A NVR CABINET A

FRONT VIEW

B B

FIX THE CABINET


WITH 4 M10 SCREWS
C C

+0,2m
TERRAIN
±0,0m

D D

535
4x M10

E E

NVR LIST OF REBARS


492

600
700
CCTV CABINET TYPE R1 TYPE R2 TYPE R3

Ø8mm REBAR Ø8mm REBAR Ø8mm REBAR


F F
L = 900mm L = 200mm L = 650mm

700 QUANTITY 24 36 26
900

NOTES:
1. THE FOUNDATION DEPT MUST BE CHECKED ACCORDING TO STUDY OF SOIL
G G
MECHANIC EXECUTED FOR THE PROJECT.
THE PROCEDURES OF PREPARATION, PREPARATION, CURING AND QUALITY
CONTROL OF THE CONCRETE FOUNDATIONS WILL BE DONE IN ACCORDANCE
SECTION A-A SECTION B-B SECTION C-C WITH Std. NCh 170 of 2016
2. REINFORCED CONCRETE ELEMENTS:
FOUNDATIONS SIDE VIEW - CONDUIT ENTRANCE CONCRETE ARMATURE * QUALITY OF MATERIALS: CONCRETE FOUNDATIONS: H30 CONCRETE
REINFORCED STEEL: STEEL A630-420H
RAINFORCED * REINFORCED STEEL EMBEDMENT (COVERING): 50mm (MINIMUM)
H CONCRETE H
+0,20m +0,20m +0,20m 3. INSTALL 4x(Ø90mm) CORRUGATED CONDUITS UNDERGROUND PRIOR TO
TERRAIN FOUNDATIONS PREPARATION. ADAPT THE DIRECTION AND ORIENTATION OF THE
200

±0,0m ±0,0m ±0,0m INSTALLED CONDUITS TO THE FOLLOWING ROUTE OF INCOMING/OUTGOING CABLES.
4. FIX THE 4x(Ø90mm) CORRUGATED CONDUITS UNDER GRAVEL AND FOUNDATIONS
WITH CONCRETE GROUT.
750

R3 R3
CABLE TRENCH
550

600
R3 R3
J J

4x(Ø90) CONDUIT
50

1400
See NOTE 3. 4x(Ø90) CONDUIT
COMPACTED GRAVEL
INSTALLATION EXAMPLE.
See NOTE 4.
SELECT THE CORRECT ORIENTATION 60
ACCORDING TO CABLE ROUTE. 1250
K R2 R2 K
B REFERENCE DRAWINGS:
R1 R1 R1 PR_CL_0141_DD_0407 CABLE TRENCH SECTIONS

175
R2
550

R2
0 07/11/2021 FIRST ISSUE EG BG JZ
R1
850

Rev. Date Description Prepared Checked Approved


L R1 L
Prepared Date DWG Code
M.MACEK
04/2021
C
A

C
A

Approved J.ZRNO

SOLEK HOLDING SE Subject Scale


Voctářova 2497/18
GRAPHIC SCALE 180 00 Prague 8 | Czech Republic
PV POWER PLANT 1:15
Ø8mm REBAR MESH R1
0.5 0.0 0.5 1.0 B 400 260 180
Project Title
CCTV MOUNTING STRUCTURE
Print Size
(FASTEN BY TYING OR WELDING) PV POWER PLANT
M ALIANZA
FOUNDATION FOR NVR CABINET A1 M
1:15 metre 1000 Drawing No. Rev. Sheet No.
Phase DETAIL DESIGN
Design No. PR_CL_0141 PR_CL_0141_DD_0311 0 1/1 PV POWER
s.r.o.
Husitská 107/3

130 00 PRAHA 3