TAX-3012D-02B Specifications
Product Overview
TAX-series industrial air conditioner is distinguished by its extraordinary intelligence for utmost energy saving
climate control. When ambient air is cool enough, It activates the built-in heat exchanging system instead of
refrigerating system to cool the cabinet with ambient air, even when ambient air is freezing, it can still keep the
heat exchanging system working by dynamically adjusting the heat exchanging effeciency, thereby
considerably lowering energy consumption.

Applications
◆ Telecom cabinets/shelters

◆ Indoor cabinets / Outdoor cabinets

◆ Network switching rooms

◆ Power supply/ Battery cabinets

◆ Automation control cabinets

◆ Machine cooling / Drive cabinets

◆ Server farms / Rack cooling

Front Back

Compressor Cooling Performance Curves

subject to change without notice Tel: +86-0755-61104272 Telca Science & Technology Co., Ltd. 이
Detail Drawing

Note:
1. Mounting gasket supplied (not shown)
2. Units: mm

subject to change without notice Tel: +86-0755-61104272 Telca Science & Technology Co., Ltd. 삼
Technical Data

Type Performance Data

Model Number TAX-3012D-02B


Dimensions mm WxHxD 500x1050x230
Cooling output 3100W(AC), 130W/K(HEX)
Heating output 1000W
Rated voltage 220VAC, 50Hz, 48VDC
Rated current 6.0A(cooling) 4.6A(heating) 2.5A(DC)
Power consumption 1320W(cooling) 1000W(heating) 190W(DC)
Temperature range
-40℃ ~ +55℃
Refrigerant R-410a
Air circuit (External) 1000m3/h
Air circuit (Internal) 850m3/h
Noise 68dB
Protection category IP55
Weight 58Kg

Control Behavior

Tin

Alarm
(High Temperature) P12
P7
TCON
P11
P8
(TCON+TCOFF)/2
P6 P10

TCOFF
P5 P9
P2
THOFF
P4
P1
THON
P3
Alarm
(Low Temperature) 0 Time
P0

subject to change without notice Tel: +86-0755-61104272 Telca Science & Technology Co., Ltd. 사
1, P0—P1 & P1—P2 & P3—P4:
Compressor OFF, External Fan OFF, Heater ON and Internal Fan Running at 50% speed

2, P2—P3:
Compressor OFF, External Fan OFF, Heater OFF and Internal Fan Running at 50% speed

3, P4—P5 & P5—P6 & P9—P10:


Compressor OFF, Heater OFF,
If ambient temp is lower than inside, Internal Fan linearly adjusts its speed from 50% @ THOFF to Full speed
@ (TCON+TCOFF)/2 and vice versa and External Fan linearly adjusts its speed from 0 @ THOFF to Full
speed @ (TCON+TCOFF)/2 and vice versa, otherwise, external fan stays OFF, Internal Fan Running at 50%
speed,

P6—P7 & P10—P11:


Compressor OFF, Heater OFF
If ambient temp is lower than inside, Both Internal Fan & External Fan run with Full speed , otherwise, external
fan stays OFF, Internal Fan Running at 50% speed.

P7—P8:
Heater OFF, Both Internal Fan & External Fan run with Full speed ,
Compressor ON unless its cooling capacity is not higher than heat exchanging cooling
capacity(130*(Tin-Tout)).

P8—P9:
Heater OFF,
External Fan adjusts its speed from Full speed @ (TCON+TCOFF)/2 to the speed when Tin reaches P5 from
P4 following the pattern stated in 3rd point above,
Compressor ON & Internal Fan run with Full speed if heat exchanging cooling
capacity(130*(Tin-Tout))<1950W, otherwise, Compressor OFF & Internal Fan run with variable speed
following the pattern stated in 3rd point above.

P11—P12:
Heater OFF, Both Internal Fan & External Fan run with Full speed , Compressor ON

End

subject to change without notice Tel: +86-0755-61104272 Telca Science & Technology Co., Ltd. 오