You are on page 1of 15

MIP PKG06 – ONSHORE OIL

FACILITIES PROJECT

Document Title : GENERAL ARRANGEMENT DRAWING OF

SAFETY SHOWER & EYE WASH

Document No. : VD-MR021-039

PROJECT LOCATION : TANAJIB, SAUDI ARABIA

COMPANY (OWNER) : SAUDI ARAMCO

CONTRACTOR PO NO. : PO-MIP6-MR-PO-021-4600061905

SAUDI ARAMCO PO NO. : IPIK-M98-21-G495-DA

BI No. :10-02454-0002

NMR No. : 602

Dec. 21, 2022


1" NPT female parallel adapter shall
be provided as confirmed by REDA.
J.S.Oh J.S.Oh
00 12/20/2022 ISSUE FOR CONSTRUCTION NS RD
J 10/4/2022 ISSUE FOR APPROVAL NS RD
I 9/1/2022 ISSUE FOR APPROVAL NS RD
H 5/17/2022 ISSUE FOR APPROVAL NS RD
G 3/30/2022 ISSUE FOR APPROVAL NS RD
F 3/1/2022 ISSUE FOR APPROVAL NS RD
E 11/17/2021 ISSUE FOR APPROVAL NS RD

D 10/18/2021 ISSUE FOR APPROVAL NS RD


APPROVED APPROVED
REV. DATE DESCRIPTION PREPARED CHECKED
(CONTRACTOR) (COMPANY)

COMPANY APPROVAL DATE

COMPANY DOCUMENT NO.

Company Electronic File Name:


This document is CONFIDENTIAL and the sole property of Hyundai Engineering and Construction Co.Ltd. It shall neither be shown to third parties nor used for
any other purposes than those for which it has been issued/sent. Any unauthorized attempt to reproduce it, in any form, is strictly prohibited
1 2 3 4 5 6 7 8

Additive inlet / 378


Overflow drain Pressure reducing valve 1 1/4"
brass EX alarm unit horn & flash light
EX alarm unit horn & flash light actived by inductive sensors

42
actived by inductive sensors adapter 1-1/2” NPT Male x 1-1/4” BSPP Male SS316L
A +Flange ASME 1 1/2" NPT RF #150 SS316L Safety sign A
96 English & Arabic
1200 Y-Strainer 1 1/4"
Detail I (1 : 10) 1200 liters GRP tank 650 x 450mm
600 housing brass, strainer SS (green ~RAL 6029)
1500
551 200 1200 378 Automatic refill brass valve Sunshield SS304
Water level Indicator brass
600
Pressure reducing valve 1 1/4"
brass
Y-Strainer 1 1/4"
B housing brass, strainer SS B

Additive inlet / I
Water temperature gauge SS
Overflow drain
Water inlet:flange Body shower:
1 1/2" NPT -activated by pullrod "stay open"
Tag plate SS -inductive sensor SP156TES IECEx
Ex Junction Box -ball valve chrome plated brass
GRP 35 -shower head SS304
35
96 125 Insulated eye wash pipe SS
Eye wash: C
3662

C
-activated by pushflag "stay open"
3460
3380

-inductive sensor SP156TES IECEx


65

-ball valve SS316


-AXION head SS304
-bowl SS304
2100

1172
E
927

D D

E
EL. 8500 ->
-
(HPP+150) --
- --
floor line --
--
--
150

1050 EX Chiller Unit 3kW -


groundling lug Frame in galvanized steel --
1130 647 900 3Ph/ 480 V/60Hz ATEX chiller unit -
Zone 2 IIB T3
groundling lug Qty : 19 EA cable entry M32
6x Anchoring boltsAnchoring bolts location plan
E M10x130 SS316 E
Note : Groundling lugs of the 1030 4x Anchoring bolts E 24.02.2022 mamu

safety shower M10x130 SS316


D
REV DESCRIPTION ECN NO.
05.10.2021
DATE
drmi
BY
and chiller are included by 750 REVISIONS
HAWS scope CATEGORY MATERIAL TITLE
569 GENERAL ARRANGEMENT - 4000.1200 OTS GRP
300 SURFACE WEIGHT (kg) SPECIFICATION

109 APPROVALS
- 880.95
DATE
Overhead tank shower GRP
ISSUED BY HAWS AG "FOR APPROVAL" BY OUR CUSTOMER MODELLED
APPROVED 0 mamu 27.04.2021 -
F CUSTOMER IS REQUIRED TO APPROVED WITH NOTES BACHWEG 3
DRAWN PART NO. F
CHECK ( ) ONE BOX ONLY T +41 (0)34 420 60 00 www.haws.ch mamu 27.04.2021
RESUBMITTED WITH NOTES F +41 (0)34 420 60 01 CH3401 BURGDORF info@haws.ch
SWITZERLAND REVISED SO00013736
0
20
340

790

1110

1808

2638

mamu 24.02.2022
______________________ ______________________ CHECKED
THIS DOCUMENT AND THE DATA DISCLOSED HEREIN pelu 28.02.2022 SIZE DOCUMENT NO. REV.
CUSTOMER SIGNATURE DATE OR HEREWITH IS NOT TO BE REPRODUCED, USED,
OR DISCLOSED IN WHOLE OR IN PART TO ANYONE
Please return all drawings signed and dated to Haws AG E-E WITHOUT THE PERMISSION OF HAWS CORPORATION.
SCALE 1:50 SHEET 1 OF 6
A3 0021257 E
Switzerland office. General tolerances ISO 2768-mK
1 2 3 4 5 6 7 8
TAG LIST OTS ATEX chiller unit location A for the first
(27nos)+ second (15nos) + third (10nos) PO:

SSEW-G54-1-01
SSEW-M95-1-01
SSEW-M95-1-02
SSEW-M95-1-03
SSEW-M95-1-08
SSEW-M95-1-09
SSEW-M95-1-10
SSEW-M95-1-12
SSEW-M95-2-02
SSEW-M96-1-01
SSEW-M96-1-02
SSEW-M96-1-03
SSEW-M96-1-05

SSEW-M96-1-06
SSEW-M96-1-10

SSEW-M97-2-31

SSEW-M96-1-08
1 2 3 4 5 6 7 8
2913

A A

82
1500

B
B
806

C
C
1500

--> --
---
D D

-
- ----
---
900 ATEX chiller unit -
540
165
cable entry M32
2490

E E
26.08.2021 mamu

REV DESCRIPTION ECN NO. DATE BY

430
REVISIONS
CATEGORY MATERIAL TITLE

350 GENERAL ARRANGEMENT - 4000.1200 OTS GRP


SURFACE WEIGHT (kg) SPECIFICATION
- 494.61
Overhead tank shower GRP
APPROVALS DATE
MODELLED
320

drmi 16.09.2021 -
F DRAWN PART NO. F
T +41 (0)34 420 60 00 BACHWEG 3 www.haws.ch mamu 26.08.2021
F +41 (0)34 420 60 01 CH3401 BURGDORF info@haws.ch
SWITZERLAND REVISED

CHECKED
THIS DOCUMENT AND THE DATA DISCLOSED HEREIN drmi 09.11.2021 SIZE DOCUMENT NO. REV.
850 OR HEREWITH IS NOT TO BE REPRODUCED, USED,
350

OR DISCLOSED IN WHOLE OR IN PART TO ANYONE


WITHOUT THE PERMISSION OF HAWS CORPORATION.
SCALE 1:50 SHEET 7 OF 9
A3 0021330 -
1045 General tolerances ISO 2768-mK
1 2 3 4 5 6 7 8
TAG LIST OTS ATEX chiller unit location B for the first
(27nos)+ second (15nos) + third (10nos) PO:

SSEW-M95-1-04

SSEW-M95-1-07
+

SSEW-M97-1-02
1 2 3 4 5 6 7 8

A A

82
900

610

1500
B

610
350
430

806
C
C
1300

1480

1500

D D

850 587
1045

E 165 E
26.08.2021 mamu

REV DESCRIPTION ECN NO. DATE BY


REVISIONS
CATEGORY MATERIAL TITLE

GENERAL ARRANGEMENT - 4000.1200 OTS GRP


SURFACE WEIGHT (kg) SPECIFICATION
- 494.61
Overhead tank shower GRP
APPROVALS DATE
MODELLED
drmi 16.09.2021 -
F DRAWN PART NO. F
T +41 (0)34 420 60 00 BACHWEG 3 www.haws.ch mamu 26.08.2021
F +41 (0)34 420 60 01 CH3401 BURGDORF info@haws.ch
SWITZERLAND REVISED

CHECKED
THIS DOCUMENT AND THE DATA DISCLOSED HEREIN drmi 09.11.2021 SIZE DOCUMENT NO. REV.
OR HEREWITH IS NOT TO BE REPRODUCED, USED,
OR DISCLOSED IN WHOLE OR IN PART TO ANYONE
WITHOUT THE PERMISSION OF HAWS CORPORATION.
SCALE 1:50
General tolerances ISO 2768-mK
SHEET 8 OF 9
A3 0021330 -
1 2 3 4 5 6 7 8
TAG LIST OTS ATEX chiller unit location C for the first
(27nos)+ second (15nos) + third (10nos) PO:

SSEW-M95-1-05
SSEW-M95-1-06
SSEW-M96-1-04
SSEW-M96-1-07
SSEW-M96-1-09
SSEW-M96-1-12
SSEW-M96-1-11

Add 1 nos to the list (SSEW-M96-1-13). SSEW-M96-1-13


1 2 3 4 5 6 7 8

2495

95
A A

1302
470

B
B
3662

C
1486

C
1501

456

D D

652
600

E E
26.08.2021 mamu

REV DESCRIPTION ECN NO. DATE BY


REVISIONS
CATEGORY MATERIAL TITLE
600

GENERAL ARRANGEMENT - 4000.1200 OTS GRP


SURFACE WEIGHT (kg) SPECIFICATION
250
403

- 501.66
Overhead tank shower GRP
510

APPROVALS DATE
MODELLED
tara 29.03.2022 -
F DRAWN PART NO. F
T +41 (0)34 420 60 00 BACHWEG 3 www.haws.ch mamu 26.08.2021
F +41 (0)34 420 60 01 CH3401 BURGDORF info@haws.ch
SWITZERLAND REVISED

801
CHECKED
THIS DOCUMENT AND THE DATA DISCLOSED HEREIN tara 29.03.2022 SIZE DOCUMENT NO. REV.
OR HEREWITH IS NOT TO BE REPRODUCED, USED,

926
OR DISCLOSED IN WHOLE OR IN PART TO ANYONE
WITHOUT THE PERMISSION OF HAWS CORPORATION.
SCALE 1:50
General tolerances ISO 2768-mK
SHEET 10 OF 10
A3 0021330 -
1 2 3 4 5 6 7 8
TAG LIST OTS SAFE AREA chiller unit location B for the first
(27nos)+ second (15nos) + third (10nos) PO:

SSEW-M97-2-27

SSEW-M95-2-04
SSEW-M97-2-28
1 2 3 4 5 6 7 8

94
A A

1300
B
B

469

C
C
1500
1500

D D

75
502 1
352

460

830
940
1330
E E
26.08.2021 mamu
1440
540(x2)

REV DESCRIPTION ECN NO. DATE BY

250 (x2) CATEGORY MATERIAL


REVISIONS
TITLE

GENERAL ARRANGEMENT - 4000.1200 OTS GRP


SURFACE WEIGHT (kg) SPECIFICATION
- 494.61
Overhead tank shower GRP
APPROVALS DATE
MODELLED
drmi 16.09.2021 -
F DRAWN PART NO. F
T +41 (0)34 420 60 00 BACHWEG 3 www.haws.ch mamu 26.08.2021
F +41 (0)34 420 60 01 CH3401 BURGDORF info@haws.ch
SWITZERLAND REVISED

CHECKED
THIS DOCUMENT AND THE DATA DISCLOSED HEREIN drmi 09.11.2021 SIZE DOCUMENT NO. REV.
OR HEREWITH IS NOT TO BE REPRODUCED, USED,
OR DISCLOSED IN WHOLE OR IN PART TO ANYONE
WITHOUT THE PERMISSION OF HAWS CORPORATION.
SCALE 1:50
General tolerances ISO 2768-mK
SHEET 9 OF 9
A3 0021330 -
1 2 3 4 5 6 7 8
TAG LIST OTS SAFE AREA chiller unit location C for the
first (27nos)+ second (15nos) + third (10nos) PO:

SSEW-G80-1-01
SSEW-M97-1-11
1 2 3 4 5 6 7 8
378
Additive inlet /
alarm unit horn & flash light Overflow drain Pressure reducing valve 1 1/4"
actived by inductive sensors brass
Water inlet adapter 1-1/2” NPT Male x 1-1/4” BSPP Male SS316L

42
A
1 1/2" NPT female +Flange ASME 1 1/2" NPT RF #150 SS316L
A

alarm unit horn & flash light


Additive inlet / Detail H (1 : 10) 96 1200 liters GRP tank actived by inductive sensors
551 200 Y-Strainer 1 1/4" (green ~RAL 6029)
Overflow drain 1500 378 housing brass, strainer SS Safety sign
Sunshield SS304 English & Arabic
Automatic refill brass valve 650 x 450mm
Water level Indicator brass
Pressure reducing valve 1 1/4"
brass
H B
B
Y-Strainer 1 1/4"
housing brass, strainer SS
Tag plate SS Water temperature gauge SS
Junction Box Body shower:
GRP -activated by pullrod "stay open"
-inductive sensor SP156TES
125 -ball valve chrome plated brass
-shower head SS304
3662
3460
3380

Insulated eye wash pipe SS C


65

C
Eye wash:
-activated by pushflag "stay open"
-inductive sensor SP156TES
-ball valve SS316
2100

-AXION head SS304


-bowl SS304
G
927

652
D EL. 8500 D
(HPP+150)

floor line -->


--
150

1050
Frame in galvanized steel ---
Groundling lug Non Ex Chiller Unit 3kW
---
1130 539 751 3Ph/ 480V/60Hz ---
Qty : 23 EA - --
6x Anchoring bolts NonATEX chiller
M10x130 SS316 Groundling lug unit - cable entry
E
Note : Groundling lugs of the Anchoring bolts location plan M20 E
safety shower 1030 4x Anchoring bolts E 24.02.2022 mamu
and chiller are included by M8x75 SS316 D 05.10.2021 drmi
HAWS scope 750 REV DESCRIPTION ECN NO. DATE BY
REVISIONS

533
CATEGORY MATERIAL TITLE

GENERAL ARRANGEMENT - 4000.1200 OTS GRP


300 SURFACE WEIGHT (kg) SPECIFICATION
83 - 880.95
Overhead tank shower GRP
APPROVALS DATE
ISSUED BY HAWS AG "FOR APPROVAL" BY OUR CUSTOMER 0 MODELLED
APPROVED mamu 26.04.2021 -
F CUSTOMER IS REQUIRED TO APPROVED WITH NOTES BACHWEG 3
DRAWN PART NO. F
CHECK ( ) ONE BOX ONLY T +41 (0)34 420 60 00 www.haws.ch mamu 27.04.2021
F +41 (0)34 420 60 01 CH3401 BURGDORF info@haws.ch
SO00013736
0
20
340

790

1110

1695

2394

RESUBMITTED WITH NOTES SWITZERLAND REVISED


mamu 24.02.2022
______________________ ______________________ CHECKED
THIS DOCUMENT AND THE DATA DISCLOSED HEREIN pelu 28.02.2022 SIZE DOCUMENT NO. REV.
CUSTOMER SIGNATURE DATE OR HEREWITH IS NOT TO BE REPRODUCED, USED,

Please return all drawings signed and dated to Haws AG G-G OR DISCLOSED IN WHOLE OR IN PART TO ANYONE
WITHOUT THE PERMISSION OF HAWS CORPORATION.
SCALE 1:50 SHEET 2 OF 6
A3 0021257 E
Switzerland office. General tolerances ISO 2768-mK
1 2 3 4 5 6 7 8
TAG LIST OTS SAFE AREA chiller unit location A for
the first (27nos)+ second (15nos) + third (10nos) PO:

SSEW-M95-1-11
SSEW-M97-1-05
SSEW-M97-1-07
SSEW-M97-1-08
SSEW-M97-2-21
SSEW-M97-2-22
SSEW-M97-2-23
SSEW-M97-2-24
SSEW-M97-2-25
SSEW-M97-2-26

SSEW-M97-2-20
SSEW-M95-2-03
SSEW-M97-1-03
SSEW-M97-1-04
SSEW-M97-1-06
SSEW-M97-1-15
SSEW-M97-2-29
SSEW-M97-2-30
SSEW-M97-2-33
SSEW-M97-1-11
+
SSEW-M97-2-35
Change the table as below (1 no. is added);
[SMJ6] List of Emergency Safety shower and Eyewash (ESEW) Unit
2022-12-21
1. Emergency Safety shower and Eyewash with chiller and water tank type
Source of Explosion CHILLER ORIENTATION
Quantity of ESEW
No. ESEW No. Emergency Safety shower and Eyewash Material
as per SAES-B-069
Ref. US SS Plan No. Location Proof (BY PIPING)
(ESEW) [Y/N] A/B/C

1 SSEW-G54-1-01 G54-D-0307 Sample Point SP-4100 HC 1 ea G80-L-CA-020043-001 Outdoor Y A


2 SSEW-G80-1-01 Sample Point SP-4103 Crude 1 ea G80-L-CA-020043-001 Outdoor N C
3 SSEW-M97-1-15 M97-U-0335 Oxygen Scavenger 1 ea G80-L-CA-020043-001 Outdoor N A
4 SSEW-M95-1-01 M95-D-0200 Sample Point M95-SP-4107/4110 Crude/OFF GAS 1 ea M95-L-CA-020044-001 Outdoor Y A
5 SSEW-M95-1-02 M95-D-0201 Sample Point M95-SP-4113/4105 Crude/OFF GAS 1 ea M95-L-CA-020044-001 Outdoor Y A
6 SSEW-M95-1-03 M95-D-0202 Sample Point M95-SP-4116/4111 Crude/OFF GAS 1 ea M95-L-CA-020044-001 Outdoor Y A
7 SSEW-M95-1-04 M95-E-0202A-H Sample Point M95-SP-4132 Crude 1 ea M95-L-CA-020044-001 Outdoor Y B
8 SSEW-M95-1-05 M95-D-0203 Sample Point M95-SP-4118/4119/4120 Crude 1 ea M95-L-CA-020044-001 Outdoor Y C
9 SSEW-M95-1-06 M95-D-0204 Sample Point M95-SP-4122/4123 Crude 1 ea M95-L-CA-020044-001 Outdoor Y C
10 SSEW-M95-1-07 M95-D-0205 Sample Point M95-SP-4126/4127 Crude 1 ea M95-L-CA-020044-001 Outdoor Y B
11 SSEW-M95-1-08 M95-D-0214 Sample Point M95-SP-4108/4106 Crude/OFF GAS 1 ea M95-L-CA-020044-001 Outdoor Y A
12 SSEW-M95-1-09 M95-D-0215 Sample Point M95-SP-4114/4112 Crude/OFF GAS 1 ea M95-L-CA-020044-001 Outdoor Y A
13 SSEW-M95-1-10 M95-D-0216 Sample Point M95-SP-4117/4115 Crude/OFF GAS 1 ea M95-L-CA-020044-001 Outdoor Y A
14 SSEW-M95-1-11 M95-G-0156A/B/C Sample Point M95-SP-4133 Crude 1 ea M95-L-CA-020044-001 Outdoor N A
15 SSEW-M95-1-12 M95-G-0228A/B/C/D/E Sample Point M95-SP-4217 Crude 1 ea M95-L-CA-020044-001 Outdoor Y A
16 SSEW-M95-2-02 M95-G-0208A/B Sample Point M95-SP-4130/4131 HC 1 ea M95-L-CA-020047-001 Outdoor Y A
17 SSEW-M95-2-03 Tanker Unloading Area for M95-D-0400 Demulsifier 1 ea M95-L-CA-020047-001 Outdoor N A
18 SSEW-M96-1-01 Tanker Unloading Area for M96-D-0318 TEG 1 ea M96-L-CA-020049-001 Outdoor Y A
19 SSEW-M96-1-02 M96-U-0301 TEG 1 ea M96-L-CA-020049-001 Outdoor Y A
20 SSEW-M96-1-03 M96-D-0304 Sample Point M96-SP-4230 HC Condensate 1 ea M96-L-CA-020049-001 Outdoor Y A
21 SSEW-M96-1-04 M96-D-0319 Sample Point M96-SP-4228 HC Condensate 1 ea M96-L-CA-020049-001 Outdoor Y C
Corrosion
22 SSEW-M96-1-05 Tanker Unloading Area for M96-D-0323 1 ea M96-L-CA-020049-001 Outdoor Y A
Inhibitor
23 SSEW-M96-1-06 M96-U-0036 Methanol 1 ea M96-L-CA-020049-001 Outdoor Y A
24 SSEW-M96-1-07 M96-D-0301 Sample Point M96-SP-4226 HC Condensate 1 ea M96-L-CA-020049-001 Outdoor Y C
25 SSEW-M96-1-08 M96-D-0302 Sample point M96-SP-4227 HC Condensate 1 ea M96-L-CA-020049-001 Outdoor Y A
26 SSEW-M96-1-09 M96-D-0303 Sample point M96-SP-4229 HC Condensate 1 ea M96-L-CA-020049-001 Outdoor Y C
27 SSEW-M96-1-10 M96-D-0305 Sample point M96-SP-4231 HC Condensate 1 ea M96-L-CA-020049-001 Outdoor Y A
28 SSEW-M96-1-11 M96-D-0315 Sample point M96-SP-4232/4234 HC Condensate 1 ea M96-L-CA-020049-001 Outdoor Y C
29 SSEW-M96-1-12 M96-D-0314 Sample point M96-SP-4233 HC Condensate 1 ea M96-L-CA-020049-001 Outdoor Y C

30 SSEW-M97-1-11 MBR CIP Dosing Area & Chemical Storage Area MBR CIP 1 ea M96-L-CA-020050-001 Outdoor N A

31 SSEW-M97-1-01 Unloading Bay adjacent to M95-D-0303 Hot Oil 1 ea M97-L-CA-020046-001 Outdoor N C


32 SSEW-M97-1-02 M95-D-0301A/B Filters Hot Oil 1 ea M97-L-CA-020046-001 Outdoor Y B
33 SSEW-M97-1-03 M95-U-0333B/0002B Biocide B 1 ea M97-L-CA-020055-001 Outdoor N A
Liquid Phase
34 SSEW-M97-1-04 M95-U-0331/0004 Corrosion 1 ea M97-L-CA-020055-001 Outdoor N A
Inhibitor
Scale
35 SSEW-M97-1-05 Tanker Unloading adjacent to M95-D-0397 & M95-D-0398 1 ea M97-L-CA-020055-001 Outdoor N A
Inhibitor/Biocide
36 SSEW-M97-1-06 M95-U-0332/0005 A 1 ea M97-L-CA-020055-001 Outdoor N A
37 SSEW-M97-1-07 Tanker Unloading adjacent to M95-D-0399A/B Biocide A/B 1 ea M97-L-CA-020055-001 Outdoor N A
38 SSEW-M97-1-08 M95-U-0002A/0333A Biocide A 1 ea M97-L-CA-020055-001 Outdoor N A
39 SSEW-M97-2-20 M97-G-0011A/B Oxygen Scavenger 1 ea M97-L-CA-020057-001 Outdoor N A
40 SSEW-M97-2-21 Tanker Unloading adjacent to M97-D-0019 SBS 1 ea M97-L-CA-020057-001 Outdoor N A
41 SSEW-M97-2-22 Tanker Unloading adjacent to M97-D-0018/0020 NaOH/Coagulant 1 ea M97-L-CA-020057-001 Outdoor N A
M97-G-0008A, M97-G-0009A/B, M97-G-0010A/B, M97-G- KMnO4/Biocide/N
42 SSEW-M97-2-23 1 ea M97-L-CA-020057-001 Outdoor N A
0012A-E, M97-G-0013A/B aOH/Coagulant
M97-G-0007A/B, M97-G-0008A, M97-G-0014A~F, M97-G-
43 SSEW-M97-2-24 KMnO4/Polymer 1 ea M97-L-CA-020057-001 Outdoor N A
0015A/B
Scale
Inhibitor/Liquid
44 SSEW-M97-2-25 M97-U-0035/0036 1 ea M97-L-CA-020057-001 Outdoor N A
Phase Corrosion
Inhibitor
45 SSEW-M97-2-26 M97-U-0034/0037 Biocide A/B 1 ea M97-L-CA-020057-001 Outdoor N A
Scale
Inhibitor/Liquid
46 SSEW-M97-2-27 Tanker Unloading adjacent to M97-D-0099/0100 1 ea M97-L-CA-020057-001 Outdoor N B
Phase Corrosion
Inhibitor
47 SSEW-M97-2-28 Tanker Unloading adjacent to M97-D-0098AB/0101 Biocide A/B 1 ea M97-L-CA-020057-001 Outdoor N B
48 SSEW-M97-2-29 Tanker Unloading adjacent to M97-D-0015AB/0016/0017 KMnO4/Biocide 1 ea M97-L-CA-020057-001 Outdoor N A
49 SSEW-M97-2-30 Truck diesel unloading near EDG 101 diesel 1 ea M97-L-CA-020059-001 Outdoor N A
50 SSEW-M97-2-31 Sample point for Scraper Crude 1 ea M97-L-CA-020041-001 Outdoor Y A
51 SSEW-M97-2-33 Sand Blasting Shelter Sand Dust 1 ea M97-L-CA-020042-001 Outdoor N A
52 SSEW-M95-2-04 M95-D-0330/0003 Demulsifier 1 ea M95-L-CA-020047-001 Outdoor N B
53 SSEW-M97-2-35 Sample point for Scraper Crude 1 ea M97-L-CA-020041-001 Outdoor N A
54 SSEW-M96-1-13 Sample point for M96-U-0301 TEG 1 ea M96-L-CA-020049-001 Outdoor Y C

Total 54 ea

LOCATION SAFE AREA CHILLER UNIT ATEX CHILLER UNIT TOTAL


A 21 17 38
B 3 3 6
C 2 8 10
26nos 28nos 54