TECHNICAL SUBMITTAL

FIRE FIGHTING EQUIPMENT

Project:
G+5P+HC+17TYP+ROOF COMMERCIAL / RESIDENTIALBUILDING
Plot No. 78 AL MAJAZ 1-KING FAISAL ROAD,SHARJAH, UAE
Client:
ASAS REAL ESTATE
Consultant:
NATIONAL ENGINEERING BUREAU (NEB)
Main Contractor:
AL QABDAH GLOBAL BUILDING CONTRACTING LLC
MEP Contractor:
TORQUE ELECTRO MECHANICAL WORKS

BSPKFMFE-01042018
Rev.02
Issue Date: 28062018
TECHNICAL SUBMITTAL
INDEX
FIRE FIGHTING EQUIPMENT

I. Consultant Comments……………………………………………………………………………….. 1
II. Reply to Consultant Comments………………………………………………………………….. 2
III. Project Details……………………………………………………………………………………………. 3
IV. Project Specification & Compliance Statement…………………………………..……… 4

V. Technical Datasheet & Catalogue


A. Fire Cabinet …………………………………………………………………..………………………….…… 5
B. Fire Hose Reel (Auto BF‐AS‐002)……………………….…..………………………………………………… 6
C. 1" Pressure Reducing Valve (BFE06068)…………………………………………………………………. 7
D. 1" Lock Shield Valve (BFE06‐039‐00A)………………………..…………………………………………….. 7
E. Fire Hose (BF‐SJ‐002)……………………………………………………………………………………...……… 8
F. Pressure Restricting Landing Valve (Dixon AVAPRF250‐I) ……………………………………………. 9
G. DCP Fire Extinguisher (DP1/2/4/6/9/12) ……………………………………………………………….… 10
H. CO Fire Extinguisher (CD2/5) ….…………………………………………………………………………… 10
I. 1" Air Release Valve (BFE090203)………………………………………….……………………………….. 11
J. Fire Blanket (FGC12)………….…………………………………………….…………………………………. 12
K. Breeching Inlet (BFE‐4WBI) ………………………….…………………….………………………………… 13
L. Breeching Inlet Cabinet ………..……..….…………….………………………………………………… 13
M. Non Return Valve (BR‐DGC‐300) ……………………………………………………………………………… 14
N. OS&Y Gate Valve (399F) ………...…………………………………………………………………………… 15
O. OSY2 Tamper Switch (OSY2) ………..….…………………………………………………………………. 15
P. Pressure Reducing Valve (90‐21) ………..….…………………………………………………………… 16
Q. Pressure Relief Valve (FP53L) ………..….……………………………………..………………………… 17
R. Water Pressure Gauge (111.10SP) ………………………………………………………….…….……… 18

VI. Method of Statement…………………………………….…………………………………………….. 19


VII. Approval Certificate…………………………………………………………………………………….. 20
VIII. Trade License……………………………………………………………………………………………….. 21
IX. DCD Certificates……………………………………………………………………………………………. 22
X. Company Profile………………………………………………………………………………………….. 23
XI. Project List …………………………………………………………………………………………………. 24
XII. Approval Copies………………………………………………………………………………………….. 25
I. Consultant Comments
II. Reply to Consultant Comments
‫‪United Arab Emirates‬‬ ‫دوﻟﺔ اﻻﻣﺎرات اﻟﻌﺮﺑﻴﺔ اﻟﻤﺘﺤﺪة‬

‫‪Ministry of Interior‬‬ ‫وزارة اﻟﺪاﺧﻠﻴﺔ‬

‫‪General Directorate of Civil Defense‬‬ ‫اﻟﻘﻴﺎدة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ‬

‫‪General Department of Civil Defense - Sharjah‬‬ ‫اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ ‪ -‬اﻟﺸﺎرﻗﺔ‬

‫اﻻﺳﻢ اﻟﺘﺠﺎري ﻟﻠﻤﻨﺸﺄة ‪ :‬ﻧﻈﺮة اﻟﺨﻠﻴﺞ ﻟﺘﺠﺎرة اﺟﻬﺰة اﻻﻃﻔﺎء و ﻣﻜﺎﻓﺤﺔ اﻟﺤﺮﻳﻖ ذ‪.‬م‪.‬م‬ ‫رﻗﻢ اﻟﺘﺮﺧﻴﺺ ‪2013-3-59668 :‬‬
‫‪Agent‬‬ ‫‪Manufacturer‬‬ ‫ﺳﻨﺔ اﻟﺘﺮﺧﻴﺺ ‪2018 :‬‬
‫ﻋﺪد اﻟﺘﺮاﺧﻴﺺ ‪2 :‬‬
‫‪17/01/2019‬‬ ‫‪Expiry date of theAgent :‬‬ ‫‪K36‬‬ ‫‪Licence No. of theAgent :‬‬ ‫ﺑﺮﻳﺴﺘﻮل اﻧﺠﻨﻴﺮﻧﺞ‬ ‫‪Name of theAgent :‬‬
‫اﺳﻢ اﻟﻤﺨﺘﺒﺮ اﻟﺼﺎدر‬ ‫ﺗﺎرﻳﺦ اﻧﺘﻬﺎء ﻗﻴﺪ‬
‫رﻗﻢ ﺷﻬﺎدة اﻟﺴﻼﻣﺔ‬ ‫رﻗﻢ ﻗﻴﺪ اﻟﻮﻛﺎﻟﺔ‬ ‫اﺳﻢ اﻟﻤﺼﻨﻊ‬ ‫ﺑﻠﺪ اﻟﺼﻨﻊ‬ ‫اﻻﺳﻢ اﻟﺘﺠﺎري‬ ‫اﺳﻢ اﻟﻤﻌﺪة‪/‬اﻟﻤﻮاد‪/‬اﻟﻨﻈﺎم‬ ‫م‬
‫ﻟﻠﺸﻬﺎدة‬ ‫اﻟﻮﻛﺎﻟﺔ‬

‫‪BRE GLOBAL‬‬
‫‪TANDA‬‬ ‫‪Detection and fire alarm system : Unit‬‬
‫‪LTD, UNITED‬‬ ‫‪(1330D-(CL-1‬‬ ‫‪16/08/2018‬‬ ‫‪17745‬‬ ‫‪China‬‬ ‫‪Tanda UK Limited‬‬
‫‪Technology co‬‬ ‫‪alarm sound‬‬
‫‪KINGDOM‬‬ ‫‪7‬‬
‫رﻗﻢ اﻟﻤﻮدﻳﻞ ‪:‬‬
‫‪Alarm Warning Device TX7300‬‬
‫‪UL,‬‬
‫‪Automatic sprinklers / hoses / point‬‬
‫‪UNDERWRITERS‬‬ ‫‪VICTAULIC‬‬ ‫‪United States of‬‬
‫‪VGYZ.EX15290‬‬ ‫‪12/10/2018‬‬ ‫‪10378‬‬ ‫‪VICTAULIC‬‬ ‫‪water supply / water systems : Metal‬‬
‫‪LABORATORIES‬‬ ‫‪EUROPE‬‬ ‫‪America‬‬
‫‪connections‬‬
‫‪INC, USA‬‬
‫‪ 8‬رﻗﻢ اﻟﻤﻮدﻳﻞ ‪:‬‬
‫‪V1201, V1202, V1203, V1204, V1205, V1206, V1207, V1208, V1211, V1212, V1213, V1214, V1215, V1216, V1217, V1218, V1221, V1222, V1223,‬‬
‫‪V1224, V1225, V1226, V1227, V1228, V1231, V1232, V1233, V1234, V1235, V1236, V1237, V1238, V1241, V1242, V1243, V1244, V1245, V1246,‬‬
‫‪V1247, V1248, V1251, V1252, V1253, V1254, V1255, V1256, V1257, V1258, V1261, V1262, V1263, V1264, V1265, V1266, V1267, V1268, V1271,‬‬
‫‪V1272, V1273, V1274, V1275, V1276, V1277, V1278,‬‬
‫‪UL,‬‬
‫‪Automatic sprinklers / hoses / point‬‬
‫‪UNDERWRITERS‬‬ ‫‪United States of‬‬
‫‪VUTX.EX2041‬‬ ‫‪14/03/2018‬‬ ‫‪11102‬‬ ‫‪DIXON‬‬ ‫‪water supply / water systems : Ground‬‬
‫‪LABORATORIES‬‬ ‫‪America‬‬
‫‪valves‬‬ ‫‪9‬‬
‫‪INC, USA‬‬
‫رﻗﻢ اﻟﻤﻮدﻳﻞ ‪:‬‬
‫‪AVAPRF250-1‬‬

‫‪ . 1‬ﻳﻌﺘﺒﺮ اﻟﻤﻮزع ﻣﺮﺧﺺ ﻣﻦ ﻗﺒﻞ اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ‪ Sharjah -‬و ﻳﺤﻖ ﻟﻪ ﻣﺰاوﻟﺔ ﻧﺸﺎﻃﻪ ﻓﻲ إﻣﺎرة ‪ Sharjah‬ﻓﻘﻂ‪ ،‬اﺳﺘﻨﺎدا إﻟﻰ ﻗﺮار ﻣﺠﻠﺲ اﻟﻮزاري رﻗﻢ )‪ (24‬ﻟﺴﻨﺔ ‪ 2012‬ﻓﻲ ﺷﺄن ﺗﻨﻈﻴﻢ ﺧﺪﻣﺎت اﻟﺪﻓﺎع اﻟﻤﺪﻧﻲ‬
‫ﻣﻼﺣﻈﺔ‪ :‬ﻟﻼﺋﺤﺔ اﻟﺘﻨﻔﻴﺬﻳﺔ رﻗﻢ )‪ (213‬ﻟﺴﻨﺔ ‪ ، 2017‬و ﻻ ﻳﺤﻖ ﻣﺰاوﻟﺔ أﻧﺸﻄﺘﻪ ﻓﻲ ﺑﺎﻗﻲ اﻹﻣﺎرات إﻻ ﺑﻌﺪ اﺳﺘﺨﺮاج ﺗﺮﺧﻴﺺ ﻣﻮزع ﻣﻦ ﻗﺒﻞ اﻹدارات اﻟﻌﺎﻣﺔ ذات اﻻﺧﺘﺼﺎص ﺑﻜﻞ إﻣﺎرة‪.‬‬
‫‪ . 2‬إﺑﻼغ اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ ﻓﻲ ﺣﺎﻟﺔ ﺗﻐﻴﻴﺮ أو ﺗﻌﺪﻳﻞ ﻓﻲ اﻟﺒﻴﺎﻧﺎت اﻟﻤﺘﻌﻠﻘﺔ ﻓﻲ اﻟﺘﺮﺧﻴﺺ اﻟﺼﺎدر ﻣﻦ ﻗﺒﻞ اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ‪.‬‬

‫ﻳﻌﺘﻤﺪ‪/‬‬
‫‪Copy number 5 - 08/04/2018 - 0558921890‬‬ ‫‪4/5‬‬
‫‪United Arab Emirates‬‬ ‫دوﻟﺔ اﻻﻣﺎرات اﻟﻌﺮﺑﻴﺔ اﻟﻤﺘﺤﺪة‬

‫‪Ministry of Interior‬‬ ‫وزارة اﻟﺪاﺧﻠﻴﺔ‬

‫‪General Directorate of Civil Defense‬‬ ‫اﻟﻘﻴﺎدة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ‬

‫‪General Department of Civil Defense - Sharjah‬‬ ‫اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ ‪ -‬اﻟﺸﺎرﻗﺔ‬

‫رﻗﻢ اﻟﺘﺮﺧﻴﺺ ‪2013-3-59668 :‬‬

‫ﺗﺮﺧﻴﺺ ﻣﻮزع‬ ‫ﺳﻨﺔ اﻟﺘﺮﺧﻴﺺ ‪2018 :‬‬

‫‪Agent‬‬ ‫‪Manufacturer‬‬ ‫ﻋﺪد اﻟﺘﺮاﺧﻴﺺ ‪2 :‬‬

‫ﺗﻢ إﺻﺪار اﻟﺘﺮﺧﻴﺺ اﺳﺘﻨﺎدا إﻟﻰ اﻟﻘﺮار اﻟﻮزاري رﻗﻢ )‪ (24‬ﻟﺴﻨﺔ ‪ ، 2012‬ﻓﻲ ﺷﺄن ﺗﻨﻈﻴﻢ ﺧﺪﻣﺎت اﻟﺪﻓﺎع اﻟﻤﺪﻧﻲ‬
‫ﻧﻈﺮة اﻟﺨﻠﻴﺞ ﻟﺘﺠﺎرة اﺟﻬﺰة اﻻﻃﻔﺎء و‬ ‫اﻻﺳﻢ اﻟﺘﺠﺎري ﻟﻠﻤﻨﺸﺄة‬
‫‪2013-3-59668‬‬ ‫رﻗﻢ اﻟﺴﺠﻞ‬ ‫‪557284‬‬ ‫رﻗﻢ اﻟﺮﺧﺼﺔ‬
‫ﻣﻜﺎﻓﺤﺔ اﻟﺤﺮﻳﻖ ذ‪.‬م‪.‬م‬
‫‪United Arab Emirates‬‬ ‫اﻟﺠﻨﺴﻴﺔ‬ ‫ﺷﻌﻴﺐ ﻋﺒﺪاﻟﻠﻪ ﻋﻠﻲ اﺣﻤﺪ‬ ‫اﺳﻢ ﺻﺎﺣﺐ اﻟﺘﺮﺧﻴﺺ‬
‫‪India‬‬ ‫اﻟﺠﻨﺴﻴﺔ‬ ‫راﺟﻨﺪرا ﻧﺎﺟﻴﻨﺪاس ﺧﺘﺮي ﻧﺎﺟﻴﻨﺪاس‬ ‫اﺳﻢ ﺻﺎﺣﺐ اﻟﺘﺮﺧﻴﺺ‬
‫‪India‬‬ ‫اﻟﺠﻨﺴﻴﺔ‬ ‫ﺑﻴﻨﺪو ﺟﻨﻐﻴﻨﻴﺎدان دﻳﻮﺳﻲ‬ ‫اﺳﻢ ﺻﺎﺣﺐ اﻟﺘﺮﺧﻴﺺ‬
‫‪Sharjah‬‬ ‫ﻣﻨﻄﻘﺔ اﻟﻨﺸﺎط‬ ‫ﺗﺠﺎرة ﻣﻮاد اﻃﻔﺎء اﻟﺤﺮﻳﻖ‬ ‫ﻧﻮع اﻟﻨﺸﺎط‬
‫‪73143‬‬ ‫ص‪.‬ب‬ ‫‪065610311‬‬ ‫رﻗﻢ اﻟﻔﺎﻛﺲ‬ ‫‪0508628851‬‬ ‫رﻗﻢ اﻟﻬﺎﺗﻒ‬
‫ﻣﻜﺘﺐ رﻗﻢ ‪ 3‬ﻣﻠﻚ ﻓﺎﻃﻤﺔ ﻋﺒﺪاﻟﻠﻪ رﺣﻤﻪ اﻟﻌﻮﻳﺲ اﻟﺸﺎﻣﺴﻲ ‪ -‬ﺷﺎرع اﻟﺰﻫﺮاء ‪Sharjah Sharjah Alsoor, ,‬‬ ‫ﻋﻨﻮان اﻟﺸﺮﻛﺔ‬
‫‪www.gulfirevision.com gvfe2007@eim.ae‬‬ ‫اﻟﻤﻮﻗﻊ و اﻟﺒﺮﻳﺪ اﻹﻟﻜﺘﺮوﻧﻲ‬
‫‪17/01/2019‬‬ ‫ﺗﺎرﻳﺦ اﻻﻧﺘﻬﺎء‬ ‫‪04/04/2018‬‬ ‫ﺗﺎرﻳﺦ اﻹﺻﺪار‬ ‫‪29/11/2007‬‬ ‫ﺗﺎرﻳﺦ ﺗﺄﺳﻴﺲ اﻟﻤﻨﺸﺄة‬
‫ﻋﺪد اﻟﻤﻌﺪات و اﻷﺟﻬﺰة اﻟﻤﺮاد ﺗﺮﺧﻴﺼﻬﺎ ‪10‬‬

‫ﻳﻌﺘﻤﺪ‪/‬‬

‫‪Copy number 5 - 08/04/2018 - 0558921890‬‬ ‫‪1/5‬‬


‫‪United Arab Emirates‬‬ ‫دوﻟﺔ اﻻﻣﺎرات اﻟﻌﺮﺑﻴﺔ اﻟﻤﺘﺤﺪة‬

‫‪Ministry of Interior‬‬ ‫وزارة اﻟﺪاﺧﻠﻴﺔ‬

‫‪General Directorate of Civil Defense‬‬ ‫اﻟﻘﻴﺎدة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ‬

‫‪General Department of Civil Defense - Sharjah‬‬ ‫اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ ‪ -‬اﻟﺸﺎرﻗﺔ‬

‫اﻻﺳﻢ اﻟﺘﺠﺎري ﻟﻠﻤﻨﺸﺄة ‪ :‬ﻧﻈﺮة اﻟﺨﻠﻴﺞ ﻟﺘﺠﺎرة اﺟﻬﺰة اﻻﻃﻔﺎء و ﻣﻜﺎﻓﺤﺔ اﻟﺤﺮﻳﻖ ذ‪.‬م‪.‬م‬ ‫رﻗﻢ اﻟﺘﺮﺧﻴﺺ ‪2013-3-59668 :‬‬
‫‪Agent‬‬ ‫‪Manufacturer‬‬ ‫ﺳﻨﺔ اﻟﺘﺮﺧﻴﺺ ‪2018 :‬‬
‫ﻋﺪد اﻟﺘﺮاﺧﻴﺺ ‪2 :‬‬
‫‪17/01/2019‬‬ ‫‪Expiry date of theAgent :‬‬ ‫‪K36‬‬ ‫‪Licence No. of theAgent :‬‬ ‫ﺑﺮﻳﺴﺘﻮل اﻧﺠﻨﻴﺮﻧﺞ‬ ‫‪Name of theAgent :‬‬
‫اﺳﻢ اﻟﻤﺨﺘﺒﺮ اﻟﺼﺎدر‬ ‫ﺗﺎرﻳﺦ اﻧﺘﻬﺎء ﻗﻴﺪ‬
‫رﻗﻢ ﺷﻬﺎدة اﻟﺴﻼﻣﺔ‬ ‫رﻗﻢ ﻗﻴﺪ اﻟﻮﻛﺎﻟﺔ‬ ‫اﺳﻢ اﻟﻤﺼﻨﻊ‬ ‫ﺑﻠﺪ اﻟﺼﻨﻊ‬ ‫اﻻﺳﻢ اﻟﺘﺠﺎري‬ ‫اﺳﻢ اﻟﻤﻌﺪة‪/‬اﻟﻤﻮاد‪/‬اﻟﻨﻈﺎم‬ ‫م‬
‫ﻟﻠﺸﻬﺎدة‬ ‫اﻟﻮﻛﺎﻟﺔ‬

‫‪BRE GLOBAL‬‬
‫‪TANDA‬‬ ‫‪Detection and fire alarm system : Unit‬‬
‫‪LTD, UNITED‬‬ ‫‪(1330D-(CL-1‬‬ ‫‪16/08/2018‬‬ ‫‪17745‬‬ ‫‪China‬‬ ‫‪Tanda UK Limited‬‬
‫‪Technology co‬‬ ‫‪alarm sound‬‬
‫‪KINGDOM‬‬ ‫‪7‬‬
‫رﻗﻢ اﻟﻤﻮدﻳﻞ ‪:‬‬
‫‪Alarm Warning Device TX7300‬‬
‫‪UL,‬‬
‫‪Automatic sprinklers / hoses / point‬‬
‫‪UNDERWRITERS‬‬ ‫‪VICTAULIC‬‬ ‫‪United States of‬‬
‫‪VGYZ.EX15290‬‬ ‫‪12/10/2018‬‬ ‫‪10378‬‬ ‫‪VICTAULIC‬‬ ‫‪water supply / water systems : Metal‬‬
‫‪LABORATORIES‬‬ ‫‪EUROPE‬‬ ‫‪America‬‬
‫‪connections‬‬
‫‪INC, USA‬‬
‫‪ 8‬رﻗﻢ اﻟﻤﻮدﻳﻞ ‪:‬‬
‫‪V1201, V1202, V1203, V1204, V1205, V1206, V1207, V1208, V1211, V1212, V1213, V1214, V1215, V1216, V1217, V1218, V1221, V1222, V1223,‬‬
‫‪V1224, V1225, V1226, V1227, V1228, V1231, V1232, V1233, V1234, V1235, V1236, V1237, V1238, V1241, V1242, V1243, V1244, V1245, V1246,‬‬
‫‪V1247, V1248, V1251, V1252, V1253, V1254, V1255, V1256, V1257, V1258, V1261, V1262, V1263, V1264, V1265, V1266, V1267, V1268, V1271,‬‬
‫‪V1272, V1273, V1274, V1275, V1276, V1277, V1278,‬‬
‫‪UL,‬‬
‫‪Automatic sprinklers / hoses / point‬‬
‫‪UNDERWRITERS‬‬ ‫‪United States of‬‬
‫‪VUTX.EX2041‬‬ ‫‪14/03/2018‬‬ ‫‪11102‬‬ ‫‪DIXON‬‬ ‫‪water supply / water systems : Ground‬‬
‫‪LABORATORIES‬‬ ‫‪America‬‬
‫‪valves‬‬ ‫‪9‬‬
‫‪INC, USA‬‬
‫رﻗﻢ اﻟﻤﻮدﻳﻞ ‪:‬‬
‫‪AVAPRF250-1‬‬

‫‪ . 1‬ﻳﻌﺘﺒﺮ اﻟﻤﻮزع ﻣﺮﺧﺺ ﻣﻦ ﻗﺒﻞ اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ‪ Sharjah -‬و ﻳﺤﻖ ﻟﻪ ﻣﺰاوﻟﺔ ﻧﺸﺎﻃﻪ ﻓﻲ إﻣﺎرة ‪ Sharjah‬ﻓﻘﻂ‪ ،‬اﺳﺘﻨﺎدا إﻟﻰ ﻗﺮار ﻣﺠﻠﺲ اﻟﻮزاري رﻗﻢ )‪ (24‬ﻟﺴﻨﺔ ‪ 2012‬ﻓﻲ ﺷﺄن ﺗﻨﻈﻴﻢ ﺧﺪﻣﺎت اﻟﺪﻓﺎع اﻟﻤﺪﻧﻲ‬
‫ﻣﻼﺣﻈﺔ‪ :‬ﻟﻼﺋﺤﺔ اﻟﺘﻨﻔﻴﺬﻳﺔ رﻗﻢ )‪ (213‬ﻟﺴﻨﺔ ‪ ، 2017‬و ﻻ ﻳﺤﻖ ﻣﺰاوﻟﺔ أﻧﺸﻄﺘﻪ ﻓﻲ ﺑﺎﻗﻲ اﻹﻣﺎرات إﻻ ﺑﻌﺪ اﺳﺘﺨﺮاج ﺗﺮﺧﻴﺺ ﻣﻮزع ﻣﻦ ﻗﺒﻞ اﻹدارات اﻟﻌﺎﻣﺔ ذات اﻻﺧﺘﺼﺎص ﺑﻜﻞ إﻣﺎرة‪.‬‬
‫‪ . 2‬إﺑﻼغ اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ ﻓﻲ ﺣﺎﻟﺔ ﺗﻐﻴﻴﺮ أو ﺗﻌﺪﻳﻞ ﻓﻲ اﻟﺒﻴﺎﻧﺎت اﻟﻤﺘﻌﻠﻘﺔ ﻓﻲ اﻟﺘﺮﺧﻴﺺ اﻟﺼﺎدر ﻣﻦ ﻗﺒﻞ اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ‪.‬‬

‫ﻳﻌﺘﻤﺪ‪/‬‬
‫‪Copy number 5 - 08/04/2018 - 0558921890‬‬ ‫‪4/5‬‬
III. Project Details

Project:
G+5P+HC+17TYP+ROOF COMMERCIAL / RESIDENTIAL BUILDING
Plot No:
78 AL MAJAZ 1-KING FAISAL ROAD,SHARJAH, UAE
Client:
ASAS REAL ESTATE
Consultant:
NATIONAL ENGINEERING BUREAU (NEB)
Main Contractor:
AL QABDAH GLOBAL BUILDING CONTRACTING LLC
MEP Contractor:
TORQUE ELECTRO MECHANICAL WORKS
IV. Project Specification & Compliance Statement
V. Technical Data Sheets and Catalogue
A.Bristol Fire Cabinets
...Technical Data Sheets and Catalogue
B. Fire Hose Reel
Swinging Type Fire Hose Reels
EN 671-1 Cert No. 1226a

LPCB Approved

Model BF-MS-001 BF-AS-002 BF-MS-003 BF-AS-004

DN 1” ¾”
Hose
Length 30m

Mechanism Manual Automatic Manual Automatic


Specifications

Hose Material Double Braided Polyester Cord-Reinforced Rubber

Drum Material Powder Coated Mild Steel

Test Pressure 300psi

Accessories Included Nozzle, Ball Valve, Mounting Bracket

Optional Accessories Lockshield Valve, Pressure-Reducing Valve


...Technical Data Sheets and Catalogue
C. Lock Shield Valve
D. Pressure Reducing Valve
Other Valves

Pressure-Reducing Valve
Model BFE06068

DN 1”
Inlet/Outlet
Type M BSPT

Body Material Brass / Chrome Plated


Specifications

Working Pressure 16bar

Test Pressure 24bar


...Technical Data Sheets and Catalogue
E. Bristol Fire Hose
Fire Hoses
Fire Hoses are high pressure hoses that carry water or other fire retardant such as foam from the supply to
the fire to be extinguished. BRISTOL Fire Hoses comply come in different sizes, length and assemblies, and
comply to both international and local standards. BRISTOL also offers accessories that complement these
hoses.

9
Single/Double Jacket Fire Hose
EX16027

UL Listed, with 2 1/2” Aluminium Coupling

BRISTOL Fire Hoses are made with polyester and its inner-lining with EPDM to ensure low friction loss and maximum flow while maintaining
high durability.

Features
- Strong and Highly Protected
- Abrasion and puncture resistant

- Chemical Resistance
- Resists contact with oil, hydrocarbons, alkalis, salt water, etc

- Weather Resistance
- Outstanding performance in extreme weather (-20oC to 50oC)

- Ease of Maintenance
- No drying needed as hose is mildew and rot proof

Model BF-SJ-001 BF-SJ-002 BF-DJ-001 BF-DJ-002

DN 2½”
Inlet
Type Male Instantaneous BS 336

DN 2½”
Outlet
Type Female Instantaneous BS 336

Coupling Material Aluminum

Hose-Coupling Connection Wired


Specifications

Diameter 1½” 2½” 1½” 2½”

Length 30m

Jacket Single - Polyester Double - Polyester


Material
Inner Lining EPDM

Color Red

Service Test 14bar 14bar 20bar 20bar

Proof Test 26bar 26bar 40bar 40bar


Pressure
Working 13bar 13bar 18bar 18bar

Burst 40bar 40bar 60bar 60bar

10
Fire Hose - Nozzle Adaptor (Accessories)

Model BF-AD-001

DN 2½”
Inlet
Type Male Instantaneous BS 336
Specifications

DN 2½”
Outlet
Type Male NPSH

Material Brass

Jet/Spray/Off Branch Pipe Nozzle (Accessories)

Model BF-NZ-001

DN 2½”
Inlet
Type Male Instantaneous BS 336

Outlet Diameter ½”
Specifications

Material Aluminum Alloy BS1490

Mode Jet/Spray/Off

Working Pressure 100psi

Flow Rate @ 100psi Jet 250L/min


...Technical Data Sheets and Catalogue
F. Landing Valve
VALVES
Data Sheet
Pressure Restricting Angle Valves
with Breakable Link
Pressure restricting valves are used when flowing water pressure needs to be
controlled. They are angle valves with preset orifices which restrict the volume
of water and thereby lower the pressure of the flowing water.

AVAPR150
AVAPR250
18-153
Female NPT inlet x Male *
• female inlet NPT only available finish:
• male outlet - specify male thread * • cast (standard)
• aluminum handwheel • polished - P
• restricts only under flow conditions • chrome - C
• for use up to 175 PSI
cast finish show
• alloy=C84400, C83600, C36000
• manufactured in the USA

AVAPRF150
AVAPRF250
18-154
Double Female
• inlet and outlet NPT only available finish:
• restricts under flow conditions only • cast (standard)
• aluminum handwheel • polished - P
• for use up to 175 PSI • chrome - C
cast finish show • alloy=C84400, C83600, C36000
• manufactured in the USA

Powhatan Cross Reference


• AVAPR150F = 18-153-00002
• AVAPR250F = 18-153-00003
• AVAPRF150 = 18-154-00001
• AVAPRF250 = 18-154-00002
Dimensions

C C Wt. in
Size Style A B D E F
(closed) (open) Lbs.
1½" 18-153 -154 2-7/32" 2-11/64" 6-13/16" 7-27/32" 3-3/4" 2-7/16" 2-13/32" 5
2½" 18-153 -154 3-7/32" 3-3/16" 9-17/32" 11-3/8" 5" 3-19/32" 3-17/32" 12
Technical Information
Pressure Restricting Valves
• Underwriters
 Listed and New York City Board of Standards and Appeals approval # MEA 54-07-E
• Restricts inlet pressure from 70 PSI (483 kPa) up to a maximum of 175 PSI (1207 kPa), down to an outlet pressure of 65, 80 or
100 PSI (448. 552 or 690 kPa).
• Outlet pressures may be set below 65 PSI (448 lPa) when authorized by the local authority having jurisdiction.
• NFPA requires restricting valves where the inlet pressure exceeds 100 PSI. Unlike the pressure regulating type of valve, the re-
stricting valve has no effect on the static pressure of a system.
• The restricting device can be manually by-passed if required by opening the valve fully. This is accomplished by breaking the
"breakable link", which allows the valve stem to rise to the full open position.
• The breakable link also serves as a simple indication of the valve condition and status. If the valve is opened without breaking the
link, the valve will resume its previous position and no resetting is necessary.

Pressure and Settings Charts


This graph is based on using 75' of 1½" rubber lined hose and a ½" discharge nozzle to obtain outlet pressures of 65, 80 or
100 PSI.

This graph is based on using 50' of 2½" rubber lined hose and a 1-1/8" discharge nozzle to obtain outlet pressures of 65, 80 or
100 PSI.

This information is only a general guideline. The company reserves the right to change any portion of this information without notice.
Terms and conditions of sale apply and are available on request.

Dixon Powhatan
800 High Street
Chestertown, MD 21620
www.dixonpowhatan.com
ph 800-355-1991 • fx 800-283-4966
® 2009 DVCC PRVAVA-SPECSHT
...Technical Data Sheets and Catalogue
G. DCP Fire Extinguisher
H. CO2 Fire Extinguisher
Portable Fire Extinguishers
Portable Fire Extinguishers are used for putting out or containing small fire until fire department arrives.
BRISTOL Portable Fire Extinguisher comply to BS EN – 3, they are light weight and easy to use, suitable for
industrial, commercial and home use.

4
Dry Chemical Powder

BSI Kitemark Approved, Pressure Type


Dry Chemical Powder Fire Extinguishers are the most widely used type of fire extinguisher. They discharge a fine powder that absorbs fuel
molecules, depriving the fire of a fuel source.

Features
- Easy grip control valve
- Seamless, corrosion-resistant body
- Refillable and parts are replaceable
- Comes with heavy-duty bracket

Model DP1 DP2 DP4 DP6 DP9 DP12

Fire Class ABC

Extinguishing Agent 40% ABC Dry Chemical Powder

Capacity 1kg 2kg 4kg 6kg 9kg 12kg

Propellant Nitrogen

Fire Rating
5A&34B 13A&70B 21A&113B 27A&183B 34A&233B 43A&233B
(BS EN 3-7:2004+A1:2007)
Specifications

Discharge Duration 6s 9s 12s 15s 18s 23s

Operating Temperature Range -20ºC to 60ºC

Working Pressure 15bar

Test Pressure 27bar

Total Height 300mm 340mm 470mm 520mm 560mm 610mm

Cylinder Diameter 86mm 120mm 140mm 161mm 190mm 190mm

Cylinder Material Steel

Body Color RAL 3000 (Signal Red)

KM 503775 0086

5
Carbon Dioxide

BSI Kitemark Approved


Carbon Dioxide Fire Extinguishers are designed to protect areas where class B and electrical fires occur. Carbon Dioxide extinguishers are
used indoors where winds and drafts do not affect discharge and where clean agent is required.

Features
- Easy grip control valve
- Seamless, corrosion-resistant body
- Refillable and parts are replaceable
- Comes with heavy-duty bracket

Model CD2 CD5

Fire Class BE

Extinguishing Agent Carbon Dioxide

Capacity 2kg 5kg

Propellant Carbon Dioxide

Fire Rating
34B 89B
(BS EN 3-7:2004+A1:2007)

Discharge Time 10s 15s


Specifications

Operating Temperature Range -20ºC to 60ºC

Working Pressure 60bar

Test Pressure 250bar

Total Height 58cm 76cm

Cylinder Diameter 10.5 13.8cm

Cylinder Material 34CrMo4 (Alloy Special Steel)

Body Color RAL 3000 (Signal Red)

Regular

Model CD2N CD5N CD6N

Fire Class BE

Extinguishing Agent Carbon Dioxide

Capacity 2kg 5kg 6kg

Propellant Carbon Dioxide


Specifications

Operating Temperature Range -20ºC to 60ºC

Working Pressure 60bar

Test Pressure 250bar

Cylinder Material Steel Alloy

Body Color RAL 3000 (Signal Red)

KM 587564

7
...Technical Data Sheets and Catalogue
I. 1" Air Release Valve
Other Valves

Air-Release Valve
Model BFE090203
Specifications

Coupling M BSPT

Body Material Brass

22
...Technical Data Sheets and Catalogue
J. Fire Blanket
FIRE BLANKET
B S I K ITE MAR K AP PROVED

Fire blankets are highly flame-resistant blankets


that can be used to extinguish a small fire by
smothering or to wrap around a person in case of
a fire. They work by cutting off the oxygen supply
to the fire.
Bristol Fire Blankets are tested and certified
according to BS EN 1869:1997.

MODEL WIDTH LENGTH


FGC11 1100mm 1100mm
FGC12 1200mm 1200mm
FGC18 1200mm 1800mm

SPECIFICATIONS
Design Standard BS EN1869:1997
Approval BSI Kitemark
Material Glass Fiber
Thickness 0.25±0.03mm
Weight 340±20g / m2
Warp 20±1pcs/cm
Weft 15±1pcs/cm
950N (Warp)
Break Strength
420N (Weft)

© Bristol Fire Engineering. All rights reserved. (2016)

WWW.BRISTOL-FIRE.COM
...Technical Data Sheets and Catalogue
K. Breeching Inlet
L. Breeching Cabinet
Breeching Inlets
Breeching Inlets are used as water feed from the fire department pump to the building fire-fighting system.
BRISTOL Breeching Inlets are designed for dry riser application, and are manufactured to comply with
BS 5041 standard comprising of male instantaneous connections.

7
Two-Way
KM 599357

BSI Kitemark Approved

Model BFE-2WBI BFE08049

Compliance BS 5041-3

BSI Kitemark Approval KM 599357 Not Applicable

Inlet Details 2 x 2½” M Instantaneous BS 336


Specifications

DN 100mm
Outlet
Type Flange PN16

Working Pressure 10bar

Operating Temperature Range 0ºC to 38ºC

Test Pressure 20bar

Four-Way
BSI Kitemark Approved

Model BFE-4WBI BFE08063A

Compliance BS 5041-3

BSI Kitemark Approval KM 599357 Not Applicable

Inlet Details 4 x 2½” M Instantaneous BS 336


Specifications

DN 150mm
Outlet
Type Flange PN16

Working Pressure 10bar

Operating Temperature Range 0ºC to 38ºC

Test Pressure 20bar

8
DESCRIPTION

Horizontal Breeching Cabinet


(Surfaced Mounted)
...Technical Data Sheets and Catalogue
M. Bristol Non-Return Valve
Non-Return / Check Valves
Non-Return Valves or Check Valves are valves that normally allow fluid to flow through it in only one direc-
tion. BRISTOL Check Valves are swing type with a tilted clapper. BRISTOL Check Valves clapper design
produces quick, non-slam closure before flow reversal can occur meeting the FM requirements for an an-
ti-water hammer valve rating.

9
Swing Type LISTED EX16011

UL Listed, FM Approved

Model BR-DGC-300

Working Pressure 300psi

Working Temperature Range -40ºC to 110ºC

Type Swing / Clapper


Check
Specifications

Material Stainless Steel + EPDM

Inlet / Outlet Coupling Grooved

Body Material Ductile Iron

Seat Material Stainless Steel

Model BR-DGC-300

Inlet/Outlet in 2.00 2.50 3.00 4.00 6.00 8.00


DN mm 50 65 80 100 150 200

in 6.75 7.25 7.75 8.12 12.75 14.37


L
Dimensions

mm 171 184 197 205 324 365

in 5.43 5.69 6.06 8.38 11 13.07


H
mm 144 153 160 187 279 331

in 4.38 4.50 4.73 6.00 8.50 10.00


D
mm 111 114 125 152 216 250

10
...Technical Data Sheets and Catalogue
N. Bristol OS&Y Gate Valve
O. OSY2 Tamper Switch
Gate Valves
Gate Valves are valves that open by lifting a round or rectangular gate/wedge out of the path of the fluid.
They are characterized as having either a rising or a non-rising stem. BRISTOL Gate Valves are made of
high quality materials and conform to international and local standards.

4
Outside Stem & Yoke LISTED EX16103

UL Listed, FM Approved

Model 399F

Working Pressure 300psi

Type Resilient Wedge


Gate
Material Ductile Iron + EPDM
Specifications

Inlet / Outlet Coupling Flange PN16 / ANSI 125

Body Material Ductile Iron

Seat Material EPDM

Model 399F

Inlet/Outlet in 2.50 3.00 4.00 5.00 6.00 8.00 10.00 12.00


DN mm 65 800 100 125 150 200 100 250

in 7.50 8.00 9.00 10.00 10.50 11.50 13.00 14.00


L
Dimensions

mm 191 203 229 254 267 292 330 356

in 16.46 19.21 21.18 25.75 29.13 36.81 44.33 51.81


H
mm 418 488 538 654 740 935 1126 1316

in 7.2 9.96 9.96 12.05 12.05 13.98 17.52 17.52


D
mm 183 253 253 306 306 355 445 445

5
OSY2
Supervisory Switch

System Sensor’s OSY2 is used to monitor the open

position of an Outside Screw and Yoke (OS&Y) type

gate valve.

Features Robust Construction. The OSY2 consists of a rugged housing,


• NEMA 3R rated enclosure intended for indoor and outdoor use. When installed with the
actuator in the vertical position, the OSY2 is NEMA 3R rated per UL.
• User-friendly mounting bracket fits newer valve yokes
• Single side conduit entry does not require right angle fittings Application Flexibility. The OSY2 features a user-friendly
• Adjustable length actuator eliminates the need for cutting the shaft mounting bracket and adjustable shaft to permit mounting to most
OS&Y valves, ranging in size from 1˝ to 12˝. Its right angle design
• Accommodates up to 12 AWG wire and wide bracket span provides maximum clearance for valve
• Three position switch monitors vandal and valve close signals components, to accommodate troublesome valves. Removing the
• Two SPDT contacts are enclosed in a durable terminal block for OSY2’s gate valve bracket allows the unit to monitor side-bracket
added strength style pressure reducing valves.

• 100% synchronization activates both alarm panel and local bell Simplified Operation. Installation is made easier with the
simultaneously OSY2’s single side conduit entrance. By providing a direct conduit
pathway to the electrical source, right angle fittings are not required.
Installation is further simplified by the OSY2’s adjustable length
actuator, which eliminates the need for cutting the shaft.

Reliable Performance. The OSY2 is equipped with tamper


resistant cover screws to prevent unauthorized entry. Inside, two sets
of SPDT (Form C) synchronized switches are enclosed in a durable
terminal block to assure reliable performance.

Agency Listings

S739 CS169 OW6A8.AY 167–93–E 7770–1209:217


OSY2 Specifications
Architectural/Engineering Specifications
Model shall be model number OSY2 supervisory switch as manufactured by System Sensor. OSY2 shall be installed on each valve as designated on the drawings
and/or as specified herein. Switches shall be mounted so as not to interfere with the normal operation of the valve and shall be adjusted to operate within
two revolutions of the valve control or when the stem has moved no more than one-fifth of the distance from its normal position. The mechanism shall be
contained in a weatherproof die cast metal housing, which shall provide a side entrance for ½˝ conduit and incorporate the necessary facilities for attachment
to the valve. A grounding provision is provided. The switch assembly shall include two switches each with a rated capacity of 10 Amp @ 125/250VAC and 2.5
Amp @ 24VDC. The cover shall contain tamper-resistant screws for which a security wrench will be provided with each switch. The OSY2 shall be Underwriters
Laboratories listed for indoor or outdoor use. The OSY2 shall be Factory Mutual, CSFM, and MEA approved.
Physical Specifications Operating Specifications
Overall Switch 5¾˝H x 3½˝W x 3¼˝D Contact Ratings Two sets of SPDT (Form C)
Dimensions (14.6cm x 8.9cm x 8.2cm) 10.0 A @ 125/250VAC; 2.5 @ 6/12/24VDC
Shipping Weight 2.8 lbs. (1.3 kg) Enclosure Rating UL indoor/outdoor
NEMA 3R when mounted with the actuator vertical

Operating Temperature 32ºF to 120°F ( 0ºC to 49ºC) Cover Tamper Switch Standard with ULC model
Range NOTE: The OSY2 will operate from –40ºF to 120ºF Optional for UL model, part no. 546-7000
(–40ºC to 49ºC); however UL does not test control
valve supervisory switches below 32ºF (0ºC).
Maximum Stem Extension 25/8˝ (6.7cm) Service Use Automatic Sprinkler: NFPA 13
One or Two Family Dwelling: NFPA 13D
Residential Occupancies up to 4 stories: NFPA 13R
National Fire Alarm code: NFPA 72
Bracket Span ¼˝H x 6¾˝W x 1˝D (5.7cm x 17.1cm x 2.5cm) Warranty 3 years
Conduit Entrances One single side open for ½˝ conduit U.S. Patent Nos. 5,478,038; 5,213,205

Electrical Connections for OSY2 OSY2 Mounting


Top View The following are examples of acceptable
Switch 1
mounting positions:

CO M
M CO

A B B A
Switch 2 CONTACT RATINGS
125/250 VAC 10 AMPS
Strip Gauge 24 VDC 2.5 AMPS

Sup. Switch Sup. Switch

B B B B

to nonsilenceable initiating end-of-line resistor


zone of listed FACP Actuator Vertical (Down) Actuator Horizontal
COM COM COM COM

Typical FACP Connection The following mounting position is not acceptable:

B
to power source
compatible local
with bell bell Break wire as shown for supervision
COM of connection. DO NOT allow stripped
wire leads to extend beyond switch
housing. DO NOT loop wires.

Typical Local Bell Connection


Actuator Vertical
(Pointing Up)

Ordering Information
Part No. Description
OSY2 Outside Screw and Yoke valve supervisory switch
OSY2A Outside Screw and Yoke valve supervisory switch (ULC model)
Accessories
OSYRK Replacement hardware kit (wrenches, screw pack and J–hooks) WFDW Replacement tamper proof wrench for cover
546-7000 Cover tamper switch kit HEXW Replacement hex wrench
S07-66-XX Tamper screws for cover

©2006 System Sensor.


3825 Ohio Avenue • St. Charles, IL 60174 Product specifications subject to change without notice. Visit systemsensor.com for
current product information, including the latest version of this data sheet.
Phone: 800-SENSOR2 • Fax: 630-377-6495 A05-0196-009 • 11/06 • #1676
...Technical Data Sheets and Catalogue
P. Cla-val Pressure Reducing Valve
MODELS
90G-21
90A-21
Fire Protection Pressure Reducing Valve
• U.L. Listed, ULC Listed, MEA Approved
• Globe or Angle Pattern
90-21 UL Listed
Fire Protection Valve • Proven Reliable Design
• Available in Cast Bronze, Ductile Iron and
90-21 UL Listed Cast Steel
Grooved End • Accurate Pressure Control
Fire Protection Valve • In Line Service
• Grooved Ends (1 1/2” - 8”)

Cla-Val 90G-21 (globe) and 90A-21 (angle) Pressure Re-


ducing Valves are indispensable in any fire protection sys-
tem. Our diaphragm actuated design is proven highly reliable
and easy to maintain. We offer both a globe or angle pattern
MEA with a full range of adjustments. These valves are also avail-
able in a variety of material options. Epoxy coating is
Approved strongly recommended for all fire system valves (excluding
bronze valves). The 90G-21 and 90A-21 can be supplied
Special System Water Control Valves – Class II with optional internal and external epoxy coating of the main
UL Product Category VLMT – File No. Ex 2534 valve wetted surfaces.
3
2

Cla-Val 90G-21 (globe) and 90A-21 (angle) Pressure Re-


ducing Valves automatically reduce a higher inlet pressure Schematic Diagram
to a steady lower outlet pressure regardless of changing Item Description
flow rate and/or varying inlet pressure. The valves pilot con- 1 Model 100-01 Hytrol
trol system is very sensitive to slight downstream pressure (Globe or Angle)
fluctuations, and will automatically open or close to maintain 2 X58C Restriction Tube Fitting
the desired pressure setting. The downstream pressure can
3 CRD Pressure Reducing Control
be set over a wide range by turning the adjustment screw
on the CRD pilot control. The adjustment screw is protected 4 X46A Flow Clean Strainer
OUTLET
by a screw-on cover, which can be sealed to discourage INLET

tampering. 4

Typical Application
Underwriters Laboratories requires the installation of pressure
CLA-VAL 90-21
gauges upstream and downstream of the Pressure Reducing Valve.
Model 55L Also, a relief valve of not less than 1/2 inch in size must be installed
on the downstream side of the pressure control valve. Adequate
CLA-VAL 90-21 drainage for the relief valve discharge must be provided.

UL / ULC Listings Globe Pattern Angle Pattern


Ductile Iron Ductile Iron Ductile Iron Bronze Bronze Bronze Cast Steel Ductile Iron Ductile Iron
Size 150# F 300# S 300 # F 300# Threaded 150# F 300# F 300# F Grooved End Grooved End
1 1/2'' UL / ULC UL / ULC UL UL / ULC UL
2" UL / ULC UL / ULC UL / ULC UL / ULC ULC ULC UL UL UL
2 1/2" UL / ULC ULC UL / ULC UL / ULC ULC ULC UL UL
3'' UL / ULC UL / ULC UL / ULC UL / ULC ULC ULC UL UL UL
4" UL / ULC UL / ULC ULC ULC UL UL UL
6" UL / ULC UL / ULC UL UL
8" UL / ULC UL/ULC UL
10" ULC ULC
Dimensions
VALVE SIZE (inches) 11⁄2 " 2" 21⁄2" 3" 4" 6" 8" 10" D DD
A THREADED 7.25 9.38 11.00 12.50 –– –– –– ––
AA 150 ANSI 8.50 9.38 11.00 12.00 15.00 20.00 25.38 29.75
AAA 300 ANSI 9.00 10.00 11.62 13.25 15.62 21.00 26.38 31.12
AAAA GROOVED 8.50 9.00 11.00 –– GG
12.50 15.00 20.00 25.38 G (MAX)
B 1.12 1.50 1.69 2.56 3.19 4.31 5.31 9.25
BB GROOVED 1.94 2.13 2.50 6.00 4.13 6.00 7.25 ––
C (MAX) 5.50 6.50 7.56 8.19 10.62 13.38 16.00 17.12
CC (MAX) GROOVED 4.10 5.00 6.88 6.50 8.80 11.10 14.50 ––
PRESSURE REDUCING CONTROL ADJUSTMENT;
D 2.81 3.31 4.00 4.56 5.75 7.88 10.00 11.81 TURN THE ADJUSTING STEM CLOCKWISE TO INCREASE
THE SETTING
DD GROOVED 2.81 3.31 4.00 4.56 5.75 7.88 10.00 ––
E THREADED 3.25 4.75 5.50 6.25 –– –– –– –– C
EE 150 ANSI 4.00 4.75 5.50 6.00 7.50 10.00 12.75 14.88 CC
(MAX)
EEE 300 ANSI 4.25 5.00 5.88 6.38 7.88 10.50 13.25 15.56
EEEE GROOVED –– 4.75 –– 6.00 7.50 –– –– ––
B
F THREADED 1.88 3.25 4.00 4.50 –– –– –– –– INLET OUTLET

FF 150 ANSI 4.00 3.25 4.00 4.00 5.00 6.00 8.00 8.62 BB
FFF 300 ANSI 4.25 3.50 4.31 9.31 A
4.38 5.31 6.50 8.50
AA
FFFF GROOVED –– 3.25 –– 4.50 5.00 –– –– –– AAA AAAA
4" SIZE
SHOWN

G (MAX) 7.50 7.75 7.75 8.00 9.00 9.50 10.50 11.50


GG (MAX) 8.10 8.00 – 8.13 9.31 10.50 11.50

VALVE SIZE (mm) 40 50 65 80 100 150 200 250


A THREADED 184 238 279 318 –– –– –– ––
AA 150 ANSI 216 238 279 305 381 508 645 756
AAA 300 ANSI 229 254 295 337 397 533 670 790 OUTLET

AAAA GROOVED 216 228 279 318 381 508 645 –– F FFF
B 28 38 43 65 81 109 135 235 FF FFFF
BB GROOVED 52 54 73 6.00 4.13 6.00 184 ––
C (MAX) 140 161 192 208 270 340 406 435 E INLET

CC (MAX) GROOVED 104 127 175 165 223 281 369 –– EE


EEE EEEE
D 71 84 102 116 146 200 254 300
DD GROOVED 71 84 102 116 146 200 254 ––
E THREADED 83 121 140 159 –– –– –– –– Selection Guidelines
EE 150 ANSI 102 121 140 152 191 254 324 378 Flow Capacity Table
EEE 300 ANSI 108 127 149 162 200 267 349 395
EEEE GROOVED 152 –– Maximum Flow Rate
–– 121 –– 191 –– –– Valve Size (GPM of Water)
F THREADED 48 83 102 114 –– –– –– ––
FF 150 ANSI 102 83 102 102 127 152 203 219 11⁄2" 160
FFF 300 ANSI 108 89 109 111 135 165 216 236 2" 262
FFFF GROOVED –– 121 –– 114 127 –– –– ––
21⁄2" 373
G (MAX) 191 197 197 203 228 241 267 292
GG (MAX) 206 203 – 207 236 267 292 –– 3" 576
4" 992
Size: 175 lb. Class 1 1/2” - 8” (Globe) Materials 2251
6"
2” - 6” (Angle)
Main valve body & cover: 8" 3900
300 lb. Class 1 1/2” - 8” (Globe)
2” - 6” (Angle) 10" 6150
Ductile Iron - ASTM A536
End Details: Note: The Actual Capacity is
150 ANSI B16.42 (Ductile Iron) Main valve internal trim: limited by available DP.
(Bronze) Bronze ASTM B61
300# (Ductile Iron) When Ordering
300# (Cast Steel). Pilot control system– Please Specify
300# (Ductile Grooved End). Pilot control valve: 1. Model Number 90-21
Bronze ASTM B62 with
Pressure Differential: 10 PSI Min. Stainless Steel 303 internal trim 2. Size
3. Globe or Angle Pattern
Pressure Adjustment Range: Copper tubing with brass fittings
30 – 165 psi
4. Main Valve Body and
175 lb. Class
Cover Material
Main valve and pilot valve
300 lb. Class 30 – 165 psi 5. Threaded, Flanged or Grooved
diaphragm and disc:
Buna-N® synthetic rubber 6. Pressure Class
Temperature Range: Water to 180°F Max.
7. Optional Epoxy Coating
SPECIAL NOTE: THE MODEL 90-21 CAN BE SUPPLIED WITH INTERNAL EPOXY COATING OF THE MAIN VALVE. THIS OPTION
IS U.L. FILE NO. EX2855, C.C. NO. HNFX EPOXY COATING IS STRONGLY RECOMMENDED FOR ALL CAST VALVES. (specify with suffix “KC)
CLA-VAL Represented By:
PO Box 1325 Newport Beach CA 92659-0325 Phone: 949-722-4800
Fax: 949-548-5441 Web Site: cla-val.com E-mail: claval@cla-val.com
CLA-VAL CANADA CLA-VAL EUROPE CLA-VAL UK
4687 Christie Drive Chemin des Mésanges 1 Dainton House, Goods Station Road
Beamsville, Ontario CH-1032 Romanel/ GB - Tunbridge Wells
Canada LOR 1B4 Lausanne, Switzerland Kent TN1 2 DH England
Phone: 905-563-4963 Phone: 41-21-643-15-55 Phone: 44-1892-514-400
Fax: 905-563-4040 Fax: 41-21-643-15-50 Fax: 44-1892-543-423
E-Mail: sales@cla-val.ca E-Mail: cla-val@cla-val.ch E-Mail: info@cla-val.co.uk
© Copyright CLA-VAL 2008 Printed in USA Specifications subject to change without notice.

E-90G-21 (R-11/08)
...Technical Data Sheets and Catalogue
Q. WATTS Pressure Relief Valve
ES-FP53L

For Fire Protection Applications


Job Name –––––––––––––––––––––––––––––––––––––––––––– Contractor –––––––––––––––––––––––––––––––––––––––––––––

Job Location –––––––––––––––––––––––––––––––––––––––––– Approval ––––––––––––––––––––––––––––––––––––––––––––––

Engineer –––––––––––––––––––––––––––––––––––––––––––––– Contractor’s P.O. No. –––––––––––––––––––––––––––––––––––

Approval –––––––––––––––––––––––––––––––––––––––––––––– Representative –––––––––––––––––––––––––––––––––––––––––

Model FP53L
Pressure Relief Valve
Size: 1⁄2" (15mm)
Watts No. FP53L is designed for use in fire protection grid systems
to provide protection against excessive water pressure caused by
thermal expansion or line surge. It is available in 175psi (12.1 bar), 1⁄2" NPT
pressure relief settings and can be installed horizontally or vertically.
Bronze body construction with stainless steel spring to inhibit corro- Female Outlet
sion. The valve is constructed with a precision stem guide to ensure
proper reseating. The test lever affords periodic manual testing and
flushing of waterways and seating surfaces.

Features
• Underwriters
 Laboratory listed
• Forged stainless steel spring
1⁄2" NPT
• Bronze body construction for superior strength and to
Male Inlet
prevent corrosion
• Manual test lever
• Valve stem is guided to enhance reseating
• 1⁄2" (15mm) male inlet x female outlet
• Pressure settings: 1 75psi (12.1 bar)
! WARNING
Specifications Following installation, the valve lever MUST be operated
AT LEAST ONCE A YEAR to ensure that the water-ways
For applications requiring a UL approved relief valve to provide
are clear. Certain naturally occurring mineral deposits may
pressure relief protection from water pressure in excess of 175psi
(12.1 bar). Each valve shall be bronze body construction with forged adhere to the valve, rendering it inoperative. When manually
stainless steel spring. It shall have a test lever and the valve shall be operating the lever, water will discharge and precautions must
guided to enhance reseating and to decrease chance of the seat be taken to avoid contact with hot water and to avoid water
being misaligned. Watts Model No. FP53L. damage. BEFORE operating lever, check to see that a dis-
charge line is connected to this valve directing the flow of hot
Dimensions — Weight water from the valve to a proper place of disposal otherwise
personal injury may result. If no water flows, valve is inopera-
tive. CALL A PLUMBER IMMEDIATELY.

MODEL SIZE HEIGHT WIDTH WEIGHT This device is designed for emergency safety relief and shall
in. mm in. mm in. mm lbs. kgs. not be used as an operating control.
FP53L ⁄
12 15 31⁄2 89 17⁄8 48 ⁄
12 .23

NOTICE
The information contained herein is not intended to replace the full
product installation and safety information available or the experience
of a trained product installer. You are required to thoroughly read all
installation instructions and product safety information before begin-
ning the installation of this product.

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Watts Technical Service. Watts
reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications
on Watts products previously or subsequently sold.

USA: Tel: (978) 689-6066 • Fax: (978) 975-8350 • Watts.com A Watts Water Technologies Company
Canada: Tel: (905) 332-4090 • Fax: (905) 332-7068 • Watts.ca
Latin America: Tel: (52) 81-1001-8600 • Fax: (52) 81-8000-7091 • Watts.com

ES-FP53L 1552 © 2015 Watts


...Technical Data Sheets and Catalogue
R. Water Pressure Gauge
Mechanical
Pressure Measurement
Bourdon Tube Pressure Gauge
Type 111.10SP Sprinkler Gauge
Standard Series
WIKA Datasheet 111.10SP

Applications

 Fire sprinkler systems


 Suitable for all media that will not obstruct the pressure
system or attack copper alloy parts

Special features

 UL-listed (UL-393), United States and Canada


 Factory Mutual (FM) approved
 Reliable and economical

Bourdon Tube Pressure Gauge Type 111.10SP


Standard Features

Design Pressure connection


EN 837-1 & ASME B40.100 Material: copper alloy
1/4“ NPT lower mount (LM)
Sizes
4” (100 mm) Movement
Copper alloy
Accuracy class
± 3/2/3% of span (ASME B40.100 Grade B) Dial
White aluminum with stop pin; black and red lettering
Ranges
0/80 psi, retard to 250 psi (air) Pointer
0/300 psi (water) Black aluminum

Working pressure Case


Steady: 3/4 of full scale value Black polycarbonate
Fluctuating: 2/3 of full scale value Window
Short time: full scale value Snap-in clear polycarbonate
Operating temperature Approvals
Ambient: -40°F to 140°F (-40°C to 60°C) UL listed (UL-393)
Media: 140°F (+60°C) maximum Factory Mutual
Temperature error
Additional error when temperature changes from reference
temperature of 68°F (20°C) +0.4% for every 18°F (10°C) ris-
ing or falling. Percentage of span.

Bourdon tube
Material: copper alloy
C-type

WIKA Datasheet 111.10SP � 04/2007 Page 1 of 2


Optional Extras
(not all options are UL or FM approved)
Dimensions

 Brass restrictor
 Friction-fit cover ring (requires steel case)
 Glass window (requires steel case & friction ring)
 Black-painted steel case
 Stainless steel case
 Special case colors
 Nickel-plated connection
 Custom dial layout
 Special threaded connection
 Custom dial layout
 Other pressure scales available:
bar, kPa, MPa, kg/cm2 and dual scales

Size
A B C E L T W Weight
4” mm 100 83.5 30 11.5 3.75 14
in 4.0 3.29 1.18 0.45 0.15 1/4” 0.55 0.35 lb.

Page 2 of 2 WIKA Datasheet 111.10SP � 04/2007

Ordering information
Pressure gauge model / Nominal size / Scale range / Size of connection / Optional extras required
Specifications and dimensions given in this leaflet represent the state of engineering at the time of printing.
Modifications may take place and materials specified may be replaced by others without prior notice. WIKA Instrument Corporation
1000 Wiegand Boulevard
Lawrenceville, GA 30045
Tel (770) 513-8200 Toll-free 1-888-WIKA-USA
Fax (770) 338-5118
E-Mail info@wika.com
www.wika.com
VI. Method Of Statement

Fire Fighting Systems

1 Fire Extinguishers
1.1 Dry Powder Extinguishers
1.2 How Dry Powder Fire Extinguishers Work.
1.3 Three Main Types of Dry Powder Extinguishers
1.4 Dry Powder Extinguishers and Water
1.5 CO2 Fire Extinguishers
1.6 How Carbon Dioxide Fire Extinguishers Work
1.7 CO2 Fire Extinguishers and Electricity
1.8 Carbon Dioxide Fire Extinguishers and Other Fire Classes
1.9 Carbon Dioxide Fire Extinguisher Pressure Gauges
2 Fire Hose Reel
2.1 General Instructions for Use
2.2 Operation
3 Sprinkler System
3.1 Glass Bulb Detector / Sprinkler Heads
3.1.1 Description
3.1.2 Design Parameters
3.1.3 Operation
3.2 Alarm Check Valve
3.2.1 Operation
3.2.2 Trim Packages
Trim Packages Available
Trim Packages Include
3.2.3 Optional Accessories
3.2.4 Installation
3.2.5 Testing
3.2.6 Maintenance
3.2.7 Retard Chamber
...Method Of Statement
1 Fire Extinguishers
1.1 Dry Powder Extinguishers

Dry powder fire extinguishers are excellent all-round fire extinguishers,


often recommended for use on vehicles and in the home. All powder fire
extinguishers are red with a blue panel, are either ABC or BC rated and
are safe to be used on fires involving electrical equipment. (Remember to
look for the electrical safety pictogram. Dry powder extinguishers are not
suitable for use in enclosed spaces such as offices, hotels, schools, etc, as
the fire-fighting agent creates a cloud that can obscure vision. The
contents may also create breathing problems.

1.2 How Dry Powder Fire Extinguishers Work

Dry powder fire extinguishers contain an extinguishing agent, which is


propelled out of the extinguisher body by a compressed, non-flammable
gas. The agent forms a ‘blanket’ over the fire, smothering it and
preventing re-ignition. All used powder residue must be cleaned away
and properly disposed of once the fire is extinguished. Sodium
bicarbonate is an effective fire extinguishing agent as it decomposes at
158 degrees F, releasing CO2 which starves the fire of oxygen.

1.3 Three Main Types of Dry Powder Extinguishers

1. ABC rated or multi-purpose powder, which contain ammonium


phosphate
2. BC rated extinguishers, containing potassium bicarbonate or
sodium bicarbonate (otherwise known as bicarbonate of soda or
baking soda!) Some BC rated powder fire extinguishers contain
Monnex. The pressurizing gas is usually nitrogen
3. A and D rated graphite powder fire extinguishers are usually used
only in Class D fires Both types of non-graphite dry powder
extinguisher are potentially corrosive to soft metal such as
aluminum, and can also be abrasive when sprayed.

1.4 Dry Powder Extinguishers and Water

Unfortunately, the additional benefit of ABC rated dry powder fire


extinguishers being able to tackle flammable gas fires also has a major
...Method Of Statement
drawback. Ammonium phosphate can react with any water present to
form phosphoric acid, which is corrosive and can seep into even the
slightest cracks in equipment.

For this reason, dry chemical ABC rated fire extinguishers should not be
used on sensitive electrical equipment such as computers, switch
installations, scientific instruments or aircraft, if other fire extinguishing
options are available.
Left in place, powder will draw moisture from the air and a common
example of corrosion will be the chrome on tools being replaced with rust.

In the event of an emergency when only a dry powder fire extinguisher is


available, however, always remember that electrical equipment can be
replaced, a human life cannot. If in doubt, get out, stay out and call the
fire brigade immediately.

1.5 CO2 Fire Extinguishers

CO2 fire extinguishers (carbon dioxide) are the only fire extinguisher
recommended for fires involving electrical equipment. CO2 is safe to use
on and around electrical equipment, as the gas itself is non-conductive,
and once used, there is no sticky foam or messy powder left behind. They
are also effective on Class B fires (flammable liquids).

Carbon dioxide fire extinguishers are painted bright red with a black
panel above the operating instructions. They have a distinctive horn-
shaped nozzle at the side on the smaller models with 5kgs and above
having a hose and horn.

1.6 How Carbon Dioxide Fire Extinguishers Work

CO2 extinguishers store carbon dioxide gas under great pressure (55 bar
or 825psi), where the gas becomes a liquid. When you operate the fire
extinguisher levers, the pressure is released; the CO2 pressure is reduced
by the diffuser (horn) and expands back into a gas, rapidly cooling the
surrounding air.

This process is so fast, it can cause ice to form on the horn, so never hold a
CO2 fire extinguisher by the horn to avoid freezing your skin. To be most
effective, a carbon dioxide fire extinguisher should be used no closer than
3 feet and no further than 8 feet from the fire itself.
...Method Of Statement
For the UK, they are commonly made in two sizes, 2kg and 5kg. The
compressed gas required an extremely thick cylinder so many buyers
prefer super-strong aluminum rather than heavier steel models, so that
their staff can lift and use the CO2 extinguishers more easily. Steel is
normally used for marine extinguishers although many of the cheap
imports are made from steel.

The 2kg models tend to have a swivel horn, which must not be held during
operation to avoid freezing your hands. The 5kg models usually feature a
hose with the horn attached with the horn normally having a handle.

1.7 CO2 Fire Extinguishers and Electricity

CO2 fire extinguishers are safe to use on fires in, on or around electrical
equipment and live cables. CO2 gas is dry, inert in air, and leaves behind
no residue that will affect electrical equipment’s future operation. So, you
will often find a CO2 fire extinguisher next to precious electrical
equipment, from switchgear to mobile discos.

In most office, workplace, factory or warehouse situations, the best


combination is to have a water additive or foam unit alongside your CO2
extinguisher, for maximum fire fighting ability.

1.8 Carbon Dioxide Fire Extinguishers and Other Fire Classes

CO2 fire extinguishers should not be used on Class D fires, involving


flammable metals. The CO2 gas reacts with many volatile metals, and as
with other non-D rated extinguishers, can also blow burning metal over a
wide area, making the situation worse. And it is not affective on Class A
fires such as paper, wood or cloth.

1.9 Carbon Dioxide Fire Extinguisher Pressure Gauges

CO2 fire extinguishers do not have pressure gauges, as the gas is


condensed in the cylinder. The only way to assess if a CO2 fire extinguisher
is empty is to weigh it. The gross weight (G W) is stamped into the metal of
the cylinder shoulder with other information. To assess how full your CO2
fire extinguisher is, weigh it (without the swivel horn) and compare this to
the stamped gross weight.
...Method Of Statement
However, rather than take the risk of a part-used fire extinguisher, or have
the expense of a call-out visit and factory refilling or service exchange, it is
often more cost effective to replace a used CO2 fire extinguisher with a
new one. Expert firms or your local Civic Amenity Centre (the local dump)
will be happy to recycle your old CO2 fire extinguisher.

2 Fire Hose Reel


2.1 General Instructions for Use

Always read the instruction plate before use, to ensure that you have
selected the correct extinguisher for the fire you intend to fight.

2.2 Operation

There is two ways of operation fire hose reel:

• Automatic Hose reel- pull out the hose for 2 m or 3 m and the water
is automatically turned on. Control the discharge by using the
nozzle in Jet/spry/Off mode

• Manual Hose Reel- to turn on the water, open the inlet valve, before
running out the hose to location the fire. Control the discharge by
using the nozzle in Jet/spry/Off mode

Ensure that you are positioned between the fire and safe exit/escape
route

Apply the water jet to the base of the fire in short sweeping burst keeping
out the smoke and steam produced.

Warning there is a continuous supply of water to the hose reel. Do not fight
the fire size increases or for too long – beware of your surrounding and
local conditions.

3 Sprinkler System
Sprinkler system is designed to the requirement of NFPA-13, Standard for
Installation of Sprinkler Systems.

The sprinkler system is provided for protection of the Fire Pump room. The
sprinkler system consists of a network of aboveground piping, sprinkler
...Method Of Statement
heads, supervised isolation valve, and water flow switch. The sprinkler
heads are located evenly and in such a manner that water is discharged
in defined spray patterns covering the entire surface area of the hazard
protected. The sprinkler heads senses the heat generated by fire and burst
at a pre-determined temperature. This bursting creates a pressure drop in
the piping. The pressure switch is activated, starting the electric motor
pump first. In case the electric motor pump fails, the standby diesel
engine pump comes into operation and supplies adequate water to the
sprinkler system. When the system is activated the flow switch located on
the piping gives a signal to the fire alarm control panel. Also a
mechanical alarm is generated by means of water flowing through the
water motor gong located externally. The system is also connected to a
breeching inlet located outside the premises in the event of fire, the fire
department or civil defense personnel is required to pump water into the
system.

3.1 Glass Bulb Detector / Sprinkler Heads


3.1.1 Description

Sprinkler system is designed to the requirement of NFPA-13, Standard for


Installation of Sprinkler Systems.

3.1.2 Design Parameters

Design density as per NFPA-13 is 6.1 lpm/m2 for a minimum area of 139m2
and the minimum pressure at the remotest sprinkler heads is 0.5 bars.

3.1.3 Operation

The operating mechanism of glass bulb sprinkler consists of a frangible


glass bulb and a spring seal to close waterway. The bulb contains a liquid
and a small air bubble. Heat from a fire causes the liquid to expand and
the bubble to disappear. Beyond this point of liquid expansions, the bulb
bursts allowing the sprinkler to open. Water then discharges freely striking
the deflector. Then it is distributed in a pattern determined by the
particular sprinkler deflector.
...Method Of Statement
3.2 Alarm Check Valve

3.2.1 Operation

The valve construction incorporates a rubber clapper and operates on


basis of differential pressure. Pressure in the system above the clapper is
always greater than below. A bypass can accommodate minor pressure
surges but it is recommended that a retard chamber be installed to
account for any variable pressure conditions.

When a sprinkler operates or a test is in progress, the clapper lifts to allow


a flow of water into the system and activates the alarm gong and
pressure switches (if fitted). Alarms will continue to sound until the shut off
valve on the supply side of the system is closed. Always ensure the shut off
valve is monitored and will set off an alarm if tampered with.

3.2.2 Trim Packages

Trim Packages Available:

1. Vertical trim for the Alarm Check Valve installed vertically.


2. Horizontal trim configuration for the Alarm Check Valve installed
horizontally.

Trim Packages Include:

1. All required pipe and fittings


2. All standard trim accessories
3. All required gauges

3.2.3 Optional Accessories:

Retard Chamber - Required when the Alarm Check Valve is installed in


variable pressure installation in order to reduce the possibility of false
alarm.

Water Motor Alarm - The Alarm Check Valve is designed to activate a


mechanical cal alarm when a flow of water (such as an sprinkler) cause
the alarm check’s clapper to lift from its seat.
...Method Of Statement
Alarm Pressure Switch - The Alarm Check Valve is designed to allow the
installation of pressure switches to activate electric alarms and control
panels when a flow of water (such as an open sprinkler) causes the alarm
check’s clapper to lift from its seat.

3.2.4 Installation

Inlet and outlet flanges can be provided to ANSI DIN BS or JIS Standards
(specify when during) Valves Should be installed in accordance with NFPA
or other appropriate local standards in accordance with the authority
having jurisdiction. Connecting piping should be flushed clean of dirt and
all other materials that may interface with proper operation of the system
to ensure that the system has a proper flow of clean uncontaminated
water. Make Sure that the direction of flow indicated by the arrow is in the
correct direction. Check to ensure that the clapper can move freely and
is clear of all associated piping.

The System should be activated in the following sequence

1. Close the system control valve.


2. Close the alarm line control valve.
3. Open inspectors check valve.
4. Slowly open the system valve
5. (*Rapid opening of the control valve may cause water hammer
and allow air to be trapped in the system*)
6. Continue to fill the system until water flows from the test orifice of the
check valve.
7. Close the inspectors test valve
8. Fully open the system control valve and observe the pressure
gauge until system pressure is achieved. Conduct a main drain test.
9. Open the alarm control valve.
10. Conduct alarm device test
11. Seal, Lock and Secure the system control valve in accordance with
the local regulations of the authority having jurisdiction.
...Method Of Statement
12. If connected to a central alarm or fire department - promptly inform
the appropriate personnel.

3.2.5 Testing

System must periodically test in accordance with the authority having


jurisdiction.
NEVER CLOSE THE SYSTEM CONTROL VALVE WITHOUT INFORMING:

The building owner the local Fire Department and all other appropriate
authorities. NFPA 25 recommends testing at least 4 times per year. Other
Authorities having jurisdiction may have different regulations and the user
should ensure that frequent tests are conducted strictly in accordance
with local regulations.

3.2.6 Maintenance
The owner is responsible for the proper operation of the system and all
related components and accessories NFPA 24 recommends periodic
maintenance procedures and the local authority having jurisdiction may
have additional requirements.

The Alarm Check Valve has been carefully constructed from the superior
quality materials in order to give trouble free service and proper operation
and should be routinely checked to ensure proper operation.

The following routine maintenance inspections should be undertaken.

Clapper

The rubber clapper facing should be checked for wear or damaged and
should be free from all external matter or materials. If damage is observed
it should be immediately replaced.

All dirt or extraneous matter should be carefully cleaned from the surface.
Do not use solvent or any hydrocarbon derivatives for cleaning purposes.
If in doubt replace completely.
...Method Of Statement
Seat Ring

Check the seat ring for dirt and damage to the seating surfaces and
thoroughly clean of all dirt and extraneous matter. Seat ring damage
could lead to a failure of the system to operate in a fire condition.

In the case of any damage to the seat ring which may cause on-
operation of the system, the valve should be replaced.

Retard Chamber

Check that the outlet and inlet orifices are free from dirt and extraneous
matter and are undamaged and clean all elements thoroughly before
replacing in service.

Bypass Line

The Bypass line must be undamaged and free of any dirt and extraneous
matter. Clean out before replacing in service. The whole system should be
periodically checked to ensure proper function.

Care should be taken to inspect for physical damage and system leaks.
The fire protection piping and all components are integral parts of a
building safety system to protect life and proper operation is a function
correct design, installation, and carefully conducted periodic
maintenance.

3.2.7 Retard Chamber

The retard chamber is installed to cater for fluctuations in water supply


pressures. Increased pressures water enters the intermediate chamber
and fills the retard chamber. Water then drains through the retard
chamber through a restricted orifice. Constant operation of the retard
chamber may indicate problems with the system and should be
investigated.

During a fire condition or system testing, water flows into intermediate and
retard chambers, activating the water motor alarm and other signaling
devices and then the system operates as normal.
VII. Approval Certificates
Certificate of Product Approval
Certificate Number: 1226a Issue: 01

Bristol Fire Engineering LLC


Al Quoz Industrial Area 3
P.O.Box 74582
Dubai
United Arab Emirates

is authorised to use the LPCB mark in association with the product(s) listed in this certificate and appendix
having complied with the requirements of the standard(s) detailed below:

Products Standards
Bristol Fire Hose Reels EN 671-1:2012
Fixed firefighting systems. Hose systems. Hose
Single Door Cabinets reels with semi-rigid hose

Double Door Cabinets

This certificate and appendix is maintained and held in force through regular surveillance activities

Joe Milton 26 March 2014 26 March 2014


Signed for LPCB Verifier Date of Issue Date of First Issue

This certificate and appendix remain the property of BRE Global Ltd and is issued
subject to terms and conditions (for details visit www.redbooklive.com/terms).
To check the validity of this certificate and appendix please visit
www.redbooklive.com/check, scan the QR tag or contact us.
LPCB is part of BRE Global Ltd, Garston, Watford, WD25 9XX
T: +44 (0)1923 664100 F: +44 (0)1923 664603 E: enquiries@breglobal.com

BF1315A Rev 0.0 Page 1 of 5 © BRE Global Ltd, 2014


Appendix to Certificate No: 1226a Issue: 01
XXXa Fire Engineering LLC
Bristol
Fire Hose Reels to EN 671-1:2012
Hose Hose
Product LPCB Ref.
Description Nominal Maximum Nozzle type
Name No.
Bore (mm) Length (m)

Manual, swinging arm, cabinet or


BF-MS-003 19 30 Rotary operated jet/spray 1226a/01
wall mounted

Manual, swinging arm, cabinet or


BF-MS-001 25 30 Rotary operated jet/spray 1226a/02
wall mounted

Automatic, swinging arm, cabinet


BF-AS-004 19 30 Rotary operated jet/spray 1226a/03
or wall mounted

Automatic, swinging arm, cabinet


BF-AS-002 25 30 Rotary operated jet/spray 1226a/04
or wall mounted

Fire Hose Reel Cabinets

LPCB Ref.
Product Name Description
No.

BF-SRM-MS1 700x700x300 single cabinet, recessed, full MS

BF-SRS-SH1 700x700x300 single cabinet, recessed, full SS hairline-finish

BF-SRS-SM1 700x700x300 single cabinet, recessed, full SS mirror-finish

BF-SRM-SH1 700x700x300 single cabinet, recessed, MS back box with SS hairline-finish


1226a/05
BF-SRM-SM1 700x700x300 single cabinet, recessed, MS back box with SS mirror-finish

BF-SSM-MS1 700x700x300 single cabinet, surface mounted, full MS

BF-SSS-SH1 700x700x300 single cabinet, surface mounted, full SS hairline-finish

BF-SSS-SM1 700x700x300 single cabinet, surface mounted, full SS mirror-finish

This certificate and appendix is maintained and held in force through regular surveillance activities

Joe Milton 26 March 2014 26 March 2014


Signed for LPCB Verifier Date of Issue Date of First Issue

This certificate and appendix remain the property of BRE Global Ltd and is issued
subject to terms and conditions (for details visit www.redbooklive.com/terms).
To check the validity of this certificate and appendix please visit
www.redbooklive.com/check, scan the QR Tag or contact us.
LPCB is part of BRE Global Ltd., Garston, Watford WD25 9XX.
T: +44 (0)1923 664100 F: +44 (0)1923 664603 E: Enquiries@breglobal.com

BF 1315A Rev 0.0 Page 2 of 5 © BRE Global Ltd, 2014


Appendix to Certificate No: 1226a Issue: 01
XXXa Fire Engineering LLC
Bristol
Fire Hose Reel Cabinets

LPCB Ref.
Product Name Description
No.

BF-SRM-MS2 800x800x300 single cabinet, recessed, full MS

BF-SRS-SH2 800x800x300 single cabinet, recessed, full SS hairline-finish

BF-SRS-SM2 800x800x300 single cabinet, recessed, full SS mirror-finish

BF-SRM-SH2 800x800x300 single cabinet, recessed, MS back box with SS hairline-finish

BF-SRM-SM2 800x800x300 single cabinet, recessed, MS back box with SS mirror-finish

BF-SSM-MS2 800x800x300 single cabinet, surface mounted, full MS

BF-SSS-SH2 800x800x300 single cabinet, surface mounted, full SS hairline-finish


1226a/05
BF-SSS-SM2 800x800x300 single cabinet, surface mounted, full SS mirror-finish

BF-SFM-MS1 700x700x300 free-standing single cabinet, full MS

BF-SFS-SH1 700x700x300 free-standing single cabinet, full SS hairline-finish

BF-SFS-SM1 700x700x300 free-standing single cabinet, full SS mirror-finish

BF-SFM-MS2 800x800x300 free-standing single cabinet, full MS

BF-SFS-SH2 800x800x300 free-standing single cabinet, full SS hairline-finish

BF-SFS-SM2 800x800x300 free-standing single cabinet, full SS mirror-finish

This certificate and appendix is maintained and held in force through regular surveillance activities

Joe Milton 26 March 2014 26 March 2014


Signed for LPCB Verifier Date of Issue Date of First Issue

This certificate and appendix remain the property of BRE Global Ltd and is issued
subject to terms and conditions (for details visit www.redbooklive.com/terms).
To check the validity of this certificate and appendix please visit
www.redbooklive.com/check, scan the QR Tag or contact us.
LPCB is part of BRE Global Ltd., Garston, Watford WD25 9XX.
T: +44 (0)1923 664100 F: +44 (0)1923 664603 E: Enquiries@breglobal.com

BF 1315A Rev 0.0 Page 3 of 5 © BRE Global Ltd, 2014


Appendix to Certificate No: 1226a Issue: 01
XXXa Fire Engineering LLC
Bristol
Fire Hose Reel Cabinets

LPCB Ref.
Product Name Description
No.

BF-DRM-MS1 1400x700x300 double cabinet, recessed, full MS

BF-DRS-SH1 1400x700x300 double cabinet, recessed, full SS hairline-finish

BF-DRS-SM1 1400x700x300 double cabinet, recessed, full SS mirror-finish

BF-DRM-SH1 1400x700x300 double cabinet, recessed, MS back box with SS hairline-finish

BF-DRM-SM1 1400x700x300 double cabinet, recessed, MS back box with SS mirror-finish

BF-DSM-MS1 1400x700x300 double cabinet, surface mounted, full MS

BF-DSS-SH1 1400x700x300 double cabinet, surface mounted, full SS hairline-finish

BF-DSS-SM1 1400x700x300 double cabinet, surface mounted, full SS mirror-finish


1226a/06
BF-DRM-MS2 1600x800x300 double cabinet, recessed, full MS

BF-DRS-SH2 1600x800x300 double cabinet, recessed, full SS hairline-finish

BF-DRS-SM2 1600x800x300 double cabinet, recessed, full SS mirror-finish

BF-DRM-SH2 1600x800x300 double cabinet, recessed, MS back box with SS hairline-finish

BF-DRM-SM2 1600x800x300 double cabinet, recessed, MS back box with SS mirror-finish

BF-DSM-MS2 1600x800x300 double cabinet, surface mounted, full MS

BF-DSS-SH2 1600x800x300 double cabinet, surface mounted, full SS hairline-finish

BF-DSS-SM2 1600x800x300 double cabinet, surface mounted, full SS mirror-finish

This certificate and appendix is maintained and held in force through regular surveillance activities

Joe Milton 26 March 2014 26 March 2014


Signed for LPCB Verifier Date of Issue Date of First Issue

This certificate and appendix remain the property of BRE Global Ltd and is issued
subject to terms and conditions (for details visit www.redbooklive.com/terms).
To check the validity of this certificate and appendix please visit
www.redbooklive.com/check, scan the QR Tag or contact us.
LPCB is part of BRE Global Ltd., Garston, Watford WD25 9XX.
T: +44 (0)1923 664100 F: +44 (0)1923 664603 E: Enquiries@breglobal.com

BF 1315A Rev 0.0 Page 4 of 5 © BRE Global Ltd, 2014


Appendix to Certificate No: 1226a Issue: 01
XXXa Fire Engineering LLC
Bristol
Fire Hose Reel Cabinets

LPCB Ref.
Product Name Description
No.

BF-DFM-MS1 1400x700x300 free-standing double cabinet, full MS

BF-DFS-SH1 1400x700x300 free-standing double cabinet, full SS hairline-finish

BF-DFS-SM1 1400x700x300 free-standing double cabinet, full SS mirror-finish


1226a/06
BF-DFM-MS2 1600x800x300 free-standing double cabinet, full MS

BF-DFS-SH2 1600x800x300 free-standing double cabinet, full SS hairline-finish

BF-DFS-SM2 1600x800x300 free-standing double cabinet, full SS mirror-finish

This certificate and appendix is maintained and held in force through regular surveillance activities

Joe Milton 26 March 2014 26 March 2014


Signed for LPCB Verifier Date of Issue Date of First Issue

This certificate and appendix remain the property of BRE Global Ltd and is issued
subject to terms and conditions (for details visit www.redbooklive.com/terms).
To check the validity of this certificate and appendix please visit
www.redbooklive.com/check, scan the QR Tag or contact us.
LPCB is part of BRE Global Ltd., Garston, Watford WD25 9XX.
T: +44 (0)1923 664100 F: +44 (0)1923 664603 E: Enquiries@breglobal.com

BF 1315A Rev 0.0 Page 5 of 5 © BRE Global Ltd, 2014


3/14/2018 VNIV.EX15981 - Sprinklers, Automatic and Open

VNIV.EX15981
Sprinklers, Automatic and Open
Page Bottom

Sprinklers, Automatic and Open

See General Information for Sprinklers, Automatic and Open

BRISTOL FIRE ENGINEERING L L C EX15981


AL QUOZ INDUSTRIAL AREA 3
PO BOX 74582
DUBAI, UNITED ARAB EMIRATES

Sprinkler Identification Number (SIN) H001, H002, H003, H004, H005 and H006 Glass Bulb Type - Chrome-plated Sprinklers are identified by
CP on the deflector.

Sprinkler Identification Number (SIN), Glass Bulb Type BF001, BF005, BF002, BF004, BF003, BF006, BF007, and BF008.

UPRIGHT AND PENDENT STANDARD SPRAY SPRINKLERS

NOMINAL 5.6 K-FACTOR

Response System Working


SIN Type Type Pressure, psig Temp Rating, °F

H001 SR Upright 175 155, 175, 200

H002 QR Upright 175 155, 175, 200

H003 SR Pendent 175 155, 175, 200

H004 QR Pendent 175 155, 175, 200

UPRIGHT AND PENDENT STANDARD SPRAY SPRINKLERS

NOMINAL 5.6 K - FACTOR

Response Nom System Working


SIN Type Type K-Factor Pressure, psig Temp Rating, °F

BF001 SR Upright 5.6 175 135, 155, 175, 200

BF005 QR Upright 5.6 175 135, 155, 175, 200

BF002 SR Pendent 5.6 175 135, 155, 175, 200

BF004 QR Pendent 5.6 175 135, 155, 175, 200

STANDARD SIDEWALL SPRAY SPRINKLERS

Response Nom System Working


SIN Type Type K-Factor Pressure, psig Temp Rating, °F

H005 SR Horizontal 5.6 175 155, 175, 200

H006 QR Horizontal 5.6 175 155, 175, 200

STANDARD SIDEWALL SPRAY SPRINKLERS

Response Nom System Working


SIN Type Type K-Factor Pressure, psig Temp Rating, °F

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=VNIV.EX15981&ccnshorttitle=Sprinklers,+Automatic+and+Open&objid=1081969
3/14/2018 VNIV.EX15981 - Sprinklers, Automatic and Open
BF007*# SR Horizontal 5.6 175 135, 155, 175, 200

BF008*# QR Horizontal 5.6 175 135, 155, 175, 200

* - Installed 4 to 6 in. below ceiling.

# - For ordinary hazard occupancies.

FLUSH, RECESSED, AND CONCEALED SPRINKLERS

Temp Rating, °F
Response Nom
SIN Type Type K-Factor Cover Sprinkler

BF003 SR Concealed 5.6 135, 155 135, 155, 175, 200

BF006 QR Concealed 5.6 135, 155 135, 155, 175, 200

Last Updated on 2016-05-09

Questions? Print this page Terms of Use Page Top

© 2018 UL LLC

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
the following format: "© 2018 UL LLC".

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=VNIV.EX15981&ccnshorttitle=Sprinklers,+Automatic+and+Open&objid=1081969
No. KM 503775
The British Standards Institution hereby grants to:

Bristol Fire Engineering


PO Box 74582
Dubai
UAE

In respect of:
BS EN 3
Portable fire extinguishers

This issues the right and licence to use the Kitemark in accordance with the Kitemark Licence Conditions of
Contract governing the use of the Kitemark, as may be updated from time to time by The British Standards
Institution, and as approved by the Registrar under the Trade Marks Act 1994 (the "Conditions"). All defined terms
in this Licence shall have the same meaning as in the Conditions.

The use of the Kitemark is authorized in respect of the Product(s) detailed on this Licence provided at or from the
above address.

For and on behalf of The British Standards Institution:

David W. Ford, Executive Director, Healthcare & Testing Services

First Issued: 13/05/2009 Latest Issue: 21/09/2010

Page 1 of 2
This Licence remains the property of The British Standards Institution and shall be returned immediately upon request. To check its validity telephone +44 (0)8450 765600.

The British Standards Institution, Kitemark House, Maylands Avenue, Hemel Hempstead, Hertfordshire, HP2 4SQ, United Kingdom. Tel:+44 (0)8450 765600 Web:
www.bsigroup.com/certification. The British Standards Institution Headquarters: 389 Chiswick High Road, London, W4 4AL. Tel:+44 (0)20 8996 9001. The British
Standards Institution is incorporated by Royal Charter.
No. KM 503775
BS EN 3 Portable fire extinguishers

Model designation Description Fire ratings


DP1 1 kg 40% ABC powder, stored pressure 5A & 34B
DP2 2 kg 40% ABC powder, stored pressure 13A & 70B
DP4 4 kg 40% ABC powder, stored pressure 21A & 113B
DP6 6 kg 40% ABC powder, stored pressure 27A & 183B
DP9 9 kg 40% ABC powder, stored pressure 34A & 233B
DP12 12 kg 40% ABC powder, stored pressure 43A & 233B
WE6 6 litre water, stored pressure 8A
WE9 9 litre water, stored pressure 13A

The above products are also branded under the names:


Eagle
Safe

First Issued: 13/05/2009 Latest Issue: 21/09/2010 Page 2 of 2

This Licence remains the property of The British Standards Institution and shall be returned immediately upon request. To check its validity telephone +44 (0)8450 765600.

The British Standards Institution, Kitemark House, Maylands Avenue, Hemel Hempstead, Hertfordshire, HP2 4SQ, United Kingdom. Tel:+44 (0)8450 765600 Web:
www.bsigroup.com/certification. The British Standards Institution Headquarters: 389 Chiswick High Road, London, W4 4AL. Tel:+44 (0)20 8996 9001. The British
Standards Institution is incorporated by Royal Charter.
No.
No. KM
KM587564
587564
The licence is granted to:

Bristol Fire Engineering


PO Box 74582
Dubai
UAE

In respect of:
Portable fire extinguishers

This issues the right and licence to use the Kitemark in accordance with the Kitemark Licence Conditions of
Contract governing the use of the Kitemark, as may be updated from time to time by The British Standards
Institution, and as approved by the Registrar under the Trade Marks Act 1994 (the "Conditions"). All defined terms
in this Licence shall have the same meaning as in the Conditions.

The use of the Kitemark is authorized in respect of the Product(s) detailed on this Licence provided at or from the
above address.

For and on behalf of BSI:

Gary Fenton, Global Assurance Director

First Issued: 6/07/2012 Latest Issue: 6/07/2012

First Issued: 6/07/2012 Latest Issue: 6/07/2012

Page
Page1 of
1 2of 2
This Licence remains the property of The British Standards Institution and shall be returned immediately upon request. To check its validity telephone +44 (0)845 080 9000

Information and contact: BSI, Kitemark Court, Davy Avenue, Knowlhill, Milton Keynes MK5 8PP. Tel: +44 845 080 9000. BSI Assurance UK Limited, registered in
England under number 7805321, at 389 Chiswick High Road, London, W4 4AL, UK. A member of the BSI Group of Companies.
No. KM 587564

BS EN 3 – Portable Fire Extinguishers

Model Description Fire ratings

CD2 2 kg carbon dioxide 34B

CD5 5 kg carbon dioxide 89B

FE6 6 litre foam, stored pressure 13A & 144B

FE9 9 litre foam, stored pressure 13A & 183B

The above products may be Kitemarked when branded with the following tradenames:
Concorde
Eagle
EFFECO
Marshal
Safe

For the purposes of traceability the Kitemark licence number must appear adjacent to the Kitemark
symbol on all branded products.

First Issued: 6/07/2012 Latest Issue: 6/07/2012

Page 2 of 2
This Licence remains the property of The British Standards Institution and shall be returned immediately upon request. To check its validity telephone +44 (0)845 080 9000

Information and contact: BSI, Kitemark Court, Davy Avenue, Knowlhill, Milton Keynes MK5 8PP. Tel: +44 845 080 9000. BSI Assurance UK Limited, registered in
England under number 7805321, at 389 Chiswick High Road, London, W4 4AL, UK. A member of the BSI Group of Companies.
11/10/2016 VLMT.EX2534 ­ Special System Water Control Valves, Pressure­reducing and Pressure­control Type

VLMT.EX2534
Special System Water Control Valves, Pressure­reducing and Pressure­control
Type

Page Bottom

Special System Water Control Valves, Pressure­reducing and Pressure­control


Type

See General Information for Special System Water Control Valves, Pressure­reducing and Pressure­control Type

GRISWOLD INDUSTRIES, DBA CLA­VAL CO EX2534


1701 PLACENTIA AVE
COSTA MESA, CA 92627­4416 USA

"Clayton" , pilot operated pressure control valves, iron iron body, (sizes 1­1/2 to 8 in.), ductile iron body (sizes 1­1/2 to 8 in) and bronze body
(sizes 1­1/2 to 3 in.) consisting of the following models, sizes, inlet pressure ratings, and outlet pressure setting ranges:

Max Rated Outlet Pressure


Inlet Pressure Setting Range
Model Size In. psig psig

90G­21 1­1/2 to 8 175 30­165

90A­21 2 to 6 175 30­165

"Clayton", pilot operated pressure control valves, steel body, (sizes 1­1/2 to 6 in.) ductile iron body (1­1/2 to 6 in.) and bronze body (sizes 1­
1/2 to 3 in.) consisting of the following models, sizes, inlet pressure ratings, and outlet pressure setting ranges:

Max Rated Outlet Pressure


Inlet Pressure Setting Range
Model Size In. psig psig

90G­21 1­1/2 to 8 300 30­165

90A­21 1­1/2 to 8 300 30­165

For all valves, the manufacturer's design and installation instructions include a description of the performance characteristics for both flow and
static conditions.

Last Updated on 2008­07­03

Questions? Print this page Terms of Use Page Top

© 2016 UL LLC

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow­Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow­Up
Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non­
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
the following format: "© 2016 UL LLC".

http://database.ul.com/cgi­bin/XYV/template/LISEXT/1FRAME/showpage.html?name=VLMT.EX2534&ccnshorttitle=Special+System+Water+Control+Valves,+… 1/1
Kitemark™ Certificate
Kitemark™ Certificate
No. KM 677822

This is to certify that: Bristol Fire Engineering LLC


PO Box 74582
Al Qouz industrial area 3
Dubai
United Arab Emirates

Holds Certificate Number: KM 677822

In respect of:

BS EN 1869
Fire Blankets

This issues the right and licence to use the Kitemark in accordance with the Kitemark Terms and Conditions
governing the use of the Kitemark, as may be updated from time to time by BSI Assurance UK Ltd (the "Conditions").
All defined terms in this Certificate shall have the same meaning as in the Conditions.

The use of the Kitemark is authorized in respect of the Product(s) detailed on this Certificate provided at or from the
above address.

For and on behalf of BSI: Gary Fenton, Global Product Certification Director

First Issued: 2017-08-22 Latest Issue: 2017-08-22

Page: 1 of 2

First Issued: 2017-08-22 Latest Issue: 2017-08-22

Page: 1 of 2
This certificate has been issued by and remains the property of BSI Assurance UK Ltd, Kitemark Court, Davy Avenue, Knowlhill, Milton Keynes MK5 8PP, United
Kingdom and should be returned immediately upon request.
To check its validity telephone +44 (0) 345 080 9000. An electronic certificate can be authenticated online.

BSI Assurance UK Limited, registered in England under number 7805321 at 389 Chiswick High Road, London W4 4AL, UK.
A member of BSI Group of Companies.
Kitemark™ Certificate
No. KM 677822

Model No Description

FGC11 1.1 x 1.1m Fire Blanket

FGC12 1.2 x 1.2m Fire Blanket

FGC18 1.2 x 1.8m Fire Blanket

All the above products are certified BS EN 1869: 1997.

First Issued: 2017-08-22 Latest Issue: 2017-08-22

Page: 2 of 2
This certificate has been issued by and remains the property of BSI Assurance UK Ltd, Kitemark Court, Davy Avenue, Knowlhill, Milton Keynes MK5 8PP, United
Kingdom and should be returned immediately upon request.
To check its validity telephone +44 (0) 345 080 9000. An electronic certificate can be authenticated online.

BSI Assurance UK Limited, registered in England under number 7805321 at 389 Chiswick High Road, London W4 4AL, UK.
A member of BSI Group of Companies.
8/14/2017 USQT.S35811 - Extinguishing System Attachments

USQT.S35811
Extinguishing System Attachments
Page Bottom

Extinguishing System Attachments

See General Information for Extinguishing System Attachments

SHANGHAI IRON MAN FIRE FIGHTING EQUIPMENT CO.,LTD. S35811


Room 2343, Block 3, No.612, Shangchuang Road
Pudong New Area
201315 Shanghai, CHINA

SPRINKLER SYSTEM ALARM INITIATING DEVICES

Wet pipe, paddle type


Size Pipe Max System
Model In. Schedule Pressure psig

IMT6001-25 1.00 10 thru 40 450

IMT6001-32 1.25 10 thru 40 450

IMT6001-40 1.50 10 thru 40 450

IMT6001-50 2.00 450

IM6001-50 2 10 thru 40 450

IM6001-65 2.5 10 thru 40 450

IM6001-80 3 10 thru 40 450

IM6001-100 4 10 thru 40 450

IM6001-125 5 10 thru 40 450

IM6001-150 6 10 thru 40 450

IM6001-200 8 10 thru 40 450

Last Updated on 2017-07-17

Questions? Print this page Terms of Use Page Top

© 2017 UL LLC

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
the following format: "© 2017 UL LLC".

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=USQT.S35811&ccnshorttitle=Extinguishing+System+Attachment… 1/1
Waterflow Detectors, Vane Type
Waterflow detectors installed in sprinkler systems provide an electrical alarm when a flow of water from the system equals or exceeds
that of a single sprinkler. They can be used with either open or closed signaling circuits.
They may consist of a flexible vane which projects into the waterway or a pressure-sensing device. For the flexible vane type, water
movement deflects the vane, and the motion is transmitted to an alarm-actuating switch after a predetermined time delay. The time
delay is accomplished by the use of an instantly recycling retard.
Unless otherwise noted in the listing, the flexible vane type is to be used with pipe having an inside diameter which corresponds to
Schedule 40 pipe for sizes up to and including 6 in. (152 mm) or Schedule 30 pipe for sizes 8 and 10 in. (203 and 254 mm).
Waterflow detectors should not be specified for those systems where the time duration of a pressure fluctuation is greater than the
retard time. Instantly recycling retards will not transmit an electrical alarm until the time duration of the pressure fluctuation or
waterflow past the vane of the flow detector has exceeded the predetermined time setting of 30-60 seconds. Unless otherwise noted
in the listing, these detectors have 175 psi (1205 kPa) rated working pressure.

Models IM6001-50, IM6001-65, IM6001-80, IM6001-100, IM6001-125, IM6001-150, IM6001-200


Models IM6001-50, IM6001-65, IM6001-80, IM6001-100, IM6001-125, IM6001-150, IM6001-200. Rated working pressure of 450 psi
(3105 kPa). Two snap switches and pneumatic retard.
All sizes rated for Schedule 10 and 40 pipe.

Model No. Nominal Pipe Size, in. (mm)


IM6001-50 2 (50)
IM6001-65 2-1/2 (65)
IM6001-80 3 (80)
IM6001-100 4 (100)
IM6001-125 5 (125)
IM6001-150 6 (150)
IM6001-200 8 (200)

Company Name: Shanghai Iron Man Fire Fighting Equipment Co., Ltd
Company Address: Room 716, 7F, No.100, Xiuyan Road, Shanghai 201315, P. R. China
Company Website: http://firefightingtool.com
New/Updated Product Listing: No
Listing Country: China
Certification Type: FM Approved

© 2007-2017 FM Approvals. All rights reserved. 1 of 1


HLXS.EX16012
Butterfly Valves

Page Bottom

Butterfly Valves

Se e Ge ne ra l Inform a tion for Butte rfly Va lve s

BRISTOL FIRE ENGINEERING L L C EX16012


AL Q UO Z INDUSTR IAL AR EA 3
PO BO X 74582
DUBAI, UNITED AR AB EMIR ATES

Pressure
Rating, psig Indicator Supervisory
Model Size, NPS Body Type (Bar) Post Switch*

Butterfly valve

"BR -DW 175" 2.5, 3, 4, 6, 8 Ductile Iron W a fe r 175 (12) — I

"BR -DG 175" 2.5, 3, 4, 6, 8 Ductile Iron Groove d End 175 (12) — I

"BR -HPW -300" 2.5, 3, 4, 6, 8 Ductile Iron W a fe r 300 (21) — O

"BR -HPG-300" 2.5, 3, 4, 6, 8 Ductile Iron Groove d End 300 (21) — O

"BR -FF-TH" 1, 1.25, 1.5, 2 Thre a de d Bronze 175 (12) — —

"BR -FF-G" 2, 2.5 Groove d End Bronze 175 (12) — O


* I = Indoor insta lla tion; O = O utdoor insta lla tion

Last Upda te d on 2013-09-03

Q ue stions? Print this page Te rm s of Use Pa ge Top

© 2013 UL LLC

W he n the UL Le a f Ma rk is on the product, or whe n the word "Environm e nt" is include d in the UL Mark , ple a se se arch the UL
Environm e nt da ta ba se for a dditiona l inform a tion re ga rding this product's ce rtification.

The appe a ra nce of a com pa ny's na m e or product in this database doe s not in itse lf a ssure that products so ide ntifie d have be e n
m anufa cture d unde r UL's Follow-Up Se rvice . O nly those products be a ring the UL Mark should be conside re d to be C e rtifie d and
cove re d unde r UL's Follow-Up Se rvice . Alwa ys look for the Ma rk on the product.

UL pe rm its the re production of the m a te ria l conta ine d in the O nline C e rtification Dire ctory subje ct to the following conditions: 1.
The Guide Inform a tion, Asse m blie s, C onstructions, De signs, Syste m s, and/or C e rtifications (file s) m ust be pre se nte d in the ir
e ntire ty a nd in a non-m isle a ding m a nne r, without a ny m a nipula tion of the data (or drawings). 2. The sta te m e nt "R e printe d from
the O nline C e rtifica tions Dire ctory with pe rm ission from UL" m ust a ppe ar adja ce nt to the e x tra cte d m a te ria l. In addition, the
re printe d m a te ria l m ust include a copyright notice in the following form at: "© 2013 UL LLC ".
Indicating Valves, Butterfly or Ball Type
Design features provide a dependable visible indication of the open position even at a distance. If excessive force is applied to the
handle, weakness-joints will break so as to preserve correct orientation between indicator and valve position. Valve and indicator
parts are so designed that they can be assembled only one way, always to give correct indication. All FM Approved indicating valves
turn clockwise to shut. They are small, lightweight, and, because of a resilient seat, are easy to operate. They are not subject to
sticking or dropped gates. They are not recommended for throttling service. Unless otherwise noted in the listing, these valves have
175 psi (1205 kPa) rated working pressure.

Model Nos. BR-HPG-300, BR-HPW-300, BR-DG 175, BR-DW 175, BR-FF-TH, BR-FF-G

Rated Working
Nominal Pipe
Model Number Product Type Pressure, Remarks
Size, mm
psi (kPa)

Butterfly Valve, 2 ½ , 3, 4, 6 300


BR-HPG-300 a, b, c
Grooved Ends (65 ,80, 100, 150) (2070)

Butterfly Valve, 2 ½, 3, 4, 6 300


BR-HPW-300 a, b, c
Wafer Style (65 ,80, 100, 150) (2070)

Butterfly Valve, 2 ½, 3, 4, 6, 8 175


BR-DG 175 a, b, c
Grooved Ends (65, 80, 100, 150, 200) (1205)

Butterfly Valve, 2 ½, 3, 4, 6, 8 175


BR-DW 175 a, b, c
Wafer Body (65, 80, 100, 150, 200) (1205)

Butterfly Valve, 1, 1 ¼, 1 ½, 2, 2 ½ 175


BR-FF-TH a, b, c
Threaded Ends (25, 32, 40, 50, 65) (1205)

Butterfly Valve, 2, 2 ½ 175


BR-FF-G a, b, c
Grooved Ends (50, 65) (1205)

Remarks:
a. Available with dual supervisory switches.
b. FM Approved for indoor and outdoor service.
c. FM Approved for aboveground installations only.

Company Name: Bristol Fire Engineering LLC


Company Address: P.O. Box 74582, Dubai, United Arab Emirates
Company Website: http://www.bristol-fire.com
New/Updated Product Listing: No
Listing Country: United Arab Emirates
Certification Type: FM Approved

© 2007-2013 FM Approvals. All rights reserved. 1 of 1


HMER.EX16011
Check Valves

Page Bottom

Check Valves

Se e Ge ne ra l Inform a tion for C he ck Va lve s

BRISTOL FIRE ENGINEERING L L C EX16011


AL Q UO Z INDUSTR IAL AR EA 3
PO BO X 74582
DUBAI, UNITED AR AB EMIR ATES

Swing type, Mode l BR -DGC -300, size s 2, 2-1/2, 3, 4, 5, 6 a nd 8 in., with re silie nt se at size for rate d pre ssure of 300 psig
horizonta l a nd ve rtica l installation.

Last Upda te d on 2013-09-03

Q ue stions? Print this page Te rm s of Use Pa ge Top

© 2013 UL LLC

W he n the UL Le a f Ma rk is on the product, or whe n the word "Environm e nt" is include d in the UL Mark , ple a se se arch the UL
Environm e nt da ta ba se for a dditiona l inform a tion re ga rding this product's ce rtification.

The appe a ra nce of a com pa ny's na m e or product in this database doe s not in itse lf a ssure that products so ide ntifie d have be e n
m anufa cture d unde r UL's Follow-Up Se rvice . O nly those products be a ring the UL Mark should be conside re d to be C e rtifie d and
cove re d unde r UL's Follow-Up Se rvice . Alwa ys look for the Ma rk on the product.

UL pe rm its the re production of the m a te ria l conta ine d in the O nline C e rtification Dire ctory subje ct to the following conditions: 1.
The Guide Inform a tion, Asse m blie s, C onstructions, De signs, Syste m s, and/or C e rtifications (file s) m ust be pre se nte d in the ir
e ntire ty a nd in a non-m isle a ding m a nne r, without a ny m a nipula tion of the data (or drawings). 2. The sta te m e nt "R e printe d from
the O nline C e rtifica tions Dire ctory with pe rm ission from UL" m ust a ppe ar adja ce nt to the e x tra cte d m a te ria l. In addition, the
re printe d m a te ria l m ust include a copyright notice in the following form at: "© 2013 UL LLC ".
Single Check Valves
Single check valves are used in fire protection systems to allow waterflow in one direction only. Typical applications are at
connections between public water supplies and private fire service systems, at the discharge from fire pumps, at gravity tank
connections and at fire service pumper connections.
Valves identified in the listing by a single asterisk (*) have side covers; valves identified by a double asterisk (**) have no removable
covers; others have top covers. Clearance must be provided for side-cover valves to permit clapper removal. Valves without covers
must be removed from the system for clapper replacement or repair. Unless otherwise noted in the listing, these valves have 175 psi
(1205 kPa) rated working pressure.

BR-DGC-300

Max Working
Product Nominal Pipe
Description Pressure, psi Remarks
Designation Size, in.
(kPa)

BR-DGC-300 Swing Check Valve 2 1/2, 3, 4, 5, 6, 8 300 a


Grooved ends 76.1 mm, 165.1 mm (2070)

a. Resilient Seat.

Company Name: Bristol Fire Engineering LLC


Company Address: P.O. Box 74582, Dubai, United Arab Emirates
Company Website: http://www.bristol-fire.com
New/Updated Product Listing: No
Listing Country: United Arab Emirates
Certification Type: FM Approved

© 2007-2013 FM Approvals. All rights reserved. 1 of 1


Sprinkler System Alarm Testers
Each separate sprinkler system must be equipped with a separate waterflow alarm. In a high rise building, the system for each floor
must be separately alarmed. Where pressure reducing valves are used, a dual alarm and drain piping arrangement is required. The
alarm testers listed below combine test and drain valves, a waterflow sight glass, and a calibrated flow orifice in a single assembly to
simplify the piping required for such arrangements.

Model BF-VT001

Rated working
Size, Nominal
Model Designation pressure, Remarks
inch NPS K-factor (s)
psi (kPa)

175
BF-VT001 1, 1-1⁄4 5.6 a
(1205)

Remarks:
a. Devices supplied with female threaded inlet and a male threaded outlet end connection.

Company Name: Bristol Fire Engineering LLC


Company Address: P.O. Box 74582, Dubai, United Arab Emirates
Company Website: http://www.bristol-fire.com
New/Updated Product Listing: No
Listing Country: United Arab Emirates
Certification Type: FM Approved

© 2007-2013 FM Approvals. All rights reserved. 1 of 1


HMRZ.EX16103
Gate Valves

Page Bottom

Gate Valves

Se e Ge ne ra l Inform a tion for Ga te Va lve s

BRISTOL FIRE ENGINEERING L L C EX16103


AL Q UO Z INDUSTR IAL AR EA 3
PO BO X 74582
DUBAI, UNITED AR AB EMIR ATES

R e silie nt Se a te d Ga te Valve s.

Rated
End Pressure,
Pattern Model Size, in. Configuration psig

*NR S 388F 2.5, 3, 4, 5, 6, 8, 10, 12 Fla nge d 300

O ,S&Y 399F 2.5, 3, 4, 5, 6, 8, 10, 12 Fla nge d 300

*NR S va lve provide d with a Post Indica tor Fla nge

Last Upda te d on 2013-09-03

Q ue stions? Print this page Te rm s of Use Pa ge Top

© 2013 UL LLC

W he n the UL Le a f Ma rk is on the product, or whe n the word "Environm e nt" is include d in the UL Mark , ple a se se arch the UL
Environm e nt da ta ba se for a dditiona l inform a tion re ga rding this product's ce rtification.

The appe a ra nce of a com pa ny's na m e or product in this database doe s not in itse lf a ssure that products so ide ntifie d have be e n
m anufa cture d unde r UL's Follow-Up Se rvice . O nly those products be a ring the UL Mark should be conside re d to be C e rtifie d and
cove re d unde r UL's Follow-Up Se rvice . Alwa ys look for the Ma rk on the product.

UL pe rm its the re production of the m a te ria l conta ine d in the O nline C e rtification Dire ctory subje ct to the following conditions: 1.
The Guide Inform a tion, Asse m blie s, C onstructions, De signs, Syste m s, and/or C e rtifications (file s) m ust be pre se nte d in the ir
e ntire ty a nd in a non-m isle a ding m a nne r, without a ny m a nipula tion of the data (or drawings). 2. The sta te m e nt "R e printe d from
the O nline C e rtifica tions Dire ctory with pe rm ission from UL" m ust a ppe ar adja ce nt to the e x tra cte d m a te ria l. In addition, the
re printe d m a te ria l m ust include a copyright notice in the following form at: "© 2013 UL LLC ".
Outside Screw and Yoke Gate Valves
Outside screw and yoke gate valves are recommended for service indoors and in pits outdoors. They are not recommended for
throttling service. The stem indicates at a glance whether or not the valve is open. Smaller sizes, 3⁄4 through 2 in. NPS inclusive, are
of bronze. Large sizes, 2 1⁄2 through 14 in. NPS inclusive, are of iron, bronze mounted. One manufacturer makes valves of bronze up
through the 3 in. size. Unless otherwise noted in the listing, these valves have 175 psi (1205 kPa) rated working pressure.

FIG NO. 399F


Resilient Seated Gate Valves. 2-1⁄2 through 12 in. NPS. Valves have a rated working pressure of 300 psi (2070 kPa). Available
with the following end connection:

Size
End
Model in.
Connection
(mm)

Fig 2 Flange ×
No. 1/2, Flange
399F 3, 4,
5, 6,
8, 10,
12
(65,
80,
100,
125,
150,
200,
250,
300)

Company Name: Bristol Fire Engineering LLC


Company Address: P.O. Box 74582, Dubai, United Arab Emirates
Company Website: http://www.bristol-fire.com
New/Updated Product Listing: No
Listing Country: United Arab Emirates
Certification Type: FM Approved

© 2007-2013 FM Approvals. All rights reserved. 1 of 1


12/19/2017 VQDI.EX4509 - Valves, System Pressure Relief

VQDI.EX4509
Valves, System Pressure Relief
Page Bottom

Valves, System Pressure Relief

See General Information for Valves, System Pressure Relief

WATTS REGULATOR CO EX4509


815 CHESTNUT ST
NORTH ANDOVER, MA 01845 USA

Model FP-53L-175 pressure relief valve, 1/2 in. NPT size for horizontal or vertical installation having a set pressure rating of 175 psig.

Last Updated on 2015-05-15

Questions? Print this page Terms of Use Page Top

© 2017 UL LLC

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
the following format: "© 2017 UL LLC".

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=VQDI.EX4509&ccnshorttitle=Valves,+System+Pressure+Relief&… 1/1
11/10/2016 VLMT.EX2534 ­ Special System Water Control Valves, Pressure­reducing and Pressure­control Type

VLMT.EX2534
Special System Water Control Valves, Pressure­reducing and Pressure­control
Type
Page Bottom

Special System Water Control Valves, Pressure­reducing and Pressure­control


Type

See General Information for Special System Water Control Valves, Pressure­reducing and Pressure­control Type

GRISWOLD INDUSTRIES, DBA CLA­VAL CO EX2534


1701 PLACENTIA AVE
COSTA MESA, CA 92627­4416 USA

"Clayton" , pilot operated pressure control valves, iron iron body, (sizes 1­1/2 to 8 in.), ductile iron body (sizes 1­1/2 to 8 in) and bronze body
(sizes 1­1/2 to 3 in.) consisting of the following models, sizes, inlet pressure ratings, and outlet pressure setting ranges:

Max Rated Outlet Pressure


Inlet Pressure Setting Range
Model Size In. psig psig

90G­21 1­1/2 to 8 175 30­165

90A­21 2 to 6 175 30­165

"Clayton", pilot operated pressure control valves, steel body, (sizes 1­1/2 to 6 in.) ductile iron body (1­1/2 to 6 in.) and bronze body (sizes 1­
1/2 to 3 in.) consisting of the following models, sizes, inlet pressure ratings, and outlet pressure setting ranges:

Max Rated Outlet Pressure


Inlet Pressure Setting Range
Model Size In. psig psig

90G­21 1­1/2 to 8 300 30­165

90A­21 1­1/2 to 8 300 30­165

For all valves, the manufacturer's design and installation instructions include a description of the performance characteristics for both flow and
static conditions.

Last Updated on 2008­07­03

Questions? Print this page Terms of Use Page Top

© 2016 UL LLC

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow­Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow­Up
Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non­
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
the following format: "© 2016 UL LLC".

http://database.ul.com/cgi­bin/XYV/template/LISEXT/1FRAME/showpage.html?name=VLMT.EX2534&ccnshorttitle=Special+System+Water+Control+Valves,+… 1/1
VEHZ.EX15983
Drain Fittings, Special Type

Page Bottom

Drain Fittings, Special Type

Se e Ge ne ra l Inform a tion for Dra in Fittings, Spe cia l Type

BRISTOL FIRE ENGINEERING L L C EX15983


AL Q UO Z INDUSTR IAL AR EA 3
PO BO X 74582
DUBAI, UNITED AR AB EMIR ATES

Mode l "BF-VT001" te st a nd dra in fitting in the following nom inal size s, discha rge coe fficie nts and rate d pre ssure s:

Size, Nominal K-Factor, Rated Pressure,


in. gpm/(psi)1/2 psig

1, 1-1/4 5.6 175

Last Upda te d on 2013-11-21

Q ue stions? Print this page Te rm s of Use Pa ge Top

© 2013 UL LLC

W he n the UL Le a f Ma rk is on the product, or whe n the word "Environm e nt" is include d in the UL Mark , ple a se se arch the UL
Environm e nt da ta ba se for a dditiona l inform a tion re ga rding this product's ce rtification.

The appe a ra nce of a com pa ny's na m e or product in this database doe s not in itse lf a ssure that products so ide ntifie d have be e n
m anufa cture d unde r UL's Follow-Up Se rvice . O nly those products be a ring the UL Mark should be conside re d to be C e rtifie d and
cove re d unde r UL's Follow-Up Se rvice . Alwa ys look for the Ma rk on the product.

UL pe rm its the re production of the m a te ria l conta ine d in the O nline C e rtification Dire ctory subje ct to the following conditions: 1.
The Guide Inform a tion, Asse m blie s, C onstructions, De signs, Syste m s, and/or C e rtifications (file s) m ust be pre se nte d in the ir
e ntire ty a nd in a non-m isle a ding m a nne r, without a ny m a nipula tion of the data (or drawings). 2. The sta te m e nt "R e printe d from
the O nline C e rtifica tions Dire ctory with pe rm ission from UL" m ust a ppe ar adja ce nt to the e x tra cte d m a te ria l. In addition, the
re printe d m a te ria l m ust include a copyright notice in the following form at: "© 2013 UL LLC ".
USQT.S739 - Extinguishing System Attachments Page 1 of 2

USQT.S739
Extinguishing System Attachments
Page Bottom

Extinguishing System Attachments

See General Information for Extinguishing System Attachments

SYSTEM SENSOR UNINCORPORATED, DIV OF HONEYWELL INTERNATIONAL INC S739


3825 OHIO AVE
ST CHARLES, IL 60174 USA

Water-supply valve position signals, Models OSY2, PIBV2, suitable for outdoor use.

Wet-pipe sprinkler system attachments: Water-flow indicators (paddle type), suitable for indoor and outdoor installation.

Max Working
Model Size In. Pipe Schedule Pressure psig

WFD20, ZSJZ50 2 10 through 40 450

WFD25, ZSJZ65 2-1/2 10 through 40 450

WFD30 3 10 through 40 450

WFD30-2, ZSJZ80 3 10 through 40 450

WFD35 3-1/2 10 through 40 450

WFD40, ZSJZ100 4 10 through 40 450

WFD50, ZSJZ125 5 10 through 40 450

WFD60, ZSJZ150 6 10 through 40 450

WFD80, ZSJZ200 8 10 through 40 450

WFDT, ZSJZ25, WFDTNR, 1, 1-1/4, 1-1/2 10, 40 or Brass 250

WFDTH 1, 1-1/4, 1-1/2 or 2 Copper 250

2 Cast/Ductile 250

Iron

1, 1-1/2 Plastic 250

LFD30-2 3 40 450

RFDTH (Rated NEMA Type 4) 1, 1-1/2, 2 Reliable Riser 250

The LFD Series waterflow indicators are low flow devices intended to operate between 1-3 gpm.

Wet-pipe sprinkler system attachments: Water-flow indicators (paddle type), suitable for indoor and outdoor installation shipped without "U"
bolts and nuts to Victaulic customer. Models may be single or bulk-packaged. The packing cartons will also include the assigned Victaulic Part Code
on the exterior.

Model WFD20V with Victaulic Part Code CXS020747020.

Model WFD20AV with Victaulic Part Code .CXS020747021

Model WFD25V with Victaulic Part Code CXS024747022.

Model WFD25VAV with Victaulic Part Code CXS024747023.

Model WFD30-2V with Victaulic Part Code CSX030747N23.

Model WFD30-2AV with Victaulic Part Code CSX030747N24.

Model WFD40V with Victaulic Part Code CXS040747025..

Model WFD40VAV with Victaulic Part Code CXS040747026.

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?nam... 11/05/2009
Electrical Signaling
Electrical protective signaling systems are configurations of components used to produce alarm signals indicative of fire, smoke,
sprinkler waterflow or other emergency and to produce supervisory signals indicative of conditions needing attention with respect to
protection equipment or watch service. System configurations are classified according to where and how the signals are received.
The categories are commonly designated as local, municipal, remote station, proprietary and central station. Auxiliary systems are
either local or proprietary systems interconnected with a municipal system.
This category presents the major system component categories and the integrated system configurations. The selection of
components to form a hybrid system should be made only by those skilled in system design. Also, the suitability of any system
application should be judged on the basis of the hazard(s) being protected.

Supervisory Signal Initiating Devices


Supervisory signals indicate non-alarm conditions affecting important parts of a protection system or timed watchman tours.
Normal/abnormal functions are monitored by these switches and switch-actuated transmitters.

Sprinkler System Supervision


Examples of sprinkler supervisory functions are control valve position, tank pressure, tank level, tank temperature, air pressure,
fire pump power and fire pump operation.

Models OSY2, OSY2A


Gate Valve Switch. Models OSY2, OSY2A. For supervising open position of a gate valve. Model OSY2A is labeled for
Canadian market and has factory installed cover tamper switch rated for 5 A at 125/250 V ac, 2.5 A at 24 V dc. Model
546-7000 cover tamper switch available for Model OSY2 rated for 5 A at 125/250 V ac, 2.5 A at 24 V dc.

Company Name: System Sensor Div of Honeywell


Company Address: 3825 Ohio Ave, Saint Charles, Illinois 60174, USA
Company Website: http://www.systemsensor.com
Listing Country: United States of America
Certification Type: FM Approved

© 2007-2009 FM Approvals. All rights reserved. 1 of 1


Pressure Gauges
Gauges for sprinkler systems and fire pumps are designed for use with air or water. These gauges are usually of the Bourdon tube
type. The moving parts are fabricated of appropriate corrosion-resistant materials.
When installed on the air side of a dry pipe system, a retard type gauge may be used. This gauge is assembled with a tube
appropriate to the unretarded pressure range of the gauge and is provided with a spring to resist the full scale load.
The two common sizes are 4 1⁄2 and 3 1⁄2 in. diameter. These gauges can be calibrated with a hydraulic testing unit by adjusting the
dial pointer to read correctly at known pressures. Accuracy requirements are that the gauge be correct within 2% over the center third
of its scale and within 3% over the remaining two-thirds. Dial marking subdivisions correspond to the maximum accuracy of the
gauge.
For service on fire pumps where the suction may be taken under a lift, compound pressure vacuum gauges are available graduated in
pressure units over both the pressure and vacuum scales, and are designed not to be injured by vacuum.
To minimize possible damage and provide maximum accuracy, gauges should be selected with scales of about twice the maximum
system pressure.

Model 111.10SP.100
Air or Water Pressure Gauge - Model 111.10SP.100

• 0-300 psi (0-2068 kPa). 4 in. (100 mm) size, Plastic Case.
• 0-300 psi (0-2068 kPa). 4 in. (100 mm) size, Steel case with brass plated finish.
• 0-400 psi (0-2760 kPa). 4 in. (100 mm) size, Plastic Case.
• 0-400 psi (0-2760 kPa). 4 in. (100 mm) size, Steel case with brass plated finish.
• 0-600 psi (0-4140 kPa). 4 in. (100 mm) size, Plastic case.
• 0-600 psi (0-4140 kPa). 4 in. (100 mm) size, Steel case with brass plated finish.

Retard Pressure Gauge - Model 111.10SP.100

• 0-80-250 psi (0-550-1725 kPa). 4 in. (100 mm) size

These gauges have a 1/4 in. male NPT bottom connection.

Company Name: Wika Instrument Corp


Company Address: 1000 Wiegand Blvd, Lawrenceville, Georgia 30043, USA
Company Website: http://www.wika.com
Listing Country: United States of America
Certification Type: FM Approved

© 2007-2011 FM Approvals. All rights reserved. 1 of 1


VEVX.EX5232 - Gauges, Pressure Page 1 of 1

VEVX.EX5232
Gauges, Pressure
Page Bottom

Gauges, Pressure

See General Information for Gauges, Pressure

WIKA INSTRUMENT CORP EX5232


1000 WIEGAND BLVD
LAWRENCEVILLE, GA 30043 USA

Bourdon spring type, Model 111.10, size 4 in. with dials graduated 0-300 psi, 0-400 psi and 0-80-250 (retard).

Last Updated on 2009-09-18

Questions? Print this page Notice of Disclaimer Page Top

Copyright © 2010 Underwriters Laboratories Inc.®

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow-Up
Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Designs and/or Listings (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the
data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc." must
appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "Copyright ©
2010 Underwriters Laboratories Inc.®"

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpage.html?name=... 03/11/2010
VIII. Trade License
IX. Civil Defense Certificates
‫‪United Arab Emirates‬‬ ‫دوﻟﺔ اﻻﻣﺎرات اﻟﻌﺮﺑﻴﺔ اﻟﻤﺘﺤﺪة‬

‫‪Ministry of Interior‬‬ ‫وزارة اﻟﺪاﺧﻠﻴﺔ‬

‫‪General Directorate of Civil Defense‬‬ ‫اﻟﻘﻴﺎدة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ‬

‫‪General Department of Civil Defense - Sharjah‬‬ ‫اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ ‪ -‬اﻟﺸﺎرﻗﺔ‬

‫اﻻﺳﻢ اﻟﺘﺠﺎري ﻟﻠﻤﻨﺸﺄة ‪ :‬ﻧﻈﺮة اﻟﺨﻠﻴﺞ ﻟﺘﺠﺎرة اﺟﻬﺰة اﻻﻃﻔﺎء و ﻣﻜﺎﻓﺤﺔ اﻟﺤﺮﻳﻖ ذ‪.‬م‪.‬م‬ ‫رﻗﻢ اﻟﺘﺮﺧﻴﺺ ‪2013-3-59668 :‬‬
‫‪Agent‬‬ ‫‪Manufacturer‬‬ ‫ﺳﻨﺔ اﻟﺘﺮﺧﻴﺺ ‪2018 :‬‬
‫ﻋﺪد اﻟﺘﺮاﺧﻴﺺ ‪2 :‬‬
‫‪17/01/2019‬‬ ‫‪Expiry date of theAgent :‬‬ ‫‪K36‬‬ ‫‪Licence No. of theAgent :‬‬ ‫ﺑﺮﻳﺴﺘﻮل اﻧﺠﻨﻴﺮﻧﺞ‬ ‫‪Name of theAgent :‬‬
‫اﺳﻢ اﻟﻤﺨﺘﺒﺮ اﻟﺼﺎدر‬ ‫ﺗﺎرﻳﺦ اﻧﺘﻬﺎء ﻗﻴﺪ‬
‫رﻗﻢ ﺷﻬﺎدة اﻟﺴﻼﻣﺔ‬ ‫رﻗﻢ ﻗﻴﺪ اﻟﻮﻛﺎﻟﺔ‬ ‫اﺳﻢ اﻟﻤﺼﻨﻊ‬ ‫ﺑﻠﺪ اﻟﺼﻨﻊ‬ ‫اﻻﺳﻢ اﻟﺘﺠﺎري‬ ‫اﺳﻢ اﻟﻤﻌﺪة‪/‬اﻟﻤﻮاد‪/‬اﻟﻨﻈﺎم‬ ‫م‬
‫ﻟﻠﺸﻬﺎدة‬ ‫اﻟﻮﻛﺎﻟﺔ‬

‫‪BRE GLOBAL‬‬
‫‪TANDA‬‬ ‫‪Detection and fire alarm system : Unit‬‬
‫‪LTD, UNITED‬‬ ‫‪(1330D-(CL-1‬‬ ‫‪16/08/2018‬‬ ‫‪17745‬‬ ‫‪China‬‬ ‫‪Tanda UK Limited‬‬
‫‪Technology co‬‬ ‫‪alarm sound‬‬
‫‪KINGDOM‬‬ ‫‪7‬‬
‫رﻗﻢ اﻟﻤﻮدﻳﻞ ‪:‬‬
‫‪Alarm Warning Device TX7300‬‬
‫‪UL,‬‬
‫‪Automatic sprinklers / hoses / point‬‬
‫‪UNDERWRITERS‬‬ ‫‪VICTAULIC‬‬ ‫‪United States of‬‬
‫‪VGYZ.EX15290‬‬ ‫‪12/10/2018‬‬ ‫‪10378‬‬ ‫‪VICTAULIC‬‬ ‫‪water supply / water systems : Metal‬‬
‫‪LABORATORIES‬‬ ‫‪EUROPE‬‬ ‫‪America‬‬
‫‪connections‬‬
‫‪INC, USA‬‬
‫‪ 8‬رﻗﻢ اﻟﻤﻮدﻳﻞ ‪:‬‬
‫‪V1201, V1202, V1203, V1204, V1205, V1206, V1207, V1208, V1211, V1212, V1213, V1214, V1215, V1216, V1217, V1218, V1221, V1222, V1223,‬‬
‫‪V1224, V1225, V1226, V1227, V1228, V1231, V1232, V1233, V1234, V1235, V1236, V1237, V1238, V1241, V1242, V1243, V1244, V1245, V1246,‬‬
‫‪V1247, V1248, V1251, V1252, V1253, V1254, V1255, V1256, V1257, V1258, V1261, V1262, V1263, V1264, V1265, V1266, V1267, V1268, V1271,‬‬
‫‪V1272, V1273, V1274, V1275, V1276, V1277, V1278,‬‬
‫‪UL,‬‬
‫‪Automatic sprinklers / hoses / point‬‬
‫‪UNDERWRITERS‬‬ ‫‪United States of‬‬
‫‪VUTX.EX2041‬‬ ‫‪14/03/2018‬‬ ‫‪11102‬‬ ‫‪DIXON‬‬ ‫‪water supply / water systems : Ground‬‬
‫‪LABORATORIES‬‬ ‫‪America‬‬
‫‪valves‬‬ ‫‪9‬‬
‫‪INC, USA‬‬
‫رﻗﻢ اﻟﻤﻮدﻳﻞ ‪:‬‬
‫‪AVAPRF250-1‬‬

‫‪ . 1‬ﻳﻌﺘﺒﺮ اﻟﻤﻮزع ﻣﺮﺧﺺ ﻣﻦ ﻗﺒﻞ اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ‪ Sharjah -‬و ﻳﺤﻖ ﻟﻪ ﻣﺰاوﻟﺔ ﻧﺸﺎﻃﻪ ﻓﻲ إﻣﺎرة ‪ Sharjah‬ﻓﻘﻂ‪ ،‬اﺳﺘﻨﺎدا إﻟﻰ ﻗﺮار ﻣﺠﻠﺲ اﻟﻮزاري رﻗﻢ )‪ (24‬ﻟﺴﻨﺔ ‪ 2012‬ﻓﻲ ﺷﺄن ﺗﻨﻈﻴﻢ ﺧﺪﻣﺎت اﻟﺪﻓﺎع اﻟﻤﺪﻧﻲ‬
‫ﻣﻼﺣﻈﺔ‪ :‬ﻟﻼﺋﺤﺔ اﻟﺘﻨﻔﻴﺬﻳﺔ رﻗﻢ )‪ (213‬ﻟﺴﻨﺔ ‪ ، 2017‬و ﻻ ﻳﺤﻖ ﻣﺰاوﻟﺔ أﻧﺸﻄﺘﻪ ﻓﻲ ﺑﺎﻗﻲ اﻹﻣﺎرات إﻻ ﺑﻌﺪ اﺳﺘﺨﺮاج ﺗﺮﺧﻴﺺ ﻣﻮزع ﻣﻦ ﻗﺒﻞ اﻹدارات اﻟﻌﺎﻣﺔ ذات اﻻﺧﺘﺼﺎص ﺑﻜﻞ إﻣﺎرة‪.‬‬
‫‪ . 2‬إﺑﻼغ اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ ﻓﻲ ﺣﺎﻟﺔ ﺗﻐﻴﻴﺮ أو ﺗﻌﺪﻳﻞ ﻓﻲ اﻟﺒﻴﺎﻧﺎت اﻟﻤﺘﻌﻠﻘﺔ ﻓﻲ اﻟﺘﺮﺧﻴﺺ اﻟﺼﺎدر ﻣﻦ ﻗﺒﻞ اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ‪.‬‬

‫ﻳﻌﺘﻤﺪ‪/‬‬
‫‪Copy number 5 - 08/04/2018 - 0558921890‬‬ ‫‪4/5‬‬
‫‪United Arab Emirates‬‬ ‫دوﻟﺔ اﻻﻣﺎرات اﻟﻌﺮﺑﻴﺔ اﻟﻤﺘﺤﺪة‬

‫‪Ministry of Interior‬‬ ‫وزارة اﻟﺪاﺧﻠﻴﺔ‬

‫‪General Directorate of Civil Defense‬‬ ‫اﻟﻘﻴﺎدة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ‬

‫‪General Department of Civil Defense - Sharjah‬‬ ‫اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ ‪ -‬اﻟﺸﺎرﻗﺔ‬

‫رﻗﻢ اﻟﺘﺮﺧﻴﺺ ‪2013-3-59668 :‬‬

‫ﺗﺮﺧﻴﺺ ﻣﻮزع‬ ‫ﺳﻨﺔ اﻟﺘﺮﺧﻴﺺ ‪2018 :‬‬

‫‪Agent‬‬ ‫‪Manufacturer‬‬ ‫ﻋﺪد اﻟﺘﺮاﺧﻴﺺ ‪2 :‬‬

‫ﺗﻢ إﺻﺪار اﻟﺘﺮﺧﻴﺺ اﺳﺘﻨﺎدا إﻟﻰ اﻟﻘﺮار اﻟﻮزاري رﻗﻢ )‪ (24‬ﻟﺴﻨﺔ ‪ ، 2012‬ﻓﻲ ﺷﺄن ﺗﻨﻈﻴﻢ ﺧﺪﻣﺎت اﻟﺪﻓﺎع اﻟﻤﺪﻧﻲ‬
‫ﻧﻈﺮة اﻟﺨﻠﻴﺞ ﻟﺘﺠﺎرة اﺟﻬﺰة اﻻﻃﻔﺎء و‬ ‫اﻻﺳﻢ اﻟﺘﺠﺎري ﻟﻠﻤﻨﺸﺄة‬
‫‪2013-3-59668‬‬ ‫رﻗﻢ اﻟﺴﺠﻞ‬ ‫‪557284‬‬ ‫رﻗﻢ اﻟﺮﺧﺼﺔ‬
‫ﻣﻜﺎﻓﺤﺔ اﻟﺤﺮﻳﻖ ذ‪.‬م‪.‬م‬
‫‪United Arab Emirates‬‬ ‫اﻟﺠﻨﺴﻴﺔ‬ ‫ﺷﻌﻴﺐ ﻋﺒﺪاﻟﻠﻪ ﻋﻠﻲ اﺣﻤﺪ‬ ‫اﺳﻢ ﺻﺎﺣﺐ اﻟﺘﺮﺧﻴﺺ‬
‫‪India‬‬ ‫اﻟﺠﻨﺴﻴﺔ‬ ‫راﺟﻨﺪرا ﻧﺎﺟﻴﻨﺪاس ﺧﺘﺮي ﻧﺎﺟﻴﻨﺪاس‬ ‫اﺳﻢ ﺻﺎﺣﺐ اﻟﺘﺮﺧﻴﺺ‬
‫‪India‬‬ ‫اﻟﺠﻨﺴﻴﺔ‬ ‫ﺑﻴﻨﺪو ﺟﻨﻐﻴﻨﻴﺎدان دﻳﻮﺳﻲ‬ ‫اﺳﻢ ﺻﺎﺣﺐ اﻟﺘﺮﺧﻴﺺ‬
‫‪Sharjah‬‬ ‫ﻣﻨﻄﻘﺔ اﻟﻨﺸﺎط‬ ‫ﺗﺠﺎرة ﻣﻮاد اﻃﻔﺎء اﻟﺤﺮﻳﻖ‬ ‫ﻧﻮع اﻟﻨﺸﺎط‬
‫‪73143‬‬ ‫ص‪.‬ب‬ ‫‪065610311‬‬ ‫رﻗﻢ اﻟﻔﺎﻛﺲ‬ ‫‪0508628851‬‬ ‫رﻗﻢ اﻟﻬﺎﺗﻒ‬
‫ﻣﻜﺘﺐ رﻗﻢ ‪ 3‬ﻣﻠﻚ ﻓﺎﻃﻤﺔ ﻋﺒﺪاﻟﻠﻪ رﺣﻤﻪ اﻟﻌﻮﻳﺲ اﻟﺸﺎﻣﺴﻲ ‪ -‬ﺷﺎرع اﻟﺰﻫﺮاء ‪Sharjah Sharjah Alsoor, ,‬‬ ‫ﻋﻨﻮان اﻟﺸﺮﻛﺔ‬
‫‪www.gulfirevision.com gvfe2007@eim.ae‬‬ ‫اﻟﻤﻮﻗﻊ و اﻟﺒﺮﻳﺪ اﻹﻟﻜﺘﺮوﻧﻲ‬
‫‪17/01/2019‬‬ ‫ﺗﺎرﻳﺦ اﻻﻧﺘﻬﺎء‬ ‫‪04/04/2018‬‬ ‫ﺗﺎرﻳﺦ اﻹﺻﺪار‬ ‫‪29/11/2007‬‬ ‫ﺗﺎرﻳﺦ ﺗﺄﺳﻴﺲ اﻟﻤﻨﺸﺄة‬
‫ﻋﺪد اﻟﻤﻌﺪات و اﻷﺟﻬﺰة اﻟﻤﺮاد ﺗﺮﺧﻴﺼﻬﺎ ‪10‬‬

‫ﻳﻌﺘﻤﺪ‪/‬‬

‫‪Copy number 5 - 08/04/2018 - 0558921890‬‬ ‫‪1/5‬‬


‫‪United Arab Emirates‬‬ ‫دوﻟﺔ اﻻﻣﺎرات اﻟﻌﺮﺑﻴﺔ اﻟﻤﺘﺤﺪة‬

‫‪Ministry of Interior‬‬ ‫وزارة اﻟﺪاﺧﻠﻴﺔ‬

‫‪General Directorate of Civil Defense‬‬ ‫اﻟﻘﻴﺎدة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ‬

‫‪General Department of Civil Defense - Sharjah‬‬ ‫اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ ‪ -‬اﻟﺸﺎرﻗﺔ‬

‫اﻻﺳﻢ اﻟﺘﺠﺎري ﻟﻠﻤﻨﺸﺄة ‪ :‬ﻧﻈﺮة اﻟﺨﻠﻴﺞ ﻟﺘﺠﺎرة اﺟﻬﺰة اﻻﻃﻔﺎء و ﻣﻜﺎﻓﺤﺔ اﻟﺤﺮﻳﻖ ذ‪.‬م‪.‬م‬ ‫رﻗﻢ اﻟﺘﺮﺧﻴﺺ ‪2013-3-59668 :‬‬
‫‪Agent‬‬ ‫‪Manufacturer‬‬ ‫ﺳﻨﺔ اﻟﺘﺮﺧﻴﺺ ‪2018 :‬‬
‫ﻋﺪد اﻟﺘﺮاﺧﻴﺺ ‪2 :‬‬
‫‪17/01/2019‬‬ ‫‪Expiry date of theAgent :‬‬ ‫‪K36‬‬ ‫‪Licence No. of theAgent :‬‬ ‫ﺑﺮﻳﺴﺘﻮل اﻧﺠﻨﻴﺮﻧﺞ‬ ‫‪Name of theAgent :‬‬
‫اﺳﻢ اﻟﻤﺨﺘﺒﺮ اﻟﺼﺎدر‬ ‫ﺗﺎرﻳﺦ اﻧﺘﻬﺎء ﻗﻴﺪ‬
‫رﻗﻢ ﺷﻬﺎدة اﻟﺴﻼﻣﺔ‬ ‫رﻗﻢ ﻗﻴﺪ اﻟﻮﻛﺎﻟﺔ‬ ‫اﺳﻢ اﻟﻤﺼﻨﻊ‬ ‫ﺑﻠﺪ اﻟﺼﻨﻊ‬ ‫اﻻﺳﻢ اﻟﺘﺠﺎري‬ ‫اﺳﻢ اﻟﻤﻌﺪة‪/‬اﻟﻤﻮاد‪/‬اﻟﻨﻈﺎم‬ ‫م‬
‫ﻟﻠﺸﻬﺎدة‬ ‫اﻟﻮﻛﺎﻟﺔ‬

‫‪BRE GLOBAL‬‬
‫‪TANDA‬‬ ‫‪Detection and fire alarm system : Unit‬‬
‫‪LTD, UNITED‬‬ ‫‪(1330D-(CL-1‬‬ ‫‪16/08/2018‬‬ ‫‪17745‬‬ ‫‪China‬‬ ‫‪Tanda UK Limited‬‬
‫‪Technology co‬‬ ‫‪alarm sound‬‬
‫‪KINGDOM‬‬ ‫‪7‬‬
‫رﻗﻢ اﻟﻤﻮدﻳﻞ ‪:‬‬
‫‪Alarm Warning Device TX7300‬‬
‫‪UL,‬‬
‫‪Automatic sprinklers / hoses / point‬‬
‫‪UNDERWRITERS‬‬ ‫‪VICTAULIC‬‬ ‫‪United States of‬‬
‫‪VGYZ.EX15290‬‬ ‫‪12/10/2018‬‬ ‫‪10378‬‬ ‫‪VICTAULIC‬‬ ‫‪water supply / water systems : Metal‬‬
‫‪LABORATORIES‬‬ ‫‪EUROPE‬‬ ‫‪America‬‬
‫‪connections‬‬
‫‪INC, USA‬‬
‫‪ 8‬رﻗﻢ اﻟﻤﻮدﻳﻞ ‪:‬‬
‫‪V1201, V1202, V1203, V1204, V1205, V1206, V1207, V1208, V1211, V1212, V1213, V1214, V1215, V1216, V1217, V1218, V1221, V1222, V1223,‬‬
‫‪V1224, V1225, V1226, V1227, V1228, V1231, V1232, V1233, V1234, V1235, V1236, V1237, V1238, V1241, V1242, V1243, V1244, V1245, V1246,‬‬
‫‪V1247, V1248, V1251, V1252, V1253, V1254, V1255, V1256, V1257, V1258, V1261, V1262, V1263, V1264, V1265, V1266, V1267, V1268, V1271,‬‬
‫‪V1272, V1273, V1274, V1275, V1276, V1277, V1278,‬‬
‫‪UL,‬‬
‫‪Automatic sprinklers / hoses / point‬‬
‫‪UNDERWRITERS‬‬ ‫‪United States of‬‬
‫‪VUTX.EX2041‬‬ ‫‪14/03/2018‬‬ ‫‪11102‬‬ ‫‪DIXON‬‬ ‫‪water supply / water systems : Ground‬‬
‫‪LABORATORIES‬‬ ‫‪America‬‬
‫‪valves‬‬ ‫‪9‬‬
‫‪INC, USA‬‬
‫رﻗﻢ اﻟﻤﻮدﻳﻞ ‪:‬‬
‫‪AVAPRF250-1‬‬

‫‪ . 1‬ﻳﻌﺘﺒﺮ اﻟﻤﻮزع ﻣﺮﺧﺺ ﻣﻦ ﻗﺒﻞ اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ‪ Sharjah -‬و ﻳﺤﻖ ﻟﻪ ﻣﺰاوﻟﺔ ﻧﺸﺎﻃﻪ ﻓﻲ إﻣﺎرة ‪ Sharjah‬ﻓﻘﻂ‪ ،‬اﺳﺘﻨﺎدا إﻟﻰ ﻗﺮار ﻣﺠﻠﺲ اﻟﻮزاري رﻗﻢ )‪ (24‬ﻟﺴﻨﺔ ‪ 2012‬ﻓﻲ ﺷﺄن ﺗﻨﻈﻴﻢ ﺧﺪﻣﺎت اﻟﺪﻓﺎع اﻟﻤﺪﻧﻲ‬
‫ﻣﻼﺣﻈﺔ‪ :‬ﻟﻼﺋﺤﺔ اﻟﺘﻨﻔﻴﺬﻳﺔ رﻗﻢ )‪ (213‬ﻟﺴﻨﺔ ‪ ، 2017‬و ﻻ ﻳﺤﻖ ﻣﺰاوﻟﺔ أﻧﺸﻄﺘﻪ ﻓﻲ ﺑﺎﻗﻲ اﻹﻣﺎرات إﻻ ﺑﻌﺪ اﺳﺘﺨﺮاج ﺗﺮﺧﻴﺺ ﻣﻮزع ﻣﻦ ﻗﺒﻞ اﻹدارات اﻟﻌﺎﻣﺔ ذات اﻻﺧﺘﺼﺎص ﺑﻜﻞ إﻣﺎرة‪.‬‬
‫‪ . 2‬إﺑﻼغ اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ ﻓﻲ ﺣﺎﻟﺔ ﺗﻐﻴﻴﺮ أو ﺗﻌﺪﻳﻞ ﻓﻲ اﻟﺒﻴﺎﻧﺎت اﻟﻤﺘﻌﻠﻘﺔ ﻓﻲ اﻟﺘﺮﺧﻴﺺ اﻟﺼﺎدر ﻣﻦ ﻗﺒﻞ اﻹدارة اﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎع اﻟﻤﺪﻧﻲ‪.‬‬

‫ﻳﻌﺘﻤﺪ‪/‬‬
‫‪Copy number 5 - 08/04/2018 - 0558921890‬‬ ‫‪4/5‬‬
X. Company Profile
Firefighting Solutions Provider
www.bristol-fire.com

BRISTOL Fire Engineering, part of the Concorde – Corodex Group (CCG), was
established in 1974 as a leading manufacturer of high quality Fire Fighting
Systems and Equipments. BRISTOL was one of the first fire fighting companies
to receive an ISO 9001 certification in the Middle East, placing a great emphasis
on achieving international and Third party approvals in all our product range
such as (Kite Mark, LPBC, UL listing and FM Approval). In addition, all our
products carry Civil Defense approvals in the market we operate in.

We are continuously working on adding new technologies to our product range


so we can meet the ever changing customer needs.

Our range of experience expands to all category projects from residential,


commercial, healthcare, Industrial and educational.

Integrity and Quality are ingrained in BRISTOL name. For over three decades,
Bristol related companies have consistently performed complex projects on
time and within the budget while never compromising quality.

BRISTOL’s complete in house staff consists of fire fighting specialist engineers,


project executive staff, professional services & maintenance teams and it
ensures that end users receive a total solution rather than merely a product.

Product range

• Fire Alarm & Detection System


• Fire Suppression systems (Novec 1230, FM200,CO2,Water Mist, Kitchen
Hood & Inert gas)
• FOAM System /FOAM Concentrate
• Fire Sprinkler systems
• Fire Pumps
• Fire and Rescue trucks
• Hydrant valves /Nozzles and accessories
• Wet / Dry riser components (Fire Hose reel ,Landing Valves ,PRV etc.. )
• Fire Extinguishers ( Wet Chemical, Dry Chemical Powder
/CO2/Foam/Water Harleton)
• Fire Doors
Concorde-Corodex Group

Group Profile

The Concorde- Corodex Group, a part of M.H Al Mana Group of Companies, is


one of the Middle East region’s pioneering providers of fire protection, water
purification, wastewater treatment and environmental services. Established in
1974, the company has evolved to become the largest group to offer a diverse
portfolio of products and services like a complete kit of water treatment services,
fire fighting equipment and marine & industrial chemical cleaning to name a few.

Looking to meet the continuously changing demands and requirements from


customers across various industry verticals, the Concorde – Corodex Group has
diversified itself into 17 individual companies--each excelling in their respective
field of expertise and operating as an independent entity. Collectively, all
subsidiary companies continue to consolidate the Concorde – Corodex Group
market leadership in the Middle East region, with assets worth over USD 90
million.

CCG’s core values have been the cornerstone of what define us and what we
stand for. They are excellence, innovation, environment stewardship, and health
& safety.

All business units of Concorde-Corodex Group are registered companies with


Quality, Environment, Occupational Health and Safety Management Systems
(QHSEMS) in compliant to international standards such as ISO 9001:2008, ISO
14001:2004 and OHSAS 18001:2007.

Our Team
From relatively small team, Concorde-Corodex Group has vastly grown in size.
Presently, we have 920 total employees, amongst which are 322 Engineers,
Specialists, Chemists and other Technical Professionals.
Mission Statement

We, the Concorde-Corodex Group, are committed to provide quality products


and services.

In pursuit of this commitment in serving the consumers, we shall adopt sound


trade and industrial policies as well as regulations provided by the government.

We shall provide timely and world class services that answer our clients'
business needs for Design, Manufacturing, Servicing and Trading.

In the same way we relate with our clients, so shall we relate with each other as
we promote an internal environment that foster professional growth.

In the attainment of this mission and for love of this country, we bind ourselves to
be the highest standards of competence, integrity and dedication.

Vision Statement
We are committed to deliver world class products in various business activities in
the fields of Designing, Manufacturing, Servicing and Trading.

We shall actively provide innovative and effective services to the consumers, with
customers' delight as our measure of success.

As we move toward this direction, we shall endeavor to become leader in


providing total quality service in the field.

We are group of highly capable, skilled and dedicated people with creative and
noble ideas committed to build an organization we can be proud of.

We shall triumph in a work environment that upholds the highest distinction in


excellence professionalism, integrity and harmony.

In essence, we shall always strive to be a provider of true service worthy of


consumer’s trust as we meet the challenges of the ever changing consumer
needs.

International Operating offices:

• U.A.E. (Head corporate office and manufacturing facility)


• Winnipeg, Canada
• London, UK
• Khartoum, Sudan
• Doha, Qatar
• Muscat, Oman
• Jeddah, K.S.A
• Amman, Jordan

UAE Operating Offices:

• Abu Dhabi
• ICAD Mussafa
• Khalidiya
• Dubai
• Al Quoz
• Al Awir
• Sheikh Zayed
• Sharjah
• Al Ain
• Ras Al Khayma

Core Activities
ƒ Water Purification / Treatment Systems
ƒ Sewage Treatment Plants
ƒ Vacuum Sewer Systems
ƒ Operation & Maintenance
ƒ Electromechanical Services
ƒ Marine and Industrial Chemical Cleaning
ƒ Fire Fighting Equipments and Systems
ƒ Fire Protection and Safety
ƒ Machine Tools and Engineering Equipment
ƒ Scientific & Laboratory Equipment
ƒ Oilfield Equipment
ƒ Industrial Gases
ƒ Welding Equipment
ƒ Vehicle Manufacturing Division

Quality Policy

Concorde-Corodex Group is a professional company devoted to build a strong


customer relation base to deliver a wide range of quality products. With a history
of service excellence that has evolved through the decades, our organization
leads a Group of Companies/ Business Operating Units, incorporating a variety
of business activities in the fields of Designing, Manufacturing, Servicing and
Trading.
We at CCG have committed ourselves to provide and exceed our customers’
expectations and contractual requirements through:

Employee: We recognize our employees as the most valuable asset of the


organization. On the basis of merit hiring the right incumbent for the right
position, we value their skills and knowledge and we lead, motivate and empower
them through a working environment that advances our business objectives.

Products/Services: Our objective is to provide products or services that meets


or exceeds customer’s satisfaction. We deliver to customer the right product or
service at the right time at the right quantity, quality and price.

Processes: We have implemented ISO 9001:2008 to define and control our


processes and ensure that they are conforming with the set policies. Our aim is
to reach to the most efficient way of carrying out the tasks to enhance our
business relations with customers.

Customers: Customer Satisfaction is recognized as the number one priority in


our organization as our success is directly linked to the satisfaction of the
customer towards his final output of the quality of our product and services.

CCG is an enterprise that retains a tradition of integrity and is on the path to


expand and continually improve in line with the market trends.

Environmental Policy
We, at Concorde-Corodex Group, are committed to provide quality products and
services in a manner that ensures a safe and healthy workplace for our
employees and minimizes our potential impact on the environment. We will
operate in compliance with ISO 14001: 2004 and all relevant environmental
legislations and will strive to use pollution prevention and environmental best
practices in all we do.
We are committed to continually improving our environmental performance
using the following measures:

1. The control of emissions and discharges consequential upon our


Operations to ensure these has minimal detrimental effect upon the
environment.
2. The control of odour, noise and litter to eliminate or minimize the
effects on surrounding areas.
3. To optimize raw materials usage and conversion efficiencies including
the rework and/or recycling of scrap.
4. To seek to reduce the consumption of materials, fuel & energy used in our
operations.
5. Compliance with environmental legislation and regulations.
6. To take into account the concerns of interested parties such
as regulators, shareholders, suppliers, employees and the public.
7. To communicate this policy to all members of the organization and
ensure all are trained in their respective environmental responsibilities.
8. To make this Environmental Policy available to customers and the public
on demand.
The introduction and implementation of this Policy is a commitment of
CCG Management and a shared responsibility of all our employees.

This policy will be reviewed annually as part of the company’s overall


Environmental Management review system.

Occupational Health and Safety (OHS) Policy


Concorde-Corodex Group is committed to prevent injury and ill health by
providing safe and healthy working conditions for all its employees and to ensure
that work done does not affect adversely the health and safety of others.

CCG strives for continual improvement in Occupational Health and Safety


(OH&S) management and performance through consultation and participation of
employees.

To achieve this, the following work policy is hereby issued:

ƒ Provide adequate control of the Health and Safety risks arising from our
work activities.
ƒ Consult with our workers and volunteers on matters affecting their Health
and Safety, including work related stress.
ƒ Provide and maintain safe plant and equipment.
ƒ Ensure safe handling and use of substances.
ƒ Provide training, information, instruction and supervision for workers to
ensure that they are aware of their individual OH&S obligations.

All works will be carried out in accordance with the requirements of OHSAS
18001:2007 and other relevant Health & Safety laws, Acts, Regulations, Codes
of Practice and Guidance Notes and ensure compliance to applicable laws where
the company subscribes to.

Management and supervisory staff have the responsibility for implementing this
policy throughout the company and must ensure that health and safety are
always given priority in planning day-to-day supervision of work.

This policy will be reviewed periodically and will be available to interested parties.
Group Members
• Concorde Trading Co, Abu Dhabi
For everything water related
• Concorde Agencies Est, Abu Dhabi
Fire protection and automation system
• Concorde Technical Est, Abu Dhabi
Fire Protection, Water and Wastewater Treatment, and Environmental
Specialists
• Corodex Trading Co, Dubai
For everything water related
• Corodex Agencies Est, Dubai
Fire protection and automation system
• Corodex Industries, Dubai
Water Purification and Wastewater Treatment Specialists
• Corodex Marine, Dubai
Step ahead in chemical cleaning
• Corodex Electromechanic, Dubai
Bringing Engineering Solutions to Life Vacuum Sewerage System Water
and Wastewater
Treatment Systems
• Bristol Fire Engineering, Dubai
Everything Fire Related
• Al Jaddaf Electromechanical, Abu Dhabi
Fire Protection, Water and Wastewater Treatment, and Environmental
Specialists
• EFLO International, United Kingdom
Wastewater Treatment Specialists
• Bristol Gases, Dubai
Industrial Gases
• Dubai Industrial Gases, Sharjah
Industrial Gases
XI. Project List
LOCAL DIVISION
PROJECT LIST

Sr No. Project Name Client Name Consultant Description of work

Fire Fighting
Al Badr Cont. & Civil Construction Co.
1 M/229 Scada CEC Consistent Engineering Consultant Equipments + Deluge
L.L.C
Valve & Pumps
Water Front Madinat Al
Fire Fighting
2 Arab -­‐ Badrah District A Mammut Contracting Co. L.L.C Woods & Bagot
Equipments
Building

3 DEWA Warehouse BAUR Electrical Middle East L.L.C A & Z Architectural Eng'g Const. Warehouse

Fire Fighting
Qassimy Maternity Hospital
4 Ali Moosa & Sons Contracting UPA Urbanism Planning Architecture Equipments + Pumps,
& Emergency Extension
preaction, Foam
Fire Fighting
B+G+12 Building @ Al
5 Air Technic A/C System Co. L.L.C Asri -­‐ Al Asri Eng'g Consultant Equipments + Pumps,
Nahda P240
preaction, Foam
2B +G+8 Building @ Al Fire Fighting
6 Air Technic A/C System Co. L.L.C Al Hawraa -­‐ Eng'g Consultant
Barsha 3rd P239 Equipments

B+G+9F+Gym Building on Fire Fighting


7 Air Technic A/C System Co. L.L.C Aldan Consultant
Plot No.245-­‐810 Equipments

Prime Star Electrical & Mechanical Fire Fighting


8 B+G+20 Residential Building NEB National Engineering
Works L.L.C Equipments

5B+G+3P+12Hotel+MF+12R+ Prime Star Electrical & Mechanical Fire Fighting


9 NEB National Engineering
MF+10R+HC Works L.L.C Equipments

Fakhrudeen Towers
FM200 and Suppressiion
10 Located at Business Bay, Radiant Technical Works L.L.C NEB National Engineering
& Fire Fighting System
Dubai
Botanica Tower on Plot no.
Fire Fighting
11 392-­‐279, @ Dubai Marina, Radiant Technical Works L.L.C NEB National Engineering
Equipments
Dubai
Building on Plot BB.A03.039
Fire Fighting
12 @ Business Bay Radiant Technical Works L.L.C NEB National Engineering
Equipments
3B+G+3P+HC+18 Floors
LOCAL DIVISION
PROJECT LIST

Sr No. Project Name Client Name Consultant Description of work

Private Academy on plot Fire Fighting


13 Radiant Technical Works L.L.C NEB National Engineering
No. 128, Abu Dhabi Equipments

Expansion work of
14 Zulekha Hospital, Sharjah MAS Co. L.L.C Winner Consultants Engineers Zulekha Hospital,
Sharjah
Al Rayyan Project -­‐ Golf
15 Gardens Residential GISCO (Gulf Industrial Services Co.) Ehav Engineering Consultant FM200 System
Community Project, Plot P-
Fire Fighting
16 Marasy -­‐ Abu dhabi GISCO (Gulf Industrial Services Co.) Ehav Engineering Consultant
Equipments

Plot No. 318/864 at Al Fire Fighting


17 Power Point Elect. & Mech. Works L.L.C Architects & Engineers Consultant
karama, Dubai Equipments

Fire Fighting
18 Al Qassimi Hospital, Sharjah Ali Moosa & Sons Ali Moosa & Sons
Equipments

B+G+3P+30 FLRS ,Al Hilal Fire Fighting


19 Radiant Technical Works Radiant Technical Works
City City, Fujairah Equipments

Fire Fighting
20 Dubai waterfront Project Mammut Contracting LLC Mammut Contracting LLC
Equipments

2B+G+3P+12F
Fire Fighting
21 HOTEL+MF+22R+MF+HC@Du Prime Star Prime Star
Equipments
bai
2B+G+31+MECHANICAL
Fire Fighting
22 FLOOR ON PLOT # 392-­‐467 Prime Star Prime Star
Equipments
,
Fire Fighting
23 Honda Showroom, Sharjah Al Futtaim Engineering Al Futtaim Engineering
Equipments

Complex On plot Nos. 354- Fire Fighting


24 Galadari Automobiles Co. Ltd. Arif & Bintoak
­‐379 Equipments
LOCAL DIVISION
PROJECT LIST

Sr No. Project Name Client Name Consultant Description of work

Fire Fighting
25 Dubai Festival City Dubai Festival City LLC Online Architects
Equipments

UAE Model School Cycle 1 Fire Fighting


26 Ministry of Public Works Dubai Delta Plumbing
Boys Grades (1-­‐5) Equipments

Fire Fighting
27 Al Farazdaq School Abu Dhabi Education Council Urbanism Planning Architecture
Equipments

Al Qassimi Maternity
Fire Fighting
28 Hospital & Emergency Ministry of Public Works UAE Urbanism Planning Architecture
Equipments
Extension
Fire Fighting
29 B+G+14+HC Mazaya Avenue Barajeel
Equipments

Higher Corporation For Special Fire Fighting


30 Worker's Village ACG
Economic Zones Equipments

Fire Fighting
31 AL FUTTAIM AVENUE RETAIL Al FUTTAIM DEWAN
Equipments

Fire Fighting
32 ASWAR-­‐WADI SFINI MINISTRY OF PUBLIC WORK
Equipments

NASSER MOHAMMED MOHAMMED Fire Fighting


33 JELFAR G+3 GROUP CONSULTANT INTERNATIONAL
LOOTAH Equipments

Fire Fighting
34 G+50 ASSAS TOWER MS./SHARJAH ISLAMIC BANK GULF International
Equipments

Proposed hote G+2P+8


35 Dainamo Electromechanical Mazaya Consultants FF System with pump
typical

Commercial Square Tower-


36 Galadari Electro mechanical Lacasa FF System
­‐ Business Bay
LOCAL DIVISION
PROJECT LIST

Sr No. Project Name Client Name Consultant Description of work

37 Al Badia 2 Building Al Futtaim Engineering Archgroup FF System with pump

38 Al Noof School and KG Ali Moosa & Sons EGEC FF System

Proposed Residential &


39 Ali Moosa & Sons Cab FF System
Commercial Building

40 B+G+12+HC+ROOF Radiant Technical Works NEB FF System

41 Al Hilal Tower 2 Radiant Technical Works FF System

42 Proposed Mosque Radiant Technical Works FF System

43 Wedding Hall Al Yazan FF System

44 B+G+15 Al Yazan Heberger Engineering FF System

45 Labour Accommodation Sultan Al Mulla MPW FF System

46 Masafi-­‐ police center Quick MPW FF System

47 Health Care Center Quick MPW FF System

48 Al Manama Police station Quick MPW FF System


LOCAL DIVISION
PROJECT LIST

Sr No. Project Name Client Name Consultant Description of work

Commercial & Residential


49 Al Naseem Electro Mechanical Archdome FF System
Building B+G+6+gym

50 Rak Global Logistics Al Pheniq FF System

51 Al Fardan 2B+G+M+1 Power Factor Adnan Saffarini

Galadari Vehicle Body &


52 Power Factor Arif & Bintoak FF System
Paint Shop

2B+G+7typ+HC @ Al
53 Power Factor Adnan Saffarini FF System
mankhool Dubai

54 G+5P+24 al abraj alwataniya sharjah engineering consultant FF System

55 G+5P+25 al abraj alwataniya sharjah engineering consultant FF System

56 G+5P+20 al salmi contracting Al hamra engineering consultant FF System

57 G+5P+20 al salmi contracting Al hamra engineering consultant FF System

AL THURIAH BUILDING CONTRACTING


58 Sharjah Bank AL NAHDA ENGINEERING CONSULTANT FF System
CO

59 G+3P+16 al wataniya CONTRACTING CO gulf internatinal CONSULTANT FF System

SOS INTERNATIONAL MECHANICAL


60 CTR -­‐ AD N/A FF System
EQUIPMENT
LOCAL DIVISION
PROJECT LIST

Sr No. Project Name Client Name Consultant Description of work

SOS INTERNATIONAL MECHANICAL


61 SEG -­‐ AD N/A FF System
EQUIPMENT

62 Residential Building AL BASHAER SECURITY & SAFETY N/A FF System

63 Residential Building EMPOWER ENERGY SOLUTIONS N/A FF System

64 Residential Building GULF INDUSTRIAL SERVICES CO. N/A FF System

BARAKAH NUCLEAR POWER


65 HIGHWAY FIRE & SAFETY EQPT. N/A FF System
STATION

BARAKAH NUCLEAR POWER


66 HIGHWAY FIRE & SAFETY EQPT. N/A FF System
STATION

SOS INTERNATIONAL MECHANICAL


67 ALQ -­‐ AD N/A FF System
EQUIPMENT

68 SANDS HOTEL ZABEEL N/A FF System

69 Residential Building KOREA B.M.T. N/A FF System

COMMANDS OF MILITARY
70 EMIRATES CODE CONTRACTING CO. N/A FF System
WORKS

BARAKAH NUCLEAR POWER


71 YOUNCHANG ENGINEERING CO. LTD N/A FF System
STATION

SEIDCO GENERAL CONTRACTING CO.


72 Residential Building N/A FF System
LLC
LOCAL DIVISION
PROJECT LIST

Sr No. Project Name Client Name Consultant Description of work

LABOUR CAMP -­‐ MAFRAQ


73 TAMOUH Safety & Security N/A FF System
AD

COMMANDS OF MILITARY
74 EMIRATES CODE CONTRACTING CO. N/A FF System
WORKS

WAREHOUSE IN SHARJAH
75 AL BASHAER SECURITY & SAFETY N/A FF System
FREEZONE

COMMANDS OF MILITARY
76 CODE CONTRACTING CO. LLC N/A FF System
WORKS

SOS INTERNATIONAL MECHANICAL


77 Residential Building N/A FF System
EQUIPMENT

78 Residential Building STARS FIRE & SAFETY EQUIPMENT EST. N/A FF System

2B+G+6 DELUXE OFFICE


AL AHD GEN. CONTRACTING &
79 BUILDING MR. SULTAN N/A FF System
MAINT.CO
KHALFAN MATAR SAEED AL

80 Residential Building BIN TOUQ FIRE & SAFETY N/A FF System

81 AL MAFRAQ HOSPITAL UNISAFE FIRE PROTECTION SPECIALISTS N/A FF System

SOS INTERNATIONAL MECHANICAL


82 Residential Building N/A FF System
EQUIPMENT

83 NURSERY -­‐ AD TAMOUH Safety & Security N/A FF System

84 Residential Building AL BASHAER SECURITY & SAFETY N/A FF System


LOCAL DIVISION
PROJECT LIST

Sr No. Project Name Client Name Consultant Description of work

85 Residential Building DAFOOS TECHNICAL SERVICES N/A FF System

BARAKAH NUCLEAR POWER


86 YOUNCHANG ENGINEERING CO. LTD N/A FF System
STATION

87 Residential Building CITYTEC FIRE & SAFETY N/A FF System

BARAKAH NUCLEAR POWER


88 HIGHWAY FIRE & SAFETY EQPT. N/A FF System
STATION

89 AL MAFRAQ HOSPITAL UNISAFE FIRE PROTECTION SPECIALISTS N/A FF System

90 G+M+ROOF BIN MASOUD SECURITY AND SAFETY N/A FF System

91 Residential Building CITYTEC FIRE & SAFETY N/A FF System

92 Residential Building BIN TOUQ FIRE & SAFETY N/A FF System

93 Residential Building BIN TOUQ FIRE & SAFETY N/A FF System

94 Residential Building BIN TOUQ FIRE & SAFETY N/A FF System

95 Residential Building BIN TOUQ FIRE & SAFETY N/A FF System

96 Residential Building BINTEC N/A FF System


LOCAL DIVISION
PROJECT LIST

Sr No. Project Name Client Name Consultant Description of work

97 Residential Building HIGHWAY FIRE & SAFETY EQPT. N/A FF System

98 Residential Building KOREA B.M.T. N/A FF System

99 Residential Building AL BASHAER SECURITY & SAFETY N/A FF System

100 Residential Building HIGHWAY FIRE & SAFETY EQPT. N/A FF System

101 Residential Building DAFOOS TECHNICAL SERVICES N/A FF System

FAWAZ REFRIGERATION & AIR


102 Residential Building N/A FF System
CONDITIONING CO.

SOS INTERNATIONAL MECHANICAL


103 Residential Building N/A FF System
EQUIPMENT

SARAYA TOWER for Sh.Diab


104 AL RAMS SANITARY N/A FF System
Bin Zayed Al Nahyan

105 REACH BRITISH SCHOOL AL RAMS SANITARY N/A FF System

HERBAL CENTER FOR


106 HEALTH AUTHORITY -­‐ GENERAL INTERNATIONAL CO. (GENINT) N/A FF System
MAFRAQ AD
COMMANDS OF MILITARY
107 WORKS -­‐ MAHAWI CAMP - BIN OMAIR ELECTROMECHANICAL N/A FF System
­‐ AD

108 Residential Building CITYTEC FIRE AND SAFETY N/A FF System


LOCAL DIVISION
PROJECT LIST

Sr No. Project Name Client Name Consultant Description of work

109 MUSANADA FIREMAN SAFETY SERVICES N/A FF System

110 MUSANADA FIREMAN SAFETY SERVICES N/A FF System

BARAKAH NUCLEAR POWER


111 HIGHWAY FIRE & SAFETY EQPT. N/A FF System
STATION

COMMANDS OF MILITARY
112 WORKS -­‐ MAHAWI CAMP - BIN OMAIR ELECTROMECHANICAL N/A FF System
­‐ AD
MR. ISSA AL KHAILI TOWER @
113 REEM CAPITAL CONTRACTING N/A FF System
BUS. BAY -­‐ DXB

ST JOSEPH CHURCH -­‐ SOS INTERNATIONAL MECHANICAL


114 N/A FF System
MUSAFFAH AD EQUIPMENT

ST JOSEPH CHURCH -­‐ SOS INTERNATIONAL MECHANICAL


115 N/A FF System
MUSAFFAH AD EQUIPMENT

116 MUSANADA FIREMAN SAFETY SERVICES N/A FF System

117 MUSANADA FIREMAN SAFETY SERVICES N/A FF System

118 MUSANADA FIREMAN SAFETY SERVICES N/A FF System

COMMANDS OF MILITARY HK ADVANCED ELECTROMECHANICAL


119 N/A FF System
WORKS CONT.
XII. Approval Copies