You are on page 1of 32

इंटरनेट मानक

Disclosure to Promote the Right To Information


Whereas the Parliament of India has set out to provide a practical regime of right to
information for citizens to secure access to information under the control of public authorities,
in order to promote transparency and accountability in the working of every public authority,
and whereas the attached publication of the Bureau of Indian Standards is of particular interest
to the public, particularly disadvantaged communities and those engaged in the pursuit of
education and knowledge, the attached public safety standard is made available to promote the
timely dissemination of this information in an accurate manner to the public.

“जान1 का अ+धकार, जी1 का अ+धकार” “प0रा1 को छोड न' 5 तरफ”


Mazdoor Kisan Shakti Sangathan Jawaharlal Nehru
“The Right to Information, The Right to Live” “Step Out From the Old to the New”

IS 15493 (2004): Gaseous Fire Extinguishing Systems -


General Requirements [CED 22: Fire Fighting]

“!ान $ एक न' भारत का +नम-ण”


Satyanarayan Gangaram Pitroda
“Invent a New India Using Knowledge”

“!ान एक ऐसा खजाना > जो कभी च0राया नहB जा सकता ह”


है”

Bhartṛhari—Nītiśatakam
“Knowledge is such a treasure which cannot be stolen”
IS15493:2004

Indian Standard
GASEOUS FIRE EXTINGUISHING SYSTEMS —
GENERAL REQUIREMENTS

ICS 13.220.10

0 BIS 2004

BUREAU OF INDIAN STANDARDS


MANAK BHAVAN, 9 BAHADUR SHAH ZAFAR MARG
NEW DELHI 110002

August 2004 Price Group 10


Fire Fighting Sectional Committee, CED 22

FOREWORD

i’his Indian Standard was adopted by the Bureau of Indian Standards, after the draft finalized by the
Fire Fighting Sectional Committee had been approved by the Civil Engineering Division Council.

Attention is drawn to Montreal Protocol on substances that deplete the ozone layer. As India is a signatory
to the Protocol. country programme was drafted wherein suitable alternative clean agents have been identified
in the place of HaIons 1301 and 12 I 1. As per the approved programme, this standard has been formulated for
the identified alternatives. The agents covered in this standard are thus introduced in response to international
restrictions on the production of certain Halon fire extinguishing agents under the Protocol signed in 1992, as
emended.

[t is important that the fire protection of a building or plant be considered as a whole. Gaseous clean agent
systems form only a part, though an important part, of the available facilities, but it should not be assumed that
(heir adoption necessarily removes the need to consider supplementary measures, such as the provision of portable
tire extinguishers or other mobile appliances for first aid or emergency use, or to deal with special hazards.

Gaseous fire suppression systems covered in these Indian Standards are designed to provide a supply of
gaseo~ls exting~lishillg mediuln for the extinction of fire invo]ving high value assets.

Gaseous clean agents have for many years been a recognized effective medium for the extinction of flammable
liquid fires and fires in the presence of electrical and ordinary Class A hazards, but it should not be forgotten, in
the planning of comprehensive schemes, thatthere may be hazards for which these mediums are not suitable, or
that in certain circumstances or situations there may be dangers in their use requiring special precautions. These
difficulties have been addressed in this standard.

Various methods of supplying clean agent to, and applying it at, the required point of discharge for fire extinction
have been developed in recent years, and there is a need for dissemination of information on established
systems and methods. This standard has been prepared to meet this need. New requirements to eliminate the
need to release clean agents during testing and commissioning procedures are included. These are linked to
the inclusion of enclosure integrity testing.

The requirements of this Indian Standard are made in the light of the best technical data available at the
time of drafting this standard but, since a wide field is, covered, it has been impracticable to consider every
possible factor or circumstance that might affect implementation of the recommendations.
It has been assumed in the preparation of this Indian Standard that the execution of its provisions is
entrusted to people appropriately qualified and experienced in the specification, design, installation, testing,
approval, inspection, operation and maintenance of systems and equipment, for whose guidance it has been
prepared, and who can be expected to exercise a duty of care to avoid unnecessary release of clean agent.
Specific requirements and advice on these matters can be obtained from the appropriate manufacturer of the
clean agent or the extinguishing system. Information may also be sought from the appropriate fire authority,
the health and safety authorities and insurers. In addition, reference should be made as necessary to other
statutory regulations.

It is essential that fire equipment be carefully maintained to ensure instant readiness when required. Routine
maintenance is liable to be overlooked or given insufficient attention by the owner of the system. The importance
of maintenance cannot be too highly emphasized.

For the purpose of deciding whether a particular requirement of this standard is complied with, the final
value, observed or calculated. expressing the result of a test or analysis, shall be rounded off in accordance
with IS 2 : 1960 ‘Rules for rounding off numerical values (revised)’. The number of significant places retained
in the rounded off value should be the same as that of the specified value in this standard.
1S 15493:2004

Indian Standard
GASEOUS FIRE EXTINGUISHING SYSTEMS —
GENERAL REQUIREMENTS
1 SCOPE responsible for approving installation or equipment
or a procedure.
This standard specifies provisions and
recommendations for general requirements, type of 3.4 Automatic — Performing a function without the
clean agent and their containers, container arrangement, necessity of human intervention.
distribution systems, such as piping, nozzles, pipe
supports, alarm system, type of enclosure etc. 3.5 Automatic/Manual Switch — A means of
converting the system from automatic to manual
NOTES ( manual override) and vice-versa.
1 This standard covers the general requirements
applicable to totai tlooding clean agent systems like 3.6 Class A Fires — Fire in ordinary combustible
Halo-Carbon agents and inert gas agents. In addition, materials, such as wood, cloth, paper, rubber, many
individual requirements for each type of clean agent plastics, electrical and electronic hazards without
system are covered un-der separate standards. Detailed
any flammable fiid or gas.
design guidelines are specitied, in other standards. Hence
before designing a protection with a particular clean
3.7 Class B Fires — Fire in flammable liquids,
agent, both the standards should be read together. Wherever
there is a difference, the individual standard takes
oils, greases, tars, oil-based paints, lacquers and
precedence, the like.
2 This standard prescribes minimum requirements for
3.8 Clean Agent — Electrically non-conducting,
total flooding clean agent tire/extinguishing systems.
Protection with carbon dioxide is not covered in this
vaporizing, or gaseous clean agent that does not
standard. leave a residue upon evaporation. The word agent
3 Nothing in this standard is intended to restrict new
wherever appearing in this document shall mean as
technologies or alternate arrangements provided the level clean agent.
of safety prescribed by this standard is not diluted.
3.9 Clearance — The air distance between clean
2 REFERENCES agent equipment, including piping and nozzles
and unenclosed or uninsulated live electrical
The standards listed in Annex A contain provisions
components at other than ground potential.
which through reference in this text, constitute
provisions of this standard. At the time of publication, 3.1O Containers — A cylinder or other vessels used
the editions indicated were valid. All standards are to store the clean agent.
subject to revision and the parties to agreements
based on this standard are encouraged to apply the 3.11 Container-Discharge Valve — A valve directly
most recent editions of the standards indicated connected to a container which when actuated
in Aflnex A. releases the clean agent into the distribution
piping.
3 TERMINOLOGY
3.12 Control Device — A device to control the sequence
For the purpose of this standard, the following of events leading to the release of clean agent.
definitions shall apply.
3.13 Concentration
3.1 Adjusted Minimum Design Quantity
( AMDQ ) — The minimum design quantity of agent 3.13.1 Design Concentration — The concentration
that has been adjusted in consideration of design ( including safety factor ) of the clean agent
factors. necessary to extinguish a fire of a particular fuel.

3.2 Approved — Acceptable to a relevant authority. 3.13.2 .Extinguishing Concentration — The


In determining the capability of the installations, concentration ( without safety factor ) of the
the authorities may base their acceptance with agent necessary to extinguish a flame ofa particular
appropriate standards. The design and system fuel at atmospheric pressure.
approval shall be from national or international
approving authority or lab of repute. 3.13.3 Hazardous Concentration — The
concentration that exceeds the LOAEL
3.3 Authority — The organization, office or individual ( see 3.28) for the agent used.
1
.

IS 15493:2004

3.13.4 Injected Concentration — The concentration extinguishing concentration surrounds the hazard.
of the agent necessary to develop under free efflux
3.24 Inert Gas Agent — A clean agent that contains
conditions the required design concentration.
as primary components one or more of the gases
3.13.5 Maximum Concentration — The concentration IGOI,IG55, IG100or !G541.
achieved from the actual clean agent quantity at the
3.25 Inerting — The prevention of reignition of
maximum ambient temperature.
a flammable or explosive atmosphere by establishing
3.13.6 Residual Oxygen Concentration — The a suitable concentration of the clean agent.
resulting concentration of oxygen achieved within
3.26 Liquefied Gas — A gas or gas mixture ( normally
a protected area after the discharge of agent into
a halocarbon ) which is liquid at the container
the area.
pressurization level at room temperature ( 20°C ).
3.14 Design Factor ( DF ) — A fraction of the agent
3.27 Lock-Off Valve — A mechanically operated
minimum design quantity ( MDQ ) added thereto
device which prevents a clean agent from being
deemed appropriate due to a specific feature of the
discharged through distribution pipe work to the
protection application or design of the suppression
protected area.
system.
3.28 Lowest Observed Adverse Effect Level
3.15 Directional Valve — A device for controlling
( LOAEL ) — The lowest concentration of clean agent
the passage of the clean agent from a supply
at which an adverse toxicological or physiological
manifold and directed to pre-selected area(s) of
effect has been observed.
protection.
3.29 Manual — Requires a human intervention to
3.16 Discharge Inhibit Switch — A manually
accomplish a function or task.
operated switch that prevents the automatic discharge
of the clean agent. 3.30 Maximum Working Pre-ssure —Equilibrium
pressure within a cylinder at the maximum working
3.17 Distribution System — All the pipe work
temperature. For liquefied gases, this is at maximum
and fittings downstream of any container discharge
fill density and may include super-pressurization, if
valve.
applicable.
3.18 Engineered Systems — A system in which
3.31 Minimum Design Quantity ( MDQ ) — The
the supply of the clean agent stored centrally is
quantity of agent required to achieve the calculated
discharged through a system of pipe and nozzles in
minimum design concentration.
which the size of each section of pipe and nozzle
orifice has been calculated in accordance with 3.32 Monitoring — The supervision of the operating
relevant clauses of ttiis standard. The design flow integrity of an electrical, mechanical, pneumatic or
rates from nozzles may vary according to the design hydraulic control feature of a system.
requirements of the hazard.
3.33 No Observed Adverse Effect Level
3.19 ‘Fill Density— The mass of gaseous agent per ( NOAEL ) — The highest concentration of a clean
unit volume of container ( kg/m3 ). agent at which no adverse toxicological or
physiological effect has been observed.
3.20 Final Design Quantity ( FDQ ) —A quantity
of agent determined from the agent minimum 3.34 Non-liquefied Gas — Gas or gas mixture
design quantity as adjusted to account for design which, under reserve pressure and allowable
factors and pressure adjustment. reserve temperature conditions, is always present
3.21 Flooding Quantity — Mass or volume of clean in a gaseous form.
agent required to achieve the design concentration 3.35 Normally Occupied Area — An area where,
within the protected volume within the specified under normal circumstances, humans are present.
discharge time.
3.36 Normally Unoccupied Area — Area not
3.22 Gross Volume — The volume enclosed by occupied by people but may be occasionally
the building elements around the protected entered for brief periods.
enclosure, less the volume of any permanent
impermeable building elements within the 3.37 Nominal Size — A numerical designation .of
enclosure. size which is common to all components in a piping
system other than components designated by
3.23 Holding Time — Period of time during which a outside diameters or by thread size. It is a convenient
concentration of clean agent greater than the fire round number for reference purposes and is only
2
IS 15493:2004

loosely related to manufacturing dimensions. 4 GENERAL INFORMATION AND


REQUIREMENTS
3.38 Operating Device — Any component involved
between actuation and release mechanisms, 4.1 General

3.39 Pre-engineered Systems — Those having 4.1.1 Extinguishing gases are thr.ee-dirnensional
pre-determined flow rates. nozzle pressures and agents that are used effectively to suppress fire
quantities of clean agent. These systems have the through physical or chemical action. Separate
specific pipe size, maximum and minimum pipe properties of specific gases are provided in other
lengths, flexible hose specifications, number of parts of this standard.
titt~ngs and number and types of nozzles prescribed
4.1.2 Gaseous total flooding systems may be used
by a testing laboratory.
to suppress fires of Classes A and B type as defined
3.40 Primary Release — Release of clean agent in 3.6 and 3.7. However, for suppressing fires where
initiated by detection system or manual operation flammable gases may be present, the possibility of
under normal operating conditions. explosion, during and after system discharge should
be considered.
3.41 Release — The opening of the cylinder and
directional valves leading to the physical discharge 4.1.3 Clean agent gas extinguishing systems are
or emission of clean agent into the enclosure. useful within the Iimits. of this standard in
extinguishing fires in specific hazards or equipment
3.42 Safety Factor ( SF ) — A multiplier of the and in occupancies where “an electrically non-
agent flame extinguishing or inerting conductive medium is essential or desirable, or where
concentration to determine the agent minimum clean-up of other media poses a problem.
design concentration.
4.1.4 Where clean agent gas extinguish& systems
3.43 Safety Interlock — A switch that monitors the are used, a fixed enclosure shall be provided about
occupation of the protected area and automatically the hazard that is adequate to enable the specific
inhibits the discharge of the clean agent when the concentration to be achieved and maintained for the
area is occupied. =specified period of time.
3.44 Sea Level Equivalent of Agent — The agent 4.1.5 The effects of agent decomposition on fire
concentration ( volume, percent ) at sea level for protection effectiveness shall be considered when
which the partial pressure of agent matches
using clean agents in hazards with high temperatures
the ambient partial pressure of agent at a given
( for example, furnaces and ovens, etc ).
altitude.
4.1.6 The design, installation, service and
3.45 Sea Level Equivalent of”Oxygen — The oxygen
maintenance of the gas extinguishing systems
concentration ( volume, percent ) at sea level for
shall be performed by those competent in the
which the partial pressure of oxygen matches the
respective field in accordance with IS 15496:2004.
ambient partial pressure of oxygen at a given
altitude. 4.1.7 The installer of the clean agent system shall
be certified by a reputed national/international
3.46 Secondary Release ( Slave) —A release that
agency/laboratory and sLIch certification shall be
is a consequence and dependent on the operation
valid at the time of installation.
of the primary release, for example, pneumatic
connection. 4.2 Suitability and Application

3.47 Super-pressurization — The addition of a gas 4.2.1 Total Flooding Svstems


to the clean agent container, where necessary, to
achieve the required pressure for proper system Gaseous fire extinguishing systems are used
operation. primarily to protect hazards that are in enclosures or
equipment that, in itself, includes an enclosure to
3.48 Total Flooding — The act and manner of contain the agent for establishment of required
discharging an agent for the purpose of achieving a concentration and maintenance thereof for the
specified minimum agent concentration throughout required pwiod. Some typical hazards that may
a hazard volume. be suitable include, but or not limited to, the
following:
3.49 Total Flooding Systems — A fire fighting system
that is arranged to discharge cl,ean agent into an a) Within enclosures, such as rooms, vaults,
enclosed space to achieve the appropriate design enclosed machines, containers, storage tanks
concentration. and bins;
3
1S 15493:2004

b) For enclosed electrical hazards, such as means other than the tire.
transformers, control cubicles, switch boards,
4.3.2 Electrostatic charging of non-grounded
circuit breakers, and rotating equipment;
conductors may occur during the discharge of
c) Forenclosed flammable liquid/gas storage gaseous fire extinguishing systems. These
and processing areas; conductors may discharge to other objects causing
d) For engines using tlammable fuels; an electric arc of sufficient charge to initiate explosion
e) For electronic hazards, such as computers, in potentially explosive atmospheres.
data processing equipment, control room, 4.4 Other Information
telecommunication facilities;
4.4.1 All devices in respect of the gaseous fire
t) Sub-floors and other concealed spaces; and
extinguishing systems shall be designed for the
g) Other high value assets. service they will encounter and shall not be readily
4.2.2 Some of the gaseous fire extinguishing rendered inoperative or susceptible to accidental
systems may also be used for explosion prevention operation. Normally, the system components shall be
and suppression where flammable materials may designed to function properly from – 210 to 55°C
collect in confined area. or marked to indicate temperature limitations in
accordance with the specifications.
4.3 Limitations
4.4.2 Gaseous fire extinguishing systems may be
4.3.1 Gaseous fire extinguishing systems shall employed to protect more than one enclosure, if
not be used on tires involving the following materials necessary, by means of directional valves. Where
unless they are pre-evaluated for the purpose: there are two or more enclosures simultaneously
a) Certain chemicals or mixture of chemicals, involved in a fire by reason of their proximity, such
such as cellulose nitrate, gun powder, which enclosures shall be protected by individual
are capable of rapid oxidation in the absence systems designed to allow simultaneous operation,
of air; or a single system sized and arranged to discharge
b) Reactive metals, such as lithium, sodium, on all potentially involved hazards simultaneously.
potassium, magnesium, titanium, zirconium, 4.4.3 Systems employing simultaneous discharge
and plutonium; of different agents to protect the same enclosure
c) Metal hydrides or metal amides, some of which shall not be permitted.
may react violently with some gaseous
agents; 4.5 Applicability of Clean Agents

d) Chemicals capable of undergoing auto- 4.5.1 The fire extinguishing clean agents addressed
thermal decomposition, such as certain in the standard are electrically non-conducting and
organic peroxides and hydrazine or; leave no residue upon evaporation.
e) Mixtures containing oxidizing materials, such 4.5.2 Tables I and IA show the details of clean
as sodium chlorate or sodium nitrate; and agents that are covered in this standard. While
f) Environments where significant surface requirements that are common to all these agents
areas exist at temperatures greater than are prescribed in this standard, individual
the breakdown temperature of the requirements for each agent are covered under
extinguishing agent and are heated by separate standards.
Table 1 Halocarbon Agents
( Clause 4.5.2 )

SI No. Clean Agent Chemical Name Commercial


Formulae Name
(1) (2) (3) (4)
i) CHC12CF~ Dichiorotritluoroethane ( HCFC- 123,
CHC1F2 4.75 percent )
CHCIFCF3 Chlorodifloromethane ( HCFC-22. HCFC Blend A
( Detoxified ) 82 percent}
Chlorotetrafluoroethane ( HCFC- 124,
9.5 percent )
Isoproponyl - 1-Illetllylcyclollcxtille
( 3.75 percent )
ii) CF3CHFCFJ Heptatluoropropane HFC-227ea

4
IS 15493:2004

Table IA Inert Gas Agents


( C/uuse 4.5.2 )

SI No. Clean Agent Chemical Name Commercial


Formulae Name
(1) (2) (3) (4)

i) Ar Argon ( 100 percent ) lGO1


ii) Nz Nitrogen ( 100 percent ) IG 100
iii) Nz Nitrogen ( 50 percent )
Ar Argon ( 50 percent ) ICi 55
iv) Nz Nitrogen ( 52 percent )
Ar Argon ( 40 percent ) [G 541
C02 Carbon dioxide ( 8 percent )

4.5.3 As such, both these standards, that is, for details of the contents, such as volume,
general and individual requirements should be read pressure, nominal capacity in agent mass at
together before designing a system. Where standard conditions of temperatures and
requirements in both the standards differ, standard pressures;
covering individual requirements shall take of pipes and fittings
precedence.
j) Descriptions
indicating also their specifications, pressure
5 REQUIREMENTS REGARDING SUBM1SS1ON ratings, etc;
OF PLANS k) Descriptions of nozzles employed
indicating their size, orifice area, type,
Plans shall contain sufficient details to enable an angle, etc, and their locations;
evaluation of the protected enclosure(s) or local
protection(s) vis-a-vis the effectiveness of the m) Electrical cabling and terminations;
system. Details shall include the property involved n) Descriptions of detectors employed
in the hazard(s), location(s), the enclosure limits indicating their locations, mounting, etc;
and isolation of the hazards and the exposure of the Bill of material and equipment schedule for
P)
hazards. each component proposed for the syste]n.
5.1 Plans for submission to the authorities shall Suppliers/manufacturer-s names, details of
be drawn up in accordance with the following approvals, quantity, etc;
requirements: 0 Isometric drawings showing the agent
distribution system indicating the lengths
a) Plans for integrity of fittings shall be clear,
and diameters of each pipe segment, nodal
contain all required details including
reference, fittings including unions, reducers,
scale and point of compass and shall be clearly
orifices, strainers, nozzles, flow rates in all
dated;
segments, equivalent orifice areas, etc;
b) Name of the enterprise, location and
r) Plan view of the enclosures showing the
detailed postal address;
entire agent piping system along with
c) Location and construction of the protected ceiling, floors, false floors, walls, partitions,
enclosures, walls and partitions; pipe supports, agent containers, cabling,
d) Cross and longitudinal sectional elevations panels, detectors, etc;
of the protection enclosures showing the s) Details showing the pipe supports, agent
full height, schematic diagram, ceilings, false container securement, etc;
floors, etc;
t) Location of ducts and similar devices,
e) Type of clean agent proposed to be used; dampers, air handling systems, venting
f) Concentration summary, that is, design, arrangements and their details with
extinguishing, injected and inerting, etc: supporting calculations, etc;

~) Type of the hazards proposed to be u) Schematic display of the operation of the


protected including descriptions of the system giving chmnologica] sequence of
occupancies, surroundings, wall/ceiling operations prior to the discharge of the agent
openings, etc; into the protected enclosures;
h) Location of the gas containers and v) Schematic diagrams showing the location

5
IS 15493:2004

and layout of all the power and indicating In areas, where there is a likelihood of significant
equipment connections, control panels, difference between gross and net volumes of the
annunciate panels, etc; enclosure, utmost care shall be exercised in pnoper
w) Tables showing the calculations for enclosure system design to ensure that maximum concentrations
volumes, agent quantity, methods used to are not exceeded.
determine number and location of audible
6.1.1 Safety Precautions (for Protected Areas )
and visual indicating equipment, number and
location of detectors, etc; and a) Normally occupied area — The minimum
Y) Other features like interconnection with safety precautions taken shall be in
other type of fire protection systems, etc, with accordance with Table 2A and provisions
the proposed system. therein, and
b) Normally unoccupied areas — The maximum
5.2 The details of the system shall include
concentration shall not exceed the LOAEL
information and calculations on the amount of agent;
for the agent used unless a lock-off valve is
container storage pressure; internal volume of the
fitted.
containers; the location, type and flow rate of each
nozzle including equivalent orifice area; the location, Warning — Any change to the enclosure
size and equivalent lengths of pipe, fittings, siphon volume, or addition or removal of contents
tube, valve, discharge head and flexible connector that was not covered in the original design
hose; and the location and size of the storage facility. will affect the concentration of agent. In such
Pipe size reductions and orientation of tees shall be instances the system shall be re-calculated
clearly indicated. Details shall be available on location to ensure that the required design
and function of the detection devices, operating concentration is achieved and that the NOAEL
devices, auxiliary equipment and electrical circuitry. or the LOAEL are not exceeded.
All the apparatus, equipment used in the system shall
be easily identifiable. 6.1.2 For unoccupiable areas, the maximum
concentration may “exceed the LOAEL for the
5.3 An as-built drawing shall be submitted upon extinguishant used, without the need for a lock-
completion of the installation for approval. Instruction off valve to be fitted.
and maintenance manuals that include a full
sequence of operations and a full set of drawings and 6.1.3 Protection of Occupants
calculations shall be available on site.
In any use of the gaseous system, where there is a
5.4 Flow Calculations possibility that people may enter or have difficulty
seeking egress from the protected enclosure, suitable
System flow calculations along with the working safeguards shall be provided. Such safety aspects
drawings shall be submitted to the authorities in as personal training, warning signs, pre-discharge
advance for approval. The hydraulic calculations
alarms and safety interlocks shall be provided. Means
shall be performed using calculation method approved of proper ventilation after fire should be readily
by the authorities. available.
6 SAFETY REQUIREM-ENTS
6.2 Safety Precautions ( Total Flooding Systems)
6.1 Safety Precautions ( for Personnel)
6.2.1 In areas protected by total flooding systems,
The discharge of some of the gas agents in fire that are capable of being occupied, the provision of
extinguishing concentrations creates serious hazards the following safety aspects shall apply:
for personnel in both the protected area and the areas
to which the gas may migrate and also to properties a) Mandatory requirements:
in the vicinity of agent discharge. These hazards may 1) A time delay shall be provided for
include reduced visibility, suffocation and toxicity, evacuation prior to agent discharge.
during and afterthe discharge period. The relevant The agent discharge delay time shall be
information on the above is available in Annex B. based on an engineering assessment of
egress time for occupants in the area
The tox[city information on the gaseous fire agents
protected,
is given in Table 2. More details are specified in
other relevant standard. Where hazardous 2) Safety interlocks and lock-off valves
concentrations of agent may exist, Iock-offvalves shall shall be provided wherever required
be fitted to the system. as per Table 2.

6
1S 15493:2004

Table2 Toxicity Information on Clean Agent Suppression Systems


( Clauses 6.1 and6.2.l )

S1 No. Clean Agent Chemical Formula NOAEL LOAEL LC50 or ALC


( Percentage by Volume )
r
(1) (2) (3) (4) (5) (6)

i) HCFC CHC12CF3 ( 4.75 percent )


Blend A CHCIF2 ( 82 percent ) 10 >10 64
CHC1FCF3 ( 9.5 percent )
Detoxified (3.75 percent)
ii) HFC-227ea CF2CHFCF3 9 10.5 >80
iii) IG-541 Nitrogen ( 52 percent ) 43 52 Not
Argon ( 40 percent ) applicable
Carbon dioxide ( 8 percent )
iv) IG-55 Nitrogen ( 50 percent ) 43 52 Not
Argon ( 50 percent ) applicable

v) IG-1OO Nitrogen ( 100 percent ) 43 52 Not


applicable
vi) IG-01 Argon ( 100 percent ) 43 52 Not
applicable

Table 2A Minimum Safety Precautions


( Clauses 6.1.1 and%.2.l )

S1 No. Injected Agent Requirements


Levels r
Inhibit Egress Safety Lock-off’
Switch and in 30 s Interlock Valve
Time Delay
(1) (2) (3) (4) (5) (6)
i) Up to NOAEL Required Not required Not required Not required
ii) Above NOAEL and Required Required Required Not required
up to LOAEL
iii) Above LOAEL Required Not Applicable’) Required Required

NOTE — The-purpose of the table is to avoid unnecessary exposure ot’occupants to the agent discharged, Factors such
as the time for egress and the risk to the occupants by the fire must be considered when determining the system discharge
time delay.
1)con~ntration levels above LOAEL are-not permitted in occupied areas and question of egress does not ark.

3) Exit routes which shall be kept clear at 8) Means of prompt ventilation of such areas
all times and the provision of after any discharge of agent. Forced draft
emergency lighting and adequate ventilation will often be necessary. Care
direction signs to minimize travel shall be taken to completely dissipate
distances, hazardous atmospheres and not just
4) Outward swinging self-closing doors move them to other locations, as agents
which can be opened from inside are generally heavier than air, and
including when locked from the outside, 9) instructions and drills of all personnel
5) Continuous visual and audible aIarms within or in the vicinity of protected
at entrances and designated exits until areas, including maintenance and
the protected area has been made safe, construction personnel who may be
brought into the area, to ensure their
6) Warning and instruction signs shall be
correct actions when the system operates.
arranged as per clause,
b) Recommendatory requirements:
m Pre-discharge alarms within such areas
that are distinctive from all other alarm 1) Adding an odour to the agent so that
signals and that will operate immediately the hazardous atmospheres are
upon detection of fire, recognizable,

7
IS 15493:2004

2) Self-contained breathing apparatus practicable, protection shall be extended


and personnel trained for its use, and to include the adjacent connected hazards
3) Means to detect a hazardous or work areas;
atmosphere in or around the protected c) Particular attention should be given to
area. openings around cable, duct and pipelines
( similar utility services ) penetrating
6.2.2 Electrostatic Discharge
through the wall(s) and floor(s);
To avoid a situation as stated in 4.3.2, the components d) In case of unavoidable openings, such
of the inerting system, such as pipe work, etc, shall openings should be restricted to as minimum
be bonded and earthed as per National Electrical as possible;
Code( SP30 : 1985).
e) In such cases, quantity of agent need to be
6.3 Miscellaneous Hazards suitably increased in consultation with the
Certain other types of hazards associated with the authorities concerned for maintaining the
desired concentration within the
usage of gaseous systems are as under:
enclosure;
a) Noise — Discharge ofa gaseous system can
f) In case of item (c) above, the openings
cause a noise loud enough to be startling,
should be effectively sealed or preferably
but not enough to cause traumatic injury;
fire studded; and
b) Turbulence — The turbulence caused by the
g) Injecting more quantity of agent in most of
high velocity discharge from nozzles may be
the cases, will only increase the rate of loss
sufficient to dislodge substantial objects
of agent through such openings. Hence,
directly in its path, such as ceiling tiles and
openings in the wall(s) and floor(s) shall be
light fittings. Therefore, tiles and light fittings
kept only to optimum requirements with
should be properly anchored. System
increase in quantity of agent as discussed
discharge may also cause enough general
in item (d) above.
turbulence in the enclosure to move unsecured
-paper and light objects; 7.2 Air Handling System and Similar Services
c) Elec~rical clearance — Where exposed a) Humidification and air handling systems
electrical conductors are present, all system catering to the protected areas shall be
components shall be located no less than capable of automatic shutdown prior to the
the minimum clearances from the energized agent discharge, Also dampers shall be
parts. The clearances stipulated in National available inside the systems to stop flow
Electrical Code shall be maintained for safe of agent through ducts and similar means
operating conditions. Where the design basic and these shall close automatically prior to
insulation level is not available and where agent discharge;
nominal voltage is used for the design criteria
b) Where it is necessary for air handling
the highest minimum clearance listed for the
systems to be kept operating to provide
purpose shall be used; and
cooling arrangement for essential equipment,
d) Other hazards, if any, appropriate to the quantity of the agent shall need to be
selected gaseous agent as specified in the suitably increased to include the volumes of
other clauses of this standard shall be given both air and the ventilation system in
due attention. addition to the volume of protected
7 REQUIREM-ENTS FOR THE PROTECTED enclosure in consultation with the authorities
ENCLOSURES concerned for maintaining the desired
concentration within the enclosure;
7.1 Unclosable Openings
c) The operations within the enclosure that
a) The protected enclosure shall have sufficient are likely to di-sperse the discharge of the
structural strength and integrity to contain agent, such as pumps, spray guns, heaters,
the agent discharge; etc, shall not be left running during the
b) The area of the unclosable openings such discharge of the agent and suitable provisions
as ventilator openings within the enclosure shall be available to shut them down prior
shall be kept to as least as possible to avoid to agent discharge; and
ingress of the agent through the leakages d) In case of extinguishment of deep-seated
to the adjoining areas. Where confinement fires such as those involving solids.
of the agent within the enclosure is not Unclosable openings shall be provided
8
IS 15493:2004

only in the ceiling level and such openings Explosives, Nagpur,


near the walls and partitions shall be Each agent container shall have a
avoided. permanent nameplate or other permanent
8 COMPONENTS OF GASEOUS FLOODING marking that indicate the details as
SYSTEMS per Table 4.
A reliable means shall be provided to
8.1 Agent Supply and Container Arrangement
determine the pressure in refillable super-
8.1.1 Agent Supply pressurized containers, and
Th~ agent containers connected to a
a) Quality Requirement — The clean agent
common manifold shall conform as per the
shall comply with quality and purity
provisions in Table 5.
standards appr~priate to the agent selected
for extinguishment. Each batch of agent Table 4 Marking on Storage Container
manufactured shall be tested and certified
[ Clause 8. 1.2(e) ]
to applicable specification. Agent blends
shall remain homogeneous in storage and S1 No. Clean Agent Marking on Container
use within the approved temperature (1) (2) (3)
range and envirornnental conditions at the i) Halocarbon clean Name of the agent
place of installation; Tare and agents gross weights
b) Super-pressurization level of
Quantity Requirements ( Main ) – The
the container
amount of agent in the system shall be at
ii) inert gas clean Name of the agent
least sufficient for the largest single
agent Pressurization level of the
hazard or group of hazards to be protected
container
simultaneously; Nominal agent volume
c) Quantity Requirements (Reserve) – Same
quantity equivalent to the largest single Table 5 Arrangement of Containers with
hazard or group of hazards to be protected Common Manifold
simultaneously shall be available as
[ C/ause 8. 1.2(g) ]
reserve. However, if the replenishing of
agent supply takes more than 7 days at the S1 No. Clean Agent Containers with
site of installation, authority concerned Common Manifold
may insist on more quantity to be kept (1) (2) (3)
available as reserve; and i) Halocarbon clean Agents in a multiple
d) Uninterrupted Protection — Where agents container system — all
uninterrupted protection is required, both containers supplying the
same manifold outlet for
the main and reserve supply shall be
distribution of the same
permanently connected to the distribution agent shall be
piping and arranged for easy change-over. interchangeable, of same
nominal size and ca~acitv.
t?.1.2 Agent Storage filled with same n;min;l
mass of agent and
a) Agent shall be stored in containers designed
pressurized to the same
to hold that specific agent at ambient nominal working pressure
temperatures, ii) Inert gas clean Agents shall be permitted to
b) Agent containers shall be charged to a fill agents utilize multiple storage
density or super-pressurization level with container sizes connected
range specified by the manufacturers, to the common manifold
provided the containers are
c) Agent storage temperatures shall not all pressurized to the same
exceed 55°C or be less than–21 “C. External nominal working pressure
heating or cooling shall be employed to
keep the temperature of the agent storage 8.1.3 Storage Container Arrangement
container within the above limits if situation
warrants so, The arrangement of storage containers and
accessories shall be as follows:
d) The agent containers used in the flooding
systems shall be designed to meet the a) Containers and accessories shall be located
requirements of the Department of and arranged so that inspection testing,
9
IS 15493:2004

recharging and other maintenance is corrosion resistant materials shall be


facilitated, and interruption to protection is required for pipes, fittings or support
kept to a minimum; brackets and steelwork;
b) Containers should be located outside and c) Before final assembly, pipes and fittings
as near as practical to the enclosure shall be inspected visually to ensure they
protected. Containers protecting a single are free of burrs, swelter and rust and that
risk can be located within the enclosure no foreign matter is inside and the full bore
they serve, only if sited so as to minimize is clear. After assembly, the system shall”be
the risk of exposure to fire and explosion; thoroughly blown through with dry air or
c) Containers shall be located so as not to be compressed gas. The pipe work shall be.free
subject to severe weather conditions or to of particulate matter and oil residue before
mechanical, chemical or other damage. the installation of nozzles and discharge
Where excessive climatic or mechanical devices;
exposures are expected, suitable guards or d) A dirt trap consisting of a ‘tee’ with a capped
enclosures shall be provided; nipple at least 50 mm long should be
d) Containers shall be adequately mounted installed at the end of each pipe run. Drain
to allow free passage of air around the base traps should also be necessary if there is a
and suitably supported to provide for possibility ofa build-up of water;
convenient individual servicing or content e) In systems where valve arrangements
weighing. There shall be enough space introduce sections of closed piping, such
for a full on-site inspection of the base of sections shall be equipped with the
the container; following:
e) In manifold systems, non-return valves 1) Indication of agent trapped in piping;
or other automatic means shall be provided 2) Means for safe manual venting; and
to prevent a loss of agent and to ensure
personnel safety if the system is operated 3) Automatic relief of excess prtssure,
when any containers are removed for where required.
maintenance; 0 Pressure relief devices, which can include
Containers brackets or devices integral the selector valve, shall be fitted so that
9
with the container for attachment to the discharge, in the event of operation, will
structures shall be designed to cater for the not endanger the personnel; and
maximum expected mass, vibration effects @ In systems using pressure-operated
and shock loading, appropriate to the container valves, automatic means shall be
installation; provided to vent any container leakage that
Reserve containers, where provided, shall could build up pressure in the pilot system
g)
be permanently sited or arranged for easy and cause unwanted opening of the container
changeover; and valve. The means provided for pressure
venting shall not prevent operation of the
h) Storage containers are located in areas container valve.
where their leakage could lead to a
hazardous concentration, consideration 8.2.2 Piping Network
shall be given to the installation of gas
8.2.2.1 The piping used in the installation shall
detectors or other means to provide
conform to the following requirements:
warning on the onset of hazardous
conditions. a) Cast iron or non-metallic pipes shall not be
used anywhere;
8.2 Agent Distribution Arrangements
b) Where used, flexible pipes, tubing, or hoses
8.2.1 General including connections shall be of approved
a) Pipe network, fitting shall be of non- materials with adequate temperature and
combustible construction having physical pressure ratings; and
and chemical properties such that their c) The thickness of the pipes shall be in
integrity under stress can be predicted with accordance with the provisions laid down
reliability; in IS 6631. The internal pressure used for
b) In severely corrosive atmospheres, special this calculation shall not be less than the
greater of either of the following values:

10
IS 15493:2004

1) The normal charging pressure in the values shown in the tables are used with prior
agent container at21°C. acceptance of the -authorities, the minimum design
2) 80 percent of the maximum pressure in pressure for the piping -shall be adjusted to the
the agent container at the maximum maximum pressure in the agent container at
storage temperature of not less than maximum temperature, using the basic design
55°C using the maximum allowable fill criteria specified in items C(1) and c(2) above.
density specified by the manufacturer, 8.2,3 Pipe Fittings
inapplicable.
a) The sizes and dimensions of pipe fittings
d) Pipe joints shall be either threaded, welded
shall be in accordance with 1S 1239 ( Part 2 ).
or flanged type only and other types of
Fittings shall be capable to withstand
jointing shall not be allowed.
minimum rated working pressure equal to or
In no case shall the value used, for the minimum greater than the minimum working
piping design pressure, be less than that specified in pressure specified in 8.2.2.1 (c) for the clean
Tables 6 and 7 for the conditions shown. agent being used. For systems that use a
pressure reducing device in the distribution
For halocarbon agents Table 6 shall be used and for piping, the fittings downstream the device
inert gas agents Table 7 shall be used. shall have a minimum rated working
pressure equal to or greater than the
Where different fill densities, pressurization levels maximum anticipated pressure in the
or higher storage temperatures other than the downstream piping;
Table6 Minimum Design Working Pressure for Halocarbon Clean Agent System Piping
( Clause 8.2.2.1)

S1 No. Clean Agent Agent Container Agent Container Agent Container Minimum
Maximum Fill Charging Charging Piping Design
Density Pressure Pressure Pressure
kg/m2 at 21OC at 55°C at 21°C
kPa kPa kPa
(1) (2) (3) (4) (5) (6)
i) HFC-227ea 992 1 0341) 1 703 1 365
1 152 2 482]) 3585 2868
1 120 4 1371) 4950 3958
ii) HCFCBlendA 900 4 1371) 5860 4689
900 2 4821) 3723 2979
I)SuPer.Pressurized with nitrogen.

Table 7 Minimum Design Working Pressure for Inert Gas Clean Agent System Piping
( Clause 8.2.2.1)

S1 No. Clean Agent Agent Container Agent Container Minimum Design Pressure at 21°C
Charging Pressure Charging Pressure r >
Piping Upstream Piping
at 21°C at 55°C of Pressure Downstream
kPa kPa Reducer of Pressure
kPa Reducer
kPa
(1) (2) (3) (4) (5) (6)
i) IG-O I 16341 18271 16341 6723
20424 22778 14997 6728
ii) IG-541 14997 17755 14997 6895
19996 23671 19996 6895
iii) IG-55 15521 17065 15318 6550
20424 22753 20424 6550
30636 34 130 30633 6550
iv) IG-100 16580 19300 16580 6895
22311 26014 22311 6895

11
IS 15493:2004

b) Cast iron fittings shall not be used All nozzles shall be such that:
threads used in joints and fittings shall 1) The design concentration shall be
comply with relevant Indian Standards; achieved in all parts of the enclosure;
c) Welding ofjoints shall comply with relevant 2) The discharge shall not unduly splash
Indian Standards; and. flammable liquids or create dust clouds
d) Where copper, stainless steel, or other that might extend the fire, create an
suitable tubing is jointed with compression explosion or otherwise adversely affect
type fittings, manufacturers pressure and the occupants;
temperature ratings of the fittings shall 3) The velocity of discharge shall not
not be exceeded. adversely affect the enclosure or its
contents;
8.2.4 Pipe Installation and Supports
4) The discharge nozzles shall be provided
a) In the installation of pipe work, care shall be with frangible discs or blow-out caps
taken to avoid possible restrictions due to where clogging by foreign materials is
foreign matter, faulty fabrication or improper possible. These devices shall provide
installation. Pipe ends shall be reamed after an unobstructed opening upon system
cutting, where required; operation and shall be arranged so they
b) Where there is a possibility of explosions, will not injure personnel;
the piping shall be attached to supports that 5) .Nozzle shall be suitable for the
are least likely to be displaced; and intended use and shall be approved for
c) The maximum distance between supports shall discharge characteristics. The discharge
take into account the total mass of pipe and nozzle consists of the orifice and any
the agent used. Distance between supports associated horn, shield or baffle;
is indicated in Table 8.
6) Nozzles shall be of adequate strength
Table 8 Maximum Pipe Work Distances for use”with the expected working
pressures, be able to resist nominal
[ Clause 8.2.4(c)]
mechanical abuse, and be constructed
Nominal Diameter Maximum Pipe
to withstand expected temperatures
S1 No.
of Pipe Work Distance without deformation; and
mm mm Nozzle discharge orifice inserts shall
(1) (2) (3) be ofcorrosion-resistant material.
i) 6 0.5 c) In order to minimize the possibility of
ii) 10 1 lifting or displacement of lightweight
iii) 15 1.5 ceiling tiles, precautions shall be taken to
iv) 20 1.s securely anchor the tiles for a minimum
25 2.1
distance of 1.5 m from each discharge nozzle.
v)
vi) 32 2.4 9 DETECTION, ACTUATION, ALARM AND
vii) 40 2.7 CONTROL SYSTEMS
viii) 50 3.4 9.1 General
ix) 65 3.5
9.1.1 Detection, actuation, alarm and control
x) 80 3.7
systems shall be installed, tested and maintained
xi) 100 4.3
in accordance with 1S2189.
xii) 125 4.8
xiii) 150 5.2
9.1.2 Automatic detection and automatic actuation
shall be used.
xiv) 200 5.8
9.2 Automatic Detection
8.2.5 Discharge Nozzles
9.2.1 Automatic detection shall be by any
a) Nozzles, including nozzles directly approved method or device capable of detecting
attached to containers, shall be of approved and indicating heat, flame, smoke, combustible
type and located with the geometry of the vapours or any abnormal condition in the hazard,
enclosure under consideration. such as process trouble, that is likely to produce
b) The type, number and placement of fiie.

12
1S 15493:2004

9.2.2 Adequate and reliable primary and 24 h control for activation shal I be located not more than
minimum standby sources of energy shall be used to 1.2 m above the floor.
provide for operation of the detection, signaling,
9.3.8 Where gas pressure from the system or pilot
control and actuation requirements of the system,
containers is used as a means for releasing the
9.2.3 When a new agent system is being installed remaining containers, the supply and discharge
in a space that has an existing detection system, an rate shall be designed for releasing all of the
analysis shall be made of the detection devices to remaining containers.
assure that the detection system is in good
9.3.9 All devices for shutting down supplementary
operating condition and will respond promptly to a
fire situation. This analysis shall be done to assist equipment shall be considered integral part of the
in limiting the decomposition products from a system and shall function with the system
suppression event. operation.

9.3 Operating Devices 9.3.10 All manual operating devices shall be


identified as to the hazard they protect.
9.3.1 Operating devices shail include agent
releasing devices or valves, discharge controls and 9.4 Control Equipment
shutdown equipment necessary for successful 9.4.1 Electric Control Equipment
performance of the system.
The control equipment shall supervise the
9.3.2 Operation shall be by approved mechanical, actuating devices and associated wiring and, as
electrical or pneumatic means, adequate and reliable required, cause actuation. The control equipment
source of energy shall be used. shall be specifically listed for the number and type
9.3.3 All devices shall be designed for the of actuating devices utilized and their compatibility
service they will encounter and shall not readily be shall have been approved.
rendered inoperative or .iusceptible to accidental 9.4.2 Pneumatic Control Equipment
operation. Devices normally shall be designed to
function properly from –2OOto 55°C or marked to Where pneumatic control equipment is used, the
indicate temperature limitations. lines shall be protected against crimping and
mechanical damage. Where installations could be
NOTE — Also care shall be taken to thoroughly
evaluate and correct any factors that could result in exposed to conditions that could lead to loss of
unwanted discharge. integrity of the pneumatic lines, special precautions
shall be taken to ensure that no loss of integrity will
9.3.4 All devices shall be located, installed or suitably occur. The control equipment shall be specifically
protected so that they are not subject to mechanical, listed for the number and type of actuating devices
chemical or other damage that would render them utilized and their compatibility shall have been
inoperative. approved.
9.3.5 A mean of manual release of the system 9.5 Operating Alarms and Indicators
shall be provided. Manual release shall be
accomplished by a mechanical manual release or 9.5.1 Alarms or indicators or both shall be used to
by an electrical manual release when the control indicate the operation of the system, hazards to
equipment monitors the battery voltage level of the personnel, or failure of any supervised device. The
standby battery supply and will provide a low type ( audible, visual or olfactory ), number, and
battery signal. The release shall cause location of the devices shall be such that their
simultaneous operation of automatically operated purpose is satisfactorily accomplished. The extent
valves controlling agent release and distribution. and type of alarms or indicator equipment or both
shall be approved.
9.3.6 The normal manual control(s) for actuation
shall be located for easy accessibility at all times, 9.5.2 Audible and visual pre-discharge alarms shall
including at the time of a fire. The manual control(s) be provided within the protected area to give positive
shall be of distinct appearance and clearly recognizable warning of impending discharge. The operation of
for the purpose intended. Operation of any control the warning devices shall be continued after agent
shall cause the complete system to operate in its normal discharge until positive action has been taken to
fashion. acknowledge the alarm and proceed with appropriate
action.
9.3.7 Manual controls shall not require a pull of
more than 18.1 kg ( 178 N ) nor a movement of more 9.5.3 Abort switches generally are not
than 355 mm to secure operation. At least one manual recommended, however, where provided, the abort
13
IS 15493:2004

switches shall be located within the protected area To determine that the system has been properly
and shall be located near the means of egress from installed and will function as specified, the tests
the area. An abort switch shall not be operated specified in 10.2.2 to 10.2.9 shall be performed.
unless the cause for the condition is known and
10.2 Review of Mechanical Components
corrective action can be taken. The abort switch
shall be of a type that requires constant manual 10.2.1 The piping distribution system shali be
pressure to cause abort. The abort switch shall not inspected to determine that it is in compliance with
be of a type that would allow the system to be left in the design and installation documents.
an aborted mode without someone present. In all
cases the normal and manual emergency control 10.2.2 Nozzles and pipe size and, if appropriate,
shall override the abort function. Operation of the pressure-reducing devices, shall be in accordance with
abort function shall result in both audible and distinct system drawings. The means for pipe size reduction
visual indication of system impairment. The abort and attitudes of tees shall be checked for conformance
switch shall be clearly recognizable for the purpose to the design.

1
intended.
10.2,3 Piping joints, discharge nozzles and piping
9.5.4 Alarms indicating failure of supervised supports shall be securely fastened to prevent
devices or equipment shall give prompt and positive unacceptable vertical or lateral movement during
indication of any failure and shall be distinctive discharge. Discharge nozzles shall be installed in such
from alarms indicating operation or hazardous a manner that piping cannot become detached
conditions. during discharge.

9.5.5 Warning and instruction signs at entrances to 10.2.4 During assembly, the piping distribution
and inside protected areas shall be provided. system shall be inspected internally to detect the
possibility of any oil or particulate matter which
9.5.6 Indication lamps shall be provided to indicate could soil the hazard area or affect the agent
the status of the abort switch, that is, Green colour distribution due to a reduction in the effective
for ‘Auto’, Yellow colour for the ‘Manual’ and Red nozzle orifice area.
colour for ‘Discharge’ modes.
10.2.5 The discharge nozzles shall be oriented in
9.6 Time Delays such a manner that optimum agent dispersal can be
9.6.1 For clean agent extinguishing systems, a effected.
pre-discharge alarm and time delay, sufficient to 10.2.6 [f nozzle deflectors are installed, they shall
allow personn-el evacuation prior to discharge, shall be positioned to obtain the maximum benefit.
be provided. For hazard areas subject to fast
growth fires, where the provision of a time delay 10.2.7 The discharge nozzles, piping and mounting
would seriously increase the threat to life and brackets shall be installed in such a manner that they
property, a time delay shall be permitted to be will not potentially cause injury to personnel, Agent
eliminated. shall not directly impinge on areas where personnel
may be found in the normal work area, or on any loose
9.6.2 Time delays shall be used only for personnel objects or shelves, cabinet tops, or similar surfaces
evacuation or to prepare the hazard area for where loose objects could be present and become
discharge. -:”.:1-.
Illlssllcs.

9.6.3 Time delays shall not be used as a means of 10.2,8 All agent storage containers shall be properly
confirming operation of a detection device before located in accordance with ‘approved for construction’
automatic actuation occurs. set of system drawings.
10 COMMISSIONING AND ACCEPTANCE 10.2.9 All containers and mounting brackets shall
The minimum requirements for the commissioning and be securely fastened in accordance with the
acceptance of the gaseous extinguishing system shall manufacturer’s requirements.
be as follows. 10.2.10 An adequate quantity of agent to produce
10.1 General the desired specified concentration shall be
provided. The actual enclosure volumes shall be
The completed system shall be reviewed and tested checked against those indicated on the system
by a competent person to meet the approval of the drawings to ensure the proper quantity of agent. Fan
authority. Only equipment and devices designed rundown and damper closure time shall be taken into
to national standards shall be used in the systems. consideration.
14
IS 15493:2004

10.2.11 Unless the total piping contains not signaling, control and actuation requirements of the
more than one change in direction fitting between the system.
storage container and the discharge nozzle, and
10.3.4 All auxiliary functions ( such as alarm
unless all piping has been physically checked for
sounding or displaying devices, remote annunciators,
tightness, the following tests shall be carried out:
air handling shutdown, power shutdown, etc ) shall
a) All open ended piping shall be pneumatically be checked for proper operation in accordance with
tested in a closed circuit for a period of 10 system requirements and design specifications.
min at 3 bar. At the end of 10 rein, the pressure
Alarm devices shall be installed so that they are
drop shall not exceed 20 percent of the test
audible and visible under normal operating and
pressure, and
environmental conditions.
b) All closed-section pipe work shall be
hydrostatically tested ‘to a minimum of Where possible, all air handling and power cut-off
1.5 times the maximum working pressure for controls should be of the type that once interrupted
2 min during which there shall be no require manual restart to restore power.
leakage. On completion of the test, the pipe
10.3.5 Check that for systems using alarm silencing,
work shall b~purged to remove moisture.
this function does not affect other auxiliary functions,
It is recommended that hydrostatic testing be carried such as air handling or power cut-off where they are
out at the manufacturer’s works where practicable. required in the design specification.

WARNING — Pneumatic pressure testing creates 10.3.6 Check the detection devices to ensure that
a potential risk of injury to personnel in the area, the types and locations are as specified in the
as a result of airborne projectiles if rupture of the system drawings and are in accordance with the
piping system occurs. Prior to conducting the manufacturer’s requirements.
pneumatic pressure test, the protected area shall
10.3.7 Check that manual release devices are
be evacuated and appropriate safeguards shall
properly installed, and are readily accessible,
be provided for test personnel.
accurately identified and properly protected to
10.2.12 A test using nitrogen, or a suitable prevent damage.
alternative, shall be performed on the piping
10.3.8 Check that manual release devices used to
network to verify that flow is continuous and that the
release agents require two separate and distinct
piping and nozzles are unobstructed.
actions for operation. They shall be properly
10.2.13 Where required, suitable venting facilities identified. Particular care shall be taken where
shall be provided for the release of excessive pressure manual release devices for more than one system are
build-up during discharge of the agent. Individual in close proximity and could be confused or the
standards for gaseous agents provide details for the wrong system actuated. Manual release devices in
design of venting facilities. this instance shall be clearly identified as to -which
hazard enclosure they protect.
10.3 Review of Electrical Components
10.3.9 Check that for systems with a main/reserve
10.3.1 All wiring systems shall be properly installed capability, the main/reserve switch is properly
in compliance with the appropriate National installed, readily accessible and clearly identified.
Standard and the system drawings..a,c. and d.c. wiring
shall not be combined in a common conduit unless 10.3.10 Check that for systems using inhibit
properly shielded and grounded. switches requiring constant manual force, these are
properly installed, readily accessible within the
10.3.2 All field circuitry shall be tested for ground hazard area and clearly identified.
fault and short circuit condition. When testing field
circuitry, all electronic components ( such as smoke 10.3.11 Check that the control panel is properly installed
and flame detectors or special electronic equipment and readily accessible.
for other detectors, or their mounting bases ) shall 10.4 Preliminary Functional Tests
be removed and jumpers properly installed to prevent
the possibility of damage within these devices. Replace 10.4.1 Where a system is connected to a remote
components after testing the circuits. central alarm station, notify the station that the fire
system test is to be conducted and that an
10.3.3 Adequate and reliable primary standby emergency response by the fire departmen(or alarm
sources of energy which comply with 9.2.2 shall be station personnel is not required. Notify all concerned
used to provide for operation of the detection, personnel at the end-user’s facility that a test is to
15
IS 15493:2004

be conducted and instruct them as to the sequence 10.6.2 Operate each type of alarm condition and
of operation. verify receipt of fault condition at the remote
station.
10.4.2 Disable or remove each agent storage
container release mechanism and selector valve, 10.7 Control Panel Primary Power Source
where fitted, so that activation of the release circuit
will not release agent. Reconnect-the release circuit 10.7.1 Verify that the control panel is connected to a
with a functional device in lieu of each agent storage dedicated unstitched circuit and is labelled properly.
container release mechanism. This panel shall be readily accessible but access shall
be restricted to authorized personnel only.
For electrically actuated release mechanisms, these
devices may include suitable lamps, flash bulbs or 10.7.2 Test a primary power failure in accordance
circuit breakers. Pneumatically actuated release with the manufacturer’s specification, with the system
mechanisms may include pressure gauges, Refer to fully operated on standby power.
the manufacturer’s recommendations in all cases.
10.8 Review ofEnclosure-integrity
10.4.3 Check each resetable detector for proper
It is preferable to subject all total flooding systems
response.
to an Enclosure Integrity ~est in order to detect
10.4.4 Check that polarity has been observed on all and seal the significant leakage paths that could
polarized alarm devices and auxiliary relays. result in-failure of an enclosure to withhold design
concentration for a specified period ( see 7,1
10.4.5 Check that all required end-or-line devices and 10.10 ).
have been installed.
10.9 Completion of Functional Tests
10.4.6 Check all supervised circuits for correct fault
response. When all functional tests are complete ( see ‘10.6
to 10.9 ), reconnect each storage container so that
10.5 System Functional Operational Test activation of the release circuit will release the agent.
Return the system to its fully operational design
10.5.1 Operate the detection initiating circuit(s).
condition. Notify the central alarm station and all
All alarm functions shall occur according to the
concerned personnel at the end-user’s facility that
design specification.
the fire system test is complete and that the system
10.5.2 Operate the necessary circuit to initiate a has been returned to full service condition by following
second alarm circuit if present. Verify that all the procedures specified in the manufacturers’
second alarm functions occur according to design specifications.
specifications.
10.10 The complete installation shall be tested in
10.5.3 Operate the manual release device. Verify one of the two methods narrated below:
that manual release functions occur according to
a) Full-scale discharge test, and
design specifications.
b) Enclosure integrity test.
10.5.4 Where appropriate, operate the inhibit
switch. Verify that functions occur according to the Where the authorities concerned insist on
design specifications. Confirm that visual and full-scale discharge test, the test shall be
audible supervisory signals are received at the control conducted in accordance with various provisions
panel. under Annex C and results of the test ( that is
concentration achieve-d, discharge time, holding
10.5.5 Check the function of all resettable valves time ) shall conform to various provisions available
and activators, unless testing the valve will rele~se in other clean agent standards with particular
agent. ‘one-shot’ valves, such as those incorporating reference to the agent used. Otherwise, the enclosure
frangible discs, should not be tested, where total flooding system is installed, shall be
10.6 Remote Monitoring Operations ( If subject to’ enclosure integrity test’ in accordance with
Applicable ) various provisions under Annex D to demonstrate
the retention time ( of the required concentration
10.6.1 Disconnect the primary power supply, then with the-enclosure ] as specified in other standards
operate one of each type of input device while on with particular reference to the agent used.
standby power. Verify that an alarm signal is received
at the remote panel after the device is operated. 10.11 Completion Certificate and Documentation
Reconnect the primary power supply. The installer shall provide to the user a completion
16
IS 15493:2004

certificate, a complete set of instructions, calculations NOTE — These equations use friction factors and
and drawings showing the system as-installed, and constants dependent on pressure and density
obtained empirically. As the equations cannot be solved
a statement that the system complies with all the
directly, a cornputcr programme is usually used to
appropriate requirements of this standard, and giving assist with the large number of iterative calculations
details of any departure from appropriate in which pipe and nozzle sizes and if appropriate,
recommendations. The certificate shall give the design size of pressure reducing devices, are selected within
concentrations and, if carried out, reports of any prescribedpressurelosses.
additional test including the door fan test. 11.5 Valves and Fitting
11 SYSTEM HYDRAULIC FLOW Valves and fittings shall be rated for resistance
CALCULATIONS coefficient or equivalent length in terms of pipe,
11.1 General or tubing sizes with which they will be used.
The equivalent length of the cylinder valves
System flow calculations shall be carried out at a shall be listed and shall include siphon tube ( where
nolninal agent storage temperature of 21 “C, shall fitted ), valve, discharge head and flexible
have been validated by an accredited approval connector.
authority by appropriate tests as described in this
standard, and shall be properly identified. The 11.6 Piping Length
system design shall be within the manufacturer’s The piping length and nozzle and fitting orientation
specified limitations. shall be in accordance with the manufacturer’s
NOTES approved manual to ensure proper system
1 Variations from the nominal 21 “C storage performance.
temperature will affect flow conditions used in
calculations.
11.7 Drawings
2 Prc-engineered systems do not require a flow If the final installation varies from the prepared
calculation when used within approved drawings and calculations new ‘as- built’ drawings
limitations.
and calculations shall be prepared.
11.2 Balanced and Unbalanced System
11.8 Liquefied Gases ( Specific Requirements)
11.2.1 A balanced system shall be one in which:
11.8.1 Allowance shall be made for changes in
a) each actual or equivalent pipe length from elevation as specified in the relevant standard
the container to each nozzle are all within 10 relating to the specific agent.
percent of each other, and
11.8.2 Minimum discharge rate for liquefied agents
b) the discharge rate of each nozzle is equal. shall be sufficient to maintain the velocity required
for turbulent flow to prevent separation.
11.2.2 Any system that does not meet the criteria
mentioned in 11.2 shall be considered to be an NOTE— 11’turbuleat flow is not maintained, separation
unbalanced system. of the liquid and-gaseous phases will occur, which can
lead to unpredictable tlow characteristics.
11.3 Friction Losses
11.8.3 For information on two-phase flow for liquefied
Allowance shall be made for the friction halocarbon gases ( see Annex E ).
losses in pipes and in container valves, dip tubes,
flexible connectors, selector valves, time delay 12 ENGINEERED AND PRE-ENGINEERED
devices and other equipment ( for example, pressure- SYSTEM
reducing devices ) within the flow line. 12.1 General
NOTE — The flow of a liquefied gas will be a two
All agents are suitable for use in both engineered
phase phenomenon, the fluid consisting of a mixture
of liquid and vapour, the proportions of which are central storage, system and pre-engineered
dependent on pressure and temperature. The pressure ( modular or packaged ) systems, as described
drop is non-linear, with an increasing rate of pressure in 12.2 and 12.3.
loss as the line pressure reduces by pipe friction.
12.2 Engineered
11.4 Pressure Drop
An engineered system uses large storage
The pressure drop shall be calculated using two phase containers installed in central location. The
flow equations for liquefied gases and single phase containers are manifold together and a single
Now-equations for non-liquefied gases. pipe feeds the nozzle located inside the

17
IS 1-5493:2004

hazard area. Predicting pipe pressure losses and 13 PHYSICAL PROPERTIES


designing nozzle orifice sizes required complex
Physical properties of inert gas and halocarbon
flow calculations for both agent and nitrogen
agents are shown in the Tables 9 and 10.
phases .( in case of halocarbon gases ) and for
agent ( in case of line gases ), which takes into 14 TRAINING
account the minimum and maximum volumes or the
enclosure. 14.1 All persons who may be expected to operate,
maintain, test or inspect fire extinguishing systems
12.3 Pre-engineered shall be kept continuously and adequately trained in
the functions they are expected to perform.
A pre-engineered system involves a single
container the maximum of two nozzles and a small 14.2 Personal working in an enclosure protected
piping network. This system can be multiplied to by or gaseous extinguishant shall be trained and
cover larger volume areas. The larger area is viewed kept fully conversant with the operation and use
as a number of smaller areas each protected by a of the system, particularly regarding safety
single modular unit. requirements.
Table 9 Physical Properties of Inert Gas Agents
( Clause 13 )

S1 No. Properties Units IG-01 IG-1OO IG-541 IG-55


(1) (2) (3) (4) (5) (6) (7)
i) Molecularweight N/A 39.9 28.0 34.0 33.95
ii) Boiling point at 760 mm Hg T -189.85 -195.8 -196 -190.1
iii) Freezing point T -189.85 -210.0 –78.5 –199.7
iv) Critical temperature T -122.3 -146.9 NIA -134.7
v) Critical pressure kPa 4903 3399 NIA 4150
vi) Specific heat, vapour at Kj/kg”C 0.519 I .04 0.574 0.782
constant pressure ( 1 atm )
and 25°C
vii) Heat of vaporization at Kj/kg 163 199 220 181
boiling point
viii) Relative dielectric strength TWA 1.01 I .0 1.03 1.01
at 1 atm at 734 mm Hg,
25°C (N2 = 1.0)
ix) Volubility of water in agent NIA 0:006 0.oo1 3 0.015 0.006
at 25°C percent percent percent percent

18
IS 15493:2004

Table 10 -Physical Properties of Clean Halocarbon Agents


( C/ause I 3 )

S1 No< Properties Units HCFC Blend A HFC 227ea


(1) (2) (3) (4) (5)

O Molecular weight N/A 92.90 170.03


ii) Boiling point at 760 mm Hg “c -38.3 -16.4
iii) Freezing point “c <107.2 -[31
iv) Critical temperature “c 124.4 -101.7

v) Critical pressure kPa 6647 2912


vi) Critical volume Cchnole 162 274
vii) Critical density kglms 577 621
viii) Specific heat, liquid at 25°C Kj/kg°C 1,~56 1.184
ix) Specific heat vapour at constant pressure Kj/kg “C 0.67 0.808
( 1 atm ) and 25°C
x) Heat of vaporization at boiling point Kjlkg 225.6 132.6
at 25°C
xi) Thermal conductivity of liquid at 25°C Whll”c 0,0900 0.069
xii) Viscosity, liquid at 25°C Centipoises 0.21 0.184
xiii) Relative dielectric strength at I atm at N/A 1.32 2.00
734 mm Hg, 25°C ( Nz = 1.0 )
xiv) Volubility of water in agent at 210C Pp m 0. I 2 percent 0.006 percent
by weight by weight

ANNEX A
( Clause 2 )
LIST OF REFERRED INDIAN STANDARDS

IS No. Title IS No. Title


1239 Mild steel tubes, tubtrlars and
6631:1972 Specification for steel pipes for
(Part2 ): 1992 other wrought steel fittings:
hydraulic purposes
Part 2 Mild steel tubulars and
other wrought steel pipe fittings
SP 30:1985 National Electrical Code
(fourth revision )
2189:1999 Selection, installation and 15496:2004 Inspection and’maintenance of
maintenance of automatic fire gaseous fire extinguishing
detection and alarm system — systems — Code of practice
Code of practice

19
ANNEX B
(Clause 6.1 )
INFORMATION ON SAFETY TO PERSONNEL AND DECOMPOSITION PRODUCTS
OF COMBUSTION

II-l Any hazard to personnel created by the that the vapour must decompose before the agent
discharge of gaseous extinguishants shall be can inhibit the combustion reaction. Decomposition
considered in the design of the system, in particular takes place on exposure to a flame or to a hot surface
with reference to the hazards associated with at a temperature above 480°.C. In the presence of
particular extinguishants in the other standards of available hydrogen ( from water vapour or the
clean agents. Unnecessary exposure to all gaseous combustion process itself), the main decomposition
extinguishants shall be avoided. product is hydrogen fluoride ( HF ).

B-2 The decomposition products generated by tbe B-6 The decomposition products .of halocarb.on
clean agent breaking down in the presence of very agents have a characteristic sharp acrid adour, even
high amounts of heat can be hazardous. All of the in minute concentrations of only a few parts per
present halocarbon agents contain fluorine. In the million. This characteristic provides abuilt-in warning
presence of available hydrogen ( from water vapour, system for the extinguishant, but at the same time
or the combustion process itself ), the main creates a noxious, irritating atmosphere for those who
decomposition product is hydrogen fluoride ( HF ). have to enter the enclosure following a fire. The actual
concentration of the decomposition products
B-3 These decomposition products have a sharp,
depends on the volume of the enclosure in which
acrid odour, even in minute concentrations of only a fire is burning and the degree of mixing and
few parts per million. This characteristic provides a
ventilation.
built-in warning system for the agent, but at the same
time creates a noxious, irritating atmosphere for those B-7 Longer exposure of the vapour to tempera-
who must enter the hazard following a fire. tures in excess of 482°C would produce greater
concentrations of these gases. The type and sensi-
B-4 The amount of agent that can be expected to
tivity of detection, cwpled with the rate of discharge,
decompose in extinguishing a fire depends .to a
should be selected to minimize the exposure time of
large extent on the size of the fire, the particular
the vapours to the elevated temperature if the
clean agent, the concentration of the agent, and the
concentration of breakdown products is to be
length of time the agent is in contact with the
minimized. In most cases, the area would be untenable
flame or heated surface. If there is a very rapid
for human occupancy due to the heat and breakdown
build-up of concentration to the critical value, then
products of the fire itself.
the fire will be extinguished quickly and the
decomposition will be limited to the minimum B-8 Clearly, longer exposure of the agent to high
possible with that agent. Should that agent’s temperatures would produce greater concentrations
specific composition be such that it could of these gases. The type and sensitivity of detection,
generate large quantities of decomposition coupled with the rate of discharge, should be selected
products, and the time to achieve the critical value is to minimize the exposure time of the agent to the
lengthy, then the quantity of decomposition elevated temperature if the concentration of the
products can be quite great. The actual concentration breakdown products is to be minimized.
of the decomposition products then depends on
the volume of the room in which the fire was burning B-9 Non-liquefied agents do not decompose
and on the degree of mixing and ventilation. measurably in extinguishing a fire. As such, toxic or
corrosive decomposition products are not found.
B-5 Although the vapour from halocarbon gas has However, breakdown products of the fire like carbon
low toxicity, the decomposition products can be monoxide itself can still be substantial and could
very hazardous. The most widely accepted theory is make the area untenable for human occupancy.

20
IS 15493:2004

ANNEX C
(-Clause 10.10 )
REQUIREMENTS FOR FULL-SCALE DISCHARGE TEST

C-1 SCOPE required by the appropriate authority,


and
This clause sets out a procedure to determine
4) Where the geometry of the enclosure
compliance of the gaseous total flooding system
with the requirements for discharge time, concentration does not lend itself to sampling in the
and holding time. above manner, take a minimum of three
samples at locations agreed upon by the
C-2 PRINCIPLE appropriate authority.
The system is operated, discharge time is measured d) Set the continuous chart recorder type
and concentration readings are taken at a specified concentration meter for the agent concerned
height at nominated periods. and check that the meter is calibrated in
accordance with the manufacturer’s
C-3 TEST MEDIUM instructions so that it will record
concentration levels at each sampling
The test medium shall be the concerned halocarbon
point for 10 min from commencement of
or inert gas.
discharge,
C-4 APPARATUS e) Record temperature in enclosure,
The following apparatus is required: f) Ensure that plant which is capable of
affecting system performan-ce, for example,
a) A chart recorder type concentration meter air-hand(ing plant is in its normal operating
calibrated in strict accordance with the mode,
manufacturer’s instructions,
g) Activate the system and record the discharge
b) A suitable time-measuring device, and time ( see 11 ), and
c) Temperature-measuring equipment. h) Record concentration readings and holding
C-5 PROCEDURE times ( see 11 ).

The procedure shall be as follows: C-6 RECOMMISS1ONING

a) Ensure that the preliminary checks, in Restore all systems to a fully operational status.
accordance with respective standard
pertaining to gaseous fire extinguishing C-7 REPORTING
system have been completed, The following shall be reported:
b) Electrically isolate all flooding systems
serving adjacent enclosures, a) 1) installation, designer and contractor;
c) 1) Concentration measurements should 2) enclosure identification;
be made at a minimum of three points, 3) enclosure temperature prior to discharge;
one-at the highest hazard level, 4) design concentration; and
2) Locate sampling points in the enclosure 5) position of sampling points.
at the specified heights ( see 10 ). Do
not locate sampling points nearer than b) Date and time of test,
200 mm to ceiling unless the combustibles c) Discharge time,
being protected extend within that area, d) Concentraticms at each sampling point
in which case special design at I and 10 min from the commencement of
considerations may be necessary, discharge, and
3) If more than one space or compartment e) System deficiencies.
is being simultaneously protected,
locate a sampling point in each space in Cross-check various observed parameters with the
accordance with the above criteria. respective operating clauses are in conformity
Additional sampling points may be therewith.

21
1S 15493:2004

ANNEX D
( Clause 10.10)
REQUIREMENTS FOR TESTING ENCLOSURE INTEGRITY
D-1 TEST FOR DETERMINATION OF e) Two thermometers, to measure ambient
PREDICTED MINIMUM HOLD TIME temperatures, and
D-1.1 Principle o Signs, reading “DO NOT OPEN —
PRESSURE TEST IN PROGRESS” and
A fan is temporarily located within an access “DO NOT CLOSE — PRESSURE TEST IN
opening to pressurize and repressurize the enclosure, PROGRESS”.
A series of pressure and air flow measurements is
NOTE — Additional apparatus, such as measuring
made from which the leakage characteristics of the tapes, torches, ladders. tools to remove floor and ceiling
enclosure; are established. tiles, computer or other calculating device, may be
necessary.
The predicted hold time is calculated using
these leakage characteristics on the following D-1.3 Calibration of Apparatus
assumptions:
a) Fan Unit — Calibrate the fan unit at the
a) That leakage occurs under the worst intervals and by the method recommended
conditions, that is, when one-half of the by the manufacturer. Keep records and, where
effective leakage area is at the maximum appropriate, calibration certificates. Use a
enclosure height and represents the flow meter accurate to + 5 percent and a
inward leakage of air, and the other half ( the pressure-measuring device accurate to+ 1 Pa.
lower leakage area ) of the total effective b) Press ure-Measttring Devices — The
leakage area is at the lowest point in the pressure-measuring- devices shall be
enclosure and represents the outward calibrated not more than 12 months before
leakage afextinguishant/air, a test. Records shall be maintained and,
b) That all leak flow is one-dimensional, i.e. where appropriate, calibration certificates.
ignoring stream functions, If inclined manometers are used, change
c) That flow through any particular leak area the fluid not more than 3 mcrnths before the
is either into or out of the enclosure and test. Level and zero inclined manometers
either from or into an infinitely large space, before each test,
d) That the system is at sea-level, at a D-1.4 Preliminary Preparation
temperature of 20”C, and atmospheric
pressure of 1.013 bar absolute, and a) Obtain a description from the user of the
air-handling equipment and extinguishant-
e) An enclosure integrity test is deemed extraction systems in the enclosure,
successful when at least 80 percent of
the design concentration is available b) Check for the following:
within the enclosure at the expiry of 1) raised platform floors and false ceiling
10 min (see D-2.10). spaces;

D-1.2 Apparatus 2) visually obvious leaks in the enclosure;


3) adequate return paths outside the
a) Fan unit, consisting of a frame which will fit
enclosure between all leaks and the”fan
into and seal an access opening in the
unit; and
enclosure, and one or more variable speed
fans, with low flow facilities, capable of 4) conflicting activities in and around the
giving a differential pressure of not less enclosure.
than 25 Pa across the enclosure boundary, c) Provide the following information to the user:
b) Two pressure-measuring devices, one to 1) a description of the test;
measure enclosure differential pressure 2) the timerequired to complete the test;
and one to measure fan flow pressure,
.3) what assistance will be needed from the
c) Flexible tubing, for connecting the user’s staffl and
pressure-measuring devices,
4) Information on any necessary
d) Chemical smoke pencils and/or smoke disturbance to the building or its
generator, services during the test ( for example,
LL
IS 15493:2004

removal of floor or ceiling tiles, during the test if this is needed


shutdown of air-handling systems, to avoid temperature build-up
holding doors open and/or shut ). in equipment such .as computers;
and
D-1.5 Evaluation of Enclosure
ii) Recirculating air-handling
Obtain or prepare a sketch plan showing the walls, equipment which would continue
the location of the door and other openings through to operate on extinguisharit
w-hich air will flow during the test, and the location discharge should be shut down, if
of any ducts penetrating the enclosure, and any it creates excessive bias pressure.
dampers in the ducts. Show the status ( that is, 5) Post the appropriate signs on doors
whether open or closed when the extinguishant [see D-1.2 (f) ].
system is discharged ) of each door, hatch and
damper, and which access opening(s) is (are) to be 6-) Open doors and remove floor or ceiling
tiles within the extinguishant- protected
used for the fan unit.
portions of the enclosure envelope so
Show the location of floor and sink drains. that the extinguishant- protected volume
is treated as one space. Do not remove
D-1.6 Measurement of Enclosure false ceiling tiles if the volume above the
Measure the protected enclosure volume as necessary false ceiling is not protected with
and record the following: extinguishant.
n Close all doors and windows in the
a) Overall height of the protected enclosure, enclosure envelope.
b) Height of the highest hazard in the 8) Check that liquid traps in the floor and
enclosure, and sink drains are sealed with liquid.
c) Gross volume of the protected enclosure.
b) Setting up Door Fan Unit
D-1.7 Test Procedure 1) Set up the fan unit in an access opening
leading from the enclosure into the
a) Preparation for Test
largest volume of building space
1) Advise supervisory personnel in the which will complete the air-flow path
area of the test. from the fan, via the enclosure, leaks and
2) Remove papers and objects likely to building space back to the fan.
be disturbed by the turbulence from the 2) Gently blow into or suck from the
fan. flexible tubing so that the readings of
3) Block open sufficient doors outside the pressure-measuring devices
the enclosure envelope to provide an traverse the full scale. Hold the
adequate return path for air between maximum reading for not less than 10s.
the fan unit and the enclosure leaks, Release the pressure and zero the
while correcting any breach of any devices.
requirements of the facility, including
3) Connect the enclosure differential
requirements for security, fire protection
pressure-measuring device. Ensure
and environmental boundaries.
that the open ends of the flexible
4) Using the sketch plan ( see D-1.5), set tubing near the fan unit are away
all air-handling equipment and from its air stream path and any other
extinguishant-extract ion systems to air flows which might affect the
the state they would be in at the time readings.
of extinguishant system discharge,
4) Use the fan(s) to raise or lower the
except for the following:
pressure of the enclosure by
i) Recirculating air-handling approximately 15 Pa. Check all
equipment without fresh air make- dampers with smoke and ensure that
up which does not give a bias they are closing properly. Check doors
pressure across the enclosure and hatches and ensure correct
boundary or otherwise preclude closure, Inspect the wall perimeter
accurate testing, and which would ( above and below any false floor) and
be shut down on extinguishant the floor slab for any major leaks and
discharge, may be left operating note their size and location.
23
1S 15493:2004

C) A4easurement of Bius Pressure or less evenly spaced over the range


1) Seal the fan unit inlet or outlet and, without down to 10 Pa.
the fan(s) operating, observe the 4) Use the fan unit to pressurize the
enclosure differential pressure-measuring enclosure and repeat the procedure
device for at least 30s. of (d) (iii). Again record the value of
2) Ifa bias p~essure is indicated, use smoke ( Pf + Pb ), which will be positive.
to detect the consequent air flow and its NOTE — For calculation purpose, either Pf or Pb or
direction. If the existence of a bias the average of the two can be taken.
pressure is confirmed, record the D-2 CALCULATIONS
pressure-measuring device reading as the
bias pressure (Pb). D-2.1 Notations
3) If the enclosure is large, or if the bias Q = air leakage rate, in m3/s;
pressure is largely caused by wind or c = flow coefficient;
stack effects, repeat the measurement at
P = pressure within enclosure, in Pa;
one or more different access openings.
Record all the values measured and use N = slope of the graph;
the largest positive value ( or if only R~ = density of agent /air Mixture, in kg/m3;
negative values are recorded, the value
closest to zero ) as the bias pressure. Agent Densi@, kg/m3

A bias pressure as low as 0.5 Pa can affect the accuracy Air 1.202
of the test result. If the bias pressure has a numerical
value greater than 25 percent of fire extinguishant/ HCFC Blend A 3.84
air column pressure, then.the hold time is likely to be HFC-227ea 7.26
low and the enclosure may not hold the specified
extinguishant concentration. The source of the IG-541 1.41
excessive bias pressure should be identified and, if IG-55 1.41
possible, permanently reduced.
RA = density of air, in kg/m3;
10 the event of fluctuating bias pressures ( such as
R~ = density of agent, in kg/m3;
those created by wind effects), it may not be possible
to achieve the necessary correlation accuracy in the PM = agent/Air column pressure, in Pascal
fan test results. These fluctuating pressures may need (Pa);
to be eliminated before an accurate fan test can be G= gravitational acceleration, 9.81 m/s2;
carried out. HO = total height of the enclosure, in m;
d) Measurement of Leakage Rate H= minimum acceptable height in the
1) Measure the air temperature inside enclosure, in m;
the enclosure, Te, and measure the air A= area of the enclosure, in m2;
temperature outside the enclosure TO,at v“ volume of the enclosure, in m3;
several points. If the location of leaks
is not known, use the average value;
~= uncorrected agent/air mixture leakage
otherwise, use the average value rate, in m3/s;
weighed according to the known Q. = corrected agent/air mixture leakage rate,
location of the leaks. in ins/s;
2) Unseal the fan inlet or outlet and TL = temperature within the enclosure, in ‘C;
connect the fan flow pressure- measuring T~ = temperature outside the enclosure, in “C;
device.
ELA = equivalent leakage area, in m2;
3) Use the fan unit to repressurize the
K= discharge coefficient ( 0.61 to
enclosure to the maximum extent, but
I depending upon nature of leakage
by not more than 60 Pa. Allow the
openings );
enclosure differential pressure
measuring reading to stabilize ( which ILA = total leakage area, in m2;
may take up to 30s ) and record the value LLF = lower leak fraction;
( Pf+ Pb ) which will be negative. Repeat
ALL = area of lower leaks, in m2;
at not less than four more fan unit
c . agent concentration, in percent;
flow rates to give five readings more
24
,-

1S 15493:2004

Cp = pass concentration in percent agent/air mixtuFe leakage rate:


( 80 perc~nt of the design agent
concentration ); QM=
(Qm)(TL+z7s)
M3,S
(TP+273)
C3 = equation simplification constant;
C4 = equation simplification constant; and D-2.7 The next step will be todetermine the equivalent
leakage area ( ELA ):
T= retention time of pass concentration
(CP) within the enclosure, in seconds. (1.271 )(Q~) mz
ELA = _
D-2.2 After pressurizing ( depressurizing ) the v PM
enclosure to various pressures, corresponding
flow rates in 1/s for each room pressure shall be D-2.8 The next step will be to determine the total
recorded wherefrom the flow at 1 Pa pressure i$ leakage area ( TLA ):
determined. This value (C) is deemed as flow TLA=(K)(ELA)m2
coefficient ( constant ) for the purpose of
calculation. D-2.9 The next step will be to determine the lower
leak fraction ( LLF):
The formula establishing a relation between flow
and the pressure is Q = CPN where Q = Air leakage ALL
rate, in m3/s, C = Flow coefllcient, P = Pressure within LLF = —
TLA
enclosure in Pa and N = Slope of the graph.
D-2.1 O The next step will be to determine the retention
NOTE — The value of N can be determined by
time ( T):
substituting observed values for Q, P and C in the above
equation.
T= (A)[(c3~o+c4)
(1-h’) _(qf+c4)( I-iv)] s

D-2.3 The next step will be to determine the density (1-N) (C3)(LLF)(TLA)
of agent/air mixture ( R~ ):
where
RM= (RG)( c)+ (RA)(1OO-C)
100 100
kg/m3 (2G)(RM-RA)
C3= l/N

D-2.4 The next step will be to determine the,agent/


air column pressure (PM):
(R~)+(RA)[]flF
1
2 ( Static pressure inside enclosure)
P~=(G)(HO) (R~– RA)Pa C4 =
R~
D-2.5 The next step will be to determine the
NOTES
uncorrected agent/air mixture leakage rate:
1 If static pressure is negative, then treat it as zero.
-Qm=(c)(pM)Nm3/s 2 If static pressure is positive, then consider actual
value.
D-2.6 The next step will be to determine the corrected

25
IS 15493:2004

ANNEX E
( Clause 11.8.3 )
1NFORMATION ON TWO-PHASE FLOW FOR LIQUEFIED HALOCARBON GASES

E-1 As the extinguishant the liquid phase flows


in Agent entering the distribution system is vaporized
from the storage container, the pressure drops or before it reaches the nozzles, due to heating by
recedes. The pressure recession varies with the pipe work and the initial low pressure in the
container fill density. It is assumed that there was system. The initial vaporization limits the flow of
thermodynamic equilibrium between the liquid and Agent through the distribution system because the
vapour phases in the storage container. In actual tests, mass flow of vapour is much lower than that ofliquid.
it has been noted that there is a sharp drop in pressure E-6 LIQUID FLOW
during the initial rush of liquid into the distribution
system. This is due to a lag between the pressure There is a significant delay between the opening of
drop and the onset of boiling in the container. As boiling the discharge valve and the first appearance of liquid
commences, the pressure returns to the pressures at the nozzles. Some of the delay is due to the flow
shown on the curves for respective gaseous restriction presented by the container and distribution
extinguishants representing the calculated pressure system, however much of delay is due to the initial
in the storage container versus the percentage vapour phase flow of the Agent.
discharge of extinguishant from the container for both E-7 PHASE SEPARATION
2.5 MPa and 4.2 MPa systems.
The flow of Agent in the distribution system is a“two-
E-2 AGENT IN PIPE WORK phase flow ( containing both liquid and vapour ). In
Agent flows through the distribution system in a properly sized distribution system the flow will
both liquid and vapour phase. As the liquid phase be highly turbulent throughout the system and the
flows through the distribution system the two phases will mix homogeneously. [fthe pipes are
pressure continues to drop, causing the liquid to boil. too big the phases may tend to separate, which can
The volume of the vapour phase increases with the cause a variety of flow problems and can in some cases
decreasing pressure and hence the density of the result in a reduced flow rate.
mixture drops. To maintain a constant flow rate, the E-8 AVERAGE PRESSURE CONDITIONS
speed through the distribution system must
Pressure at the nozzle is not constant throughout
continuously increase down the pipe work. The
discharge because the pressure in the storage
pressure drop for a given flow rate is no-tlinear, as it
container is constantly decreasing. If one were .to
is with water, but is variable along the pipe.
attempt manual calculation it would be desirable to
E-3 DENSITY -OF AGENT IN DISTRIBUTION use an average pressure condition. It is difficult to
SYSTEM arrive at an average as the volume of piping has a
marked effect on the average nozzle ( pressure,
Using the thermodynamic properties of the
density and velocity conditions ), all of which, have
Agent, including the nitrogen used for super-
a marked effect on discharge quantities and times.
pressurization, the density of the two-phase mixture
in the distribution system can be calculated. The E-9 AVERAGE NOZZLE PRESSURE
density of the Agent leaving the storage container The nozzle pressure used for calculations is the
varies over the course of the discharge, The density pressure when half the liquid phase has been
is lowest at the start of discharge and increases discharged from the nozzle. The timing of this is used
until the last of the liquid leaves the container.
to-calculate an average pressure drop in the distribution
E-4 TEMPERATURE system. To calculate the correct storage container
pressure, allowance must be made for the amount of
The drop in container pressure as the Agent flows liquid in the piping system.
from the container causes remaining Agent in the
container to cool. As a result, liquid that is below E-10 PERCENT IN DISTR1BUTION SYSTEM
ambient temperature is introduced to the distribution The points outlined above are taken into
system. During a system discharge the temperature consideration to calculate the average container
of the Agent leaving the storage container recedes pressure during discharge. The ratio of the pipe
as a function of instantaneous container pressure. volume to the volume of Agent supply expanded
E-5 INITIAL VAPOUR TIME under flowing conditions varies with average
container pressure, The former quantity shall be
At the start of discharge virtually all the liquid phase referred to as percent-in-the-pipe.
26
-Bureau of Indian Standards

BIS is a statutory institution established under the Bureau of Indian Standards Act, 1986 to promote
harmonious development of the activities of standardization, marking and quality certification of goods and
attending to connected matters in the country.

Copyright

131Shas the copyright of all its publications. No part of these publications may be reproduced in any form
without the prior permission in writing of BIS. This does not preclude the free use, in the course of implementing
the standard, of necessary details, such as symbols and sizes, type or grade designations. Enquiries relating
to copyright be addressed to the Director (Publications), BIS.

Review of Indian Standards

Amendments are issued to standards as the need arises on the basis of comments. Standards are also reviewed
periodically; a standard along with amendments is reaffirmed when such review indicates that no changes are
needed; if the review indicates that changes are needed, it is taken up for revision. Users of Indian Standards
should ascertain that they are in possession of the latest amendments or edition by referring to the latest issue
of ‘BIS Catalogue’ and ‘Standards : Monthly Additions’.

This Indian Standard has been developed from Doc : No. CED22(7011 ).

Amendments Issued Since Publication

Amend No. Date of Issue Text Affected

BUREAU OF IINDIAN STANDARDS


Headquarters:
Manak Bhavan, 9 Bahadur Shah Zafar Marg, New Delhi 110002
Telephones: 23230131,23233375,2323 9402 Website: www.bis.org.in

Regional Offices: Telephones

Central : Manak Bhavan, 9 Bahadur Shah Zafar Marg 23237617


NEW DELHI 110002 { 23233841

Eastern : l/14 C. I.T. Scheme VII M,V. I. P. Road, Kankurgachi 23378499,23378561


KOLKATA 700054 { 23378626,23379120
Northern : SCO 335-336, Sector 34-A, CHANDIGARH 160022 2603843
{ 2609285
Southern: C. 1.T. Campus, IV Cross Road, CHENNAI 600113 22541216,22541442
{ 22542519,22542315
Western : Manakalaya, E9 MlDC, Marol, Andheri (East) 28329295,28327858
MUMBA1400093 [~ 28327891,28327892

Branches: AHMEDABAD. BANGALORE. BHOPAL. BHUBANESHWAR. COIMBATORE.


FAR1DA13AD. GHAZIABAD. GUWAHAT1. HYDERABAD. JAIPUR. KANPUR.
LUCKNOW. NAGPUR. NALAGARH. PATNA. PUNE. RAJKOT. THIRUVANANTHAPURAM.
VISAKHAPATNAM.
Printed at New India Printing Press, Khurja, India

You might also like