You are on page 1of 19

HIGH EFFICIENCY HEAT RECOVERY UNIT

DATA SHEET

HRC+
Decentralized high efficiency heat recovery unit
For commercial applications, schools, offices

Page1
HIGH EFFICIENCY HEAT RECOVERY UNIT
DATA SHEET

GENERAL CHARACTERISTICS

STRUCTURE FANS RECOVERY


High strength frame construction The unit is equipped with EC centrifugal fans Very high efficiency counter-flow cross-flow
self-supporting in sheet metal and internal With high efficiency brushless motor. polypropylene heat exchanger.
insulation in polyethylene.

FILTRATION BYPASS CHECK


Upstream of the recuperator are present The units are equipped with recuperator bypass, The unit provides for operation through
two filters with filtration class ePM1 which allow the function of fresh air input from Remote control and APP;
Removal can happen the outside when there are ideal conditions. Air quality, humidity and temperature sensor.
without the aid of any tools.

Page2
HIGH EFFICIENCY HEAT RECOVERY UNIT
DATA SHEET

CONSTRUCTION FEATURES
HRC is a ventilation unit complete with heat recovery unit dedicated to air exchange without wasting energy.
The unit is particularly suitable for single rooms where it is not possible to create ducted systems;

CHASSIS: Self-supporting sheet metal frame with polyethylene insulated interior;

HEAT EXCHANGER: High efficiency counter-current cross-flow polypropylene heat exchanger.


Low freezing temperatures and operation down to -25°C.
Very high exchange efficiency.

FANS: Brushless forward curved centrifugal fans with electronic motor and modulating control.
Very high efficiency and low noise levels.

FILTERS: 70% ePM1 filters with low pressure drop.


Easily extractable by removing the external lower panels;

FREE COOLING: Free cooling realized inside the unit with large air passage and damper with motorized actuator.

ELECTRICAL CABINET: Electrical panel complete with 4-speed fan management board, antifreeze, automatic bypass,
temperature probes, post-heating coil management and automatic dirty filter signalling.
Control panel on the machine for HV and V units, remote for H units, necessary for unit operation
with capacitive touch, integrated air quality and humidity temperature sensors;
for mounting on box 502-503 or on wall;
Wifi chip for management through remote APP;

EFFICIENCY: Thanks to the construction features and its components, it is able to achieve recovery efficiency
greater than 90%.
In the winter and summer seasons there is a considerable energy recovery of the fresh air
introduced into the environment.

Page3
HIGH EFFICIENCY HEAT RECOVERY UNIT
DATA SHEET

COMMAND FUNCTIONALITY
The composition of the three possible electronics of the unit and the functions of the various versions is defined below:

VERSION I
CARDS ON BOARD THE MACHINE

REMOTE PANEL WITH AIR QUALITY, HUMIDITY AND TEMPERATURE


REMOTE PANELCNV MODBUS CNV MODBUS REMOTE PANEL CNW WIFI REMOTE PANEL CNW WIFI REMOTE PANEL

EXTERNAL COMMANDS
ON OFF

Page4
HIGH EFFICIENCY HEAT RECOVERY UNIT
DATA SHEET

UNIT CONFIGURATION

-1- -2- -3-

HRC+ 60 H I
1) Defines the maximum range 2) Type of installation 3) Type of control
Models from: 600 m³/h and 1150 m³/H H: horizontal I: electronics I
HV: vertical sub-window
V: vertical

HORIZONTAL (H)

REAR VIEW FRONT VIEW

SUB-WINDOW VERTICAL (HV)

REAR VIEW FRONT VIEW

VERTICAL CABINET VERTICAL (V)

REAR VIEW FRONT VIEW

Page5
HIGH EFFICIENCY HEAT RECOVERY UNIT
DATA SHEET

HRC+ 60H / HV
GENERAL TECHNICAL DATA
Size 60 H/HV

Fans
Type of Fans Forward curved centrifugal fans - directly coupled electronic motor - 0/10 V signal
Number of fans No 2+1
Air flow V3/V2/V1 m³/h 620 / 355 / 165
Useful pressure Pa 15

Heat exchanger(Data referring to the UNI EN 13141-7 standard Internal temp. 20° - Internal humidity 28% - External temp. 7° - External humidity 72%)
Type of exchanger Counterflow plates – polypropylene material
Number of Exchangers No 2
Recovery efficiency EN13141-7 % 86.1
Recovery efficiency EN305 % 91.8

Filters
Type of filters Pleated filters
Filtration class ePM1 70

Acoustic data(Data referring to the UNI EN 3741 and UNI EN 3744 standards)
Sound power Lw
dB(A) 59
sent by the facility

Sound pressure at 3 m V1 dB(A) 41


Sound pressure at 3m V2 dB(A) 36
Sound pressure at 3m V3 dB(A 33

Electrical data
Supply voltage v 230 / 1 / 50Hz.
Current consumption TO 3.5
Max absorbed power w 340
Max absorbed power with
kW 1.34
electrical resistance
Current drawn with electrical
TO 7.8
resistance
Power consumption V3
With 15 pa pressure and clean 165
filters
Degree of protection IP X0

Page6
HIGH EFFICIENCY HEAT RECOVERY UNIT
DATA SHEET

DIMENSIONS AND FUNCTIONAL SPACES

HRC+ 60H HRC+ 60HV

Width A mm 1033 1033

Depth B mm 904 403

Height C mm 403 feet 904+50 pins

Diameter DN OR 200 200

Weight Kg 71 72

Condensation OR 20 20

Page7
HIGH EFFICIENCY HEAT RECOVERY UNIT
DATA SHEET

Specification item
High-flow heat recovery ventilation units for decentralized applications;Specific unit for ventilation in environments with ventilation and air
treatment needs, such as commercial environments, offices, schools and small tertiary sectors;
CONSTRUCTION FEATURES
self-supporting structure in galvanized sheet metal with internal insulation in polyethylene; Heat exchangers and counter-current cross-
flows with maximum tightness and no leakage of traditional heat exchangers;
Compact dimensions for simplified ceiling (H) or wall (HV) installation with front and bottom panels easily accessible for maintenance and
inspection.
Circular inlets for air ducts to the outside with grilles, installation template supplied;
Rapid filter inspection and drain for condensate evacuation;
Electrical panel with management cards and power cables and remote panel prepared; forward curved centrifugal fans with EC motors
with electronic flow control and low consumption ePm1 class filters with low pressure drop outside air and stale air
Electrical panel on the unit with microprocessor and dedicated regulation. Fan management, temperature display, timed dirty filter
management, freecooling management and antifreeze function;
Possibility of installation on board an electric pre-heating coil and hydronic post-heating coils for integration or replacement of existing
radiators.
Remote control panel with WIFI and APP or modbus RTU to be purchased separately

Product details
TO Supplier name or brand
b Model identifier HRC+ 60
c Declared typology UVNR

d Drive type installed Variable speed


AND Heat recovery system To recovery

f Thermal efficiency of heat recovery % 86.1


h Nominal flow rate Mc/s 0.172
W/
THE SPF int
(m3/s)
634
j Front speed m/s 1.19

k Nominal external pressure (Dps , ext) Pa 15

L Internal pressure drop (Dps , int) Pa 194


Internal pressure drop
m to components extraneous to ventilation (Dps, Pa /
int)
Static efficiency of the fans as per
No % 31
EU 327/2011

OR Maximum percentages declared for leakage % 2.5 exts / 2.9 ints

P Energy classification of filters F7/F7

Q Location and description of the signal related to the filter Displayed on control panel and unit manual

R Sound power level Lwa 55


St Disassembly instructions internet address

Page8
HIGH EFFICIENCY HEAT RECOVERY UNIT
DATA SHEET

HRC+ 120H / HV
GENERAL TECHNICAL DATA
Size 120H/HV

Fans
Type of Fans Forward curved centrifugal fans - directly coupled electronic motor - 0/10 V signal
Number of fans No 3+2
Air flow V3/V2/V1 m³/h 1150 / 750 / 255
Useful pressure Pa 15

Heat exchanger(Data referring to the UNI EN 13141-7 standard Internal temp. 20° - Internal humidity 28% - External temp. 7° - External humidity 72%)
Type of exchanger Counterflow plates – polypropylene material
Number of Exchangers No 2
Recovery efficiency EN13141-7 % 84.9
Recovery efficiency EN305 % 90.4

Filters
Type of filters Pleated filters
Filtration class ePM1 70

Acoustic data(Data referring to the UNI EN 3741 and UNI EN 3744 standards)
Sound power Lw
dB(A) 62
sent by the facility

Sound pressure at 3m V1 dB(A) 43


Sound pressure at 3m V2 dB(A) 37
Sound pressure at 3m V3 dB(A 34

Electrical data
Supply voltage v 230 / 1 / 50Hz.
Current consumption TO 4.8
Max absorbed power w 620
Max absorbed power with
kW 2.12
electrical resistance
Current drawn with electrical
TO 11.3
resistance
Power consumption V3
With 15pa pressure and clean 355
filters
Degree of protection IP X0

Page9
HIGH EFFICIENCY HEAT RECOVERY UNIT
DATA SHEET

DIMENSIONS AND FUNCTIONAL SPACES

HRC+ 120 H HRC+ 120 HV

Width A mm 1433 1433

Depth B mm 904 403

Height C mm 403 feet 904+50 pins

Diameter DN OR 250 250

Weight Kg 88 89

Condensation OR 20 20

Page10
HIGH EFFICIENCY HEAT RECOVERY UNIT
DATA SHEET

Specification item
High-flow heat recovery ventilation units for decentralized applications;Specific unit for ventilation in environments with ventilation and air
treatment needs, such as commercial environments, offices, schools and small tertiary sectors;
CONSTRUCTION FEATURES
self-supporting structure in galvanized sheet metal with internal insulation in polyethylene; Heat exchangers and counter-current cross-
flows with maximum tightness and no leakage of traditional heat exchangers;
Compact dimensions for simplified ceiling (H) or wall (HV) installation with front and bottom panels easily accessible for maintenance and
inspection.
Circular inlets for air ducts towards the outside with grilles, template for installation supplied;;
Rapid filter inspection and drain for condensate evacuation;
Electrical panel with management cards and power cables and remote panel prepared; forward curved centrifugal fans with EC motors
with electronic flow control and low consumption ePm1 class filters with low pressure drop outside air and stale air
Electrical panel on the unit with microprocessor and dedicated regulation. Fan management, temperature display, timed dirty filter
management, freecooling management and antifreeze function;
Possibility of installation on board an electric pre-heating coil and hydronic post-heating coils for integration or replacement of existing
radiators. Remote control panel with WIFI and APP or modbus RTU to be purchased separately

TO Supplier name or brand


b Model identifier HRC+ 120
c Declared typology UVNR

d Drive type installed Variable speed


AND Heat recovery system To recovery

f Thermal efficiency of heat recovery % 85.3


h Nominal flow rate Mc/s 0.313
W/
THE SPF int
(m3/s)
651
j Front speed m/s 1.21

Nominal external pressure


k Pa 15
(Dps , ext)

Internal pressure drop


L Pa 199
(Dps, int)
Internal pressure drop
m to components extraneous to ventilation Pa /
(Dps , int)
Static efficiency of the fans as per
No % 37
EU 327/2011
Maximum percentages declared for
OR % 2.1 ext / 2.5 int
leakage
P Energy classification of filters F7/F7

Location and description of the signal related to the


Q Displayed on control panel and unit manual
filter

R Sound power level Lwa 57


St Internet address disassembly instructions

Page11
HIGH EFFICIENCY HEAT RECOVERY UNIT
DATA SHEET

HRC+ 70V Enthalpy


GENERAL TECHNICAL DATA
Size 70 V

Fans
Type of Fans Backward curved centrifugal fans - directly coupled electronic motor - 0/10 V signal
Number of fans No 2
Air flow V3/V2/V1 m3/h 700
Useful pressure Pa 15

Heat exchanger(Data referring to the UNI EN 13141-7 standard Internal temp. 22° - Internal humidity 50% - External temp. -12° -External humidity 90%)
Type of exchanger Counterflow plates – polypropylene material
Number of Exchangers No 1
Recovery efficiency EN13141-7 % 87
Recovery efficiency EN305 % 93

Filters
Type of filters Pleated filters
Filtration class ePM1 70

Acoustic data(Data referring to the UNI EN 3741 and UNI EN 3744 standards)
Sound power Lw
dB(A) 60
sent by the facility

Sound pressure at 3m V1 dB(A) 41


Sound pressure at 3m V2 dB(A) 35
Sound pressure at 3m V3 dB(A 32

Electrical data
Supply voltage v 230 / 1 / 50Hz.
Current consumption TO 3.6
Max absorbed power w 360
Max absorbed power with
kW 1.36
electrical resistance
Current drawn with electrical
TO 7.9
resistance
Power consumption V3
With 15 pa pressure and clean 330
filters
Degree of protection IP X0

Page12
HIGH EFFICIENCY HEAT RECOVERY UNIT
DATA SHEET

DIMENSIONS AND FUNCTIONAL SPACES

HRC+ 70 V

Width A mm 633

Depth B mm 636

Height C mm 1802+150 pins

Diameter DN OR 200

Weight Kg 86

Condensation OR 20

Page13
HIGH EFFICIENCY HEAT RECOVERY UNIT
DATA SHEET

Specification item
High-flow heat recovery ventilation units for decentralized applications;
Specific unit for ventilation in environments with ventilation and air treatment needs, such as commercial environments, offices, schools
and small tertiary sectors;
CONSTRUCTION FEATURES
self-supporting structure in galvanized sheet metal with internal insulation in polyethylene; Heat exchangers and counter-current cross-
flows with maximum tightness and no leakage of traditional heat exchangers;
Compact wall dimensions on standard dimensions 600x600 mm with front panels easily accessible for maintenance and inspection.
Circular inlets for air ducts to the outside with grilles, installation template supplied;
Rapid filter inspection and drain for condensate evacuation; Electrical panel with management cards and power cables and remote panel
prepared;
centrifugal fans of the centrifugal type with backward curved blades with EC motors with electronic flow control and low consumption
ePm1 class filters with low external air pressure drop and stale air
Electrical panel on the unit with microprocessor and dedicated regulation. Fan management, temperature display, timed dirty filter
management, freecooling management and antifreeze function;
Possibility of installation on board an electric pre-heating coil and hydronic post-heating coils for integration or replacement of existing
radiators.
Remote control panel with WIFI and APP or modbus RTU to be purchased separately

TO Supplier name or brand


b Model identifier HRC+ 70
c Declared typology UVNR

d Drive type installed Variable speed


AND Heat recovery system To recovery

f Thermal efficiency of heat recovery % 85.9


h Nominal flow rate Mc/s 0.18
W/
THE SPF int
(m3/s)
628
j Front speed m/s 1.18

Nominal external pressure


k Pa 15
(Dps , ext)

Internal pressure drop


L Pa 175
(Dps, int)
Internal pressure drop
m to components extraneous to ventilation (Dps , Pa /
int)
Static efficiency of the fans as per
No % 48
EU 327/2011

OR Maximum percentages declared for leakage % 2.5 exts / 2.9 ints

P Energy classification of filters F7/F7

Location and description of the signal related to the


Q Displayed on control panel and unit manual
filter

R Sound power level Lwa 55


St Internet address disassembly instructions

Page14
HIGH EFFICIENCY HEAT RECOVERY UNIT
DATA SHEET

ACCESSORY LIST

RES - Ordered and installed on board the machine when ordering

Electric resistance for automatic


management according to the outside air
temperature.

Model RES1 RES2 RES3


Compatible model unit HRC+ 60H / HV HRC+ 120H / HV HRC+ 70V
Rated electric power kW 1 (0.5 x 2) 1.5 (0.5 x 3) 1 (0.5 x 1)
Diet / 230V / 1 / 50

WATER HEATING COIL BAC (FOR POST-HEATING OPERATION)

The water pre/post heating units consist of a galvanized


sheet metal frame and a heat exchange coil made up of
copper pipes and aluminum fins.
They are equipped with circular flanges which facilitate
the installation to the duct.
They are equipped with threaded connections including
valves for air venting and coil discharge.
Model bac extension
Compatible model unit HRC+ 60H / HV HRC+ 70V HRC+ 120H / HV
Rated thermal power (1) kW 3.38 4.17 6.16
Nominal water flow (1) Mc/h 0.3 0.37 0.54
Water side pressure drop (1) Kpa 1 5 5
Flow temperature (1) °C 50 50 50
Air side pressure drop Pa 14 27 33
Water attacks OR 3-4” 3-4” 3-4”

* (1) Yields and technical data with nominal flow rates and temperatures: Water IN / OUT - 50° / 40° - Air IN 20°

COMMAND
B/W

Removable panel for mounting on box 502-503 or on wall;


Speed, temperature and operating mode control;
Integrated air quality, temperature and humidity sensor
Maximum connection length 50 m if made with 4-wire twisted shielded cable.
Black and white version

COMMAND
B/W

Removable panel for mounting on box 502-503 or on wall;


Speed, temperature and operating mode control;
Integrated air quality, temperature and humidity sensor
Maximum connection length 50 m if made with 4-wire twisted shielded cable.
Wifi command for management via smartphone or tablet and dedicated APP;
Black and white version

Page15
HIGH EFFICIENCY HEAT RECOVERY UNIT
DATA SHEET

FDR – REPLACEMENT FILTERS F7

Kit consisting of four F7 filters for unit maintenance;


The filters are easily removable through the dedicated inspectable doors;

UVC – Ordered and installed on board the machine when ordering

The UVC system, with germicidal action, includes a UVC lamp and power
supply wired and installed inside the unit to be selected when ordering;
The lamp has a UVC wavelength of 254 nm;
The life of the lamp is estimated at 10,000 hours of operation;

Model UVR1
Compatible model unit Channeled models
Rated electric power Watt 36
Diet / 230V / 1 / 50
Wave length n 254
Bulb length mm 350

Spare UV lamp

Kit consisting of a bulb for the UVC system placed inside the unit;

FDR – REPLACEMENT FILTERS F7

Kit consisting of two F7 filters for unit maintenance;


The filters are easily removable through the dedicated inspectable doors;

GEM – EXTERNAL GRIDS 200 mm

Kit consisting of two external grilles for external wall holes diam. 200 mm;

GEM – EXTERNAL GRIDS 250 mm

Kit consisting of two external grilles for external wall holes diam. 250 mm;

Page16
HIGH EFFICIENCY HEAT RECOVERY UNIT
DATA SHEET

SIL – SILENCER DIAM 200 mm

Kit consisting of 2 silencers 500 mm long for external noise reduction


Certified with unit in laboratory for Dnew value

SIL – SILENCER DIAM 250 mm

Kit consisting of 2 silencers 500 mm long for external noise reduction


Certified with unit in laboratory for Dnew value

IT ORDERING CODESTO
H models with sensitive high efficiency heat exchanger
Model Description Code
HRC+60HI High flow decentralized sensible heat recovery unit for horizontal installation Dn250x2 VRVP60OC1II
HRC+ 120HI High flow decentralized enthalpy heat recovery unit for horizontal installation Dn250x2 VRVPX2HC1II

H models with high efficiency enthalpy exchanger


Model Description Code
HRC+ 60 HX I High flow decentralized enthalpy heat recovery unit for horizontal installation Dn250x2 VRVP60HC1II
HRC+ 120 HX I High flow decentralized enthalpy heat recovery unit for horizontal installation Dn250x2 VRVPX2HC1II

HV models with sensitive high efficiency heat exchanger


Model Description Code
HRC+ 60 HV I High flow decentralized sensible heat recovery unit for vertical installation Dn 250x2 VRVP60VC1II
HRC+ 120 HV I High flow decentralized enthalpy heat recovery unit for vertical installation Dn 250x2 VRVPX2VC1II

Models with high efficiency enthalpy exchanger


Model Description Code
HRC+ 60 HVXI High flow decentralized enthalpy heat recovery unit for vertical installation Dn250x2 VRVP60WC1II
HRC+ 120 HVXI High flow decentralized enthalpy heat recovery unit for vertical installation Dn250x2 VRVPX2WC1II

V models with sensitive high efficiency heat exchanger


Model Description Code
HRC+ 70 HV I High flow decentralized sensible heat recovery unit for vertical installation Dn250x2 VRVP70VC1II

Page17
HIGH EFFICIENCY HEAT RECOVERY UNIT
DATA SHEET

Remote control
Compatible model All versions
Description Black White
Code EQA649II EQB649II

Remote control with Wi-Fi


Compatible model All versions
Description Black White
Code ERA649II ERB649II

UVR lamp installed on the unit


Description UVR
Compatible model All
Code AHRD0651ITHE

Spare UVR lamp


Description UVR
Compatible model All
Code AHRD0652II

Resistors installed on board


Compatible model HRC 60 HRC 120 HRC 70
Description RES1 RES2 RES3
Code AHRA0721II AHRA0722II AHRA0723II

Hydronic coils installed on board


Compatible model HRC 60 HRC 120 HRC 70
Description BAC1 BAC2 BAC3
Code AHRA0731II AHRA0732II AHRA0733II

Spare filter pair kit F7


Compatible model HRC+ 60H / HV HRC+ 120H / HV HRC+70V
Description REPLACEMENT FILTERS REPLACEMENT FILTERS REPLACEMENT FILTERS
Code AHRP0042II AHRP0044II AHRP0911II
FDR FDR FDR

Diam 200 silencers (size 60)


Description SIL
Compatible model Size 60-70
Code AHRC0038II

Diam 250 silencers (size 120)


Description SIL
Compatible model Size 120
Code AHRC0039II

Page18
HIGH EFFICIENCY HEAT RECOVERY UNIT
DATA SHEET

External grids Diam 200


Description GEM
Compatible model Size 60
Code STE020150II

External grids Diam 250


Description GEM
Compatible model Size 120
Code STE025180II

CE marking

The CE marking (present on each machine) certifies compliance with the following EU standards:

• Low Voltage Directive 2014/35/EC


• Electromagnetic Compatibility Directive 2014/30/EC