Project:
G+5P+HC+17TYP+ROOF COMMERCIAL / RESIDENTIALBUILDING
Plot No. 78 AL MAJAZ 1-KING FAISAL ROAD,SHARJAH, UAE
Client:
ASAS REAL ESTATE
Consultant:
NATIONAL ENGINEERING BUREAU (NEB)
Main Contractor:
AL QABDAH GLOBAL BUILDING CONTRACTING LLC
MEP Contractor:
TORQUE ELECTRO MECHANICAL WORKS
BSPKFMFE-01042018
Rev.02
Issue Date: 28062018
TECHNICAL SUBMITTAL
INDEX
FIRE FIGHTING EQUIPMENT
I. Consultant Comments……………………………………………………………………………….. 1
II. Reply to Consultant Comments………………………………………………………………….. 2
III. Project Details……………………………………………………………………………………………. 3
IV. Project Specification & Compliance Statement…………………………………..……… 4
General Department of Civil Defense - Sharjah اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ -اﻟﺸﺎرﻗﺔ
اﻻﺳﻢ اﻟﺘﺠﺎري ﻟﻠﻤﻨﺸﺄة :ﻧﻈﺮة اﻟﺨﻠﻴﺞ ﻟﺘﺠﺎرة اﺟﻬﺰة اﻻﻃﻔﺎء و ﻣﻜﺎﻓﺤﺔ اﻟﺤﺮﻳﻖ ذ.م.م رﻗﻢ اﻟﺘﺮﺧﻴﺺ 2013-3-59668 :
Agent Manufacturer ﺳﻨﺔ اﻟﺘﺮﺧﻴﺺ 2018 :
ﻋﺪد اﻟﺘﺮاﺧﻴﺺ 2 :
17/01/2019 Expiry date of theAgent : K36 Licence No. of theAgent : ﺑﺮﻳﺴﺘﻮل اﻧﺠﻨﻴﺮﻧﺞ Name of theAgent :
اﺳﻢ اﻟﻤﺨﺘﺒﺮ اﻟﺼﺎدر ﺗﺎرﻳﺦ اﻧﺘﻬﺎء ﻗﻴﺪ
رﻗﻢ ﺷﻬﺎدة اﻟﺴﻼﻣﺔ رﻗﻢ ﻗﻴﺪ اﻟﻮﻛﺎﻟﺔ اﺳﻢ اﻟﻤﺼﻨﻊ ﺑﻠﺪ اﻟﺼﻨﻊ اﻻﺳﻢ اﻟﺘﺠﺎري اﺳﻢ اﻟﻤﻌﺪة/اﻟﻤﻮاد/اﻟﻨﻈﺎم م
ﻟﻠﺸﻬﺎدة اﻟﻮﻛﺎﻟﺔ
BRE GLOBAL
TANDA Detection and fire alarm system : Unit
LTD, UNITED (1330D-(CL-1 16/08/2018 17745 China Tanda UK Limited
Technology co alarm sound
KINGDOM 7
رﻗﻢ اﻟﻤﻮدﻳﻞ :
Alarm Warning Device TX7300
UL,
Automatic sprinklers / hoses / point
UNDERWRITERS VICTAULIC United States of
VGYZ.EX15290 12/10/2018 10378 VICTAULIC water supply / water systems : Metal
LABORATORIES EUROPE America
connections
INC, USA
8رﻗﻢ اﻟﻤﻮدﻳﻞ :
V1201, V1202, V1203, V1204, V1205, V1206, V1207, V1208, V1211, V1212, V1213, V1214, V1215, V1216, V1217, V1218, V1221, V1222, V1223,
V1224, V1225, V1226, V1227, V1228, V1231, V1232, V1233, V1234, V1235, V1236, V1237, V1238, V1241, V1242, V1243, V1244, V1245, V1246,
V1247, V1248, V1251, V1252, V1253, V1254, V1255, V1256, V1257, V1258, V1261, V1262, V1263, V1264, V1265, V1266, V1267, V1268, V1271,
V1272, V1273, V1274, V1275, V1276, V1277, V1278,
UL,
Automatic sprinklers / hoses / point
UNDERWRITERS United States of
VUTX.EX2041 14/03/2018 11102 DIXON water supply / water systems : Ground
LABORATORIES America
valves 9
INC, USA
رﻗﻢ اﻟﻤﻮدﻳﻞ :
AVAPRF250-1
. 1ﻳﻌﺘﺒﺮ اﻟﻤﻮزع ﻣﺮﺧﺺ ﻣﻦ ﻗﺒﻞ اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ Sharjah -و ﻳﺤﻖ ﻟﻪ ﻣﺰاوﻟﺔ ﻧﺸﺎﻃﻪ ﻓﻲ إﻣﺎرة Sharjahﻓﻘﻂ ،اﺳﺘﻨﺎدا إﻟﻰ ﻗﺮار ﻣﺠﻠﺲ اﻟﻮزاري رﻗﻢ ) (24ﻟﺴﻨﺔ 2012ﻓﻲ ﺷﺄن ﺗﻨﻈﻴﻢ ﺧﺪﻣﺎت اﻟﺪﻓﺎع اﻟﻤﺪﻧﻲ
ﻣﻼﺣﻈﺔ :ﻟﻼﺋﺤﺔ اﻟﺘﻨﻔﻴﺬﻳﺔ رﻗﻢ ) (213ﻟﺴﻨﺔ ، 2017و ﻻ ﻳﺤﻖ ﻣﺰاوﻟﺔ أﻧﺸﻄﺘﻪ ﻓﻲ ﺑﺎﻗﻲ اﻹﻣﺎرات إﻻ ﺑﻌﺪ اﺳﺘﺨﺮاج ﺗﺮﺧﻴﺺ ﻣﻮزع ﻣﻦ ﻗﺒﻞ اﻹدارات اﻟﻌﺎﻣﺔ ذات اﻻﺧﺘﺼﺎص ﺑﻜﻞ إﻣﺎرة.
. 2إﺑﻼغ اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ ﻓﻲ ﺣﺎﻟﺔ ﺗﻐﻴﻴﺮ أو ﺗﻌﺪﻳﻞ ﻓﻲ اﻟﺒﻴﺎﻧﺎت اﻟﻤﺘﻌﻠﻘﺔ ﻓﻲ اﻟﺘﺮﺧﻴﺺ اﻟﺼﺎدر ﻣﻦ ﻗﺒﻞ اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ.
ﻳﻌﺘﻤﺪ/
Copy number 5 - 08/04/2018 - 0558921890 4/5
United Arab Emirates دوﻟﺔ اﻻﻣﺎرات اﻟﻌﺮﺑﻴﺔ اﻟﻤﺘﺤﺪة
General Department of Civil Defense - Sharjah اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ -اﻟﺸﺎرﻗﺔ
ﺗﻢ إﺻﺪار اﻟﺘﺮﺧﻴﺺ اﺳﺘﻨﺎدا إﻟﻰ اﻟﻘﺮار اﻟﻮزاري رﻗﻢ ) (24ﻟﺴﻨﺔ ، 2012ﻓﻲ ﺷﺄن ﺗﻨﻈﻴﻢ ﺧﺪﻣﺎت اﻟﺪﻓﺎع اﻟﻤﺪﻧﻲ
ﻧﻈﺮة اﻟﺨﻠﻴﺞ ﻟﺘﺠﺎرة اﺟﻬﺰة اﻻﻃﻔﺎء و اﻻﺳﻢ اﻟﺘﺠﺎري ﻟﻠﻤﻨﺸﺄة
2013-3-59668 رﻗﻢ اﻟﺴﺠﻞ 557284 رﻗﻢ اﻟﺮﺧﺼﺔ
ﻣﻜﺎﻓﺤﺔ اﻟﺤﺮﻳﻖ ذ.م.م
United Arab Emirates اﻟﺠﻨﺴﻴﺔ ﺷﻌﻴﺐ ﻋﺒﺪاﻟﻠﻪ ﻋﻠﻲ اﺣﻤﺪ اﺳﻢ ﺻﺎﺣﺐ اﻟﺘﺮﺧﻴﺺ
India اﻟﺠﻨﺴﻴﺔ راﺟﻨﺪرا ﻧﺎﺟﻴﻨﺪاس ﺧﺘﺮي ﻧﺎﺟﻴﻨﺪاس اﺳﻢ ﺻﺎﺣﺐ اﻟﺘﺮﺧﻴﺺ
India اﻟﺠﻨﺴﻴﺔ ﺑﻴﻨﺪو ﺟﻨﻐﻴﻨﻴﺎدان دﻳﻮﺳﻲ اﺳﻢ ﺻﺎﺣﺐ اﻟﺘﺮﺧﻴﺺ
Sharjah ﻣﻨﻄﻘﺔ اﻟﻨﺸﺎط ﺗﺠﺎرة ﻣﻮاد اﻃﻔﺎء اﻟﺤﺮﻳﻖ ﻧﻮع اﻟﻨﺸﺎط
73143 ص.ب 065610311 رﻗﻢ اﻟﻔﺎﻛﺲ 0508628851 رﻗﻢ اﻟﻬﺎﺗﻒ
ﻣﻜﺘﺐ رﻗﻢ 3ﻣﻠﻚ ﻓﺎﻃﻤﺔ ﻋﺒﺪاﻟﻠﻪ رﺣﻤﻪ اﻟﻌﻮﻳﺲ اﻟﺸﺎﻣﺴﻲ -ﺷﺎرع اﻟﺰﻫﺮاء Sharjah Sharjah Alsoor, , ﻋﻨﻮان اﻟﺸﺮﻛﺔ
www.gulfirevision.com gvfe2007@eim.ae اﻟﻤﻮﻗﻊ و اﻟﺒﺮﻳﺪ اﻹﻟﻜﺘﺮوﻧﻲ
17/01/2019 ﺗﺎرﻳﺦ اﻻﻧﺘﻬﺎء 04/04/2018 ﺗﺎرﻳﺦ اﻹﺻﺪار 29/11/2007 ﺗﺎرﻳﺦ ﺗﺄﺳﻴﺲ اﻟﻤﻨﺸﺄة
ﻋﺪد اﻟﻤﻌﺪات و اﻷﺟﻬﺰة اﻟﻤﺮاد ﺗﺮﺧﻴﺼﻬﺎ 10
ﻳﻌﺘﻤﺪ/
General Department of Civil Defense - Sharjah اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ -اﻟﺸﺎرﻗﺔ
اﻻﺳﻢ اﻟﺘﺠﺎري ﻟﻠﻤﻨﺸﺄة :ﻧﻈﺮة اﻟﺨﻠﻴﺞ ﻟﺘﺠﺎرة اﺟﻬﺰة اﻻﻃﻔﺎء و ﻣﻜﺎﻓﺤﺔ اﻟﺤﺮﻳﻖ ذ.م.م رﻗﻢ اﻟﺘﺮﺧﻴﺺ 2013-3-59668 :
Agent Manufacturer ﺳﻨﺔ اﻟﺘﺮﺧﻴﺺ 2018 :
ﻋﺪد اﻟﺘﺮاﺧﻴﺺ 2 :
17/01/2019 Expiry date of theAgent : K36 Licence No. of theAgent : ﺑﺮﻳﺴﺘﻮل اﻧﺠﻨﻴﺮﻧﺞ Name of theAgent :
اﺳﻢ اﻟﻤﺨﺘﺒﺮ اﻟﺼﺎدر ﺗﺎرﻳﺦ اﻧﺘﻬﺎء ﻗﻴﺪ
رﻗﻢ ﺷﻬﺎدة اﻟﺴﻼﻣﺔ رﻗﻢ ﻗﻴﺪ اﻟﻮﻛﺎﻟﺔ اﺳﻢ اﻟﻤﺼﻨﻊ ﺑﻠﺪ اﻟﺼﻨﻊ اﻻﺳﻢ اﻟﺘﺠﺎري اﺳﻢ اﻟﻤﻌﺪة/اﻟﻤﻮاد/اﻟﻨﻈﺎم م
ﻟﻠﺸﻬﺎدة اﻟﻮﻛﺎﻟﺔ
BRE GLOBAL
TANDA Detection and fire alarm system : Unit
LTD, UNITED (1330D-(CL-1 16/08/2018 17745 China Tanda UK Limited
Technology co alarm sound
KINGDOM 7
رﻗﻢ اﻟﻤﻮدﻳﻞ :
Alarm Warning Device TX7300
UL,
Automatic sprinklers / hoses / point
UNDERWRITERS VICTAULIC United States of
VGYZ.EX15290 12/10/2018 10378 VICTAULIC water supply / water systems : Metal
LABORATORIES EUROPE America
connections
INC, USA
8رﻗﻢ اﻟﻤﻮدﻳﻞ :
V1201, V1202, V1203, V1204, V1205, V1206, V1207, V1208, V1211, V1212, V1213, V1214, V1215, V1216, V1217, V1218, V1221, V1222, V1223,
V1224, V1225, V1226, V1227, V1228, V1231, V1232, V1233, V1234, V1235, V1236, V1237, V1238, V1241, V1242, V1243, V1244, V1245, V1246,
V1247, V1248, V1251, V1252, V1253, V1254, V1255, V1256, V1257, V1258, V1261, V1262, V1263, V1264, V1265, V1266, V1267, V1268, V1271,
V1272, V1273, V1274, V1275, V1276, V1277, V1278,
UL,
Automatic sprinklers / hoses / point
UNDERWRITERS United States of
VUTX.EX2041 14/03/2018 11102 DIXON water supply / water systems : Ground
LABORATORIES America
valves 9
INC, USA
رﻗﻢ اﻟﻤﻮدﻳﻞ :
AVAPRF250-1
. 1ﻳﻌﺘﺒﺮ اﻟﻤﻮزع ﻣﺮﺧﺺ ﻣﻦ ﻗﺒﻞ اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ Sharjah -و ﻳﺤﻖ ﻟﻪ ﻣﺰاوﻟﺔ ﻧﺸﺎﻃﻪ ﻓﻲ إﻣﺎرة Sharjahﻓﻘﻂ ،اﺳﺘﻨﺎدا إﻟﻰ ﻗﺮار ﻣﺠﻠﺲ اﻟﻮزاري رﻗﻢ ) (24ﻟﺴﻨﺔ 2012ﻓﻲ ﺷﺄن ﺗﻨﻈﻴﻢ ﺧﺪﻣﺎت اﻟﺪﻓﺎع اﻟﻤﺪﻧﻲ
ﻣﻼﺣﻈﺔ :ﻟﻼﺋﺤﺔ اﻟﺘﻨﻔﻴﺬﻳﺔ رﻗﻢ ) (213ﻟﺴﻨﺔ ، 2017و ﻻ ﻳﺤﻖ ﻣﺰاوﻟﺔ أﻧﺸﻄﺘﻪ ﻓﻲ ﺑﺎﻗﻲ اﻹﻣﺎرات إﻻ ﺑﻌﺪ اﺳﺘﺨﺮاج ﺗﺮﺧﻴﺺ ﻣﻮزع ﻣﻦ ﻗﺒﻞ اﻹدارات اﻟﻌﺎﻣﺔ ذات اﻻﺧﺘﺼﺎص ﺑﻜﻞ إﻣﺎرة.
. 2إﺑﻼغ اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ ﻓﻲ ﺣﺎﻟﺔ ﺗﻐﻴﻴﺮ أو ﺗﻌﺪﻳﻞ ﻓﻲ اﻟﺒﻴﺎﻧﺎت اﻟﻤﺘﻌﻠﻘﺔ ﻓﻲ اﻟﺘﺮﺧﻴﺺ اﻟﺼﺎدر ﻣﻦ ﻗﺒﻞ اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ.
ﻳﻌﺘﻤﺪ/
Copy number 5 - 08/04/2018 - 0558921890 4/5
III. Project Details
Project:
G+5P+HC+17TYP+ROOF COMMERCIAL / RESIDENTIAL BUILDING
Plot No:
78 AL MAJAZ 1-KING FAISAL ROAD,SHARJAH, UAE
Client:
ASAS REAL ESTATE
Consultant:
NATIONAL ENGINEERING BUREAU (NEB)
Main Contractor:
AL QABDAH GLOBAL BUILDING CONTRACTING LLC
MEP Contractor:
TORQUE ELECTRO MECHANICAL WORKS
IV. Project Specification & Compliance Statement
V. Technical Data Sheets and Catalogue
A.Bristol Fire Cabinets
...Technical Data Sheets and Catalogue
B. Fire Hose Reel
Swinging Type Fire Hose Reels
EN 671-1 Cert No. 1226a
LPCB Approved
DN 1” ¾”
Hose
Length 30m
Pressure-Reducing Valve
Model BFE06068
DN 1”
Inlet/Outlet
Type M BSPT
9
Single/Double Jacket Fire Hose
EX16027
BRISTOL Fire Hoses are made with polyester and its inner-lining with EPDM to ensure low friction loss and maximum flow while maintaining
high durability.
Features
- Strong and Highly Protected
- Abrasion and puncture resistant
- Chemical Resistance
- Resists contact with oil, hydrocarbons, alkalis, salt water, etc
- Weather Resistance
- Outstanding performance in extreme weather (-20oC to 50oC)
- Ease of Maintenance
- No drying needed as hose is mildew and rot proof
DN 2½”
Inlet
Type Male Instantaneous BS 336
DN 2½”
Outlet
Type Female Instantaneous BS 336
Length 30m
Color Red
10
Fire Hose - Nozzle Adaptor (Accessories)
Model BF-AD-001
DN 2½”
Inlet
Type Male Instantaneous BS 336
Specifications
DN 2½”
Outlet
Type Male NPSH
Material Brass
Model BF-NZ-001
DN 2½”
Inlet
Type Male Instantaneous BS 336
Outlet Diameter ½”
Specifications
Mode Jet/Spray/Off
AVAPR150
AVAPR250
18-153
Female NPT inlet x Male *
• female inlet NPT only available finish:
• male outlet - specify male thread * • cast (standard)
• aluminum handwheel • polished - P
• restricts only under flow conditions • chrome - C
• for use up to 175 PSI
cast finish show
• alloy=C84400, C83600, C36000
• manufactured in the USA
AVAPRF150
AVAPRF250
18-154
Double Female
• inlet and outlet NPT only available finish:
• restricts under flow conditions only • cast (standard)
• aluminum handwheel • polished - P
• for use up to 175 PSI • chrome - C
cast finish show • alloy=C84400, C83600, C36000
• manufactured in the USA
C C Wt. in
Size Style A B D E F
(closed) (open) Lbs.
1½" 18-153 -154 2-7/32" 2-11/64" 6-13/16" 7-27/32" 3-3/4" 2-7/16" 2-13/32" 5
2½" 18-153 -154 3-7/32" 3-3/16" 9-17/32" 11-3/8" 5" 3-19/32" 3-17/32" 12
Technical Information
Pressure Restricting Valves
• Underwriters
Listed and New York City Board of Standards and Appeals approval # MEA 54-07-E
• Restricts inlet pressure from 70 PSI (483 kPa) up to a maximum of 175 PSI (1207 kPa), down to an outlet pressure of 65, 80 or
100 PSI (448. 552 or 690 kPa).
• Outlet pressures may be set below 65 PSI (448 lPa) when authorized by the local authority having jurisdiction.
• NFPA requires restricting valves where the inlet pressure exceeds 100 PSI. Unlike the pressure regulating type of valve, the re-
stricting valve has no effect on the static pressure of a system.
• The restricting device can be manually by-passed if required by opening the valve fully. This is accomplished by breaking the
"breakable link", which allows the valve stem to rise to the full open position.
• The breakable link also serves as a simple indication of the valve condition and status. If the valve is opened without breaking the
link, the valve will resume its previous position and no resetting is necessary.
This graph is based on using 50' of 2½" rubber lined hose and a 1-1/8" discharge nozzle to obtain outlet pressures of 65, 80 or
100 PSI.
This information is only a general guideline. The company reserves the right to change any portion of this information without notice.
Terms and conditions of sale apply and are available on request.
Dixon Powhatan
800 High Street
Chestertown, MD 21620
www.dixonpowhatan.com
ph 800-355-1991 • fx 800-283-4966
® 2009 DVCC PRVAVA-SPECSHT
...Technical Data Sheets and Catalogue
G. DCP Fire Extinguisher
H. CO2 Fire Extinguisher
Portable Fire Extinguishers
Portable Fire Extinguishers are used for putting out or containing small fire until fire department arrives.
BRISTOL Portable Fire Extinguisher comply to BS EN – 3, they are light weight and easy to use, suitable for
industrial, commercial and home use.
4
Dry Chemical Powder
Features
- Easy grip control valve
- Seamless, corrosion-resistant body
- Refillable and parts are replaceable
- Comes with heavy-duty bracket
Propellant Nitrogen
Fire Rating
5A&34B 13A&70B 21A&113B 27A&183B 34A&233B 43A&233B
(BS EN 3-7:2004+A1:2007)
Specifications
KM 503775 0086
5
Carbon Dioxide
Features
- Easy grip control valve
- Seamless, corrosion-resistant body
- Refillable and parts are replaceable
- Comes with heavy-duty bracket
Fire Class BE
Fire Rating
34B 89B
(BS EN 3-7:2004+A1:2007)
Regular
Fire Class BE
KM 587564
7
...Technical Data Sheets and Catalogue
I. 1" Air Release Valve
Other Valves
Air-Release Valve
Model BFE090203
Specifications
Coupling M BSPT
22
...Technical Data Sheets and Catalogue
J. Fire Blanket
FIRE BLANKET
B S I K ITE MAR K AP PROVED
SPECIFICATIONS
Design Standard BS EN1869:1997
Approval BSI Kitemark
Material Glass Fiber
Thickness 0.25±0.03mm
Weight 340±20g / m2
Warp 20±1pcs/cm
Weft 15±1pcs/cm
950N (Warp)
Break Strength
420N (Weft)
WWW.BRISTOL-FIRE.COM
...Technical Data Sheets and Catalogue
K. Breeching Inlet
L. Breeching Cabinet
Breeching Inlets
Breeching Inlets are used as water feed from the fire department pump to the building fire-fighting system.
BRISTOL Breeching Inlets are designed for dry riser application, and are manufactured to comply with
BS 5041 standard comprising of male instantaneous connections.
7
Two-Way
KM 599357
Compliance BS 5041-3
DN 100mm
Outlet
Type Flange PN16
Four-Way
BSI Kitemark Approved
Compliance BS 5041-3
DN 150mm
Outlet
Type Flange PN16
8
DESCRIPTION
9
Swing Type LISTED EX16011
UL Listed, FM Approved
Model BR-DGC-300
Model BR-DGC-300
10
...Technical Data Sheets and Catalogue
N. Bristol OS&Y Gate Valve
O. OSY2 Tamper Switch
Gate Valves
Gate Valves are valves that open by lifting a round or rectangular gate/wedge out of the path of the fluid.
They are characterized as having either a rising or a non-rising stem. BRISTOL Gate Valves are made of
high quality materials and conform to international and local standards.
4
Outside Stem & Yoke LISTED EX16103
UL Listed, FM Approved
Model 399F
Model 399F
5
OSY2
Supervisory Switch
gate valve.
• 100% synchronization activates both alarm panel and local bell Simplified Operation. Installation is made easier with the
simultaneously OSY2’s single side conduit entrance. By providing a direct conduit
pathway to the electrical source, right angle fittings are not required.
Installation is further simplified by the OSY2’s adjustable length
actuator, which eliminates the need for cutting the shaft.
Agency Listings
Operating Temperature 32ºF to 120°F ( 0ºC to 49ºC) Cover Tamper Switch Standard with ULC model
Range NOTE: The OSY2 will operate from –40ºF to 120ºF Optional for UL model, part no. 546-7000
(–40ºC to 49ºC); however UL does not test control
valve supervisory switches below 32ºF (0ºC).
Maximum Stem Extension 25/8˝ (6.7cm) Service Use Automatic Sprinkler: NFPA 13
One or Two Family Dwelling: NFPA 13D
Residential Occupancies up to 4 stories: NFPA 13R
National Fire Alarm code: NFPA 72
Bracket Span ¼˝H x 6¾˝W x 1˝D (5.7cm x 17.1cm x 2.5cm) Warranty 3 years
Conduit Entrances One single side open for ½˝ conduit U.S. Patent Nos. 5,478,038; 5,213,205
CO M
M CO
A B B A
Switch 2 CONTACT RATINGS
125/250 VAC 10 AMPS
Strip Gauge 24 VDC 2.5 AMPS
B B B B
B
to power source
compatible local
with bell bell Break wire as shown for supervision
COM of connection. DO NOT allow stripped
wire leads to extend beyond switch
housing. DO NOT loop wires.
Ordering Information
Part No. Description
OSY2 Outside Screw and Yoke valve supervisory switch
OSY2A Outside Screw and Yoke valve supervisory switch (ULC model)
Accessories
OSYRK Replacement hardware kit (wrenches, screw pack and J–hooks) WFDW Replacement tamper proof wrench for cover
546-7000 Cover tamper switch kit HEXW Replacement hex wrench
S07-66-XX Tamper screws for cover
tampering. 4
Typical Application
Underwriters Laboratories requires the installation of pressure
CLA-VAL 90-21
gauges upstream and downstream of the Pressure Reducing Valve.
Model 55L Also, a relief valve of not less than 1/2 inch in size must be installed
on the downstream side of the pressure control valve. Adequate
CLA-VAL 90-21 drainage for the relief valve discharge must be provided.
FF 150 ANSI 4.00 3.25 4.00 4.00 5.00 6.00 8.00 8.62 BB
FFF 300 ANSI 4.25 3.50 4.31 9.31 A
4.38 5.31 6.50 8.50
AA
FFFF GROOVED –– 3.25 –– 4.50 5.00 –– –– –– AAA AAAA
4" SIZE
SHOWN
AAAA GROOVED 216 228 279 318 381 508 645 –– F FFF
B 28 38 43 65 81 109 135 235 FF FFFF
BB GROOVED 52 54 73 6.00 4.13 6.00 184 ––
C (MAX) 140 161 192 208 270 340 406 435 E INLET
E-90G-21 (R-11/08)
...Technical Data Sheets and Catalogue
Q. WATTS Pressure Relief Valve
ES-FP53L
Model FP53L
Pressure Relief Valve
Size: 1⁄2" (15mm)
Watts No. FP53L is designed for use in fire protection grid systems
to provide protection against excessive water pressure caused by
thermal expansion or line surge. It is available in 175psi (12.1 bar), 1⁄2" NPT
pressure relief settings and can be installed horizontally or vertically.
Bronze body construction with stainless steel spring to inhibit corro- Female Outlet
sion. The valve is constructed with a precision stem guide to ensure
proper reseating. The test lever affords periodic manual testing and
flushing of waterways and seating surfaces.
Features
• Underwriters
Laboratory listed
• Forged stainless steel spring
1⁄2" NPT
• Bronze body construction for superior strength and to
Male Inlet
prevent corrosion
• Manual test lever
• Valve stem is guided to enhance reseating
• 1⁄2" (15mm) male inlet x female outlet
• Pressure settings: 1 75psi (12.1 bar)
! WARNING
Specifications Following installation, the valve lever MUST be operated
AT LEAST ONCE A YEAR to ensure that the water-ways
For applications requiring a UL approved relief valve to provide
are clear. Certain naturally occurring mineral deposits may
pressure relief protection from water pressure in excess of 175psi
(12.1 bar). Each valve shall be bronze body construction with forged adhere to the valve, rendering it inoperative. When manually
stainless steel spring. It shall have a test lever and the valve shall be operating the lever, water will discharge and precautions must
guided to enhance reseating and to decrease chance of the seat be taken to avoid contact with hot water and to avoid water
being misaligned. Watts Model No. FP53L. damage. BEFORE operating lever, check to see that a dis-
charge line is connected to this valve directing the flow of hot
Dimensions — Weight water from the valve to a proper place of disposal otherwise
personal injury may result. If no water flows, valve is inopera-
tive. CALL A PLUMBER IMMEDIATELY.
MODEL SIZE HEIGHT WIDTH WEIGHT This device is designed for emergency safety relief and shall
in. mm in. mm in. mm lbs. kgs. not be used as an operating control.
FP53L ⁄
12 15 31⁄2 89 17⁄8 48 ⁄
12 .23
NOTICE
The information contained herein is not intended to replace the full
product installation and safety information available or the experience
of a trained product installer. You are required to thoroughly read all
installation instructions and product safety information before begin-
ning the installation of this product.
Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Watts Technical Service. Watts
reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications
on Watts products previously or subsequently sold.
USA: Tel: (978) 689-6066 • Fax: (978) 975-8350 • Watts.com A Watts Water Technologies Company
Canada: Tel: (905) 332-4090 • Fax: (905) 332-7068 • Watts.ca
Latin America: Tel: (52) 81-1001-8600 • Fax: (52) 81-8000-7091 • Watts.com
Applications
Special features
Bourdon tube
Material: copper alloy
C-type
Brass restrictor
Friction-fit cover ring (requires steel case)
Glass window (requires steel case & friction ring)
Black-painted steel case
Stainless steel case
Special case colors
Nickel-plated connection
Custom dial layout
Special threaded connection
Custom dial layout
Other pressure scales available:
bar, kPa, MPa, kg/cm2 and dual scales
Size
A B C E L T W Weight
4” mm 100 83.5 30 11.5 3.75 14
in 4.0 3.29 1.18 0.45 0.15 1/4” 0.55 0.35 lb.
Ordering information
Pressure gauge model / Nominal size / Scale range / Size of connection / Optional extras required
Specifications and dimensions given in this leaflet represent the state of engineering at the time of printing.
Modifications may take place and materials specified may be replaced by others without prior notice. WIKA Instrument Corporation
1000 Wiegand Boulevard
Lawrenceville, GA 30045
Tel (770) 513-8200 Toll-free 1-888-WIKA-USA
Fax (770) 338-5118
E-Mail info@wika.com
www.wika.com
VI. Method Of Statement
1 Fire Extinguishers
1.1 Dry Powder Extinguishers
1.2 How Dry Powder Fire Extinguishers Work.
1.3 Three Main Types of Dry Powder Extinguishers
1.4 Dry Powder Extinguishers and Water
1.5 CO2 Fire Extinguishers
1.6 How Carbon Dioxide Fire Extinguishers Work
1.7 CO2 Fire Extinguishers and Electricity
1.8 Carbon Dioxide Fire Extinguishers and Other Fire Classes
1.9 Carbon Dioxide Fire Extinguisher Pressure Gauges
2 Fire Hose Reel
2.1 General Instructions for Use
2.2 Operation
3 Sprinkler System
3.1 Glass Bulb Detector / Sprinkler Heads
3.1.1 Description
3.1.2 Design Parameters
3.1.3 Operation
3.2 Alarm Check Valve
3.2.1 Operation
3.2.2 Trim Packages
Trim Packages Available
Trim Packages Include
3.2.3 Optional Accessories
3.2.4 Installation
3.2.5 Testing
3.2.6 Maintenance
3.2.7 Retard Chamber
...Method Of Statement
1 Fire Extinguishers
1.1 Dry Powder Extinguishers
For this reason, dry chemical ABC rated fire extinguishers should not be
used on sensitive electrical equipment such as computers, switch
installations, scientific instruments or aircraft, if other fire extinguishing
options are available.
Left in place, powder will draw moisture from the air and a common
example of corrosion will be the chrome on tools being replaced with rust.
CO2 fire extinguishers (carbon dioxide) are the only fire extinguisher
recommended for fires involving electrical equipment. CO2 is safe to use
on and around electrical equipment, as the gas itself is non-conductive,
and once used, there is no sticky foam or messy powder left behind. They
are also effective on Class B fires (flammable liquids).
Carbon dioxide fire extinguishers are painted bright red with a black
panel above the operating instructions. They have a distinctive horn-
shaped nozzle at the side on the smaller models with 5kgs and above
having a hose and horn.
CO2 extinguishers store carbon dioxide gas under great pressure (55 bar
or 825psi), where the gas becomes a liquid. When you operate the fire
extinguisher levers, the pressure is released; the CO2 pressure is reduced
by the diffuser (horn) and expands back into a gas, rapidly cooling the
surrounding air.
This process is so fast, it can cause ice to form on the horn, so never hold a
CO2 fire extinguisher by the horn to avoid freezing your skin. To be most
effective, a carbon dioxide fire extinguisher should be used no closer than
3 feet and no further than 8 feet from the fire itself.
...Method Of Statement
For the UK, they are commonly made in two sizes, 2kg and 5kg. The
compressed gas required an extremely thick cylinder so many buyers
prefer super-strong aluminum rather than heavier steel models, so that
their staff can lift and use the CO2 extinguishers more easily. Steel is
normally used for marine extinguishers although many of the cheap
imports are made from steel.
The 2kg models tend to have a swivel horn, which must not be held during
operation to avoid freezing your hands. The 5kg models usually feature a
hose with the horn attached with the horn normally having a handle.
CO2 fire extinguishers are safe to use on fires in, on or around electrical
equipment and live cables. CO2 gas is dry, inert in air, and leaves behind
no residue that will affect electrical equipment’s future operation. So, you
will often find a CO2 fire extinguisher next to precious electrical
equipment, from switchgear to mobile discos.
Always read the instruction plate before use, to ensure that you have
selected the correct extinguisher for the fire you intend to fight.
2.2 Operation
• Automatic Hose reel- pull out the hose for 2 m or 3 m and the water
is automatically turned on. Control the discharge by using the
nozzle in Jet/spry/Off mode
• Manual Hose Reel- to turn on the water, open the inlet valve, before
running out the hose to location the fire. Control the discharge by
using the nozzle in Jet/spry/Off mode
Ensure that you are positioned between the fire and safe exit/escape
route
Apply the water jet to the base of the fire in short sweeping burst keeping
out the smoke and steam produced.
Warning there is a continuous supply of water to the hose reel. Do not fight
the fire size increases or for too long – beware of your surrounding and
local conditions.
3 Sprinkler System
Sprinkler system is designed to the requirement of NFPA-13, Standard for
Installation of Sprinkler Systems.
The sprinkler system is provided for protection of the Fire Pump room. The
sprinkler system consists of a network of aboveground piping, sprinkler
...Method Of Statement
heads, supervised isolation valve, and water flow switch. The sprinkler
heads are located evenly and in such a manner that water is discharged
in defined spray patterns covering the entire surface area of the hazard
protected. The sprinkler heads senses the heat generated by fire and burst
at a pre-determined temperature. This bursting creates a pressure drop in
the piping. The pressure switch is activated, starting the electric motor
pump first. In case the electric motor pump fails, the standby diesel
engine pump comes into operation and supplies adequate water to the
sprinkler system. When the system is activated the flow switch located on
the piping gives a signal to the fire alarm control panel. Also a
mechanical alarm is generated by means of water flowing through the
water motor gong located externally. The system is also connected to a
breeching inlet located outside the premises in the event of fire, the fire
department or civil defense personnel is required to pump water into the
system.
Design density as per NFPA-13 is 6.1 lpm/m2 for a minimum area of 139m2
and the minimum pressure at the remotest sprinkler heads is 0.5 bars.
3.1.3 Operation
3.2.1 Operation
3.2.4 Installation
Inlet and outlet flanges can be provided to ANSI DIN BS or JIS Standards
(specify when during) Valves Should be installed in accordance with NFPA
or other appropriate local standards in accordance with the authority
having jurisdiction. Connecting piping should be flushed clean of dirt and
all other materials that may interface with proper operation of the system
to ensure that the system has a proper flow of clean uncontaminated
water. Make Sure that the direction of flow indicated by the arrow is in the
correct direction. Check to ensure that the clapper can move freely and
is clear of all associated piping.
3.2.5 Testing
The building owner the local Fire Department and all other appropriate
authorities. NFPA 25 recommends testing at least 4 times per year. Other
Authorities having jurisdiction may have different regulations and the user
should ensure that frequent tests are conducted strictly in accordance
with local regulations.
3.2.6 Maintenance
The owner is responsible for the proper operation of the system and all
related components and accessories NFPA 24 recommends periodic
maintenance procedures and the local authority having jurisdiction may
have additional requirements.
The Alarm Check Valve has been carefully constructed from the superior
quality materials in order to give trouble free service and proper operation
and should be routinely checked to ensure proper operation.
Clapper
The rubber clapper facing should be checked for wear or damaged and
should be free from all external matter or materials. If damage is observed
it should be immediately replaced.
All dirt or extraneous matter should be carefully cleaned from the surface.
Do not use solvent or any hydrocarbon derivatives for cleaning purposes.
If in doubt replace completely.
...Method Of Statement
Seat Ring
Check the seat ring for dirt and damage to the seating surfaces and
thoroughly clean of all dirt and extraneous matter. Seat ring damage
could lead to a failure of the system to operate in a fire condition.
In the case of any damage to the seat ring which may cause on-
operation of the system, the valve should be replaced.
Retard Chamber
Check that the outlet and inlet orifices are free from dirt and extraneous
matter and are undamaged and clean all elements thoroughly before
replacing in service.
Bypass Line
The Bypass line must be undamaged and free of any dirt and extraneous
matter. Clean out before replacing in service. The whole system should be
periodically checked to ensure proper function.
Care should be taken to inspect for physical damage and system leaks.
The fire protection piping and all components are integral parts of a
building safety system to protect life and proper operation is a function
correct design, installation, and carefully conducted periodic
maintenance.
During a fire condition or system testing, water flows into intermediate and
retard chambers, activating the water motor alarm and other signaling
devices and then the system operates as normal.
VII. Approval Certificates
Certificate of Product Approval
Certificate Number: 1226a Issue: 01
is authorised to use the LPCB mark in association with the product(s) listed in this certificate and appendix
having complied with the requirements of the standard(s) detailed below:
Products Standards
Bristol Fire Hose Reels EN 671-1:2012
Fixed firefighting systems. Hose systems. Hose
Single Door Cabinets reels with semi-rigid hose
This certificate and appendix is maintained and held in force through regular surveillance activities
This certificate and appendix remain the property of BRE Global Ltd and is issued
subject to terms and conditions (for details visit www.redbooklive.com/terms).
To check the validity of this certificate and appendix please visit
www.redbooklive.com/check, scan the QR tag or contact us.
LPCB is part of BRE Global Ltd, Garston, Watford, WD25 9XX
T: +44 (0)1923 664100 F: +44 (0)1923 664603 E: enquiries@breglobal.com
LPCB Ref.
Product Name Description
No.
This certificate and appendix is maintained and held in force through regular surveillance activities
This certificate and appendix remain the property of BRE Global Ltd and is issued
subject to terms and conditions (for details visit www.redbooklive.com/terms).
To check the validity of this certificate and appendix please visit
www.redbooklive.com/check, scan the QR Tag or contact us.
LPCB is part of BRE Global Ltd., Garston, Watford WD25 9XX.
T: +44 (0)1923 664100 F: +44 (0)1923 664603 E: Enquiries@breglobal.com
LPCB Ref.
Product Name Description
No.
This certificate and appendix is maintained and held in force through regular surveillance activities
This certificate and appendix remain the property of BRE Global Ltd and is issued
subject to terms and conditions (for details visit www.redbooklive.com/terms).
To check the validity of this certificate and appendix please visit
www.redbooklive.com/check, scan the QR Tag or contact us.
LPCB is part of BRE Global Ltd., Garston, Watford WD25 9XX.
T: +44 (0)1923 664100 F: +44 (0)1923 664603 E: Enquiries@breglobal.com
LPCB Ref.
Product Name Description
No.
This certificate and appendix is maintained and held in force through regular surveillance activities
This certificate and appendix remain the property of BRE Global Ltd and is issued
subject to terms and conditions (for details visit www.redbooklive.com/terms).
To check the validity of this certificate and appendix please visit
www.redbooklive.com/check, scan the QR Tag or contact us.
LPCB is part of BRE Global Ltd., Garston, Watford WD25 9XX.
T: +44 (0)1923 664100 F: +44 (0)1923 664603 E: Enquiries@breglobal.com
LPCB Ref.
Product Name Description
No.
This certificate and appendix is maintained and held in force through regular surveillance activities
This certificate and appendix remain the property of BRE Global Ltd and is issued
subject to terms and conditions (for details visit www.redbooklive.com/terms).
To check the validity of this certificate and appendix please visit
www.redbooklive.com/check, scan the QR Tag or contact us.
LPCB is part of BRE Global Ltd., Garston, Watford WD25 9XX.
T: +44 (0)1923 664100 F: +44 (0)1923 664603 E: Enquiries@breglobal.com
VNIV.EX15981
Sprinklers, Automatic and Open
Page Bottom
Sprinkler Identification Number (SIN) H001, H002, H003, H004, H005 and H006 Glass Bulb Type - Chrome-plated Sprinklers are identified by
CP on the deflector.
Sprinkler Identification Number (SIN), Glass Bulb Type BF001, BF005, BF002, BF004, BF003, BF006, BF007, and BF008.
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=VNIV.EX15981&ccnshorttitle=Sprinklers,+Automatic+and+Open&objid=1081969
3/14/2018 VNIV.EX15981 - Sprinklers, Automatic and Open
BF007*# SR Horizontal 5.6 175 135, 155, 175, 200
Temp Rating, °F
Response Nom
SIN Type Type K-Factor Cover Sprinkler
© 2018 UL LLC
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
the following format: "© 2018 UL LLC".
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=VNIV.EX15981&ccnshorttitle=Sprinklers,+Automatic+and+Open&objid=1081969
No. KM 503775
The British Standards Institution hereby grants to:
In respect of:
BS EN 3
Portable fire extinguishers
This issues the right and licence to use the Kitemark in accordance with the Kitemark Licence Conditions of
Contract governing the use of the Kitemark, as may be updated from time to time by The British Standards
Institution, and as approved by the Registrar under the Trade Marks Act 1994 (the "Conditions"). All defined terms
in this Licence shall have the same meaning as in the Conditions.
The use of the Kitemark is authorized in respect of the Product(s) detailed on this Licence provided at or from the
above address.
Page 1 of 2
This Licence remains the property of The British Standards Institution and shall be returned immediately upon request. To check its validity telephone +44 (0)8450 765600.
The British Standards Institution, Kitemark House, Maylands Avenue, Hemel Hempstead, Hertfordshire, HP2 4SQ, United Kingdom. Tel:+44 (0)8450 765600 Web:
www.bsigroup.com/certification. The British Standards Institution Headquarters: 389 Chiswick High Road, London, W4 4AL. Tel:+44 (0)20 8996 9001. The British
Standards Institution is incorporated by Royal Charter.
No. KM 503775
BS EN 3 Portable fire extinguishers
This Licence remains the property of The British Standards Institution and shall be returned immediately upon request. To check its validity telephone +44 (0)8450 765600.
The British Standards Institution, Kitemark House, Maylands Avenue, Hemel Hempstead, Hertfordshire, HP2 4SQ, United Kingdom. Tel:+44 (0)8450 765600 Web:
www.bsigroup.com/certification. The British Standards Institution Headquarters: 389 Chiswick High Road, London, W4 4AL. Tel:+44 (0)20 8996 9001. The British
Standards Institution is incorporated by Royal Charter.
No.
No. KM
KM587564
587564
The licence is granted to:
In respect of:
Portable fire extinguishers
This issues the right and licence to use the Kitemark in accordance with the Kitemark Licence Conditions of
Contract governing the use of the Kitemark, as may be updated from time to time by The British Standards
Institution, and as approved by the Registrar under the Trade Marks Act 1994 (the "Conditions"). All defined terms
in this Licence shall have the same meaning as in the Conditions.
The use of the Kitemark is authorized in respect of the Product(s) detailed on this Licence provided at or from the
above address.
Page
Page1 of
1 2of 2
This Licence remains the property of The British Standards Institution and shall be returned immediately upon request. To check its validity telephone +44 (0)845 080 9000
Information and contact: BSI, Kitemark Court, Davy Avenue, Knowlhill, Milton Keynes MK5 8PP. Tel: +44 845 080 9000. BSI Assurance UK Limited, registered in
England under number 7805321, at 389 Chiswick High Road, London, W4 4AL, UK. A member of the BSI Group of Companies.
No. KM 587564
The above products may be Kitemarked when branded with the following tradenames:
Concorde
Eagle
EFFECO
Marshal
Safe
For the purposes of traceability the Kitemark licence number must appear adjacent to the Kitemark
symbol on all branded products.
Page 2 of 2
This Licence remains the property of The British Standards Institution and shall be returned immediately upon request. To check its validity telephone +44 (0)845 080 9000
Information and contact: BSI, Kitemark Court, Davy Avenue, Knowlhill, Milton Keynes MK5 8PP. Tel: +44 845 080 9000. BSI Assurance UK Limited, registered in
England under number 7805321, at 389 Chiswick High Road, London, W4 4AL, UK. A member of the BSI Group of Companies.
11/10/2016 VLMT.EX2534 Special System Water Control Valves, Pressurereducing and Pressurecontrol Type
VLMT.EX2534
Special System Water Control Valves, Pressurereducing and Pressurecontrol
Type
Page Bottom
See General Information for Special System Water Control Valves, Pressurereducing and Pressurecontrol Type
"Clayton" , pilot operated pressure control valves, iron iron body, (sizes 11/2 to 8 in.), ductile iron body (sizes 11/2 to 8 in) and bronze body
(sizes 11/2 to 3 in.) consisting of the following models, sizes, inlet pressure ratings, and outlet pressure setting ranges:
"Clayton", pilot operated pressure control valves, steel body, (sizes 11/2 to 6 in.) ductile iron body (11/2 to 6 in.) and bronze body (sizes 1
1/2 to 3 in.) consisting of the following models, sizes, inlet pressure ratings, and outlet pressure setting ranges:
For all valves, the manufacturer's design and installation instructions include a description of the performance characteristics for both flow and
static conditions.
© 2016 UL LLC
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's FollowUp Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's FollowUp
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
the following format: "© 2016 UL LLC".
http://database.ul.com/cgibin/XYV/template/LISEXT/1FRAME/showpage.html?name=VLMT.EX2534&ccnshorttitle=Special+System+Water+Control+Valves,+… 1/1
Kitemark™ Certificate
Kitemark™ Certificate
No. KM 677822
In respect of:
BS EN 1869
Fire Blankets
This issues the right and licence to use the Kitemark in accordance with the Kitemark Terms and Conditions
governing the use of the Kitemark, as may be updated from time to time by BSI Assurance UK Ltd (the "Conditions").
All defined terms in this Certificate shall have the same meaning as in the Conditions.
The use of the Kitemark is authorized in respect of the Product(s) detailed on this Certificate provided at or from the
above address.
For and on behalf of BSI: Gary Fenton, Global Product Certification Director
Page: 1 of 2
Page: 1 of 2
This certificate has been issued by and remains the property of BSI Assurance UK Ltd, Kitemark Court, Davy Avenue, Knowlhill, Milton Keynes MK5 8PP, United
Kingdom and should be returned immediately upon request.
To check its validity telephone +44 (0) 345 080 9000. An electronic certificate can be authenticated online.
BSI Assurance UK Limited, registered in England under number 7805321 at 389 Chiswick High Road, London W4 4AL, UK.
A member of BSI Group of Companies.
Kitemark™ Certificate
No. KM 677822
Model No Description
Page: 2 of 2
This certificate has been issued by and remains the property of BSI Assurance UK Ltd, Kitemark Court, Davy Avenue, Knowlhill, Milton Keynes MK5 8PP, United
Kingdom and should be returned immediately upon request.
To check its validity telephone +44 (0) 345 080 9000. An electronic certificate can be authenticated online.
BSI Assurance UK Limited, registered in England under number 7805321 at 389 Chiswick High Road, London W4 4AL, UK.
A member of BSI Group of Companies.
8/14/2017 USQT.S35811 - Extinguishing System Attachments
USQT.S35811
Extinguishing System Attachments
Page Bottom
© 2017 UL LLC
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
the following format: "© 2017 UL LLC".
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=USQT.S35811&ccnshorttitle=Extinguishing+System+Attachment… 1/1
Waterflow Detectors, Vane Type
Waterflow detectors installed in sprinkler systems provide an electrical alarm when a flow of water from the system equals or exceeds
that of a single sprinkler. They can be used with either open or closed signaling circuits.
They may consist of a flexible vane which projects into the waterway or a pressure-sensing device. For the flexible vane type, water
movement deflects the vane, and the motion is transmitted to an alarm-actuating switch after a predetermined time delay. The time
delay is accomplished by the use of an instantly recycling retard.
Unless otherwise noted in the listing, the flexible vane type is to be used with pipe having an inside diameter which corresponds to
Schedule 40 pipe for sizes up to and including 6 in. (152 mm) or Schedule 30 pipe for sizes 8 and 10 in. (203 and 254 mm).
Waterflow detectors should not be specified for those systems where the time duration of a pressure fluctuation is greater than the
retard time. Instantly recycling retards will not transmit an electrical alarm until the time duration of the pressure fluctuation or
waterflow past the vane of the flow detector has exceeded the predetermined time setting of 30-60 seconds. Unless otherwise noted
in the listing, these detectors have 175 psi (1205 kPa) rated working pressure.
Company Name: Shanghai Iron Man Fire Fighting Equipment Co., Ltd
Company Address: Room 716, 7F, No.100, Xiuyan Road, Shanghai 201315, P. R. China
Company Website: http://firefightingtool.com
New/Updated Product Listing: No
Listing Country: China
Certification Type: FM Approved
Page Bottom
Butterfly Valves
Pressure
Rating, psig Indicator Supervisory
Model Size, NPS Body Type (Bar) Post Switch*
Butterfly valve
"BR -DG 175" 2.5, 3, 4, 6, 8 Ductile Iron Groove d End 175 (12) — I
© 2013 UL LLC
W he n the UL Le a f Ma rk is on the product, or whe n the word "Environm e nt" is include d in the UL Mark , ple a se se arch the UL
Environm e nt da ta ba se for a dditiona l inform a tion re ga rding this product's ce rtification.
The appe a ra nce of a com pa ny's na m e or product in this database doe s not in itse lf a ssure that products so ide ntifie d have be e n
m anufa cture d unde r UL's Follow-Up Se rvice . O nly those products be a ring the UL Mark should be conside re d to be C e rtifie d and
cove re d unde r UL's Follow-Up Se rvice . Alwa ys look for the Ma rk on the product.
UL pe rm its the re production of the m a te ria l conta ine d in the O nline C e rtification Dire ctory subje ct to the following conditions: 1.
The Guide Inform a tion, Asse m blie s, C onstructions, De signs, Syste m s, and/or C e rtifications (file s) m ust be pre se nte d in the ir
e ntire ty a nd in a non-m isle a ding m a nne r, without a ny m a nipula tion of the data (or drawings). 2. The sta te m e nt "R e printe d from
the O nline C e rtifica tions Dire ctory with pe rm ission from UL" m ust a ppe ar adja ce nt to the e x tra cte d m a te ria l. In addition, the
re printe d m a te ria l m ust include a copyright notice in the following form at: "© 2013 UL LLC ".
Indicating Valves, Butterfly or Ball Type
Design features provide a dependable visible indication of the open position even at a distance. If excessive force is applied to the
handle, weakness-joints will break so as to preserve correct orientation between indicator and valve position. Valve and indicator
parts are so designed that they can be assembled only one way, always to give correct indication. All FM Approved indicating valves
turn clockwise to shut. They are small, lightweight, and, because of a resilient seat, are easy to operate. They are not subject to
sticking or dropped gates. They are not recommended for throttling service. Unless otherwise noted in the listing, these valves have
175 psi (1205 kPa) rated working pressure.
Model Nos. BR-HPG-300, BR-HPW-300, BR-DG 175, BR-DW 175, BR-FF-TH, BR-FF-G
Rated Working
Nominal Pipe
Model Number Product Type Pressure, Remarks
Size, mm
psi (kPa)
Remarks:
a. Available with dual supervisory switches.
b. FM Approved for indoor and outdoor service.
c. FM Approved for aboveground installations only.
Page Bottom
Check Valves
Swing type, Mode l BR -DGC -300, size s 2, 2-1/2, 3, 4, 5, 6 a nd 8 in., with re silie nt se at size for rate d pre ssure of 300 psig
horizonta l a nd ve rtica l installation.
© 2013 UL LLC
W he n the UL Le a f Ma rk is on the product, or whe n the word "Environm e nt" is include d in the UL Mark , ple a se se arch the UL
Environm e nt da ta ba se for a dditiona l inform a tion re ga rding this product's ce rtification.
The appe a ra nce of a com pa ny's na m e or product in this database doe s not in itse lf a ssure that products so ide ntifie d have be e n
m anufa cture d unde r UL's Follow-Up Se rvice . O nly those products be a ring the UL Mark should be conside re d to be C e rtifie d and
cove re d unde r UL's Follow-Up Se rvice . Alwa ys look for the Ma rk on the product.
UL pe rm its the re production of the m a te ria l conta ine d in the O nline C e rtification Dire ctory subje ct to the following conditions: 1.
The Guide Inform a tion, Asse m blie s, C onstructions, De signs, Syste m s, and/or C e rtifications (file s) m ust be pre se nte d in the ir
e ntire ty a nd in a non-m isle a ding m a nne r, without a ny m a nipula tion of the data (or drawings). 2. The sta te m e nt "R e printe d from
the O nline C e rtifica tions Dire ctory with pe rm ission from UL" m ust a ppe ar adja ce nt to the e x tra cte d m a te ria l. In addition, the
re printe d m a te ria l m ust include a copyright notice in the following form at: "© 2013 UL LLC ".
Single Check Valves
Single check valves are used in fire protection systems to allow waterflow in one direction only. Typical applications are at
connections between public water supplies and private fire service systems, at the discharge from fire pumps, at gravity tank
connections and at fire service pumper connections.
Valves identified in the listing by a single asterisk (*) have side covers; valves identified by a double asterisk (**) have no removable
covers; others have top covers. Clearance must be provided for side-cover valves to permit clapper removal. Valves without covers
must be removed from the system for clapper replacement or repair. Unless otherwise noted in the listing, these valves have 175 psi
(1205 kPa) rated working pressure.
BR-DGC-300
Max Working
Product Nominal Pipe
Description Pressure, psi Remarks
Designation Size, in.
(kPa)
a. Resilient Seat.
Model BF-VT001
Rated working
Size, Nominal
Model Designation pressure, Remarks
inch NPS K-factor (s)
psi (kPa)
175
BF-VT001 1, 1-1⁄4 5.6 a
(1205)
Remarks:
a. Devices supplied with female threaded inlet and a male threaded outlet end connection.
Page Bottom
Gate Valves
R e silie nt Se a te d Ga te Valve s.
Rated
End Pressure,
Pattern Model Size, in. Configuration psig
© 2013 UL LLC
W he n the UL Le a f Ma rk is on the product, or whe n the word "Environm e nt" is include d in the UL Mark , ple a se se arch the UL
Environm e nt da ta ba se for a dditiona l inform a tion re ga rding this product's ce rtification.
The appe a ra nce of a com pa ny's na m e or product in this database doe s not in itse lf a ssure that products so ide ntifie d have be e n
m anufa cture d unde r UL's Follow-Up Se rvice . O nly those products be a ring the UL Mark should be conside re d to be C e rtifie d and
cove re d unde r UL's Follow-Up Se rvice . Alwa ys look for the Ma rk on the product.
UL pe rm its the re production of the m a te ria l conta ine d in the O nline C e rtification Dire ctory subje ct to the following conditions: 1.
The Guide Inform a tion, Asse m blie s, C onstructions, De signs, Syste m s, and/or C e rtifications (file s) m ust be pre se nte d in the ir
e ntire ty a nd in a non-m isle a ding m a nne r, without a ny m a nipula tion of the data (or drawings). 2. The sta te m e nt "R e printe d from
the O nline C e rtifica tions Dire ctory with pe rm ission from UL" m ust a ppe ar adja ce nt to the e x tra cte d m a te ria l. In addition, the
re printe d m a te ria l m ust include a copyright notice in the following form at: "© 2013 UL LLC ".
Outside Screw and Yoke Gate Valves
Outside screw and yoke gate valves are recommended for service indoors and in pits outdoors. They are not recommended for
throttling service. The stem indicates at a glance whether or not the valve is open. Smaller sizes, 3⁄4 through 2 in. NPS inclusive, are
of bronze. Large sizes, 2 1⁄2 through 14 in. NPS inclusive, are of iron, bronze mounted. One manufacturer makes valves of bronze up
through the 3 in. size. Unless otherwise noted in the listing, these valves have 175 psi (1205 kPa) rated working pressure.
Size
End
Model in.
Connection
(mm)
Fig 2 Flange ×
No. 1/2, Flange
399F 3, 4,
5, 6,
8, 10,
12
(65,
80,
100,
125,
150,
200,
250,
300)
VQDI.EX4509
Valves, System Pressure Relief
Page Bottom
Model FP-53L-175 pressure relief valve, 1/2 in. NPT size for horizontal or vertical installation having a set pressure rating of 175 psig.
© 2017 UL LLC
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
the following format: "© 2017 UL LLC".
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=VQDI.EX4509&ccnshorttitle=Valves,+System+Pressure+Relief&… 1/1
11/10/2016 VLMT.EX2534 Special System Water Control Valves, Pressurereducing and Pressurecontrol Type
VLMT.EX2534
Special System Water Control Valves, Pressurereducing and Pressurecontrol
Type
Page Bottom
See General Information for Special System Water Control Valves, Pressurereducing and Pressurecontrol Type
"Clayton" , pilot operated pressure control valves, iron iron body, (sizes 11/2 to 8 in.), ductile iron body (sizes 11/2 to 8 in) and bronze body
(sizes 11/2 to 3 in.) consisting of the following models, sizes, inlet pressure ratings, and outlet pressure setting ranges:
"Clayton", pilot operated pressure control valves, steel body, (sizes 11/2 to 6 in.) ductile iron body (11/2 to 6 in.) and bronze body (sizes 1
1/2 to 3 in.) consisting of the following models, sizes, inlet pressure ratings, and outlet pressure setting ranges:
For all valves, the manufacturer's design and installation instructions include a description of the performance characteristics for both flow and
static conditions.
© 2016 UL LLC
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's FollowUp Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's FollowUp
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
the following format: "© 2016 UL LLC".
http://database.ul.com/cgibin/XYV/template/LISEXT/1FRAME/showpage.html?name=VLMT.EX2534&ccnshorttitle=Special+System+Water+Control+Valves,+… 1/1
VEHZ.EX15983
Drain Fittings, Special Type
Page Bottom
Mode l "BF-VT001" te st a nd dra in fitting in the following nom inal size s, discha rge coe fficie nts and rate d pre ssure s:
© 2013 UL LLC
W he n the UL Le a f Ma rk is on the product, or whe n the word "Environm e nt" is include d in the UL Mark , ple a se se arch the UL
Environm e nt da ta ba se for a dditiona l inform a tion re ga rding this product's ce rtification.
The appe a ra nce of a com pa ny's na m e or product in this database doe s not in itse lf a ssure that products so ide ntifie d have be e n
m anufa cture d unde r UL's Follow-Up Se rvice . O nly those products be a ring the UL Mark should be conside re d to be C e rtifie d and
cove re d unde r UL's Follow-Up Se rvice . Alwa ys look for the Ma rk on the product.
UL pe rm its the re production of the m a te ria l conta ine d in the O nline C e rtification Dire ctory subje ct to the following conditions: 1.
The Guide Inform a tion, Asse m blie s, C onstructions, De signs, Syste m s, and/or C e rtifications (file s) m ust be pre se nte d in the ir
e ntire ty a nd in a non-m isle a ding m a nne r, without a ny m a nipula tion of the data (or drawings). 2. The sta te m e nt "R e printe d from
the O nline C e rtifica tions Dire ctory with pe rm ission from UL" m ust a ppe ar adja ce nt to the e x tra cte d m a te ria l. In addition, the
re printe d m a te ria l m ust include a copyright notice in the following form at: "© 2013 UL LLC ".
USQT.S739 - Extinguishing System Attachments Page 1 of 2
USQT.S739
Extinguishing System Attachments
Page Bottom
Water-supply valve position signals, Models OSY2, PIBV2, suitable for outdoor use.
Wet-pipe sprinkler system attachments: Water-flow indicators (paddle type), suitable for indoor and outdoor installation.
Max Working
Model Size In. Pipe Schedule Pressure psig
2 Cast/Ductile 250
Iron
LFD30-2 3 40 450
The LFD Series waterflow indicators are low flow devices intended to operate between 1-3 gpm.
Wet-pipe sprinkler system attachments: Water-flow indicators (paddle type), suitable for indoor and outdoor installation shipped without "U"
bolts and nuts to Victaulic customer. Models may be single or bulk-packaged. The packing cartons will also include the assigned Victaulic Part Code
on the exterior.
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?nam... 11/05/2009
Electrical Signaling
Electrical protective signaling systems are configurations of components used to produce alarm signals indicative of fire, smoke,
sprinkler waterflow or other emergency and to produce supervisory signals indicative of conditions needing attention with respect to
protection equipment or watch service. System configurations are classified according to where and how the signals are received.
The categories are commonly designated as local, municipal, remote station, proprietary and central station. Auxiliary systems are
either local or proprietary systems interconnected with a municipal system.
This category presents the major system component categories and the integrated system configurations. The selection of
components to form a hybrid system should be made only by those skilled in system design. Also, the suitability of any system
application should be judged on the basis of the hazard(s) being protected.
Model 111.10SP.100
Air or Water Pressure Gauge - Model 111.10SP.100
• 0-300 psi (0-2068 kPa). 4 in. (100 mm) size, Plastic Case.
• 0-300 psi (0-2068 kPa). 4 in. (100 mm) size, Steel case with brass plated finish.
• 0-400 psi (0-2760 kPa). 4 in. (100 mm) size, Plastic Case.
• 0-400 psi (0-2760 kPa). 4 in. (100 mm) size, Steel case with brass plated finish.
• 0-600 psi (0-4140 kPa). 4 in. (100 mm) size, Plastic case.
• 0-600 psi (0-4140 kPa). 4 in. (100 mm) size, Steel case with brass plated finish.
VEVX.EX5232
Gauges, Pressure
Page Bottom
Gauges, Pressure
Bourdon spring type, Model 111.10, size 4 in. with dials graduated 0-300 psi, 0-400 psi and 0-80-250 (retard).
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Designs and/or Listings (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the
data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc." must
appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "Copyright ©
2010 Underwriters Laboratories Inc.®"
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=... 03/11/2010
VIII. Trade License
IX. Civil Defense Certificates
United Arab Emirates دوﻟﺔ اﻻﻣﺎرات اﻟﻌﺮﺑﻴﺔ اﻟﻤﺘﺤﺪة
General Department of Civil Defense - Sharjah اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ -اﻟﺸﺎرﻗﺔ
اﻻﺳﻢ اﻟﺘﺠﺎري ﻟﻠﻤﻨﺸﺄة :ﻧﻈﺮة اﻟﺨﻠﻴﺞ ﻟﺘﺠﺎرة اﺟﻬﺰة اﻻﻃﻔﺎء و ﻣﻜﺎﻓﺤﺔ اﻟﺤﺮﻳﻖ ذ.م.م رﻗﻢ اﻟﺘﺮﺧﻴﺺ 2013-3-59668 :
Agent Manufacturer ﺳﻨﺔ اﻟﺘﺮﺧﻴﺺ 2018 :
ﻋﺪد اﻟﺘﺮاﺧﻴﺺ 2 :
17/01/2019 Expiry date of theAgent : K36 Licence No. of theAgent : ﺑﺮﻳﺴﺘﻮل اﻧﺠﻨﻴﺮﻧﺞ Name of theAgent :
اﺳﻢ اﻟﻤﺨﺘﺒﺮ اﻟﺼﺎدر ﺗﺎرﻳﺦ اﻧﺘﻬﺎء ﻗﻴﺪ
رﻗﻢ ﺷﻬﺎدة اﻟﺴﻼﻣﺔ رﻗﻢ ﻗﻴﺪ اﻟﻮﻛﺎﻟﺔ اﺳﻢ اﻟﻤﺼﻨﻊ ﺑﻠﺪ اﻟﺼﻨﻊ اﻻﺳﻢ اﻟﺘﺠﺎري اﺳﻢ اﻟﻤﻌﺪة/اﻟﻤﻮاد/اﻟﻨﻈﺎم م
ﻟﻠﺸﻬﺎدة اﻟﻮﻛﺎﻟﺔ
BRE GLOBAL
TANDA Detection and fire alarm system : Unit
LTD, UNITED (1330D-(CL-1 16/08/2018 17745 China Tanda UK Limited
Technology co alarm sound
KINGDOM 7
رﻗﻢ اﻟﻤﻮدﻳﻞ :
Alarm Warning Device TX7300
UL,
Automatic sprinklers / hoses / point
UNDERWRITERS VICTAULIC United States of
VGYZ.EX15290 12/10/2018 10378 VICTAULIC water supply / water systems : Metal
LABORATORIES EUROPE America
connections
INC, USA
8رﻗﻢ اﻟﻤﻮدﻳﻞ :
V1201, V1202, V1203, V1204, V1205, V1206, V1207, V1208, V1211, V1212, V1213, V1214, V1215, V1216, V1217, V1218, V1221, V1222, V1223,
V1224, V1225, V1226, V1227, V1228, V1231, V1232, V1233, V1234, V1235, V1236, V1237, V1238, V1241, V1242, V1243, V1244, V1245, V1246,
V1247, V1248, V1251, V1252, V1253, V1254, V1255, V1256, V1257, V1258, V1261, V1262, V1263, V1264, V1265, V1266, V1267, V1268, V1271,
V1272, V1273, V1274, V1275, V1276, V1277, V1278,
UL,
Automatic sprinklers / hoses / point
UNDERWRITERS United States of
VUTX.EX2041 14/03/2018 11102 DIXON water supply / water systems : Ground
LABORATORIES America
valves 9
INC, USA
رﻗﻢ اﻟﻤﻮدﻳﻞ :
AVAPRF250-1
. 1ﻳﻌﺘﺒﺮ اﻟﻤﻮزع ﻣﺮﺧﺺ ﻣﻦ ﻗﺒﻞ اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ Sharjah -و ﻳﺤﻖ ﻟﻪ ﻣﺰاوﻟﺔ ﻧﺸﺎﻃﻪ ﻓﻲ إﻣﺎرة Sharjahﻓﻘﻂ ،اﺳﺘﻨﺎدا إﻟﻰ ﻗﺮار ﻣﺠﻠﺲ اﻟﻮزاري رﻗﻢ ) (24ﻟﺴﻨﺔ 2012ﻓﻲ ﺷﺄن ﺗﻨﻈﻴﻢ ﺧﺪﻣﺎت اﻟﺪﻓﺎع اﻟﻤﺪﻧﻲ
ﻣﻼﺣﻈﺔ :ﻟﻼﺋﺤﺔ اﻟﺘﻨﻔﻴﺬﻳﺔ رﻗﻢ ) (213ﻟﺴﻨﺔ ، 2017و ﻻ ﻳﺤﻖ ﻣﺰاوﻟﺔ أﻧﺸﻄﺘﻪ ﻓﻲ ﺑﺎﻗﻲ اﻹﻣﺎرات إﻻ ﺑﻌﺪ اﺳﺘﺨﺮاج ﺗﺮﺧﻴﺺ ﻣﻮزع ﻣﻦ ﻗﺒﻞ اﻹدارات اﻟﻌﺎﻣﺔ ذات اﻻﺧﺘﺼﺎص ﺑﻜﻞ إﻣﺎرة.
. 2إﺑﻼغ اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ ﻓﻲ ﺣﺎﻟﺔ ﺗﻐﻴﻴﺮ أو ﺗﻌﺪﻳﻞ ﻓﻲ اﻟﺒﻴﺎﻧﺎت اﻟﻤﺘﻌﻠﻘﺔ ﻓﻲ اﻟﺘﺮﺧﻴﺺ اﻟﺼﺎدر ﻣﻦ ﻗﺒﻞ اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ.
ﻳﻌﺘﻤﺪ/
Copy number 5 - 08/04/2018 - 0558921890 4/5
United Arab Emirates دوﻟﺔ اﻻﻣﺎرات اﻟﻌﺮﺑﻴﺔ اﻟﻤﺘﺤﺪة
General Department of Civil Defense - Sharjah اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ -اﻟﺸﺎرﻗﺔ
ﺗﻢ إﺻﺪار اﻟﺘﺮﺧﻴﺺ اﺳﺘﻨﺎدا إﻟﻰ اﻟﻘﺮار اﻟﻮزاري رﻗﻢ ) (24ﻟﺴﻨﺔ ، 2012ﻓﻲ ﺷﺄن ﺗﻨﻈﻴﻢ ﺧﺪﻣﺎت اﻟﺪﻓﺎع اﻟﻤﺪﻧﻲ
ﻧﻈﺮة اﻟﺨﻠﻴﺞ ﻟﺘﺠﺎرة اﺟﻬﺰة اﻻﻃﻔﺎء و اﻻﺳﻢ اﻟﺘﺠﺎري ﻟﻠﻤﻨﺸﺄة
2013-3-59668 رﻗﻢ اﻟﺴﺠﻞ 557284 رﻗﻢ اﻟﺮﺧﺼﺔ
ﻣﻜﺎﻓﺤﺔ اﻟﺤﺮﻳﻖ ذ.م.م
United Arab Emirates اﻟﺠﻨﺴﻴﺔ ﺷﻌﻴﺐ ﻋﺒﺪاﻟﻠﻪ ﻋﻠﻲ اﺣﻤﺪ اﺳﻢ ﺻﺎﺣﺐ اﻟﺘﺮﺧﻴﺺ
India اﻟﺠﻨﺴﻴﺔ راﺟﻨﺪرا ﻧﺎﺟﻴﻨﺪاس ﺧﺘﺮي ﻧﺎﺟﻴﻨﺪاس اﺳﻢ ﺻﺎﺣﺐ اﻟﺘﺮﺧﻴﺺ
India اﻟﺠﻨﺴﻴﺔ ﺑﻴﻨﺪو ﺟﻨﻐﻴﻨﻴﺎدان دﻳﻮﺳﻲ اﺳﻢ ﺻﺎﺣﺐ اﻟﺘﺮﺧﻴﺺ
Sharjah ﻣﻨﻄﻘﺔ اﻟﻨﺸﺎط ﺗﺠﺎرة ﻣﻮاد اﻃﻔﺎء اﻟﺤﺮﻳﻖ ﻧﻮع اﻟﻨﺸﺎط
73143 ص.ب 065610311 رﻗﻢ اﻟﻔﺎﻛﺲ 0508628851 رﻗﻢ اﻟﻬﺎﺗﻒ
ﻣﻜﺘﺐ رﻗﻢ 3ﻣﻠﻚ ﻓﺎﻃﻤﺔ ﻋﺒﺪاﻟﻠﻪ رﺣﻤﻪ اﻟﻌﻮﻳﺲ اﻟﺸﺎﻣﺴﻲ -ﺷﺎرع اﻟﺰﻫﺮاء Sharjah Sharjah Alsoor, , ﻋﻨﻮان اﻟﺸﺮﻛﺔ
www.gulfirevision.com gvfe2007@eim.ae اﻟﻤﻮﻗﻊ و اﻟﺒﺮﻳﺪ اﻹﻟﻜﺘﺮوﻧﻲ
17/01/2019 ﺗﺎرﻳﺦ اﻻﻧﺘﻬﺎء 04/04/2018 ﺗﺎرﻳﺦ اﻹﺻﺪار 29/11/2007 ﺗﺎرﻳﺦ ﺗﺄﺳﻴﺲ اﻟﻤﻨﺸﺄة
ﻋﺪد اﻟﻤﻌﺪات و اﻷﺟﻬﺰة اﻟﻤﺮاد ﺗﺮﺧﻴﺼﻬﺎ 10
ﻳﻌﺘﻤﺪ/
General Department of Civil Defense - Sharjah اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ -اﻟﺸﺎرﻗﺔ
اﻻﺳﻢ اﻟﺘﺠﺎري ﻟﻠﻤﻨﺸﺄة :ﻧﻈﺮة اﻟﺨﻠﻴﺞ ﻟﺘﺠﺎرة اﺟﻬﺰة اﻻﻃﻔﺎء و ﻣﻜﺎﻓﺤﺔ اﻟﺤﺮﻳﻖ ذ.م.م رﻗﻢ اﻟﺘﺮﺧﻴﺺ 2013-3-59668 :
Agent Manufacturer ﺳﻨﺔ اﻟﺘﺮﺧﻴﺺ 2018 :
ﻋﺪد اﻟﺘﺮاﺧﻴﺺ 2 :
17/01/2019 Expiry date of theAgent : K36 Licence No. of theAgent : ﺑﺮﻳﺴﺘﻮل اﻧﺠﻨﻴﺮﻧﺞ Name of theAgent :
اﺳﻢ اﻟﻤﺨﺘﺒﺮ اﻟﺼﺎدر ﺗﺎرﻳﺦ اﻧﺘﻬﺎء ﻗﻴﺪ
رﻗﻢ ﺷﻬﺎدة اﻟﺴﻼﻣﺔ رﻗﻢ ﻗﻴﺪ اﻟﻮﻛﺎﻟﺔ اﺳﻢ اﻟﻤﺼﻨﻊ ﺑﻠﺪ اﻟﺼﻨﻊ اﻻﺳﻢ اﻟﺘﺠﺎري اﺳﻢ اﻟﻤﻌﺪة/اﻟﻤﻮاد/اﻟﻨﻈﺎم م
ﻟﻠﺸﻬﺎدة اﻟﻮﻛﺎﻟﺔ
BRE GLOBAL
TANDA Detection and fire alarm system : Unit
LTD, UNITED (1330D-(CL-1 16/08/2018 17745 China Tanda UK Limited
Technology co alarm sound
KINGDOM 7
رﻗﻢ اﻟﻤﻮدﻳﻞ :
Alarm Warning Device TX7300
UL,
Automatic sprinklers / hoses / point
UNDERWRITERS VICTAULIC United States of
VGYZ.EX15290 12/10/2018 10378 VICTAULIC water supply / water systems : Metal
LABORATORIES EUROPE America
connections
INC, USA
8رﻗﻢ اﻟﻤﻮدﻳﻞ :
V1201, V1202, V1203, V1204, V1205, V1206, V1207, V1208, V1211, V1212, V1213, V1214, V1215, V1216, V1217, V1218, V1221, V1222, V1223,
V1224, V1225, V1226, V1227, V1228, V1231, V1232, V1233, V1234, V1235, V1236, V1237, V1238, V1241, V1242, V1243, V1244, V1245, V1246,
V1247, V1248, V1251, V1252, V1253, V1254, V1255, V1256, V1257, V1258, V1261, V1262, V1263, V1264, V1265, V1266, V1267, V1268, V1271,
V1272, V1273, V1274, V1275, V1276, V1277, V1278,
UL,
Automatic sprinklers / hoses / point
UNDERWRITERS United States of
VUTX.EX2041 14/03/2018 11102 DIXON water supply / water systems : Ground
LABORATORIES America
valves 9
INC, USA
رﻗﻢ اﻟﻤﻮدﻳﻞ :
AVAPRF250-1
. 1ﻳﻌﺘﺒﺮ اﻟﻤﻮزع ﻣﺮﺧﺺ ﻣﻦ ﻗﺒﻞ اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ Sharjah -و ﻳﺤﻖ ﻟﻪ ﻣﺰاوﻟﺔ ﻧﺸﺎﻃﻪ ﻓﻲ إﻣﺎرة Sharjahﻓﻘﻂ ،اﺳﺘﻨﺎدا إﻟﻰ ﻗﺮار ﻣﺠﻠﺲ اﻟﻮزاري رﻗﻢ ) (24ﻟﺴﻨﺔ 2012ﻓﻲ ﺷﺄن ﺗﻨﻈﻴﻢ ﺧﺪﻣﺎت اﻟﺪﻓﺎع اﻟﻤﺪﻧﻲ
ﻣﻼﺣﻈﺔ :ﻟﻼﺋﺤﺔ اﻟﺘﻨﻔﻴﺬﻳﺔ رﻗﻢ ) (213ﻟﺴﻨﺔ ، 2017و ﻻ ﻳﺤﻖ ﻣﺰاوﻟﺔ أﻧﺸﻄﺘﻪ ﻓﻲ ﺑﺎﻗﻲ اﻹﻣﺎرات إﻻ ﺑﻌﺪ اﺳﺘﺨﺮاج ﺗﺮﺧﻴﺺ ﻣﻮزع ﻣﻦ ﻗﺒﻞ اﻹدارات اﻟﻌﺎﻣﺔ ذات اﻻﺧﺘﺼﺎص ﺑﻜﻞ إﻣﺎرة.
. 2إﺑﻼغ اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ ﻓﻲ ﺣﺎﻟﺔ ﺗﻐﻴﻴﺮ أو ﺗﻌﺪﻳﻞ ﻓﻲ اﻟﺒﻴﺎﻧﺎت اﻟﻤﺘﻌﻠﻘﺔ ﻓﻲ اﻟﺘﺮﺧﻴﺺ اﻟﺼﺎدر ﻣﻦ ﻗﺒﻞ اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ.
ﻳﻌﺘﻤﺪ/
Copy number 5 - 08/04/2018 - 0558921890 4/5
X. Company Profile
Firefighting Solutions Provider
www.bristol-fire.com
BRISTOL Fire Engineering, part of the Concorde – Corodex Group (CCG), was
established in 1974 as a leading manufacturer of high quality Fire Fighting
Systems and Equipments. BRISTOL was one of the first fire fighting companies
to receive an ISO 9001 certification in the Middle East, placing a great emphasis
on achieving international and Third party approvals in all our product range
such as (Kite Mark, LPBC, UL listing and FM Approval). In addition, all our
products carry Civil Defense approvals in the market we operate in.
Integrity and Quality are ingrained in BRISTOL name. For over three decades,
Bristol related companies have consistently performed complex projects on
time and within the budget while never compromising quality.
Product range
Group Profile
CCG’s core values have been the cornerstone of what define us and what we
stand for. They are excellence, innovation, environment stewardship, and health
& safety.
Our Team
From relatively small team, Concorde-Corodex Group has vastly grown in size.
Presently, we have 920 total employees, amongst which are 322 Engineers,
Specialists, Chemists and other Technical Professionals.
Mission Statement
We shall provide timely and world class services that answer our clients'
business needs for Design, Manufacturing, Servicing and Trading.
In the same way we relate with our clients, so shall we relate with each other as
we promote an internal environment that foster professional growth.
In the attainment of this mission and for love of this country, we bind ourselves to
be the highest standards of competence, integrity and dedication.
Vision Statement
We are committed to deliver world class products in various business activities in
the fields of Designing, Manufacturing, Servicing and Trading.
We shall actively provide innovative and effective services to the consumers, with
customers' delight as our measure of success.
We are group of highly capable, skilled and dedicated people with creative and
noble ideas committed to build an organization we can be proud of.
• Abu Dhabi
• ICAD Mussafa
• Khalidiya
• Dubai
• Al Quoz
• Al Awir
• Sheikh Zayed
• Sharjah
• Al Ain
• Ras Al Khayma
Core Activities
Water Purification / Treatment Systems
Sewage Treatment Plants
Vacuum Sewer Systems
Operation & Maintenance
Electromechanical Services
Marine and Industrial Chemical Cleaning
Fire Fighting Equipments and Systems
Fire Protection and Safety
Machine Tools and Engineering Equipment
Scientific & Laboratory Equipment
Oilfield Equipment
Industrial Gases
Welding Equipment
Vehicle Manufacturing Division
Quality Policy
Environmental Policy
We, at Concorde-Corodex Group, are committed to provide quality products and
services in a manner that ensures a safe and healthy workplace for our
employees and minimizes our potential impact on the environment. We will
operate in compliance with ISO 14001: 2004 and all relevant environmental
legislations and will strive to use pollution prevention and environmental best
practices in all we do.
We are committed to continually improving our environmental performance
using the following measures:
Provide adequate control of the Health and Safety risks arising from our
work activities.
Consult with our workers and volunteers on matters affecting their Health
and Safety, including work related stress.
Provide and maintain safe plant and equipment.
Ensure safe handling and use of substances.
Provide training, information, instruction and supervision for workers to
ensure that they are aware of their individual OH&S obligations.
All works will be carried out in accordance with the requirements of OHSAS
18001:2007 and other relevant Health & Safety laws, Acts, Regulations, Codes
of Practice and Guidance Notes and ensure compliance to applicable laws where
the company subscribes to.
Management and supervisory staff have the responsibility for implementing this
policy throughout the company and must ensure that health and safety are
always given priority in planning day-to-day supervision of work.
This policy will be reviewed periodically and will be available to interested parties.
Group Members
• Concorde Trading Co, Abu Dhabi
For everything water related
• Concorde Agencies Est, Abu Dhabi
Fire protection and automation system
• Concorde Technical Est, Abu Dhabi
Fire Protection, Water and Wastewater Treatment, and Environmental
Specialists
• Corodex Trading Co, Dubai
For everything water related
• Corodex Agencies Est, Dubai
Fire protection and automation system
• Corodex Industries, Dubai
Water Purification and Wastewater Treatment Specialists
• Corodex Marine, Dubai
Step ahead in chemical cleaning
• Corodex Electromechanic, Dubai
Bringing Engineering Solutions to Life Vacuum Sewerage System Water
and Wastewater
Treatment Systems
• Bristol Fire Engineering, Dubai
Everything Fire Related
• Al Jaddaf Electromechanical, Abu Dhabi
Fire Protection, Water and Wastewater Treatment, and Environmental
Specialists
• EFLO International, United Kingdom
Wastewater Treatment Specialists
• Bristol Gases, Dubai
Industrial Gases
• Dubai Industrial Gases, Sharjah
Industrial Gases
XI. Project List
LOCAL DIVISION
PROJECT LIST
Fire Fighting
Al Badr Cont. & Civil Construction Co.
1 M/229 Scada CEC Consistent Engineering Consultant Equipments + Deluge
L.L.C
Valve & Pumps
Water Front Madinat Al
Fire Fighting
2 Arab -‐ Badrah District A Mammut Contracting Co. L.L.C Woods & Bagot
Equipments
Building
3 DEWA Warehouse BAUR Electrical Middle East L.L.C A & Z Architectural Eng'g Const. Warehouse
Fire Fighting
Qassimy Maternity Hospital
4 Ali Moosa & Sons Contracting UPA Urbanism Planning Architecture Equipments + Pumps,
& Emergency Extension
preaction, Foam
Fire Fighting
B+G+12 Building @ Al
5 Air Technic A/C System Co. L.L.C Asri -‐ Al Asri Eng'g Consultant Equipments + Pumps,
Nahda P240
preaction, Foam
2B +G+8 Building @ Al Fire Fighting
6 Air Technic A/C System Co. L.L.C Al Hawraa -‐ Eng'g Consultant
Barsha 3rd P239 Equipments
Fakhrudeen Towers
FM200 and Suppressiion
10 Located at Business Bay, Radiant Technical Works L.L.C NEB National Engineering
& Fire Fighting System
Dubai
Botanica Tower on Plot no.
Fire Fighting
11 392-‐279, @ Dubai Marina, Radiant Technical Works L.L.C NEB National Engineering
Equipments
Dubai
Building on Plot BB.A03.039
Fire Fighting
12 @ Business Bay Radiant Technical Works L.L.C NEB National Engineering
Equipments
3B+G+3P+HC+18 Floors
LOCAL DIVISION
PROJECT LIST
Expansion work of
14 Zulekha Hospital, Sharjah MAS Co. L.L.C Winner Consultants Engineers Zulekha Hospital,
Sharjah
Al Rayyan Project -‐ Golf
15 Gardens Residential GISCO (Gulf Industrial Services Co.) Ehav Engineering Consultant FM200 System
Community Project, Plot P-
Fire Fighting
16 Marasy -‐ Abu dhabi GISCO (Gulf Industrial Services Co.) Ehav Engineering Consultant
Equipments
Fire Fighting
18 Al Qassimi Hospital, Sharjah Ali Moosa & Sons Ali Moosa & Sons
Equipments
Fire Fighting
20 Dubai waterfront Project Mammut Contracting LLC Mammut Contracting LLC
Equipments
2B+G+3P+12F
Fire Fighting
21 HOTEL+MF+22R+MF+HC@Du Prime Star Prime Star
Equipments
bai
2B+G+31+MECHANICAL
Fire Fighting
22 FLOOR ON PLOT # 392-‐467 Prime Star Prime Star
Equipments
,
Fire Fighting
23 Honda Showroom, Sharjah Al Futtaim Engineering Al Futtaim Engineering
Equipments
Fire Fighting
25 Dubai Festival City Dubai Festival City LLC Online Architects
Equipments
Fire Fighting
27 Al Farazdaq School Abu Dhabi Education Council Urbanism Planning Architecture
Equipments
Al Qassimi Maternity
Fire Fighting
28 Hospital & Emergency Ministry of Public Works UAE Urbanism Planning Architecture
Equipments
Extension
Fire Fighting
29 B+G+14+HC Mazaya Avenue Barajeel
Equipments
Fire Fighting
31 AL FUTTAIM AVENUE RETAIL Al FUTTAIM DEWAN
Equipments
Fire Fighting
32 ASWAR-‐WADI SFINI MINISTRY OF PUBLIC WORK
Equipments
Fire Fighting
34 G+50 ASSAS TOWER MS./SHARJAH ISLAMIC BANK GULF International
Equipments
2B+G+7typ+HC @ Al
53 Power Factor Adnan Saffarini FF System
mankhool Dubai
COMMANDS OF MILITARY
70 EMIRATES CODE CONTRACTING CO. N/A FF System
WORKS
COMMANDS OF MILITARY
74 EMIRATES CODE CONTRACTING CO. N/A FF System
WORKS
WAREHOUSE IN SHARJAH
75 AL BASHAER SECURITY & SAFETY N/A FF System
FREEZONE
COMMANDS OF MILITARY
76 CODE CONTRACTING CO. LLC N/A FF System
WORKS
78 Residential Building STARS FIRE & SAFETY EQUIPMENT EST. N/A FF System
100 Residential Building HIGHWAY FIRE & SAFETY EQPT. N/A FF System
COMMANDS OF MILITARY
112 WORKS -‐ MAHAWI CAMP - BIN OMAIR ELECTROMECHANICAL N/A FF System
‐ AD
MR. ISSA AL KHAILI TOWER @
113 REEM CAPITAL CONTRACTING N/A FF System
BUS. BAY -‐ DXB