OBCAL SHEET

ULR No.: XXX Page 1 of XX


Test Report No.: XXX Issue Date: XXX
Discipline: Electrical Testing Group: Power Supplies & Stabilizers
Name of Customer
XXXX
(Report Issued To):
XXXXX
Name of Manufacturer:
XXXXX
Item Description: Utility-interconnected Photovoltaic Inverters (Grid-tied Solar Inverter)
Sample Condition: Fit for testing
Model Tested: iMars XG60KTR F012210040023 &
Serial No.:
Identification: Series Model(s): iMars XG60KTR-S, iMars XG50KTR, F012210040024
iMars XG50KTR-S Sample Code: 22E4636N
Sample Deposited/Collected by: XXX
Reference no. Nil Date: XXX
Date of
Job Order No.: BTH-R1/EL/2211206/4 06/12/2022
receipt:
Date(s) of performance of tests: 07/12/2022 to 09/03/2023
BHARAT TEST HOUSE PVT. LTD.
Laboratory Name and Address: 1474, HSIIDC Indl. Estate, Rai,
Distt. Sonepat-131029 Haryana (QR code)
Test Location: At lab
Test specification(s): IS 16169: 2014/IEC 62116:2008
General Environmental Conditions: Temperature: 27±2°C, Relative Humidity: 65±5%RH
Result: The Sample conforms the relevant test specification as per below result.
Notes: XXX
Supplementary Information: a) Sampling procedure: Nil
b) Supporting documents for the measurements taken and results derived like graphs, tables, sketches
and/or photographs as appropriate to test report, if any: Nil
c) Deviation from the test methods as prescribed in relevant ISS/Work Instructions: Nil
d) The information supplied by the customer may affect the validity of results reported as per standard
requirement.
Abbreviations: N/A – Not Applicable.
Remarks:

1. Series Model(s): iMars XG60KTR-S, iMars XG50KTR, iMars XG50KTR-S; Brand/Trademark: are in the same product family

and can be undertaken in series with Model Tested: iMars XG60KTR; Trademark: . All the tests have been performed on
Model: iMars XG60KTR (worst case).
The Results are related to the sample submitted.

Tested by: Reviewed by: Authorized by:

Testing Engineer/Analyst Lab in-charge/TM/QM/Dy.QM Lab in-charge/TM/QM/Dy.QM


Date: Date: Date:

BTHPL/OBCAL/EL/GEN/UIPVI/040222_V1.1

Tested By : ARIF JAMAL Approved By : VAIBHAV GUPTA


Date Uploaded : 09/03/2023 Date Approved : 09/03/2023
Job Order No. BTH-R1/EL/2211206/4 IS 16169: 2014/IEC 62116:2008 Page : 2 of 21

Protocol followed as per IS 16169: 2014/IEC 62116: 2008


Test Procedure of Islanding Prevention Measures for Utility-Interconnected
- Photovoltaic Inverters
Report Reference No. ...................................: XXX
Date of issue ..................................................: XXX
Total number of pages ................................... XX
Testing Laboratory ........................................: BHARAT TEST HOUSE PVT. LTD.
Address ..........................................................: 1474, HSIIDC Indl. Estate, Rai,
Distt. Sonepat-131001 Haryana.
Customer/Manufacturer’s name ................ : XXX
Address ..........................................................: XXX
XXX
Test specification:
Standard ........................................................: IS 16169: 2014/IEC 62116: 2008
Test procedure ..............................................: Compliance Report
Non-standard test method…………..: N/A
Test Report Form No. ...................................: IS 16169/IEC 62116:2008_V1.0
Test Report Form(s) Originator .....................: BIS
Master TRF ....................................................: Dated: 05.04.2018
Test item description ....................................: Utility-interconnected Photovoltaic Inverters (Grid-tied Solar Inverter)
Trade Mark ....................................................:

Manufacturer.............................................: XXX
Factory..........................................................: XXX
Model/Type reference ..................................: Model Tested: iMars XG60KTR
Series Model(s): iMars XG60KTR-S, iMars XG50KTR, iMars XG50KTR-S
Ratings ...........................................................: As Indicated in marking label (refer page no. 4)

Tested by: Approved by / Authorized Signatory:

Testing Engineer/Analyst Lab in-charge/TM/QM/Dy.QM


Date: Date:

Tested by: Reviewed by:

BTHPL/OBCAL/EL/GEN/UIPVI/040222_V1.1

Tested By : ARIF JAMAL Approved By : VAIBHAV GUPTA


Date Uploaded : 09/03/2023 Date Approved : 09/03/2023
Job Order No. BTH-R1/EL/2211206/4 IS 16169: 2014/IEC 62116:2008 Page : 3 of 21

Summary of testing:
Tests performed (name of test and test clause): Testing location:
All Applicable tests BHARAT TEST HOUSE PVT. LTD.
1474, HSIIDC Indl. Estate, Rai,
Distt. Sonepat-131001 Haryana.
Unintensional Islanding

Tested by: Reviewed by:

BTHPL/OBCAL/EL/GEN/UIPVI/040222_V1.1

Tested By : ARIF JAMAL Approved By : VAIBHAV GUPTA


Date Uploaded : 09/03/2023 Date Approved : 09/03/2023
Job Order No. BTH-R1/EL/2211206/4 IS 16169: 2014/IEC 62116:2008 Page : 4 of 21

Copy of marking plate:


Model Tested: iMars XG60KTR

Tested by: Reviewed by:

BTHPL/OBCAL/EL/GEN/UIPVI/040222_V1.1

Tested By : ARIF JAMAL Approved By : VAIBHAV GUPTA


Date Uploaded : 09/03/2023 Date Approved : 09/03/2023
Job Order No. BTH-R1/EL/2211206/4 IS 16169: 2014/IEC 62116:2008 Page : 5 of 21

1st code Inverter standard F Non-standard model


2nd & 3rd code Company code & 01 Shenzhen INVT Electric Co., Ltd. Bao'an Branch
address F1-F4, NO.3 BUILDING, EMERSON INDUSTRIAL PARK, FENGTANG ROAD,
TANGWEI COMMUNITY, FUHAI, BAO’AN DISTRICT, SHENZHEN,
GUANGDONG, 518103
4th & 5th code Year of manufacture 22 2022
6th & 7th code Month of manufacture 10 October
8th & 9th code Date of manufacture 04 04
10th to 13th code Serial code 0023 & 0024 Serial numbers

(Warning label)

Tested by: Reviewed by:

BTHPL/OBCAL/EL/GEN/UIPVI/040222_V1.1

Tested By : ARIF JAMAL Approved By : VAIBHAV GUPTA


Date Uploaded : 09/03/2023 Date Approved : 09/03/2023
Job Order No. BTH-R1/EL/2211206/4 IS 16169: 2014/IEC 62116:2008 Page : 6 of 21

Series Model: : iMars XG60KTR-S Series Model: : iMars XG50KTR

Tested by: Reviewed by:

BTHPL/OBCAL/EL/GEN/UIPVI/040222_V1.1

Tested By : ARIF JAMAL Approved By : VAIBHAV GUPTA


Date Uploaded : 09/03/2023 Date Approved : 09/03/2023
Job Order No. BTH-R1/EL/2211206/4 IS 16169: 2014/IEC 62116:2008 Page : 7 of 21

Series Model No. : iMars XG50KTR-S

Tested by: Reviewed by:

BTHPL/OBCAL/EL/GEN/UIPVI/040222_V1.1

Tested By : ARIF JAMAL Approved By : VAIBHAV GUPTA


Date Uploaded : 09/03/2023 Date Approved : 09/03/2023
Job Order No. BTH-R1/EL/2211206/4 IS 16169: 2014/IEC 62116:2008 Page : 8 of 21

GENERAL INFORMATION
Test item particulars.....................................................................: Utility-interconnected Photovoltaic Inverters (Grid-tied Solar Inverter)
Accessories and detachable parts included in the evaluation.......: N/A
Options included.............................................................................: N/A
Abbreviations used in the report: See below
EUT – Equipment Under Test MPPT – Maximum Power Point Tracking
Qf – Quality factor W – Utility Real Power
Var – Utility Reactive Power VDC – DC Voltage
VEUT - AC voltage of EUT TR – Run on time
IR – Resistive load current IL – Inductive load current
IC – Capacitive load current PAC – Utility Real Power
QAC – Utility Reactive Power IAC - Utility Current
Possible test case verdicts:
- test case does not apply to the test object ……………………………….: N/A
- test object does meet the requirement …………………………………..: Pass (P)
- test object does not meet the requirement ……………………………..: Fail (F)
Differences between the models:
Model Specification Model Differences Model Similarities
As Indicated in marking label
iMars XG60KTR Model designation, 1) Same rated Input/ Output voltage
(refer page no. 4)
DC Input Max. Current, 2) Same frequency and No. of Phases at
As Indicated in marking label Isc PV. output
iMars XG60KTR-S
(refer page no. 6) 3) Same PCB design and layout
4) Same power stage topology
As Indicated in marking label Model designation,
iMars XG50KTR DC Input Max. Current, 5) Same insulation class
(refer page no. 6)
Isc PV, 6) Same control algorithm/ firmware
7) Same cabinet design and class of
As Indicated in marking label AC Output Max. Current,
iMars XG50KTR-S Rated Power, construction
(refer page no. 7)
Max. Output Power,
Model tested with-in the family series: iMars XG60KTR

General remarks:
The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing testing laboratory.
"(see Enclosure #)" refers to additional information appended to the report.
"(see appended table)" refers to a table appended to the report.
Throughout this report a point is used as the decimal separator.
Measurement of uncertainty reported is 1.28%.

Tested by: Reviewed by:

BTHPL/OBCAL/EL/GEN/UIPVI/040222_V1.1

Tested By : ARIF JAMAL Approved By : VAIBHAV GUPTA


Date Uploaded : 09/03/2023 Date Approved : 09/03/2023
Job Order No. BTH-R1/EL/2211206/4 IS 16169: 2014/IEC 62116:2008 Page : 9 of 21

General Product Information:


Product Electrical Ratings

Parameter Value Remarks


1) Rating -
a) Maximum output power VA 60000W -
b) DC voltage range Vdc 200-1000 -
c) DC current limits Adc 39/39/39/39 -
d) AC voltage range Vac 230/400 -
e) Frequency range Hz 50/60 -
f) AC current limits Aac 95.6 -
g) Efficiency % 98.80 -
h) Voltage trip settings Under voltage: 196V,1.9s
V -
(magnitude and timing) Over Voltage: 254V,1.9s
i) Frequency trip settings Under Frequency: 49Hz,0.2s
V -
(magnitude and timing) Over Frequency: 51Hz,0.2s
j) Other software settings Refer user manual# -
k) Firmware version - V1.0 -
2) Others - - -
a) Displays - LCD -
b) Temperature range °C -30°C~ 60°C -
c) Relative Humidity %RH 0-100% -
d) Size mm 650x450x260 (mm×mm×mm) -
e) Weight Kg 50 -

Tested by: Reviewed by:

BTHPL/OBCAL/EL/GEN/UIPVI/040222_V1.1

Tested By : ARIF JAMAL Approved By : VAIBHAV GUPTA


Date Uploaded : 09/03/2023 Date Approved : 09/03/2023
Job Order No. BTH-R1/EL/2211206/4 IS 16169: 2014/IEC 62116:2008 Page : 10 of 21

Clause Requirement + Test Result - Remark Verdict


4 Testing circuit P
The testing circuit shown in Figure 1 is employed. Complied P
Similar circuits are used for three-phase output. Complied P
Parameters to be measured are shown in Table 1 and Figure 1.
Refer to Cl.7 P
Parameters to be recorded in the test report are discussed in Clause 7.
5 Testing equipment P
5.1 Measuring instruments See below P
The waveform measurement/capture device is able to record the
Digital oscilloscope is used to measure
waveform from the beginning of the islanding test until the EUT ceases P
waveform
to energize the island.
For multi-phase EUT, all phases are monitored. Complied P
A waveform monitor designed to detect and calculate the run-on time
Complied P
may be used.
For multi-phase EUT, the test and measurement equipment is
recorded each phase current and each phase-to-neutral or phase-to-
Complied P
phase voltage, as appropriate, to determine fundamental frequency
active and reactive power flow over the duration of the test.
A sampling rate of 10 kHz or higher is recommended. The minimum
measurement accuracy is 1 % or less of rated EUT nominal output Complied P
voltage and 1 % or less of rated EUT output current
Current, active power, and reactive power measurements through
switch S1 used to determine the circuit balance conditions report the Complied P
fundamental (50 Hz or 60 Hz) component.
5.2 DC power source P
5.2.1 General See below P
A PV array or PV array simulator (preferred) may be used. If the EUT
can operate in utility-interconnected mode from a storage battery, a
DC power source may be used in lieu of a battery as long as the DC DC power source is used P
power source is not the limiting device as far as the maximum EUT
input current is concerned.
The DC power source provides voltage and current necessary to meet
Complied P
the testing requirements described in Clause 6.
5.2.2 PV array simulator DC power source is used N/A
The tests are conducted at the input voltage defined in Table 2 below,
and the current is limited to 1,5 times the rated photovoltaic input N/A
current, except when specified otherwise by the test requirements.
A PV array simulator is recommended, however, any type of power
N/A
source may be used if it does not influence the test results.

Tested by: Reviewed by:

BTHPL/OBCAL/EL/GEN/UIPVI/040222_V1.1

Tested By : ARIF JAMAL Approved By : VAIBHAV GUPTA


Date Uploaded : 09/03/2023 Date Approved : 09/03/2023
Job Order No. BTH-R1/EL/2211206/4 IS 16169: 2014/IEC 62116:2008 Page : 11 of 21

5.2.3 Current and voltage limited DC power supply with series resistance See below P
A DC power source used as the EUT input source is capable of EUT
maximum input power (so as to achieve EUT maximum output power) Complied P
at minimum and maximum EUT input operating voltage.
The power source provides adjustable current and voltage limit, set to
provide the desired short circuit current and open circuit voltage when Complied P
combined with the series and shunt resistance described below.
A series resistance (and, optionally, a shunt resistance) is selected to
provide a fill factor within the range:
Output power: Sufficient to provide maximum EUT output power and
other levels specified by test conditions of table 5.
Response speed: The response time of a simulator to a step in output
voltage, due to a 5% load change, results in a settling of the output
current to within 10% of its final value in less than 1ms. Complied P
Stability: Excluding the variations caused by the EUT MPPT, simulator
output power remains stable within 2 % of specified power level over
the duration of the test: from the point where load balance is
achieved until the island condition is cleared or the allowable run-on
time is exceeded.
Power factor: 0.25 to 0.8
5.2.4 PV array DC power source is used N/A
A PV array used as the EUT input source is capable of EUT maximum
N/A
input power at minimum and maximum EUT input operating voltage.
Testing is limited to times when the irradiance varies by no more than
2 % over the duration of the test as measured by a silicon-type
pyranometer or reference device. It may be necessary to adjust the N/A
array configuration to achieve the input voltage and power levels
prescribed in 6.1.
5.3 AC power source P
The utility grid or other AC power source may be used as long as it
meets the conditions specified in Table 4.
Table 4 – Ac power source requirements
Items Conditions
Voltage Nominal ± 2.0 % Utility Grid is used P
Voltage THD < 2.5 %
Frequency Nominal ± 0.1 Hz
Phase angle distance 1) 120° ± 1.5°
1) Three-phase case only

5.4 AC loads P
On the AC side of the EUT, variable resistance, capacitance, and
inductance are connected in parallel as loads between the EUT and
Complied P
the AC power source. Other sources of load, such as electronic loads,
may be used if it can be shown that the source does not cause results

Tested by: Reviewed by:

BTHPL/OBCAL/EL/GEN/UIPVI/040222_V1.1

Tested By : ARIF JAMAL Approved By : VAIBHAV GUPTA


Date Uploaded : 09/03/2023 Date Approved : 09/03/2023
Job Order No. BTH-R1/EL/2211206/4 IS 16169: 2014/IEC 62116:2008 Page : 12 of 21

that are different than would be obtained with passive resistors,


inductors, and capacitors.
All AC loads are rated for and adjustable to all test conditions. The
equations for Qf are based upon an ideal parallel RLC circuit. For this
reason, non-inductive resistors, low loss (high Qf) inductors, and
capacitors with low effective series resistance and effective series
inductance are utilized in the test circuit. Iron core inductors, if used,
Complied P
are not exceed a current THD of 2 % when operated at nominal
voltage. Load components are conservatively rated for the voltage and
power levels expected. Resistor power ratings are chosen so as to
minimize thermally-induced drift in resistance values during the
course of the test.
Active and reactive power is calculated (using the measurements
provided in Table 1) in each of the R, L and C legs of the load so that
Complied P
these parasitic parameters (and parasitic introduced by variacs or
autotransformers) are properly accounted for when calculating Qf.
6 Test for single or multi-phase inverter P
6.1 Test procedure See low P
The test uses an RLC load, resonant at the EUT nominal frequency (50
Satisfactory P
Hz or 60 Hz) and matched to the EUT output power.
For multi-phase EUT, the load is balanced across all phases and the
Complied P
switch S1 as in Figure 1 opens all phases
This test is performed with the EUT conditions as in Table 5, where
power and voltage values are given as a percent of EUT full output See below P
rating.
a) Determine EUT test output power See table 6.1 P
b) Adjusting the DC input source See table 6.1 P
c) Turn off the EUT and open S1 See table 6.1 P
d) Adjust the RLC circuit to have Qf = 1.0 ± 0.05 See table 6.1 P
e) Connect the RLC load configured in step d) to the EUT by closing S2 See table 6.1 P
f) Open the utility-disconnect switch S1 to initiate the test, Run-on
See table 6.1 P
time is recorded.
g). For test condition A, adjust the real load and only one of the
reactive load components to each of the load imbalance conditions
shown in the shaded portion of table 6. If any of the recorded run-on
See table 6.1 P
times are longer than the one recorded for the rated balance
condition, then the non-shaded parameter combinations also require
testing.
h) For test condition B and C, adjust the only one reactive load
components by approximately 1,0% per test, within a total range of
95% to 105% of the operating point. If run-on times are still increasing See table 6.1 P
at the 95% or 105% points, additional 1% increments have to be taken
until run-on times begin decreasing.
Tested by: Reviewed by:

BTHPL/OBCAL/EL/GEN/UIPVI/040222_V1.1

Tested By : ARIF JAMAL Approved By : VAIBHAV GUPTA


Date Uploaded : 09/03/2023 Date Approved : 09/03/2023
Job Order No. BTH-R1/EL/2211206/4 IS 16169: 2014/IEC 62116:2008 Page : 13 of 21

6.2 Pass/fail criteria P


An EUT is considered to comply with the requirements for islanding
Complied
protection when each case of recorded run-on time is less than 2 s or P
(See table 6.1)
meets the requirements of local codes.
7 Documentation P
At a minimum, the following information is recorded and maintained
See below P
in the test report.
a) Specifications of EUT. Table 8 provides an example of the type of
Refer page no. 7 P
information that is provided.
b) Measurement results. Table 9 provides an example of the type of
information that is provided. Actual measured values is to be See table 6.1 P
recorded.
c) Block diagram of test circuit. See Page no. 18 P
d) Specifications of the test and measurement equipment. Table 10
Complied P
provides an example of the type of information that is provided.
e) Any test configuration or procedure details such as methods of
P
achieving specified load and EUT output conditions.
f) Any additional information required by the testing laboratory's
N/A
accreditation.
g) Specify the evaluation criterion from clause 6.2 that was utilized to
Complied with criteria P
determine if the product passed or failed the test.
Annex A Islanding as it applies to PV systems (Informative) P
A.1 General Complied P
A.2 Impact of distortion on islanding P
Annex B Test for independent islanding detection device (relay)(Informative) N/A
B.1 Introduction No such construction N/A
B.2 Testing circuit N/A
B.3 Testing equipment N/A
B.4 Testing procedure N/A
B.5 Documentation N/A

Tested by: Reviewed by:

BTHPL/OBCAL/EL/GEN/UIPVI/040222_V1.1

Tested By : ARIF JAMAL Approved By : VAIBHAV GUPTA


Date Uploaded : 09/03/2023 Date Approved : 09/03/2023
Job Order No. BTH-R1/EL/2211206/4 IS 16169: 2014/IEC 62116:2008 Page : 14 of 21

6.1 Table: Tested condition and run-on time


PEUT a
Reactive PAC b (% QAC b Run on/ Pc
(% of PEUT Pr (resistive) Pl (Inductive)
S. No. load (% of/ (% of/ time (Capacitive) Actual QF VDC Remarks
EUT/ (KW) KW Kvar
of QL) nominal) nominal) (ms) Kvar
rating)
L1: 19.981 L1: 19.971 L1: 20.025 L1: 1.001
1 100 100 0 0 24.0 60.0 L2: 20.076 L2: 19.972 L2: 20.108 L2: 0.998 742 BL
L3: 20.108 L3: 20.043 L3: 20.146 L3: 0.999
L1: 13.241 L1: 13.251 L1: 13.181 L1: 0.998
2 66 66 0 0 16.8 40.0 L2: 13.157 L2: 13.204 L2: 13.174 L2: 1.002 500 BL
L3: 13.269 L3: 13.186 L3: 13.275 L3: 0.997
L1: 6.612 L1: 6.631 L1: 6.627 L1: 1.003
3 33 33 0 0 26.4 20.0 L2: 6.633 L2: 6.627 L2: 6.608 L2: 0.998 255 IB
L3: 6.604 L3: 6.612 L3: 6.624 L3: 1.002
L1: 20.982 L1: 20.972 L1: 20.022 L1: 0.977
4 100 100 -5 -5 19.2 60.0 L2: 21.078 L2: 20.970 L2: 20.108 L2: 0.974 742 IB
L3: 21.115 L3: 21.045 L3: 20.146 L3: 0.975
L1: 20.977 L1: 19.971 L1: 20.024 L1: 0.953
5 100 100 -5 0 20.4 60.0 L2: 21.080 L2: 19.970 L2: 20.108 L2: 0.951 742 IB
L3: 21.112 L3: 20.043 L3: 20.147 L3: 0.952
L1: 20.980 L1: 18.974 L1: 20.025 L1: 0.929
6 100 100 -5 5 18.6 60.0 L2: 21.082 L2: 18.973 L2: 20.110 L2: 0.927 742 IB
L3: 21.110 L3: 19.041 L3: 20.146 L3: 0.928
L1: 19.982 L1: 20.971 L1: 20.024 L1: 1.026
7 100 100 0 -5 16.2 60.0 L2: 20.076 L2: 20.971 L2: 20.109 L2: 1.023 742 IB
L3: 20.108 L3: 21.046 L3: 20.146 L3: 1.024
L1: 19.982 L1: 18.971 L1: 20.023 L1: 0.975
8 100 100 0 5 12.6 60.0 L2: 20.077 L2: 18.973 L2: 20.109 L2: 0.973 742 IB
L3: 20.108 L3: 19.041 L3: 20.146 L3: 0.974
L1: 18.980 L1: 20.972 L1: 20.023 L1: 1.080
9 100 100 5 -5 24.0 60.0 L2: 19.071 L2: 20.970 L2: 20.109 L2: 1.077 742 IB
L3: 19.103 L3: 21.043 L3: 20.146 L3: 1.078
L1: 18.985 L1: 19.971 L1: 20.024 L1: 1.053
10 100 100 5 0 12.2 60.0 L2: 19.072 L2: 19.974 L2: 20.105 L2: 1.051 742 IB
L3: 19.104 L3: 20.042 L3: 20.147 L3: 1.052
L1: 18.979 L1: 18.975 L1: 20.021 L1: 1.027
11 100 100 5 5 22.0 60.0 L2: 19.070 L2: 18.974 L2: 20.111 L2: 1.024 742 IB
L3: 19.101 L3: 19.040 L3: 20.146 L3: 1.025
L1: 21.981 L1: 17.974 L1: 20.023 L1: 0.863
12 100 100 -10 10 18.6 60.0 L2: 22.086 L2: 17.975 L2: 20.109 L2: 0.861 742 IB
L3: 22.121 L3: 18.041 L3: 20.144 L3: 0.862
L1: 20.981 L1: 17.974 L1: 20.025 L1: 0.904
13 100 100 -5 10 24.0 60.0 L2: 21.079 L2: 17.976 L2: 20.108 L2: 0.902 742 IB

Tested by: Reviewed by:

BTHPL/OBCAL/EL/GEN/UIPVI/040222_V1.1

Tested By : ARIF JAMAL Approved By : VAIBHAV GUPTA


Date Uploaded : 09/03/2023 Date Approved : 09/03/2023
Job Order No. BTH-R1/EL/2211206/4 IS 16169: 2014/IEC 62116:2008 Page : 15 of 21

L3: 21.113 L3: 18.040 L3: 20.146 L3: 0.903


L1: 19.981 L1: 17.974 L1: 20.025 L1: 0.949
14 100 100 0 10 26.2 60.0 L2: 20.077 L2: 17.975 L2: 20.107 L2: 0.947 742 IB
L3: 20.110 L3: 18.041 L3: 20.144 L3: 0.948
L1: 17.983 L1: 17.976 L1: 20.026 L1: 1.055
15 100 100 10 10 20.6 60.0 L2: 18.067 L2: 17.975 L2: 20.109 L2: 1.052 742 IB
L3: 18.097 L3: 18.042 L3: 20.146 L3: 1.053
L1: 17.983 L1: 18.970 L1: 20.027 L1: 1.084
16 100 100 10 5 20.0 60.0 L2: 18.069 L2: 18.974 L2: 20.110 L2: 1.081 742 IB
L3: 18.097 L3: 19.041 L3: 20.144 L3: 1.082
L1: 17.980 L1: 19.971 L1: 20.025 L1: 1.112
17 100 100 10 0 18.8 60.0 L2: 18.068 L2: 19.969 L2: 20.107 L2: 1.109 742 IB
L3: 18.095 L3: 20.043 L3: 20.146 L3: 1.110
L1: 17.984 L1: 20.970 L1: 20.024 L1: 1.139
18 100 100 10 -5 22.0 60.0 L2: 18.069 L2: 20.971 L2: 20.108 L2: 1.136 742 IB
L3: 18.098 L3: 21.045 L3: 20.143 L3: 1.138
L1: 17.983 L1: 21.970 L1: 20.026 L1: 1.166
19 100 100 10 -10 32.2 60.0 L2: 18.068 L2: 21.972 L2: 20.108 L2: 1.163 742 IB
L3: 18.097 L3: 22.044 L3: 20.144 L3: 1.164
L1: 18.982 L1: 21.969 L1: 20.024 L1: 1.105
20 100 100 5 -10 22.8 60.0 L2: 19.070 L2: 21.968 L2: 20.108 L2: 1.102 742 IB
L3: 19.104 L3: 22.047 L3: 20.146 L3: 1.103
L1: 19.981 L1: 21.968 L1: 20.022 L1: 1.050
21 100 100 0 -10 12.2 60.0 L2: 20.077 L2: 21.973 L2: 20.109 L2: 1.047 742 IB
L3: 20.108 L3: 22.046 L3: 20.146 L3: 1.048
L1: 20.981 L1: 21.968 L1: 20.025 L1: 1.000
22 100 100 -5 -10 22.6 60.0 L2: 21.080 L2: 21.969 L2: 20.108 L2: 0.997 742 IB
L3: 21.112 L3: 22.049 L3: 20.144 L3: 0.998
L1: 21.978 L1: 21.968 L1: 20.025 L1: 0.954
23 100 100 -10 -10 14.0 60.0 L2: 22.084 L2: 21.972 L2: 20.108 L2: 0.952 742 IB
L3: 22.120 L3: 22.047 L3: 20.146 L3: 0.953
L1: 21.980 L1: 20.971 L1: 20.022 L1: 0.932
24 100 100 -10 -5 14.8 60.0 L2: 22.084 L2: 20.973 L2: 20.109 L2: 0.930 742 IB
L3: 22.119 L3: 21.045 L3: 20.143 L3: 0.931
L1: 21.982 L1: 19.971 L1: 20.025 L1: 0.910
25 100 100 -10 0 16.0 60.0 L2: 22.084 L2: 19.972 L2: 20.108 L2: 0.907 742 IB
L3: 22.119 L3: 20.041 L3: 20.144 L3: 0.908
L1: 21.982 L1: 18.972 L1: 20.025 L1: 0.887
26 100 100 -10 5 22.4 60.0 L2: 22.084 L2: 18.971 L2: 20.108 L2: 0.884 742 IB
L3: 22.119 L3: 19.041 L3: 20.146 L3: 0.885
L1: 13.241 L1: 13.912 L1: 13.180 L1: 1.023
27 66 66 0 -5 25.6 40.0 L2: 13.157 L2: 13.866 L2: 13.176 L2: 1.027 500 IB
L3: 13.272 L3: 13.845 L3: 13.275 L3: 1.021
L1: 13.240 L1: 13.781 L1: 13.180 L1: 1.018
28 66 66 0 -4 16.8 40.0 L2: 13.158 L2: 13.731 L2: 13.174 L2: 1.022 500 IB
Tested by: Reviewed by:

BTHPL/OBCAL/EL/GEN/UIPVI/040222_V1.1

Tested By : ARIF JAMAL Approved By : VAIBHAV GUPTA


Date Uploaded : 09/03/2023 Date Approved : 09/03/2023
Job Order No. BTH-R1/EL/2211206/4 IS 16169: 2014/IEC 62116:2008 Page : 16 of 21

L3: 13.269 L3: 13.713 L3: 13.275 L3: 1.017


L1: 13.241 L1: 13.649 L1: 13.182 L1: 1.013
29 66 66 0 -3 22.4 40.0 L2: 13.157 L2: 13.601 L2: 13.174 L2: 1.017 500 IB
L3: 13.269 L3: 13.580 L3: 13.277 L3: 1.012
L1: 13.240 L1: 13.516 L1: 13.181 L1: 1.008
30 66 66 0 -2 20.0 40.0 L2: 13.157 L2: 13.469 L2: 13.175 L2: 1.012 500 IB
L3: 13.269 L3: 13.449 L3: 13.275 L3: 1.007
L1: 13.241 L1: 13.384 L1: 13.181 L1: 1.003
31 66 66 0 -1 18.8 40.0 L2: 13.157 L2: 13.338 L2: 13.176 L2: 1.008 500 IB
L3: 13.269 L3: 13.317 L3: 13.275 L3: 1.002
L1: 13.241 L1: 13.118 L1: 13.184 L1: 0.993
32 66 66 0 1 20.4 40.0 L2: 13.159 L2: 13.072 L2: 13.174 L2: 0.997 500 IB
L3: 13.269 L3: 13.054 L3: 13.275 L3: 0.992
L1: 13.243 L1: 12.987 L1: 13.180 L1: 0.988
33 66 66 0 2 24.6 40.0 L2: 13.157 L2: 12.940 L2: 13.174 L2: 0.992 500 IB
L3: 13.272 L3: 12.922 L3: 13.275 L3: 0.987
L1: 13.241 L1: 12.853 L1: 13.183 L1: 0.983
34 66 66 0 3 22.4 40.0 L2: 13.157 L2: 12.808 L2: 13.174 L2: 0.987 500 IB
L3: 13.271 L3: 12.793 L3: 13.275 L3: 0.982
L1: 13.241 L1: 12.721 L1: 13.179 L1: 0.978
35 66 66 0 4 20.4 40.0 L2: 13.157 L2: 12.675 L2: 13.174 L2: 0.982 500 IB
L3: 13.270 L3: 12.656 L3: 13.275 L3: 0.977
L1: 13.240 L1: 12.589 L1: 13.180 L1: 0.973
36 66 66 0 5 26.0 40.0 L2: 13.158 L2: 12.544 L2: 13.174 L2: 0.977 500 IB
L3: 13.269 L3: 12.527 L3: 13.273 L3: 0.972
L1: 6.613 L1: 6.961 L1: 6.625 L1: 1.027
37 33 33 0 -5 17.6 20.0 L2: 6.631 L2: 6.960 L2: 6.610 L2: 1.023 255 IB
L3: 6.602 L3: 6.943 L3: 6.624 L3: 1.027
L1: 6.610 L1: 6.894 L1: 6.628 L1: 1.023
38 33 33 0 -4 22.0 20.0 L2: 6.635 L2: 6.890 L2: 6.611 L2: 1.017 255 IB
L3: 6.605 L3: 6.876 L3: 6.624 L3: 1.022
L1: 6.610 L1: 6.830 L1: 6.629 L1: 1.018
39 33 33 0 -3 14.2 20.0 L2: 6.633 L2: 6.825 L2: 6.611 L2: 1.013 255 IB
L3: 6.606 L3: 6.812 L3: 6.624 L3: 1.017
L1: 6.614 L1: 6.764 L1: 6.629 L1: 1.012
40 33 33 0 -2 22.8 20.0 L2: 6.633 L2: 6.761 L2: 6.608 L2: 1.008 255 IB
L3: 6.604 L3: 6.742 L3: 6.626 L3: 1.012
L1: 6.612 L1: 6.697 L1: 6.626 L1: 1.007
41 33 33 0 -1 16.2 20.0 L2: 6.631 L2: 6.691 L2: 6.608 L2: 1.003 255 IB
L3: 6.604 L3: 6.679 L3: 6.624 L3: 1.007
L1: 6.614 L1: 6.562 L1: 6.628 L1: 0.997
42 33 33 0 1 24.6 20.0 L2: 6.634 L2: 6.561 L2: 6.608 L2: 0.993 255 IB
L3: 6.604 L3: 6.547 L3: 6.624 L3: 0.997
L1: 6.611 L1: 6.498 L1: 6.627 L1: 0.993
43 33 33 0 2 22.0 20.0 L2: 6.630 L2: 6.491 L2: 6.610 L2: 0.988 255 IB
Tested by: Reviewed by:

BTHPL/OBCAL/EL/GEN/UIPVI/040222_V1.1

Tested By : ARIF JAMAL Approved By : VAIBHAV GUPTA


Date Uploaded : 09/03/2023 Date Approved : 09/03/2023
Job Order No. BTH-R1/EL/2211206/4 IS 16169: 2014/IEC 62116:2008 Page : 17 of 21

L3: 6.604 L3: 6.482 L3: 6.624 L3: 0.992


L1: 6.612 L1: 6.434 L1: 6.627 L1: 0.988
44 33 33 0 3 20.2 20.0 L2: 6.636 L2: 6.428 L2: 6.608 L2: 0.982 255 IB
L3: 6.604 L3: 6.415 L3: 6.624 L3: 0.987
L1: 6.612 L1: 6.366 L1: 6.624 L1: 0.982
45 33 33 0 4 25.0 20.0 L2: 6.632 L2: 6.361 L2: 6.604 L2: 0.977 255 IB
L3: 6.604 L3: 6.352 L3: 6.625 L3: 0.982
L1: 6.612 L1: 6.302 L1: 6.627 L1: 0.977
46 33 33 0 5 18.4 20.0 L2: 6.632 L2: 6.298 L2: 6.608 L2: 0.973 255 IB
L3: 6.604 L3: 6.280 L3: 6.625 L3: 0.977
a PEUT: EUT output power.
b PAC: Active power flow at S1 in Figure 1. Positive means power from EUT to utility. Nominal is the 0 % test condition value.
c QAC: Reactive power flow at S1 in Figure 1. Positive means power from EUT to utility. Nominal is the 0 % test condition value.
d BL: balance condition, IB: imbalance condition.

Tested by: Reviewed by:

BTHPL/OBCAL/EL/GEN/UIPVI/040222_V1.1

Tested By : ARIF JAMAL Approved By : VAIBHAV GUPTA


Date Uploaded : 09/03/2023 Date Approved : 09/03/2023
Job Order No. BTH-R1/EL/2211206/4 IS 16169: 2014/IEC 62116:2008 Page : 18 of 21

Appendix A
Photographs

External view 1 External view 2

Internal view Main board Top view

Tested by: Reviewed by:

BTHPL/OBCAL/EL/GEN/UIPVI/040222_V1.1

Tested By : ARIF JAMAL Approved By : VAIBHAV GUPTA


Date Uploaded : 09/03/2023 Date Approved : 09/03/2023
Job Order No. BTH-R1/EL/2211206/4 IS 16169: 2014/IEC 62116:2008 Page : 19 of 21

Main board Bottom view

Tested by: Reviewed by:

BTHPL/OBCAL/EL/GEN/UIPVI/040222_V1.1

Tested By : ARIF JAMAL Approved By : VAIBHAV GUPTA


Date Uploaded : 09/03/2023 Date Approved : 09/03/2023
Job Order No. BTH-R1/EL/2211206/4 IS 16169: 2014/IEC 62116:2008 Page : 20 of 21

Waveforms:

100% Balanced Condition 100% Un-Balanced Condition

66% Balanced Condition 66% Un-Balanced Condition

Tested by: Reviewed by:

BTHPL/OBCAL/EL/GEN/UIPVI/040222_V1.1

Tested By : ARIF JAMAL Approved By : VAIBHAV GUPTA


Date Uploaded : 09/03/2023 Date Approved : 09/03/2023
Job Order No. BTH-R1/EL/2211206/4 IS 16169: 2014/IEC 62116:2008 Page : 21 of 21

33% Balanced Condition 33% Un-Balanced Condition


Test Circuit

……………………………………………………………………………………………End of the Report………………………………………………………………………………………….