Professional Documents
Culture Documents
Government of India
रे ल मं ा ल य Ministry of Railways
रे ल ड बा का र खा ना Rail
ail Coach Factory
क पु र थ ला Kapurthala
urthala
पं जा ब 1 4 4 6 0 2 RCF Punjab
unjab 144602
ESTT: 1986
था प त : 1 9 8 6
KAPURTHALA
Brief Description
Water based Portable Fire Extinguisher
© RCF/KXH 2021
FOREWORD
This technical requirements laid down general / technical , testing requirements of 6 litter
stored pressurised water based portable fire extinguishers to be fitted in passenger
coaches of Indian Railways.
DISCLAIMER
This specification is based on the studies, trials& experience by RCF/KXH. Although
every care is taken in specifying details adequately and unambiguously, RCF/KXH shall
not liable for any kind of damages / losses incurred by any and all due to errors or
omissions in this document. When using the information described herein, the user is
ultimately responsible for their own actions, as well as the actions of subordinates and
assistants, and the consequences arising therefrom.
This document may mention numerous commercial and proprietary trade names,
registered trademarks and the like (not necessarily marked as such), patents, production
and manufacturing procedures, registered designs, and designations. RCF wishes to
state clearly that the present legal situation in respect of these names or designations or
trademarks must be carefully examined before making any commercial use of the same.
Names of industrially produced apparatus and equipment may be included to a
necessarily restricted extent only and any exclusion of products not mentioned in this
document does not imply that any such exclusion has been based on quality criteria or
any other qualifying consideration.
COPYRIGHT
RCF/KXH has the copyright of all its publications. No part of these publications may be
reproduced in any form without the prior permission of RCF. Enquires relating to the
copyright should be addressed to Public Relations Officer, RCF/KXH.
Specification Title: SCHEDULE OF TECHNICAL REQUIREMENTS FOR 6 LITERS STORED PRESSURE TYPE WATER BASED PORTABLE FIRE
EXTINGUISHER
DOCUMENT CONTROL
LIST OF AMENDMENTS
Printed: 2021/04/30
RAIL COACH FACTORY, KAPURTHALA, PUNJAB 144602
Page 1 of 5
Document No: MDTS-46352 Revision No:0 Date Issued: 30/04/2021
Specification Title: SCHEDULE OF TECHNICAL REQUIREMENTS FOR 6 LITERS STORED PRESSURE TYPE WATER BASED PORTABLE FIRE
EXTINGUISHER
CONTENTS
1 Genral ....................................................................................................................................................3
2 Description of Fire Extinguisher ............................................................................................................3
3 Prototype Approval ................................................................................................................................4
4 Classsification of Tests ..........................................................................................................................4
5 Warranty ................................................................................................................................................5
1. IS:15683-2018
Printed: 2021/04/30
RAIL COACH FACTORY, KAPURTHALA, PUNJAB 144602
Page 2 of 5
Document No: MDTS-46352 Revision No:0 Date Issued: 30/04/2021
Specification Title: SCHEDULE OF TECHNICAL REQUIREMENTS FOR 6 LITERS STORED PRESSURE TYPE WATER BASED PORTABLE FIRE
EXTINGUISHER
1. General:
a. This specification covers general & technical requirements of water based fire
extinguishers to be provided in passenger coaches of Indian Railway.
b. While quoting, the supplier shall submit the following details:
i. The fire extinguisher should be Stored pressure type water based of 6 liters capacity &
shall be useable on Class A,B & F of fires. The details requirements should be as per
Table-1.
Table-1
S.No. Description Parameters
1 Capacity 6 Liters
2 Standard specification IS:15683:2018
3 Extinguishing medium Water Based
4 Fire rating (Minimum) 3A
5 Minimum effective discharge time 13 seconds (minimum)
6 Percentage of discharge 90% ( Min)
7 Service pressure <= 15 bar Max
8 Propellant Nitrogen
9 Dia of cylinder ( Max) 180 mm
Printed: 2021/04/30
RAIL COACH FACTORY, KAPURTHALA, PUNJAB 144602
Page 3 of 5
Document No: MDTS-46352 Revision No:0 Date Issued: 30/04/2021
Specification Title: SCHEDULE OF TECHNICAL REQUIREMENTS FOR 6 LITERS STORED PRESSURE TYPE WATER BASED PORTABLE FIRE
EXTINGUISHER
vi. The release discharge from extinguisher shall be uniform without any pressure
drop.
vii. The fire extinguisher cylinder shall withstand hydrostatic pressure upto 35 bar (
3.5 Mpa) and OEM has to submit hydrostatic pressure testing certificate for the
same.
viii. The fire extinguisher shall be provided with pressure gauge compiling parameters
laid down as per IS: 15683-2018.
ix. The extinguisher should have a controllable discharge mechanism (Discharge
hose, siphon tube, discharge nozzle etc) as per IS:15683-2018 to provide
flexibility of releasing extinguishing agent on targeted fire location.
3. Prototype approval:
The firm, who has not got their prototype sample approved earlier, shall submit
following documents for prototype approval from CDE/RCF for only PO placed by
RCF, before bulk supply:
The prototype and drawings shall be examined from all view points and supplier shall
incorporate modifications suggested by RCF on the basis of this review of prototype
and drawings. Only after getting approval of drawings and prototype from CDE, the
firm can undertake bulk supply.
The prototype approval is applicable on the first supply of material as per this
specification from a supplier. RCF will do prototype approval for POs placed by RCF
only. Approval for PO placed by Railways is to be done by them.
4. Classification of Test:
Printed: 2021/04/30
RAIL COACH FACTORY, KAPURTHALA, PUNJAB 144602
Page 4 of 5
Document No: MDTS-46352 Revision No:0 Date Issued: 30/04/2021
Specification Title: SCHEDULE OF TECHNICAL REQUIREMENTS FOR 6 LITERS STORED PRESSURE TYPE WATER BASED PORTABLE FIRE
EXTINGUISHER
a. Type test : Schedule of testing of fire extinguishers shall be carried out as per
Annexure –D of product manual for portable fire extinguishers- performance
and construction as per PM/IS:15683/1/March-2019 for parameters in this
specification & applicable parameters in IS:15683-2018. The firm shall
submit BIS certification of the same.
b. Acceptance Tests: Tests mentioned in Annexure –E of product manual for
portable fire extinguishers-performance and construction as per PM/
IS:15683/1/March-2019. BIS approval with ISI mark approval of the product,
specifying of fire rating, capacity, extinguishing medium, overall height and
dia. of cylinder are to be checked.
5. Warranty: The manufacturer shall submit 5 years warranty on the fire extinguishers
for failing or proving unsatisfactory in service due to defective deign, material or
workmanship and shall replace the same at his own cost and risk.
Printed: 2021/04/30