You are on page 1of 11

PEARL CONTINENTAL HOTEL AND RESORT

Fire Hose System Reports

for

PEARL CONTINENTAL HOTEL AND RESORT

HUNZA

Prepared By:

SHAHZAIB AHMAD
INNOVATIVE ENGINEERING SOLUTION
HOUSE 84-B, ZARAR SHAHEED ROAD
LAHORE-54000
+924236674002
25/03/24
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem PEARL CONTINENTAL HOTEL AND RESORT
heaven Page 2

General Project Data Report (Inputs may have changed)

General Data
Project Title: PEARL CONTINENTAL HOTEL
Project File Name: CASE SCENARIO-3..fiw
AND RESORT
Designed By: SHAHZAIB AHMAD Date: 25/03/24
Code Reference: NFPA 1, NFPA 13, NFPA 14, NFPA
Approving Agency:
20
CASE SCENARIO - 3 (BASED ON PROVIDING 250 GPM AT THE FOUR HYDRAULICALLY
MOST REMOTE HOSE CONNECTIONS ON HORIZONTAL STANDPIPE AND AT TOPMOST
OUTLET OF EACH OTHER STANDPIPES.
Client Name: PEARL CONTINENTAL HOTEL
Phone:
AND RESORT
Address: HUNZA City, State Zip Code:
Company Name: INNOVATIVE ENGINEERING
Representative:
SOLUTION
Company Address: HOUSE 84-B, ZARAR SHAHEED
City And State: LAHORE-54000
ROAD
Phone: +924236674002
Building Name: PEARL CONTINENTAL HOTEL
Building Owner: PEARL CONTINENTAL
AND RESORT
Contact at Building: Phone at Building:
Address Of Building: City, State Zip Code:

Project Data
Description Of Hazard: STANDPIPE Hose System Type: Wet
Design Area Of Water Application: 1 ft² Maximum Area Per Hose: 1 ft²
Default Hose K-Factor: 25.00 K Default Pipe Material: SCHED 40 WET STEEL
Inside Hose Stream Allowance: 0.00 gpm Outside Hose Stream Allowance: 0.00 gpm
In Rack Sprinkler Allowance: 0.00 gpm

Hose Specifications
Make: Model:
Size: Temperature Rating: 0 F
HOTEL AND RESTAURANT
BUILDING

Water Supply Test Data


Source Of Information:
Test Hydrant ID: Date Of Test:

Hydrant Elevation: 0 ft Static Pressure: 0.00 psi


Test Flow Rate: 0.00 gpm Test Residual Pressure: 0.00 psi
Calculated System Flow Rate: 1051.81 gpm Calculated Inflow Residual Pressure: 160.11 psi

Calculation Project Data


Calculation Mode: Demand
HMD Minimum Residual Pressure: 100.00 psi Minimum Desired Flow Density: 0.00 gpm/ft²
Number Of Active Nodes: 15
Number Of Active Pipes: 14 Number Of Inactive Pipes: 0
Number Of Active Hoses: 4 Number Of Inactive Hoses: 0

Z:\ ...\CASE SCENARIO-3.fiw Friday, April 19, 2024, 6:11 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem PEARL CONTINENTAL HOTEL AND RESORT
heaven Page 3

Fire Hose Input Data

Node Input Data (Inputs may have changed)


Hose KFactor Pressure Node Elev (ft) Fixed Flow
Area Group
Node Node Description (K) Estimate (psi) Branch Non- (gpm)
Branch Dia.
No. Branch Description Branch Len. Branch Stnd Stnd Fittings Branch Sprk
(in)
(ft) Fittings (ft) KFactor (K)

No Discharge ---- N/A 160.11 -17.00 0.00


1
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 155.72 -14.00 0.00


2
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 146.74 -7.00 0.00


3
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 139.24 7.00 0.00


4
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 116.74 58.50 0.00


5
---- 0.000 0.0 ---- 0.0 0.00

Hose ---- 25.00 116.37 58.50 0.00


6
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 135.47 7.00 0.00


7
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 116.13 48.00 0.00


8
---- 0.000 0.0 ---- 0.0 0.00

Hose ---- 25.00 115.76 48.00 0.00


9
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 111.17 58.50 0.00


10
---- 0.000 0.0 ---- 0.0 0.00

Hose ---- 25.00 110.81 58.50 0.00


11
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 108.16 64.70 0.00


12
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 106.49 64.70 0.00


13
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 105.07 64.70 0.00


14
---- 0.000 0.0 ---- 0.0 0.00

Hose ---- 25.00 100.00 64.70 0.00


15
---- 0.000 0.0 ---- 0.0 0.00

Z:\ ...\CASE SCENARIO-3.fiw Friday, April 19, 2024, 6:11 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem PEARL CONTINENTAL HOTEL AND RESORT
heaven Page 4

Fire Hose Input Data

Pipe Input Data (Inputs may have changed)


Nominal Nominal Fitting Total CFactor
Beg. End. Type Fitting
Pipe Description Diameter Length Length Length (gpm/inc
Node Node Group Data
(inch) (feet) (feet) (feet) h-psi)

1 2 SCHED 40 WET STEEL 6.000 0 2ET 22.00 58.00 80.00 120

2 3 SCHED 40 WET STEEL 6.000 0 5E 84.00 70.00 154.00 120

3 4 SCHED 40 WET STEEL 6.000 0 T 7.00 30.00 37.00 120

4 5 SCHED 40 WET STEEL 6.000 0 E 51.50 14.00 65.50 120

5 6 SCHED 40 WET STEEL 2.500 0 1.50 0.00 1.50 120

4 7 SCHED 40 WET STEEL 6.000 0 FE 148.00 21.00 169.00 120

7 8 SCHED 40 WET STEEL 6.000 0 T 41.00 30.00 71.00 120

8 9 SCHED 40 WET STEEL 2.500 0 1.50 0.00 1.50 120

8 10 SCHED 40 WET STEEL 6.000 0 T 10.50 30.00 40.50 120

10 11 SCHED 40 WET STEEL 2.500 0 1.50 0.00 1.50 120

10 12 SCHED 40 WET STEEL 4.000 0 E 6.00 10.00 16.00 120

12 13 SCHED 40 WET STEEL 4.000 0 2F2E 55.91 28.00 83.91 120

13 14 SCHED 40 WET STEEL 4.000 0 E 61.50 10.00 71.50 120

14 15 SCHED 40 WET STEEL 2.500 0 2E 11.50 12.00 23.50 120

Z:\ ...\CASE SCENARIO-3.fiw Friday, April 19, 2024, 6:11 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem PEARL CONTINENTAL HOTEL AND RESORT
heaven Page 5

Fire Hose Output Data

Group Peak Node Groupings Output Data (Inputs may have changed)
Pipe Segment Pipe Pipe Hose Flow Fixed Flow Beg. Node Imbalance
Beg. End. Type Flow Rate At Beg. Node Out (+) In (-) Residual Flow At Beg.
Node Node Group (gpm) (gpm) (gpm) (gpm) Pressure (psi) Node (gpm)

1 2 0 0.00 0.00 0.00 0.00 160.11

2 1 0 0.00 0.00 0.00 0.00 155.72


2 3 0 0.00

3 2 0 0.00 0.00 0.00 0.00 146.74


3 4 0 0.00

4 3 0 0.00 0.00 0.00 0.00 139.24


4 5 0 0.00
4 7 0 0.00

5 4 0 0.00 0.00 0.00 0.00 116.74


5 6 0 0.00

6 5 0 0.00 269.69 0.00 0.00 116.37 0.00904

7 4 0 0.00 0.00 0.00 0.00 135.47


7 8 0 0.00

8 7 0 0.00 0.00 0.00 0.00 116.13


8 9 0 0.00
8 10 0 0.00

9 8 0 0.00 268.98 0.00 0.00 115.76 0.00690

10 8 0 0.00 0.00 0.00 0.00 111.17


10 11 0 0.00
10 12 0 0.00

11 10 0 0.00 263.17 0.00 0.00 110.81 0.00672

12 10 0 0.00 0.00 0.00 0.00 108.16


12 13 0 0.00

13 12 0 0.00 0.00 0.00 0.00 106.49


13 14 0 0.00

14 13 0 0.00 0.00 0.00 0.00 105.07


14 15 0 0.00

15 14 0 0.00 250.00 0.00 0.00 100.00 0.00504

Z:\ ...\CASE SCENARIO-3.fiw Friday, April 19, 2024, 6:11 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem PEARL CONTINENTAL HOTEL AND RESORT
heaven Page 6

Fire Hose Output Data

Group Peak Pipe Output Data (Inputs may have changed)


q (gpm) F. L./ft Pipe-Len.
Beg. Nodal Hose/Fix Residual Nom. Dia. PF-(psi)
Elevation Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure Inside Dia. PE-(psi)
(feet) Velocity Fittings Tot-Len.
Node (K) (gpm) (psi) C-Value PT-(psi)
(fps) Type-Grp (ft)

1 0.00 -17.00 0.00 160.11 6.00 0.00 0.03866 22.00 3.093


2 0.00 -14.00 0.00 155.72 6.065 1051.81 2ET 58.00 1.299
SCHED 40 WET STEEL 120 11.68 0 80.00 4.392

2 0.00 -14.00 0.00 155.72 6.00 0.00 0.03866 84.00 5.954


3 0.00 -7.00 0.00 146.74 6.065 1051.81 5E 70.00 3.031
SCHED 40 WET STEEL 120 11.68 0 154.00 8.985

3 0.00 -7.00 0.00 146.74 6.00 0.00 0.03866 7.00 1.430


4 0.00 7.00 0.00 139.24 6.065 1051.80 T 30.00 6.062
SCHED 40 WET STEEL 120 11.68 0 37.00 7.492

4 0.00 7.00 0.00 139.24 6.00 0.00 0.00312 51.50 0.204


5 0.00 58.50 0.00 116.74 6.065 269.67 E 14.00 22.300
SCHED 40 WET STEEL 120 2.99 0 65.50 22.504

4 0.00 7.00 0.00 139.24 6.00 0.00 0.02235 148.00 3.777


7 0.00 7.00 0.00 135.47 6.065 782.13 FE 21.00 0.000
SCHED 40 WET STEEL 120 8.69 0 169.00 3.777

5 0.00 58.50 0.00 116.74 2.50 0.00 0.24801 1.50 0.372


6 25.00 58.50 269.69 116.37 2.469 269.68 ----- 0.00 0.000
SCHED 40 WET STEEL 120 18.07 0 1.50 0.372

7 0.00 7.00 0.00 135.47 6.00 0.00 0.02235 41.00 1.587


8 0.00 48.00 0.00 116.13 6.065 782.12 T 30.00 17.753
SCHED 40 WET STEEL 120 8.69 0 71.00 19.340

8 0.00 48.00 0.00 116.13 2.50 0.00 0.24681 1.50 0.370


9 25.00 48.00 268.98 115.76 2.469 268.97 ----- 0.00 0.000
SCHED 40 WET STEEL 120 18.02 0 1.50 0.370

8 0.00 48.00 0.00 116.13 6.00 0.00 0.01025 10.50 0.415


10 0.00 58.50 0.00 111.17 6.065 513.16 T 30.00 4.547
SCHED 40 WET STEEL 120 5.70 0 40.50 4.962

10 0.00 58.50 0.00 111.17 2.50 0.00 0.23704 1.50 0.356


11 25.00 58.50 263.17 110.81 2.469 263.16 ----- 0.00 0.000
SCHED 40 WET STEEL 120 17.63 0 1.50 0.356

10 0.00 58.50 0.00 111.17 4.00 0.00 0.01993 6.00 0.319


12 0.00 64.70 0.00 108.16 4.026 250.00 E 10.00 2.685
SCHED 40 WET STEEL 120 6.30 0 16.00 3.003

12 0.00 64.70 0.00 108.16 4.00 0.00 0.01993 55.91 1.672


13 0.00 64.70 0.00 106.49 4.026 250.00 2F2E 28.00 0.000
SCHED 40 WET STEEL 120 6.30 0 83.91 1.672

Z:\ ...\CASE SCENARIO-3.fiw Friday, April 19, 2024, 6:11 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem PEARL CONTINENTAL HOTEL AND RESORT
heaven Page 7

Fire Hose Output Data

Group Peak Pipe Output Data


q (gpm) F. L./ft Pipe-Len.
Beg. Nodal Hose/Fix Residual Nom. Dia. PF-(psi)
Elevation Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure Inside Dia. PE-(psi)
(feet) Velocity Fittings Tot-Len.
Node (K) (gpm) (psi) C-Value PT-(psi)
(fps) Type-Grp (ft)

13 0.00 64.70 0.00 106.49 4.00 0.00 0.01993 61.50 1.425


14 0.00 64.70 0.00 105.07 4.026 250.00 E 10.00 0.000
SCHED 40 WET STEEL 120 6.30 0 71.50 1.425

14 0.00 64.70 0.00 105.07 2.50 0.00 0.21557 11.50 5.066


15 25.00 64.70 250.00 100.00 2.469 249.99 2E 12.00 0.000
SCHED 40 WET STEEL 120 16.75 0 23.50 5.066

Z:\ ...\CASE SCENARIO-3.fiw Friday, April 19, 2024, 6:11 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem PEARL CONTINENTAL HOTEL AND RESORT
heaven Page 8

Fire Hose Output Data

Group Peak Hose Output Data (Inputs may have changed)


Flowing Node Residual Flowing Hose
Area Group Hose Flowing
Hose Node Elevation Pressure Density Discharge
Code KFactor (K) Area (ft²)
No. (feet) (psi) (gpm/ft²) (gpm)

6 25.00 58.50 116.37 1.00 269.685 269.69


Sub Totals For Non-Group 1.00 269.685 269.69

9 25.00 48.00 115.76 1.00 268.976 268.98


Sub Totals For Non-Group 1.00 268.976 268.98

11 25.00 58.50 110.81 1.00 263.166 263.17


Sub Totals For Non-Group 1.00 263.166 263.17

15 25.00 64.70 100.00 1.00 250.000 250.00


Sub Totals For Non-Group 1.00 250.000 250.00

Totals For All Groups 4.00 262.957 1051.83

Z:\ ...\CASE SCENARIO-3.fiw Friday, April 19, 2024, 6:11 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem PEARL CONTINENTAL HOTEL AND RESORT
heaven Page 9

Fire Hose Output Summary (Inputs may have changed)

Hydraulically Most Demanding Hose Node


HMD Hose Node Number: 15
HMD Actual Residual Pressure: 100.00 psi
HMD Actual Flow: 250.00 gpm

Hose Summary
Hose System Type: Wet
Specified Area Of Application: 1.00 ft²
Minimum Desired Density: 0.000 gpm/ft²
Application Average Density: 1051.828 gpm/ft²
Application Average Area Per Hose: 0.25 ft²
Hose Flow: 1051.83 gpm
Average Hose Flow: 262.96 gpm

Flow Velocity And Imbalance Summary


Maximum Flow Velocity ( In Pipe 0 - 0 ) 0.00 ft/sec
Maximum Velocity Pressure ( In Pipe 0 - 0 ) 0.00 psi

Allowable Maximum Nodal Pressure Imbalance: 0.1000 psi


Actual Maximum Nodal Pressure Imbalance: 0.0009 psi
Actual Average Nodal Pressure Imbalance: 0.0004 psi
Actual Maximum Nodal Flow Imbalance: 0.0090 gpm
Actual Average Nodal Flow Imbalance: 0.0018 gpm

Overall Network Summary


Number Of Unique Pipe Sections: 14
Number Of Flowing Hoses: 4

Pipe System Water Volume: 631.88 gal

Hose Flow: 1051.83 gpm


Fixed Flow: 0.00 gpm

Minimum Required Residual Pressure At System Inflow


160.11 psi
Node:
Demand Flow At System Inflow Node: 1051.81 gpm

Z:\ ...\CASE SCENARIO-3.fiw Friday, April 19, 2024, 6:11 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem PEARL CONTINENTAL HOTEL AND RESORT
heaven Page 10

Fire Hose Output Data (Inputs may have changed)

Hydraulic Supply/Demand Graph

200

180

160
160

140
Pressure psi

120

100

80

60

40

20

0
2 4 6 8 10 12 14 16 18 20
Flowrate(x100) gpm

Demand Curve Data


Calculated Residual Pressure: 160.11 psi
Calculated Flow Rate: 1051.81 gpm
Pressure Required For First Sprinkler Downstream From Inflow Node To Flow: 32.69 psi

Z:\ ...\CASE SCENARIO-3.fiw Friday, April 19, 2024, 6:11 PM


EL
EV
AT
IO
N
=+
64
'-9
"
14
DIA
LE MET
NG E
TH R = /2"
=6 Ø 3 2-1 "
Ø
1'-6" R= 1'-6
" TE = 1
ME TH
DIAENG
L

EL
EV
AT
IO
N=
+6
4'-9
"
"
13
8'-6
+5 15
N=
IO
AT
EV
EL

EL
EV
AT
IO
N
=+
64
'-9
" 12
4" "

R 1
TE 55'-1 4"

ME H = R "
DIANGT TE 6'-0
LE ME H =
DIANGT
LE

11E
DIA LEVA
10
EL LENMET TION
EV G ER =+
AT TH = 58
IO =1 Ø 2-1 '-6
N
= + '-6" /2" "
58
'-6
"

6Ø"
R= "
TE 10'-6
ME H =
DIANGT
LE

06 09EL
EL
DIA EV DIA EVA
AT
EL LENMET TION
05 08
EL LE MET IO
N= EV G ER
EV NG ER AT TH = =+
AT TH = +5 IO =1 Ø 2 48
IO =1 Ø 2 8'-6 N = '-6 -1/2 '-0
N = '-6 -1/2 " "
+5 " " +4 " "
8'-6 8'-0
" "

E
OSHER
6Ø"
R= "
TE 41'-0
ME H =
DIANGT
LE

H
O TE E OT
M H
REOF T2)
6"

R "
TE 51'-6
ME H =
DIANGT
LE

T .
M OSACH .1.2
Y E 1 0
LL OF ): 7.
"
'-0
+7 07
N=

A T IO

6
VA

T
E
EL

IC E 1
A UL UTL 4 (20
R O 1
DIA

H YD ST FPA
LE ME
NG TE

O
UROPMER N
TH R =
=1 6Ø"
48
'-0
"

O
F T P
6"

T HETHE AS
D
Ø
R= "

AT AT AN
TE 84'-0
ME H =
DIANGT "
LE +7
'-0
N=
IO
AT

M D
02

2
EV
ELE EL

P N .1.
VA
TIO 04
N
= -1
4'-0

0 GPE A10.1
DIA "
01 LE ME
N TE
ELEGTH R = =Ø6" "
VA = 22Ø 6" R '-0
TIO ' TE = 7
N= ME TH

5
-17'
-0"
DIAENG
L

2 I .
IN G DP 6): 7
N 1
VID STA (20
"
-7'-0
03

N=
A TIO
EV
EL

O L 4
N PRNTA A 1
O FP
ED ORIZ R N
S O E
(BA E HAS P
-3 H
R IO ON TIPES
A P
C ENIONSAND
S T T
ASE NEC S
C ON
C

You might also like