You are on page 1of 1

This drawing should not be scaled. Dimensions to be verified on site.

Any discrepancies should be referred to the Engineer prior to work being put in
hand.

This drawing is the property of Kiloh Associates Limited, and the drawing is
issued on the condition that it is not copied reproduced, retained or disclosed to
any unauthorised person, either wholly or in part without the consent in writing of
Kiloh Associates Limited, Unit 6, Pitreavie Court, Pitreavie Business Park,
Dunfermline, KY11 8UU t 0131 629 3434

GENERAL NOTES

1. DO NOT SCALE THIS DRAWING. ANY DISCREPANCY IS TO BE


REPORTED TO THE ENGINEER IMMEDIATELY.

2. THIS DRAWING IS TO BE READ IN CONJUNCTION WITH ALL


ENGINEER'S OR OTHER RELEVANT DRAWINGS AND SPECIFICATIONS.

3. ALL DIMENSIONS AND LEVELS ARE TO BE CHECKED ON SITE BY THE


CONTRACTOR PRIOR TO PREPARING ANY WORKING DRAWINGS OR
COMMENCING ON SITE.

4. THE CONTRACTOR MUST ENSURE AND WILL BE HELD RESPONSIBLE


FOR THE OVERALL STABILITY OF THE
BUILDING/STRUCTURE/EXCAVATION AT ALL STAGES OF THE WORK.

5. ALL WORK BY THE CONTRACTOR MUST BE CARRIED OUT IN SUCH A


WAY THAT ALL REQUIREMENTS UNDER THE HEALTH AND SAFETY AT
WORK ACT ARE SATISFIED.

6. ALL WORK IS TO BE CARRIED OUT IN COMPLIANCE WITH THE


REQUIREMENTS OF THE RELEVANT STATUTORY AUTHORITIES AND
REGULATIONS.
LEGEND;
NOTES:
520x520 DIFFUSER VENT
THE CEILING CONTRACTOR IS RESPONSIBLE FOR CUTTING ALL PENETRATIONS INTO
(LOCATION TO MATCH EXISTING)
LEV CEILING TILES IN FULL ACCORDANCE WITH THE MANUFACTURERS RECOMMENDATIONS:
NEW 300x1400 LIGHTING
1 1. THE AREA OF THE TILES PAINTED SURFACE THAT REQUIRES CUTTING SHOULD
HAVE MASKING TAPE APPLIED ONTO WHICH THE LINE OF THE CUT SHOULD BE
MARKED. CARE SHOULD BE TAKEN TO AVOID EXCESSIVE TAPE APPLICATION
NEW 600x600 ACCESS HATCH
BEYOND THE EXTREMES OF THE LINE OF CUT.
2. THE CUT, WHERE POSSIBLE, SHOULD BE MADE WITH A PROPRIETARY ELECTRIC
NEW 600x600 SYSTEM: BURGESS CLEAN ROOM CLIP-IN CEILING
SHEAR CUTTER OR HAND SCISSOR SHEARS ENSURING THAT THE CUTTING BLADE
METAL CEILING SYSTEM SYSTEM WITH SWING DOWN AND SLIDE FACILITY.
IS SHARP AND FIT FOR THE PURPOSE.
3. WHERE CIRCULAR HOLES ARE REQUIRED TO BE CUT INTO THE FACE OF THE TILE SWING-DOWN AND SLIDE FACILITY.
THIS SHOULD BE CARRIED OUT USING A STEEL CIRCULAR HOLE SAW. IN SOME TILE: BURGESS ZINC COATED STEEL, PPC CEILING
INSTANCES FOR LARGER SIZE HOLES A SERIES OF CHAIN DRILLED HOLES WILL BE TILES, PLAIN (UNPERFORATED)
REQUIRED TO MINIMISE THE DISTORTION ALONG THE CUTTING LINE. CARE WITH TYPE 'A' BEVEL EDGE.
SHOULD BE TAKEN TO SUPPORT THE FACE OF THE TILE (INSIDE SURFACE) TO SIZE: 600x600mm
AVOID DISTORTION OF THE FACE OF THE TILE. GRID: BURGESS H4 CONCEALED GRID SYSTEM.
4. WHEN CUTTING SQUARE OR RECTANGULAR HOLES IN THE FACE A TILE IT IS SUSPENSION: TO SUIT CONCEALED GRID SYSTEM.
ADVISABLE TO DRILL A HOLE AT EACH CORNER OF THE PROPOSED OPENING. PRIMARY GRID, HANGERS, BRACKETS, SPRING TEE
5. ALL CUTTING/DRILLING SHOULD BE CARRIED OUT WORKING ON THE PAINTED BARS ETC ALL IN GALVANISED MILD STEEL.
FACE OF THE TILE, WHICH SHOULD BE ADEQUATELY SUPPORTED DURING THIS PERIMETER: DETAIL B - ET181 CHANNEL TRIM SECTION
OPERATION. COMPLETE WITH HOLD DOWN WEDGES. STANDARD
6. AFTER COMPLETING THE CUT OUT THE FACE OF THE CUT SHOULD BE SUPPLY ALUMINIUM WILL NOT BE ACCEPTED - ET181
FILED/DRESSED TO REMOVE ANY BURNS OR HIGH POINTS PRIOR TO THE CHANNEL TRIM MUST BE IN PPC MILD STEEL.
MASKING TAPE BEING REMOVED AND ANY RESIDUE OF THE TAPE CLEANED OFF SEAL: SOUDAL SILIRUB 2/S SILICONE SEALANT
THE FACE OF THE TILE. (COLOUR: NEUTRAL) APPLIED BETWEEN ALL TILE/TRIM
7. CEILING CONTRACTOR TO PROVIDE REQUIRED ATTENDANCES FOR INSTALLATION JOINTS TO FORM A TOTALLY AIR & DUST TIGHT CEILING.
OF THE CEILING MOUNTED/CEILING PENETRATION INSTALLATIONS. COLOUR: WHITE TO CEILING TILE, PERIMETER TRIM AND
ALL EXPOSED COMPONENTS.

PERIMETER DETAIL
BURGESS REF: B - ET181
CONCEALED GRID PERIMETER CHANNEL
+2.400 HOLD NOTES;
1. GSK TO CONFIRM LIGHTING
U/S CEILING SPECIFICATION & POSITIONS.
FIRE RATED (60 MIN) HOOD +2.200 APPROX
OVER ROLLER DOOR
CEILING TILE
GSK APPROVED
SILICONE SEALANT

2971.8
CEILING PERIMETER DETAIL
SCALE 1:10

2971.8
00 29/11/23 ISSUED FOR COMMENT JB MM

Rev Date Description Dr'n Ch'd

Amendments

Project

PROPOSED REFLECTED CEILING PLAN DISSO ROOM


SCALE 1:50

Title

PROPOSED REFLECTED
CEILING LAYOUT
Client

Kiloh Associates
Local Engineering for Local Clients
Unit 6, Pitreavie Court,
Pitreavie Business Park,
Dunfermline, Fife,
KY11 8UU
t: 0131 629 3434
e:en uiries@kiloh.co.uk
www.kiloh.co.uk
Status

COMMENT
Drawn by Date Designed by Checked by

JB NOVEMBER 2023 SF MM
Scales @ A1
work to figured dimensions only 1:50 Project No.
KIL2189
Drawing No.
KIL2189_200_0004 Rev
00