Professional Documents
Culture Documents
MEE Unit 4
MEE Unit 4
shooting of transformers
2.Efficiency test
• Procedure
• All three line terminals of the winding to be tested are connected together.
• Other winding terminals which are not under test and also tank of the
transformer should be connected to earth.
• single-phase A.C. voltage of sinusoidal waveform is applied at rated frequency.
The highest value of the test voltage is as given in the table below. At the time
of conducting the test a voltage less than l/3rd of the test value is applied at
the beginning. It is then increased gradually to full-test value and maintained
for 60 seconds, then it is reduced to less than l/3rd test value and then the
supply is switched off.
•
The test is successful if no break down in the dielectric of the insulation occurs
during test.
Although the actual lightning impulse disturbance may not have exactly these three
shapes but by defining these waves one can establish a minimum impulse dielectric
strength of a transformer.
If lighting disturbance travels some distance along the transmission line before it reaches
the transformer, its wave shape may approach to full wave. If during traveling, if flash-
over occurs at any insulator of the transmission line, after the peak of the wave has been
reached, the wave may become in form of chopped wave. If the lightning stroke directly
hits the transformer terminals, the impulse voltage rises rapidly until it is relieved by a
flash over. At the instant of flash-over the voltage suddenly collapses and may form the
front of wave shape.
The effect of these waveforms on the transformer insulation may be different from each
other. whatever may be the shape of lightning disturbance voltage wave, all of them can
cause insulation failure in the transformer. So lighting impulse test of transformer is one
of the most important type test of transformer.
EE5962 MRS.A.V.THAKARE LEE GP
Wednesday, May 19, 2021 37
AMRAVATI
• Hence , a impulse test has been developed to determine the ability of a
transformer to withstand the effects of high unidirectional voltages
resembling the lightning surge. For carrying out this test a high voltage
impulse generator is required The simplest basic circuit used for
developing a 1/50 wave and its application to the electrical equipment
under test is shown in Fig. 1. The 1/50 wave is represented in Fig. 2.
•
Delta/Delta connected
transformers
auxiliary
transformer
This test is carried out only on 3 phase transformer to idenitify primary and secondary
winding belonging to same phase .
Procedure:-
Short primary & secondary winding of other phases expect the one under test.
Connect voltmeter to secondary winding. A small DC current is circulated through the primary
winding through switch.
Now with the help of switch interrupt the DC supply instantly & repeatedly.
If voltmeter indicator deflects than it indicates the two windings concerned belong to the
same phase. If not deflect then two windings are not belong to same phase.
Repeat the procedure by connecting voltmeter to secondary side to next secondary
winding tillMay
voltmeter EE5962 MRS.A.V.THAKARE LEE GP
Wednesday, 19, 2021 gives deflection. 49
AMRAVATI
In this way we can search the phasing out.
DISSOLVED GAS ANALYSIS OF TRANSFORMER OIL
In dissolved gas analysis of transformer oil (or DGA of transformer oil) the gases in
oil are extracted from oil and analyze the quantity of gasses in a specific amount of
oil. By observing percentages of different gasses present in the oil, one can predict
the internal condition of transformer.
Generally the gasses found in the oil in service are hydrogen (H 2), methane(CH4),
Ethane (C2H6), ethylene(C2H4), acetylene (C2H3), carbon monoxide (CO), carbon
dioxide (CO2), nitrogen(N2) and oxygen(O2).
Most commonly used method of determining the content of these gases in
oil, is using a Vacuum Gas Extraction Apparatus and Gas Chronographs.
By this apparatus first gasses are extracted from oil by stirring it under vacuum.
These extracted gasses are then introduced in gas Chronographs for measurement of
each component.
conclusion:
Generally it is found that hydrogen and methane are produced in large quantity
if internal temperature of power transformer rises up to 150°C to 300°C due to
abnormal thermal stresses.
If temperature goes above 300°C, ethylene(C2H4) are produced in large quantity.
At the temperature is higher than 700°C large amount of hydrogen(H2) and ethylene
(C2H4) are produced. Ethylene(C2H4) is indication of very high temperature hot spot
inside transformer .
If during DGA test of transformer oil,MRS.A.V.THAKARE
EE5962 CO and COLEE2 GPare found in large quantity it is
Wednesday, May 19, 2021 50
predicted that there is decomposition of AMRAVATI
paper insulation.
Furfural Test or Furfuraldehyde Analysis of Transformer Oil:
Transformer core and winding have mainly paper insulation. Base of paper is
cellulose. The Cellulose has a structure of long chain of molecules. As the paper
becomes aged, these long chains are broken into number of shorter parts.
.In transformer, the aging affect of paper insulation is accelerated due to oxidation
occurs in oil. When insulating paper becomes mechanically weak, it can not withstand
the mechanical stresses applied during electrical short circuit and leads to electrical
breakdown.
It is therefore necessary to monitor the condition of paper insulation inside a power
transformer. It is not possible to bring out a piece of paper insulation from a transformer
in service for testing purpose. But ,there is a testing technique developed, where we
can examine the condition of paper insulation without touching it. The method is called
Furfuradehyde analysis of in short Furfural test.
Although by dissolved gas analysis one can predict the condition of the paper
insulation primarily, but it is not very sensitive method.
There is a guide line in IEC-599, where it is said that if the ratio of CO2 and CO in
DGA results is more than 11, it is predicted that the condition of paper insulation inside
the transformer is not good.
A healthy cellulose insulation gives that ratio in a range of 4 to 11. But still it is not a
very sensitive way of monitoring the condition of paper insulation. Because CO 2 and
CO gases also produced during oil breakdown
EE5962 and
MRS.A.V.THAKARE LEEsometimes
GP the ratio may misleads
Wednesday, May 19, 2021 51
the prediction. AMRAVATI
Causes of failure: internal and external, types of faults:
mechanical. electrical and magnetic
1. Overheating Overloads Failure of cooling Check cooling system, whether fans are operating whether
system High ambient oil/water is circulating. Reduce the load on the transformer. If
temperature temperature of coii high, switch-off the transformer till safe
temperature is reached. If overload problem is occurring for long
durations, install another transforme' in parallel. If ambient
temperature is higher than that considered in specifications of
transformer derate the transformer
2. Sustained higher Poor voltage control of power Transformer fail due to sustained over voltage. Provide overfluxing
voftage on primary system use of shunt reactance protection and over-voltage protection for bus-bar. Flux density
resulting in and tap changing transformer depends upon V/f ratio. Generator transformers, get overfluxed
overheating of core to control busbar voltage within during low frequency operation.
due to over fluxing. specified limit.
3. Frequent external Insufficient clearances on Transformer windings should be capable of withstanding repeated
short-circuits. overhead lines, accumulation of external short-circuits without failure. Transformer should be
dust on insulation. provided with over current protection.
4. Short-circuit .Sharp corners on conductors Buchholtz relay should operate and sound alarm. Over-current and
between adjacent cutting into insulation. differential protection should operate and open the circuit breaker.
turns, usually high External short circuit (1:3).
voltage winding. Moisture in oil. Fluctuating
EE5962 MRS.A.V.THAKARE LEE GP
Wednesday, May 19, 2021 53
loads. Transient over voltage. AMRAVATI
Trouble Cause Remarks
5. Internal Sustained overload and insulation failure Overcurrent protection Earth fault
short-circuit Fault in tap changer protection Differential protection
Failure of end turns of coil due to over voltage
surges
Bad solder joint causing local overheating and
open circuit Ageing of insulation, abrasion of
insulation resulting in internal shod: circuits
6. Moisture • Moisture in the oil while filling Oil should be filtered. Silica jel should be
in oil • Breother saturated replaced, gaskets should be replaced.
• Defective seal;; Transformer should be dried out.
Failure of insulation of bolts Failure of insulation bolts used for clamping the core
used for clamping core and and yoke cause! heavy circulating short circuit
yoke currents resulting in core heating.
Vibrations in core The loose core clamping bolts and bolts between
core and structure results in vibration of core. This
results in weak core insulation.
Excessive core heating, high Excessive heating of core result ir temperature rise of
magnetizing currents, high in winding.
rush current.
The natural air always consists of more or less moisture in it and this
moisture can be mixed up with oil if it is allowed to enter into the
transformer. The air moisture should be resisted during entering of
the air into the transformer, because moisture is very harmful for
transformer insulation.
A silica gel breather is the most commonly used way of filtering air
from moisture. Silica gel breather for transformer is connected with
EE5962 MRS.A.V.THAKARE LEE GP
conservator tank by means of AMRAVATI
Wednesday, May 19, 2021
breathing pipe. 56
Working Principle of Silica Gel Breather
Silica gel crystal has tremendous capacity of absorbing moisture.
When air passes through these crystals in the breather; the
moisture of the air is absorbed by them. Therefore, the air reaches
to the conservator is quite dry, the dust particles in the air get
trapped by the oil in the oil seal cup. The oil in the oil sealing cup
acts as barrier between silica gel crystal and air when there is no
flow of air through silica gel breather.
The color of silica gel crystal is dark blue but, when it absorbs
moisture; it becomes pink. When there is sufficient difference
between the air inside the conservator and the outside air, the oil
level in two components of the oil seal changes until the lower oil
level just reaches the rim of the inverted cup, the air then moves
from high pressure compartment to the low pressure compartment
of the oil seal . Both of these happen when the oil acts as core filter
and removes the dust from the outside
EE5962 MRS.A.V.THAKARE LEE GP
air. Wednesday, May 19, 2021
AMRAVATI
57
EE5962 MRS.A.V.THAKARE LEE GP
Wednesday, May 19, 2021 58
AMRAVATI
SPECIAL TEST
• Short circuit withstand ability test.
This tests measures the ability of the transformer to withstand the
mechanical and thermal stresses caused by the external short circuit.
HV terminals are connected to the supply bus of the testing plant. The LV is
short circuited. The testing plant parameters are such adjusted to give the
rated short circuit current.
Supply is made on and closed after specified duration of short circuit. The
record of current wave form is noted.
There should not be any mechanical distortion, fire to the transformer during
this test. Similarly no wave form distortion. The transformer should also
withstand the routine tests after the short circuit test.
The reactance of the winding measured before and after the S.C. test should
not vary beyond the limits stated in the IS2026.
1. A overall inspection of the control and relay panels, cable junction boxes is carried out and
observed if any connection is left open.
2. Tests on relays such as over current, earth fault, reverse power etc. is carried out for their
operation.
3. Voltage ratio with equal tappings on all phases can be checked.
4. Measurement of earth resistance and necessary steps for bringing it within suitable value.
5. Tests carried out on Buchholz relay for its contact operation.
6. Test can be carried out, on cooling fans, cooling water pumps about their direction of rotation,
speed and troubles in starting etc.
7. If on loading tap changing arrangement is there, its operation can be checked with the
indication of tap number on panel and buzzer etc. at the time of change.
8. If required phasing out test is carried out.
9. Insulation resistance measurement with megger between H.V. and between LV. and core, H.V.
and core etc. at the same time on C.T. and P.T. used in measurement and protection systems.
10. Oil in conservator should be upto the indication mark on glass plate.
11. If neutral earthing switch is provided, it should be closed before switching on supply.
12.Transformer can then be loaded and the meters both on H.V. and L.V. sides be checked for their
readings on all the phases. It should be equal for same loading.
13. Operation of on-foad tap changing arrangement can then be checked.
14. If possible transformers above 1000 kVA rating should be connected to variable supply and the
EE5962 MRS.A.V.THAKARE LEE GP
voltage then be
Wednesday, Mayincreased
19, 2021 to rated value gradually
AMRAVATI
60
MAINTENANCE OF TRANSFORMER
• Transformer is the heart of any power
system. Hence preventive maintenance is
always cost effective and time saving. Any
failure to the transformer can extremely
affect the whole functioning of the
organization.