 2500 12 6 A 1670 (3000 x 1600 x 2300) 6500
7500 6 6 A 1670 (4000 x 1600 x 2300) 6500
10000 6 6 W 2080 (8000 x 1600 x 2300) 9000

2 x 5000 12 6 W 2080 (8000 x 1600 x 2300) 9000

SOFT STARTER APPLICATION – Container solution


OUTPUT
PULSES COOLING IDC Approx. Dim. (L x W x H) Notes
POWER
(kW) Line Side Mot. Side A/W Amps mm

1500 6 6 A
1000
2 x 750 12 6 A (6055 x 2438 x 2900)
19 ft Container
5000 6 6 A
1670
2 x 2500 12 12 A
10000 6 6 W 25 ft Container
2080 (7620 x 2438 x 2900)
2 x 5000 12 6 W Redundant Pumps

Technical Features
Drive Silcovert S
Drive Type AC/AC converter
Power Rating 1 to 40 MW
Input Supply Voltage 3-phase 900V to 6000V ± 10% (higher voltages for special applications)
Input Frequency 50 Hz or 60 Hz ± 2%
Output Frequency 0 to 120 Hz
Configuration 6/12/24-pulse
Redundancy n+1 thyristor (optional)
Speed Control Closed loop (Encoder) or Sensorless Configuration
Typical service factor 1.0
Efficiency ≥98,5 % @rated power
Cooling Method Forced-air or de-ionized water
Converter Enclosure IP31 (higher protection degrees on request)
Noise Level <80 dB (A)
Reference Standard IEC, NEMA for overload
Protections Motor on incoming line over-current, differential-current, over-voltage
or unde-voltage (network side), over-voltage (motor side), ventilation fault,
reactance over-temperature, ground fault
Automation Connection Profibus™, Modbus™

For further information: www.asiansaldo.com Page 4 of 4