Professional Documents
Culture Documents
Is 15493 2004
Is 15493 2004
Indian Standard
GASEOUS FIRE EXTINGUISHING SYSTEMS —
GENERAL REQUIREMENTS
ICS 13.220.10
0 BIS 2004
FOREWORD
i’his Indian Standard was adopted by the Bureau of Indian Standards, after the draft finalized by the
Fire Fighting Sectional Committee had been approved by the Civil Engineering Division Council.
Attention is drawn to Montreal Protocol on substances that deplete the ozone layer. As India is a signatory
to the Protocol. country programme was drafted wherein suitable alternative clean agents have been identified
in the place of HaIons 1301 and 12 I 1. As per the approved programme, this standard has been formulated for
the identified alternatives. The agents covered in this standard are thus introduced in response to international
restrictions on the production of certain Halon fire extinguishing agents under the Protocol signed in 1992, as
emended.
[t is important that the fire protection of a building or plant be considered as a whole. Gaseous clean agent
systems form only a part, though an important part, of the available facilities, but it should not be assumed that
(heir adoption necessarily removes the need to consider supplementary measures, such as the provision of portable
tire extinguishers or other mobile appliances for first aid or emergency use, or to deal with special hazards.
Gaseous fire suppression systems covered in these Indian Standards are designed to provide a supply of
gaseo~ls exting~lishillg mediuln for the extinction of fire invo]ving high value assets.
Gaseous clean agents have for many years been a recognized effective medium for the extinction of flammable
liquid fires and fires in the presence of electrical and ordinary Class A hazards, but it should not be forgotten, in
the planning of comprehensive schemes, thatthere may be hazards for which these mediums are not suitable, or
that in certain circumstances or situations there may be dangers in their use requiring special precautions. These
difficulties have been addressed in this standard.
Various methods of supplying clean agent to, and applying it at, the required point of discharge for fire extinction
have been developed in recent years, and there is a need for dissemination of information on established
systems and methods. This standard has been prepared to meet this need. New requirements to eliminate the
need to release clean agents during testing and commissioning procedures are included. These are linked to
the inclusion of enclosure integrity testing.
The requirements of this Indian Standard are made in the light of the best technical data available at the
time of drafting this standard but, since a wide field is, covered, it has been impracticable to consider every
possible factor or circumstance that might affect implementation of the recommendations.
It has been assumed in the preparation of this Indian Standard that the execution of its provisions is
entrusted to people appropriately qualified and experienced in the specification, design, installation, testing,
approval, inspection, operation and maintenance of systems and equipment, for whose guidance it has been
prepared, and who can be expected to exercise a duty of care to avoid unnecessary release of clean agent.
Specific requirements and advice on these matters can be obtained from the appropriate manufacturer of the
clean agent or the extinguishing system. Information may also be sought from the appropriate fire authority,
the health and safety authorities and insurers. In addition, reference should be made as necessary to other
statutory regulations.
It is essential that fire equipment be carefully maintained to ensure instant readiness when required. Routine
maintenance is liable to be overlooked or given insufficient attention by the owner of the system. The importance
of maintenance cannot be too highly emphasized.
For the purpose of deciding whether a particular requirement of this standard is complied with, the final
value, observed or calculated. expressing the result of a test or analysis, shall be rounded off in accordance
with IS 2 : 1960 ‘Rules for rounding off numerical values (revised)’. The number of significant places retained
in the rounded off value should be the same as that of the specified value in this standard.
1S 15493:2004
Indian Standard
GASEOUS FIRE EXTINGUISHING SYSTEMS —
GENERAL REQUIREMENTS
1 SCOPE responsible for approving installation or equipment
or a procedure.
This standard specifies provisions and
recommendations for general requirements, type of 3.4 Automatic — Performing a function without the
clean agent and their containers, container arrangement, necessity of human intervention.
distribution systems, such as piping, nozzles, pipe
supports, alarm system, type of enclosure etc. 3.5 Automatic/Manual Switch — A means of
converting the system from automatic to manual
NOTES ( manual override) and vice-versa.
1 This standard covers the general requirements
applicable to totai tlooding clean agent systems like 3.6 Class A Fires — Fire in ordinary combustible
Halo-Carbon agents and inert gas agents. In addition, materials, such as wood, cloth, paper, rubber, many
individual requirements for each type of clean agent plastics, electrical and electronic hazards without
system are covered un-der separate standards. Detailed
any flammable fiid or gas.
design guidelines are specitied, in other standards. Hence
before designing a protection with a particular clean
3.7 Class B Fires — Fire in flammable liquids,
agent, both the standards should be read together. Wherever
there is a difference, the individual standard takes
oils, greases, tars, oil-based paints, lacquers and
precedence, the like.
2 This standard prescribes minimum requirements for
3.8 Clean Agent — Electrically non-conducting,
total flooding clean agent tire/extinguishing systems.
Protection with carbon dioxide is not covered in this
vaporizing, or gaseous clean agent that does not
standard. leave a residue upon evaporation. The word agent
3 Nothing in this standard is intended to restrict new
wherever appearing in this document shall mean as
technologies or alternate arrangements provided the level clean agent.
of safety prescribed by this standard is not diluted.
3.9 Clearance — The air distance between clean
2 REFERENCES agent equipment, including piping and nozzles
and unenclosed or uninsulated live electrical
The standards listed in Annex A contain provisions
components at other than ground potential.
which through reference in this text, constitute
provisions of this standard. At the time of publication, 3.1O Containers — A cylinder or other vessels used
the editions indicated were valid. All standards are to store the clean agent.
subject to revision and the parties to agreements
based on this standard are encouraged to apply the 3.11 Container-Discharge Valve — A valve directly
most recent editions of the standards indicated connected to a container which when actuated
in Aflnex A. releases the clean agent into the distribution
piping.
3 TERMINOLOGY
3.12 Control Device — A device to control the sequence
For the purpose of this standard, the following of events leading to the release of clean agent.
definitions shall apply.
3.13 Concentration
3.1 Adjusted Minimum Design Quantity
( AMDQ ) — The minimum design quantity of agent 3.13.1 Design Concentration — The concentration
that has been adjusted in consideration of design ( including safety factor ) of the clean agent
factors. necessary to extinguish a fire of a particular fuel.
IS 15493:2004
3.13.4 Injected Concentration — The concentration extinguishing concentration surrounds the hazard.
of the agent necessary to develop under free efflux
3.24 Inert Gas Agent — A clean agent that contains
conditions the required design concentration.
as primary components one or more of the gases
3.13.5 Maximum Concentration — The concentration IGOI,IG55, IG100or !G541.
achieved from the actual clean agent quantity at the
3.25 Inerting — The prevention of reignition of
maximum ambient temperature.
a flammable or explosive atmosphere by establishing
3.13.6 Residual Oxygen Concentration — The a suitable concentration of the clean agent.
resulting concentration of oxygen achieved within
3.26 Liquefied Gas — A gas or gas mixture ( normally
a protected area after the discharge of agent into
a halocarbon ) which is liquid at the container
the area.
pressurization level at room temperature ( 20°C ).
3.14 Design Factor ( DF ) — A fraction of the agent
3.27 Lock-Off Valve — A mechanically operated
minimum design quantity ( MDQ ) added thereto
device which prevents a clean agent from being
deemed appropriate due to a specific feature of the
discharged through distribution pipe work to the
protection application or design of the suppression
protected area.
system.
3.28 Lowest Observed Adverse Effect Level
3.15 Directional Valve — A device for controlling
( LOAEL ) — The lowest concentration of clean agent
the passage of the clean agent from a supply
at which an adverse toxicological or physiological
manifold and directed to pre-selected area(s) of
effect has been observed.
protection.
3.29 Manual — Requires a human intervention to
3.16 Discharge Inhibit Switch — A manually
accomplish a function or task.
operated switch that prevents the automatic discharge
of the clean agent. 3.30 Maximum Working Pre-ssure —Equilibrium
pressure within a cylinder at the maximum working
3.17 Distribution System — All the pipe work
temperature. For liquefied gases, this is at maximum
and fittings downstream of any container discharge
fill density and may include super-pressurization, if
valve.
applicable.
3.18 Engineered Systems — A system in which
3.31 Minimum Design Quantity ( MDQ ) — The
the supply of the clean agent stored centrally is
quantity of agent required to achieve the calculated
discharged through a system of pipe and nozzles in
minimum design concentration.
which the size of each section of pipe and nozzle
orifice has been calculated in accordance with 3.32 Monitoring — The supervision of the operating
relevant clauses of ttiis standard. The design flow integrity of an electrical, mechanical, pneumatic or
rates from nozzles may vary according to the design hydraulic control feature of a system.
requirements of the hazard.
3.33 No Observed Adverse Effect Level
3.19 ‘Fill Density— The mass of gaseous agent per ( NOAEL ) — The highest concentration of a clean
unit volume of container ( kg/m3 ). agent at which no adverse toxicological or
physiological effect has been observed.
3.20 Final Design Quantity ( FDQ ) —A quantity
of agent determined from the agent minimum 3.34 Non-liquefied Gas — Gas or gas mixture
design quantity as adjusted to account for design which, under reserve pressure and allowable
factors and pressure adjustment. reserve temperature conditions, is always present
3.21 Flooding Quantity — Mass or volume of clean in a gaseous form.
agent required to achieve the design concentration 3.35 Normally Occupied Area — An area where,
within the protected volume within the specified under normal circumstances, humans are present.
discharge time.
3.36 Normally Unoccupied Area — Area not
3.22 Gross Volume — The volume enclosed by occupied by people but may be occasionally
the building elements around the protected entered for brief periods.
enclosure, less the volume of any permanent
impermeable building elements within the 3.37 Nominal Size — A numerical designation .of
enclosure. size which is common to all components in a piping
system other than components designated by
3.23 Holding Time — Period of time during which a outside diameters or by thread size. It is a convenient
concentration of clean agent greater than the fire round number for reference purposes and is only
2
IS 15493:2004
3.39 Pre-engineered Systems — Those having 4.1.1 Extinguishing gases are thr.ee-dirnensional
pre-determined flow rates. nozzle pressures and agents that are used effectively to suppress fire
quantities of clean agent. These systems have the through physical or chemical action. Separate
specific pipe size, maximum and minimum pipe properties of specific gases are provided in other
lengths, flexible hose specifications, number of parts of this standard.
titt~ngs and number and types of nozzles prescribed
4.1.2 Gaseous total flooding systems may be used
by a testing laboratory.
to suppress fires of Classes A and B type as defined
3.40 Primary Release — Release of clean agent in 3.6 and 3.7. However, for suppressing fires where
initiated by detection system or manual operation flammable gases may be present, the possibility of
under normal operating conditions. explosion, during and after system discharge should
be considered.
3.41 Release — The opening of the cylinder and
directional valves leading to the physical discharge 4.1.3 Clean agent gas extinguishing systems are
or emission of clean agent into the enclosure. useful within the Iimits. of this standard in
extinguishing fires in specific hazards or equipment
3.42 Safety Factor ( SF ) — A multiplier of the and in occupancies where “an electrically non-
agent flame extinguishing or inerting conductive medium is essential or desirable, or where
concentration to determine the agent minimum clean-up of other media poses a problem.
design concentration.
4.1.4 Where clean agent gas extinguish& systems
3.43 Safety Interlock — A switch that monitors the are used, a fixed enclosure shall be provided about
occupation of the protected area and automatically the hazard that is adequate to enable the specific
inhibits the discharge of the clean agent when the concentration to be achieved and maintained for the
area is occupied. =specified period of time.
3.44 Sea Level Equivalent of Agent — The agent 4.1.5 The effects of agent decomposition on fire
concentration ( volume, percent ) at sea level for protection effectiveness shall be considered when
which the partial pressure of agent matches
using clean agents in hazards with high temperatures
the ambient partial pressure of agent at a given
( for example, furnaces and ovens, etc ).
altitude.
4.1.6 The design, installation, service and
3.45 Sea Level Equivalent of”Oxygen — The oxygen
maintenance of the gas extinguishing systems
concentration ( volume, percent ) at sea level for
shall be performed by those competent in the
which the partial pressure of oxygen matches the
respective field in accordance with IS 15496:2004.
ambient partial pressure of oxygen at a given
altitude. 4.1.7 The installer of the clean agent system shall
be certified by a reputed national/international
3.46 Secondary Release ( Slave) —A release that
agency/laboratory and sLIch certification shall be
is a consequence and dependent on the operation
valid at the time of installation.
of the primary release, for example, pneumatic
connection. 4.2 Suitability and Application
b) For enclosed electrical hazards, such as means other than the tire.
transformers, control cubicles, switch boards,
4.3.2 Electrostatic charging of non-grounded
circuit breakers, and rotating equipment;
conductors may occur during the discharge of
c) Forenclosed flammable liquid/gas storage gaseous fire extinguishing systems. These
and processing areas; conductors may discharge to other objects causing
d) For engines using tlammable fuels; an electric arc of sufficient charge to initiate explosion
e) For electronic hazards, such as computers, in potentially explosive atmospheres.
data processing equipment, control room, 4.4 Other Information
telecommunication facilities;
4.4.1 All devices in respect of the gaseous fire
t) Sub-floors and other concealed spaces; and
extinguishing systems shall be designed for the
g) Other high value assets. service they will encounter and shall not be readily
4.2.2 Some of the gaseous fire extinguishing rendered inoperative or susceptible to accidental
systems may also be used for explosion prevention operation. Normally, the system components shall be
and suppression where flammable materials may designed to function properly from – 210 to 55°C
collect in confined area. or marked to indicate temperature limitations in
accordance with the specifications.
4.3 Limitations
4.4.2 Gaseous fire extinguishing systems may be
4.3.1 Gaseous fire extinguishing systems shall employed to protect more than one enclosure, if
not be used on tires involving the following materials necessary, by means of directional valves. Where
unless they are pre-evaluated for the purpose: there are two or more enclosures simultaneously
a) Certain chemicals or mixture of chemicals, involved in a fire by reason of their proximity, such
such as cellulose nitrate, gun powder, which enclosures shall be protected by individual
are capable of rapid oxidation in the absence systems designed to allow simultaneous operation,
of air; or a single system sized and arranged to discharge
b) Reactive metals, such as lithium, sodium, on all potentially involved hazards simultaneously.
potassium, magnesium, titanium, zirconium, 4.4.3 Systems employing simultaneous discharge
and plutonium; of different agents to protect the same enclosure
c) Metal hydrides or metal amides, some of which shall not be permitted.
may react violently with some gaseous
agents; 4.5 Applicability of Clean Agents
d) Chemicals capable of undergoing auto- 4.5.1 The fire extinguishing clean agents addressed
thermal decomposition, such as certain in the standard are electrically non-conducting and
organic peroxides and hydrazine or; leave no residue upon evaporation.
e) Mixtures containing oxidizing materials, such 4.5.2 Tables I and IA show the details of clean
as sodium chlorate or sodium nitrate; and agents that are covered in this standard. While
f) Environments where significant surface requirements that are common to all these agents
areas exist at temperatures greater than are prescribed in this standard, individual
the breakdown temperature of the requirements for each agent are covered under
extinguishing agent and are heated by separate standards.
Table 1 Halocarbon Agents
( Clause 4.5.2 )
4
IS 15493:2004
4.5.3 As such, both these standards, that is, for details of the contents, such as volume,
general and individual requirements should be read pressure, nominal capacity in agent mass at
together before designing a system. Where standard conditions of temperatures and
requirements in both the standards differ, standard pressures;
covering individual requirements shall take of pipes and fittings
precedence.
j) Descriptions
indicating also their specifications, pressure
5 REQUIREMENTS REGARDING SUBM1SS1ON ratings, etc;
OF PLANS k) Descriptions of nozzles employed
indicating their size, orifice area, type,
Plans shall contain sufficient details to enable an angle, etc, and their locations;
evaluation of the protected enclosure(s) or local
protection(s) vis-a-vis the effectiveness of the m) Electrical cabling and terminations;
system. Details shall include the property involved n) Descriptions of detectors employed
in the hazard(s), location(s), the enclosure limits indicating their locations, mounting, etc;
and isolation of the hazards and the exposure of the Bill of material and equipment schedule for
P)
hazards. each component proposed for the syste]n.
5.1 Plans for submission to the authorities shall Suppliers/manufacturer-s names, details of
be drawn up in accordance with the following approvals, quantity, etc;
requirements: 0 Isometric drawings showing the agent
distribution system indicating the lengths
a) Plans for integrity of fittings shall be clear,
and diameters of each pipe segment, nodal
contain all required details including
reference, fittings including unions, reducers,
scale and point of compass and shall be clearly
orifices, strainers, nozzles, flow rates in all
dated;
segments, equivalent orifice areas, etc;
b) Name of the enterprise, location and
r) Plan view of the enclosures showing the
detailed postal address;
entire agent piping system along with
c) Location and construction of the protected ceiling, floors, false floors, walls, partitions,
enclosures, walls and partitions; pipe supports, agent containers, cabling,
d) Cross and longitudinal sectional elevations panels, detectors, etc;
of the protection enclosures showing the s) Details showing the pipe supports, agent
full height, schematic diagram, ceilings, false container securement, etc;
floors, etc;
t) Location of ducts and similar devices,
e) Type of clean agent proposed to be used; dampers, air handling systems, venting
f) Concentration summary, that is, design, arrangements and their details with
extinguishing, injected and inerting, etc: supporting calculations, etc;
5
IS 15493:2004
and layout of all the power and indicating In areas, where there is a likelihood of significant
equipment connections, control panels, difference between gross and net volumes of the
annunciate panels, etc; enclosure, utmost care shall be exercised in pnoper
w) Tables showing the calculations for enclosure system design to ensure that maximum concentrations
volumes, agent quantity, methods used to are not exceeded.
determine number and location of audible
6.1.1 Safety Precautions (for Protected Areas )
and visual indicating equipment, number and
location of detectors, etc; and a) Normally occupied area — The minimum
Y) Other features like interconnection with safety precautions taken shall be in
other type of fire protection systems, etc, with accordance with Table 2A and provisions
the proposed system. therein, and
b) Normally unoccupied areas — The maximum
5.2 The details of the system shall include
concentration shall not exceed the LOAEL
information and calculations on the amount of agent;
for the agent used unless a lock-off valve is
container storage pressure; internal volume of the
fitted.
containers; the location, type and flow rate of each
nozzle including equivalent orifice area; the location, Warning — Any change to the enclosure
size and equivalent lengths of pipe, fittings, siphon volume, or addition or removal of contents
tube, valve, discharge head and flexible connector that was not covered in the original design
hose; and the location and size of the storage facility. will affect the concentration of agent. In such
Pipe size reductions and orientation of tees shall be instances the system shall be re-calculated
clearly indicated. Details shall be available on location to ensure that the required design
and function of the detection devices, operating concentration is achieved and that the NOAEL
devices, auxiliary equipment and electrical circuitry. or the LOAEL are not exceeded.
All the apparatus, equipment used in the system shall
be easily identifiable. 6.1.2 For unoccupiable areas, the maximum
concentration may “exceed the LOAEL for the
5.3 An as-built drawing shall be submitted upon extinguishant used, without the need for a lock-
completion of the installation for approval. Instruction off valve to be fitted.
and maintenance manuals that include a full
sequence of operations and a full set of drawings and 6.1.3 Protection of Occupants
calculations shall be available on site.
In any use of the gaseous system, where there is a
5.4 Flow Calculations possibility that people may enter or have difficulty
seeking egress from the protected enclosure, suitable
System flow calculations along with the working safeguards shall be provided. Such safety aspects
drawings shall be submitted to the authorities in as personal training, warning signs, pre-discharge
advance for approval. The hydraulic calculations
alarms and safety interlocks shall be provided. Means
shall be performed using calculation method approved of proper ventilation after fire should be readily
by the authorities. available.
6 SAFETY REQUIREM-ENTS
6.2 Safety Precautions ( Total Flooding Systems)
6.1 Safety Precautions ( for Personnel)
6.2.1 In areas protected by total flooding systems,
The discharge of some of the gas agents in fire that are capable of being occupied, the provision of
extinguishing concentrations creates serious hazards the following safety aspects shall apply:
for personnel in both the protected area and the areas
to which the gas may migrate and also to properties a) Mandatory requirements:
in the vicinity of agent discharge. These hazards may 1) A time delay shall be provided for
include reduced visibility, suffocation and toxicity, evacuation prior to agent discharge.
during and afterthe discharge period. The relevant The agent discharge delay time shall be
information on the above is available in Annex B. based on an engineering assessment of
egress time for occupants in the area
The tox[city information on the gaseous fire agents
protected,
is given in Table 2. More details are specified in
other relevant standard. Where hazardous 2) Safety interlocks and lock-off valves
concentrations of agent may exist, Iock-offvalves shall shall be provided wherever required
be fitted to the system. as per Table 2.
6
1S 15493:2004
NOTE — The-purpose of the table is to avoid unnecessary exposure ot’occupants to the agent discharged, Factors such
as the time for egress and the risk to the occupants by the fire must be considered when determining the system discharge
time delay.
1)con~ntration levels above LOAEL are-not permitted in occupied areas and question of egress does not ark.
3) Exit routes which shall be kept clear at 8) Means of prompt ventilation of such areas
all times and the provision of after any discharge of agent. Forced draft
emergency lighting and adequate ventilation will often be necessary. Care
direction signs to minimize travel shall be taken to completely dissipate
distances, hazardous atmospheres and not just
4) Outward swinging self-closing doors move them to other locations, as agents
which can be opened from inside are generally heavier than air, and
including when locked from the outside, 9) instructions and drills of all personnel
5) Continuous visual and audible aIarms within or in the vicinity of protected
at entrances and designated exits until areas, including maintenance and
the protected area has been made safe, construction personnel who may be
brought into the area, to ensure their
6) Warning and instruction signs shall be
correct actions when the system operates.
arranged as per clause,
b) Recommendatory requirements:
m Pre-discharge alarms within such areas
that are distinctive from all other alarm 1) Adding an odour to the agent so that
signals and that will operate immediately the hazardous atmospheres are
upon detection of fire, recognizable,
7
IS 15493:2004
10
IS 15493:2004
1) The normal charging pressure in the values shown in the tables are used with prior
agent container at21°C. acceptance of the -authorities, the minimum design
2) 80 percent of the maximum pressure in pressure for the piping -shall be adjusted to the
the agent container at the maximum maximum pressure in the agent container at
storage temperature of not less than maximum temperature, using the basic design
55°C using the maximum allowable fill criteria specified in items C(1) and c(2) above.
density specified by the manufacturer, 8.2,3 Pipe Fittings
inapplicable.
a) The sizes and dimensions of pipe fittings
d) Pipe joints shall be either threaded, welded
shall be in accordance with 1S 1239 ( Part 2 ).
or flanged type only and other types of
Fittings shall be capable to withstand
jointing shall not be allowed.
minimum rated working pressure equal to or
In no case shall the value used, for the minimum greater than the minimum working
piping design pressure, be less than that specified in pressure specified in 8.2.2.1 (c) for the clean
Tables 6 and 7 for the conditions shown. agent being used. For systems that use a
pressure reducing device in the distribution
For halocarbon agents Table 6 shall be used and for piping, the fittings downstream the device
inert gas agents Table 7 shall be used. shall have a minimum rated working
pressure equal to or greater than the
Where different fill densities, pressurization levels maximum anticipated pressure in the
or higher storage temperatures other than the downstream piping;
Table6 Minimum Design Working Pressure for Halocarbon Clean Agent System Piping
( Clause 8.2.2.1)
S1 No. Clean Agent Agent Container Agent Container Agent Container Minimum
Maximum Fill Charging Charging Piping Design
Density Pressure Pressure Pressure
kg/m2 at 21OC at 55°C at 21°C
kPa kPa kPa
(1) (2) (3) (4) (5) (6)
i) HFC-227ea 992 1 0341) 1 703 1 365
1 152 2 482]) 3585 2868
1 120 4 1371) 4950 3958
ii) HCFCBlendA 900 4 1371) 5860 4689
900 2 4821) 3723 2979
I)SuPer.Pressurized with nitrogen.
Table 7 Minimum Design Working Pressure for Inert Gas Clean Agent System Piping
( Clause 8.2.2.1)
S1 No. Clean Agent Agent Container Agent Container Minimum Design Pressure at 21°C
Charging Pressure Charging Pressure r >
Piping Upstream Piping
at 21°C at 55°C of Pressure Downstream
kPa kPa Reducer of Pressure
kPa Reducer
kPa
(1) (2) (3) (4) (5) (6)
i) IG-O I 16341 18271 16341 6723
20424 22778 14997 6728
ii) IG-541 14997 17755 14997 6895
19996 23671 19996 6895
iii) IG-55 15521 17065 15318 6550
20424 22753 20424 6550
30636 34 130 30633 6550
iv) IG-100 16580 19300 16580 6895
22311 26014 22311 6895
11
IS 15493:2004
b) Cast iron fittings shall not be used All nozzles shall be such that:
threads used in joints and fittings shall 1) The design concentration shall be
comply with relevant Indian Standards; achieved in all parts of the enclosure;
c) Welding ofjoints shall comply with relevant 2) The discharge shall not unduly splash
Indian Standards; and. flammable liquids or create dust clouds
d) Where copper, stainless steel, or other that might extend the fire, create an
suitable tubing is jointed with compression explosion or otherwise adversely affect
type fittings, manufacturers pressure and the occupants;
temperature ratings of the fittings shall 3) The velocity of discharge shall not
not be exceeded. adversely affect the enclosure or its
contents;
8.2.4 Pipe Installation and Supports
4) The discharge nozzles shall be provided
a) In the installation of pipe work, care shall be with frangible discs or blow-out caps
taken to avoid possible restrictions due to where clogging by foreign materials is
foreign matter, faulty fabrication or improper possible. These devices shall provide
installation. Pipe ends shall be reamed after an unobstructed opening upon system
cutting, where required; operation and shall be arranged so they
b) Where there is a possibility of explosions, will not injure personnel;
the piping shall be attached to supports that 5) .Nozzle shall be suitable for the
are least likely to be displaced; and intended use and shall be approved for
c) The maximum distance between supports shall discharge characteristics. The discharge
take into account the total mass of pipe and nozzle consists of the orifice and any
the agent used. Distance between supports associated horn, shield or baffle;
is indicated in Table 8.
6) Nozzles shall be of adequate strength
Table 8 Maximum Pipe Work Distances for use”with the expected working
pressures, be able to resist nominal
[ Clause 8.2.4(c)]
mechanical abuse, and be constructed
Nominal Diameter Maximum Pipe
to withstand expected temperatures
S1 No.
of Pipe Work Distance without deformation; and
mm mm Nozzle discharge orifice inserts shall
(1) (2) (3) be ofcorrosion-resistant material.
i) 6 0.5 c) In order to minimize the possibility of
ii) 10 1 lifting or displacement of lightweight
iii) 15 1.5 ceiling tiles, precautions shall be taken to
iv) 20 1.s securely anchor the tiles for a minimum
25 2.1
distance of 1.5 m from each discharge nozzle.
v)
vi) 32 2.4 9 DETECTION, ACTUATION, ALARM AND
vii) 40 2.7 CONTROL SYSTEMS
viii) 50 3.4 9.1 General
ix) 65 3.5
9.1.1 Detection, actuation, alarm and control
x) 80 3.7
systems shall be installed, tested and maintained
xi) 100 4.3
in accordance with 1S2189.
xii) 125 4.8
xiii) 150 5.2
9.1.2 Automatic detection and automatic actuation
shall be used.
xiv) 200 5.8
9.2 Automatic Detection
8.2.5 Discharge Nozzles
9.2.1 Automatic detection shall be by any
a) Nozzles, including nozzles directly approved method or device capable of detecting
attached to containers, shall be of approved and indicating heat, flame, smoke, combustible
type and located with the geometry of the vapours or any abnormal condition in the hazard,
enclosure under consideration. such as process trouble, that is likely to produce
b) The type, number and placement of fiie.
12
1S 15493:2004
9.2.2 Adequate and reliable primary and 24 h control for activation shal I be located not more than
minimum standby sources of energy shall be used to 1.2 m above the floor.
provide for operation of the detection, signaling,
9.3.8 Where gas pressure from the system or pilot
control and actuation requirements of the system,
containers is used as a means for releasing the
9.2.3 When a new agent system is being installed remaining containers, the supply and discharge
in a space that has an existing detection system, an rate shall be designed for releasing all of the
analysis shall be made of the detection devices to remaining containers.
assure that the detection system is in good
9.3.9 All devices for shutting down supplementary
operating condition and will respond promptly to a
fire situation. This analysis shall be done to assist equipment shall be considered integral part of the
in limiting the decomposition products from a system and shall function with the system
suppression event. operation.
switches shall be located within the protected area To determine that the system has been properly
and shall be located near the means of egress from installed and will function as specified, the tests
the area. An abort switch shall not be operated specified in 10.2.2 to 10.2.9 shall be performed.
unless the cause for the condition is known and
10.2 Review of Mechanical Components
corrective action can be taken. The abort switch
shall be of a type that requires constant manual 10.2.1 The piping distribution system shali be
pressure to cause abort. The abort switch shall not inspected to determine that it is in compliance with
be of a type that would allow the system to be left in the design and installation documents.
an aborted mode without someone present. In all
cases the normal and manual emergency control 10.2.2 Nozzles and pipe size and, if appropriate,
shall override the abort function. Operation of the pressure-reducing devices, shall be in accordance with
abort function shall result in both audible and distinct system drawings. The means for pipe size reduction
visual indication of system impairment. The abort and attitudes of tees shall be checked for conformance
switch shall be clearly recognizable for the purpose to the design.
1
intended.
10.2,3 Piping joints, discharge nozzles and piping
9.5.4 Alarms indicating failure of supervised supports shall be securely fastened to prevent
devices or equipment shall give prompt and positive unacceptable vertical or lateral movement during
indication of any failure and shall be distinctive discharge. Discharge nozzles shall be installed in such
from alarms indicating operation or hazardous a manner that piping cannot become detached
conditions. during discharge.
9.5.5 Warning and instruction signs at entrances to 10.2.4 During assembly, the piping distribution
and inside protected areas shall be provided. system shall be inspected internally to detect the
possibility of any oil or particulate matter which
9.5.6 Indication lamps shall be provided to indicate could soil the hazard area or affect the agent
the status of the abort switch, that is, Green colour distribution due to a reduction in the effective
for ‘Auto’, Yellow colour for the ‘Manual’ and Red nozzle orifice area.
colour for ‘Discharge’ modes.
10.2.5 The discharge nozzles shall be oriented in
9.6 Time Delays such a manner that optimum agent dispersal can be
9.6.1 For clean agent extinguishing systems, a effected.
pre-discharge alarm and time delay, sufficient to 10.2.6 [f nozzle deflectors are installed, they shall
allow personn-el evacuation prior to discharge, shall be positioned to obtain the maximum benefit.
be provided. For hazard areas subject to fast
growth fires, where the provision of a time delay 10.2.7 The discharge nozzles, piping and mounting
would seriously increase the threat to life and brackets shall be installed in such a manner that they
property, a time delay shall be permitted to be will not potentially cause injury to personnel, Agent
eliminated. shall not directly impinge on areas where personnel
may be found in the normal work area, or on any loose
9.6.2 Time delays shall be used only for personnel objects or shelves, cabinet tops, or similar surfaces
evacuation or to prepare the hazard area for where loose objects could be present and become
discharge. -:”.:1-.
Illlssllcs.
9.6.3 Time delays shall not be used as a means of 10.2,8 All agent storage containers shall be properly
confirming operation of a detection device before located in accordance with ‘approved for construction’
automatic actuation occurs. set of system drawings.
10 COMMISSIONING AND ACCEPTANCE 10.2.9 All containers and mounting brackets shall
The minimum requirements for the commissioning and be securely fastened in accordance with the
acceptance of the gaseous extinguishing system shall manufacturer’s requirements.
be as follows. 10.2.10 An adequate quantity of agent to produce
10.1 General the desired specified concentration shall be
provided. The actual enclosure volumes shall be
The completed system shall be reviewed and tested checked against those indicated on the system
by a competent person to meet the approval of the drawings to ensure the proper quantity of agent. Fan
authority. Only equipment and devices designed rundown and damper closure time shall be taken into
to national standards shall be used in the systems. consideration.
14
IS 15493:2004
10.2.11 Unless the total piping contains not signaling, control and actuation requirements of the
more than one change in direction fitting between the system.
storage container and the discharge nozzle, and
10.3.4 All auxiliary functions ( such as alarm
unless all piping has been physically checked for
sounding or displaying devices, remote annunciators,
tightness, the following tests shall be carried out:
air handling shutdown, power shutdown, etc ) shall
a) All open ended piping shall be pneumatically be checked for proper operation in accordance with
tested in a closed circuit for a period of 10 system requirements and design specifications.
min at 3 bar. At the end of 10 rein, the pressure
Alarm devices shall be installed so that they are
drop shall not exceed 20 percent of the test
audible and visible under normal operating and
pressure, and
environmental conditions.
b) All closed-section pipe work shall be
hydrostatically tested ‘to a minimum of Where possible, all air handling and power cut-off
1.5 times the maximum working pressure for controls should be of the type that once interrupted
2 min during which there shall be no require manual restart to restore power.
leakage. On completion of the test, the pipe
10.3.5 Check that for systems using alarm silencing,
work shall b~purged to remove moisture.
this function does not affect other auxiliary functions,
It is recommended that hydrostatic testing be carried such as air handling or power cut-off where they are
out at the manufacturer’s works where practicable. required in the design specification.
WARNING — Pneumatic pressure testing creates 10.3.6 Check the detection devices to ensure that
a potential risk of injury to personnel in the area, the types and locations are as specified in the
as a result of airborne projectiles if rupture of the system drawings and are in accordance with the
piping system occurs. Prior to conducting the manufacturer’s requirements.
pneumatic pressure test, the protected area shall
10.3.7 Check that manual release devices are
be evacuated and appropriate safeguards shall
properly installed, and are readily accessible,
be provided for test personnel.
accurately identified and properly protected to
10.2.12 A test using nitrogen, or a suitable prevent damage.
alternative, shall be performed on the piping
10.3.8 Check that manual release devices used to
network to verify that flow is continuous and that the
release agents require two separate and distinct
piping and nozzles are unobstructed.
actions for operation. They shall be properly
10.2.13 Where required, suitable venting facilities identified. Particular care shall be taken where
shall be provided for the release of excessive pressure manual release devices for more than one system are
build-up during discharge of the agent. Individual in close proximity and could be confused or the
standards for gaseous agents provide details for the wrong system actuated. Manual release devices in
design of venting facilities. this instance shall be clearly identified as to -which
hazard enclosure they protect.
10.3 Review of Electrical Components
10.3.9 Check that for systems with a main/reserve
10.3.1 All wiring systems shall be properly installed capability, the main/reserve switch is properly
in compliance with the appropriate National installed, readily accessible and clearly identified.
Standard and the system drawings..a,c. and d.c. wiring
shall not be combined in a common conduit unless 10.3.10 Check that for systems using inhibit
properly shielded and grounded. switches requiring constant manual force, these are
properly installed, readily accessible within the
10.3.2 All field circuitry shall be tested for ground hazard area and clearly identified.
fault and short circuit condition. When testing field
circuitry, all electronic components ( such as smoke 10.3.11 Check that the control panel is properly installed
and flame detectors or special electronic equipment and readily accessible.
for other detectors, or their mounting bases ) shall 10.4 Preliminary Functional Tests
be removed and jumpers properly installed to prevent
the possibility of damage within these devices. Replace 10.4.1 Where a system is connected to a remote
components after testing the circuits. central alarm station, notify the station that the fire
system test is to be conducted and that an
10.3.3 Adequate and reliable primary standby emergency response by the fire departmen(or alarm
sources of energy which comply with 9.2.2 shall be station personnel is not required. Notify all concerned
used to provide for operation of the detection, personnel at the end-user’s facility that a test is to
15
IS 15493:2004
be conducted and instruct them as to the sequence 10.6.2 Operate each type of alarm condition and
of operation. verify receipt of fault condition at the remote
station.
10.4.2 Disable or remove each agent storage
container release mechanism and selector valve, 10.7 Control Panel Primary Power Source
where fitted, so that activation of the release circuit
will not release agent. Reconnect-the release circuit 10.7.1 Verify that the control panel is connected to a
with a functional device in lieu of each agent storage dedicated unstitched circuit and is labelled properly.
container release mechanism. This panel shall be readily accessible but access shall
be restricted to authorized personnel only.
For electrically actuated release mechanisms, these
devices may include suitable lamps, flash bulbs or 10.7.2 Test a primary power failure in accordance
circuit breakers. Pneumatically actuated release with the manufacturer’s specification, with the system
mechanisms may include pressure gauges, Refer to fully operated on standby power.
the manufacturer’s recommendations in all cases.
10.8 Review ofEnclosure-integrity
10.4.3 Check each resetable detector for proper
It is preferable to subject all total flooding systems
response.
to an Enclosure Integrity ~est in order to detect
10.4.4 Check that polarity has been observed on all and seal the significant leakage paths that could
polarized alarm devices and auxiliary relays. result in-failure of an enclosure to withhold design
concentration for a specified period ( see 7,1
10.4.5 Check that all required end-or-line devices and 10.10 ).
have been installed.
10.9 Completion of Functional Tests
10.4.6 Check all supervised circuits for correct fault
response. When all functional tests are complete ( see ‘10.6
to 10.9 ), reconnect each storage container so that
10.5 System Functional Operational Test activation of the release circuit will release the agent.
Return the system to its fully operational design
10.5.1 Operate the detection initiating circuit(s).
condition. Notify the central alarm station and all
All alarm functions shall occur according to the
concerned personnel at the end-user’s facility that
design specification.
the fire system test is complete and that the system
10.5.2 Operate the necessary circuit to initiate a has been returned to full service condition by following
second alarm circuit if present. Verify that all the procedures specified in the manufacturers’
second alarm functions occur according to design specifications.
specifications.
10.10 The complete installation shall be tested in
10.5.3 Operate the manual release device. Verify one of the two methods narrated below:
that manual release functions occur according to
a) Full-scale discharge test, and
design specifications.
b) Enclosure integrity test.
10.5.4 Where appropriate, operate the inhibit
switch. Verify that functions occur according to the Where the authorities concerned insist on
design specifications. Confirm that visual and full-scale discharge test, the test shall be
audible supervisory signals are received at the control conducted in accordance with various provisions
panel. under Annex C and results of the test ( that is
concentration achieve-d, discharge time, holding
10.5.5 Check the function of all resettable valves time ) shall conform to various provisions available
and activators, unless testing the valve will rele~se in other clean agent standards with particular
agent. ‘one-shot’ valves, such as those incorporating reference to the agent used. Otherwise, the enclosure
frangible discs, should not be tested, where total flooding system is installed, shall be
10.6 Remote Monitoring Operations ( If subject to’ enclosure integrity test’ in accordance with
Applicable ) various provisions under Annex D to demonstrate
the retention time ( of the required concentration
10.6.1 Disconnect the primary power supply, then with the-enclosure ] as specified in other standards
operate one of each type of input device while on with particular reference to the agent used.
standby power. Verify that an alarm signal is received
at the remote panel after the device is operated. 10.11 Completion Certificate and Documentation
Reconnect the primary power supply. The installer shall provide to the user a completion
16
IS 15493:2004
certificate, a complete set of instructions, calculations NOTE — These equations use friction factors and
and drawings showing the system as-installed, and constants dependent on pressure and density
obtained empirically. As the equations cannot be solved
a statement that the system complies with all the
directly, a cornputcr programme is usually used to
appropriate requirements of this standard, and giving assist with the large number of iterative calculations
details of any departure from appropriate in which pipe and nozzle sizes and if appropriate,
recommendations. The certificate shall give the design size of pressure reducing devices, are selected within
concentrations and, if carried out, reports of any prescribedpressurelosses.
additional test including the door fan test. 11.5 Valves and Fitting
11 SYSTEM HYDRAULIC FLOW Valves and fittings shall be rated for resistance
CALCULATIONS coefficient or equivalent length in terms of pipe,
11.1 General or tubing sizes with which they will be used.
The equivalent length of the cylinder valves
System flow calculations shall be carried out at a shall be listed and shall include siphon tube ( where
nolninal agent storage temperature of 21 “C, shall fitted ), valve, discharge head and flexible
have been validated by an accredited approval connector.
authority by appropriate tests as described in this
standard, and shall be properly identified. The 11.6 Piping Length
system design shall be within the manufacturer’s The piping length and nozzle and fitting orientation
specified limitations. shall be in accordance with the manufacturer’s
NOTES approved manual to ensure proper system
1 Variations from the nominal 21 “C storage performance.
temperature will affect flow conditions used in
calculations.
11.7 Drawings
2 Prc-engineered systems do not require a flow If the final installation varies from the prepared
calculation when used within approved drawings and calculations new ‘as- built’ drawings
limitations.
and calculations shall be prepared.
11.2 Balanced and Unbalanced System
11.8 Liquefied Gases ( Specific Requirements)
11.2.1 A balanced system shall be one in which:
11.8.1 Allowance shall be made for changes in
a) each actual or equivalent pipe length from elevation as specified in the relevant standard
the container to each nozzle are all within 10 relating to the specific agent.
percent of each other, and
11.8.2 Minimum discharge rate for liquefied agents
b) the discharge rate of each nozzle is equal. shall be sufficient to maintain the velocity required
for turbulent flow to prevent separation.
11.2.2 Any system that does not meet the criteria
mentioned in 11.2 shall be considered to be an NOTE— 11’turbuleat flow is not maintained, separation
unbalanced system. of the liquid and-gaseous phases will occur, which can
lead to unpredictable tlow characteristics.
11.3 Friction Losses
11.8.3 For information on two-phase flow for liquefied
Allowance shall be made for the friction halocarbon gases ( see Annex E ).
losses in pipes and in container valves, dip tubes,
flexible connectors, selector valves, time delay 12 ENGINEERED AND PRE-ENGINEERED
devices and other equipment ( for example, pressure- SYSTEM
reducing devices ) within the flow line. 12.1 General
NOTE — The flow of a liquefied gas will be a two
All agents are suitable for use in both engineered
phase phenomenon, the fluid consisting of a mixture
of liquid and vapour, the proportions of which are central storage, system and pre-engineered
dependent on pressure and temperature. The pressure ( modular or packaged ) systems, as described
drop is non-linear, with an increasing rate of pressure in 12.2 and 12.3.
loss as the line pressure reduces by pipe friction.
12.2 Engineered
11.4 Pressure Drop
An engineered system uses large storage
The pressure drop shall be calculated using two phase containers installed in central location. The
flow equations for liquefied gases and single phase containers are manifold together and a single
Now-equations for non-liquefied gases. pipe feeds the nozzle located inside the
17
IS 1-5493:2004
18
IS 15493:2004
ANNEX A
( Clause 2 )
LIST OF REFERRED INDIAN STANDARDS
19
ANNEX B
(Clause 6.1 )
INFORMATION ON SAFETY TO PERSONNEL AND DECOMPOSITION PRODUCTS
OF COMBUSTION
II-l Any hazard to personnel created by the that the vapour must decompose before the agent
discharge of gaseous extinguishants shall be can inhibit the combustion reaction. Decomposition
considered in the design of the system, in particular takes place on exposure to a flame or to a hot surface
with reference to the hazards associated with at a temperature above 480°.C. In the presence of
particular extinguishants in the other standards of available hydrogen ( from water vapour or the
clean agents. Unnecessary exposure to all gaseous combustion process itself), the main decomposition
extinguishants shall be avoided. product is hydrogen fluoride ( HF ).
B-2 The decomposition products generated by tbe B-6 The decomposition products .of halocarb.on
clean agent breaking down in the presence of very agents have a characteristic sharp acrid adour, even
high amounts of heat can be hazardous. All of the in minute concentrations of only a few parts per
present halocarbon agents contain fluorine. In the million. This characteristic provides abuilt-in warning
presence of available hydrogen ( from water vapour, system for the extinguishant, but at the same time
or the combustion process itself ), the main creates a noxious, irritating atmosphere for those who
decomposition product is hydrogen fluoride ( HF ). have to enter the enclosure following a fire. The actual
concentration of the decomposition products
B-3 These decomposition products have a sharp,
depends on the volume of the enclosure in which
acrid odour, even in minute concentrations of only a fire is burning and the degree of mixing and
few parts per million. This characteristic provides a
ventilation.
built-in warning system for the agent, but at the same
time creates a noxious, irritating atmosphere for those B-7 Longer exposure of the vapour to tempera-
who must enter the hazard following a fire. tures in excess of 482°C would produce greater
concentrations of these gases. The type and sensi-
B-4 The amount of agent that can be expected to
tivity of detection, cwpled with the rate of discharge,
decompose in extinguishing a fire depends .to a
should be selected to minimize the exposure time of
large extent on the size of the fire, the particular
the vapours to the elevated temperature if the
clean agent, the concentration of the agent, and the
concentration of breakdown products is to be
length of time the agent is in contact with the
minimized. In most cases, the area would be untenable
flame or heated surface. If there is a very rapid
for human occupancy due to the heat and breakdown
build-up of concentration to the critical value, then
products of the fire itself.
the fire will be extinguished quickly and the
decomposition will be limited to the minimum B-8 Clearly, longer exposure of the agent to high
possible with that agent. Should that agent’s temperatures would produce greater concentrations
specific composition be such that it could of these gases. The type and sensitivity of detection,
generate large quantities of decomposition coupled with the rate of discharge, should be selected
products, and the time to achieve the critical value is to minimize the exposure time of the agent to the
lengthy, then the quantity of decomposition elevated temperature if the concentration of the
products can be quite great. The actual concentration breakdown products is to be minimized.
of the decomposition products then depends on
the volume of the room in which the fire was burning B-9 Non-liquefied agents do not decompose
and on the degree of mixing and ventilation. measurably in extinguishing a fire. As such, toxic or
corrosive decomposition products are not found.
B-5 Although the vapour from halocarbon gas has However, breakdown products of the fire like carbon
low toxicity, the decomposition products can be monoxide itself can still be substantial and could
very hazardous. The most widely accepted theory is make the area untenable for human occupancy.
20
IS 15493:2004
ANNEX C
(-Clause 10.10 )
REQUIREMENTS FOR FULL-SCALE DISCHARGE TEST
a) Ensure that the preliminary checks, in Restore all systems to a fully operational status.
accordance with respective standard
pertaining to gaseous fire extinguishing C-7 REPORTING
system have been completed, The following shall be reported:
b) Electrically isolate all flooding systems
serving adjacent enclosures, a) 1) installation, designer and contractor;
c) 1) Concentration measurements should 2) enclosure identification;
be made at a minimum of three points, 3) enclosure temperature prior to discharge;
one-at the highest hazard level, 4) design concentration; and
2) Locate sampling points in the enclosure 5) position of sampling points.
at the specified heights ( see 10 ). Do
not locate sampling points nearer than b) Date and time of test,
200 mm to ceiling unless the combustibles c) Discharge time,
being protected extend within that area, d) Concentraticms at each sampling point
in which case special design at I and 10 min from the commencement of
considerations may be necessary, discharge, and
3) If more than one space or compartment e) System deficiencies.
is being simultaneously protected,
locate a sampling point in each space in Cross-check various observed parameters with the
accordance with the above criteria. respective operating clauses are in conformity
Additional sampling points may be therewith.
21
1S 15493:2004
ANNEX D
( Clause 10.10)
REQUIREMENTS FOR TESTING ENCLOSURE INTEGRITY
D-1 TEST FOR DETERMINATION OF e) Two thermometers, to measure ambient
PREDICTED MINIMUM HOLD TIME temperatures, and
D-1.1 Principle o Signs, reading “DO NOT OPEN —
PRESSURE TEST IN PROGRESS” and
A fan is temporarily located within an access “DO NOT CLOSE — PRESSURE TEST IN
opening to pressurize and repressurize the enclosure, PROGRESS”.
A series of pressure and air flow measurements is
NOTE — Additional apparatus, such as measuring
made from which the leakage characteristics of the tapes, torches, ladders. tools to remove floor and ceiling
enclosure; are established. tiles, computer or other calculating device, may be
necessary.
The predicted hold time is calculated using
these leakage characteristics on the following D-1.3 Calibration of Apparatus
assumptions:
a) Fan Unit — Calibrate the fan unit at the
a) That leakage occurs under the worst intervals and by the method recommended
conditions, that is, when one-half of the by the manufacturer. Keep records and, where
effective leakage area is at the maximum appropriate, calibration certificates. Use a
enclosure height and represents the flow meter accurate to + 5 percent and a
inward leakage of air, and the other half ( the pressure-measuring device accurate to+ 1 Pa.
lower leakage area ) of the total effective b) Press ure-Measttring Devices — The
leakage area is at the lowest point in the pressure-measuring- devices shall be
enclosure and represents the outward calibrated not more than 12 months before
leakage afextinguishant/air, a test. Records shall be maintained and,
b) That all leak flow is one-dimensional, i.e. where appropriate, calibration certificates.
ignoring stream functions, If inclined manometers are used, change
c) That flow through any particular leak area the fluid not more than 3 mcrnths before the
is either into or out of the enclosure and test. Level and zero inclined manometers
either from or into an infinitely large space, before each test,
d) That the system is at sea-level, at a D-1.4 Preliminary Preparation
temperature of 20”C, and atmospheric
pressure of 1.013 bar absolute, and a) Obtain a description from the user of the
air-handling equipment and extinguishant-
e) An enclosure integrity test is deemed extraction systems in the enclosure,
successful when at least 80 percent of
the design concentration is available b) Check for the following:
within the enclosure at the expiry of 1) raised platform floors and false ceiling
10 min (see D-2.10). spaces;
A bias pressure as low as 0.5 Pa can affect the accuracy Air 1.202
of the test result. If the bias pressure has a numerical
value greater than 25 percent of fire extinguishant/ HCFC Blend A 3.84
air column pressure, then.the hold time is likely to be HFC-227ea 7.26
low and the enclosure may not hold the specified
extinguishant concentration. The source of the IG-541 1.41
excessive bias pressure should be identified and, if IG-55 1.41
possible, permanently reduced.
RA = density of air, in kg/m3;
10 the event of fluctuating bias pressures ( such as
R~ = density of agent, in kg/m3;
those created by wind effects), it may not be possible
to achieve the necessary correlation accuracy in the PM = agent/Air column pressure, in Pascal
fan test results. These fluctuating pressures may need (Pa);
to be eliminated before an accurate fan test can be G= gravitational acceleration, 9.81 m/s2;
carried out. HO = total height of the enclosure, in m;
d) Measurement of Leakage Rate H= minimum acceptable height in the
1) Measure the air temperature inside enclosure, in m;
the enclosure, Te, and measure the air A= area of the enclosure, in m2;
temperature outside the enclosure TO,at v“ volume of the enclosure, in m3;
several points. If the location of leaks
is not known, use the average value;
~= uncorrected agent/air mixture leakage
otherwise, use the average value rate, in m3/s;
weighed according to the known Q. = corrected agent/air mixture leakage rate,
location of the leaks. in ins/s;
2) Unseal the fan inlet or outlet and TL = temperature within the enclosure, in ‘C;
connect the fan flow pressure- measuring T~ = temperature outside the enclosure, in “C;
device.
ELA = equivalent leakage area, in m2;
3) Use the fan unit to repressurize the
K= discharge coefficient ( 0.61 to
enclosure to the maximum extent, but
I depending upon nature of leakage
by not more than 60 Pa. Allow the
openings );
enclosure differential pressure
measuring reading to stabilize ( which ILA = total leakage area, in m2;
may take up to 30s ) and record the value LLF = lower leak fraction;
( Pf+ Pb ) which will be negative. Repeat
ALL = area of lower leaks, in m2;
at not less than four more fan unit
c . agent concentration, in percent;
flow rates to give five readings more
24
,-
1S 15493:2004
D-2.3 The next step will be to determine the density (1-N) (C3)(LLF)(TLA)
of agent/air mixture ( R~ ):
where
RM= (RG)( c)+ (RA)(1OO-C)
100 100
kg/m3 (2G)(RM-RA)
C3= l/N
25
IS 15493:2004
ANNEX E
( Clause 11.8.3 )
1NFORMATION ON TWO-PHASE FLOW FOR LIQUEFIED HALOCARBON GASES
BIS is a statutory institution established under the Bureau of Indian Standards Act, 1986 to promote
harmonious development of the activities of standardization, marking and quality certification of goods and
attending to connected matters in the country.
Copyright
131Shas the copyright of all its publications. No part of these publications may be reproduced in any form
without the prior permission in writing of BIS. This does not preclude the free use, in the course of implementing
the standard, of necessary details, such as symbols and sizes, type or grade designations. Enquiries relating
to copyright be addressed to the Director (Publications), BIS.
Amendments are issued to standards as the need arises on the basis of comments. Standards are also reviewed
periodically; a standard along with amendments is reaffirmed when such review indicates that no changes are
needed; if the review indicates that changes are needed, it is taken up for revision. Users of Indian Standards
should ascertain that they are in possession of the latest amendments or edition by referring to the latest issue
of ‘BIS Catalogue’ and ‘Standards : Monthly Additions’.
This Indian Standard has been developed from Doc : No. CED22(7011 ).