Professional Documents
Culture Documents
BULLETIN
Current situation
Wärtsilä RT-flex and RTA diesel engines
which are operated at continuous low load
(below 60% CMCR).
Solutions
To limit the adverse effects of continuous
low load operation as much as possible, a
series of recommendations are described
in this Technical Bulletin.
Reference
This document is only valid for RT-flex and
RTA engines. For engines of newer
generations, (RT-flex50-D, RT-flex58T-E,
X-type and DF engines), please refer to the
latest issue of the Technical Bulletin
RT-235, named “Continuous low load
operation (slow steaming)”.
Note
This Technical Bulletin supersedes Service
Bulletin RT-174 Issue 2, dated 22.01.2020
entitled “Continuous Low Load Operation
(Slow Steaming)” due to the revision of
application scope, additional chapter for
RT-flex engines.
* At your convenience: Action is necessary or recommended, but can be taken at your convenience, for example
during maintenance.
Contents
Page
1 Introduction 2
2 Recommendations for Low load operation 3
3 Cylinder cooling water outlet temperature 4
4 Reference to other related documents 5
5 Improve engine performance and running behaviour for Slow Steaming Upgrade Kit
(SSUK) 6
6 Improve engine performance and running behaviour Retrofit Pulse Lubrication
System (RPLS) 6
7 Contacts 7
1 Introduction
NOTE:
This Technical Bulletin supersedes Service Bulletin RT-174 Issue 2
dated 22.01.2020 entitled “Continuous low load operation (slow steaming)”.
Wärtsilä RT-flex and RTA engines are optimised for operation in the load range above
approximately 60% CMCR. Continuous running at lower loads down to 10% CMCR is
possible, but only with special care.
© 2021 Wärtsilä Services Switzerland Ltd – All rights reserved – Please read the complete disclaimer at the end of this
document.
TECHNICAL BULLETIN
3. The exhaust gas temperature at cylinders’ outlets should be kept above 250 °C to
avoid cold corrosion, fouling of exhaust gas receiver and turbocharger nozzle ring. If
the exhaust gas temperature drops below this value, the engine power should be
increased if feasible.
4. If the exhaust gas temperature gets too high (>450 °C at cylinders’ outlets) the
auxiliary blower may be switched to “continuous running”. However, it must be noted
that not all auxiliary blowers and circuit breakers may be suitable for continuous
operation at electrical loads above nominal current. This shall be checked with the
respective maker.
6. Inspect and lubricate the bearings of the auxiliary blowers more frequently if
considered necessary due to more frequent operation of the blower. The flaps in the
scavenging air receiver shall be inspected more frequently.
© 2021 Wärtsilä Services Switzerland Ltd – All rights reserved – Please read the complete disclaimer at the end of this
document.
TECHNICAL BULLETIN
8. Exhaust manifold and other related components (scavenge air receiver, exhaust
gas valves, turbocharger grid, etc.) need more frequent inspections and possible
cleaning. Depending on results of inspections, the regular engine load-up intervals
might be adapted if no excessive deposit accumulations is detected.
9. An economiser with closely-spaced fins may also require more frequent soot
blowing.
© 2021 Wärtsilä Services Switzerland Ltd – All rights reserved – Please read the complete disclaimer at the end of this
document.
TECHNICAL BULLETIN
ATTENTION:
The temperature settings mentioned in Table 2 are valid for all RTA engines with the
exception of RTA82C, RTA82T, RTA84C, RTA84T, RTA84T-B, RTA84T-D, RTA96C
and RTA96C-B. For these engines see Table on the next page.
© 2021 Wärtsilä Services Switzerland Ltd – All rights reserved – Please read the complete disclaimer at the end of this
document.
TECHNICAL BULLETIN
In order to further optimize the engine operation at low load, Wärtsilä has developed A
Slow Steaming Upgrade Kit that involves cutting out of a turbocharger. This increases
the scavenge air delivery at low load for better combustion and more optimum
temperatures of engine components.
Wärtsilä Services Switzerland Ltd offers the following Slow Steaming Upgrade Kit
(SSUK) solutions:
• Permanent blinding
• Removable blinding
• Butterfly valves
o Pneumatic local control
o Full Automation
With the Slow Steaming Upgrade Kit SSUK the following is achieved:
• With the increased scavenge air pressure the auxiliary blower on/off threshold is at
lower loads compared to engines with all turbochargers operative.
• A considerable reduction in BSFC with cut out turbocharger and increased scavenge
air pressure in the low-load range.
• Due to better combustion at lower loads the risk of turbocharger and economizer
fouling is decreased and the formation of deposits due to unburnt fuel is reduced.
The time interval between engine load-up to burn off carbon deposits can be increased
based on inspection results. In order to burn off the deposits a high enough exhaust gas
temperature at turbine inlet is needed. The engine needs to be loaded up until the
exhaust gas temperature at turbine inlet corresponds to 380°C. If this temperature is not
possible to reach, the engine needs to be loaded up to the maximum load that can be
reached with one turbocharger cut-out (See Technical Bulletin RT-162, Operational limits
with turbocharger cut out).
In combination with the above described SSUK, Wärtsilä recommends the installation of
electronically controlled cylinder lubrication.
© 2021 Wärtsilä Services Switzerland Ltd – All rights reserved – Please read the complete disclaimer at the end of this
document.
TECHNICAL BULLETIN
7 Contacts
7.1 How to contact Wärtsilä
For questions about the content of this Technical Bulletin, or if you need Wärtsilä
assistance, services, spare parts and/or tools, please contact your nearest Wärtsilä
representative.
If you do not have the contact details at hand, please follow the link:
www.wartsila.com/contact