x Also, it was noticed that UV-114066 valve showed some sudden movement with a fixed valve command.
See Figure 2
x It was noticed that valve UV-114066 showed a lot of friction 50% and above. See Figure 3.
04-pbril-21
31-March-21
04-April-21
x After calibration was done. The valve still showed a deadband higher than 3%. Looks like the valve is
working hard to get out its seat.
31-March-21
x During first stroke test of valve UV-114070, it was found small valve overshoot of 2.3% at 1% controller
command. The valve feedback position was not tracking the command. See Figure 8
04-April-21
x During last stroke test of valve UV-114070 the overshoot observed was 2.3% at 1% controller command,
but the valve feedback position was properly tracking the command. See Figure 9.
31-March-21
x During first stroke test of valve UV-114072 the valve never closed all the way to 0%. It stayed at 2.1%
open while controller command was at 0%. See Figure 10.
4-April-21
x As it can be observed in Figure 11 after valve UV-114072 was recalibrated and it did close to 0%.