Pressure Drop Data SD60 air performance testing is performed in accordance with AMCA Standard 500-D configuration 5.3 as illustrated be-
low. All data are corrected to standard air density of .075 lb/ft3 (1.201 kg/m3).
6D
Ruskin Company certifies that the SD60 shown
hereon is licensed to bear the AMCA Seal. 5D
The ratings shown are based on tests and
procedures performed in accordance with AMCA
Publication 511 and comply with the require-
ments of the AMCA Certified Ratings Program.
The AMCA Certified Ratings Seal applies to air
performance for the SD60.
4 (W) (H)
D=
3.14
AMCA Figure 5.3 was established to represent a fully ducted damper with straight duct upstream and downstream. With entrance and exit losses
minimized by this straight duct arrangement, this configuration has the lowest pressure drop of all three configurations.
For other damper sizes refer to Air Performance Data For All Smoke Dampers spec sheet.
1.0
0.9
0.8
0.7
0.6 48” x 12”
0.5
12” x 48”
0.4
0.3
24” x 24”
PRESSURE DROP - INCHES W.G.
0.2
0.1
.09
.08
36” x 36”
.07
.06
.05
.04
.03
.02
12” x 12”
.01
2 3 4 6 7 8 9 2 3 4 6 7 8 9
100 500 1000 5000 10000
Spec SD60-819/Replaces SD60-715 ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE OR OBLIGATION. Ruskin® September 2019